Siemens OCM III Instruction Manual

Page 1
Instruction Manual November 2005
open channel
OCM III
Page 2
Safety Guidelines: Warning notices must be observed to ensure personal safety as well as that of
Qualified Personnel: This device/system may only be set up and operated in conjunction with this
manual. Qualified personnel are only authorized to install and operate this equipment in accordance with established safety practices and standards.
Unit Repair and Excluded Liability:
The user is responsible for all changes and repairs made to the device by the user or the user’s
agent.
All new components are to be provided by Siemens Milltronics Process Instruments Inc.
Restrict repair to faulty components only.
Do not reuse faulty components.
Warning: This product can only function properly and safely if it is correctly transported, stored,
installed, set up, operated, and maintained.
Note: Always use product in accordance with specifications.
Copyright Siemens Milltronics Process
Disclaimer of Liability
Instruments Inc. 2005. All Rights Reserved
This document is available in bound version and in electronic version. We encourage users to purchase authorized bound manuals, or to view electronic versions as designed and authored by Siemens Milltronics Process Instruments Inc. Siemens Milltronics Process Instruments Inc. will not be responsible for the contents of partial or whole reproductions of either bound or electronic versions.
While we have verified the contents of this manual for agreement with the instrumentation described, variations remain possible. Thus we cannot guarantee full agreement. The contents of this manual are regularly reviewed and corrections are included in subsequent editions. We welcome all suggestions for improvement.
Technical data subject to change.
MILLTRONICS®is a registered trademark of Siemens Milltronics Process Instruments Inc.
Contact SMPI Technical Publications at the following add r ess:
Technical Publications Siemens Milltronics Process Instruments Inc. 1954 Technology Drive, P.O. Box 4225 Peterborough, Ontario, Canada, K9J 7B1 Email: techpubs.smpi@siemens.com
For a selection of Siemens Milltronics level measurement manuals, go to:
www. siemens.com/processautomation. Under Process Instrumentation, select
Measurement
For a selection of Siemens Milltronics weighing manuals, go to:
www. siemens.com/processautomation. Under Weighing Technology, select
Weighing Systems
and then go to the manual archive listed under the product family.
and then go to the manual archive listed under the product family.
Level
Continuous
© Siemens Milltronics Process Instruments Inc. 2005
Page 3
TABLE OF CONTENTS
TITLE PAGE
ABOUT THIS ...
About This Manual 7
About the OCM-3 7
SPECIFICATIONS 9
Programmer 10
Transducer 11
Temperature Sensor 11
Cabling 11
Communication Software 11
INSTALLATION
Installing the OCM-3 13
Outline and Mounting 13
OCM-3 Layout 14
System Diagram 15
Installing the Transducer 16
Installing the Temperature Sensor 16
mA Output 17
Relays 17
Synchronization 18
Power Connections 19
Installing the Memory Back-up Battery 20
Communicating Via Computer 20
Installing the Programmer 20
7ML19985AB01 OCM III 3
Page 4
START UP
General 21
Keypad 21
Legend 22
Initial Start Up 22
Fundamental Checks 25
OPERATION
Memory 27
Security 27
Units 27
Flow Calculation 28
Display 28
Damping 29
Relays 30
mA Output 30
Fail-Safe 31
Flow rate and Totalizing 31
Logging 32
Blanking 34
Temperature 34
Time and Date 34
Emulation Mode 35
Reset 35
Flow Velocity Input 36
Auxiliary Head Input 36
DC Output 37
Diagnostic Aids 37
7ML19985AB01 OCM III 4
Page 5
‘D’ PARAMETER LISTING 39
‘F’ PARAMET ER LI STING 41
‘P’ PARAMETER LISTING 43
‘U’ PARAMETERS FOR P3 PRIMARY ELEMENT 51
Simple Exponential Devices, P3 = 0 53
BS-3680 Rectangular Flume, P3 = 1 58
BS-3680 Round Nose Horizontal Crest Weir, P3 = 2 60
BS-3680 Trapezoidal Flume, P3 = 3 62
BS-3680 U - Flume, P3 = 4 64
BS-3680 Finite Crest Weir, P3 = 5 66
BS-3680 Thin Plate Rectangular Weir, P3 = 6 68
BS-3680 Thin Plate V-Notch Weir, P3 = 7 70
Rectangular Weir (Contracted), P3 = 8 72
Round Pipe, P3 = 9 74
Palmer-Bowlus Flume, P3 = 10 76
H - Flume, P3 = 11 78
Universal Head vs. Flow, P3 =12 80
Rectangular Area x Velocity, P3 = 13 82
Trapezoidal Area x Velocity, P3 =14 84
Modified Trapezoidal Area x Velocity, P3 = 15 86
U Channel Area x Velocity, P3 = 16 88
Circular Area x Velocity, P3 = 17 90
Gull-Wing Area x Velocity, P3 = 18 92
Egg-Shaped Area x Velocity, P3 =19 94
Universal Area x Velocity, P3 = 20 96
APPENDICES
Maintenance 99
Error Codes 100
Communications 101
7ML19985AB01 OCM III 5
Page 6
7ML19985AB01 OCM III 6
Page 7
ABOUT THIS ...
ABOUT THIS MANUAL
Although the OCM-3 is very ‘approachable’ due its dialogue capabilities and intuitive operation, the user should be familiar with this manual. This manual provides the user with the necessary information required to install, start up and operate the OCM-3.
As the OCM-3 prompts the user with specific messages in a step-by-step fashion during programming, the Start Up section serves essentially to compliment the OCM-3. Start Up provides the user with instructions on the use of the programmer and an overview of the programming requirements.
The ‘D’, ‘F’, ‘P’ and ‘U’ parameters listed in the Parameters section provide a quick reference of the available programming and display parameters and their options. The ‘U’ parameter listing also provides mathematical and graphical details as a reference to assist the user in programming the OCM-3 to the primary element being used. The user is urged to rely on the manufacturer’s specification for obtaining and identifying the primary element to which the OCM-3 is being applied.
In short,
If you want to know about
the product About This . . .
getting started Installation
how it works Operation
Read
Specifications
Start Up
Parameters Appendices
ABOUT THE OCM-3
The OCM-3 is to be used only in the manner
outlined in this instruction manual.
The Milltronics OCM-3, Open Channel Meter, is an electronic instrument designed to measure flow in open channels. It is housed in a polycarbonate enclosure and comes with a removable programmer. As a system, it is used in conjunction with a remote ultrasonic transducer (or auxiliary head measurement device) and a temperature sensor.
The OCM-3 transmits a pulse signal to the transducer which is then emitted as ultrasonic pulses. The pulses echo off the water surface and are then sensed by the transducer. The time for a pulse to echo back from the water surface is temperature compensated and converted into a measurement of head.
7ML19985AB01 OCM III 7
Page 8
The OCM-3 converts the head measurement into flow rate, but also provides a velocity sensor input for applications where a flow velocity measurement is required to perform the flow calculation. The flow rate is totalized and stored in a comprehensive data log to provide detailed flow analysis.
Programming of the OCM-3 allows the operator to select the flow calculation specific to the primary measuring device (flume, weir or pipe). Special emphasis has been placed on providing the most accurate flow calculations possible. To this end, specific routines have been written to comply with the British Standards Institute’s Specifications BS-3680. These routines calculate correction factors taking into account second order effects such as approach velocity and boundary layer. In the event that flow measurement is not covered by one of the flow calculations provided, the OCM-3 can be programmed for flow measurement using one of the universal flow calculations.
The OCM-3 provides serial communication for remote programming, data log retrieval and print out for devices such as computers, PLCs and printers. Milltronics provides a standard utilities software package for OCM-3 programming, remote display and data retrieval. However, the user is not limited to the software provided. The user can develop his own software program to perform tasks suited to his specific nee ds.
The OCM-3 features:
multi field illuminated LCD, for ‘Flow and Total’ and ‘Relay Status’ display
0 or 4 to 20 mA output
three multipurpose relays, including remote totalization
1 to 24 months data log, subject to logging rate
extensive serial communication, including RS-232
removable infra-red programmer
AC and DC (bi-current) operation.
7ML19985AB01 OCM III 8
Page 9
SPECIFICATIONS
Power: » dc supply: » 9 to 30 V DC, 8 W max
» ac supply: » 100/115/200/230 V ac ± 15%, 50/60 Hz,
20 VA max
Environmental: » location » indoor /outdoor
» altitude: » 2000 m max
» ambient temperature » – 20 to 50 °C (–5 to 122 °F)
» relative humidity » suitable for outdoor (Type 4X/Nema 4X
» installation category » II
» pollution degree » 4
Memory back-up: » 3 V lithium battery (NEDA 5003LC or equivalent)
» operating life 1 year
» ‘SuperCap’ capacitor for back-up during battery replacement
Range: » 0.3 m min to 1.2 m max ( 1 to 4 ft)
and / or
IP65 enclosure)
0.6 m min to 3 m max (2 to 10 ft)
Resolution: » 0.2 mm (0.007")
Accuracy: » ±1 mm/m, calculated error less than 0.02%
Temperature Compensation: » external sensor to compensate over
the operating range
Programming: » via supplied programmer and
communication link
Inputs: » velocity sensor and
auxiliary head » range: » 0 to 10 V dc
» resolution: » 2.7 mV
Outputs: » transducer drive: » 44 Khz, 400 Vpp pulses of 0.1 msec typical
duration at a 100 msec typical repetition rate.
