Safety Guidelines: Warning notices must be observed to ensure personal safety as well as that of
others, and to protect the product and the connected equipment. These warning notices are
accompanied by a clarification of the level of caution to be observed.
Qualified Personnel: This device/system may only be set up and operated in conjunction with this
manual. Qualified personnel are only authorized to install and operate this equipment in accordance with
established safety practices and standards.
Unit Repair and Excluded Liability:
• The user is responsible for all changes and repairs made to the device by the user or the user’s
agent.
• All new components are to be provided by Siemens Milltronics Process Instruments Inc.
• Restrict repair to faulty components only.
• Do not reuse faulty components.
Warning: This product can only function properly and safely if it is correctly transported, stored,
installed, set up, operated, and maintained.
Note: Always use product in accordance with specifications.
Copyright Siemens Milltronics Process
Disclaimer of Liability
Instruments Inc. 2005. All Rights Reserved
This document is available in bound version and in
electronic version. We encourage users to purchase
authorized bound manuals, or to view electronic versions
as designed and authored by Siemens Milltronics Process
Instruments Inc. Siemens Milltronics Process Instruments
Inc. will not be responsible for the contents of partial or
whole reproductions of either bound or electronic
versions.
While we have verified the contents of this
manual for agreement with the
instrumentation described, variations
remain possible. Thus we cannot
guarantee full agreement. The contents of
this manual are regularly reviewed and
corrections are included in subsequent
editions. We welcome all suggestions for
improvement.
Technical data subject to change.
MILLTRONICS®is a registered trademark of Siemens Milltronics Process Instruments Inc.
Contact SMPI Technical Publications at the following add r ess:
Technical Publications
Siemens Milltronics Process Instruments Inc.
1954 Technology Drive, P.O. Box 4225
Peterborough, Ontario, Canada, K9J 7B1
Email: techpubs.smpi@siemens.com
• For a selection of Siemens Milltronics level measurement manuals, go to:
www. siemens.com/processautomation. Under Process Instrumentation, select
Measurement
• For a selection of Siemens Milltronics weighing manuals, go to:
www. siemens.com/processautomation. Under Weighing Technology, select
Weighing Systems
and then go to the manual archive listed under the product family.
and then go to the manual archive listed under the product family.
BS-3680 Round Nose Horizontal Crest Weir, P3 = 260
BS-3680 Trapezoidal Flume, P3 = 362
BS-3680 U - Flume, P3 = 464
BS-3680 Finite Crest Weir, P3 = 566
BS-3680 Thin Plate Rectangular Weir, P3 = 668
BS-3680 Thin Plate V-Notch Weir, P3 = 770
Rectangular Weir (Contracted), P3 = 872
Round Pipe, P3 = 974
Palmer-Bowlus Flume, P3 = 1076
H - Flume, P3 = 1178
Universal Head vs. Flow, P3 =1280
Rectangular Area x Velocity, P3 = 1382
Trapezoidal Area x Velocity, P3 =1484
Modified Trapezoidal Area x Velocity, P3 = 1586
U Channel Area x Velocity, P3 = 1688
Circular Area x Velocity, P3 = 1790
Gull-Wing Area x Velocity, P3 = 1892
Egg-Shaped Area x Velocity, P3 =1994
Universal Area x Velocity, P3 = 2096
APPENDICES
Maintenance99
Error Codes100
Communications101
7ML19985AB01OCM III5
Page 6
7ML19985AB01OCM III6
Page 7
ABOUT THIS ...
ABOUT THIS MANUAL
Although the OCM-3 is very ‘approachable’ due its dialogue capabilities and intuitive
operation, the user should be familiar with this manual. This manual provides the user
with the necessary information required to install, start up and operate the OCM-3.
As the OCM-3 prompts the user with specific messages in a step-by-step fashion
during programming, the Start Up section serves essentially to compliment the
OCM-3. Start Up provides the user with instructions on the use of the programmer
and an overview of the programming requirements.
The ‘D’, ‘F’, ‘P’ and ‘U’ parameters listed in the Parameters section provide a quick
reference of the available programming and display parameters and their options. The
‘U’ parameter listing also provides mathematical and graphical details as a reference
to assist the user in programming the OCM-3 to the primary element being used. The
user is urged to rely on the manufacturer’s specification for obtaining and identifying
the primary element to which the OCM-3 is being applied.
In short,
If you want to know about
the product About This . . .
getting startedInstallation
how it worksOperation
Read
Specifications
Start Up
Parameters
Appendices
ABOUT THE OCM-3
The OCM-3 is to be used only in the manner
outlined in this instruction manual.
The Milltronics OCM-3, Open Channel Meter, is an electronic instrument designed to
measure flow in open channels. It is housed in a polycarbonate enclosure and comes
with a removable programmer. As a system, it is used in conjunction with a remote
ultrasonic transducer (or auxiliary head measurement device) and a temperature
sensor.
The OCM-3 transmits a pulse signal to the transducer which is then emitted as
ultrasonic pulses. The pulses echo off the water surface and are then sensed by the
transducer. The time for a pulse to echo back from the water surface is temperature
compensated and converted into a measurement of head.
7ML19985AB01OCM III7
Page 8
The OCM-3 converts the head measurement into flow rate, but also provides a
velocity sensor input for applications where a flow velocity measurement is required to
perform the flow calculation. The flow rate is totalized and stored in a comprehensive
data log to provide detailed flow analysis.
Programming of the OCM-3 allows the operator to select the flow calculation specific
to the primary measuring device (flume, weir or pipe). Special emphasis has been
placed on providing the most accurate flow calculations possible. To this end, specific
routines have been written to comply with the British Standards Institute’s
Specifications BS-3680. These routines calculate correction factors taking into
account second order effects such as approach velocity and boundary layer. In the
event that flow measurement is not covered by one of the flow calculations provided,
the OCM-3 can be programmed for flow measurement using one of the universal
flow calculations.
The OCM-3 provides serial communication for remote programming, data log retrieval
and print out for devices such as computers, PLCs and printers. Milltronics provides a
standard utilities software package for OCM-3 programming, remote display and data
retrieval. However, the user is not limited to the software provided. The user can
develop his own software program to perform tasks suited to his specific nee ds.
The OCM-3 features:
✓ multi field illuminated LCD, for ‘Flow and Total’ and ‘Relay Status’ display
✓ 0 or 4 to 20 mA output
✓ three multipurpose relays, including remote totalization
✓ 1 to 24 months data log, subject to logging rate
✓ extensive serial communication, including RS-232
✓ removable infra-red programmer
✓ AC and DC (bi-current) operation.
