Siemens CU240E-2, CU240B-2 Operating Instructions Manual

Page 1
___________________
___________________
___________________
___________________
___________________
SINAMICS
SINAMICS G120 CU240B-2 and CU240E-2 Control Units
Compact Operating Instructions
01/2017
A5E39910322B AA
Fundamental safety instructions
1
Scope of delivery
2
Installing
3
Commissioning
4
More information
5
Page 2
Siemens AG Division Digital Factory Postfach 48 48 90026 NÜRNBERG GERMANY
A5E39910322B AA
01/2017 Subject to change
Copyright © Siemens AG 2015 - 2017. All rights reserved
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by
personnel qualified
for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions.
Page 3
CU240B-2 and CU240E-2 Control Units Compact Operating Instructions, 01/2017, A5E39910322B AA
3
Table of contents
1 Fundamental safety instructions .............................................................................................................. 4
1.1 General safety instructions ....................................................................................................... 4
1.2 Industrial security ...................................................................................................................... 5
2 Scope of delivery .................................................................................................................................... 6
3 Installing ................................................................................................................................................. 7
3.1 Plugging the Control Unit onto the Power Module .................................................................... 7
3.2 Overview of the interfaces ........................................................................................................ 9
3.3 Terminal strips on CU240B-2 Control Units............................................................................ 11
3.4 Factory setting of the CU240B-2 interfaces ............................................................................ 13
3.5 Terminal strips on CU240E-2 Control Units............................................................................ 15
3.6 Factory setting of the CU240E-2 interfaces ............................................................................ 17
4 Commissioning ..................................................................................................................................... 19
4.1 Tools to commission the converter ......................................................................................... 19
4.2 Commissioning with BOP-2 operator panel ............................................................................ 20
4.2.1 Quick commissioning with the BOP-2 ..................................................................................... 20
4.2.2 Standard Drive Control ........................................................................................................... 22
4.2.3 Dynamic Drive Control ............................................................................................................ 24
4.2.4 Identifying the motor data and optimizing the closed-loop control ......................................... 26
4.3 Connecting the inverter to the fieldbus ................................................................................... 28
4.4 Frequently required parameters ............................................................................................. 30
5 More information ................................................................................................................................... 33
5.1 Overview of the manuals ........................................................................................................ 33
5.2 Technical support .................................................................................................................... 34
This manual describes how you install the CU240B-2 or CU240E-2 Control Unit of the SINAMICS G120 inverter and commission it.
What is the meaning of the symbols in the manual?
Reference to further information in the manual
An operating instruction starts here.
This concludes the operating instruction.
Download from the Internet
DVD that can be ordered
Page 4
CU240B-2 and CU240E-2 Control Units
4 Compact Operating Instructions, 01/2017, A5E39910322B AA
1
1.1
General safety instructions
WARNING
Danger to life if the safety instructions and residual risks are not observed
If the safety instructions and residual risks in the associated hardware documentation are not observed, accidents involving severe injuries or death can occur.
Observe the safety instructions given in the hardware documentation.
Consider the residual risks for the risk evaluation.
WARNING
Danger to life or malfunctions of the machine as a result of incorrect or changed parameterization
As a result of incorrect or changed parameterization, machines can malfunction, which in turn can lead to injuries or death.
Protect the parameterization (parameter assignments) against unauthorized access.
Respond to possible malfunctions by applying suitable measures (e.g. EMERGENCY
STOP or EMERGENCY OFF).
Page 5
Fundamental safety instructions
1.2 Industrial security
CU240B-2 and CU240E-2 Control Units Compact Operating Instructions, 01/2017, A5E39910322B AA
5
1.2
Industrial security
Note Industrial security
Siemens provides products and solutions with industrial security functions that support the secure operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber
threats, it is
necessary to implement
– and continuously maintain – a holistic, state-of-the-art industrial
security concept. Siemens products and solutions only represent one component of such a concept.
The customer is responsible for preventing unautho
rized access to its plants, systems,
machines and networks. Systems, machines and components should only be connected to the enterprise network or the internet if and to the extent necessary and with appropriate security measures (e.g. use of firewalls and
network segmentation) in place.
Additionally, Siemens’ guidance on appropriate security measures should be taken into account. For more information about industrial security, please visit:
Industrial security (
http://www.siemens.com/industrialsecurity).
Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends to apply product updates as soon as available and to always use the latest product versions. Use of product versions that are no longer supported, and failure to apply latest updates may increase customer’s exposure to cyber threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed at:
I
ndustrial security (http://www.siemens.com/industrialsecurity).
