Siemens LC 500, Treadmill Sitrans User Manual

Instruction Manual January 2003
sitrans
LC 500
Safety Guidelines
Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected equipment. These warning notices are accompanied by a clarification of the level of caution to be observed.
This device/system may only be set up and operated in conjunction with this manual. Qualified personnel are only authorized to install and operate this equipment in accordance with established safety practices and standards.
Warning: This product can only function properly and safely if it is correctly transported,
stored, installed, set up, operated, and maintained.
Note: Always use product in accordance with specifications.
Copyright Siemens Milltronics Process
Disclaimer of Liability
Instruments Inc. 2003. All Rights Reserved
This document is available in bound version and in electronic version. We encourage users to purchase authorized bound manuals, or to view electronic versions as designed and authored by Siemens Milltronics Process Instruments Inc. Siemens Milltronics Process Instruments Inc. will not be responsible for the contents of partial or whole reproductions of either bound or electronic versions.
MILLTRONICS®is a registered trademark of Siemens Milltronics Process Instruments Inc.
Contact SMPI Techni cal Publications at th e following address:
Technical Publications Siemens Milltronics Process Instruments Inc. 1954 Technology Drive, P.O. Box 4225 Peterborough, Ontario, Canada, K9J 7B1 Email: techpubs@siemens-milltronics.com
While we have verified the contents of this manual for agreement with the instrumentation described, variations remain possible. Thus we cannot guarantee full agreement. The contents of this manual are regularly reviewed and corrections are included in subsequent editions. We welcome all suggestions for improvement.
Technical data subject to change.
For the library of SMPI instruction manuals, visit our Web site: www.siemens-milltronics.com
© Siemens Milltronics Process Instruments Inc. 2003
Table of Contents
SITRANS LC 500 ............................. .....................................................................................1
Applications ....................................................................................................................................1
Safety Notes .............................................................................................................................................2
Safety marking symbols ..............................................................................................................2
The Manual .....................................................................................................................................2
Abbreviations and Identifications .............................................................................................3
Technical Specifications: SITRANS LC 500 ...................................................................4
SITRANS LC 500: Transmitter ............................................................................................8
Operating Principles ...............................................................................................................................8
The SITRANS LC 500 variable frequency oscillator .......................................................................8
The SITRANS LC 500 electrode .........................................................................................................10
Application: SITRANS LC 500 ...................................................................................................12
Level Measurement ....................................................................................................................13
Interface Measurement .............................................................................................................14
Switch action ................................................................................................................................14
Fault Signalling .............................................................................................................................15
SITRANS LC 500: Probe Configuration ..........................................................................16
SITRANS LC 500 Electrode (Probe) Characteristics .....................................................................16
Electrode Assembly ..............................................................................................................................17
Process Connections ..................................................................................................................17
Seal Types .....................................................................................................................................17
Process Connection and Seal Configuration of SITRANS LC 500 ..................................17
Pressure and Temperature Considerations ..........................................................................18
Non-standard applications .......................................................................................................19
Table of Contents
SITRANS LC 500: Installation ....... ...................................................................................20
Handling Electrodes ..............................................................................................................................20
Mounting Instructions ..........................................................................................................................21
Protection for solid-state switch .............................................................................................21
Process Cautions .......................................................................................................................21
SITRANS LC 500: Standard Level Version .............................................................................22
Interconnection: SITRANS LC 500 ..................................... ............................................23
Wiring .......................................................................................................................................................23
Supply .............................................................................................................................................23
Cable ...............................................................................................................................................24
Selecting the correct instrumentation cable ......................................................................24
Terminals .................................................................................................................................................26
Connecting SITRANS LC 500 ..............................................................................................................26
Connection Diagram .................................................................................................................26
Protection for solid-state switch .............................................................................................27
Grounding instructions ..............................................................................................................27
Grounding Examples: SITRANS LC 500 ...........................................................................................28
System Grounding (referencing) .............................................................................................28
Metal Tanks ................................................................................................................................28
i
Cathodically Protected Metal Tanks ....................................................................................29
Non-Conductive Tanks ............................................................................................................29
Safety Grounding .........................................................................................................................30
Communications ....................................................................................................................................32
Typical PLC configuration with HART ..................................................................................32
Diagnostics .............................................................................................................................................32
Table of Contents
Applications for Solid-state Output ..................................................................................................33
Switch Protection (Diode) .........................................................................................................34
Factory Settings .....................................................................................................................................34
Settings: .......................................................................................................................................34
The SITRANS LC 500 User Interface .............................................................................36
The LCD (display) ...................................................................................................................................36
How to access the data: ......................................................................................................................37
Menu Levels 00 to 0F and 10 to 1F ..........................................................................................37
The rotary switch ...................................................................................................................................38
The push-buttons ........................................................................................................................38
Access to a menu item: ............................................................................................................38
Adjusting the value .....................................................................................................................38
Transmitter Variables ...........................................................................................................................39
Start-up: SITRANS LC 500 ...................................................................... .........................40
Quick Start ..............................................................................................................................................40
Menu levels 0 and 1 ..............................................................................................................................42
Start up using push-button calibration: (overview) ......................................................................42
Calibration using push-button adjustment ......................................................................................43
Calibration using HART ........................................................................................................................46
Maintenance ........ ........ ...... ...... ....... ...... ........ ...... ....... ...... ........ ...... ...... ....... ...... ........ .........50
Test function ...........................................................................................................................................50
Inspections ....................................................................................................................................50
Troubleshooting: SITRANS LC 500 .. ...............................................................................52
Error Messages and Error Codes ...................................................................................53
Error Messages (push-button operation) .......................................................................................53
Error Codes (HART) ...............................................................................................................................53
Appendix A: Menu Groups ..............................................................................................54
Menu Items .............................................................................................................................................55
Transmitter: Variable Settings: menu level 0......................................................................................... 55
Transmitter Variable Values: menu level 0............................................................................................. 59
Analog Output Signalling (proportional or 2-state): menu level 0..................................................... 62
Analog Signalling Mode (2-state): menu level 0................................................................................... 64
Digital Output Signalling (solid-state output): menu level 1 ............................................................... 67
Miscellaneous............................................................................................................................................... 72
Appendix B: LCD display examples ..............................................................................74
LCD: alphanumeric display examples ....................................................................................74
ii
Appendix C: HART Documentat ion ...............................................................................75
HART Communications for the SITRANS LC 500 ..........................................................................75
HART Device Descriptor (DD) ..................................................................................................75
Simatic Process Device Manager (PDM) .............................................................................75
HART information ..................................................................................................................................75
Expanded Device Type Code: ................................................................................................75
Physical Layer Information .....................................................................................................75
SITRANS LC 500 DD Menu/Variable Organization .......................................................................76
HART Response Code Information ...................................................................................................77
Bit #7: Field Device Malfunction ............................................................................................77
Bit #6: Configuration Changed ...............................................................................................77
Bit #5: Cold Start ........................................................................................................................77
Bit #4: Extended Status Available .........................................................................................77
Bit #3: Output Current Fixed ....................................................................................................77
Bit #2: Primary Variable Analog Output Saturated ...........................................................77
Bit #0: Primary Variable Out of Limits ...................................................................................77
HART Conformance and Command Class ......................................................................................78
General Transmitter Information .......................................................................................................79
Damping information ................................................................................................................79
Non-volatile Memory Data Storage .....................................................................................79
MultiDrop operation .................................................................................................................80
Burst mode .................................................................................................................................80
Units conversions .....................................................................................................................80
Additional Universal Command Specifications .............................................................................80
Appendix D: Block Diagram, and Correlation table, mA to % ................................81
Correlation Table: 0% - 100% to 4-20 mA or 20-4 mA ...................................................................82
Table of Contents
Appendix E: SITRANS LC 500, alternate versions and application details ...........83
Standard Version ...................................................................................................................................83
Standard Version S-Series, Threaded ..................................................................................83
Standard Version S-Series, Threaded ...................................................................................84
Standard Version S-Series, Welded and Machined Flanged Versions .........................85
Standard Version D-Series, Machined Flange ....................................................................86
Interface Version ...................................................................................................................................88
Sanitary Version ....................................................................................................................................89
Flanges .....................................................................................................................................................90
Flange Standards ........................................................................................................................90
Applications Examples .........................................................................................................................91
Generic Application Calculations ............................................................................................91
Application: level indicator and solid-state switch output ................................................93
Application: Analog fault signalling (2-state output) ..........................................................94
iii
Appendix F: Approvals .....................................................................................................96
CE Certificate ................................................................................................................................96
CE Certificate ................................................................................................................................97
Instrument label: SITRANS LC 500 ...................................................................................................98
KEMA certificate and schedules .......................................................................................................99
Certificates and Approvals .............................................................................................................. 107
Table of Contents
NAMUR recommendation NE 43 .......................................................................................... 107
Control Drawing FM/CSA Approval ............................................................................................... 108
SITRANS LC 500 ................................................................................................................................. 108
Glossary ............ ................................. ............................... ............................... .................109
Index .................. .............. ............ ............. ............ ............. ............ ............... ............ ......... 111
Quick Reference: SITRANS LC 500 .............................................................................. 113
Quick Start ............................................................................................................................................113
iv