» instrumentation: » range: 0-20 or 4-20 mA
7ML19985AB01 OCM III 9
» resolution: 5 uA » maximum loading: 1 K
Page 10
» isolation: 300 V ac continuous
» relays: » 3 alarm/control relays
» 1 form ’C’ SPDT contact per relay, rated at
5 A at 250 V ac non-inductive or 30 V dc
» dc output: » +24 V dc
» 20 mA average to 200 mA at 1/10 duty
cycle max
Communication: » RS-232 or ± 20 mA bipolar current loop,300,
600, 1200, 2400, 4800, 9600 or 19200 baud
Data Logs: » variable rate on 1, 5, 15, 30 or 60 min or 24 hr
» 31 days minimum/2 years maximum
Display: » illuminated liquid crystal 5 x 7 dot matrix
display with 2 lines of 40 characters each
Enclosure: »Type 4X / NEMA 4X / IP65
» 209 mm W x 285 mm H x 92 mm D (8.2" W x 11.2" H x 3.6" D)
» polycarbonate
Weight: » 2.3 Kg (5.1 lb)
Approvals: » CE *, FM, CSA
» MCERTS Class 1 open channel flow device with environment
operation limits at 35 °C (95 °F) at 93% relative humidity
SIRA MC 050058/01
PROGRAMMER
NRTL/C
Enclosure: » general purpose
Operating Temperature: » –20 to 50 °C (–5 to 122 °F)
7ML19985AB01 OCM III 10
» 67 mm W x 100 mm H x 25 mm D
(2.6" W x 4" H x 1" D)
» ABS plastic
Page 11
Battery: » 9 V (ANSI / NEDA 1604, PP3 or equivalent) or
3V lithium battery
TRANSDUCER
Model: » XRS-5*
Refer to associated Transducer manual.
TEMPERATURE SENSOR
Model: » TS-2, LTS-1 or LTS-1C
Refer to associated Temperature Sensor manual.
CABLING
Transducer: » RG-62U coaxial
» maximum separation 183 m (600 ft)
» must be run in grounded metal conduit
mA Output: » Belden 8760 or equivalent
Synchronisation: » Belden 8760
Temperature Sensor: » Belden 8760, 1 pair shielded/twisted,
18 AWG or equivalent
» maximum separation 183 m (600 ft)
» can be run in conduit with transducer cable
Communication: » RS-232: » Belden 8770, 3 wire shielded, 24 AWG
or equivalent
» maximum separation 15 m (50 ft)
» Bipolar Current: » Belden 9552, 2 pair shielded/twisted,
18 AWG or equivalent
» maximum separation 1,500 m (5,000 ft)
*Note: The XRS-5 must be used with the TS-2 external temperature sensor when operating with the OCM-3.
Velocity Input: » Belden 8760 or equivalent
7ML19985AB01 OCM III 11
Page 12
Auxiliary Input: » Belden 8760 or equivalent
24 V Output: » Belden 8760
COMMUNICATION SOFTWARE
Milltronics Utilities Software on standard PC floppy disk for DOS 3.1 and up.
7ML19985AB01 OCM III 12
Page 13
INSTALLATION
Installation shall only be performed by qualified personnel
and in accordance with local governing regulations.
INSTALLING THE OCM-3
The OCM-3 should be mounted in a clean, dry area that is: within the ambient temperature range and suitable for the specified enclosure. The front cover should be accessible for programming and viewing.
It is advisable to keep the OCM-3 away from high voltage or current runs, contactors and SCR control drives.
Do not mount the OCM-3 in direct sunlight without the use of a sun shield.
This product is susceptible to electrostatic shock.
Follow proper grounding procedures.
OUTLINE AND MOUNTING
16 mm
(0.6")
209 mm
(8.2")
172 mm
(6.8")
267 mm
(10.5")
lid screws (6 places)
285 mm
(11.2")
106 mm
(4.2")
91 mm
(3.6")
programmer
suitable location for
conduit entrances
Milltronics reccomends using a punch for making
holes in enclosure. Use suitable cable glands to
maintain ingress rating.
Non metallic enclosure does not provide grounding between connections.
13 OCM III 7ML19985AB01
mounting holes
(accessed under
lid 4.3 mm (0.17")
dia.,4 places
customer mounting
lid
enclosure
screw
Use grounding type bushings and jumpers.
Page 14
OCM-3 LAYOUT
board A
display board
board B
All field wiring must have insulation suitable for at least 250 V.
Hazardous voltage present on transducer terminals during operation.
dc terminals shall be supplied from SELV source in accordance with IEC 1010-1 Annex H.
Relay contact terminals are for use with equipment having no accessible live parts and wiring having insulation suitable for at least 250 V.
The maximum allowable working voltage between adjacent relay contacts shall be 250 V.
14 OCM III 7ML19985AB01
Page 15
SYSTEM DIAGRAM
OCM-3
mA output
relay output
auxiliary input
velocity input
Milltronics transducer, see Specifications
Milltronics TS- 2, temperature sensor
customer device
customer alarm, pump or control device
customer device
customer device
bi-polar current
(Milltronics communication)
Maximum syste m ca pability. Not all components or their maximum quantity may be required.
15 OCM III 7ML19985AB01
RS-232
customer device
Milltronics CVCC
98/03/05
Page 16
INSTALLING THE TRANSDUCER
Max cable run 183 m (600 ft) of RG-62U or equivalent. Cable must be run in a grounded metal conduit with no other cabling (except Temp. Sensor cable).
Ground shield at OCM-3 only.
Insulate shield at junctions to prevent inadvertent grounding.
Basic Wiring – Transducer
Hazardous voltage present on transducer terminals during operation.
Note: When using the XRS-5 transducer with the OCM-3, use the TS-2 external temperature sensor. The internal temperature sensor in the XRS-5 cannot be used.
INSTALLING THE TEMPERATURE SENSOR
In order to compensate for uniform temperature change in the air between the transducer and the flow surface, the temperature sensor must be connected to the OCM-3.
Maximum cable run 183 m (600 ft) of Beldon 8760, 1 pair shielded/twisted, 18 AWG or equivalent.
Temperature sensor cable can be run with the transducer cable in a grounded metal conduit.
Ground shield at OCM-3 only.
Basic Wiring – Temperature Sensor
16 OCM III 7ML19985AB01
Page 17
mA OUTPUT
RELAYS
isolated 0 or 4 to 20 mA output (P26) into 1 KΩ loa d maximum. Wiring should conform to standard instrumentation practices. Ground shield at OCM-3 only.
relays shown in de-energized state, contacts rated at 5 A at 250 V non-inductive.
n.c. com n. o. n.c. com n. o. n. c. com n. o.
All relays are certified for use in equipment where the short circuit capacity of the circuits in which they are connected is limited by fuses having ratings not exceeding the rating of the relays.
17 OCM III 7ML19985AB01
Page 18
SYNCHRONIZATION
Where two to a maximum of twelve transducers will be sharing a common conduit the OCM-3s should be synchronized. In order to synchronize OCM-3s:
» remove jumper J1 on board A on all but one OCM-3
» interconnect the SYNC terminal (TB1-20) of all OCM-3s. Insure that all OCM-3s share a common ground (TB1-34).
18 OCM III 7ML19985AB01
Page 19
POWER CONNECTIONS
The OCM-3 power supply accepts 100, 115, 200 or 230 V ac per switch SW1 (board B) selection and 9 to 30 V dc.
The OCM-3 operates either under ac or dc power, or both ac and dc live simultaneously. If both ac and dc power are live, the OCM-3 normally draws power from the ac supply. In the event that the ac supply fails, the OCM-3 then draws power from the dc supply.
AC POWER
*
100/115/200/230 V ac, 50/60 Hz,
select voltage via switch on board B
* switch shown in ‘OFF’ position, select appropriate voltage.
The equipment must be protected by a 15 A fuse or
circuit breaker in the building installation.
A circuit breaker or switch in the building installation, marked
as the disconnect switch, shall be in close proximity to
the equipment and within easy reach of the operator.
DC POWER
19 OCM III 7ML19985AB01
nega tive dc input (T B1 - 24) is
9 to 30 Volt
dc input
tied to ground (TB1-34)
dc terminals shall be supplied from SELV source in accordance with IEC 1010-1 Annex H.
Page 20
INSTALLING THE MEMORY BACK-UP BATTERY
Disconnect power before installing or replacing the battery.
Do not install the memory back-up battery until the OCM-3 is to be used.
The unit is supplied with one battery package. Remove the battery from the package and insert it into the battery socket.
Refer to Operation \ Memory.
The memory battery, B1 (see Specifications) should be replaced yearly to insure memory back up during lengthy power outages. An on board capacitor provides one hour of memory retention in order to preserve the memory while the ba ttery is being changed.
COMMUNICATING VIA COMPUTER
Refer to Communication.
INSTALLING THE PROGRAMMER
To program the OCM-3 via the Programmer, it must be placed into the front cover recess of the OCM-3. The back of the Programmer has a magnetic plate which will hold the programmer in place. It can be removed when programming is completed.
20 OCM III 7ML19985AB01
Page 21
START UP
GENERAL
For the initial start up, it is advisable to use the programmer for programming the OCM-3. The programmer transmits a coded infrared signal each time a key is pressed.
The OCM-3 is designed to automatically scroll through the ‘A’, ‘D’, ‘F’, ‘P’ and ‘U’ parameters in a structured sequence. The scrolling is interactive in that, depending on the option chosen for a given parameter, subsequent parameters may be skipped or modified. The user is thus prompted to satisfy only the parameters which are available to him for the application he has chosen.
KEYPAD
numeric entries with decimal point
access to ‘D’, ‘F’, ‘P’ and ‘U’ parameters
negative
access to ‘A’ parameters / initiate s a printout while viewing ‘Flow and T otal’
scrolls through selected parameter options
scrolls
Forward
the parameters / enters content of entry field
scrolls
Backward
parameters / clears content of entry field
through
through the
7ML19985AB01 OCM III 21
Page 22
LEGEND
Press the associated programmer key:
Display shown on OCM -3:
Programmer key:
INITIAL START UP
After installation procedures have been completed, the OCM-3 may be powered up. Upon initial powering up, the unit momentarily displays:
and then scrolls through the available languages:
The OCM-3 is asking which language you prefer to communicate in!