7ML19985AB01OCM III8
Page 9
SPECIFICATIONS
Power:» dc supply: » 9 to 30 V DC, 8 W max
» ac supply:» 100/115/200/230 V ac ± 15%, 50/60 Hz,
20 VA max
Environmental:» location » indoor /outdoor
» altitude: » 2000 m max
» ambient temperature » – 20 to 50 °C (–5 to 122 °F)
» relative humidity » suitable for outdoor (Type 4X/Nema 4X
» installation category » II
» pollution degree » 4
Memory
back-up: » 3 V lithium battery (NEDA 5003LC or equivalent)
» operating life 1 year
» ‘SuperCap’ capacitor for back-up
during battery replacement
Range:» 0.3 m min to 1.2 m max ( 1 to 4 ft)
and / or
IP65 enclosure)
0.6 m min to 3 m max (2 to 10 ft)
Resolution: » 0.2 mm (0.007")
Accuracy:» ±1 mm/m, calculated error less than 0.02%
Temperature
Compensation:» external sensor to compensate over
*Note: The XRS-5 must be used with the TS-2 external temperature sensor when
operating with the OCM-3.
Velocity Input:» Belden 8760 or equivalent
7ML19985AB01OCM III11
Page 12
Auxiliary Input:» Belden 8760 or equivalent
24 V Output:» Belden 8760
COMMUNICATION SOFTWARE
Milltronics Utilities Software on standard PC floppy disk for DOS 3.1 and up.
7ML19985AB01OCM III12
Page 13
INSTALLATION
Installation shall only be performed by qualified personnel
and in accordance with local governing regulations.
INSTALLING THE OCM-3
The OCM-3 should be mounted in a clean, dry area that is: within the ambient
temperature range and suitable for the specified enclosure. The front cover should be
accessible for programming and viewing.
It is advisable to keep the OCM-3 away from high voltage or current runs, contactors
and SCR control drives.
Do not mount the OCM-3 in direct sunlight without the use of a sun shield.
This product is susceptible to electrostatic shock.
Follow proper grounding procedures.
OUTLINE AND MOUNTING
16 mm
(0.6")
209 mm
(8.2")
172 mm
(6.8")
267 mm
(10.5")
lid screws
(6 places)
285 mm
(11.2")
106 mm
(4.2")
91 mm
(3.6")
programmer
suitable location for
conduit entrances
Milltronics reccomends using a punch for making
holes in enclosure. Use suitable cable glands to
maintain ingress rating.
Non metallic enclosure does not provide grounding between connections.
13OCM III7ML19985AB01
mounting holes
(accessed under
lid 4.3 mm (0.17")
dia.,4 places
customer mounting
lid
enclosure
screw
Use grounding type bushings and jumpers.
Page 14
OCM-3 LAYOUT
board A
display
board
board B
All field wiring must have insulation suitable for at least 250 V.
Hazardous voltage present on transducer terminals during operation.
dc terminals shall be supplied from SELV source in accordance
with IEC 1010-1 Annex H.
Relay contact terminals are for use with equipment having no accessible
live parts and wiring having insulation suitable for at least 250 V.
The maximum allowable working voltage between
adjacent relay contacts shall be 250 V.
14OCM III7ML19985AB01
Page 15
SYSTEM DIAGRAM
OCM-3
mA output
relay output
auxiliary input
velocity input
Milltronics transducer,
see Specifications
Milltronics TS- 2,
temperature sensor
customer device
customer alarm,
pump or control
device
customer device
customer device
bi-polar current
(Milltronics communication)
Maximum syste m ca pability. Not all components or their maximum quantity
may be required.
15OCM III7ML19985AB01
RS-232
customer device
Milltronics CVCC
98/03/05
Page 16
INSTALLING THE TRANSDUCER
Max cable run 183 m (600 ft) of
RG-62U or equivalent. Cable must
be run in a grounded metal conduit
with no other cabling (except
Temp. Sensor cable).
Ground shield at OCM-3 only.
Insulate shield at junctions to
prevent inadvertent grounding.
Basic Wiring – Transducer
Hazardous voltage present on transducer terminals during operation.
Note: When using the XRS-5 transducer with the OCM-3, use the TS-2 external
temperature sensor. The internal temperature sensor in the XRS-5 cannot be used.
INSTALLING THE TEMPERATURE SENSOR
In order to compensate for uniform
temperature change in the air
between the transducer and the flow
surface, the temperature sensor
must be connected to the OCM-3.
Maximum cable run 183 m (600 ft) of
Beldon 8760, 1 pair shielded/twisted,
18 AWG or equivalent.
Temperature sensor cable can be
run with the transducer cable in a
grounded metal conduit.
Ground shield at OCM-3 only.
Basic Wiring – Temperature Sensor
16OCM III7ML19985AB01
Page 17
mA OUTPUT
RELAYS
isolated 0 or 4 to 20 mA output (P26) into 1 KΩ loa d maximum.
Wiring should conform to standard instrumentation practices.
Ground shield at OCM-3 only.
relays shown in de-energized state,
contacts rated at 5 A at 250 V
non-inductive.
n.c. com n. o. n.c. com n. o. n. c. com n. o.
All relays are certified for use in equipment where the short circuit capacity of the
circuits in which they are connected is limited by fuses having ratings not exceeding
the rating of the relays.
17OCM III7ML19985AB01
Page 18
SYNCHRONIZATION
Where two to a maximum of twelve transducers will be sharing a common conduit the
OCM-3s should be synchronized. In order to synchronize OCM-3s:
» remove jumper J1 on board A on all but one OCM-3
» interconnect the SYNC terminal (TB1-20) of all OCM-3s. Insure that
all OCM-3s share a common ground (TB1-34).
18OCM III7ML19985AB01
Page 19
POWER CONNECTIONS
The OCM-3 power supply accepts 100, 115, 200 or 230 V ac per switch SW1
(board B) selection and 9 to 30 V dc.
The OCM-3 operates either under ac or dc power, or both ac and dc live
simultaneously. If both ac and dc power are live, the OCM-3 normally draws power
from the ac supply. In the event that the ac supply fails, the OCM-3 then draws power
from the dc supply.
AC POWER
*
100/115/200/230 V ac, 50/60 Hz,
select voltage via switch on board B
* switch shown in
‘OFF’ position,
select appropriate
voltage.
The equipment must be protected by a 15 A fuse or
circuit breaker in the building installation.