SITRANS LC 500

SITRANS LC 500 is a high performance 2-wire capacitance instrument for continuous level and interface measurement in extreme or critical conditions. It uses a unique frequency­based measurement system and patented Active-Shield technology to deliver highly accurate, repeatable results. The measurement is unaffected by moisture, vapors, foam, temperature and pressure variations, or material build-up around the mounting glands.
SITRANS LC 500 combines a sophisticated, easy-to-adjust transmitter (MSP-2002-2) with a measurement electrode and process seal selected from a range of options variety of applications. The advanced electronics and integrated local display provide for one-step calibration without interrupting the process, and the probe shield design eliminates the need for frequent recalibration.
SITRANS LC 500 can be used as a level controller, by connecting the mA output and/or the solid-state switch to a relay, and activating a pump via an auxiliary power circuit.
The SITRANS LC 500 is equipped with:
Smart 2-wire transmitter
Remote adjustable commissioning / control capabilities via HART
Analog (2-wire) 4 to 20mA / 20 to 4 mA output
Solid-state and Current detection (4 or 20 mA / 20 or 4 mA, two-state functionality)
Adjustable hystereses on/off for solid-state output and for current signal
Damping functionality
Signal current (measurement/detection) according to NAMUR NE 43
Integrated local display for commissioning and services activities
Full range of local/remote diagnostic facilities
Pre-detection of trip point for high safety requirements
Polarity-insensitive current loop
Integrated zener safety barrier for Intrinsically Safe applications
1
, to suit a wide
2
Introduction

Applications

General Purpose, Dust Ignition Proof, Explosion Proof, and Intrinsically Safe
A wide range of applications in high pressure and temperature, chemically aggressive, and other extreme measurement/detection environments
Liquids, Solids, Quality, and Interface measurement
Viscous non-conducting and conducting liquids
1.
Customized probe configurations can also be provided.
2.
HART® is a registered trademark of the HART Communications Foundation, Austin, Texas, USA.
7ML19985GE01 SITRANS LC 500 – INSTRUCTION MANUAL Page 1

Safety Notes

Special attention must be paid to warnings and notes highlighted from the rest of the text by grey boxes.
WARNING: relates to a caution symbol on the product, and means
Introduction

