This manual contains notices you have to observe in order to ensure your personal safety, as well as to
prevent damage to property. The notices referring to your personal safety are highlighted in the manual
by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These
notices shown below are graded according to the degree of danger.
Danger
indicates that death or severe personal injury will result if proper precautions are not taken.
Warning
indicates that death or severe personal injury may result if proper precautions are not taken.
Caution
with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not
taken.
Caution
without a safety alert symbol, indicates that property damage can result if proper precautions are not
taken.
Notice
indicates that an unintended result or situation can occur if the corresponding information is not taken into
account.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning
relating to property damage.
Qualified Personnel
The device/system may only be set up and used in conjunction with this documentation. Commissioning
and operation of a device/system may only be performed by qualified personnel. Within the context of
the safety notes in this documentation qualified persons are defined as persons who are authorized to
commission, ground and label devices, systems and circuits in accordance with established safety practices and standards.
Prescribed Usage
Note the following:
Warning
This device may only be used for the applications described in the catalog or the technical description and
only in connection with devices or components from other manufacturers which have been approved or
recommended by Siemens.
Correct, reliable operation of the product requires proper transport, storage, positioning and assembly as
well as careful operation and maintenance.
Trademarks
All names identified by ® are registered trademarks of the Siemens AG. The remaining trademarks in this
publication may be trademarks whose use by third parties for their own purposes could violate the rights
of the owner.
Copyright Siemens AG 2007 All Rights Reserved
The distribution and duplication of this document or the utilization and
transmission of its contents are not permitted without express written
permission. Offenders will be liable for damages. All rights, including
rights created by patent grant or registration of a utility model or
design, are reserved.
Siemens AG
Automation & Drives
Standard Drives
Postfach 3269, 91050 Erlangen
Germany
Disclaimer of Liability
We have reviewed the contents of this publication to ensure
consistency with the hardware and software described. Since
variance cannot be precluded entirely, we cannot guarantee full
consistency. However, the information in this publication is reviewed
regularly and any necessary corrections are included in subsequent
editions.
Indicates the relevant parameter number. The numbers used are 4-digit numbers
in the range 0000 to 9999. Only for PROFINET there are a few parameters in the
range of 61.000. Numbers prefixed with an “r” indicate that the parameter is a
“read-only” parameter, which displays a particular value but cannot be changed
directly by specifying a different value via this parameter number.
All other parameters are prefixed with a “P”. The values of these parameters can
be changed directly in the range indicated by the “Min” and “Max” settings in the
header. If these values have a physical unit, it is shown in brackets.
[index] indicates that the parameter is an indexed parameter and specifies the
range of indices available.
,QGH[
%,&2LIH[LVW
6HOFWLRQRIFRPPDQGVRXUFH&RPPDQGVRXUFHVH
$FFHVVOHYHO
4XLFNFRPP12
&DQEHFKDQJHG7
0LQ
3*URXS&RPPDQGV
$FWLYH<(6
8QLW
0D[
'DWDW\SH8QVLJQHG
'DWDVHW&'6
)DFWRU\VHWWLQJ
schreibparameter.pdf
1-8
.0...15 indicates that the parameter has several bits, which can be evaluated or
connected individually.
SINAMICS G120 Control Units CU240S, Edition 05/2007
Page 9
Parameter text (Long name/Short name)
Indicates the name of the relevant parameter.
Certain parameter names include the following abbreviated prefixes: BI, BO, CI,
CO and CO/BO followed by a colon.
These abbreviations have the following meanings:
BI=
P9999
Binector input, i.e. parameter selects the source of a
(0)
binary signal
Parameters
Introduction to Parameters
BO=
CI=
CO=
CO/BO =
r9999
r9999
(999:9)
r9999 [99]
r9999
r9999
Binector output, i.e. parameter connects as a binary
signal
Connector input, i.e. parameter selects the source of an
analog signal
Connector output, i.e. parameter connects as an analog
signal
Connector/Binector output, i.e. parameter connects as
an analog signal and/or as a binary signal
CoBo.pdf
To make use of BICO you will need access to the full parameter list. At this level
many new parameter settings are possible, including BICO functionality. BICO
functionality is a different, more flexible way of setting and combining input and
output functions. It can be used in most cases in conjunction with the simple,
access level 2 settings.
The BICO system allows complex functions to be programmed. Boolean and
mathematical relationships can be set up between inputs (digital, analog, serial
etc.) and outputs (inverter current, frequency, analog output, relays, etc.).
At BI and CI parameters the parameter number is specified under Factory setting
with which this parameter is connected. In this case the Min and Max values have
dashes.
Access level (refers only to access via Operator Panel (OP))
Indicates the level of user access. There are four access levels: Standard,
Extended, Expert and Service. The number of parameters that appear in each
functional group depends on the access level set in P0003 (user access level).
P-Group (refers only to access via Operator Panel (OP))
Specifies the functional group to which the parameter belongs.
Note:
Parameter P0004 (parameter filter) acts as a filter and focuses access to parameters according to the functional group selected.
The data types available are shown in the table below.
Table 1-1Available data types
NotationMeaning
Unsigned88-bit unsigned
Unsigned1616-bit unsigned
Unsigned3232-bit unsigned
Integer1616-bit integer
Floating PointFloating point
Quick Comm
Indicates whether or not (Yes or No) a parameter can only be changed during
quick commissioning, i.e. when P0010 (parameter groups for commissioning) is
set to 1 (quick commissioning).
Active
Data set
• YESchanges to the parameter values take effective immediately after
they have been entered.
• Nothe “P” button on the Operator Panel must be pressed before the
changes take effect.
Parameters which are dependent on a data set are identified as follows:
SINAMICS G120 Control Units CU240S, Edition 05/2007
Page 11
Can be changed
Unit
Min
Parameters
Introduction to Parameters
Inverter state in which the parameter is changeable. Three states are possible:
• CommissioningC
• RunU
• Ready to runtT
This indicates when the parameter can be changed. One, two or all three states
may be specified. If all three states are specified, this means that it is possible to
change this parameter setting in all three inverter states.
Indicates the unit of measure applicable to the parameter values.
Indicates the minimum value to which the parameter can be set.
Max
Indicates the maximum value to which the parameter can be set.
Factory setting
Indicates the default value, i.e. the value which applies if the user does not specify
a particular value for the parameter.
Description
Explanation of the function of a parameter.
Values
Lists the possible values of a parameter.
Recommendation
Information about recommended settings.
Index
The name and meaning of each individual index is specified for indexed parameters, except indexed parameters which belong to a data set (see Data set).
For parameters with bit fields, the following information is provided about each bit:
• Bit number and signal name
• Meaning with signal states 0 and 1
• Function diagram (optional). The signal is shown on this function diagram.
Dependency
Conditions which need to be fulfilled in connection with this parameter. Also
includes special effects which can occur between this parameter and others.
Seven-segment display
The seven-segment display of the OP is structured as follows:
9 8 11 10 13 12 15 14 Segment Bit
Segment Bit
Fig. 1-3Seven-segment display
1 0 3 2 5 4 7 6
Visio-7-Segment Display.pdf
1-12
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description:Defines user access level to parameter sets. The default setting (standard) is sufficient for most simple applications.
