Siemens GENESIS II Installation Manual

009159_a_en_--.doc 1
Building Technologies Fire & Security Products
GENESIS II
Installation Manual and Technical Data
Control panel with one fire detection zone, associated an intrusion and/or hold-up-system
Installation manual 009159_a_en_-­Edition 10.11.2005 Supersedes -
1
PU4
PU1
PU2
PU3
GENESIS II MODULE
DL2
DL3
DL4
DL1
GENERAL MODULE
INTRUSION CONTROL
PANEL
Out
In-R
2K7
REOL
Detector
Socket
Out
In-R
Detector
Socket
-
+
R470/1W
Call Point
- LINE
+LINE
-
+
CONT
Activity LED
max. 20mA
-
+
OUT >5mA
POWER SUPPLY
12V
FAULT
ALARM
TAMPER
for details see Fig. 2, 3
12V
CONTROL
NC
NO
See description for Indicators and Jumpers
2 3
R
NC
NO
1
Fault
Alarm
Alarm and fault outputs to one zone of the Intrusion Control Panel (1)
R
NC
NO
1
T
Fault
Alarm
Tamper
Alarm and fault outputs (tamper incl.) to one zone of the Intrusion Control Panel(1)
2 009159_a_en_--.doc
Instructions for use the GENESIS II Control Panel
Overview
The GENESIS II, makes it possible to install single­zone fire detection based on a conventional intrusion detection control panel, controlling and supervising a 2-wire line, equipped with up to 32 conventional de­tectors at 24Vdc.
The GENESIS II is supplied with 13.8Vdc from the intrusion control panel and, by means of an internal converter, is able to provide the 24Vdc supply re­quired by the detectors and/or call points. This elimi­nates the need for an external 24Vdc power supply and battery backup, as in the case of mains failure /­disconnection, the intrusion control panel backup powers the system.
Jumper settings
Description ON OFF
Non current limited detectors PU1
PU2
Current limited detectors PU1
PU2
Fault Output C-NC PU3
(2,3)
Fault Output C-NO PU3
(1,2)
Local Control (Push button GENESIS II)
PU4
Remote control (from Intrusion control panel)
PU4
LED displays
LED Colour Description
DL1 Green Enable LED DL2 Red Fire LED DL3 Amber Short Circuit fault LED DL4 Amber Open Circuit fault LED
Wiring
Power supply and control.
GENESIS II has two control possibilities, depending on the fact that the Intrusion Control Panel has an output for sensors rearming or not.
Follow the steps detailed here below: – Carry the supply (11 to 14Vdc) from the Intrusion
Control Panel to the terminals designated (-12V+) of GENESIS II.
– If the Intrusion Control Panel does not include the
aforementioned output for detectors rearming, the control on GENESIS II will be carried out from the reset push-button itself (make sure that the PU4 jumper has been inserted).
– In case the Intrusion Control Panel has the output
available, wire it at the input of the terminals input labelled (CONT) of GENESIS II. It will be reset when it detects a level of 0V in that control input; this implies a rearming in the detectors line if that level is present during the period required by the detectors (3 to 4 seconds is usually enough for most of them). To have this feature available, you must remove the PU4.
Detectors and/or call points line.
Connect the detectors (ionizing, optical, etc) and/or call points line to (+LINE-) as shown in fig.1.
The GENESIS II allows both current-limited
and non-current-limited detectors and/or call points provided that the two types are not mixed on the same line.
Setup
Set up the GENESIS II according to the type used as follows:
Non-current-limited detectors and/or call points:
Remove GENESIS II jumpers PU1 and PU2. See Fig.1
Compatibility with the non-current detectors below: – DL0 beam detector – DF1191/92 infrared flame detector
Current-limited detectors and/or call points
Insert GENESIS II jumpers PU1 and PU2. See Fig.1
Compatibility with the current detectors below: – OP320C optical detector – OH320C multi detector – HI320C heat detector – HI322C heat detector – MT320C manual call point
Alarm and fault output
It incorporates alarm and fault outputs by means of voltage-free relay contacts, what facilitates its adap­tation to the different Intrusion Control Panels, re­gards to connection.
Figures 2 and 3 show, as an example, 2 types of connection, among the most common ones, used for this kind of installations: – Figure 2 presents a typical connection for the iden-
tification of alarm and fault on the detectors line of GENESIS II, in two independent zones associated to the Intrusion Control Panel.