Safety marking symbols

that failure to observe the necessary precautions can result in death, serious injury, and/or considerable material damage.
WARNING: means that failure to observe the necessary precautions can result in death, serious injury, and/or considerable material damage.
CAUTION: means that failure to observe the necessary precautions can result in considerable material damage.
Note: means important information about the product or that part of the operating
manual.
Alternating Current Direct Current
Earth (ground) Terminal
Protective Conductor Terminal
Frame or Chassis Terminal Cathodic protection resulting in a potential difference: for example,
between the ground on the instrument and the potential of the vessel or tank

The Manual

Notes:
Please follow the installation and operating procedures for a quick, trouble-free installation and to ensure the maximum accuracy and reliability of your SITRANS LC 500.
This manual applies to the SITRANS LC 500 only.
This manual will help you set up your SITRANS LC 500 for optimum performance. We always welcome suggestions and comments about manual content, design, and accessibility.
Please direct your comments to techpubs@siemens-milltronics.com library of Siemens Milltronics manuals, go to www.siemens-milltronics.com
Page 2 SITRANS LC 500 – INSTRUCTION MANUAL 7ML19985GE01
. For the complete

Abbreviations and Identifications

Short form Long Form Description Units
A/D Analog to Digital
Conformitè Europèene / Factory
CE / FM / CSA
D/A Digital to Analog DAC Digital Analog Converter DCS Distributed Control System control room apparatus ESD Electrostatic Discharge Ex Explosion Proof safety approval Exd Flame Proof safety approval FV Full Vacuum
HART
IS Intrinsically Safe safety approval LRV Lower Range Value value for 0 % 4 mA
LSL Lower Sensor Limit
µF micro Farads 10 µs micro Seconds 10
PED Pressure Equipment Directive safety approval pF pico Farads 10 ppm parts per million PV Primary Variable measured value
Stilling Well
SV Secondary Variable equivalent value
SVLRV
SVURV
TV Transmitter Variable URV Upper Range Value value for 100% 20 mA
USL Upper Sensor Limit
Mutual / Canadian Standards Association
Highway Addressable Remote Trans ducer
Grounded metal tube with openings
Secondary Variable Lower Range Value
Secondary Variable Upper Range Value
safety approval
below which no PV is anticipated
-6
-6
-12
0% equivalent value
100% equivalent value
above which no PV is anticipated
Farad Seconds
Farad
Introduction
7ML19985GE01 SITRANS LC 500 – INSTRUCTION MANUAL Page 3

Technical Specifications: SITRANS LC 500

Power

Supply voltage
• maximum: 33 Vdc, (30 Vdc for IS)
• minimum 12 Vdc at 3.6 mA (9.5 Vdc at 22 mA)
Loop current 3.6 to 22 mA / 22 to 3.6 mA (2-wire current loop)

Environmental

Location indoor/outdoor
Altitude 2000 m max.
Specifications

Performance

Ambient temperature
• standard: –40
• ATEX-Explosion Proof –40 oC to 70 oC (–40 oF to 158oF) for T6
Relative humidity suitable for outdoor (Type 4X / NEMA 4X / IP 65
Installation category II
Pollution degree 4
Measurement range
• MSP-2002-2 0 to 3300 pF
Minimum span 3.3 pF
Measurement frequency 420 kHz @ Cx = 0 pF
Accuracy deviation <0.1% of actual measurement value
Non-linearity 0.1% full scale
Repeatability 0.1% actual measurement
Temperature stability 0.15 pF (0pF) or <0.25% (typically <0.1%) of actual
o
C to 85 oC (–40 oF to 185 oF)
–40 oC to 85 oC (–40 oF to 185 oF) for T5 to T1
enclosure)
measurement value, whichever is greater over the full temperature range of the transmitter
Page 4 SITRANS LC 500 – INSTRUCTION MANUAL 7ML19985GE01
Safety • current signalling according to NAMUR NE 43;
3.6 to 22 mA / 22 to 3.6 mA
• probe input ESD protected to 55 kV
• inputs/outputs fully galvanically isolated
• polarity-insensitive current loop
• fully potted
• integrated safety barrier
Diagnostics (Includes • primary variable (PV) out of limits fault alarm) • system failure measurement circuit
• deviation between A/D and D/A converter values
•check sum
•watch dog
• self-checking facility

Outputs

• galvanically isolated
• damping range 1 to 10,000
Current loop
• continuous signal 4 to 20 mA / 20 to 4 mA
• 2-state functionality 4 or 20 mA / 20 or 4 mA, on or off
• time delay 1 to 100 sec. activating / de-activating
• adjustable hysteresis (on / off) 0 to 100%, min. 1% of range
Solid-state switch 40 Vdc / 28 Vac / 100 mA at 2 VA max.
• time delay 1 to 100 sec. activating / de-activating
• adjustable hysteresis (on / off) 0 to 100%, min. 1% of range
Specifications

User Interface

Local digital display 4 1/2 digit LCD
Rotary function switch for selecting programmable menu items
• 16 Positions 0 to 9, A to F
Push-buttons: RED (+), BLUE (–) used in conjunction with rotary switch, for
programming menu items

Communications

HART 1 Communication protocol
1.
HART® is a registered trademark of the HART Communications Foundation.
7ML19985GE01 SITRANS LC 500 – INSTRUCTION MANUAL Page 5