WARNING
Danger to life as a result of unsafe operating states resulting from software manipulation
Software manipulations (e.g. viruses, trojans, malware or worms) can cause unsafe operating states in your system that may lead to death, serious injury, and property damage.
Keep the software up to date.
Incorporate the automation and drive components into a holistic, state-of-the-art
industrial security concept for the installation or machine.
Make sure that you include all installed products into the holistic industrial security concept.
Protect files stored on exchangeable storage media from malicious software by with suitable protection measures, e.g. virus scanners.
Page 6
CU240B-2 and CU240E-2 Control Units
6 Compact Operating Instructions, 01/2017, A5E39910322B AA
2
The delivery comprises at least the following components:
A CU240B-2 or a CU240E-2 control unit with firmware, which is ready to run. Options for upgrading and downgrading the firmware can be found on the Internet: Firmware (http://support.automation.siemens.com/WW/news/en/67364620)
The fieldbus interface of the Control Unit depends on the Article No. The Article No., the designation and the version of the hardware (e.g. 02) and firmware (e.g. 4.6) can be found on the rating plate
of the Control Unit.
Designation
Article number
Fieldbus
CU240B-2
6SL3244-0BB00-1BA1
USS, Modbus RTU
CU240B-2 DP
6SL3244-0BB00-1PA1
PROFIBUS DP
CU240E-2
6SL3244-0BB12-1BA1
USS, Modbus RTU
CU240E-2 F
6SL3244-0BB13-1BA1
CU240E-2 DP
6SL3244-0BB12-1PA1
PROFIBUS DP
CU240E-2 DP-F
6SL3244-0BB13-1PA1
CU240E-2 PN
6SL3244-0BB12-1FA0
PROFINET IO, EtherNet/IP
CU240E-2 PN-F 6SL3244-0BB13-1FA0
● Compact Operating Instructions in German and English
The inverter contains open-source software (OSS). The OSS license terms are saved in
the inverter.
Transferring OSS license terms to a PC
Procedure
To transfer OSS license terms to a PC, proceed as follows:
1. Switch off the inverter power supply.
2. Insert an empty memory card into the card slot of the inverter.
Overview of the interfaces (Page 9)
3. Switch on the inverter power supply.
4. The inverter writes file "Read_OSS.ZIP" to the memory card within approximately 30 seconds.
5. Switch off the inverter power supply.
6. Withdraw the memory card from the inverter.
7. Insert the memory card into the card reader of a PC.
8. Please read the license terms.
You have transferred the OSS license terms to a PC.
Page 7
CU240B-2 and CU240E-2 Control Units Compact Operating Instructions, 01/2017, A5E39910322B AA
7
3
3.1
Plugging the Control Unit onto the Power Module
Permissible Power Modules
You may operate the Control Unit with the following Power Modules:
Power Module
= operation with Power Module permissible, --- = not per-
missible
CU240B-2
CU240E-2
PM230 IP20 and push-through
PM230 IP55 ---
PM240P-2
PM240-2
PM250
Installing the Control Unit - General
Each Power Module has an appropriate holder for the Control Unit and a release mechanism.
Inserting the Control Unit
Proceed as follows to plug the Control Unit onto a Power Module:
1.
Place the two catches of the
Control Unit in the matching grooves of the Power Module.
2.
Press the Control Unit onto the
Power Module until you hear that it
latches.
You have now plugged the Control Unit onto the Power Module.
Removing the Control Unit
Remove the Control Unit from the Power Module by pressing the release mechanism.
Page 8
Installing
3.1 Plugging the Control Unit onto the Power Module
CU240B-2 and CU240E-2 Control Units
8 Compact Operating Instructions, 01/2017, A5E39910322B AA
Special features for the PM230 Power Module IP55, FSA … FSC
To insert or detach the Control Unit, you must release eight
or ten fixing screws of the cover
and then remove the cover. The Power Module release mechanism is
shown in the diagram. Attach the cover again before you commission
the inverter. Do not damage the seal of the cover when attaching it.
Adapter for operating a PM230 IP55 Power Module
For operating the Control Unit with a PM230 IP55 Power Module, FSA … FSC, an adapter is required between the Control Unit and operator panel (BOP-2 or IOP).
The adapter, which is included in the scope of delivery of the Power Module, is too short for the CU240E-2 Control Unit. The matching adapter for the CU240E-2 Control Unit can be ordered through the KnorrTec company.