0
(0) language
F0 enter security code < - - -
7ML19985AB01 OCM III 22
English
English language selected
advance to ‘F0’
Page 23
8 2 8
1
72
factory set security code
2.71828 must be entered
P0 language 0 English
P1 dimensional units 0centimeters
P0 language 0 English
if the wrong language was selected, it may be changed here
continue programming by entering the desired options and advancing until the scroll returns to ‘P0’. It is then assumed that the user has entered all the required parameters.
For optimum calibration accuracy, an ‘F13’ should be performed prior to accessing ‘F2’, the normal operating mode.
3
1
F13 auto zero calibration
enter the current head. The OCM-3 calculates ‘P46’ and automatically enters the value.
e.g. 1 6 0
01 6
F13 auto zero calibration 160
F13 auto zero calibration 0 completed
7ML19985AB01 OCM III 23
Page 24
If data logging is desired, the time and date must be set.
4
F4 24-hr. time
e.g. 1141
4
1
1
1
F4 24-hr. time 1141
F4 24-hr. time 11:41:00 enter new time
11: 41 a.m. seconds are always assumed to be 00
time is displayed in hh:mm:ss
,
F5 (ddmmyyyy) date
e.g. 12101492 October 12, 1492
0 1
4
9 211 2
F5 (ddmmyyyy) date 12/10/1492 enter new date
The start up procedure is now complete. Enter ‘F2’ to place the OCM-3 in the normal operating mode.
2
Note: To save parameter values, return to RUN mode (F2) after programming.
The OCM-3 now displays the flow rate and total. Refer to Operation \ Display
7ML19985AB01 OCM III 24
Page 25
FUNDAMENTAL CHECKS
For accurate determination of flowrate, accurate head measurement is essential. Check the following and correct if necessary.
» check D5 for correct temperature at transducer location.
» check D9 for corre ct distance from transducer to head.
» check D0 for accurate head measurement.
7ML19985AB01 OCM III 25
Page 26
7ML19985AB01 OCM III 26
Page 27
OPERATION
Upon power up, the transducer is fired periodically as set by P36. A long interval between measurements may be desirable in order to conserve power* when operating the OCM-3 from a DC source of limited capacity.
The echo is processed to determine the head (D0). The flow rate (D1) is calculated by the OCM-3 as a mathematical function (P3 and P4) of head or a function of head and velocity (P42). The flow rate is then integrated to yield the totalized flow (D2). The ‘Flow’ and ‘Total’ fields which are displayed during the normal running mode (F2) are also continuously updated.
Viewing or changing the content of a parameter (except F1, emulation) is done without disturbing the acquisition, processing or logging of flow data (see \ Security).
*
restricted usage of display lighting (P14), relays (P15, 18 & 21), mA output and communications will also conserve power.
MEMORY
During a power interruption, the memory back up will hold the programming, the log and the totalizer values, and run the clock. The memory battery (B1) provides up to one year of memory retention (see Appendices \ Maintenance).
Note: To save parameter values, return to RUN mode (F2) after programming.
SECURITY
The content of all ‘A’, ‘D’, ‘F’, ‘P’ and ‘U’ parameters can be viewed without having to satisfy the security parameter, F0. However if it is desired to change the content of any of these parameters, the security parameter must be satisfied (except for resetting the running min/max displays, parameters D3/D4 and D6/D7).
Once security has been satisfied, a ccess continues for 5 minutes after the last key is pressed or until F2 is re-entered.
The security code may be changed from its factory set value, 2.71828, by entering a new value into F10. It is imperative that the new value be recorded, as the code can not be viewed. If the code is lost, consult Milltronics.
UNITS
Programming of the OCM-3 involves setting the units of measure:
» P1 linear and velocity
» P2 temperature
» P5 flow rate and volume
If the units are changed during the course of operation, the change will be effected through all associated parameters and displays and will rescale flow and total data stored in the logs.
7ML19985AB01 OCM III 27
Page 28
FLOW CALCULATION
Absolute vs. ratiome tric
The OCM-3 can be programmed to use eithe r of two methods (P4) for calculating flow from the head measurement: absolute or ratiometric. The result is the same regardless of the method used. The principal difference is the information that must be entered in orde r for the OCM-3 to carry out the calculation. The user’s choice of method may ultimately be based upon the information which is at hand. Refer to U parameters for the primary element selected for a listing of the information required.
For the ratiometric method, it is usually sufficient that the user know the flow rate
) which occurs at maximum head (h
(Q
cal
On the other hand, absolute calculations require that the user enter information such as: the physical dimensions of the primary element and the constant relating to units of measure for both linear dimensions and flow rates.
e.g.
the general formula for flow through a single exponent primary element is:
cal
).
Q = KH
x
the specific formula for flow through a 45° V-notch weir is:
cfs = 1.03H
2.5
thus: Q = flow in cubic fe et per second
K = constant of 1.03 H = head in feet
The absolute method is not applicable to the following:
Palmer Bowlus flume H flume
DISPLAY
The normal display during operation is the Flow and Total Display (F 2).
flow rate field
totalizer fie ld
7ML19985AB01 OCM III 28
relay / "no echo" field
status field
Page 29
Flow Rate Field
Totalizer Field
flow rate
units, P5
total
multiplier, P32
Relay / No Echo Field
relay identification
under loss of echo condition, "NO ECHO" will alternately flash
Status Field
relay status : 0 = relay de-energized
1 = relay energized * = alarm state (indicated when
flashing)
The OCM-3 provides illumination for the LCD for easier viewing of the display. Illumination can be set (P14) to be normally on or off, or automatic. When automatic is selected, the lighting will automatically go on when keypad activity is sensed and then extinguish after 15 seconds of inactivity.
For battery operation, set display lighting to off or auto.
DAMPING
The OCM-3 provides two separate damping functions: reading and mA output. Zero or no damping allows fastest response while high or 100% provides the slowest response. The damping is usually set to provide a reliable response without sacrificing stability.
The reading damping, P13, dampens only the flow rate reading of the ‘Flow and Total’ display F2. The damping selections are: off, low, medium and high. Relay functions associated with flow rate respond to the dampened reading values.
mA output damping, P27, dampens the change in the mA output. The parameter entry is in seconds for spanning the 0 to 100% of the mA range selected (P26). Displays and relay functions associated with the mA output respond to its dampened value.
7ML19985AB01 OCM III 29
Page 30
RELAYS
Three on board multipurpose relays are provided by the OCM-3. P15, 18 and 21 set the respective functions for relays 1, 2 and 3. Depending on the function selected, these parameters determine the need and configuration of the subsequent relay control parameters, P16, 17 (relay 1); P19, 20 (relay 2) and P22, 23 (relay 3).
If the relay is to function as a driver for a remote totalizer or as a flow sampler contact, the totalizer multiplier (P32) will be factored by the setpoint . Note that parameters P16, P19, and P22 will default to zero. When a relay is set to totalizer (P32), you must have the applicable parameter (P16 for relay 1, P19 for relay 2, or P22 for relay 3) set to something other than zero (normally 1).
Example: For relay 1
Re la y totalizer factor =
totalizer factor (P32)
relay 1 setpoint (P16)
100 (P32=5)
= 2 (P16)
= 50 units/pulse
The status of each relay is shown in the display. Refer to \ Flow and Total Display.
For battery operation, have relays energizing on alarm.
mA OUTPUT
The OCM-3 provides a mA output (TB1-4/5) which can be assigned (P24) to represent the measurement of flow, head, velocity or temperature. The associated scaling, P25, is factory set to a value of ‘0’. This provides normal scaling with respect to the assigned measurement.
Normal scaling for representation of flow, head or velocity is:
» 0 or 4 mA = 0
» 20 mA = maximum measurement value for: » P6
» P7: maximum head
Normal scaling for representation of temperature is:
» 0 or 4 mA = – 40 °C
» 20 mA = 60 °C
If custom scaling is required, the 20 mA corresponding value (other than 0) can be entered into P25. The range (0 to 20 or 4 to 20 mA) and damping (see Damping) are set via P26 and P27 respectively.
7ML19985AB01 OCM III 30
*
: flow rate
at maximum head
» P10: velocity at maximum head
Page 31
The mA function can be overridden for test purposes by setting the desired mA value into F3. When the value is entered, the mA output will go to that value. When F3 is exited, the mA output will revert to normal operation. Also, see \ Emulation Mode.
*In the case of absolute calculations (P4=0),
P6 is calculated by the OCM-3.
FAIL-SAFE
In the event of an echo loss, the fail-safe timer will begin counting. If the echo loss duration surpasses that of the time set (P29), a ‘
No Echo
’ alert will be displayed in the Status field (see \ Display). The mA output will respond (P30) by either holding the last value or immediately going to a predetermined value (P31). The head and derived flow will hold their last value and totalization and logging will continue, based on that value. Upon resumption of a valid echo, the mA output will return to a value corresponding to the present value of the measurement assigned, at the mA damping rate (P27).
FLOW RATE AND TOTALIZING
Flow rate
Calculation of the flow rate is ongoing. It is normally viewed under the Flow and Total display (F2) with the decimal point set per P33. It can also be viewed under D1 as the raw flow calculation. Data on the running minimum and maximum flows that have occurred since the last reset can be viewed in two ways:
» F7 gives the running min/max flows and their time and date of occurrence since
the last reset. F7 is rese t by F8 but only after satisfying the security pa rameter F0.
» D3/D4 give the respective running min/max flow data , only, that have occurred
since they were last reset. D3/D4 are reset simultaneously by entering 0 into either D3 or D4. D3 and D4 will then adopt the current flow rate and track the running min/max values from that point on. The security parameter (F0) does not need to be satisfied in order to reset D3/D4.
Flow data specific to a particular time and date can be viewed under the data log F14 (see \ Logging).
Totalizing
Totalizing of the calculated flow is ongoing. It is normally viewed under the Flow and Total display (F2).
An auxiliary totalizer (D2) is provided for operator usage and is intended for short term totalizing to a maximum count of 999999. It can be reset or preset independently of the F2 totalizer after satisfying the security parameter (F0).