Electrodes

Specifications

Wetted Parts

Process connections
• threaded connection AISI 316 L stainless steel, 3/4”, 1”, 1-1/4”, 1-1/2”, 2”, NPT, BSPT, JIS
• flat-faced flanges AISI 316 L stainless steel (optional C 22.8 N, Monel Hastelloy2 C22, Duplex) ANSI, DIN
3
Probe diameter
• Cable: 9 mm (0.35”)
• Rod: 16 mm (0.63”) or 24 mm (0.95”)
Probe length
• Rod version: up to 3500 mm (138”) with 16 mm (0.63”) diameter probe up to 5500 mm (216”) with 24 mm (0.95”) diameter probe
• Cable version: 35 m (15 ft.)
Probe insulation PFA, Enamel
4
Probe insulation PFA / Enamel
Threaded connection AISI 316 L stainless steel
5
Flange AISI 316 L stainless steel or Teflon
covered
1
400,

Enclosure (electronic)

• construction aluminum, epoxy-coated; diameter 160 mm (6.3")
• cable entry 2 x 1/2” NPT
• ingress protection Type 4X / NEMA 4X / IP 65

Weight

Depends on configuration.
Example:
model: S-series rod: PFA insulated, 16 mm (0.63”) dia., 1 m (39.4”) insertion length weight: approx. 5 kg
1.
Monel® is a registered trademark of the International Nickel Company.
2.
Hastelloy® is a registered trademark of Haynes International Inc.
3.
Please see
4.
Only available as Rod version, max. length 1500 mm (59”), and only for use in applications where pH ≤ 7.
5.
Teflon® is a registered trademark of Dupont.
Page 6 SITRANS LC 500 – INSTRUCTION MANUAL 7ML19985GE01
Flange Standards
on page 90 for a table showing flange sizes.

Process Conditions

Pressure rating
• standard FV (full vacuum) to 200 bar (2920 psi)
• option up to 525 bar (7665 psi)
Temperature rating
• standard –200 °C to 200 °C (–328 °F to 392 °F)
• option up to 400 °C (752 °F)
1
1

Approvals

CE Complies with the requirements of E.C.C. as per EN 55011
and EN 61326
Dust Ignition Proof (DIP) ATEX II 3GD (EEx nA [ib] IIC T4...T6)
FM/CSA: Class I, Div. 2, Gr. A,B,C,D T4
Class II, Div. 1, Gr. E,F,G T4 Class III, Div. 1, Gr. E,F,G T4
Intrinsically Safe (IS) ATEX II 1 G (EEx ia IIC T4...T6)
FM/CSA: Class I, Div. 1, Gr. A,B,C,D T4
Flame-proof/ ATEX II 1/2 GD (EEx d [ia] IIC T6...T1) Explosion-proof enclosure FM/CSA: Class I, Div. 1, Gr. A,B,C,D T4
Sanitary 3A
Lloyds Register of Shipping Categories ENV1, ENV2, ENV3, ENV5
European Pressure, PED 97 / 23 / EC
Note: See
Appendix F: Approvals
on page 96 for details of certification.
Specifications
1.
Please refer to page 18, Temperature/ Pressure Curve chart, for specific combi­nations of temperature and pressure.
7ML19985GE01 SITRANS LC 500 – INSTRUCTION MANUAL Page 7

SITRANS LC 500: Transmitter

Operating Principles

Capacitance1 measurement operates by forming a variable capacitor resulting from the installation of a vertical measurement electrode in a vessel or silo. The tank wall usually forms the reference electrode of the capacitor. Whatever material is sandwiched between the two electrodes forms the dielectric. This will be composed of the vessel contents (air, vapor, liquid, solid, or a combination) and, if the measurement electrode is insulated, the insulating layer (PFA, for example). The dielectric gives a capacitance value that is proportional to level.
Capacitance is affected by the surface area of the electrodes, the separation distance between the electrodes, and the dielectric constant of the vessel contents. The dielectric constant is the measure of a material’s ability to store energy. The relative dielectric constant of air (vacuum) is 1: all other materials have a higher value.
Note: To preserve linearity of the measurement, both electrodes must be parallel.
(When the vessel contents are conductive, the measurement electrode is insulated and the interface between the insulating layer and the contents acts as a parallel reference electrode independent of the tank wall.)

The SITRANS LC 500 variable frequency oscillator

The SITRANS LC 500 probe is equipped with a variable frequency oscillator which responds to the capacitance: a change in capacitance is registered as a change in frequency. The relationship between capacitance and frequency is inverse, resulting in
Operation & Application
high resolution and accuracy. The variable frequency maintains a constant relationship to the reading.

Capacitance measurement in a cylindrical metal tank

In a cylindrical tank, it is possible to determine the initial capacitance in air by factoring in the length of the probe, diameter of the probe, diameter of the tank, and the relative dielectric constant of air.
1.
For definitions relating to capacitance, see the glossary, page 109.
Page 8 SITRANS LC 500 – INSTRUCTION MANUAL 7ML19985GE01
The formula1 is:
K ε L××
C
--------------------------=
Log D d()
where C = capacitance
K = constant
ε = dielectric constant
L = active measurement length D = diameter of tank d = probe diameter.
(For detailed application examples, see page 91.)
The transmitter measures the capacitance of the measurement electrode relative to the tank wall (reference electrode) and transforms it to a 4-20 mA signal. Any material that covers the probe will cause an increase in capacitance relative to an uncovered probe surrounded by air. As the product level rises the capacitance will increase.
Non-conductive or conductive contents
In practice, the SITRANS LC 500 probe is usually insulated. If the vessel contents are non­conductive, the dielectric is composed of the vessel contents and the insulation, and the separation distance is from the probe to the tank wall. The tank wall is the reference electrode, and it must be connected to the ground point on the instrument.
dielectric = contents plus insulation (non-conductive contents) dielectric = insulation (conductive contents)
Operation & Application
probe
dia. (d)
internal tank wall
internal tank diameter (D)
(insulation)
p ro b e
sleeve
Note: For simplicity, the probe is shown centrally mounted. If it is to be mounted off-
centre, take care to ensure the electrode remains parallel to the tank wall.
If the vessel contents are conductive, the electrode must be insulated. In this case the dielectric is the insulation layer and the interface between the conductive contents and the insulating sleeve acts as the reference electrode. This reduces the separation distance for the filled portion of the tank to the thickness of the insulation. It also creates a linear reference electrode independent of the tank wall.
1.
This formula applies to a centrally mounted probe: for a probe mounted off-centre, the formula must be adjusted.
7ML19985GE01 SITRANS LC 500 – INSTRUCTION MANUAL Page 9
In a non-conductive or irregular tank
Where the vessel contents are non-conductive:
a reference electrode parallel to the measurement electrode is required
the reference electrode must be grounded to the instrument
a stilling well can form the reference electrode.
Where the vessel contents are conductive:
the interface between the contents and the electrode insulation acts as the reference electrode
a connection from the vessel contents to the instrument ground is required
a stilling well can provide a means of connecting the contents to the instrument ground.
The stilling well
The stilling well is a metal tube concentric with the electrode, with vent openings to facilitate level equalization. Its diameter is somewhat larger than that of the electrode, depending on the application. The stilling well can either be integral to the SITRANS LC 500, or it may be part of the tank
1
.

