
Technical Instructions
Document No. 155-717
September 25, 2018
SKB/C/D 62UA Series
Electronic Valve Actuator 24 Vac
Proportional Control
Advanced Features
The Flowrite 599 Series SKB/C/D62UA Electronic Valve Actuator requires a 24 Vac
supply and receives a 0 to 10 Vdc or a 4 to 20 mA control signal to proportionally control
a valve. This actuator is designed to work with valves with a 3/4-inch (20 mm) or 1-1/2inch (40 mm) stroke.
• Direct-coupled installation requires no special tools or adjustments
• Visual and electronic stroke indication
• Die-cast aluminum housing
• Manual override
• Spring return to fail-safe position
• Automatic stroke calibration
• Direct or reverse acting
• Adjustable start and span
• Stroke limit control
• Choice of linear or equal-percentage flow characteristic
• Maintenance-free
These electronic actuators are designed to be used with Flowrite 599 Series valves with
either 3/4-inch (20 mm) stroke (SKB/D) or a 1-1/2 inch (40 mm) stroke (SKC) in liquid
and steam service applications; or other manufacturer's valves with appropriate
Universal Valve Linkage Kits.

Technical Instructions Flowrite 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features
Document Number 155-717
September 25, 2018
Page 2 Siemens Industry, Inc.
Table 1. Product Numbers.
Warning/Caution Notations
Personal injury or loss of life may occur if you do not
perform a procedure as specified.
Equipment damage or loss of data may occur if you
do not perform a procedure as specified.
Operating voltage (SELV,PELV) 24 Vac ± 20%
Frequency 50 or 60 Hz
Power consumption
SKB62UA 17 VA/12W
SKC62UA 28 VA/20W
SKD62UA 17 VA/12W
Type of control (proportional) 0 to 10 Vdc; 4 to 20 mA;
or 0 to 1000 ohms
Running time Opening: Closing:
SKB62UA 120 seconds 15 seconds
SKC62UA 120 seconds 20 seconds
SKD62UA 30 seconds 15 seconds
Spring-return time Closing:
SKB62UA 15 seconds
SKC62UA 20 seconds
SKD62UA 15 seconds
Nominal stroke
SKB62UA 3/4-inch (20 mm)
SKC62UA 1-1/2-inch (40 mm)
SKD62UA 3/4-inch (20 mm)
Position force
SKB/C 62UA 2800N
SKD62UA 1000N

Flowrite 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features Technical Instructions
Document Number 155-717
September 25, 2018
Siemens Industry, Inc. Page 3
Terminal Y
Voltage 0 to 10 Vdc
Input impendence 100K ohm
Current 4 to 20 mA
Input impedance 240 ohm
Signal resolution <1%
Hysteresis <1%
Terminal Z
Resistance 0 to 1000 ohm
Override control functions
Z not connected No function (priority at Terminal Y)
Z connected directly to G Maximum stroke 100%
Z connected directly to G0 Minimum stroke 0%
Z connected to M via 0 to 1000 ohm Linear or equal percentage
Terminal U
Voltage 0 to 9.8 Vdc ± 2%
Load impedance >500 ohm
Current 4 to 19.6 mA ± 2%
Load impedance <500 ohms
Media temperature
SKD 20°F to 300°F (-7°C to 150°C)
SKB/C 20°F to 337°F (-7°C to 170°C)
Operation To IEC 721-3-3
Environmental conditions Class 3K5
Temperature
SKD 5°F to 122°F (-15°C to 50°C)
SKB/C 5°F to 130°F (-15°C to 55°C)
Humidity 5% to 95% rh
Transport To IEC 721-2-1
Environmental conditions Class 3K5
Temperature 22°F to 149°F (-5°C to 65°C)
Humidity <95% rh
Storage To IEC 721-3-1
Environmental conditions Class 1K3
Temperature
SKD 5°F to 122°F (-15°C to 50°C)
SKB/C 5°F to 130°F (-15°C to 55°C)
Humidity 5% to 95% rh
UL Listed to UL873
C-UL Certified to Canadian standard
C22.2 No. 24-93
Meets CE requirements:
EMC Directive 89/336/EEC
C-tick N474
Protection standard IP54 to EN 60 529
Protection Class III to EN 60 730