Article number 10055500
Figure 3-1 Insert the KnorrTec adapter on the interface for the operator panel
Page 9
Installing
3.2 Overview of the interfaces
CU240B-2 and CU240E-2 Control Units Compact Operating Instructions, 01/2017, A5E39910322B AA
9
3.2
Overview of the interfaces
Interfaces at the front of the Control Unit
To access the interfaces at the front of the Control Unit, you must lift the Operator Panel (if one is being used) and open the front doors.
Memory card slot
Terminal strips
Bus termination, only for USS and Modbus field buses
Fieldbus interface at the lower side
Selecting the fieldbus address
On all Control Units with the exception of CU240E
-2 PN and
CU240E
-2 PN-F
Status LED
USB interface for connection to a PC
Switch for AI
0 and AI 1
1)
(U/I)
I 0/4 mA … 20 mA
U -10/0 V … 10 V
Interface to the operator panel
AI 1 is not available on the CU240B-2 Control Unit
Table 3- 1 Number of inputs and outputs
Digital
inputs DI
Digital
outputs DO
Analog
inputs AI
Analog
outputs AO
Fail-safe digital
inputs F-DI
1)
CU240B-2, CU240B-2 DP
4 1 1 1 0
CU240E-2, CU240E-2 DP,
CU240E-2 PN
6 3 2 2 1
CU240E-2 F, CU240E-2 DP-F,
CU240E-2 PN-F
6 3 2 2 3
1)
Each fail-safe digital input F-DI used takes up two digital inputs DI
Page 10
Installing
3.2 Overview of the interfaces
CU240B-2 and CU240E-2 Control Units
10 Compact Operating Instructions, 01/2017, A5E39910322B AA
Table 3- 2 Permissible cable and wiring options
Solid or flexible conduc-
tors
Finely stranded con-
ductor with non-
insulated end sleeve
Finely stranded con-
ductor with partially
insulated end sleeve
Two finely stranded conductors with the same cross-section
with partially insulated
twin end sleeves
Wiring the terminal strip in compliance with EMC
If you use shielded cables, then you must connect the shield to the mounting plate of the control cabinet or with the shield support of the inverter through a good electrical connection and a large surface area.
Use the shield connection plate of the Control Unit as shield support and strain relief.
Table 3- 3 Article numbers
Shield connection kit 2 for the CU240B-2 and CU240E-2 Control Units with
all fieldbus interfaces except for PROFINET.
6SL3264-1EA00-0HA0
Shield connection kit 3 for the CU230P-2 and CU240E-2 Control Units with
PROFINET interface
6SL3264-1EA00-0HB0
Additional information about EMC-compliant wiring is available on the Internet: EMC installation guideline (http://support.automation.siemens.com/WW/view/en/60612658)
Interfaces at the lower side of the CU240B-2 and CU240E-2 Control Units
Page 11
Installing
3.3 Terminal strips on CU240B-2 Control Units
CU240B-2 and CU240E-2 Control Units Compact Operating Instructions, 01/2017, A5E39910322B AA
11
3.3
Terminal strips on CU240B-2 Control Units
Terminal strips with wiring example
Figure 3-2 Wiring example of the digital inputs with the internal inverter 24 V power supply
All terminals labelled with reference potential "GND" are connected internally in the inverter.
Reference potential "DI COM" is electrically isolated from "GND".
→ if, as described above, you use the 24-V power supply from terminal 9 to supply the digital inputs, then you must connect "GND" with "DI COM" at the terminals.
When an optional 24-V power supply is connected to terminals 31, 32, the Control Unit remains in operation even after the Power Module has been disconnected from the line supply. The Control Unit thus maintains the fieldbus communication, for example.
→ At terminals 31, 32, only connect a power supply that is in accordance with SELV (Safety Extra Low Voltage) or PELV (Protective Extra Low Voltage).
→ if you also wish to use the power supply at terminals 31, 32 for the digital inputs, then you
must connect "DI COM" and "GND IN" with one another at the terminals.
You may use the internal 10V power supply or an external power supply for the analog input.
→ If you use the internal 10 V power supply, you must connect AI 0- to GND.
Page 12
Installing
3.3 Terminal strips on CU240B-2 Control Units
CU240B-2 and CU240E-2 Control Units
12 Compact Operating Instructions, 01/2017, A5E39910322B AA
Additional options for wiring the digital inputs
Connecting P-switching contacts with an external
power supply
You must remove the jumper between terminals 28 and 69 if it is necessary to have electrical isolation between the ex
ternal power supply and the internal
inverter power supply.