The SITRANS LC 500 electrode

The SITRANS LC 500 electrode, comprising a measurement section and an active shield section, is the primary sensor of the system. It supplies the electrical capacitance value of the measurement section relative to the environment (tank wall or stilling well).
The SITRANS LC 500 patented Active-Shield Technology electrically isolates the measurement section and prevents any non-measurement capacitance from interfering with the measurement. (Capacitance changes could result from uncontrolled variations occurring in the connection cable, process connection, and non-active parts of the
Operation & Application
probe). This results in a better ratio of initial capacitance to total capacitance, resulting in higher accuracy.
1.
The tank wall, or the stilling well if it is part of the tank, must be grounded.
Page 10 SITRANS LC 50 0 – INSTRUCTION MANUAL 7ML19985GE01
R = Ratio between initial
capacitance and total capacitance
Ca = Initial capacitance (air)
Cm = Capacitance Increase
(product)
C1 = Capacitance connection
point
C2 = Capacitance connection
cable
C3 = Capacitance Process
connection (includes active part)
Conventional Capacitance
Measurement
R = (C1 + C2 + C3) + Ca
(C1 + C2 + C3) + Ca + Cm
Measuring-
Circuit
C1
C2
C3
Ca
Cm
SITRANS LC 500
with Active Shield
R = Ca
Ca + Cm
Measuring-
Circuit
Ca
Cm
The measurement is further protected from interference by a buffer, which applies the frequency signal from the measurement section to the active shield section. This effectively eliminates any electrical potential difference between the shield and the measurement section and prevents additional changes in capacitance occurring.
SITRANS LC 500
active shield
active measurement
empty
tank
full
tank
100%
section
probe seal
buffer
(inactive)
frequency (f)
0%
K
capacitance (C)
The relative lengths of the measurement section and active shield section can be specified to suit a particular application. If the measured range will be short relative to the total length of the electrode, specify a short measurement section. This increases the achievable resolution of the measurement, since any change in level will be greater relative to the length of the measurement section.
Operation & Application
7ML19985GE01 SITRANS LC 500 – INSTRUCTION MANUAL Page 11
The entire SITRANS LC 500 transmitter is potted in epoxy resin as part of the intrinsic safety protection. The potting also protects the electronics against mechanical vibration and moisture influences.
The transmitter is connected to the electrode by a mini coaxial cable, and grounded to a connection point inside the enclosure. The external ground lug on the enclosure provides a means of connecting the instrument system ground to a grounded tank or stilling well (For more detailed information on grounding requirements, please see Grounding Examples, page 28.)
–12
The measuring range of the SITRANS LC 500 is 3300 pF (1.0 pF ≅ 10
F).
Note: For safety purposes, and to ensure reliable measurement signals, the external
ground lug provided on the SITRANS LC 500 enclosure must be firmly connected by an adequate cable to the grounded vessel or stilling well
1
.

Application: SITRANS LC 500

The SITRANS LC 500 provides an analog and a solid-state output. The analog output can be either a continuous signal proportional to the reading, or in 2-state mode, a mA signal operating according to NAMUR recommendations for fault signalling
0% (LRV) and 100% (URV) can be set anywhere within the measurement range.
1. The loop current provides either: a. an analog signal:
• a reading proportional to level (PV) under normal conditions
• an out-of-limits display, ‘ooL’, alternating with PV, in fault conditions (if the process level exceeds the limit settings [USL] or [LSL])
or:
2
.
1
.
Operation & Application
b. in 2-state mode, provides a mA output:
• 4 mA or 20 mA output for 0% and 100%, under normal conditions
• a 3.6 or 22 mA output in fault conditions (when 2-state fault signalling [menu 08] is enabled, if the process level exceeds the limit settings [USL or LSL])
2. The solid-state output can be set to ‘contact open’ or ‘contact closed’, relative to a covered probe: it can be wired to an external relay and used to activate an external alarm or a pump via an auxiliary power circuit. It can be activated under normal conditions by the threshold settings, or Fault signalling can be enabled at menu 18.
1.
Where the stilling well is welded to the tank.
2.
See page 93 for detailed examples.
Page 12 SITRANS LC 50 0 – INSTRUCTION MANUAL 7ML19985GE01
solid­state switch output or 2-state mA output
Indicator - dynamic Primary Variable (units or % of range)
0-100%
current loop connection
Active Shield section
USL
URV = 100%
Upper Threshold Setting = % (activation hysteresis)
(deactivation hysteresis) Lower Threshold Setting = %
LRV = 0%
LSL
solid­state output
auxiliary power pump power
P
3. Upper Threshold Setting and Lower Threshold Setting activate and deactivate the 2-state output, and/or the solid-state output: the settings can be modified to adjust the hysteresis (the window within which the probe is considered ‘covered’).
4. The speed of response to activation and deactivation of the solid-state and/or 2-state output can be modified by Upper and/or Lower Threshold delays.
5. The PV reading can be stabilized if necessary by applying Damping.
6. Overfill or underfill protection can be set in the absence of those conditions by applying the Delta Range Setting.
7. Analog Fault Signalling (menu 08) and Digital Fault Signalling (menu 18) take precedence over the threshold settings (menus 07 and 17).