Values:0:User defined parameter list - see P0013 for details on use
1:Standard: Allows access into most frequently used parameters.
2:Extended: Allows extended access e.g. to inverter I/O functions
3:Expert: For expert use only.
4:Service: Only for use by authorized service, password protected
Note:Only valid for control units with OP.
p0004Parameter filter / Parameter filter
CU240E
CU240S
CU240S DP
CU240S PN
Description:Filters parameters according to functionality to enable a more focussed approach to commissioning.
Values:0:All parameters
Access level: 1P-Group: -Data type: Unsigned16
Quick comm. NOActive: NOData set: -
Can be changed: U, T
Min Max Factory setting
0 22 0
2:Inverter
3:Motor
4:Speed sensor
5:Technol. application / units
7:Commands, binary I/O
8:AI and AO
10:Setpoint channel / RFG
12:Drive features
13:Motor control
19:Motor identification
20:Communication
21:Alarms / warnings / monitoring
22:Technology controller
P0003 (user access level) also determines access to parameters.
The inverter can be commissioned very quickly and easily by setting P0010 = 1. After that only the important
parameters (e.g.: P0304, P0305, etc.) are visible. The value of these parameters must be entered one after the
other. The end of quick commissioning and the start of internal calculation will be done by setting P3900 = 1 - 3.
Afterwards parameter P0010 and P3900 will be reset to zero automatically.
•P0010 = 2
For service purposes only.
•P0010 = 29
To transfer a parameter file via PC tool (e.g.: STARTER) parameter P0010 will be set to 29 by the PC tool.
When download has been finished PC tool resets parameter P0010 to zero.
•P0010 = 30
When resetting the parameters of inverter P0010 must be set to 30.
Resetting of the parameters will be started by setting parameter P0970 = 1.
The inverter will automatically reset all its parameters to their default settings.
This can prove beneficial if you experience problems during parameter setup and wish to start again.
Duration of factory setting will take about 60 s.
P0003 (user access level) also determines access to parameters.
Note:•P0010 = 1
The inverter can be commissioned very quickly and easily by setting P0010 = 1. After that only the important
parameters (e.g.: P0304, P0305, etc.) are visible. The value of these parameters must be entered one after the
other. The end of quick commissioning and the start of internal calculation will be done by setting P3900 = 1 - 3.
Afterwards parameter P0010 and P3900 will be reset to zero automatically.
•P0010 = 2
For service purposes only.
•P0010 = 29
To transfer a parameter file via PC tool (e.g.: STARTER) parameter P0010 will be set to 29 by the PC tool.
When download has been finished PC tool resets parameter P0010 to zero.
•P0010 = 30
When resetting the parameters of inverter P0010 must be set to 30.
Resetting of the parameters will be started by setting parameter P0970 = 1.
The inverter will automatically reset all its parameters to their default settings.
This can prove beneficial if you experience problems during parameter setup and wish to start again.
Duration of factory setting will take about 60 s.
•P0010 = 95
For changing the safety parameters select access level 3 and set the safety password. Only then P0010 can be
set to 95. The safety commissioning including safety dynamization will take about 2 s. For finishing the safety
commissioning, see P3900.
p0011Lock for user defined parameter / LockUserDefinedPar
Access level: 3P-Group: -Data type: Unsigned16
Quick comm. NOActive: NOData set: -
Can be changed: C, U, T
Min Max Factory setting
0 65535 0
Note:See parameter P0013 (user defined parameter)
p0012Key for user defined parameter / Key UserDefinedPar
Access level: 3P-Group: -Data type: Unsigned16
Quick comm. NOActive: NOData set: -
Can be changed: C, U, T
Min Max Factory setting
0 65535 0
Note:See parameter P0013 (user defined parameter).
p0013[0...19]User defined parameter / User-defined par
Access level: 3P-Group: -Data type: Unsigned16
Quick comm. NOActive: NOData set: -
Can be changed: C, U, T
Min Max Factory setting
0 65535 0
Description:Defines a limited set of parameters to which the end user will have access.
Instructions for use:
1. Set P0003 = 3 (expert user).
2. Go to P0013 indices 0 to 16 (user list)
3. Enter into P0013 index 0 to 16 the parameters required to be visible in the user-defined list.
The following values are fixed and cannot be changed:
- P0013 index 17 = 3 (user access level)
- P0013 index 18 = 10 (commissioning parameter filter)
- P0013 index 19 = 12 (key for user defined parameter)
4. Set P0003 = 0 to activate the user defined parameter.
Index:[0] = 1st user parameter
Dependency:First, set P0011 ("lock") to a different value then P0012 ("key") to prevent changes to user-defined parameter.
Note:The default values of P0011 ("lock") and P0012 ("key") are the same.
[1] = 2nd user parameter
[2] = 3rd user parameter
[3] = 4th user parameter
[4] = 5th user parameter
[5] = 6th user parameter
[6] = 7th user parameter
[7] = 8th user parameter
[8] = 9th user parameter
[9] = 10th user parameter
[10] = 11th user parameter
[11] = 12th user parameter
[12] = 13th user parameter
[13] = 14th user parameter
[14] = 15th user parameter
[15] = 16th user parameter
[16] = 17th user parameter
[17] = 18th user parameter
[18] = 19th user parameter
[19] = 20th user parameter
Then, set P0003 to 0 to activate the user-defined list.
When locked and the user-defined parameter is activated, the only way to exit the user-defined parameter (and
view other parameters) is to set P0012 ("key") to the value in P0011 ("lock").
SINAMICS G120 Control Units CU240S, Edition 05/2007
Page 19
Parameters
List of Parameters
p0014[0...2]Store mode / Store mode
Access level: 3P-Group: -Data type: Unsigned16
Quick comm. NOActive: NOData set: -
Can be changed: U, T
Min Max Factory setting
0 1 0
Description:Sets the store mode for parameters.
The store mode can be configured for all interfaces listed under "Index".
Values:0:Volatile (RAM)
1:Nonvolatile (EEPROM)
Index:[0] = USS on RS485
Note:An independent store request may be part of the serial communications (e.g. PKE bits 15-12 of USS protocol), set
[1] = USS on RS232
[2] = Fieldbus
by a PLC or PC tools like STARTER. See the table below for an influence on the settings of P0014.
Value of p0014[x]Result
RAM
EEPROM
EEPROM
1. With the BOP the parameter will always be stored in the EEPROM.
2. P0014 itself will always be stored in the EEPROM.
3. P0014 will not be changed by performing a factory reset (P0010 = 30 and P0970 = 1).
4. P0014 can be transferred during a download (P0010 = 29).
When transferring parameter p0014, the inverter uses its processor to carry-out internal calculations. Communications - both via USS as well as via the Fieldbus - are interrupted for the time that it takes to make these calculations.
This can result in the following error messages at the connected SIMATIC S7 control (communications via fieldbus):
•Parameter fault 30
•Drive fault 70
•Drive fault 75
When using STARTER (USS) to commission the drive system, data cannot be entered while these calculations are
being made.
The faults can be acknowledged as soon as the calculations have been completed in the frequency inverter. These
calculations can take up to one minute to complete.
Store request via USS/PROFIBUS
EEPROM
EEPROM
r0018Firmware version / Firmware version
Access level: 1P-Group: ConverterData type: Floating Point
Unit: -Data set: -
Description:Displays version number of installed firmware.