Technical Instructions Flowrite 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features
Document Number 155-717
September 25, 2018
Page 4 Siemens Industry, Inc.
Materials
Actuator housing and bracket Die-cast aluminum
Housing box and manual adjustor Plastic
Conduit opening 1/2-inch NPSM
Dimensions See Figure 23, Figure 24, Figure 25
and Figure 26.
Weight
SKB62UA 18.9 lbs (8,60 kg)
SKC62UA 22.5 lbs (10,00 kg)
SKD62UA 8.5 lbs (3,85 kg)
NEMA Rating NEMA 1 (Interior only)
See Accessories
Direction of Operation
Direct acting / reverse acting 0 to 10 Vdc; 10 to 0 Vdc
4 20 mA; 20 to 4 mA
0 to 1000 ohm/1000 to 0 ohm
Stroke Limit Control
Range of lower limit 0% to 45% adjustable
Range of upper limit 100% to 55% adjustable
Sequence Control
Starting Point of Sequence (Start) 0 to 15V adjustable
Operating Range of Sequence (Span) 3 to 15V adjustable
Figure 1. Auxiliary Switch.
ASC1.6 Auxiliary switch
• Sends a signal to indicate that the valve is
in the 0% stroke position.
• The switching point is fixed at the 0%
stroke position.
Switching capacity 24 Vac
4A resistive,
2A inductive
Lowest recommended current 10 mA
Figure 2. Stem Heating Element.
ASZ6.6 The stem heating element prevents
the formation of ice on the stem when the
medium temperature drops below 32°F (0°C).
It is suited for universal use with valves having
a stem or spindle diameter of 10 or 14 mm.
Operating voltage 24 Vac/dc ± 20%
Power consumption ≤ 40 VA/30W
Figure 3. SKB/C Weather Shield.
599-10065 The SKB/C actuator is UL listed to
meet NEMA Type 3R requirements (a degree
of protection against rain, sleet, and damage
from external ice formation) when installed with
this weather shield and outdoor-rated conduit
fittings in the vertical position. See Service Kits
for replacement ultraviolet resistant cable ties.

Flowrite 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features Technical Instructions
Document Number 155-717
September 25, 2018
Siemens Industry, Inc. Page 5
Figure 4. SKD Weather Shield.
599-10071 The SKD actuator is UL listed to
meet NEMA TYPE 3R requirements (a degree
of protection against rain, sleet, and damage
from external ice formation) when installed with
this weather shield and outdoor-rated conduit
fittings in the vertical position. See Service Kits
for replacement ultraviolet resistant cable ties.
Figure 5. Valve Retrofit Kit.
Universal Retrofit Kit
Kit contains the parts needed to adapt a valve
to the following Siemens 599 Series Flowrite
actuators: SKB, SKC, SKD, SQX. Selected
valves from the following manufacturers can
also be accommodated: Honeywell, Johnson
Controls, and Siebe. See your local Siemens
representative for details.
Circuit board replacement 4 668 5751 8
Manual override kit 4268 5510 8
Plastic wiring compartment cover 4 104 5582 8
Stem retainer kit
Contains one stem nut (Figure 7, Item 6) and one stem retainer clip.
2-1/2 and 3-inch valves 599-10048
4, 5, and 6-inch valves 599-10049
Retainer clamp kit 599-10200
Ultraviolet (UV) resistant cable ties (pkg. of 8) 538-994
WARNING:
This product contains a spring under high compression. Do not
attempt to disassemble the actuator.
Figure 6. SKB/C Valve Parts.
1. Manual Adjuster
2. Pressure Cylinder
3. Piston
4. Reservoir
5. Pressure Chamber
6. Pump
7. Return Spring
8. Bypass Valve
9. Coupling
10. Valve Stem
11. Inner Valve
12. Position Indicator (0 to 1)

Technical Instructions Flowrite 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features
Document Number 155-717
September 25, 2018
Page 6 Siemens Industry, Inc.
Figure 7. SKD Valve Parts.
1. Pressure cylinder
2. Piston
3. Oscillating pump
4. Return spring
5. Bypass valve
6. Valve stem retainer
7. Manual override knob
8. Position indicator
Figure 8. SKB/C Valve Stem Travel Indication.
Figure 9. SKD Valve Stem Travel Indication.
The actuator accepts a 0 to 10 Vdc or a 4 to 20 mA control signal. The actuator
mounted on a valve produces a stroke proportional to the input signal. When power is
turned off or in the event of a power failure, the actuator spring returns the valve to its
normal position.