Level Measurement

The continuous 4-20 or 20-4 mA signal is proportional to the surface level of the product, with an accuracy of 0.1% of the actual measurement (for example, 1mm/m).
Typically, Lower Range Value (LRV - 0%) is set to 4 mA and Upper Range Value (URV ­100%) is set to 20 mA: but the reverse is possible if required. The measurement takes place anywhere within that range. The LCD displays the value as mA, or pF, or percent, depending on the setting for the transmitter variable (TV). If you are using HART, you have the option to define the units.
Operation & Application
7ML19985GE01 SITRANS LC 500 – INSTRUCTION MANUAL Page 13

Interface Measurement

The capacitance of the electrode system is dependent on the dielectric constant of the product surrounding the probe. By comparing the capacitances resulting from different products with different dielectric constants, it is possible to determine which product is surrounding the probe.
For miscible products:
Contamination of one product by another can be measured:
100% product A 4 mA 100% product B 20 mA Values in between 4 and 20 mA represent the ratio of the two products.
For immiscible products:
The interface between two products can be detected by the change in capacitance from one to the other. (See example,
For Vessels filled with Oil
on page 91.)

Switch action

2-state Switch
The mA output can be used as a 2-state switch set to either 4 or 20 mA. It can be set to go to 4 mA if the probe is covered and 20 mA if the probe is uncovered, or the reverse.
Solid-state Switch
The solid-state output can be set to ‘contact open’ or ‘contact closed’ with a covered probe.
Adjustable hysteresis and time delay
Operation & Application
The adjustable hysteresis and time delay settings allow you to adjust the switch action for applications with a lot of surface movement.
Examples: With a moving surface that fluctuates between 79% and 80%, if the hysteresis is set so that 80 is on and 79 is off, the alarm will constantly alternate between on and off. Either set a time delay, or adjust the hysteresis:
Set the time delay to 10 seconds (for example): the alarm will be on only after
the surface has been at 80% for at least 10 seconds.
Reset the hysteresis for 70 (for example): the unit will ignore small surface
fluctuations between 79 and 80%.
Page 14 SITRANS LC 50 0 – INSTRUCTION MANUAL 7ML19985GE01

Fault Signalling

The SITRANS LC 500 has three fault signalling options:
via the loop-current
via HART
via the solid-state output or solid-state relay.
Via the loop current
When using the mA signal, the SITRANS LC 500 operates according to NAMUR standards1 for fault signalling. The fault/failure signal can be triggered by a failure in the measuring system, such as:
a checksum error
a loss of signal caused by a defect in the module
a short circuit in the sensor
a process failure if the level exceeds the limit settings and if the unit is
programmed to detect this
You can set the Upper and Lower Sensor Limits (menus 0B and 0C) outside the Upper and Lower Range Value settings. In this case, if the process value is outside its nominal range (the span between LRV and URV), but still not at a fault/failure level, the continuous mA output will saturate to 3.8 mA or 20.5 mA. If the process value is outside the Upper or Lower Sensor Limits, this will be registered as a fault/failure.
Depending on the setting chosen for 2-state Fault Signalling (menu 08), the signal will go to either 3.6 mA (F: Lo) or to 22 mA (F:Hi). If you do not use communications to receive status information, we recommend enabling analog fault signalling (menu 08), in order to be warned if a fault or failure occurs. (This feature is disabled by default.)
Operation & Application
Via HART
See page 75 for by a response code. It is then up to the Host to decide what to do in the case of a fault situation. The Host may decide to issue Command 48, which returns more detailed information.
HART Response Code Information
. Each HART message is accompanied
Via the solid-state output
The solid-state switch can be wired up to an external relay, to provide a second level of protection. It can then be used to activate a failure alarm, or a level switch. (See page 93 for details of an application using SITRANS LC 500 as a level indicator, with the two-state output connected to a relay that activates a pump.)
1.
See
NAMUR recommendation NE 43
7ML19985GE01 SITRANS LC 500 – INSTRUCTION MANUAL Page 15
on page 107 for more details.

SITRANS LC 500: Probe Configuration

The probe (electrode) comprises a measurement section and an active shield section. This electrode connects to the capacitance detector portion of the two-wire loop powered electronic transmitter. The transmitter module is mounted in a powder-coated aluminum enclosure which provides reliable operation in environments with dust, moisture, and high-frequency interference.

SITRANS LC 500 Electrode (Probe) Char acteristics

Apply to all general connection configurations:
The standard SITRANS LC 500 insulated electrode is designed for use in both conducting and non-conducting liquid applications.
Most electrodes consist of an active shield portion and a measurement portion, which combine to form the complete electrode. (This is not the case for cable electrodes or electrodes with ceramic/enamel insulation.)
The sum of the active shield length and the measurement length is the total insertion length.
The active shield design provides continuous immunity from changes in conditions at the top of the vessel where levels of vapors, dust, and condensation may be constantly changing.
The design of the active shield isolates the starting capacitance of the electrode from the effects of changes in capacitance due to temperature and pressure fluctuations that could cause small changes in the seal geometry.
The carefully-controlled diameter of the electrodes and insulation produces a linear output over a wide range of capacitance values (1 pF to 3300 pF).
The end seal is formed as an integral part of the electrode insulation, giving smooth and uniform characteristics (tested to 55 kV).
Standard single cone seal
active shield
Probe Configuration
insertion length
measure-
probe seal (inactive)
Page 16 SITRANS LC 500 – INSTRUCTION MANUAL 7ML19985GE01
ment portion

