Transmitt al, reproduction, dissemination and/or editing of this doc ument as well as
utilization of its contents and communication thereof to others without expr ess
authorization are prohibited. Offenders will be held liable for payment of damages.
All rights creat ed by patent grant or registration of a utility model or design patent
are reserved.
Issued by:
Siemens Switzerland Ltd.
Building Technologies Div ision
International Headquarters
Gubelstrasse 22
CH-6301 Zug
Tel. +41 41 724-2424
www.siemens.com/buildingtechnologies
8.3Environ mental compatib ility and dispo sal ........................................................ 51
Glossa ry ...................................................................................................................... 5 2
Index ....................................................................................................................... 53
4
Building TechnologiesA6V10227635_g_en_--
Fire Safety2015-03-11
Applicable documents
1About this document
Goal and purpose
This document contains all information on the radio fire detector FDOOT271.
Following the instruc tions consistently will ensure that the product can be used
safely and without any problems.
Intended use
The radio fire detector FDOOT271 may only be used in a detector base FDB271
and together with a radio gateway FDCW241 in a fire detection system
FS20/FS720.
Target groups
The information in this document is intended f or the following target groups:
Target groupActivityQualificat ion
About this document
1
Product Manager
Project Manager
Project engineer
Installation personnel
Maintenance personnell Carries out all maintenance work.
l Is responsible for information passing
between the manufacturer and regional
company.
l Coordinates the flow of information
between the individual groups of people
involved in a project.
l Coordinates the deployment of all
persons and resources involved in the
project according to schedule .
l Provides the information required to run
the project.
l Sets parameters for product depending
on specific national and/or customer
requirements.
l Checks operability and approves the
product for commissioning at the place
of installation.
l Is responsible for trouble-shooting.
l Assembles and installs the product
components at the place of installation.
l Carries out a performance check
following installation.
l Checks that the products are in perfect
working order.
l Searches for and corrects malfunctions.
l Has obtained suitable specialist training
for the function and for the products.
l Has attended the tr aining courses for
Product Managers.
l Has obtained suitable specialist training
for the function and for the products.
l Has attended the tr aining courses for
Project Managers.
l Has obtained suitable specialist training
for the function and for the products.
l Has attended the tr aining courses for
Product Engineer.
l Has received specialist tr aining in the
area of building installation technology
or electrical installations.
l Has obtained suitable specialist training
for the function and for the products.
Building TechnologiesA6V10227635_g_en_-Fire Safety2015-03-11
Source language and reference document
l The source/original language of this document is German (de).
l T he reference version of this document is the international version in English.
The international ver sion is not localized.
5
About this document
Applicable documents
The 'i' symbol identif ies supplementary information and tips for an easier way of
1
Document identification
The document ID is structured as follows:
ID codeExamples
ID_ModificationIndex_Language_COUNTRY
The date format in the document corresponds to the recomm endation of
international standard ISO 8601 (format YYYY-MM-DD).
Conventions for text marking
Markups
Special markups are shown in this document as follows:
⊳Requirement for a behavior instruction
1.
2.
–Version, option, or detailed information for a behavior instruction
⇨Intermediate result of a behavior instruction
⇨End result of a behavior instruction
l
Behavior instruction with at least two operation sequences
Numbered lists and behavior instructions with an operation
sequence
[➙ X]Reference to a page number
'Text'Quotation, reproduced identically
<Key>Identificat ion of keys
>
In addition to relation symbols and for identif ication between steps
in a sequence, e.g., 'Menu bar' > 'Help' > 'Help topics'
↑ Te xtIdentif ication of a glossary entry
Supplementary information and tips
working.
6
Building TechnologiesA6V10227635_g_en_--
Fire Safety2015-03-11
Applicable documents
1.1Applicable documents
You will also find inform ation about search variants and links to mobile
Document IDTitle
About this document
1
001508
008331List of compatibility (for 'Sinteso™' product line)
009409
010030Application guideline Sinteso Fire detectors
A6V10208552Installation Detector locking device FDBZ293
A6V10227631Planning Radio fire detection system SWING
A6V10227637
Guidelines Connection factors, line resistances and
capacitances for fire detection systems collective, AnalogPLUS,
interactive, FDnet
Data sheet Colored detectors, bases and base attachment
FDO.., FDOOT…, FDT…, FDB…
Installation Radio fire detector FDOOT271, Detector base
FDB271
Data sheet SWING Neural radio fire detector FDOOT271,
FDCW241
1.2Download center
You can download various types of documents, such as data sheets, installation
instructions, and license texts v ia the following Internet address:
http://siemens.com/bt/download
l Ent er the document ID in the 'Find by keyword' input box.
applications (apps) for various systems on the home page.
