The Model CZM-1B6 from Siemens Industry, Inc.,
is an MXL intelligent device that connects a single
zone of conventional devices to an analog loop.
The CZM-1B6 can power up to fifteen compatible
2-wire, ionization or photoelectric smoke detectors.
It can also monitor an unlimited number of shorting
devices such as waterflow switches, thermal
detectors, manual stations, etc.
Each CZM-1B6 can be assigned a 32 character
custom alphanumeric message. A multicolor LED,
visable through the cover plate, indicates the
condition of the circuit. This multicolor LED displays
red for alarm, yellow for trouble, and green for
normal operation (See Figure 1).
The CZM-1B6 supports Class A and Class B
wiring. The module uses one address on the
analog circuit. It does not require any mechanical
address programming. Use Model DPU Device
Programming Unit or FPI-32 Programmer/Tester to
program and test the module.
For additional information on the MXL/MXLV System,
refer to the MXL/MXLV Manual, P/N 315-092036.
SETTING THE MODULE ADDRESS
INSTALLATION
Remove all system power before installation, first
battery and then AC. (To power up, first connect the
AC and then the battery.)
Electrical Connections
After you have set the CZM-1B6 address, connect the
field wiring.
CZM-1B6. All terminals are power limited.
1. Initiating Devices (Figures 2, 3, and 4)
The CZM-1B6 supports one zone of initiating devices
in either Class A or Class B. The initiating devices are
connected to terminals 5–8 on the CZM-1B6 terminal
block. Figure 2 shows the Class A wiring. Figure 3
shows the Class B wiring.
Figure 4 shows the wiring for the PBA-1191 beam
detector. When the PBA-1191 is used, the 2-position
plug from jumper J1 must be removed. Follow the
steps listed below:
a. Remove the screw from the center of the
b. Remove the circuit board and locate jumper J1.
c. Remove the 2-position plug from J1.
There are three basic connections
CZM-1B6 plastic cover and place it to one side.
to the
1. Using the DPU Device Programming Unit or
FPI-32 Programmer/Tester, plug the
programming cable into the programming
receptacle on the CZM-1B6 (See Figure 1).
2. Set the System address for the CZM-1B6 by
following the instructions in the FPI-32 Programmer/
Tester Manual, P/N 315-090077, or the DPU
User's Manual, P/N 315-033260, as appropriate.
NOTE:With FPI-32 Rev. 1.3 software, only 1=MXL
mode should be used when programming a
device.
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
P/N 315-095355-9
Figure 1
Model CZM-1B6
Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario
L6T 5E4 Canada
Page 2
d. Reassemble the circuit board and plastic cover
)
)ylnOdevorppAMF(efaSyllacisnirtnI
rotceteDesaB
snoitcurtsnInoitallatsnI
rebmuNtraP
1-ISIhtiwSI3-IDS3-BD81-34
9180-513
using the screw that was removed in the first
step.
e. Be sure to use the correct end of line device with
the CZM-1B6 in this configuration.
The devices in the tables at the right are listed for use
with the CZM-1B6. Use up to fifteen detectors, any
combination of those listed. Only one PB-1191 or one
DF-1192, and no additional devices, can be connected
to a CZM-1B6. Detector operated accessories cannot
be used with the CZM-1B6. The model numbers listed
are the UL compatibility identifiers.
STYLE D
(CLASS A)
WIRE MINIMUM 18 AWG, 35 ohms MAX
SUPERVISED, POWER
LIMITED PER NEC 760
VOLTAGE 24V UNFILTERED FULL WAVE
POWER
ANALOG LOOP
+
+
+
+
+
+
EOL *
-
-
-
-
-
-
EARTH
6B1-MZCrofytilibitapmoC
noitallatsnI
rotceteDesaB
H3/3-IDS3-BD349180-513
H3A/3A-IDS3-BD3
49180-513
H3B/3B-IDI3-DA432390-513
*531-P3-TDS3-BD545710-513
11-TD11-BD
11-ABP1911-BBP424590-513
19
3-EPS3-BD
PLI3-DA
T11/11-EP11-BD
P11-DA
TPDA-BDhtiwS3-BD
TPDA-BDhtiwS3-BD
924590-513
924590-513
578090-513
432390-513
891490-513
891490-513
956590-513
May use up to 15 detectors of any type.
* Only one PBA-1191 or one DF-1192, and no additional
devices, can be connected to a CZM-1B6.
snoitcurtsnI
rebmuNtraP
1
+
3
2
----
+++
5
4
* EOL DEVICE IS 4.7K,1/4W(P/N 140-820188
Figure 2
CZM-1B6 Wiring Diagram (Initiating Devices)
Class A (Style D) Installation
STYLE B
(CLASS B)
WIRE MINIMUM 18 AWG, 35 ohms MAX
SUPERVISED, POWER
LIMITED PER NEC 760
VOLTAGE 24V UNFILTERED FULL WAVE
POWER
ANALOG LOOP
1
+
3
2
-- --
4
+++
+
+
+
+
+
+
5
6789
Figure 3
CZM-1B6 Wiring Diagram (Initiating Devices)
Class B (Style B) Installation
6789
EOL*
*EOL DEVICE IS 4.7K,
1/4W (P/N 140-820188)
-
-
-
-
-
-
EARTH
Positive and negative ground fault detected at
NOTE:
<30K ohms for terminals 5-8 on CZM-1B6.