SINAMICS G120 Control Units CU240S, Edition 05/2007
Page 21
Parameters
List of Parameters
r0025CO: Act. output voltage / Act.outp. volt
Access level: 2P-Group: Closed-loop controlData type: Floating Point
Unit: [V]Data set: -
Description:Displays filtered [rms] voltage applied to motor. This value is available filtered (r0025) and unfiltered (r0072).
r0026[0...1]CO: Act. filtered DC-link volt. / Act. fil. Vdc
Access level: 2P-Group: ConverterData type: Floating Point
Unit: [V]Data set: -
Description:Displays filtered DC-link voltage. This value is available filtered (r0026) and unfiltered (r0070).
Index:[0] = Compensation DC voltage Channel
[1] = Measurement/Monitoring DC voltage Channel
Note:r0026[0] = Main DC-link voltage
r0026[1] = Decoupled DC-link voltage for internal supply (e.g. for CU). It depends on the drive topology. If it is not
available it shows the value 0.
r0027CO: Act. output current / Act. outp. cur
Access level: 2P-Group: Closed-loop controlData type: Floating Point
Unit: [A]Data set: -
Description:Displays rms value of motor current [A]. This value is available filtered (r0027) and unfiltered (r0068).
r0029CO: Flux gen. current / Flux gen. cur.
Access level: 3P-Group: Closed-loop controlData type: Floating Point
Unit: [A]Data set: -
Description:Displays flux-generating current component. This value is available filtered (r0029) and unfiltered (r0076).
The flux-generating current component is based on the nominal flux, which is calculated from the motor parameters
(P0340 - Calculation of motor parameters).
Dependency:Applies when vector control is selected in P1300 (control mode); otherwise, the display shows the value zero.
Note:The flux-generating current component is generally constant up to the base speed of the motor; above base speed,
this component is weakened (field weakening) thus enabling an increase in motor speed but at reduced torque.
r0030CO: Torque gen. current / Torque gen.cur
Access level: 3P-Group: Closed-loop controlData type: Floating Point
Unit: [A]Data set: -
Description:Displays torque-generating current component. This value is available filtered (r0030) and unfiltered (r0078).
The torque-generating current component is calculated from the torque setpoint values delivered by the speed controller.
Dependency:Applies when vector control is selected in P1300 (control mode); otherwise, the display shows the value zero.
Note:For asynchronous motors, a limit is calculated for the torque generating current component (in conjunction with the
maximum possible output voltage (r0071), motor leakage and current field weakening (r0377)) and this prevents
motor stalling.
r0031CO: Act. filtered torque / Act fil torque
Access level: 2P-Group: Closed-loop controlData type: Floating Point
Unit: [Nm]Data set: -
Description:Displays electrical torque. Output value will be zero at low speeds when current injection is active (r1751.4 = 1).
This value is available filtered (r0031) and unfiltered (r0080).
Note:The electrical torque is not the same as the mechanical torque, which can be measured on the shaft. Due to wind-
age and friction a part of the electrical torque is lost in the motor.
Access level: 4P-Group: ConverterData type: Floating Point
Unit: [%]Data set: -
Description:Displays inverter overload utilization calculated via the I2t model.
The actual I2t value relative to the max. possible I2t value supplies utilization in [%].
If the current exceeds the threshold for P0294 (inverter I2t overload warning), alarm A0505 (inverter I2t) is generated and the output current of the inverter reduced via P0290 (inverter overload reaction).
If 100 % utilization is exceeded, alarm F0005 (inverter I2t) is tripped.
Example:
Normalized output current
r0027
r0207
100 %
p0294 (95 %)
A0505
Dependency:r0036 > 0:
If the nominal current (see r0207) of the inverter is exceed, utilization will be displayed, otherwise, 0 % utilization is
displayed.
Description:Displays first active status word of inverter (bit format) and can be used to diagnose inverter status.
Bit field:Bit Signal name1 signal0 signalFP
Dependency:r0052 Bit03 "Drive fault active": Output of Bit3 (Fault) will be inverted on digital output (Low = Fault, High = No
Description:Displays first control word of inverter (in bit format) and can be used to diagnose which commands are active.
Bit field:Bit Signal name1 signal0 signalFP
00ON/OFF1YesNo01OFF2: Electrical stopNoYes02OFF3: Fast stopNoYes03Pulse enableYesNo04RFG enableYesNo05RFG startYesNo06Setpoint enableYesNo07Fault acknowledgeYesNo08JOG rightYesNo09JOG leftYesNo10Control from PLCYesNo11Reverse (setpoint inversion)YesNo13Motor potentiometer MOP upYesNo14Motor potentiometer MOP downYesNo15CDS Bit 0 (Hand/Auto)YesNo-
Notice:r0054 is identical to r2036 if USS is selected as command source via P0700 or P0719.
Description:Displays additional control word of inverter (in bit format) and can be used to diagnose which commands are active.
Bit field:Bit Signal name1 signal0 signalFP
Notice:r0055 is identical to r2037 if USS is selected as command source via P0700 or P0719.
00Fixed frequency Bit 0YesNo01Fixed frequency Bit 1YesNo02Fixed frequency Bit 2YesNo03Fixed frequency Bit 3YesNo04Drive Dataset (DDS) Bit 0YesNo05Drive Dataset (DDS) Bit 1YesNo08Enable PIDYesNo09Enable DC brakeYesNo11Enable DroopYesNo12Torque controlYesNo13External fault 1NoYes15Command Dataset (CDS) Bit 1YesNo-
r0056.0...15CO/BO: Status of motor control / CO/BO:Stat MotCtrl
Description:Displays status of motor control (in bit format), which can be used to diagnose inverter status.
Bit field:Bit Signal name1 signal0 signalFP
SINAMICS G120 Control Units CU240S, Edition 05/2007
Page 27
Parameters
List of Parameters
r0056.0...13CO/BO: Status of motor control / CO/BO:Stat MotCtrl
PM250
PM260
Description:Displays status of motor control (in bit format), which can be used to diagnose inverter status.
Bit field:Bit Signal name1 signal0 signalFP
Notice:The I-max controller (r0056 Bit13) will be activated when the actual output current (r0027) exceeds the current limit
Access level: 3P-Group: Closed-loop controlData type: Floating Point
Unit: [V]Data set: -
Description:Displays maximum output voltage.
Dependency:Actual maximum output voltage depends on the actual input supply voltage.
r0072CO: Act. output voltage / Act. outp.volt
Access level: 3P-Group: Closed-loop controlData type: Floating Point
Unit: [V]Data set: -
Description:Displays output voltage. This value is available filtered (r0025) and unfiltered (r0072).
r0074CO: Act. modulation / Act modulation
Access level: 4P-Group: Closed-loop controlData type: Floating Point
Unit: [%]Data set: -
Description:Displays actual modulation index.
The modulation index is defined as ratio between the magnitude of the fundamental component in the inverter
phase output voltage and half of the DC-link voltage.
r0075CO: Current setpoint Isd / Cur. setp. Isd
Access level: 3P-Group: Closed-loop controlData type: Floating Point
Unit: [A]Data set: -
Description:Displays setpoint of flux generating current component.
