Siemens NK8225 Product Data Sheet

Building Technologies
Fire Safety & Security Products
Product Datasheet
NK8000
MP3.20
NK8225 Ethernet Port with BACnet Gateway
The NK8225 Ethernet Port with BACnet Gateway is used to connect local and distributed safety and security devices to DMS8000 Management Stations, and DESIGOTM building automation and control systems. It pro­vides a first level of centralisation, and converts the native protocols of the safety and security devices to BACnet.
Allows to build Total Building Solutions with DMS8000 and DESIGO INSIGHT
Management Stations, and DESIGO PX automation units
Provides BACnet connectivity for AlgoRex CS114x fire detection systems,
Guarto CS6 and Sintony SI410 intrusion detection systems to the DESIGO
building automation and control system
Integrated interaction machine supporting logical combinations between lo-
cally connected subsystems
Based on the standards BACnet/IP and Ethernet
NK8225 is based on a flexible, high performance hardware platform, that has
been specifically designed for safety and security applications
Supplied in a plastic box, easy to install on DIN-rails
Optional housing solutions with autonomous power supply
2 Building Technologies
Fire Safety & Security Products
Connectivity
Connectivity example
Upstream connectivity:
BACnet/IP on Ethernet connectivity for connection to local and remote management
stations (DMS8000 and / or DESIGO INSIGHT);
Conversion of native protocols (CS114x AlgoRex, CS6 MP3, SI410 Sintony) to
BACnet for DESIGO;
Simultaneous multiple host connectivity (up to four);
Downstream connectivity:
Up to 4 serial connections supporting fire, gas and intrusion detection systems, and
digital I/Os;
LON adapter for connecting up to 4 CS6 intrusion detection systems; Direct support for local digital I/O with up to 16 non-supervised inputs and 8 relay
outputs.
For application examples, see the DMS8000 Application & Planning guide.
3
Building Technologies Fire Safety & Security Products
Internal structure
Upstream device
MM8000 + NS8210
or
MK8000 + NS8210
Upstream device
MM8000 + NS8210
or
MK8000 + NS8210
Upstream device
MM8000 + NS8210
or
MK8000 + NS8210
Power supply
supervision
DF8090
LON
Up to 4 CS6 (Guarto)
NK8225
LON
2 x RS232
Power Supply, x86 CPU, Flash, RAM, RTC
Ethernet
Upstream device
DMS8000 /
DESIGO INSIGHT
and / or DESIGO PX
I²C
Serial Subsystems
To DMS8000 and/or DESIGO INSIGHT:
CS11 (AlgoRex) / FC700A
MK7022 (Cerloop)
SI410 Sintony
To DMS8000 only:
CZ10, CZ12, CS4, CS440, CC60
STT2410, STT11, STT20, DMS7000
units, Simatrix, Philips-Burle CCTV
crossbar, CF9000 I/O system,
1 x
RS232/RS485
1 x RS232
I/O Modules
2 x DF8040 1 x DF8020
Up to four
DESIGO INSIGHT can subscribe to NK8225
The NK8225 employs industry standard x86 CPUs and PC104 extension boards, and is composed of:
Base board with power supply, CPU, and basic configuration of interfaces; Optional add-on board with 2 RS232 ports; Optional PC104 LON board.
The Base board is equipped with:
Power supply; 2 serial interfaces (2 RS232 or 1 RS485 and 1 RS232); Ethernet 10Base-T interface; DIMM-PC / 520-I module with:
32MB RAM; 32MB Flash disk; Real Time Clock (RTC); Real Time Operating System
(RTOS) with integrated IP protocol stack
– BACnet protocol stack;
Flash EPROM; RAM; I
2
C bus;
Diagnostic LEDs.
4 Building Technologies
Fire Safety & Security Products
Configuration
Hardware configurations The NK8225 is available in four hardware configurations:
NK8225.2
1 Ethernet line for local or remote host 2 serial lines for subsystems
NK8225.4
1 Ethernet line for local or remote host 4 serial lines for subsystems
NK8225.CL2
1 Ethernet line for local or remote host 1 LON line for subsystems 2 serial lines for subsystems
NK8225.CL4
1 Ethernet line for local or remote host 1 LON line for subsystems 4 serial lines for subsystems
Further options:
NH8002
2 serial port add-on board
DF8040 8 input module on I2C bus
8 input (non supervised) module for acquiring digital contacts. A
max of 2 modules can be directly connected to NK8225. For more connectivity (as well as for supervised inputs), it is neces­sary to use a CF9003 CPU on one of the serial connections.
DF8020 8-output relays module on I2C bus
8 output (non supervised) relay module for controlling digital con-
tacts. Only one module can be directly connected to NK8225. For more connectivity, it is necessary to use a CF9003 CPU on one of the serial connections.
DF8090 power supply supervision module on I2C bus
Optional module for supervising the NK8225 power supply and
detecting power failures and battery low conditions. It is not needed when NK8225 is installed in a fire or intrusion control unit, whose power supply is already supervised.
NE8001
Wall-mountable, metallic cabinet with DIN-rail, including power
supply unit.
Input: 100 – 240 Vac,; Output: 12Vdc 4A.
NE8002
Wall-mountable, metallic cabinet with DIN-rail.
Parameterisation The NK8225 configuration is part of the Composer tool environment. To perform the
SW-configuration for NK8225, a WW8000 Composer license is required.
The configuration tool includes connection parameters, as well as interaction parame­ters (with AND, OR, XOR, and NOT logic combinations).
5
Building Technologies Fire Safety & Security Products
Application examples
Management level The DMS8000 and/or DESIGO INSIGHT management station is connected via
BACnet/IP on Ethernet to the NK8225 for the centralisation of:
Cerloop network via MK7022 (CS114x AlgoRex); Up to 4 CS6 Guarto units on the LON line; Serial connection to CS114x AlgoRex, FC700A and SI410 Sintony control units.
Optionally, DF80xx modules for up to 16 digital inputs, 8 relay outputs, or power supply supervision can also be installed on the local I2C bus.
The following figure shows the various subsystem connections of NK8225s in a Total Building Solution (TBS) with DMS8000 and DESIGO INSIGHT.
Example of a Total Building Solution with DMS8000 / DESIGO INSIGHT
DMS8000 only: The NK8225 also offers connectivity via Ethernet TCP/IP for the centralisation of:
– CF9000 I/O System (RS485 party lines for multiple units (directly connected or via
IC-2 converter));
CCTV Simatrix crossbar or Philips-Burle ; Cerloop network via MK7022 (CS11 AlgoRex, CZ10, STT11 (Système de Télé-
commande et Télésignalisation), CC60 (Gas), CS440, CS4, CZ12 intrusion control units, and DMS7000 units);
Up to 4 CS6 Guarto units on the LON line; Serial connection to CS11 AlgoRex, FC700A, CZ10, CC60 (Gas), SI410 Sintony,
CS440, CS4, and CZ12 intrusion control units.