1.3Technical terms
TermExplanation
AIAlarm indicator
Battery emptyFault message in the event of a battery failing completely
Battery lowFault message in the event that the spare battery is activated
FDnet/C-NETAddressed detector line
LEDLight-emitting diode
Building TechnologiesA6V10227635_g_en_-Fire Safety2015-03-11
7
About this document
Revision history
The first edition of a language version or a country variant may, for example, be
The language versions and country variants pr oduced by a local comp
any have
1
1.4Revision history
The reference docum ent's version applies to all languages into which the reference
document is trans lated.
version 'd' inst ead of 'a' if the reference document is already this version.
The table below shows this document's revision history:
Modification index Edition dateBrief description
g2015-03-11
f2014-01-31
e2013-09-01Changes in chapter: Planning, Technical data
l Detector base seal RS720 added; mounting marking in 'Mechanical
setup' chapter removed
l Flashing behavior table added
l Editorial changes
Changes in chapter: Parameter sets for FDOOT271; data sheet in
'Applicable documents' chapter added; reference to approvals added;
information on flashing pattern and sensory added; chapter with reference
to download center added; neural fire detector function added; value for
response sensitivity change d
Note on service devices added
the same modification index as the corresponding reference document. They are
not however included in the t able below.
The table below shows the published language versions and count ry variants with
the corresponding modif ication index:
Modification index en_--de_--fr_--it_--es_--
gXXXXX
f–X–––
eXXXXX
d–X–––
cXXXXX
bXXXXX
a–X–––
X = published
– = no publication with this modification index
8
Building TechnologiesA6V10227635_g_en_--
Fire Safety2015-03-11
Safety instructions
2Safety
2.1Safety instructions
The safety notices mus t be observed in order to protect people and property.
The safety notices in this document contain the following elements:
l Symbol for danger
l Signal word
l Nature and origin of the danger
l Consequences if the danger occurs
l Measures or prohibitions for danger avoidance
Symbol for danger
This is the symbol for danger. It warns of risks of injury.
Follow all measures ident ified by this symbol to avoid injury or deat h.
Additional dan ger symbols
These symbols indic ate general dangers, the type of danger or poss ible
consequences, measures and prohibitions, examples of which are shown in the
following table:
Safety
2
General dangerExplosive atmosphere
Voltage/electric shockLaser light
BatteryHeat
Signal word
The signal word classifies the danger as defined in the following table:
Signal wordDanger level
DANGER
WARNING
CAUTION
NOTICE
DANGER identifies a dangerous situation, which will result directly in deat h or
serious injury if you do not avoid this situation.
WARNING identifies a dangerous situation, which may result in death or serious
injury if you do not avoid this situation.
CAUTION identif ies a dangerous situation, which could result in slight to
moderately serious injury if you do not avoid this situation.
NOTICE
observance.
identifies possible damage to property that may result from non-
Building TechnologiesA6V10227635_g_en_-Fire Safety2015-03-11
9
2
Safety instructions
Nature and origin of the danger
Nature and origin of the danger
●
Measures / prohibit ions for danger av
oidance
Safety
How risk of injury is presented
Information about the risk of injury is shown as follows:
WARNING
Consequences if the danger oc curs
● Meas ures / prohibitions for danger avoidance
How possible damage to property is presented
Information about possible damage to property is s hown as follows:
NOTICE
Consequences if the danger oc curs
10
Building TechnologiesA6V10227635_g_en_--
Fire Safety2015-03-11
Safety
Safety regulations for the method of operation
Electrical volt age
regulations.
2.2Safety regulations for the method of operation
National standards, regulations and legislation
Siemens products ar e developed and produced in compliance with the relevant
European and international safety standards . Should additional national or local
safety standards or legislation concerning the planning, mounting, inst allation,
operation or disposal of the product apply at the place of operation, then these
must also be taken into account together with the safety regulations in the product
documentation.