In order to adjust the rate of filling of the totalizer, the totalizer multiplier (P32) can be set to an appropriate value. The totalizer can be reset via F11. Totalizing that is specific to the time and date can be viewed under the data log F14.
The OCM-3 can be programmed to operate a remote totalizer by assigning any of the relays (P15, 18 or 21) to act as a totalizer contact*. Under this function, the maximum rate of contact closure is 2/sec with a closure duration of 200 msec**.
The totalizer count is set by the relay setpoint parameter (P16, 19 or 22 respectively).
*
**
Typically the totalizer should be set for 300 to 3000 counts per day at maximum flow.
7ML19985AB01 OCM III 31
Page 32
Under low flow conditions, a cut-off head (P45) can be entered to avoid totalizing flows occurring at or below the flow corresponding to the cut-off head.
LOGGING
The OCM-3 provides an extensive logging feature which can be viewed on the local display or retrieved via the serial communication link. The logging rate (P39) can be fixed or variable. The latter being useful in conserving logging space. The condition for variable logging is determined when selecting the logging rate.
Variable logging rate conditions are catagorized as : rate of change of flow, percent of maximum flow or percent of maximum head. Logging occurs at the normal (slower) rate while the condition is less than the setpoint (P40). If the condition exceeds the log rapid setpoint, the rapid rate of logging takes effect until the condition falls below the log normal setpoint (P41).
The associated setpoint units are : % change of maximum flowrate per minute, % of maximum flowrate and % of maximum head, respectively. The setpoints represent the absolute value of the rate of change; that is, for either increasing or decreasing flowrate. The OCM-3 does not recognize negative entries into P-40 and P-41.
Flow data is logged in 1/2 % increments from 0 to 110 % of maximum flow. Flows above 110 % are logged as 110 %. Truncation of flows to 110 % does not apply to daily totalization.
Log Capacity vs Rates
rate capacity
1 min 31 days
5 3 months
15 9 months
30 1 year
60 1.5 years
24 hr 2 years
e.g. 15 / 5 9 months max / 3 months min
Once the log is filled, the old data will be successively written ove r with the new data being logged.
The log can be examined via F14. Viewing of the log is done by task and by method. The viewing tasks are: daily flow totals, flow rates and min-max flow data for flow or temperature. The viewing methods are: by first entry, by last entry and by specified date. The scrolling keys are used to maneuver through the tasks, methods and time of day.
7ML19985AB01 OCM III 32
Page 33
Viewing the data log
The day totalizer (F14) does not use the master totalizer multiplier (P32). It is possible that the daily total overflows. In such a case the display will show +++.++.
7ML19985AB01 OCM III 33
Page 34
BLANKING
Blanking is used to ignore the zone in front of the transducer where ringing or other false echo is at a level that interferes with the processing of the true echo. The minimum blanking is factory set, but can be overridden by entering the desired distance into P47.
Ringing is the inherent nature of the transducer mass to continue vibrating after the transducer has been fired. Ringing decays to acceptable levels in the order of milliseconds. Excessive cold or over tightening of the transducer mounting may increase the ring time such that it appears as an echo during the receive cycle. This is usually indicated by an incorrect high head reading. Excessive ring time may be overcome by increasing the blanking.
TEMPERATURE
The temperature as currently registered by the temperature se nsor is viewed under D5. Data on the running minimum and maximum temperatures that have occurred since the last reset can be viewed in several ways:
F7 gives the running min/max temperatures and their time and date of occurrence since the last reset. F7 is reset by F8 but only after satisfying the security parameter F0.
D6/D7 give the respective running min/max temperature data, only, that have occurred since they were last reset. D6 is reset by entering a value lower than D5, and D7 is reset by entering a value larger than D5. D6 and D7 will then adopt the current temperature value and track the min/max values from that point on. The security parameter F0 does not need to be satisfied in order to reset D6 or D7.
Temperature data specific to the time and date can be viewed under the data log F14 (see \ Logging).
D14 indicates the resistance of the temperature sensor corresponding to the temperature shown in D5.
TIME AND DATE
If the data logging features of the OCM-3 are to be used, the time (F4) and date (F5) must be set. The day starts at 00:00:00 and ends at 23:59:59.
Adjusting the Time
If the clock time is advanced beyond the next anticipated logging time, the entry for each missed logging time is filled with a code which indicates that the system was not able to make entries at those times.
The daily total will be reduced proportional to the amount of time the day was shortened.
If the clock time is set back beyond the preceding logging time, the previously logged date will be written over with new data as the logging proceeds.
7ML19985AB01 OCM III 34
Page 35
The daily total will be increased proportional to the amount of time the day was lengthened.
Adjusting the Date
If the calendar is reset, the OCM-3 will adjust the log dates accordingly, taking into account leap years and days per month.
EMULATION MODE
The flow calculation (P3/ P4) can be checked for accuracy by using the emulation parameter F1. The head is entered and the corresponding flow is displayed. This function is useful when troubleshooting discrepancies between the OCM-3 calculation and the expected flow.
Relays assigned to functions associated with the emulation parameter respond to the emulated flows.
The mA output does not track the emulated flows when P28 (mA output emulation) =
0. However, if it is required to do so, then the emulator parameter should be set to 1.
RESET
The following resets can only be e xecuted after satisfying the security access, F0.
Cold Start
If it is desired to reset all parameters, logs and totalizers to their factory setting, this is done by forcing a cold start, F12 .
Master Totalizer
If it is desired to reset the master totalizer (F2), this is done by parame ter F11.
Data Log
If it is desired to reset the data log (F14), this is done by parameter F15.
Min/Max Log
If it is desired to reset the min/max log (F7), this is done by parameter F8.
7ML19985AB01 OCM III 35
Page 36
FLOW VELOCITY INPUT
In some applications, the flow calculation for the chosen primary element requires a velocity input. In this type of application, the transducer measurement is used to calculate the cross sectional area of the flow. By multiplying the area with the distance per time units of velocity, the volume per time units of flow are calculated. The calculate d velocity can be viewed via D8.
The 0% and 100% limits of the velocity input must be scaled using parameters P8 and P9.
» se le ct P8 » enter the voltage corresponding to zero velocity » se le ct P9 » enter the velocity corresponding to 5 V
e.g. If the velocity sensor output is 1 V per m/ sec and the output is
scaled for 7 V at 100% velocity (7 m/sec), then enter 5 m/sec. If the output is scaled for 4 V at 100% velocity (4 m/sec), enter 5 m/sec.
P8 and P9 can only be accessed if P3 has been set for an option that requires the use of a velocity input. The input voltage level can be viewed via D12.
Voltage Input
typical 1 - 5 V signal from velocity sensor.
Signal must be positive with respect to ground.
Velocity Input
AUXILIARY HEAD INPUT
Current Input
typical 4 - 2 0 mA signal from velocity sensor. Add termina ting resistor. e.g. 250 for 1 - 5 V over 4 - 20 mA.
(additional to Basic Wiring)
In some applications, the transducer input (TB1-1/2) is not used to provide a signal for head measurement. A typical example of this is an application which is beyond the 3 m (10 ft) range of the OCM-3. In such a ca se, the head could be derived from another Milltronics level monitor or other compatible device.
The method of head determination is set by P42. The OCM-3 simply substitutes the signal from the auxiliary device for the ultrasonic measurement provided by the transducer. The programming and consequent flow calculation are performed as normal.
7ML19985AB01 OCM III 36
Page 37
The 0% and 100% limits of the auxiliary input must be scaled using parameters P43 and P44.
» se le ct P4 3 » enter the voltage corresponding to zero head » se le ct P4 4 » enter the head corresponding to 5 V.
e.g. if the head output is 1 V per m and the output is scaled for 7 V at
100% head (7 m), then enter 5 m. If the output is scaled for 4 V at 100% head (4 m), enter 5 m.
P43 and P44 can only be accessed if P42 has been set for head determination by an auxiliary device. The input voltage level can be viewed via D13.
Voltage Input
typical 1 - 5 V signal from auxiliary device.
Signal must be positive with respect to ground.
Auxiliary Input
typical 4 - 20 mA signal from auxiliary device. Add termina ting resistor. e.g. 250 for 1 - 5 V over 4 - 20 mA.
(additional to Basic Wiring)
Current Input
DC OUTPUT
The OCM-3 provides a 24 V DC output that can be used to supply power to a remote customer device. The output is not isolated from the DC rails that supply the OCM-3 electronics and no overload protection is provided. As such, the output must not operate beyond its specified capacity.
DIAGNOSTIC AIDS
D15 through D18 are diagnostic aids to Milltronics service personnel when troubleshooting system problems.
D18 also serves as a performance indicator by displaying the number of valid echos received as a percentage of the number of pulses being fired by the transducer. A low value indicates that a large proportion of the pulses fired are not producing valid echos. In such instances, the transducer should be checked for proper mounting and aiming or the transducer wiring checked for excessive noise. If the value is zero, shorted or opened transducer wiring may be suspect.
7ML19985AB01 OCM III 37
Page 38
‘D’ PARAMETER LISTING
Refer to ‘Operation’ for details.
D0 head
D1 flow rate
D2 short total *
D3 maximum flow rate
D4 minimum flow rate
D5 temperature
D6 maximum temperature
D7 minimum temperature
D8 velocity
D9 nominal target range
D10 analog milliamps
D11 internal DC volts
D12 velocity volts
D13 auxiliary input volts
D14 tempe rature sensor ohms
D15 self-test checksum
D16 restarts
D17 exceptions
D18 valid echos per 100
7ML19985AB01 OCM III 39
*
security access required
applicable to flow calculations requiring velocity sensor
Page 39
7ML19985AB01 OCM III 40
Page 40
‘F’ PARAMETER LISTING
Refer to ‘Operation’ for details.