Dependency:Applies when vector control is selected in P1300 (control mode); otherwise, the display shows the value zero.
r0076CO: Act. current Isd / Act. cur. Isd
Access level: 3P-Group: Closed-loop controlData type: Floating Point
Unit: [A]Data set: -
Description:Displays flux generating current component. This value is available filtered (r0029) and unfiltered (r0076).
Dependency:Applies when vector control is selected in P1300 (control mode); otherwise, the display shows the value zero.
r0077CO: Current setpoint Isq / Cur. setp. Isq
Access level: 3P-Group: Closed-loop controlData type: Floating Point
Unit: [A]Data set: -
Description:Displays setpoint for component of torque generating current.
Dependency:Applies when vector control is selected in P1300 (control mode); otherwise, the display shows the value zero.
r0078CO: Act. current Isq / Act. cur. Isq
Access level: 3P-Group: Closed-loop controlData type: Floating Point
Unit: [A]Data set: -
Description:Displays component of torque generating current. This value is available filtered (r0030) and unfiltered (r0078).
r0079CO: Torque setpoint (total) / Total trq setp
Access level: 3P-Group: Closed-loop controlData type: Floating Point
Unit: [Nm]Data set: -
Description:Displays total torque setpoint after limitation.
Dependency:Applies when vector control is selected in P1300 (control mode); otherwise, the display shows the value zero.
1-30
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description:Selects source of display for PZD signals.
Index:[0] = 1st PZD signal
[1] = 2nd PZD signal
[2] = 3rd PZD signal
[3] = 4th PZD signal
[4] = 5th PZD signal
[5] = 6th PZD signal
[6] = 7th PZD signal
[7] = 8th PZD signal
[8] = 9th PZD signal
[9] = 10th PZD signal
r0096[0...9]PZD signals / PZD signals
Access level: 3P-Group: Closed-loop controlData type: Floating Point
Unit: [%]Data set: -
Description:Displays PZD signals in [%].
Index:[0] = 1st PZD signal
[1] = 2nd PZD signal
[2] = 3rd PZD signal
[3] = 4th PZD signal
[4] = 5th PZD signal
[5] = 6th PZD signal
[6] = 7th PZD signal
[7] = 8th PZD signal
[8] = 9th PZD signal
[9] = 10th PZD signal
Note:r0096 = 100 % corresponds to 4000 hex.
p0100Europe / North America / Europe / Nth Amer.
Access level: 1P-Group: -Data type: Unsigned16
Quick comm. YESActive: NOData set: -
Can be changed: C
Min Max Factory setting
0 2 0
Description:Determines whether power settings are expressed in [kW] or [hp] (e.g. Rated motor power P0307).
The default settings for the rated motor frequency P0310 and maximum frequency P1082 are also set automatically
here, in addition to reference frequency P2000.
Values:0:Europe [kW], motor base frequency is 50 Hz
1:North America [hp], motor base frequency is 60 Hz
2:North America [kW], motor base frequency is 60 Hz
Dependency:Where:
•Stop drive first (i.e. disable all pulses) before you change this parameter.
•Parameter P0100 can only be changed with P0010 = 1 (Commissioning mode) via the respective interface (e.g.
USS on RS232).
•Changing P0100 resets all rated motor parameters as well as other parameters that depend on the rated motor
parameters (see P0340 - calculation of motor parameters).
Description:Displays hardware features of power module.
Bit field:Bit Signal name1 signal0 signalFP
Note:Parameter r0204 = 0 indicates that no power module has been identified.
00DC input voltageYesNo01RFI filterYesNo02Active Line ModuleYesNo03SLMYesNo04BLM with thryistorYesNo05BLM with DiodeYesNo06Water CooledYesNo12Safe BrakeYesNo13Saftey EnabledYesNo14Integrated Output FilterYesNo-
r0204Power module features / Pmodule features
PM250
PM260
Description:Displays hardware features of power module.
Bit field:Bit Signal name1 signal0 signalFP
Note:Parameter r0204 = 0 indicates that no power module has been identified.
The inverter and motor requirements are determined by the speed range and torque requirements of the load. The
relationship between speed and torque for different loads (high overloads or light overloads) is shown in the following figure:
SINAMICS G120 Control Units CU240S, Edition 05/2007
Page 35
Parameters
List of Parameters
Torque
Power
1
~M
f
p = const.p ~ fp ~ f
M = const.
f~M
2
Characteristic
Application
P
M
f
Winders
Facing lathes
Rotary cutting
machines
M
P
Hoisting gear
Belt conveyors
Process machines
Involving forming
M
f
Calenders with
viscous friction
Eddy-current brakes
P
f
Rolling mills
Planers
Compressors
•High overload (HO):
HO is used if the application needs a high overload on the whole frequency range.Many loads can be considered to be high overloads.Typical high overloads are conveyors, compressors and positve displacement
pumps.
•Light overload (LO):
LO is used if the application has a parabolic frequency/torque characteristic like many fans and pumps.Light
overload offers the following possibilities with the same inverter:
- Higher rated inverter current r0207
- Higher rated inverter power r0206
- Higher threshold for I2t protection
If P0205 is modified in quick commissioning it immediately calculates various motor parameters:
1. P0305 Rated motor current
2. P0307 Rated motor power
3. P0640 Motor overload factor
It is recommended to modify P0205 first. Afterwards motor parameter may be adapted.
Motor parameter will be overridden by changing this sequence.
Values:0:High overload
Notice:Use setting 1 (light overload) only for light-overload applications (e.g. pumps and fans).
Note:The parameter value is not reset by the factory setting (see P0970).
1:Light overload
If used for high-overload applications, I2t warning will be produced too late, causing overheating in the motor.
M ~ f
p ~ f
M
Pumps
Fans
Centrifuges
2
3
P
f
r0206Rated inverter power [kW] / [hp] / Rated power[kW/hp]
Access level: 2P-Group: ConverterData type: Floating Point
Unit: -Data set: -
Description:Displays nominal rated motor power from inverter.
Dependency:Value is displayed in [kW] or [hp] depending on setting for P0100 (operation for Europe / North America).
•the modulation index is limited to 100 % (P1803 = 100) what limits the output voltage.
•-the modulation type is set to SVM (P1802 = 2).
•-the resultant max. output frequency r1084 is limited depending on the filter and motor specifications.
Do not start the drive if a LC-filter is connected and no load is present.
This could damage the filter.
The paramter is only changeable in quick commissioning. In case of an internal sinus-/LC- output filter it will be set
to LC-filter (P0230 = 3) and is not visible and changeable.
Description:Selects reaction of inverter to an internal thermal overload condition.
Values:0:Reduce output frequency and output current
Dependency:Following physical values influence the inverter overload protection (see diagram):
1:No reduction, trip (F0004/ 5/ 6) when thermal limits reached
2:Reduce pulse frequency, output current and output frequency
3:Reduce pulse freq. only and trip (F0006), when overload too hig
•Heat sink temperature (r0037.0); causes A0504 and F0004.
•IGBT Junction temperature (r0037.1); causes F0004 or F0006.
•Delta temperature between heat sink and junction temperature; causes A0504 and F0006.