A circuit breaker or switch in the building installation, marked
as the disconnect switch, shall be in close proximity to
the equipment and within easy reach of the operator.
DC POWER
19OCM III7ML19985AB01
nega tive dc input (T B1 - 24) is
9 to 30 Volt
dc input
tied to ground (TB1-34)
dc terminals shall be supplied from SELV source in accordance
with IEC 1010-1 Annex H.
Page 20
INSTALLING THE MEMORY BACK-UP BATTERY
Disconnect power before installing or replacing the battery.
Do not install the memory back-up
battery until the OCM-3 is to be used.
The unit is supplied with one battery
package. Remove the battery from
the package and insert it into the
battery socket.
Refer to Operation \ Memory.
The memory battery, B1 (see Specifications) should be replaced yearly to insure
memory back up during lengthy power outages. An on board capacitor provides
one hour of memory retention in order to preserve the memory while the ba ttery
is being changed.
COMMUNICATING VIA COMPUTER
Refer to Communication.
INSTALLING THE PROGRAMMER
To program the OCM-3 via the Programmer, it must be placed into the front cover
recess of the OCM-3. The back of the Programmer has a magnetic plate which will
hold the programmer in place. It can be removed when programming is completed.
20OCM III7ML19985AB01
Page 21
START UP
GENERAL
For the initial start up, it is advisable to use the programmer for programming the
OCM-3. The programmer transmits a coded infrared signal each time a key is pressed.
The OCM-3 is designed to automatically scroll through the ‘A’, ‘D’, ‘F’, ‘P’ and ‘U’
parameters in a structured sequence. The scrolling is interactive in that, depending on
the option chosen for a given parameter, subsequent parameters may be skipped or
modified. The user is thus prompted to satisfy only the parameters which are available
to him for the application he has chosen.
KEYPAD
numeric
entries with
decimal point
access to ‘D’, ‘F’,
‘P’ and ‘U’
parameters
negative
access to ‘A’ parameters
/ initiate s a printout while
viewing ‘Flow and T otal’
scrolls through selected
parameter options
scrolls
Forward
the parameters / enters
content of entry field
scrolls
Backward
parameters / clears content of entry field
through
through the
7ML19985AB01OCM III21
Page 22
LEGEND
Press the associated programmer key:
Display shown on OCM -3:
Programmer key:
INITIAL START UP
After installation procedures have been completed, the OCM-3 may be powered up.
Upon initial powering up, the unit momentarily displays:
and then scrolls through the available languages:
The OCM-3 is asking which language you prefer to communicate in!
0
(0)language
F0enter security code
< - - -
7ML19985AB01OCM III22
English
English language
selected
advance to ‘F0’
Page 23
828
1
72
factory set security code
2.71828 must be entered
P0language
0English
P1dimensional units
0centimeters
P0language
0English
if the wrong language
was selected, it may
be changed here
continue programming by
entering the desired options
and advancing until the
scroll returns to ‘P0’. It is
then assumed that the
user has entered all the
required parameters.
For optimum calibration accuracy, an ‘F13’ should be performed prior to accessing
‘F2’, the normal operating mode.
3
1
F13 auto zero calibration
enter the current head. The
OCM-3 calculates ‘P46’ and
automatically enters the value.
e.g. 1 6 0
016
F13 auto zero calibration
160
F13 auto zero calibration
0completed
7ML19985AB01OCM III23
Page 24
If data logging is desired, the time and date must be set.
4
F424-hr. time
e.g. 1141
4
1
1
1
F424-hr. time
1141
F4 24-hr. time
11:41:00 enter new time
11: 41 a.m.
seconds are always
assumed to be 00
time is displayed in
hh:mm:ss
,
F5 (ddmmyyyy) date
e.g. 12101492October 12, 1492
01
4
92112
F5 (ddmmyyyy) date
12/10/1492 enter new date
The start up procedure is now complete. Enter ‘F2’ to place the OCM-3 in the normal
operating mode.
2
Note: To save parameter values, return to RUN mode (F2) after programming.
The OCM-3 now displays the flow rate and total. Refer to Operation \ Display
7ML19985AB01OCM III24
Page 25
FUNDAMENTAL CHECKS
For accurate determination of flowrate, accurate head measurement is essential.
Check the following and correct if necessary.
» check D5 for correct temperature at transducer location.
» check D9 for corre ct distance from transducer to head.
» check D0 for accurate head measurement.
7ML19985AB01OCM III25
Page 26
7ML19985AB01OCM III26
Page 27
OPERATION
Upon power up, the transducer is fired periodically as set by P36. A long interval
between measurements may be desirable in order to conserve power* when
operating the OCM-3 from a DC source of limited capacity.
The echo is processed to determine the head (D0). The flow rate (D1) is calculated by
the OCM-3 as a mathematical function (P3 and P4) of head or a function of head and
velocity (P42). The flow rate is then integrated to yield the totalized flow (D2). The
‘Flow’ and ‘Total’ fields which are displayed during the normal running mode (F2) are
also continuously updated.
Viewing or changing the content of a parameter (except F1, emulation) is done
without disturbing the acquisition, processing or logging of flow data (see \ Security).
*
restricted usage of display lighting (P14), relays (P15, 18 & 21), mA
output and communications will also conserve power.
MEMORY
During a power interruption, the memory back up will hold the programming, the log
and the totalizer values, and run the clock. The memory battery (B1) provides up to
one year of memory retention (see Appendices \ Maintenance).
Note: To save parameter values, return to RUN mode (F2) after programming.
SECURITY
The content of all ‘A’, ‘D’, ‘F’, ‘P’ and ‘U’ parameters can be viewed without having to
satisfy the security parameter, F0. However if it is desired to change the content of
any of these parameters, the security parameter must be satisfied (except for
resetting the running min/max displays, parameters D3/D4 and D6/D7).
Once security has been satisfied, a ccess continues for 5 minutes after the last key is
pressed or until F2 is re-entered.
The security code may be changed from its factory set value, 2.71828, by entering a
new value into F10. It is imperative that the new value be recorded, as the code can
not be viewed. If the code is lost, consult Milltronics.
UNITS
Programming of the OCM-3 involves setting the units of measure:
» P1 linear and velocity
» P2 temperature
» P5 flow rate and volume
If the units are changed during the course of operation, the change will be effected
through all associated parameters and displays and will rescale flow and total data
stored in the logs.