Electrode Assembly

SITRANS LC 500 electrodes come in a variety of formats to provide the necessary characteristics for correct mounting, chemical compatibility, temperature and pressure requirements, and dielectric constant of the medium. The main body of the manual discusses the standard configuration. Other options, with details, are shown in
SITRANS LC 500, alternate versions and application details

Process Connections

The standard threaded process connection (S-Series) with PFA insulated electrode, including the active shield, provides good results in all measurement situations within the temperature, pressure, and corrosive capabilities of the materials and seals. This remains true over a wide range of dielectric constants in both non-conducting and conducting materials.
Any standard process connection is available with the SITRANS LC 500, and special versions can be fabricated to match the mounting and application requirements. A wide range of threaded and flanged fittings is available. (Contact your local Siemens Milltronics representative for details, or check our website at: www.siemens-milltronics.com.)

Seal Types

The basic internal seal for the SITRANS LC 500 has a conical-shaped, preloaded pressure/leak resistant construction. Up to three levels of seal protection are implemented depending on the integrity requirements of the application. A single or double cone internal seal forms one or two barriers against leaking, and a third flange face gasket is also available in the D and DD seal construction. The flange face seal also provides a design with no metal wetted parts if required.
, page 83.
Appendix E:

Process Connection and Seal Configur ation of SITRANS LC 500

Process Connection Seal Type Seal Description
Threaded S Single Cone
Welded Flange S Single Cone
S Single Cone
D Single Cone + Teflon flange seal
Solid Machined Flange
DD
SD Double Cone (used for stilling well applications)
7ML19985GE01 SITRANS LC 500 – INSTRUCTION MANUAL Page 17
Double Cone + Teflon flange seal. (Consult your local Siemens Milltronics representative.)
Probe Configuration

Pressure and Temperature Considerations

The maximum temperature and pressure of operation for the standard SITRANS LC 500 level probe is 200°C (392°F) and 200 bar (2900 psi). Please consult the pressure curve on page 18 for qualifications that must be applied to these maximums.
Enamel probes are recommended when the process temperature exceeds 200 °C, and/or in combination with very high pressure.
Note: Consult your Siemens Milltronics representative if the material to be measured may be incompatible with the SITRANS LC 500 materials of construction.
Temperature Versus Pressure Curve for SITRANS LC 500 PFA-insulated Level Probe
As the temperature approaches 75°C (167°F), the maximum pressure must be derated1. When the temperature reaches 200°C (392°F), the maximum pressure is limited to 50 bar (725 psi). This curve is typical for water only. For other, more aggressive chemicals the derating curve will be more severe.
–1bar (–
14.6 ps i)
pressure
o
0
o
(32
–100 (–148
o
o
C F)
200 bar (2920 psi)
150 bar (2190 psi)
100 bar (1460 psi)
70 bar (1022 psi)
50 bar (725 psi)
o
–50
C
o
F)
(–58
consult factory when pressure or temperatures fall within this area
o
70
C
o
F)
(158
o
50
C
F)
(122
100 oC
C
o
o
F)
(212
o
150
C
o
F)
F)
(302
temperature
o
200
C
o
F)
(392
Reference Product: Water
Notes:
For high temperature and pressure ratings for the Enamel probe, please contact your Siemens Milltronics representative.
Probe Configuration
For FM / CSA Explosion Proof applications: if the process temperature exceeds 135
1.
Decreased within the limits specified in the diagram (maximum 200 bar).
o
C (275 oF), select process seal type SD,DD,HP or HT.
Page 18 SITRANS LC 500 – INSTRUCTION MANUAL 7ML19985GE01

Non-standard applications

Applications outside the standard capabilities of the S-Series require a different design configuration. These non-standard applications include:
Non-Standard Application SITRANS LC 500 Configuration
Non-metallic tanks with both conducting and non-conducting liquids.
Non-conducting liquids in spherical and horizontal-cylindrical tanks.
Highly corrosive materials requiring no metallic wetted parts.
Sanitary/food safe applications. Use SITRANS LC 500 sanitary version.
For more details on alternate configurations, see,
versions and application details on
Use stilling well for second electrode reference.
Use a stilling well as linearizer.
Use flange mount with D, DD seal version.
Appendix E: SITRANS LC 500, alternate
page 83.
Probe Configuration
7ML19985GE01 SITRANS LC 500 – INSTRUCTION MANUAL Page 19

SITRANS LC 500: Installation

Notes:
• Installation shall only be performed by qualified personnel and in accordance with local governing regulations.
• This product is susceptible to electrostatic discharge. Follow proper grounding procedures.
WARNINGS:
• Disconnect the device before any welding is carried out in the vicinity of the instrument.
• Provide protection when the solid-state switch is activating an external relay to prevent possible switch/relay damage resulting from inductive spikes generated by the relay coil. (See
state switch
on page 21 for details.)