SINAMICS G120 Control Units CU240S, Edition 05/2007
Page 43
IEC Motor
W2U1U2V1V2
W1
W2
U1
U2
V1
Parameters
List of Parameters
V2
W1
U1
V1
W1
Delta connection
Note:Safety Integrated: If driving loads occur in the application, the motor must be dimensioned so that its slip in super-
synchronous operation always remains within the rated slip.
U1
V1
W1
Star connection
p0305[0...2]Rated motor current / Rated mot. current
Access level: 1P-Group: MotorData type: Floating Point
Quick comm. YESActive: NOData set: DDS
Can be changed: C
Min Max Factory setting
0.01 [A]10000.00 [A]1.86 [A]
Description:Nominal motor current [A] from rating plate - see diagram in P0304.
Dependency:Changeable only when P0010 = 1 (quick commissioning).
Depends also on P0320 (motor magnetization current).
Note:The maximum value of P0305 depends on the maximum inverter current r0209 and the motor type:
Asynchronous motor : P0305_max = P0209
Synchronous motor : P0305_max = 2 * P0209 (for HO operation) and P0305_max = P0209 (for LO operation)
It is recommended that the ratio of P0305 (rated motor current) and r0207 (rated inverter current) should not be
lower than:
r0207
r0207
1.52.5
P0305 81
P0305 41
P0305 2 ⋅
r0209
U/f :
SLVC and VC :
When the relation of the nominal motor current P0305 and half of the maximal inverter current (r0209) exceeds 1.5
an additional current derating is applied. This is necessary to protect the inverter from harmonic current waves.
I
max,Inv
r0209
r0209 0.7 ⋅
Default value is depending on inverter type and its rating data.
1:Complete parameterization
2:Calculation of equivalent circuit data
3:Calculation of V/f and vector control data
4:Calculation of controller settings only
Note:This parameter is required during commissioning to optimize inverter performance. If there is a large mismatch in
Power ratings of Inverter to Motor it is possible that r0384 and r0386 may not be calculated correct. In these cases
use P1910.
When transferring parameter p0340, the frequency inverter uses its processor to carry-out internal calculations.
Communications - both via USS as well as via the Fieldbus - are interrupted for the time that it takes to make these
calculations.
This can result in the following error messages at the connected SIMATIC S7 control (communications via fieldbus):
•Parameter fault 30
•Drive fault 70
•Drive fault 75
When using STARTER (USS) to commission the drive system, data cannot be entered while these calculations are
being made.
The faults can be acknowledged as soon as the calculations have been completed in the frequency inverter. These
calculations can take up to one minute to complete.
Access level: 3P-Group: MotorData type: Floating Point
Quick comm. NOActive: YESData set: DDS
Can be changed: U, T
Min Max Factory setting
0.00010 1000.00000 0.00180
Description:Sets no-load inertia of motor.
Together with P0342 (inertia ratio total/motor) and P1496 (scaling factor acceleration), this value produces the
acceleration torque (r1518), which can be added to any additional torque produced from a BICO source (P1511),
and incorporated in the torque control function.
Note:The result of P0341 * P0342 is included in the speed controller calculation.
P0341 * P0342 (inertia ratio total/motor) = total motor inertia
P1496 (scaling factor acceleration) = 100 % activates acceleration pre-control for the speed controller and calculates the torque from P0341 (motor inertia) and P0342 (inertia ratio total/motor).
p0342[0...2]Total/motor inertia ratio / Tot/mot inert.rat.
Access level: 3P-Group: MotorData type: Floating Point
Quick comm. NOActive: YESData set: DDS
Can be changed: U, T
Min Max Factory setting
1.000 400.000 1.000
Description:Specifies ratio between total inertia (load + motor) and motor inertia.
p0344[0...2]Motor weight / Motor weight
Access level: 3P-Group: MotorData type: Floating Point
Quick comm. NOActive: YESData set: DDS
Can be changed: U, T
Min Max Factory setting
1.0 [kg]6500.0 [kg]9.4 [kg]
Description:Specifies motor weight [kg].
Note:This value is used in the motor thermal model. It is normally calculated automatically from P0340 (motor parame-
ters) but can also be entered manually.
Default value is depending on inverter type and its rating data.
SINAMICS G120 Control Units CU240S, Edition 05/2007
Page 49
List of Parameters
r0345[0...2]Motor start-up time / Mot. start-up time
Access level: 3P-Group: MotorData type: Floating Point
Unit: [s]Data set: DDS
Description:Displays motor start-up time.
This time corresponds to the standardized motor inertia.
The start-up time is the time taken to reach rated motor speed from standstill at acceleration with rated motor torque
(r0333).
p0346[0...2]Magnetization time / Magnetization time
Access level: 3P-Group: MotorData type: Floating Point
Quick comm. NOActive: YESData set: DDS
Can be changed: U, T
Min Max Factory setting
0.000 [s]20.000 [s]1.000 [s]
Description:Sets magnetization time [s], i.e. waiting time between pulse enable and start of ramp-up.
Motor magnetization builds up during this time. Magnetization time is normally calculated automatically from the
motor data and corresponds to the rotor time constant.
Notice:An excessive reduction of this time can result in insufficient motor magnetization.
Note:If boost settings are higher than 100 %, magnetization time may be reduced.
Default value is depending on inverter type and its rating data.
Parameters
p0347[0...2]Demagnetization time / Demagnet. time
Access level: 3P-Group: MotorData type: Floating Point
Quick comm. NOActive: YESData set: DDS
Can be changed: U, T
Min Max Factory setting
0.000 [s]20.000 [s] 1.000 [s]
Description:Changes time allowed after OFF2 / fault condition, before pulses can be re-enabled.
Notice:Not active following a normally completed ramp-down, e.g. after OFF1, OFF3 or JOG.
Overcurrent trips will occur if the time is decreased excessively.
Note:The demagnetization time is approximately 2.5 x rotor time constant in seconds.
Default value is depending on inverter type and its rating data.
Access level: 3P-Group: MotorData type: Floating Point
Quick comm. NOActive: YESData set: DDS
Can be changed: U, T
Min Max Factory setting
0.00001 [Ohm]2000.00000 [Ohm]2.00000 [Ohm]
Description:Stator resistance value in [Ohms] for connected motor (line value).
The parameter value doesn't include the cable resistance.
There are three ways to determine the value for this parameter:
1. Calculate using
- P0340 = 1 (data entered from rating plate) or
- P0010 = 1, P3900 = 1, 2 or 3 (end of quick commissioning).
2. Measure using P1900 = 2 (standard motor data identification - value for stator resistance is overwritten).
Measure using P1900 = 3 (compleate motor data identification - same like setting 2; additional detection of the
saturation curve)
3. Measure manually using an Ohmmeter.
Note:Since the manually measured resistor is a line-to-line value, which includes the cable resistors, the measured value
has to be divided by two and the cable resistor of a line has to be subtracted from that value.
The value entered in P0350 (stator resistance) is the one obtained by the method last used.
Default value is depending on inverter type and its rating data.
p0352[0...2]Cable resistance / Cable resistance
Access level: 3P-Group: MotorData type: Floating Point
Quick comm. NOActive: YESData set: DDS
Can be changed: U, T
Min Max Factory setting
0.0 [Ohm]120.0 [Ohm]0.0 [Ohm]
Description:Describes cable resistance between inverter and motor for one phase.