7ML19985AB01OCM III27
Page 28
FLOW CALCULATION
Absolute vs. ratiome tric
The OCM-3 can be programmed to use eithe r of two methods (P4) for calculating flow
from the head measurement: absolute or ratiometric. The result is the same
regardless of the method used. The principal difference is the information that must
be entered in orde r for the OCM-3 to carry out the calculation. The user’s choice of
method may ultimately be based upon the information which is at hand. Refer to U
parameters for the primary element selected for a listing of the information required.
For the ratiometric method, it is usually sufficient that the user know the flow rate
) which occurs at maximum head (h
(Q
cal
On the other hand, absolute calculations require that the user enter information such
as: the physical dimensions of the primary element and the constant relating to units
of measure for both linear dimensions and flow rates.
e.g.
the general formula for flow through a single exponent primary element is:
cal
).
Q = KH
x
the specific formula for flow through a 45° V-notch weir is:
cfs = 1.03H
2.5
thus:Q = flow in cubic fe et per second
K = constant of 1.03
H = head in feet
The absolute method is not applicable to the following:
Palmer Bowlus flume
H flume
DISPLAY
The normal display during operation is the Flow and Total Display (F 2).
flow rate field
totalizer fie ld
7ML19985AB01OCM III28
relay / "no echo" field
status field
Page 29
Flow Rate Field
Totalizer Field
flow rate
units, P5
total
multiplier, P32
Relay / No Echo Field
relay identification
under loss of echo
condition, "NO
ECHO" will
alternately flash
Status Field
relay status : 0 = relay de-energized
1 = relay energized
* = alarm state (indicated when
flashing)
The OCM-3 provides illumination for the LCD for easier viewing of the display.
Illumination can be set (P14) to be normally on or off, or automatic. When automatic is
selected, the lighting will automatically go on when keypad activity is sensed and then
extinguish after 15 seconds of inactivity.
For battery operation, set display lighting to off or auto.
DAMPING
The OCM-3 provides two separate damping functions: reading and mA output. Zero
or no damping allows fastest response while high or 100% provides the slowest
response. The damping is usually set to provide a reliable response without
sacrificing stability.
The reading damping, P13, dampens only the flow rate reading of the ‘Flow and Total’
display F2. The damping selections are: off, low, medium and high. Relay functions
associated with flow rate respond to the dampened reading values.
mA output damping, P27, dampens the change in the mA output. The parameter entry
is in seconds for spanning the 0 to 100% of the mA range selected (P26). Displays
and relay functions associated with the mA output respond to its
dampened value.
7ML19985AB01OCM III29
Page 30
RELAYS
Three on board multipurpose relays are provided by the OCM-3. P15, 18 and 21 set
the respective functions for relays 1, 2 and 3. Depending on the function selected,
these parameters determine the need and configuration of the subsequent relay
control parameters, P16, 17 (relay 1); P19, 20 (relay 2) and P22, 23 (relay 3).
If the relay is to function as a driver for a remote totalizer or as a flow sampler contact,
the totalizer multiplier (P32) will be factored by the setpoint . Note that parameters
P16, P19, and P22 will default to zero. When a relay is set to totalizer (P32), you must
have the applicable parameter (P16 for relay 1, P19 for relay 2, or P22 for relay 3) set
to something other than zero (normally 1).
Example: For relay 1
Re la y totalizer factor =
totalizer factor (P32)
relay 1 setpoint (P16)
100 (P32=5)
=
2 (P16)
= 50 units/pulse
The status of each relay is shown in the display. Refer to \ Flow and Total Display.
For battery operation, have relays energizing on alarm.
mA OUTPUT
The OCM-3 provides a mA output (TB1-4/5) which can be assigned (P24) to
represent the measurement of flow, head, velocity or temperature. The associated
scaling, P25, is factory set to a value of ‘0’. This provides normal scaling with respect
to the assigned measurement.
Normal scaling for representation of flow, head or velocity is:
» 0 or 4 mA = 0
» 20 mA= maximum measurement value for: » P6
» P7: maximum head
Normal scaling for representation of temperature is:
» 0 or 4 mA = – 40 °C
» 20 mA= 60 °C
If custom scaling is required, the 20 mA corresponding value (other than 0) can be
entered into P25. The range (0 to 20 or 4 to 20 mA) and damping (see Damping) are
set via P26 and P27 respectively.
7ML19985AB01OCM III30
*
: flow rate
at maximum head
» P10: velocity
at maximum head
Page 31
The mA function can be overridden for test purposes by setting the desired mA value
into F3. When the value is entered, the mA output will go to that value. When F3 is
exited, the mA output will revert to normal operation. Also, see \ Emulation Mode.
*In the case of absolute calculations (P4=0),
P6 is calculated by the OCM-3.
FAIL-SAFE
In the event of an echo loss, the fail-safe timer will begin counting. If the echo loss
duration surpasses that of the time set (P29), a ‘
No Echo
’ alert will be displayed in the
Status field (see \ Display). The mA output will respond (P30) by either holding the last
value or immediately going to a predetermined value (P31). The head and derived flow
will hold their last value and totalization and logging will continue, based on that value.
Upon resumption of a valid echo, the mA output will return to a value corresponding to
the present value of the measurement assigned, at the mA damping rate (P27).
FLOW RATE AND TOTALIZING
Flow rate
Calculation of the flow rate is ongoing. It is normally viewed under the Flow and Total
display (F2) with the decimal point set per P33. It can also be viewed under D1 as the
raw flow calculation. Data on the running minimum and maximum flows that have
occurred since the last reset can be viewed in two ways:
» F7 gives the running min/max flows and their time and date of occurrence since
the last reset. F7 is rese t by F8 but only after satisfying the security pa rameter F0.
» D3/D4 give the respective running min/max flow data , only, that have occurred
since they were last reset. D3/D4 are reset simultaneously by entering 0 into
either D3 or D4. D3 and D4 will then adopt the current flow rate and track the
running min/max values from that point on. The security parameter (F0) does
not need to be satisfied in order to reset D3/D4.
Flow data specific to a particular time and date can be viewed under the data log F14
(see \ Logging).
Totalizing
Totalizing of the calculated flow is ongoing. It is normally viewed under the Flow and
Total display (F2).
An auxiliary totalizer (D2) is provided for operator usage and is intended for short term
totalizing to a maximum count of 999999. It can be reset or preset independently of
the F2 totalizer after satisfying the security parameter (F0).
In order to adjust the rate of filling of the totalizer, the totalizer multiplier (P32) can be
set to an appropriate value. The totalizer can be reset via F11. Totalizing that is
specific to the time and date can be viewed under the data log F14.