F0 enter security code
F1 emulation mode
*
F2 run mode
F3 keypad to mA output
*
F4 show time
set time
*
F5 show date
set date
*
F6 software identification number
F7 view min/max data
F8 reset min/max data
F9 self check
*
F10 change security code
*
*
F11 reset master totalizer
F12 force a cold start
*
F13 auto zero calibration
F14 examine data log:
task: view daily totals
view flow rates
view min/max data
method:
first day
last day
specified da y
F15 clear data log
*
*
*
7ML19985AB01 OCM III 41
*
security access required
Page 41
7ML19985AB01 OCM III 42
Page 42
‘P’ PARAMETER LISTING
Refer to ‘Operation’ for details.
P0 language
0 = english
1 = french
2 = italian
3 = german
4 = spanish
P1 dimensional units
linear velocity
0 = centimetres centimetres per second
1 = inches inches per second
2 = feet feet per second
3 = metres metres per second
P2 temperature units
0 = Celcius
1 = Fahrenheit
P3 primary element
0 = exponential device
1 = BS-3680 Rectangular Flume
2 = BS-3680 Round Nose Horizontal Crest Weir
3 = BS-3680 Trapezoidal Flume
4 = BS-3680 U-throated Flume
5 = BS-3680 Finite Crest Weir
6 = BS-3680 Thin Plate Rectangular Weir
7 = BS-3680 Thin Plate V-notch Weir
7ML19985AB01 OCM III 43
8 = Rectangular Weir (contracted)
9 = Round Pipe
10 = Palmer Bowlus Flume
11 = H Flume
12 = Universal Head vs. Flow
Page 43
13 = Rectangular Area x Velocity
14 = Trapezoidal Area
15 = Modified Trapezoidal Area
16 = U-channel Area
17 = Circular Area
18 = Gull-wing Area
19 = Egg-shaped Area
20 = Universal Area
P4 method of calculation
0 = absolute
1 = ratiometric
P5 flow rate units
flowrate
Velocity
x
Velocity
x
Velocity
x
Velocity
x
Velocity
x
Velocity
x
Velocity
x
volume
0 = litres per second litres
1 = cubic feet per second cubic feet
2 = imperial gallons per minute imperial gallons
3 = U.S. gallons per minute U.S. gallons
4 = imperial million gallons per day imperial million gallons
5 = U.S. million gallons per day U.S. million gallons
6 = cubic metres per hour cubic metres
7 = cubic metres per day cubic metres
P6 flow at maximum head
P7 height of maximum head
P8 volts in at zero velocity
P9 velocity at 5 volts in
P10 velocity at maximum flow
7ML19985AB01 OCM III 44
Page 44
P13 display damping
0 = off
1 = low
2 = med
3 = high
P14 display lighting
0 = on
1 = auto off
2 = off
P15 / P18 / P21 relay 1 / 2 / 3 assignment
0 = not in service
1 = de-energize on loss of echo
2 = energize on loss of echo
3 = de-energize on high flow rate
4 = energize on high flow rate
5 = de-energize on low flow rate
6 = energize on low flow rate
7 = de-energize on high head
8 = energize on high head
9 = de-energize on low head
10 = energize on low head
11 = de-energize on high velocity
12 = energize on high velocity
13 = de-energize on low velocity
14 = energize on low velocity
15 = de-energize on high analog
16 = energize on high analog
17 = de-energize on low analog
18 = energize on low analog
7ML19985AB01 OCM III 45
19 = de-energize on low D11 volts
20 = energize on low D11 volts
21 = de-energize on high D11 volts
22 = energize on high D11 volts
23 = de-energize on low Aux. volts
Page 45
24 = energize on low Aux. volts
25 = de-energize on high Aux. volts
26 = energize on high Aux. volts
27 = de-energize up control on head
28 = energize up control on head
29 = de-energize down control on head
30 = energize down control on head
31 = de-energize up control on analog
32 = energize up control on analog
33 = de-energize down control on analog
34 = energize down control on analog
35 = ( pulse ) flow totalizer
36 = ( pulse ) sampler by volume
37 = ( pulse ) sampler by time
38 = ( pulse ) by time of day
P16 / P19 / P22 relay 1 / 2 / 3 high setpoint
P17 / P20 / P23 relay 1 / 2 / 3 low setpoint
P24 mA assignment
0 = flow rate
1 = head
2 = velocity
3 = temperature
P25 If custom mA, 20 mA = ?
0 = normal
0 = custom
P26 mA span
7ML19985AB01 OCM III 46
0 = 4-20 mA
1 = 0-20 mA
Page 46
P27 mA damping (secs)
P28 mA options (emulator tracking)
0 = don’t track emulator
1 = track emulator
P29 fail-safe time (secs)
P30 fail-safe analog mode
0 = hold last value
1 = assume value in P31
P31 fail-safe analog mA (default value)
P32 totalizer multiplier
0 = x 1/1000 (0.001)
1 = x 1/100 (0.01)
2 = x 1/ 10 (0.1)
3 = x 1
4 = x 10
5 = x 100
6 = x 1000
P33 flow rate display (decimal point)
0 = no decimal places
1 = 1
2 = 2
3 = 3
4 = 4
7ML19985AB01 OCM III 47
Page 47
P34 printer mode
0 = never print
1 = interval to be in minutes
2 = interval to be in hours
3 = print once each day
P35 printer timing
P36 measurement interval
0 = 1 sec
1 = 15 sec
2 = 30 sec
3 = 1 min
4 = 5 min
P37 serial data rate
0 = 300 baud
1 = 600
2 = 1200
3 = 2400
4 = 4800
5 = 9600
6 = 19200
P38 site number
7ML19985AB01 OCM III 48
Page 48
P39 data logging rate
fixed
0 = 1 min 3 = 30
1 = 5 4 = 60
2 = 15 5 = 24 hr
6 = 15/1 min (
variable
% flow / min
(
condition
)
) 19 = 60 / 1 (
flow
7 = 15 / 5 " 20 = 60 / 5 "
8 = 30 / 1 " 21 = 24 hr / 1 min "
9 = 30 / 5 " 22 = 24 hr / 5 min "
10 = 60 / 1 " 23 = 24 hr / 15 min "
11 = 60 / 5 " 24 = 15 / 1 min (
head
12 = 24 hr / 1 min " 25 = 15 / 5 "
13 = 24 hr / 5 min " 26 = 30 / 1 "
14 = 24 hr / 15 min " 27 = 30 / 5 "
)
)
15 = 15 / 1 min (
16 = 15 / 5 " 29 = 60 / 5 "
17 = 30 / 1 " 30 = 24 hr / 1 min "
18 = 30 / 5 " 31 = 24 hr / 5 min "
P40 log rapid setpoint
P39 variable logging condition units
% flow / min % change of maximum flow per minute
flow % of maximum flow
head % of maximum head
P41 log normal setpoint
P39 variable logging condition units
) 28 = 60 / 1 "
flow
32 = 24 hr / 15 min "
% flow / min % change of maximum flow per minute
7ML19985AB01 OCM III 49
flow % of maximum flow
head % of maximum head
Page 49
P42 head determination
0 = by OCM-3
1 = by auxiliary device
P43 volts in for zero head
P44 head at 5 volts in
P45 low flow cut-off head
P46 range at zero head
P47 blanking distance
7ML19985AB01 OCM III 50
Page 50
‘U’ PARAMETERS FOR P3 PRIMARY ELEMENT
The number of ‘U’ parameters required varies according to the primary element chosen (P3) and the method of calculation (P4). The OCM -3 prompts the user by displaying the next required parameter, insuring the programming is complete.
The following is a list of the specific primary elements to which the OCM-3 can be applied.
Refer to the page covering your particular application; the rest may be disregarded.
P3 primary element
0 exponential device (e.g. proportional, V-notch, Parshall etc)
1 BS-3680 Rectangular Flume (ISO 4359)
2 BS-3680 Round Nose Horizontal Crest Weir (ISO 4374)
3 BS-3680 Trapezoidal Flume (ISO 4359)
4 BS-3680 U-throated Flume (ISO 4359)
5 BS-3680 Finite Crest Weir (ISO 3846)
6 BS-3680 Thin Plate Rectangular Weir (ISO 1438/1)
7 BS-3680 Thin Plate V Notch Weir (ISO 1438/1)
8 Rectangular Weir (contracted)
9 Round Pipe
10 Palmer-Bowlus Flume
11 H Flume
12 Universal Head vs. Flow
13 Rectangular Area
14 Trapezoidal Area
15 Modified Trapezoidal Area
16 U-channel Area
7ML19985AB01 OCM III 51
Velocity
x
Velocity
x
Velocity
x
Velocity
x
Page 51
17 Circular Area
x Velocity
18 Gull Wing Area
19 Egg-shaped Area
20 Universal Area
x Velocity
x Velocity
x Velocity
The primary element must be installed in accordance with the manufacturers recommendations and in accordance with all governing regulations.
7ML19985AB01 OCM III 52
Page 52
SIMPLE EXPONENTIAL DEVICES, P3 = 0
‘U’ parameters required *
U0 = exponent
U1 = k factor (P4 = 0 only)
Typical Exponential Devices:
» Sutro (proportional) weir
» head measurement only
» Rectangular (suppressed) or Trapezoidal (Cipolletti) weir
» Kahfagi venturi
» Parshall flume
» Leopold Lagco
» Triangular (V-notch) weir
*
obtain from manufacturer’s specifications.
Reference
ABSOLUTE CALCULATION, P4 = 0¤
For flows that can be calculated by the equation:
q = k h
x
where q = flowrate x = exponent (U0)
k = constant factor (U1) h = head
RATIOMETRIC CALCULATION, P4 = 1¤
For flows that can be calculated by the equation:
cal
(h/h
q = q
where q = flowrate q
x
)
cal
h = head h
= flowrate at maximum head
cal
= maximum head
cal
x = exponent (U0)
Refer to manufacturers specifications for the exponent value.
¤
Refer to Operation \ Flow Calculation.