The value corresponds to the resistance of the cable between the inverter and the motor, relative to the rated
impedance.
p0354[0...2]Rotor resistance / Rotor resistance
Access level: 3P-Group: MotorData type: Floating Point
Quick comm. NOActive: YESData set: DDS
Can be changed: U, T
Min Max Factory setting
0.0 [Ohm]300.0 [Ohm]10.0 [Ohm]
Description:Sets rotor resistance of motor equivalent circuit (phase value).
Dependency:Calculated automatically using the motor model or determined using P1900 (motor identification).
Access level: 4P-Group: MotorData type: Floating Point
Quick comm. NOActive: YESData set: DDS
Can be changed: U, T
Min Max Factory setting
20.0 [%]200.0 [%]60.0 [%]
Description:Specifies first flux value of saturation characteristic in [%] relative to rated motor voltage (P0304).
The saturation characteristic is defined using 4 points (P0362 - P0365, P0366 - P0369). This parameter specifies
the y coordinate (flux) for the first value pair of the characteristic.
Dependency:The following applies for the flux values: P0362 < P0363 < P0364 < P0365, otherwise a linear characteristic is
applied internally.
Note:P0362 = 100 % corresponds to rated motor flux.
Access level: 4P-Group: MotorData type: Floating Point
Quick comm. NOActive: YESData set: DDS
Can be changed: U, T
Min Max Factory setting
20.0 [%]200.0 [%]85.0 [%]
Description:Specifies second flux value of saturation characteristic in [%] relative to rated motor voltage (P0304).
The saturation characteristic is defined using 4 points (P0362 - P0365, P0366 - P0369). This parameter specifies
the y coordinate (flux) for the second value pair of the characteristic.
Dependency:The following applies for the flux values: P0362 < P0363 < P0364 < P0365, otherwise a linear characteristic is
applied internally.
Note:P0363 = 100 % corresponds to rated motor flux.
Access level: 4P-Group: MotorData type: Floating Point
Quick comm. NOActive: YESData set: DDS
Can be changed: U, T
Min Max Factory setting
20.0 [%]200.0 [%]115.0 [%]
Description:Specifies third flux value of saturation characteristic in [%] relative to rated motor voltage (P0304).
The saturation characteristic is defined using 4 points (P0362 - P0365, P0366 - P0369). This parameter specifies
the y coordinate (flux) for the third value pair of the characteristic.
Dependency:The following applies for the flux values: P0362 < P0363 < P0364 < P0365, otherwise a linear characteristic is
Note:P0364 = 100 % corresponds to rated motor flux.
Access level: 4P-Group: MotorData type: Floating Point
Quick comm. NOActive: YESData set: DDS
Can be changed: U, T
Min Max Factory setting
20.0 [%]200.0 [%]125.0 [%]
Description:Specifies fourth flux value of saturation characteristic in [%] relative to rated motor voltage (P0304).
The saturation characteristic is defined using 4 points (P0362 - P0365, P0366 - P0369). This parameter specifies
the y coordinate (flux) for the fourth value pair of the characteristic.
Dependency:The following applies for the flux values: P0362 < P0363 < P0364 < P0365, otherwise a linear characteristic is
applied internally.
Note:P0365 = 100 % corresponds to rated motor flux.
Access level: 4P-Group: MotorData type: Floating Point
Quick comm. NOActive: YESData set: DDS
Can be changed: U, T
Min Max Factory setting
20.0 [%]250.0 [%]50.0 [%]
Description:Specifies first magnetizing current value of the saturation characteristic in [%] relative to the rated magnetizing cur-
rent (P0331).
The saturation characteristic is defined using 4 points (P0362 - P0365, P0366 - P0369). This parameter specifies
the x coordinate (magnetizing current) for the first value pair of the characteristic.
Access level: 4P-Group: MotorData type: Floating Point
Quick comm. NOActive: YESData set: DDS
Can be changed: U, T
Min Max Factory setting
20.0 [%]250.0 [%]75.0 [%]
Description:Specifies second magnetizing current value of saturation characteristic in [%] relative to rated magnetizing current
(P0331).
The saturation characteristic is defined using 4 points (P0362 - P0365, P0366 - P0369). This parameter specifies
the x coordinate (magnetizing current) for the second value pair of the characteristic.
Access level: 4P-Group: MotorData type: Floating Point
Quick comm. NOActive: YESData set: DDS
Can be changed: U, T
Min Max Factory setting
20.0 [%]250.0 [%]135.0 [%]
Description:Specifies third magnetizing current value of saturation characteristic in [%] relative to rated magnetizing current
(P0331).
The saturation characteristic is defined using 4 points (P0362 - P0365, P0366 - P0369). This parameter specifies
the x coordinate (magnetizing current) for the third value pair of the characteristic.
The saturation characteristic is defined using 4 points (P0362 - P0365, P0366 - P0369). This parameter specifies
the x coordinate (magnetizing current) for the fourth value pair of the characteristic.
The following applies for the magnetizing currents: P0366 < P0367 < P0368 < P0369, otherwise a linear characteristic is applied internally.
2:Quadrature encoder without zero pulse
12:Quadrature encoder with zero pulse
same. If this is not achieved, then the functional operation of the Vector Control will not be guaranteed (positive
instead of negative feedback).
Extreme care must therefore be taken with respect to the connection of the motor to the inverter as well as the correct connection of the encoder to the inverter. Motor and encoder must not be incorrectly wired up !
P0400 = 12 (quadrature encoder and zero pulse) will not detect encoder loss on Zero pulse. Zero pulse is only used
to synchronise measured angle.
be observed in order to stop encoder loss trips when the brake is applied:
•The delay speed loss reaction should be > brake holding times (i.e. P0494 > P1216 and P0494 > P1217 )
•The delay time for motor pulled out should be > brake holding times (i.e. P2178 > P1216 and P2178 > P1217 )
•The allowed speed difference P0492 should be > f_min P1080
r0403.0...4CO/BO: Encoder status word / Enc. StatWd
CU240S
CU240S DP
CU240S DP-F
CU240S PN
Description:Displays status word of encoder (in bit format).
Bit field:Bit Signal name1 signal0 signalFP
The following equation calculates the encoder frequency depending on the encoder resoulution and the rotational
speed (rpm). The encoder frequency has to be less than the max. pulse frequency:
> f =
p0408 x rpm
60
f
max
p0410[0...2]Reverses internal direction sense / Rev dir sense
CU240S
CU240S DP
CU240S DP-F
CU240S PN
Description:Reverses internal direction sense of the encoder signal. This does the same thing as switching the ENC_A and
Description:Parameter P0492 is used for low and high speed encoder loss detection (fault: F0090).
Dependency:This parameter is updated when motor start-up time P0345 is changed or when a speedloop optimisation is per-
Caution:P0492 = 0 (disabled):
Access level: 2P-Group: EncoderData type: Floating Point
Quick comm. NOActive: YESData set: DDS
Can be changed: T
Min Max Factory setting
0.00 [Hz]100.00 [Hz]10.00 [Hz]
High speed encoder loss detection:
This condition occurs when the allowed frequency and the allowed difference of the speed signals between samples, set in P0492 is exceeded.