The OCM-3 can be programmed to operate a remote totalizer by assigning any of the
relays (P15, 18 or 21) to act as a totalizer contact*. Under this function, the maximum
rate of contact closure is 2/sec with a closure duration of 200 msec**.
The totalizer count is set by the relay setpoint parameter (P16, 19 or 22 respectively).
*
**
Typically the totalizer should be set for 300 to 3000 counts per day at maximum flow.
7ML19985AB01OCM III31
Page 32
Under low flow conditions, a cut-off head (P45) can be entered to avoid totalizing
flows occurring at or below the flow corresponding to the cut-off head.
LOGGING
The OCM-3 provides an extensive logging feature which can be viewed on the local
display or retrieved via the serial communication link. The logging rate (P39) can be
fixed or variable. The latter being useful in conserving logging space. The condition for
variable logging is determined when selecting the logging rate.
Variable logging rate conditions are catagorized as : rate of change of flow, percent of
maximum flow or percent of maximum head. Logging occurs at the normal (slower)
rate while the condition is less than the setpoint (P40). If the condition exceeds the log
rapid setpoint, the rapid rate of logging takes effect until the condition falls below the
log normal setpoint (P41).
The associated setpoint units are : % change of maximum flowrate per minute, % of
maximum flowrate and % of maximum head, respectively. The setpoints represent the
absolute value of the rate of change; that is, for either increasing or decreasing
flowrate. The OCM-3 does not recognize negative entries into P-40 and P-41.
Flow data is logged in 1/2 % increments from 0 to 110 % of maximum flow. Flows
above 110 % are logged as 110 %. Truncation of flows to 110 % does not apply to
daily totalization.
Log Capacity vs Rates
ratecapacity
1 min31 days
53 months
159 months
301 year
601.5 years
24 hr2 years
e.g.15 / 59 months max / 3 months min
Once the log is filled, the old data will be successively written ove r with the new
data being logged.
The log can be examined via F14. Viewing of the log is done by task and by method.
The viewing tasks are: daily flow totals, flow rates and min-max flow data for flow or
temperature. The viewing methods are: by first entry, by last entry and by specified
date. The scrolling keys are used to maneuver through the tasks, methods and
time of day.
7ML19985AB01OCM III32
Page 33
Viewing the data log
The day totalizer (F14) does not use the master totalizer multiplier (P32). It is possible
that the daily total overflows. In such a case the display will show +++.++.
7ML19985AB01OCM III33
Page 34
BLANKING
Blanking is used to ignore the zone in front of the transducer where ringing or other
false echo is at a level that interferes with the processing of the true echo. The
minimum blanking is factory set, but can be overridden by entering the desired
distance into P47.
Ringing is the inherent nature of the transducer mass to continue vibrating after the
transducer has been fired. Ringing decays to acceptable levels in the order of
milliseconds. Excessive cold or over tightening of the transducer mounting may
increase the ring time such that it appears as an echo during the receive cycle. This is
usually indicated by an incorrect high head reading. Excessive ring time may be
overcome by increasing the blanking.
TEMPERATURE
The temperature as currently registered by the temperature se nsor is viewed under
D5. Data on the running minimum and maximum temperatures that have occurred
since the last reset can be viewed in several ways:
F7 gives the running min/max temperatures and their time and date of occurrence
since the last reset. F7 is reset by F8 but only after satisfying the security
parameter F0.
D6/D7 give the respective running min/max temperature data, only, that have
occurred since they were last reset. D6 is reset by entering a value lower than D5,
and D7 is reset by entering a value larger than D5. D6 and D7 will then adopt the
current temperature value and track the min/max values from that point on. The
security parameter F0 does not need to be satisfied in order to reset D6 or D7.
Temperature data specific to the time and date can be viewed under the data log F14
(see \ Logging).
D14 indicates the resistance of the temperature sensor corresponding to the
temperature shown in D5.
TIME AND DATE
If the data logging features of the OCM-3 are to be used, the time (F4) and date (F5)
must be set. The day starts at 00:00:00 and ends at 23:59:59.
Adjusting the Time
If the clock time is advanced beyond the next anticipated logging time, the entry for
each missed logging time is filled with a code which indicates that the system was not
able to make entries at those times.
The daily total will be reduced proportional to the amount of time the day
was shortened.
If the clock time is set back beyond the preceding logging time, the previously logged
date will be written over with new data as the logging proceeds.
7ML19985AB01OCM III34
Page 35
The daily total will be increased proportional to the amount of time the day was
lengthened.
Adjusting the Date
If the calendar is reset, the OCM-3 will adjust the log dates accordingly, taking into
account leap years and days per month.
EMULATION MODE
The flow calculation (P3/ P4) can be checked for accuracy by using the emulation
parameter F1. The head is entered and the corresponding flow is displayed. This
function is useful when troubleshooting discrepancies between the OCM-3 calculation
and the expected flow.
Relays assigned to functions associated with the emulation parameter respond to the
emulated flows.
The mA output does not track the emulated flows when P28 (mA output emulation) =
0. However, if it is required to do so, then the emulator parameter should be set to 1.
RESET
The following resets can only be e xecuted after satisfying the security access, F0.
Cold Start
If it is desired to reset all parameters, logs and totalizers to their factory setting, this is
done by forcing a cold start, F12 .
Master Totalizer
If it is desired to reset the master totalizer (F2), this is done by parame ter F11.
Data Log
If it is desired to reset the data log (F14), this is done by parameter F15.
Min/Max Log
If it is desired to reset the min/max log (F7), this is done by parameter F8.
7ML19985AB01OCM III35
Page 36
FLOW VELOCITY INPUT
In some applications, the flow calculation for the chosen primary element requires a
velocity input. In this type of application, the transducer measurement is used to
calculate the cross sectional area of the flow. By multiplying the area with the distance
per time units of velocity, the volume per time units of flow are calculated. The
calculate d velocity can be viewed via D8.
The 0% and 100% limits of the velocity input must be scaled using parameters
P8 and P9.
» se le ct P8
» enter the voltage corresponding to zero velocity
» se le ct P9
» enter the velocity corresponding to 5 V
e.g. If the velocity sensor output is 1 V per m/ sec and the output is
scaled for 7 V at 100% velocity (7 m/sec), then enter 5 m/sec. If the
output is scaled for 4 V at 100% velocity (4 m/sec), enter 5 m/sec.
P8 and P9 can only be accessed if P3 has been set for an option that requires the use
of a velocity input. The input voltage level can be viewed via D12.