Flowrite 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features Technical Instructions
Document Number 155-717
September 25, 2018
Siemens Industry, Inc. Page 7
Mounting and
Installation
The vertical position is the recommended position for mounting and the only position for
NEMA Type 3R rating with the Weather Shield. Acceptable mounting positions are shown
in Figure 10.
Figure 10. Acceptable Mounting Positions.
Allow four inches (100 mm) around the sides and back of the actuator and eight inches
(200 mm) above and to the front of the actuator.
See dimensions in Figure 23, Figure 24, Figure 25, and Figure 26.
Detailed installation instructions for field mounting are shipped with the actuator.
CAUTION:
When removing the knockout do not damage the circuit board. Use
the top knockout position, if possible.
Check the wiring for proper connections.
NOTE: The valve body assembly determines the complete assembly action.
All SKB/C/D62UA actuators are factory-fitted with a spring-return function. If the control
signal or power supply fails, the actuator will return to the 0% stroke position (stem fully
retracted).
The override control input (Z) has three modes of operation:
NOTE: The Z-modes have a "direct acting" factory setting.

Technical Instructions Flowrite 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features
Document Number 155-717
September 25, 2018
Page 8 Siemens Industry, Inc.
To determine the stroke positions 0% and 100% in the valve, calibration is required when the
valve/actuator are commissioned for the first time. The actuator must be mechanically
connected to a valve and must have a supply voltage of 24 Vac. The calibration procedure can
be repeated as often as necessary
CAUTION:
Before starting calibration, be sure that the manual adjuster is set to Automatic for
the actual values to register.
There is a slot on the printed circuit boards for the actuators. To
initiate the calibration procedure, the contacts inside this slot must
be short-circuited (possibly with a screwdriver). See Figure 11.
Automatic calibration proceeds as follows (see Figure 12):
• Actuator runs to the 0% stroke position (1), the green LED
flashes.
• Actuator then runs to the 100% stroke position (2), the
green LED flashes.
• Measured values are stored in the EPROM.
• The actuator now moves to the position defined by control
signal Y or Z (3), and the green LED now glows steady
(normal operation).
• Throughout this procedure, output U is inactive, meaning
the values only represent actual positions when the green
LED stops flashing and remains on continuously.
Figure 12.
Automatic Calibration.
Stroke calibration In
Progress
Wait for calibration to be
completed (LED stops flashing)
Faulty stroke calibration
Internal Error
- Check mounting
- Restart stroke calibration (by
short-circuiting calibration slot)
- Replace electronics
• No power supply
• Faulty electronics
- Check mains
- Replace electronics

Flowrite 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features Technical Instructions
Document Number 155-717
September 25, 2018
Siemens Industry, Inc. Page 9
Start-up, Continued
Advanced Features
DIP Switches
(From Left to Right)
1
Select
Direction of
Operation
2
Sequence Control
or
Stroke Limit Control
3
Selection of
Control
Signal
4
Selection of
Flow
Characteristic
*Changing the default setting will modify an equal percentage valve to a linear flow characteristic. When
set to default, the flow characteristic is determined by the valve body.

Technical Instructions Flowrite 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features
Document Number 155-717
September 25, 2018
Page 10 Siemens Industry, Inc.
Start-Up,
continued
Selecting the
Direction of
Operation
• With normally-closed valves, "direct-acting" means that with a 0 Vdc signal input, the valve
is closed.
• With Normally-open valves, "direct-acting" means that with a 0 Vdc signal input, the valve
is open.
Figure 14. Direction of Operation.
Sequence Control
or Stroke Limit
Control
Check the wiring for proper connections.
NOTE: The valve body assembly determines the complete assembly action.
Setting the Stroke Limit Control
Setting the Sequence Control
The rotary switches LO and UP can be
used to apply an upper and lower limit
to the stroke in increments of 3% up to
a maximum of 45%.
The rotary switches LO and UP can be used
to determine the starting point (Start) or the
operating range of a sequence (Span).
Starting
Point for
Sequence
Control
Operating
Range of
Sequence
Control
*The smallest adjustment is 3 Vdc; Control with 0 to
3 Vdc is possible only via Y.