•f_act and f(t_2) - f(t_1) > P0492
Low speed encoder loss detection:
This condition occurs when the actual frequency is < P0492 when encoder loss occurs.
•Condition 1:
- r0061 = 0 and torque limit and then
- r0061 = 0 with setpoint frequency > 0 for time > P0494
•Condition 2:
- Act. freq. < P0492 and f(t_2) < P0492 and ASIC detect channel B loss
formed (P1960 = 1).
There is a fixed delay of 40 ms before acting upon loss of encoder at high speeds.
When allowed speed difference is set to 0, both the high speed and low speed encoder loss detection are disabled,
thus encoder loss will not be detected.
If encoder loss detection is disabled and encoder loss occurs, then operation of the motor may become unstable.
Consideration also needs to be given to drive operation when the drive is operating in vector speed control or vector
torque control mode (P1300 = 21, 23) and the drive attempts to start the motor while it has a failed encoder.
Under these circumstances, the drive uses parameters P1520 and P1521 (the upper and lower torque limits
respectively) to decide when to trip.
In the case of a very low frequency set point, it may take the drive a considerable period to reach this condition, during which time the drive can lose orientation.
If the motor shaft speed is less than the value in P0492 then encoder loss is detected using a low speed encoder
loss detection algorithm.
This parameter selects the delay between loss of encoder at low speed and reaction to the encoder loss.
formed (P1960 = 1).
When the delay in P0494 is set to 0, then low speed encoder loss detection is disabled and low speed encoder loss
cannot be detected (high speed encoder loss detection will still operate if P0492 > 0).
If low speed encoder loss detection is disabled and encoder should be lost at low speed, then operation of motor
may become unstable.
encoder loss trips when the brake is applied, the delay speed loss reaction should be > brake holding times (i.e.
P0494 > P1216 and P494 > P1217).
The motor temperature monitoring will be done based on the estimated value of the thermal motor model.
PTC thermistor (P0601 = 1)
The motor is monitored by the thermal motor model and additionally by the PTC thermistor, thus providing a redundant system for monitoring the motor temperature.
Should the resistance value of 2000 Ohm be exceeded, the inverter trips with fault F0011 (motor overheating).
If the resistance value is below 10 Ohm, then the fault F0015 (motor temperature signal lost) is output.
This protects the motor from overheating and also from a sensor wire breakage.
KTY84 (P0601 = 2)
The temperature of the sensor (thus that of the motor windings) is written to parameter r0035. This motor temperature is then additionally calculated via the thermal motor model.
If the electric circuit to the KTY84 sensor is open or if a short circuit occurs, fault F0015 (motor temperature signal
lost) is generated.
Values:0:No sensor
1:PTC thermistor
2:KTY84
Dependency:The motor overheating warning threshold needs to be assigned with parameter P0604 (the factory setting is 130
°C). This warning threshold depends on the motor's thermal class.
The motor overheating disturbance threshold is automatically set by the inverter at 10 % higher than the temperature declared in parameter P0604. In parameter P0610 is set, how the inverter reacts on overtemperature.
p0604[0...2]Threshold motor temperature / Thresh. mot. temp.
Access level: 2P-Group: MotorData type: Floating Point
Quick comm. NOActive: YESData set: DDS
Can be changed: U, T
Min Max Factory setting
0.0 [°C]200.0 [°C]130.0 [°C]
Description:Enters warning threshold for motor temperature protection.
The trip temperature defined is always 10 % higher than the warning threshold P0604. When actual motor temperature exeeds trip temperature then inverter trips as defined in P0610.
Dependency:This value should be at least 40°C higher than the motor ambient temperature P0625.
Note:Default value depends on P0300 (select motor type).
Description:Defines reaction when motor temperature reaches warning threshold.
Values:0:No reaction, warning only
1:Warning and Imax reduction (results in reduced output frequency
2:Warning and trip (F0011)
Dependency:Trip level = P0604 (motor temperature threshold) * 110 %
Note:The purpose of motor I2t is to calculate or measure (KTY84) the motor temperature and disable the inverter if the
motor is in danger of overheating.
I2t operation:
The measured motor current is displayed in r0027. The motor temperature in °C is displayed in r0035.
This temperature is derived either from a KTY84 temperature sensor mounted in the motor, or from a calculated
value. The value from the KTY84 is used only when P0601 = 2; in all other cases (including motor temperature signal lost) the calculated value is used.
The reaction to the warning can be changed from this default using P0610.
Parameter r0035 is particularly useful to monitor if the calculated motor temperature is rising excessively.
p0621[0...2]Motor temp. ident after restart / Mot.temp ident.
Switches command and setpoint source between freely programmable BICO parameters and fixed command/setpoint profiles.
Command and setpoint sources can be changed independently.
The tens digit chooses the command source and the units digit chooses the setpoint source.
1:Cmd = BICO parameter Setpoint = MOP setpoint
2:Cmd = BICO parameter Setpoint = Analog setpoint
3:Cmd = BICO parameter Setpoint = Fixed frequency
4:Cmd = BICO parameter Setpoint = USS on RS232
5:Cmd = BICO parameter Setpoint = USS on RS485
7:Cmd = BICO parameter Setpoint = Analog setpoint 2
10:Cmd = BOP Setpoint = BICO parameter
11:Cmd = BOP Setpoint = MOP setpoint
12:Cmd = BOP Setpoint = Analog setpoint
13:Cmd = BOP Setpoint = Fixed frequency
14:Cmd = BOP Setpoint = USS on RS232
15:Cmd = BOP Setpoint = USS on RS485
17:Cmd = BOP Setpoint = Analog setpoint 2
40:Cmd = USS on RS232 Setpoint = BICO parameter
41:Cmd = USS on RS232 Setpoint = MOP setpoint
42:Cmd = USS on RS232 Setpoint = Analog setpoint
43:Cmd = USS on RS232 Setpoint = Fixed frequency
44:Cmd = USS on RS232 Setpoint = USS on RS232
45:Cmd = USS on RS232 Setpoint = USS on RS485
47:Cmd = USS on RS232 Setpoint = Analog setpoint 2
50:Cmd = USS on RS485 Setpoint = BICO parameter
51:Cmd = USS on RS485 Setpoint = MOP setpoint
52:Cmd = USS on RS485 Setpoint = Analog setpoint
53:Cmd = USS on RS485 Setpoint = Fixed frequency
54:Cmd = USS on RS485 Setpoint = USS on RS232
55:Cmd = USS on RS485 Setpoint = USS on RS485
57:Cmd = USS on RS485 Setpoint = Analog setpoint 2
If set to a value other than 0 (i.e. BICO parameter is not the setpoint source), P0844 / P0848 (first source of OFF2 /
OFF3) are not effective; instead, P0845 / P0849 (second source of OFF2 / OFF3) apply and the OFF commands
are obtained via the particular source defined.
BICO connections made previously remain unchanged.
Settings in P0719 (contrary to P0700 settings) do not reset the digital inputs (P0701, P0702, ...)
Switches command and setpoint source between freely programmable BICO parameters and fixed command/setpoint profiles.
Command and setpoint sources can be changed independently.
The tens digit chooses the command source and the units digit chooses the setpoint source.