Voltage Input
typical 1 - 5 V signal from
velocity sensor.
Signal must be positive with respect to ground.
Velocity Input
AUXILIARY HEAD INPUT
Current Input
typical 4 - 2 0 mA signal from velocity sensor.
Add termina ting resistor.
e.g. 250 Ω for 1 - 5 V over 4 - 20 mA.
(additional to Basic Wiring)
In some applications, the transducer input (TB1-1/2) is not used to provide a signal for
head measurement. A typical example of this is an application which is beyond the 3
m (10 ft) range of the OCM-3. In such a ca se, the head could be derived from another
Milltronics level monitor or other compatible device.
The method of head determination is set by P42. The OCM-3 simply substitutes the
signal from the auxiliary device for the ultrasonic measurement provided by the
transducer. The programming and consequent flow calculation are performed
as normal.
7ML19985AB01OCM III36
Page 37
The 0% and 100% limits of the auxiliary input must be scaled using parameters P43
and P44.
» se le ct P4 3
» enter the voltage corresponding to zero head
» se le ct P4 4
» enter the head corresponding to 5 V.
e.g.if the head output is 1 V per m and the output is scaled for 7 V at
100% head (7 m), then enter 5 m. If the output is scaled for 4 V at
100% head (4 m), enter 5 m.
P43 and P44 can only be accessed if P42 has been set for head determination by an
auxiliary device. The input voltage level can be viewed via D13.
Voltage Input
typical 1 - 5 V signal from
auxiliary device.
Signal must be positive with respect to ground.
Auxiliary Input
typical 4 - 20 mA signal from auxiliary device.
Add termina ting resistor.
e.g. 250 Ω for 1 - 5 V over 4 - 20 mA.
(additional to Basic Wiring)
Current Input
DC OUTPUT
The OCM-3 provides a 24 V DC output that can be used to supply power to a remote
customer device. The output is not isolated from the DC rails that supply the OCM-3
electronics and no overload protection is provided. As such, the output must not
operate beyond its specified capacity.
DIAGNOSTIC AIDS
D15 through D18 are diagnostic aids to Milltronics service personnel when
troubleshooting system problems.
D18 also serves as a performance indicator by displaying the number of valid echos
received as a percentage of the number of pulses being fired by the transducer. A low
value indicates that a large proportion of the pulses fired are not producing valid
echos. In such instances, the transducer should be checked for proper mounting and
aiming or the transducer wiring checked for excessive noise. If the value is zero,
shorted or opened transducer wiring may be suspect.
7ML19985AB01OCM III37
Page 38
‘D’ PARAMETER LISTING
Refer to ‘Operation’ for details.
D0head
D1flow rate
D2short total *
D3maximum flow rate
D4minimum flow rate
D5temperature
D6maximum temperature
D7minimum temperature
D8velocity
✧
D9nominal target range
D10analog milliamps
D11internal DC volts
D12velocity volts
✧
D13auxiliary input volts
D14tempe rature sensor ohms
D15self-test checksum
D16restarts
D17exceptions
D18valid echos per 100
7ML19985AB01OCM III39
*
security access required
✧
applicable to flow calculations requiring velocity sensor
Page 39
7ML19985AB01OCM III40
Page 40
‘F’ PARAMETER LISTING
Refer to ‘Operation’ for details.
F0enter security code
F1emulation mode
*
F2run mode
F3keypad to mA output
*
F4show time
set time
*
F5show date
set date
*
F6software identification number
F7view min/max data
F8reset min/max data
F9self check
*
F10change security code
*
*
F11reset master totalizer
F12force a cold start
*
F13auto zero calibration
F14examine data log:
task: view daily totals
view flow rates
view min/max data
method:
first day
last day
specified da y
F15clear data log
*
*
*
7ML19985AB01OCM III41
*
security access required
Page 41
7ML19985AB01OCM III42
Page 42
‘P’ PARAMETER LISTING
Refer to ‘Operation’ for details.
P0language
0 = english
1 = french
2 = italian
3 = german
4 = spanish
P1dimensional units
linear velocity
0 = centimetrescentimetres per second
1 = inchesinches per second
2 = feetfeet per second
3 = metresmetres per second
P2temperature units
0 = Celcius
1 = Fahrenheit
P3primary element
0 = exponential device
1 = BS-3680 Rectangular Flume
2 = BS-3680 Round Nose Horizontal Crest Weir
3 = BS-3680 Trapezoidal Flume
4 = BS-3680 U-throated Flume
5 = BS-3680 Finite Crest Weir
6 = BS-3680 Thin Plate Rectangular Weir
7 = BS-3680 Thin Plate V-notch Weir
7ML19985AB01OCM III43
8 = Rectangular Weir (contracted)
9 = Round Pipe
10 = Palmer Bowlus Flume
11 = H Flume
12 = Universal Head vs. Flow
Page 43
13 = Rectangular Area x Velocity
14 = Trapezoidal Area
15 = Modified Trapezoidal Area
16 = U-channel Area
17 = Circular Area
18 = Gull-wing Area
19 = Egg-shaped Area
20 = Universal Area
P4method of calculation
0 = absolute
1 = ratiometric
P5flow rate units
flowrate
Velocity
x
Velocity
x
Velocity
x
Velocity
x
Velocity
x
Velocity
x
Velocity
x
volume
0 = litres per secondlitres
1 = cubic feet per secondcubic feet
2 = imperial gallons per minuteimperial gallons
3 = U.S. gallons per minuteU.S. gallons
4 = imperial million gallons per dayimperial million gallons
5 = U.S. million gallons per dayU.S. million gallons
6 = cubic metres per hourcubic metres
7 = cubic metres per day cubic metres
P6flow at maximum head
P7height of maximum head
P8volts in at zero velocity
P9velocity at 5 volts in
P10velocity at maximum flow
7ML19985AB01OCM III44
Page 44
P13display damping
0 = off
1 = low
2 = med
3 = high
P14display lighting
0 = on
1 = auto off
2 = off
P15 / P18 / P21relay 1 / 2 / 3 assignment
0 = not in service
1 = de-energize on loss of echo
2 = energize on loss of echo
3 = de-energize on high flow rate
4 = energize on high flow rate
5 = de-energize on low flow rate
6 = energize on low flow rate
7 = de-energize on high head
8 = energize on high head
9 = de-energize on low head
10 = energize on low head
11 = de-energize on high velocity
12 = energize on high velocity
13 = de-energize on low velocity
14 = energize on low velocity
15 = de-energize on high analog
16 = energize on high analog
17 = de-energize on low analog
18 = energize on low analog
7ML19985AB01OCM III45
19 = de-energize on low D11 volts
20 = energize on low D11 volts
21 = de-energize on high D11 volts
22 = energize on high D11 volts
23 = de-energize on low Aux. volts
Page 45
24 = energize on low Aux. volts
25 = de-energize on high Aux. volts
26 = energize on high Aux. volts
27 = de-energize up control on head
28 = energize up control on head
29 = de-energize down control on head
30 = energize down control on head
31 = de-energize up control on analog
32 = energize up control on analog
33 = de-energize down control on analog
34 = energize down control on analog
35 = ( pulse ) flow totalizer
36 = ( pulse ) sampler by volume
37 = ( pulse ) sampler by time
38 = ( pulse ) by time of day
P16 / P19 / P22 relay 1 / 2 / 3 high setpoint
P17 / P20 / P23 relay 1 / 2 / 3 low setpoint
P24mA assignment
0 = flow rate
1 = head
2 = velocity
3 = temperature
P25If custom mA, 20 mA = ?