– In those Intrusion Panels with EOL resistor in each
zone, being possible to program some of them as “fire zone” so that a short-circuit or open-circuit in that zone will be identified as fire alarm or fault, re­spectively, the wiring can be done as shown in fig.3, which includes an electrical diagram for a better comprehension.
– In addition to the connection shown in figure 2,
fig.3 presents the possibility of tamper detection on the part of the GENESIS II box.
Functional test
Before testing the installation ensure that the power supply polarity is correct. Also, check that jumpers PU1 and PU2 are in the correct positions according to the type of detectors used in the installation.
Next, connect the GENESIS II to power and check that the green “ENABLED” led is lit and that the In­trusion Control Panel is in standby mode.
Open-circuit fault.
– Disconnect the 2K7 end of line resistor. The amber
“OC FAULT” led on the GENESIS II will be lit and the Intrusion Control Panel indicate fault on the
corresponding zone. – Reconnect the resistor. The indicator will go out. – Remove each of the detectors from their sockets
one at a time (the line will open as each is re-
moved provided the standard mounting instruc-
tions for the detectors have been followed). Check
that unit in exactly the same was as described in
the previous paragraph.
Short-circuit fault
– Short-circuit the 2K7 end of line resistor. The am-
ber “SC FAULT” led on the GENESIS II will be lit
and the Intrusion Control Panel will indicate fault
on de corresponding zone. Remove the short-
circuit. The indicator will go out.
Alarm
– Now activate each detector by means of the effect
it is designed to detect (smoke, rapid temperature
rise, manual call point activation etc). The indicator
on the detector will be lit, as will the “ALARM” led
on the GENESIS II. The Intrusion Control Panel
will indicate alarm on the corresponding zone.
Resetting the detector lines
– From the reset push-button of GENESIS II, or from
a sensors rearming output, in case the Intrusion
Control Panel allows it, cause a 3 seconds rearm-
ing approximately in the detectors line, checking
that during this period of time, the “ENABLED”
LED of GENESIS II will go out, so that if the cause
that originated the activation of the detectors has
disappeared, the detectors will go back to standby
condition.
Technical data
General features Dimensions in mm (wide x height x depth)
134 x 85 x 27cm
Aprox. Weight (gr.) 125gr Temperature and relative humidity
without condensation.
00 - 500C 10% - 90%
Standards CE EN50130-4 9 EN61000-6-3 9 89/336/EEC 9 93/68/EWG 9
Electrical features Supply voltage 11 - 14V. Stand-by consumption (with no detectors)
35 - 45mA
Max. consumption <200mA Establishment timing since rearming <500ms. Delay timing of alarm signal <300ms
Output features Alarm output by voltage-free contacts C NO NC
30Vd.c. 1A
Fault output by voltage-free contacts C-NO or C-NC
30Vd.c. 1A
Line characteristics for PU1 and PU2 for non-current-limited detectors OFF
Power supply voltage 11 - 14V Line voltage with detectors in stand-by, 17.5 - 22.5V Line voltage in alarm condition 6 - 10V. Line consumption to indicate alarm 18 - 56mA. Line consumption to indicate short­circuit.
59 - 65mA
Line consumption to indicate open­circuit
<4mA
Maximum consumption of stand-by detectors
<4mA
End-of-line resistor 2K7 Ohm 1/2W
+/-10%
Line characteristics for PU1 and PU2 for current-limited detectors ON
Line voltage with detectors in stand-by 11 -14V Line voltage in alarm condition 18.5 - 24V Line consumption to indicate alarm 17 - 22.5V Line consumption to indicate short­circuit.
25 - 58mA
Line consumption to indicate open­circuit
60 - 75mA
Maximum consumption of stand-by detectors
<4mA
End-of-line resistor 2K7 Ohm 1/2W
+/-10%
Details for ordering
Type Part no Designation
MGEN2 9300170001 Fire detection panel
PCB
GEN2-DE 9300150001 Fire detection panel
German
GEN2-EN 9300110001 Fire detection panel
English
GEN2-ES 9300100001 Fire detection panel
Spanish
GEN2-PL 9300090001 Fire detection panel
Polish
GEN2-IT 930012.0-001 Fire detection panel
Italian
GEN2­SV(SE)
9300130001 Fire detection panel
Swedish
GEN2-FR) 9300180001 Fire detection panel
French
GEN2-NL 9300190001 Fire detection panel
Netherlands
GEN2-NO 9300140001 Fire detection panel
Norwegian
Loading...