1:Cmd = BICO parameter Setpoint = MOP setpoint
2:Cmd = BICO parameter Setpoint = Analog setpoint
3:Cmd = BICO parameter Setpoint = Fixed frequency
4:Cmd = BICO parameter Setpoint = USS on RS232
6:Cmd = BICO parameter Setpoint = Fieldbus
7:Cmd = BICO parameter Setpoint = Analog setpoint 2
10:Cmd = BOP Setpoint = BICO parameter
11:Cmd = BOP Setpoint = MOP setpoint
12:Cmd = BOP Setpoint = Analog setpoint
13:Cmd = BOP Setpoint = Fixed frequency
14:Cmd = BOP Setpoint = USS on RS232
16:Cmd = BOP Setpoint = Fieldbus
17:Cmd = BOP Setpoint = Analog setpoint 2
40:Cmd = USS on RS232 Setpoint = BICO parameter
41:Cmd = USS on RS232 Setpoint = MOP setpoint
42:Cmd = USS on RS232 Setpoint = Analog setpoint
43:Cmd = USS on RS232 Setpoint = Fixed frequency
44:Cmd = USS on RS232 Setpoint = USS on RS232
46:Cmd = USS on RS232 Setpoint = Fieldbus
47:Cmd = USS on RS232 Setpoint = Analog setpoint 2
60:Cmd = Fieldbus Setpoint = BICO parameter
61:Cmd = Fieldbus Setpoint = MOP setpoint
62:Cmd = Fieldbus Setpoint = Analog setpoint
63:Cmd = Fieldbus Setpoint = Fixed frequency
64:Cmd = Fieldbus Setpoint = USS on RS232
66:Cmd = Fieldbus Setpoint = Fieldbus
67:Cmd = Fieldbus Setpoint = Analog setpoint 2
If set to a value other than 0 (i.e. BICO parameter is not the setpoint source), P0844 / P0848 (first source of OFF2 /
OFF3) are not effective; instead, P0845 / P0849 (second source of OFF2 / OFF3) apply and the OFF commands
are obtained via the particular source defined.
BICO connections made previously remain unchanged.
USS on RS485 is not supported.
Settings in P0719 (contrary to P0700 settings) do not reset the digital inputs (P0701, P0702, ...)
Description:Defines type of analog input and also enables analog input monitoring.
To switch over from voltage to current analog input it is not sufficient to merely modify parameter P0756.
Rather, the general I/O DIP switches must also be set to the correct position.
The DIP settings are as follows:
•OFF = voltage input (10 V)
•ON = current input (20 mA)
Allocation of DIPs to analog inputs is as follows:
•DIP on left (DIP 1) = Analog input 0
•DIP on right (DIP 2) = Analog input 1
Values:0:Unipolar voltage input (0 to +10 V)
1:Unipolar voltage input with monitoring (0 to 10 V)
2:Unipolar current input (0 to 20 mA)
3:Unipolar current input with monitoring (0 to 20 mA)
4:Bipolar voltage input (-10 V to +10 V)
Index:[0] = Analog input 0 (AI0)
[1] = Analog input 1 (AI1)
Dependency:Function disabled if analog scaling block programmed to output negative setpoints (see P0757 to P0760).
Notice:When monitoring is enabled and a deadband defined (P0761), a fault condition will be generated (F0080) if the ana-
Note:See P0757 to P0760 (AI scaling).
log input voltage falls below 50 % of the deadband voltage.
It is not possible to select the bipolar voltage for analog input 1.
p0761[0...1]Width of AI deadband / AI deadband width
Access level: 2P-Group: TerminalsData type: Floating Point
Quick comm. NOActive: NOData set: -
Can be changed: U, T
Min Max Factory setting
0 20 0
Description:Defines width of deadband on analog input.
Example:The below example produces a 2 to 10 V, 0 to 50 Hz analog input (AI value 2 to 10 V, 0 to 50 Hz):
•P2000 = 50 Hz
•P0759 = 8 V P0760 = 75 %
•P0757 = 2 V P0758 = 0 %
•P0761 = 2 V
•P0756 = 0 or 1
The below example produces a 0 to 10 V analog input (-50 to +50 Hz) with center zero and a "holding point" 0.2 V
wide (0.1 V to each side of center, AI value 0 to 10 V, -50 to +50 Hz):
•P2000 = 50 Hz
•P0759 = 8 V P0760 = 75 %
•P0757 = 2 V P0758 = -75 %
•P0761 = 0.1 V
•P0756 = 0 or 1
Index:[0] = Analog input 0 (AI0)
[1] = Analog input 1 (AI1)
Notice:Deadband starts from 0 V to value of P0761, if both values of P0758 and P0760 (y coordinates of AI scaling) are
positive or negative respectively.
However, deadband is active in both directions from point of intersection (x axis with AI scaling curve), if sign of
P0758 and P0760 are opposite.
Note:P0761[x] = 0 : No deadband active.
Min. frequency P1080 should be zero when using center zero setup.
There is no hysteresis at the end of the deadband.
p0762[0...1]Delay for loss of signal action / Delay on sig. loss
Note:Analog Output 0 can be switched to a voltage output with a range 0...10 V.
[1] = Analog output 1 (AO1)
Analog Output 1 is only a current output. By connecting an external resistor of 500 Ohm to the terminals a voltage
output with a range of 0...10 V can be created.
p0777[0...1]Value x1 of AO scaling / Value x1:AO scal.
Access level: 2P-Group: TerminalsData type: Floating Point
Quick comm. NOActive: NOData set: -
Can be changed: U, T
Min Max Factory setting
-99999.0 [%]99999.0 [%]0.0 [%]
Description:Defines x1 output characteristic in [%].
Scaling block is responsible for adjustment of output value defined in P0771 (AO connector input).
x1 is the first value of the two pairs of variants x1/y1 and x2/y2 which determine the straight line. The two points P1
(x1, y1) and P2 (x2, y2) can be chosen freely.
Index:[0] = Analog output 0 (AO0)
[1] = Analog output 1 (AO1)
Dependency:Affects P2000 to P2003 (referency frequency, voltage, current or torque) depending on which setpoint is to be gen-
erated.
p0778[0...1]Value y1 of AO scaling / Value y1:AO scal.
Access level: 2P-Group: TerminalsData type: Floating Point
Quick comm. NOActive: NOData set: -
Can be changed: U, T
Min Max Factory setting
0 20 0
Description:Defines y1 of output characteristic.
Index:[0] = Analog output 0 (AO0)
[1] = Analog output 1 (AO1)
p0779[0...1]Value x2 of AO scaling / Value x2:AO scal.
Access level: 2P-Group: TerminalsData type: Floating Point
Quick comm. NOActive: NOData set: -
Can be changed: U, T
Min Max Factory setting
-99999.0 [%]99999.0 [%]100.0 [%]
Description:Defines x2 of output characteristic in [%].
Index:[0] = Analog output 0 (AO0)
Dependency:Affects P2000 to P2003 (referency frequency, voltage, current or torque) depending on which setpoint is to be gen-
Description:Binector output to display whether command and setpoint source is connected to an external client.
Bit field:Bit Signal name1 signal0 signalFP
All PROFIBUS DIP switches = OFF --> Address defined in P0918 is valid otherwise the DIP switch setting has priority and P0918 indicates DIP switch setting.