0 = normal
0 = custom
P26mA span
7ML19985AB01OCM III46
0 = 4-20 mA
1 = 0-20 mA
Page 46
P27mA damping (secs)
P28mA options (emulator tracking)
0 = don’t track emulator
1 = track emulator
P29 fail-safe time (secs)
P30 fail-safe analog mode
0 = hold last value
1 = assume value in P31
P31fail-safe analog mA (default value)
P32totalizer multiplier
0 = x 1/1000 (0.001)
1 = x 1/100 (0.01)
2 = x 1/ 10 (0.1)
3 = x 1
4 = x 10
5 = x 100
6 = x 1000
P33flow rate display (decimal point)
0 = no decimal places
1 = 1
2 = 2
3 = 3
4 = 4
7ML19985AB01OCM III47
Page 47
P34printer mode
0 = never print
1 = interval to be in minutes
2 = interval to be in hours
3 = print once each day
P35printer timing
P36measurement interval
0 = 1 sec
1 = 15 sec
2 = 30 sec
3 = 1 min
4 = 5 min
P37serial data rate
0 = 300 baud
1 = 600
2 = 1200
3 = 2400
4 = 4800
5 = 9600
6 = 19200
P38site number
7ML19985AB01OCM III48
Page 48
P39data logging rate
fixed
0 = 1 min3 = 30
1 = 54 = 60
2 = 155 = 24 hr
6 = 15/1 min (
variable
% flow / min
(
condition
)
)19 = 60 / 1(
flow
7 = 15 / 5"20 = 60 / 5"
8 = 30 / 1"21 = 24 hr / 1 min "
9 = 30 / 5"22 = 24 hr / 5 min "
10 = 60 / 1"23 = 24 hr / 15 min "
11 = 60 / 5"24 = 15 / 1 min(
head
12 = 24 hr / 1 min"25 = 15 / 5"
13 = 24 hr / 5 min"26 = 30 / 1"
14 = 24 hr / 15 min "27 = 30 / 5"
)
)
15 = 15 / 1 min (
16 = 15 / 5"29 = 60 / 5"
17 = 30 / 1"30 = 24 hr / 1 min"
18 = 30 / 5"31 = 24 hr / 5 min"
P40log rapid setpoint
P39 variable logging conditionunits
% flow / min% change of maximum flow per minute
flow% of maximum flow
head% of maximum head
P41log normal setpoint
P39 variable logging conditionunits
)28 = 60 / 1"
flow
32 = 24 hr / 15 min "
% flow / min% change of maximum flow per minute
7ML19985AB01OCM III49
flow% of maximum flow
head% of maximum head
Page 49
P42 head determination
0 = by OCM-3
1 = by auxiliary device
P43 volts in for zero head
P44 head at 5 volts in
P45 low flow cut-off head
P46 range at zero head
P47 blanking distance
7ML19985AB01OCM III50
Page 50
‘U’ PARAMETERS FOR P3 PRIMARY ELEMENT
The number of ‘U’ parameters required varies according to the primary element
chosen (P3) and the method of calculation (P4). The OCM -3 prompts the user by
displaying the next required parameter, insuring the programming is complete.
The following is a list of the specific primary elements to which the OCM-3 can
be applied.
Refer to the page covering your particular application; the rest may be disregarded.
2BS-3680 Round Nose Horizontal Crest Weir (ISO 4374)
3BS-3680 Trapezoidal Flume (ISO 4359)
4BS-3680 U-throated Flume (ISO 4359)
5BS-3680 Finite Crest Weir (ISO 3846)
6BS-3680 Thin Plate Rectangular Weir (ISO 1438/1)
7BS-3680 Thin Plate V Notch Weir (ISO 1438/1)
8Rectangular Weir (contracted)
9Round Pipe
10Palmer-Bowlus Flume
11H Flume
12Universal Head vs. Flow
13Rectangular Area
14Trapezoidal Area
15Modified Trapezoidal Area
16U-channel Area
7ML19985AB01OCM III51
Velocity
x
Velocity
x
Velocity
x
Velocity
x
Page 51
17Circular Area
x Velocity
18Gull Wing Area
19Egg-shaped Area
20Universal Area
x Velocity
x Velocity
x Velocity
The primary element must be installed in accordance with the manufacturers
recommendations and in accordance with all governing regulations.
7ML19985AB01OCM III52
Page 52
SIMPLE EXPONENTIAL DEVICES, P3 = 0
‘U’ parameters required *
U0 = exponent
U1 = k factor (P4 = 0 only)
Typical Exponential Devices:
» Sutro (proportional) weir
» head measurement only
» Rectangular (suppressed) or Trapezoidal (Cipolletti) weir
» Kahfagi venturi
» Parshall flume
» Leopold Lagco
» Triangular (V-notch) weir
*
obtain from manufacturer’s specifications.
Reference
ABSOLUTE CALCULATION, P4 = 0¤
For flows that can be calculated by the equation:
q = k h
x
where q = flowratex = exponent (U0)
k = constant factor (U1)h = head
RATIOMETRIC CALCULATION, P4 = 1¤
For flows that can be calculated by the equation:
cal
(h/h
q = q
where q = flowrateq
x
)
cal
h = headh
= flowrate at maximum head
cal
= maximum head
cal
x = exponent (U0)
Refer to manufacturers specifications for the exponent value.
¤
Refer to Operation \ Flow Calculation.