Flowrite 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features Technical Instructions
Document Number 155-717
September 25, 2018
Siemens Industry, Inc. Page 11
Start-up, continued
Normally Closed Valve
When actuator pressure cylinder:
Moves outward (0 to 1): Valve opens.
Moves inward (1 to 0): Valve closes.
When actuator pressure cylinder:
Moves outward (0 to 1): Valve closes.
Moves inward (1 to 0): Valve opens.
When actuator pressure cylinder:
Moves outward (0 to 1): Valve opens between port NC and C.
Moves inward (1 to 0): Valve opens between ports NO and C.
The measuring voltage at terminal U provides valve stem position feedback to an
indicating instrument or building automation system.
Figure 15. SKB/C Manual
Operation.
Figure 16. SKD Manual Operation.
Turn the manual setting knob clockwise for
manual operation. As you begin to turn, a red
indicator becomes visible. Each complete
revolution (360°) is equal to 3/32-inch (2.5 mm)
stroke.
NOTE: If a signal is sent to the actuator while it is in manual operation, the actuator
will move, but the control will not be accurate. The valve cannot be
commanded to its 0% position while in manual operation.

Technical Instructions Flowrite 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features
Document Number 155-717
September 25, 2018
Page 12 Siemens Industry, Inc.
Start-up, Continued
Automatic Operation
SKB/C
When returning to automatic control, you must turn the crank arm of the manual
setting knob counterclockwise until the red numbers disappear. It is essential that the
window is clear and the crank arm is snapped into position. See Figure 17.
Figure 17. SKB/C Automatic Operation.
For automatic operation, the manual override knob must be in the fully closed
position. Turn the manual override knob counterclockwise until the red indicator
disappears.
CAUTION:
The manual adjuster must be rotated
counterclockwise to the end stop until
the red indicator marked MAN is no
longer visible.

Flowrite 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features Technical Instructions
Document Number 155-717
September 25, 2018
Siemens Industry, Inc. Page 13
Do not use auto-transformers. Use earth ground isolating step-down Class II power
supplies.
Determine supply transformer rating by summing total VA of all actuators used.
Determine the rating for Class 2 step-down transformer is 100 VA and consider the
following requirements:
SKB62UA = 17 VA SKC62UA = 28 VA SKD62UA = 17 VA;
A maximum of four actuators can be powered by one transformer (80% of transformer
VA). Operating more than four SK series actuators requires additional transformers or
separate 100 VA power supplies.
The position output signal U will switch from 0 to 10 Vdc to 4 to 20 mA when a 4 to
20 mA input signal is selected and used on the Y terminal.
Figure 19. Terminal Connections.
Control input signal 0 to 10 (30) Vdc or 4 to 20 mA
Position indication 0 to 10 Vdc or 4 to 20 mA (see Table 1)
Figure 20. Auxiliary Switches.
Table 1. Actuator Output Signal U.

Technical Instructions Flowrite 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features
Document Number 155-717
September 25, 2018
Page 14 Siemens Industry, Inc.
Wiring Diagrams, Continued
System potential (SP) black
Figure 21.
Auxiliary Switch
ASC1.6.
Figure 22.
Stem Heating Element
ASZ6.6.
Dimensions
Figure 23. Dimensions of 599-10065 SKB\C Weather Shield in Inches (Millimeters).

Flowrite 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features Technical Instructions
Document Number 155-717
September 25, 2018
Siemens Industry, Inc. Page 15
Figure 24. Dimensions of 599-10071 SKD Weather Shield in Inches (Millimeters).
Figure 25. Dimensions of SKB/C Weather Shield, 599-10071 in Inches (Millimeters).

Technical Instructions Flowrite 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features
Document Number 155-717
September 25, 2018
Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as
design improvements are introduced. Flowrite is a trademark of Siemens Industry, Inc. Other product or company names mentioned herein may
be the trademarks of their respective owners. © 2018 Siemens Industry, Inc.
Siemens Industry, Inc.
Building Technologies Division
1000 Deerfield Parkway
Buffalo Grove, IL 60089
USA
+ 1 847-215-1000
Your feedback is important to us. If you have comments about this
document, please send them to
sbt_technical.editor.us.sbt@siemens.com
Document No. 155-717
Printed in the USA
Page 16
Figure 26. Dimensions of SKD Actuator in Inches (Millimeters).