7ML19985AB01 OCM III 53
Page 53
SIMPLE EXPONENTIAL DEVICES, P3 = 0
TYPICAL SHARP-CRESTED WEIRS
transducer *
minimum
3 x h
max
Typical Weir Profiles
V - notch or Triangular
U 0 = 2.5
Tra pezoidal (Cipolletti)
U 0 = 1.5
Rectangular - suppressed
U 0 = 1.5
Sutro (Proportional)
U 0 = 1
(symmetrical or asymmetrical)
For rated flows under free flow conditions, the head is measured upstream of the weir plate at a minimum distance of 3 times the maximum head (i.e. where the liquid surface is not affected by drawdown).
* The transducer must be above the maximum head by at least the blanking value, P47.
7ML19985AB01 OCM III 54
Page 54
SIMPLE EXPONENTIAL DEVICES, P3 = 0
KHAFAGI VENTURI
15 cm (6")
plan
transducer *
0
head
front
side
For rated flows under free flow conditions, the hea d is measured 15 cm (6") upstream from the beginning of the converging section.
* The transducer must be above the maximum head by at least the blanking value, P47.
7ML19985AB01 OCM III 55
Page 55
SIMPLE EXPONENTIAL DEVICES, P3 = 0
TYPICAL PARSHALL FLUME
C
2/3 C
plan
transducer *
0
head
front
side
For rated flows under free flow conditions, the head is measured at 2/3 the length of the converging section upstream of the beginning of the throat section.
* The transducer must be above the maximum head by at least the blanking value, P47.
7ML19985AB01 OCM III 56
Page 56
SIMPLE EXPONENTIAL DEVICES, P3 = 0
TYPICAL LEOPOLD LAGCO
throat
Q
converging
point of measurement
plan
side
diverging
transducer *
0
head
front
For rated flows under free flow conditions, the head is measured at a point upstream referenced to the beginning of the converging section. Refer to the following table.
Flume Size Point of Measurement
(pipe dia. in inches) mm inches
4 - 12 25 1.0
15 32 1.3
18 38 1.5
21 44 1.8
24 51 2.1
30 64 2.5
36 76 3.0
42 89 3.5
48 102 4.0
54 114 4.5
60 127 5.0
66 140 5.5
72 152 6.0
* The transducer must be above the maximum head by at least the blanking value, P47.
7ML19985AB01 OCM III 57
Page 57
BS-3680 Rectangular Flume, P3 = 1
‘U’ parameters required * ‘U’ parameters calculated **
U0 = approach width B U4 = Cv
U1 = throat width b U5 = Cd
U2 = hump height p U6 = A
U3 = throat length L
*obtain from manufacturer’s specifications.
**
calculated by OCM -3. May be viewed by accessing ‘U’ parameter.
Reference
ABSOLUTE CALCULATION, P4 = 0¤
For flows that can be calculated by the equation:
q = (2/3)
0.5
x g
x Cv x Cs x Cd x B x h
1.5
1.5
where : q = flow rate Cv = velocity coefficient
b = throat width Cs = shape coefficient
g = gravitational acceleration Cd = discharge coefficient
h = head
RATIOMETRIC CALCULATION, P4 = 1¤
For flows that can be calculated by the equation:
q = q
x Cd/Cd
cal
x Cv/Cv
cal
x (h/h
cal
cal
1.5
)
where : q = flow rate
q
= flow rate at maximum head
cal
h = head
h
= maximum head
cal
Cv = velocity coefficient
Cv
= velocity coefficient for maximum head
cal
Cd = discharge coefficient for head
Cd
= discharge coefficient for maximum head
cal
¤
Refer to Operation \ Flow Calculation.
7ML19985AB01 OCM III 58
Page 58
BS-3680 RECTANGULAR FLUME
0 head
3 to 4 x h
h
max
transducer *
p
L
* The transducer must be above the maximum head by at least the blanking value, P47.
7ML19985AB01 OCM III 59
Page 59
BS-3680 Round Nose Horizontal Crest Weir, P3 = 2
‘U’ parameters required * ‘U’ parameters calculated **
U0 = crest width b U3 = Cv
U1 = crest height p U4 = Cd
U2 = crest length L U5 = A
*
obtain from manufacturer’s specifications.
**
calculated by OCM -3. May be viewed by accessing ‘U’ parameter.
Reference
ABSOLUTE CALCULATION, P4 = 0¤
For flows that can be calculated by the equation:
1.5
q = (2/3)
0.5
x g
x Cv x Cs x Cd x b x h
1.5
where : q = flow rate Cv = velocity coefficient
g = gravitational acceleration Cs = shape coefficient
b = throat width Cd = discharge coefficient
h = head
RATIOMETRIC CALCULATION, P4 = 1¤
For flows that can be calculated by the equation:
q = q
x Cd/Cd
cal
x Cv/Cv
cal
x (h/h
cal
cal
1.5
)
where : q = flow rate
q
= flow rate at maximum head
cal
h = head
h
= maximum head
cal
Cv = velocity coefficient
Cv
= velocity coefficient for maximum head
cal
Cd = discharge coefficient for head
Cd
= discharge coefficient for maximum head
cal
¤
Refer to Operation \ Flow Calculation.
7ML19985AB01 OCM III 60
Page 60
BS-3680 ROUND NOSE HORIZONTAL CREST WEIR
transducer *
3 to 4 x h
max
* The transducer must be above the maximum head by at least the blanking value, P47.
7ML19985AB01 OCM III 61
Page 61
BS-3680 TRAPEZOIDAL FLUME, P3 = 3
‘U’ parameters required * ‘U’ parameters calculated **
U0 = approach width B U5 = Cv
U1 = throat width b U6 = Cd
U2 = hump height p U7 = Cs
U3 = throat length L U8 = A
U4 = slope m
*obtain from manufacturer’s specifications.
**
calculated by OCM -3. May be viewed by accessing ‘U’ parameter.
Reference
ABSOLUTE CALCULATION, P4 = 0¤
For flows that can be calculated by the equation:
q = (2/3)
0.5
x g
x Cv x Cs x Cd x b x h
1.5
1.5
where : q = flow rate Cv = velocity coefficient
g = gravitational acceleration Cs = shape coefficient
b = throat width Cd = discharge coefficient
h = head
RATIOMETRIC CALCULATION, P4 = 1¤
For flows that can be calculated by the equation:
q = q
x Cs/Cs
cal
x Cd/Cdal x Cv/Cv
cal
x (h/h
cal
cal
1.5
)
where :
q = flow rate Cs
q
= flow rate at maximum head Cv = velocity coefficient
cal
h = head Cv
h
= maximum head Cd = discharge coefficient for head
cal
Cs = shape coefficient for head Cd
= shape coefficient for maximum head
cal
= velocity coefficient for maximum head
cal
= discharge coefficient for maximum head
cal
¤
Refer to Operation \ Flow Calculation.
7ML19985AB01 OCM III 62
Page 62
BS-3680 TRAPEZOIDAL FLUME
p
b
end
B
transducer *
3 to 4 x h
max
plan
L
h
* The transducer must be above the maximum head by at least the blanking value, P47.
7ML19985AB01 OCM III 63
p
side
Page 63
BS-3680 U-Flume, P3 = 4
‘U’ parameters required * ‘U’ parameters calculated **
U0 = approach diameter Da U4 = Cv
U1 = throat diameter D U5 = Cd
U2 = hump height p U6 = Cu
U3 = throat length L U7 = A
*
obtain from manufacturer’s specifications.
**
calculated by OCM -3. May be viewed by accessing ‘U’ parameter.
Reference
ABSOLUTE CALCULATION, P4 = 0¤
For flows that can be calculated by the equation:
q = (2/3)
0.5
x g
x Cv x Cu x Cd x D x h
1.5
1.5
where : q = flow rate Cv = velocity coefficient
g = gravitational acceleration Cu = shape coefficient
b = throat width Cd = discharge coefficient
h = head
RATIOMETRIC CALCULATION, P4 = 1¤
For flows that can be calculated by the equation:
q = q
x Cu/Cu
cal
x Cd/Cd
cal
x Cv/Cv
cal
x (h/h
cal
cal
1.5
)
where : q = flow rate
q
= flow rate at maximum head
cal
h = head h
= maximum head
cal
Cu = shape coefficient for head Cu
= shape coefficient for maximum head
cal
Cv = velocity coefficient Cv
= velocity coefficient for maximum head
cal
Cd = discharge coefficient for head Cd
= discharge coefficient for maximum head
cal
¤
Refer to Operation \ Flow Calculation.
7ML19985AB01 OCM III 64
Page 64
BS-3680 U-FLUME
0
head
3 to 4 x h
Da
h
max
transducer *
p
L
D
* The transducer must be above the maximum head by at least the blanking value, P47.
7ML19985AB01 OCM III 65
Page 65
BS-3680 FINITE CREST WEIR, P3 = 5
‘U’ parameters required * ‘U’ parameters calculated **
U0 = crest width b U3 = C
U1 = crest height p U4 = Cp
U2 = crest length L
*
obtain from manufacturer’s specifications.
**
calculated by OCM -3. May be viewed by accessing ‘U’ parameter.
Reference
ABSOLUTE CALCULATION, P4 = 0¤
For flows that can be calculated by the equation:
q = (2/3)
0.5
x g
x C x Cp x b x h
1.5
1.5
where : q = flow rate C = a function of h and L
g = gravitational acceleration b = crest width Cp = a correction factor as a function h = head of h and p applied to C
RATIOMETRIC CALCULATION, P4 = 1¤
For flows that can be calculated by the equation:
q = q
x C/C
cal
x Cp/Cp
cal
x (h/h
cal
cal
1.5
)
where : q = flow rate
q
= flow rate at maximum head
cal
h = head
h
= maximum head
cal
C = discharge coefficient for head
C
= discharge coefficient for maximum head
cal
Cp = correction fa ctor for C
Cp
= correction factor for C
cal
cal
¤
Refer to Operation \ Flow Calculation.
7ML19985AB01 OCM III 66
Page 66
BS-3680 FINITE CREST WEIR
transducer *
3 to 4 x h
max
* The transducer must be above the maximum head by at least the blanking value, P47.