7ML19985AB01OCM III53
Page 53
SIMPLE EXPONENTIAL DEVICES, P3 = 0
TYPICAL SHARP-CRESTED WEIRS
transducer *
minimum
3 x h
max
Typical Weir Profiles
V - notch or Triangular
U 0 = 2.5
Tra pezoidal (Cipolletti)
U 0 = 1.5
Rectangular - suppressed
U 0 = 1.5
Sutro (Proportional)
U 0 = 1
(symmetrical or asymmetrical)
For rated flows under free flow conditions, the head is measured upstream of the weir
plate at a minimum distance of 3 times the maximum head (i.e. where the liquid
surface is not affected by drawdown).
* The transducer must be above the maximum head by at least the
blanking value, P47.
7ML19985AB01OCM III54
Page 54
SIMPLE EXPONENTIAL DEVICES, P3 = 0
KHAFAGI VENTURI
15 cm (6")
plan
transducer *
0
head
front
side
For rated flows under free flow conditions, the hea d is measured 15 cm (6") upstream
from the beginning of the converging section.
* The transducer must be above the maximum head by at least the
blanking value, P47.
7ML19985AB01OCM III55
Page 55
SIMPLE EXPONENTIAL DEVICES, P3 = 0
TYPICAL PARSHALL FLUME
C
2/3 C
plan
transducer *
0
head
front
side
For rated flows under free flow conditions, the head is measured at 2/3 the length of
the converging section upstream of the beginning of the throat section.
* The transducer must be above the maximum head by at least the
blanking value, P47.
7ML19985AB01OCM III56
Page 56
SIMPLE EXPONENTIAL DEVICES, P3 = 0
TYPICAL LEOPOLD LAGCO
throat
Q
converging
point of measurement
plan
side
diverging
transducer *
0
head
front
For rated flows under free flow conditions, the head is measured at a point upstream
referenced to the beginning of the converging section. Refer to the following table.
Flume SizePoint of Measurement
(pipe dia. in inches)mminches
4 - 12251.0
15321.3
18381.5
21441.8
24512.1
30642.5
36763.0
42893.5
481024.0
541144.5
601275.0
661405.5
721526.0
* The transducer must be above the maximum head by at least the
blanking value, P47.
calculated by OCM -3. May be viewed by accessing ‘U’ parameter.
Reference
ABSOLUTE CALCULATION, P4 = 0¤
For flows that can be calculated by the equation:
q = 1/1000 x A x v
where :q = flow rate in l/sec
v = flow velocity in cm/sec
RATIOMETRIC CALCULATION, P4 = 1¤
For flows that can be calculated by the equation:
q = q
x A/A
cal
cal
x v/v
cal
where :q = flow rate
q
= flow rate at h
cal
cal
A = cross sectional area of flow
A
= cross sectional area of flow at h
cal
v = flow velocity
¤
Refer to Operation \ Flow Calculation.
cal
7ML19985AB01OCM III94
Page 94
EGG-SHAPED AREA X VELOCITY
transducer *
standpipe **
* This dimension should be at least 15 cm (6") shorter than
the blanking value, P47.
** The transducer must be above the maximum head by at least the
blanking value, P47.
7ML19985AB01OCM III95
Page 95
UNIVERSAL AREA X VELOCITY, P3 = 20
Arbitrary area is typically used when the primary element and/or its flow do not fit any
of the primary elements covered by P3. There is no user difference between absolute
and ratiometric calculations P4.
The flow curve is characterized by entering the head (A
) and area (A
even
odd
)
ordinates for the number of data points (n, 4 to 16) over the flow range. The first
point (A0,A1) generally being at 0 head and the last point (A
calculated by OCM -3. May be viewed by accessing ‘U’ parameter.
e.g. typical open channel
(n, 4 to 16)
U1 = area (h)
transducer *
* The transducer must be above the maximum head by at least the
blanking value, P47.
7ML19985AB01OCM III96
Page 96
UNIVERSAL AREA X VELOCITY
odd
A
Area
U0 = 8
A0 = 0head, point 1
A1 = 0.0area, point 1
A2 = 0.05head, point 2
A3 = 0.03area, point 2
A4 = 0.1head, point 3
A5 = 0.06area, point 3
A6 = 0.15head, point 4
A7 = 0.09area, point 4
A8 = 0.25head, point 5
A9 = 0.18area, point 5
A10 = 0.45 head, point 6
A11 = 0.35 area, point 6
A8 = 0.70head, point 7
A9 = 0.59area, point 7
A8 = 1.00head, point 8
A9 = 0.89area, point 8
Head
A
even
For best accuracy concentrate data points where changes in flow are the greatest.
7ML19985AB01OCM III97
Page 97
7ML19985AB01OCM III98
Page 98
MAINTENANCE
The OCM-3 requires very little maintenance due to its solid-state circuitry. However, a
program of periodic preventative maintenance should be initiated. This should include
regula r inspection, general cleaning, overall system performance checks and standard
good housekeeping practices.
A periodic inspection of the transducer is recommended, at which time any build-up of
material on the face should be removed.
The enclosure should be cleaned using a vacuum cleane r and a clean, dry brush.
For battery replacement refer to Installation / Installing the Memory Back-up Battery.
7ML19985AB01OCM III99
Page 99
Error Code Listing
1number underflow
2number overflow
3divide error
4bad argument
5invalid parameter
6system is locked
7head exceeds BS-3680 spec
ERROR CODES
8must use ratiometric
9invalid angle size
10invalid selection
11value is view-only
12characterizer in use
13feature not available
14need whole number
15invalid date
16invalid time
20can’t zero auxiliary device
21b must be greater than R-r
7ML19985AB01OCM III100
Page 100
COMMUNICATIONS
The OCM-3 provides serial communication either through Milltronics proprietary
bipolar current loop or industry standard RS-232. Communication can be used to
provide a video or paper printout of OCM activity. It can also be used to provide
remote programming and retrieval of the data log, from devices such as computers
and PLCs.
When using the bipolar current loop, communication runs of up to 1,500 m can be
achieved, as opposed to the limited runs of 15 m using RS-232. By terminating the
bipolar current loop with a Milltronics CVCC, the communication format is then
converted to RS-232.
OCM - 3
site number
(P39 )
RS-232
serial printer
customer’s
computer *
bipolar current loop
CVCC **
customer’s
computer *
optional parallel printer
* Milltronics OCM -3 Utilities Software available
** provides conversion to RS -232 or 422
7ML19985AB01OCM III101
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.