Handling Electrodes

WARNINGS:
• Do not scratch or gouge the PFA electrode insulation since this could reduce the integrity of the insulation and the useful life of the electrode.
• Be careful with an enamel-insulated electrode
• Do not damage the insulation jacket on the electrode during shipping, packing, and installation proper performance.
• (ATEX 100): Precautions MUST be taken to avoid ignition due to hazardous electrostatic discharges:
a. Where an isolated probe is used in gas, vapor, or a non-
conductive liquid that is potentially explosive, requiring apparatus group IIC equipment.
b. Where the probe is used in a potentially explosive dusty
atmosphere.
2
. Any damage to the electrode can prevent
Protection for solid-
1
.
1.
Normally the enamel insulation is protected by a stilling well, which is part of the design.
2.
Most electrodes use PFA insulation, a very dense and reliable type of Teflon® that prevents leakage and corrosion of the metal electrode and acts as an insulator when conductive materials are being measured.
Installation
Page 20 SITRANS LC 500 – INSTRUCTION MANUAL 7ML19985GE01

Mounting Instructions

The SITRANS LC 500 is easily installed: simply mount the instrument on the process connection of the vessel.
Notes:
• The transmitter is specified for use at temperatures ranging from –40 °C to 85 °C (–40 standard option is available with a thermal isolator.
• Before mounting the SITRANS LC 500, check to ensure the threads are matching to avoid damaging them.

Protection for solid-state switch

for dc circuits: connect protection diodes in the correct polarity across the relay coil
for ac circuits: connect a Voltage Dependent Resistor (VDR) or other ac compatible component (such as zeners and protection diodes in combination) in the correct polarity across the relay coil

Process Cautions

AUTION: Consider material surface
onfiguration when installing unit.
o
F to 185 oF): if your process temperature is outside this range, a
CAUTIONS:
• With a centrally mounted cable version, take care that the tensile load does not exceed probe or vessel rating
• With a cable version mounted close to the tank wall, take care that the product does not push the cable against the tank wall: a spring can be used as a retainer.
??
500 mm (20”) min.
7ML19985GE01 SITRANS LC 500 – INSTRUCTION MANUAL Page 21
Installation

SITRANS LC 500: Standard Level Version

Available with the following features:
Threaded flanges, welded flanges, and single-piece flanges
S series, D series, SD series, DD series, and HP series process seals
Selections of standard ANSI and DIN flanges
The most common electrode is insulated with PFA. Enamel (HP seal) is also available (rigid design only).
Various process connection materials
Both Rod and Cable versions
Appendix E: SITRANS LC 500, alternate versions and application details
See onward, for details on dimensions, and for application examples.
, page 83
Installation
Page 22 SITRANS LC 500 – INSTRUCTION MANUAL 7ML19985GE01

Interconnection: SITRANS LC 500

Wiring

Supply

Notes:
The transmitter is powered by the current loop and needs at least 9.5-13 Volt on the terminals: 9.5 V at 22 mA or 12 V at 3.6 mA.
The maximum supply is 33 Volt. If the voltage is higher the device will shut down.
The loop-circuit will withstand voltages up to 250 Vac/Vdc without any damage.
The SITRANS LC 500 uses a switched power supply circuit, which makes the most efficient use of the available power present on the terminals. If the signal current is low, (4mA), the terminal voltage will be high, and if the signal current is high, (20 mA), the terminal voltage may be low, due to all the resistive elements in the loop, such as the barrier and sense resistor.
Voltage drop versus mA for current transmitter operation
voltage drop over 250 ohm measuring resistance
voltage drop over 280 ohm in barrier
V-s uppl y
voltage drop over blocking diode in barrier
margin or voltage drop over instrument cable
operation voltage, transmitter
Interconnection
mA
Examples:
With a 250 Ohm sensing resistor, no barrier and negligible cable resistance, the overall supply voltage should be at least 15.0 V.
With a 250 Ohm sensing resistor, a barrier of 280 Ohm, and 20 Ohm cable resistance (500 m), the total resistance is 550 Ohm, so the overall supply voltage should be at least 20.5 Volts.
For a multi-drop application, where the measuring supply is fixed to 4 mA, the voltage on the terminals of the SITRANS LC 500 should be at least 12 Volts.
The loop circuit is completely isolated from the measurement circuit. It is designed so that the internal capacitance and inductance on the terminals are isolated and do not factor in safety calculations.
7ML19985GE01 SITRANS LC 500 – INSTRUCTION MANUAL Page 23

Cable

Notes:
To maintain reliable transfer of the HART modem signals, the RC1 time constant of the connections should be less than 65 µSec.
Cable capacitance must also be considered when selecting cable for intrinsically safe installations.
Interconnection
For output signals (from the SITRANS LC 500), only the cable and barrier resistance are relevant. For input signals the measurement resistance is also relevant.
Use twisted pair cable, screened as a pair.
1.
RC = Resistance * Capacitance
2.
Or, if you use a common screen over a cable containing multiple twisted pairs, do not use other pairs for signals that could interfere with HART signals.
Selecting the correct instrumentation cable
you need to know the cable length, the barrier type (if applicable), and the measurement resistance
select a cable that will give you a capacitance time constant of less than 65 µSec
1. Calculate the capacitance for a time constant of 65 µSec, using the following formula:
tRC×=
R
is the sum of the load resistor and cable resistance.
C
is the sum of the cable capacitance and the capacitances of the connected
device/devices.
2. Determine the cable length allowed, by subtracting the capacitance value of the device (or devices) on the loop from the total capacitance, and using the maximum allowable limit of 100 pF per meter (or 1 nF per 10 meters).
Example
1. Calculate the cable capacitance which will give a time constant of 65 µSec: A twisted pair cable with a conductor cross-section of 1 mm a copper resistance of 73.6 Ohm/km and a capacitance of 100 pF/m (or 1 nF/10m).
For a standard 28 V 280 Ohm barrier and a 250 Ohm measuring resistance, with a 100 meter cable:
Resistance = 280 (barrier) + 250 (sensing device) + 7.36 (cable)= 537.36
(time constant = Resistance * Capacitance)
tRC×=
2
2
(AWG 18 equivalent) has
CtR=
65 10
C 65 10
Page 24 SITRANS LC 500 – INSTRUCTION MANUAL 7ML19985GE01
6
× 537.36 C×
s = nF
6
× 537.36()121==
nF
Loading...
+ 92 hidden pages