7ML19985AB01 OCM III 67
Page 67
BS-3680 THIN PLATE RECTANGULAR WEIR, P3 = 6
‘U’ parameters required * ‘U’ parameters calculated **
U0 = approach width B U3 = Ce
U1 = crest width b U4 = K
b
U2 = crest height p
*obtain from manufacturer’s specifications.
**
calculated by OCM -3. May be viewed by accessing ‘U’ parameter.
Reference
ABSOLUTE CALCULATION, P4 = 0¤
For flows that can be calculated by the equation:
q
= Ce x
2
√⎯⎯⎯2g x be x (
3
where : q = flow rate Ce = a function of h, p, b and B
g = gravitational acceleration be = effective crest width (b + K
b = crest width h
h = head K
1.5
h
)
e
= effective head (h + Kh)
e
= 1 mm
h
)
b
RATIOMETRIC CALCULATION, P4 = 1¤
For flows that can be calculated by the equation:
q = q
x Ce/Ce
cal
x (h/h
cal
cal
1.5
)
where : q = flow rate
q
= flow rate at maximum head
cal
h = head
h
= maximum head
cal
Ce = discharge coefficient for head
Cv
= discharge coefficient for maximum head
cal
¤
Refer to Operation \ Flow Calculation.
7ML19985AB01 OCM III 68
Page 68
BS-3680 THIN PLATE RECTANGULAR WEIR
transducer *
4 to 5 x h
max
* The transducer must be above the maximum head by at least the blanking value, P47.
7ML19985AB01 OCM III 69
Page 69
BS-3680 THIN PLATE V-NOTCH WEIR, P3 = 7
‘U’ parameters required * ‘U’ parameters calculated **
U0 = notch angle alpha U1 = Ce
*
obtain from manufacturer’s specifications.
**
calculated by OCM -3. May be viewed by accessing ‘U’ parameter.
Reference
ABSOLUTE CALCULATION, P4 = 0¤
For flows that can be calculated by the equation:
0.5
q = Ce x 8/15 x tan(
/2) x (2g)
α
where : q = flow rate h = head
x h
2.5
g = gravitational acceleration Ce = function of h and
= notch angle alpha
α
angle is restricted to 90°, 53.133° or 28.066°. Otherwise use ratiometric calculation.
RATIOMETRIC CALCULATION, P4 = 1¤
α
For flows that can be calculated by the equation:
q = q
x Ce/Ce
cal
x (h/h
cal
cal
2.5
)
where : q = flow rate
q
= flow rate at maximum head
cal
h = head
h
= maximum head
cal
Ce = discharge coefficient for head
Ce
= discharge coefficient for maximum head
cal
¤
Refer to Operation \ Flow Calculation.
7ML19985AB01 OCM III 70
Page 70
BS-3680 THIN PLATE V-NOTCH WEIR
transducer *
4 to 5 x h
max
* The transducer must be above the maximum head by at least the blanking value, P47.
7ML19985AB01 OCM III 71
Page 71
RECTANGULAR WEIR (CONTRACTED), P3 = 8
‘U’ parameters required *
U0 = crest width b
*
obtain from manufacturer’s specifications.
**
calculated by OCM -3. May be viewed by accessing ‘U’ parameter.
Reference
ABSOLUTE CALCULATION, P4 = 0¤
For flows that can be calculated by the equation:
q = K x (b - 0.2h) x h
1.5
where : q = flow rate
h = head
K = constant
RATIOMETRIC CALCULATION, P4 = 1¤
For flows that can be calculated by the equation:
q = q
x (b - 0.2h)/(b - 0.2h
cal
) x (h/h
cal
cal
2.5
)
where : q = flow rate
q
= flow rate at maximum head
cal
h = head
h
= maximum head
cal
¤
Refer to Operation \ Flow Calculation.
7ML19985AB01 OCM III 72
Page 72
RECTANGULAR WEIR - CONTRACTED
transducer *
4 to 5 x h
max
* The transducer must be above the maximum head by at least the blanking value, P47.
7ML19985AB01 OCM III 73
Page 73
ROUND PIPE, P3 = 9
(based on the Manning Formula)
‘U’ parameters required *
U0 = pipe inside diameter D
U1 = slope (fall/run) s
U2 = roughness coefficientn
*obtain from manufacturer’s specifications.
Reference
ABSOLUTE CALCULATION, P4 = 0¤
For flows that can be calculated by the equation:
q = K/n x f(h) x s
0.5
where : q = flow rate
h = head
K = constant
f(h) = A x R
0.66
A = cross sectional area
R = hydraulic radius
s = slope of hydraulic gradient
n = roughness coe fficient
RATIOMETRIC CALCULATION, P4 = 1¤
For flows that can be calculated by the equation:
q = q
x f(h)/f(h
cal
cal
)
where : q = flow rate h = head
q
= flow rate at maximum head h
cal
= maximum head
cal
¤
Refer to Operation \ Flow Calculation.
7ML19985AB01 OCM III 74
Page 74
ROUND PIPE
transducer
*
**
* This dimension should be at least 15 cm (6") shorter than the blanking value, P47.
** The transducer must be above the maximum head by at least the blanking value, P47.
h
7ML19985AB01 OCM III 75
Page 75
PALMER-BOWLUS FLUME *, P3 = 10
‘U’ parameters required **
U0 = maximum flume width, h
*
typically those manufactured by Warminster or Plasti-Fab.
**
obtain from manufacturer’s specifications.
max
Reference
RATIOMETRIC CALCULATION, P4 = 1¤
For flows that can be calculated by the equation:
q = q
x f(h/h
cal
max)
/ f(h
cal/hmax
)
where : q = flow rate
q
= flow rate at maximum head
cal
h = head
h
= maximum head
cal
f(h/h
) is determined by polynomial synthesis
max
¤
Refer to Operation \ Flow Calculation.
7ML19985AB01 OCM III 76
Page 76
PALMER-BOWLUS FLUME
D / 2, point of measurement *
D = pipe or sewer diameter
* for rated flows under free flow conditions
transducer **
0
head
** The transducer must be above the maximum head by at least the blanking value, P47.
7ML19985AB01 OCM III 77
Page 77
H-FLUME *, P3 = 11
‘U’ parameters required *
U0 = maximum listed head, h
*
as developed by the U.S. Department of Agriculture, Soil Conservation Service.
**
obtain from manufacturer’s specifications.
max
Reference
RATIOMETRIC CALCULATION, P4 = 1¤
For flows that can be calculated by the equation:
q = q
x f(h/h
cal
max
)/f(h
cal/hmax
)
where : q = flow rate
q
= flow rate at maximum head
cal
f(h/h
¤
Refer to Operation \ Flow Calculation.
) and f(h
max
cal/hmax
) are determined by polynomial synthesis
7ML19985AB01 OCM III 78
Page 78
H-FLUME
transducer *
point of measurement
plan
front
side
For rated flows under free flow conditions, the head is measured at a point downstream from the flume entrance. Refer to the following table.
Flume Size Point of Measurement
D (feet) cm inches
0.5 4.7 1.88
0.75 6.7 2.69
1.0 9.1 3.63
1.5 13.5 5.38
2.0 17.9 7.19
2.5 22.5 9.00
3.0 27.2 10.88
4.5 40.5 16.19
* The transducer must be above the maximum head by at least the blanking value, P47.
7ML19985AB01 OCM III 79
Page 79
UNIVERSAL HEAD vs FLOW, P3 = 12
The flow curve is characterized by entering the head (A
) and flow (A
even
odd
) ordinates for the number of data points (n, 4 to 16) over the flow range. The first point (A0,A1) generally being at 0 head and the last point (A
2n-2,A2n-1
) generally being
at maximum head .
‘U’ parameters required *
U0 = number of data points
= head
A
even
A
= flow rate
odd
*
obtain from manufacturer’s specifications.
Reference
RATIOMETRIC CALCULATION, P4 = 1¤
(n, 4 to 16)
For flows that can be calculated by the equation:
q = q
where : f(h) and f(h
¤
x f(h)/f(h
cal
cal
)
) are polynomials based on interpolation of data points
cal
Refer to Operation \ Flow Calculation.
7ML19985AB01 OCM III 80
Page 80
UNIVERSAL HEAD vs FLOW
e. g. typical compound weir
Parameters
U0 = 11
A0 = 0 head, point 1 A12 = 1.05 head, point 7
A1 = 0 flow, point 1 A13 = 2.65 flow, point 7
A2 = 0.3 head, point 2 A14 = 1.2 head, point 8
A3 = 0.1 flow, point 2 A15 = 3.4 flow, point 8
A4 = 0.6 head, point 3 A16 = 1.4 head, point 9
A5 = 0.7 flow, point 3 A17 = 5.0 flow, point 9
A6 = 0.8 head, point 4 A18 = 1.7 head, point 10
A7 = 1.5 flow, point 4 A19 = 8.0 flow, point 10
A8 = 0.95 head, point 5 A20 = 2 head, point 11
A9 = 2.25 flow, point 5 A21 = 11.8 flow, point 11
A10 = 1 head, point 6
A11 = 2.5 flow, point 6
odd
A
F
l o w
R a
t e
For best accuracy concentrate data points where changes in flow rate are the greatest.
7ML19985AB01 OCM III 81
Head
A
even
Page 81
RECTANGULAR AREA X VELOCITY, P3 = 13
‘U’ parameters required * ‘U’ parameters calculated **
U0 = channel width B U1 = area (h)
*obtain from manufacturer’s specifications.
**
calculated by OCM -3. May be viewed by accessing ‘U’ parameter.
Reference
ABSOLUTE CALCULATION, P4 = 0¤
For flows that can be calculated by the equation:
q = 1/1000 x B x h x V
where : q = flow rate in l/sec
B = channel width in cm
h = head in cm
V = velocity in cm/sec
RATIOMETRIC CALCULATION, P4 = 1¤
For flows that can be calculated by the equation:
q = q
x A/A
cal
cal
x v/v
cal
where : q = flow rate
q
= flow rate at maximum head
cal
h = head
h
= maximum head
cal
v = ve locity
v
= velocity at maximum head
cal
¤
Refer to Operation \ Flow Calculation.