Electrical installations
WARNING
Electric shock
● Work on electrical installations may only be carried out by qualified
electricians or by instructed persons work ing under the guidance and
supervision of a qualified electrician, in accordanc e with the electrotechnical
2
l W herever possible disconnect products from the power supply when carrying
out commissioning, maintenance or repair work on them.
l Lock volt-free areas to prevent them being switched back on again by mistake.
l Label the connection terminals with external external voltage using a
'DANGER External voltage' sign.
l Rout e mains connections to products separately and fuse them with their own,
clearly marked fuse.
l F it an easily accessible disconnecting device in accordance with IEC 60950-1
outside the installation.
l Produce earthing as stated in local safety regulations.
Mounting, installation, commissioning and maintenance
l If you require tools such as a ladder, these must be safe and must be intended
for the work in hand.
l W hen starting the fire control panel ensure that unstable conditions cannot
arise.
l Ensure that all points listed in the 'Testing the product operability' section below
are observed.
l You may only set controls to normal function when the product operability has
been completely tested and the system has been handed over to the customer.
Building TechnologiesA6V10227635_g_en_-Fire Safety2015-03-11
11
2
Safety regulations for the method of operation
Safety
Testing the product operability
l Prevent the remot e transmis sion from t riggering erroneously.
l I f testing building installations or activating devices from third-party companies,
you must collaborate with the people appointed.
l T he activation of fire control installations for test purposes must not cause
injury to anyone or damage to the building installations. The following
instructions m ust be observed:
– Use the correct potential for activation; this is generally the potential of the
building installation.
– Only check controls up to the interface (relay with blocking option).
– Make sure that only the controls to be tested are activated.
l I nform people before testing the alarm devices and allow for possible panic
responses.
l I nform people about any noise or mist which may be produced.
l Bef ore testing the remote transmission, inform the corresponding alarm and
fault signal receiving stations.
Modifications to the system design and the products
Modifications to the system and to individual products m ay lead to faults,
malfunctioning and safety risks. Written confirmation must be obtained from
Siemens and the corresponding safety bodies for m odifications or additions.
Modules and spare parts
l Components and spare parts must comply with the technical specifications
defined by Siemens. Only use products specified or recommended by
Siemens.
l Only use fuses with the specified fuse charact eristics.
l Wrong battery types and improper battery changing lead to a risk of explosion.
Only use the same battery type or an equivalent battery t ype recommended by
Siemens.
l Bat teries must be disposed of in an environmentally friendly manner. Observe
national guidelines and regulations.
Disregard of the safety regulations
Before they ar e delivered, Siemens products ar e tested to ensure they function
correctly when used properly. Siemens disclaims all liability for damage or injuries
caused by the incorrec t application of the instructions or the disregard of danger
warnings contained in the documentation. This applies in particular to the following
damage:
l Per sonal injuries or damage to property caused by improper use and incorrect
application
l Per sonal injuries or damage to property caused by disregarding safety
instructions in the documentation or on the product
l Personal injury or damage to property caused by poor maintenance or lack of
maintenance
12
Building TechnologiesA6V10227635_g_en_--
Fire Safety2015-03-11
Standards and directives complied with
2.3Standards and directives complied with
Limited or non
-
existent fire detection
detection installation.
Incorrect planning and/or configurat ion
A list of the standards and directives complied wit h is available from your Siemens
contact.
2.4Release Notes
Limitations t o the configuration or use of devices in a fire detection installation with
a particular firmware version are possible.
WARNING
Personal injury and damage to property in the event of a fire.
● Read the 'Release Notes' before you plan and/or configure a fire detection
installation.
● Read the 'Release Notes' before you carry out a firmware update to a fire
Safety
2
NOTICE
Important st andards and specifications are not satisfied.
Fire detection installation is not accepted f or commissioning.
Additional expense result ing from necessary new planning and/ or configuration.
● Read the 'Release Notes' before you plan and/or configure a fire detection
installation.
● Read the 'Release Notes' before you carry out a firmware update to a fire
detection installation.
Building TechnologiesA6V10227635_g_en_-Fire Safety2015-03-11
13
Structure and function
Overview
3
3Structure and functio n
In this document, the term 'detector' refers to an automatic fire detector that
communicates with a radio gateway and other radio devices in a radio cell using
radio signals. The detector is connected to a cont rol panel FC20xx or FC72x via
the radio gateway and the detector line.