Figure 4
CZM-1B6 Wiring Diagram
PB-1191 Installation
2
Page 3
2. Analog Loops (See Figure 5)
3. 24 VDC Power (See Figure 6)
The CZM-1B6 communicates with the MXL via its
analog addressable loops. These loops may be on the
MMB or on the optional ALD-2I module. The analog
loops may be wired Class A or Class B. Figure 5
shows both wiring types, as well as the connections to
either the MMB or the MOM-4 when the ALD-2I
module is used.
ALD-2I
LOOP
2
MMB
TB2
MMB
TB3
LOOP1LOOP
2
-
-
1
+
2
+
*OPERATES IN FULL COMFORMANCE WITH STYLE 6
***
-
+
1
2
***
**OPERATES IN FULL COMFORMANCE WITH STYLE 4
***JUMPERS CAN BE REMOVED FROM MMB-3
WITH CSGM CONFIGURATION
MOM-4
TB2
LOOP
LOOP
1
2
488
377
266
155
488
377
266
1
55
MOM-4
TB1
LOOP
1
444
333
222
111
444
333
222
111
NOTE:
Positive and negative ground fault detected at <30K ohms
for terminals 5-8 on CZM-1B6.
CZM-1B6 Wiring Diagram (Analog Loop)
The CZM-1B6 receives its power from the CZM-1B6
power output on the MMB. This power is available on
TB5 of the MMB at terminals 9–12 or TB3 on the
PSR-1 on terminals 3-6. The power may be wired as
Class A or Class B. Since the CZM-1B6 monitors the
power at its screw terminals, you can star or T-tap the
power connection in the Class B configuration only.
Refer to Figure 6 for the wiring diagram.
CLASS A INSTALLATION*
NO T-TAPPING ALLOWED
CZM-1/1B6
3
4
5
6
7
1
8
2
CLASS B INSTALLATION**
T-TAPPING ALLOWED
CZM-1/1B6
3
4
5
6
7
1
8
2
Figure 5
CZM-1/1B6
3
4
5
CZM-1/1B6
3
4
5
2
3
4
CZM-1/1B6
2
3
4
CZM-1/1B6
5
6
7
5
6
7
1
6
7
8
LOOP RESISTANCE 100 Ohms MAX.
ALL WIRE MINIMUM 18 AWG
NO EOL DEVICE REQUIRED
SUPERVISED, POWER LIMITED PER NEC 760
1
6
7
8
CZM-1/1B6
2
3
4
5
6
7
1
8
8
8
PSR-1
TB3
3
4
5
6
3
4
5
6
MMB
TB5
12
11
10
+
+
-
-
4
1
2
3
9
12
11
10
9
*
*
4
1
2
3
+
-
*JUMPERS CAN BE REMOVED FROM MMB-3
WITH CSGM CONFIGURATION
1
NOTE:
Positive and negative ground fault detected at
<30K ohms for terminals 5-8 on CZM-1B6.
CLASS A INSTALLATION
NO T-TAPPING ALLOWED
CZM-1B6
5
7
8
6
CLASS B INSTALLATION
2
9
1
T-TAPPING ALLOWED
CZM-1B6
5
7
8
6
4
5
2
3
9
1
CZM-1B6
6
7
2
8
CZM-1B6
4
3
5
7
8
9
6
CZM-1B6
4
3
5
7
6
8
9
1
2
9
2
1
ALL WIRE MINIMUM 18 AWG
NO EOL DEVICE REQUIRED
SUPERVISED, POWER LIMITED PER NEC 760
1. Mount the CZM-1B6 in a standard two gang
electrical box. The box must have a depth of at
least 3½ inches.
2. When the field wiring is connected (See above),
press the CZM-1B6 into the box and fasten it with
the four screws provided.
3. Attach a dress bezel if necessary, making sure
that the ALARM LED is aligned with the hole in the
bezel.
SAERA1-ISI
LENNAHCEFASSUODRAZAH
+19 5
-18 4
+2212
-2111
01,7,6,3:NOITCENNOCON
INTRINSICALLY SAFE APPLICATION
FM APPROVED ONLY
*THE ISI-1 IS A TWO-CHANNEL INTERFACE.
ONE CHANNEL IS SHOWN CONNECTED.
12
11
10
ISI-1*
9
8
7
1
2
3
4
5
6
tnerruCeludoMCDV5evitcAAm0
tnerruCeludoMCDV42evitcAAm05
tnerruCeludoMCDV42ybdnatSAm5.21
Zone resistance:35 ohms total
6
5
4
ISI-1*
3
2
1
7
8
9
10
11
12
NOTES:
1. Intrinsically Safe Output:
Open Circuit Voltage: 28 VDC
Short Circuit Current: 93mA
2. Maximum loop resistance must not exceed 35 ohms.
3. A maximum of ten DI-3IS Ionization Detectors or up to five
S121 or S122 Flame Detectors can be used in addition to
mechanical (non-energy storing) shorting devices.
4. Maximum safe system voltage is 250 VAC.
5. For mounting and installation of the ISI-1, see the ISI-1
instructions.
6. Only mechanical (non-energy storing) shorting devices
such as the MS-51 Manual Station may be used.
Wiring Diagram of Intrinsically Safe Zone
P/N 315-095355-9
7. WARNING: Do not make any connection to terminal 6
of the DB-3S base. Such a connection would void use
in an intrinsically safe application.
8. In addition, S121 and S122 are also approved for use
in Class II and Class III, Groups E, F, and G.
9. For guidance on installation see ANSI/ISA RP 12.6,
“Installation of Instrinsically Safe Instrument Systems in
Class I Hazardous Locations”.
10. For DI-3IS information, see the DI-3 Series installation
instructions, P/N 315-081943.
11. For S121 and S122 information, see the installation
instructions, P/N 315-085258.
Figure 7