7ML19985AB01 OCM III 82
Page 82
RECTANGULAR AREA X VELOCITY
transducer *
* The transducer must be above the maximum head by at least the blanking value, P47.
7ML19985AB01 OCM III 83
Page 83
TRAPEZOIDAL AREA X VELOCITY, P3 = 14
‘U’ parameters required * ‘U’ parameters calculated **
U0 = channel top width B U3 = area (h)
U1 = channel base width b
U2 = channel depth ht
*
obtain from manufacturer’s specifications.
**
calculated by OCM -3. May be viewed by accessing ‘U’ parameter.
Reference
ABSOLUTE CALCULATION, P4 = 0¤
For flows that can be calculated by the equation:
q = 1/1000 x (b + mh) x v
m = (B - b)/d
where : q = flow rate, l/sec
B = channel top width, cm b = channel bottom width, cm d = depth of channel, cm h = head, cm v = flow velocity, cm/sec
RATIOMETRIC CALCULATION, P4 = 1¤
For flows that can be calculated by the equation:
q = q
x A/A
cal
cal
x v/v
cal
A = (b + mh) x h
A
= (b + mh
cal
cal
) x h
cal
m = (B - b)/d
where : q = flow rate, l/sec
B = channel top width, cm b = channel bottom width, cm d = depth of channel, cm h = head, cm v = flow velocity, cm/sec
¤
Refer to Operation \ Flow Calculation.
7ML19985AB01 OCM III 84
Page 84
TRAPEZOIDAL AREA X VELOCITY
transducer *
* The transducer must be above the maximum head by at least the blanking value, P47.
7ML19985AB01 OCM III 85
Page 85
MODIFIED TRAPEZOIDAL AREA X VELOCITY, P3 = 15
‘U’ parameters listed * ‘U’ parameters calculated **
U0 = channel top width B U3 = area (h)
U1 = channel base width b
U2 = transition height ht
*obtain from manufacturer’s specifications.
**
calculated by OCM -3. May be viewed by accessing ‘U’ parameter.
Reference
ABSOLUTE CALCULATION, P4 = 0¤
For flows that can be calculated by the equation:
q = 1/1000 x (b + mh) x v for h ≤ d
q = 1/1000 x ((b + md)d + (B(h - d))) x v for h ≥ d
m = (B - b)/d
where : q = flow rate, l/s d = height of transition, cm
B = channel top width, cm h = head, cm b = channel base width, cm v = flow velocity, cm/sec
RATIOMETRIC CALCULATION, P4 = 1¤
For flows that can be calculated by the equation:
q = q
x A/A
cal
cal
x v/v
cal
for h d: A = (b + mh) x h
A
= (b + mh
cal
cal
) x h
cal
for h d: A = (b + md) x d + B(h - d)
A
= (b + md) x d + B(h
cal
cal
- d)
m = (B - b)/d
where : q = flow rate d = depth of channel
q
= flow rate at h
cal
cal
h = head B = channel top width, cm v = flow velocity, cm/sec b = channel base width, cm
¤
Refer to Operation \ Flow Calculation.
7ML19985AB01 OCM III 86
Page 86
MODIFIED TRAPEZOIDAL AREA X VELOCITY
transducer *
* The transducer must be above the maximum head by at least the blanking value, P47.
7ML19985AB01 OCM III 87
Page 87
U-CHANNEL AREA X VELOCITY, P3 = 16
‘U’ parameters required * ‘U’ parameters calculated **
U0 = base diameter D U1 = area (h)
*
obtain from manufacturer’s specifications.
**
calculated by OCM -3. May be viewed by accessing ‘U’ parameter.
7ML19985AB01 OCM III 88
Page 88
U-CHANNEL AREA x VELOCITY
transducer *
* The transducer must be above the maximum head by at least the blanking value, P47.
7ML19985AB01 OCM III 89
Page 89
CIRCULAR AREA X VELOCITY, P3 = 17
‘U’ parameters listed * ‘U’ parameters calculated **
U0 = conduit diameter ID U1 = area (h)
*
obtain from manufacturer’s specifications.
**
calculated by OCM -3. May be viewed by accessing ‘U’ parameter.
7ML19985AB01 OCM III 90
Page 90
CIRCULAR AREA X VELOCITY
transducer
*
**
h
* This dimension should be at least 15 cm (6") shorter than the blanking value, P47.
** The transducer must be above the maximum head by at least the blanking value, P47.
7ML19985AB01 OCM III 91
Page 91
GULL-WING AREA X VELOCITY, P3 = 18
‘U’ parameters required * ‘U’ parameters calculated **
U0 = channel base width b U4 = area (h)
U1 = lower angle alpha (α)
U2 = upper angle beta (β)
U3 = transition height ht
*
obtain from manufacturer’s specifications.
**
calculated by OCM -3. May be viewed by accessing ‘U’ parameter.
7ML19985AB01 OCM III 92
Page 92
GULL WING AREA X VELOCITY
transducer *
* The transducer must be above the maximum head by at least the blanking value, P47.
7ML19985AB01 OCM III 93
V
Page 93
EGG-SHAPED AREA X VELOCITY, P3 = 19
‘U’ parameters listed * ‘U’ parameters calculated **
U0 = top radius R U3 = area (h)
U1 = bottom radius r
U2 = axial displacement d
*
obtain from manufacturer’s specifications.
**
calculated by OCM -3. May be viewed by accessing ‘U’ parameter.
Reference
ABSOLUTE CALCULATION, P4 = 0¤
For flows that can be calculated by the equation:
q = 1/1000 x A x v
where : q = flow rate in l/sec
v = flow velocity in cm/sec
RATIOMETRIC CALCULATION, P4 = 1¤
For flows that can be calculated by the equation:
q = q
x A/A
cal
cal
x v/v
cal
where : q = flow rate
q
= flow rate at h
cal
cal
A = cross sectional area of flow A
= cross sectional area of flow at h
cal
v = flow velocity
¤
Refer to Operation \ Flow Calculation.
cal
7ML19985AB01 OCM III 94
Page 94
EGG-SHAPED AREA X VELOCITY
transducer *
standpipe **
* This dimension should be at least 15 cm (6") shorter than the blanking value, P47.
** The transducer must be above the maximum head by at least the blanking value, P47.
7ML19985AB01 OCM III 95
Page 95
UNIVERSAL AREA X VELOCITY, P3 = 20
Arbitrary area is typically used when the primary element and/or its flow do not fit any of the primary elements covered by P3. There is no user difference between absolute and ratiometric calculations P4.
The flow curve is characterized by entering the head (A
) and area (A
even
odd
) ordinates for the number of data points (n, 4 to 16) over the flow range. The first point (A0,A1) generally being at 0 head and the last point (A
2n-2,A2n-1
) generally being
at maximum head .
‘U’ parameters required * ‘U’ parameters calculated **
U0 = number of data points
A
= head
even
A
= area
odd
*
obtain from manufacturer’s specifications.
**
calculated by OCM -3. May be viewed by accessing ‘U’ parameter.
e.g. typical open channel
(n, 4 to 16)
U1 = area (h)
transducer *
* The transducer must be above the maximum head by at least the blanking value, P47.
7ML19985AB01 OCM III 96
Page 96
UNIVERSAL AREA X VELOCITY
odd
A
Area
U0 = 8
A0 = 0 head, point 1
A1 = 0.0 area, point 1
A2 = 0.05 head, point 2
A3 = 0.03 area, point 2
A4 = 0.1 head, point 3
A5 = 0.06 area, point 3
A6 = 0.15 head, point 4
A7 = 0.09 area, point 4
A8 = 0.25 head, point 5
A9 = 0.18 area, point 5
A10 = 0.45 head, point 6
A11 = 0.35 area, point 6
A8 = 0.70 head, point 7
A9 = 0.59 area, point 7
A8 = 1.00 head, point 8
A9 = 0.89 area, point 8
Head
A
even
For best accuracy concentrate data points where changes in flow are the greatest.
7ML19985AB01 OCM III 97
Page 97
7ML19985AB01 OCM III 98
Page 98
MAINTENANCE
The OCM-3 requires very little maintenance due to its solid-state circuitry. However, a program of periodic preventative maintenance should be initiated. This should include regula r inspection, general cleaning, overall system performance checks and standard good housekeeping practices.
A periodic inspection of the transducer is recommended, at which time any build-up of material on the face should be removed.
The enclosure should be cleaned using a vacuum cleane r and a clean, dry brush.
For battery replacement refer to Installation / Installing the Memory Back-up Battery.
7ML19985AB01 OCM III 99
Page 99
Error Code Listing
1 number underflow
2 number overflow
3 divide error
4 bad argument
5 invalid parameter
6 system is locked
7 head exceeds BS-3680 spec
ERROR CODES
8 must use ratiometric
9 invalid angle size
10 invalid selection
11 value is view-only
12 characterizer in use
13 feature not available
14 need whole number
15 invalid date
16 invalid time
20 can’t zero auxiliary device
21 b must be greater than R-r
7ML19985AB01 OCM III 100
Page 100
COMMUNICATIONS
The OCM-3 provides serial communication either through Milltronics proprietary bipolar current loop or industry standard RS-232. Communication can be used to provide a video or paper printout of OCM activity. It can also be used to provide remote programming and retrieval of the data log, from devices such as computers and PLCs.
When using the bipolar current loop, communication runs of up to 1,500 m can be achieved, as opposed to the limited runs of 15 m using RS-232. By terminating the bipolar current loop with a Milltronics CVCC, the communication format is then converted to RS-232.
OCM - 3 site number (P39 )
RS-232
serial printer
customer’s computer *
bipolar current loop
CVCC **
customer’s computer *
optional parallel printer
* Milltronics OCM -3 Utilities Software available
** provides conversion to RS -232 or 422
7ML19985AB01 OCM III 101
Loading...