3.1Overview
Properties
l Radio communication with:
– Radio gateway
– Other radio devices
l Signal processing with ASAtechnology and opt ional detection behavior
l Int ernal alarm indicator with status display (red and green):
– identifies alarm
– confirms positioning on detector base
– confirms contact with the radio network
l Easy installation on t he detector base
14
Building TechnologiesA6V10227635_g_en_--
Fire Safety2015-03-11
Overview
3.1.1Details f or orderi ng
The battery pack and det ector base are not included in the scope of deliver y. A
ES
Depending on the product and various approvals, the product labels may differ in
TypeOrder no.Designation
FDOOT271S54313-F1-A1Radio fire detector
FDOOT271
battery pack and detector base are required for commissioning and operation.
3.1.2Product version ES
The product version ES provides the technical stat us of a device in t erms of
software and hardware. The product version is provided as a two-digit number.
You will find the det ails of your device's product ver sion:
l On the packaging label
l On the product label or the type plate
S54313-F1-A2 +
RAL no.
Structure and function
Radio fire detector (colored)
3
Product version on the packaging label
Details of the product version can be found directly on the pac kaging label in the
barcode:
Example of a packaging label with details of the product version
Product version on the product label and t he type plate
Details of the product version can be found after the device order number:
04
ES
Example of a product label with details of the product version
terms of the informat ion type and layout.
Look for your device' s order number on the product label.
You will find the produc t version after the order number.
Building TechnologiesA6V10227635_g_en_-Fire Safety2015-03-11
15
Structure and function
Overview
3
3.1.3Features of fire detection functions
The FDOOT271 has the following features in terms of its fire detection functions:
l Dynamic influence on t he parameter sets
l Pattern recognition
l Real time interpretation of t he situat ion
l Process- and time-controlled switchover of the parameter sets
Signal processing is based on ASAtechnology (ASA = Advanced Signal Analysis).
ASAtechnology can als o be characterized as second generation algorithms. Signal
processing with ASAtechnology allows for opt imum adaptation of detector behavior
to the corresponding ambient conditions.
The detectors are char acterized by their unique detect ion reliabil ity and high
immunity to deceptive phenomena.
Operating mode: Signal processing with ASAtechnology
The figure below shows signal processing in the form of a diagram.
Environment
Evaluation of the
situation
C
Signal analysisSensory
Signal processing with ASAtechnology
Algorithms
Dynamic influence
of parameter
Danger
level
Result
16
Building TechnologiesA6V10227635_g_en_--
Fire Safety2015-03-11
Overview
Sensory
2
3
4
The signals captured by the sensory are transmitted to the algorithm. The
algorithms are set by selec t ing the parameter set.
Algorithms
In comparison t o the det ection algorithms, the individual parameters of the selected
parameter set can be adapted with ASAtechnology. A real time interpretation of the
situation leads t o a dynamic influence on the algorithm. This results in a
broadening of the application range of the parameter set and thus of the detector.
The detector reacts more sensitively in the event of fire, and more robustly in the
event of deceptive phenomena.
Switching over the parameter set
In addition to selec ting the parameter set, the detectors enable time- or processcontrolled switching over of the parameter sets (M anned/Unmanned s witchover).
Thanks to this function, the detector can be us ed in places where the situation
changes significant ly on a regular basis (e.g., kitchen, production hall).
3.1.4Sens ory
The radio fire detector has optical and thermal sensors. T he radio fire detector can
be parameterized as a smoke detector or a heat detector.
Structure and function
3
1
Fire detector structure
1 Heat sensors3 Forward scatterer
2
Backward scatterer4 Labyrinth
The radio fire det ector has a sophisticated opto-electronic measuring chamber wit h
two optical transmitters, an optical rec eiver, and two thermal sensors.
The transmitt ers illuminate the smoke par ticles from different angles. One sensor
acts as forward scatterer, the other as backward scatterer. The scattered light then
hits the receiver (photodiode) and generates a measurable elect ric signal.
The combination of a forward and backward scatt erer facilitates an optimum
detection and the dif ferentiation of light and dark par ticles, which leads to a
homogenous response behavior and optimizes the differentiation of wanted signals
and deceptive phenomena.
17
Building TechnologiesA6V10227635_g_en_-Fire Safety2015-03-11
Loading...
+ 37 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.