Connecting M-switching contacts with an external
power supply
It is not permissible that terminals 28 and 69 are connected with one another.
Page 13
Installing
3.4 Factory setting of the CU240B-2 interfaces
CU240B-2 and CU240E-2 Control Units Compact Operating Instructions, 01/2017, A5E39910322B AA
13
3.4
Factory setting of the CU240B-2 interfaces
The factory setting of the terminals depends on which fieldbus the Control Unit supports.
Control Units with PROFIBUS interface
The function of the fieldbus interface and digital inputs DI 0, DI 1 depends on DI 3.
--- No function.
DO 0: p0730
AO 0: p0771[0]
DI x: r0722.x
Speed setpoint (main setpoint): p1070[0] = 2050[1]
Figure 3-3 Factory setting of the CU240B-2 DP Control Unit
Page 14
Installing
3.4 Factory setting of the CU240B-2 interfaces
CU240B-2 and CU240E-2 Control Units
14 Compact Operating Instructions, 01/2017, A5E39910322B AA
Control Units with USS interface
The fieldbus interface is not active.
--- No function.
DO 0: p0730
AO 0: p0771[0]
DI x: r0722.x
AI 0: r0755[0]
Speed setpoint (main setpoint): p1070[0] = 755[0]
Figure 3-4 Factory setting of the CU240B-2 Control Unit
Changing the function of the terminals
The function of the terminals marked in color in the two figures above, can be set.
In order that you do not have to successively change terminal for terminal, several terminals can be jointly set using default settings ("p0015 Macro drive unit").
The terminal settings made in the factory described above correspond to the following default settings:
Default setting 12 (p0015 = 12): "Standard I/O with analog setpoint"
Default setting 7 (p0015 = 7): "Fieldbus with data set switchover"
Further default settings can be found in the Operating Instructions.
Overview of the manuals (Page 33)
Page 15
Installing
3.5 Terminal strips on CU240E-2 Control Units
CU240B-2 and CU240E-2 Control Units Compact Operating Instructions, 01/2017, A5E39910322B AA
15
3.5
Terminal strips on CU240E-2 Control Units
Terminal strips with wiring example
Figure 3-5 Wiring example of the digital inputs with the internal inverter 24 V power supply
All terminals labelled with reference potential "GND" are connected internally in the inverter.
Reference potentials "DI COM1" and "DI COM2" are electrically isolated from "GND". → if, as described above, you use the 24-V power supply from terminal 9 to supply the digital
inputs, then you must connect "GND" with "DI COM1" and "DI COM2" at the terminals.
When an optional 24-V power supply is connected to terminals 31, 32, the Control Unit remains in operation even after the Power Module has been disconnected from the line supply. The Control Unit thus maintains the fieldbus communication, for example.
→ At terminals 31, 32, only connect a power supply that is in accordance with SELV (Safety Extra Low Voltage) or PELV (Protective Extra Low Voltage).
→ if you also wish to use the power supply at terminals 31, 32 for the digital inputs, then you
must connect "DI COM1/2" and "GND IN" with one another at the terminals.
You may use the internal 10V power supply or an external power supply for the analog inputs.
→ If you use the internal 10 V power supply, you must connect AI 0- or AI 1- to GND.
Page 16
Installing
3.5 Terminal strips on CU240E-2 Control Units
CU240B-2 and CU240E-2 Control Units
16 Compact Operating Instructions, 01/2017, A5E39910322B AA
Additional options for wiring the digital inputs
Connecting P-switching contacts with an external
power supply
If you wish to connect the external and the internal inverter power supply vol
t-
ages with one another, then you must connect "GND" with termina
ls 34 and
69 at the terminals.
Connecting M-switching contacts with an external
power supply
Connect terminals 69 and 34 at the te
rminals.
Page 17
Installing
3.6 Factory setting of the CU240E-2 interfaces
CU240B-2 and CU240E-2 Control Units Compact Operating Instructions, 01/2017, A5E39910322B AA
17
3.6
Factory setting of the CU240E-2 interfaces
The factory setting of the terminal strip depends on the Control Unit.
Control Units with PROFIBUS or PROFINET interface
The function of the fieldbus interface and digital inputs DI 0, DI 1 depends on DI 3.
--- No function.
DO x: p073x
AO 0: p0771[0]
DI x: r0722.x
Speed setpoint (main setpoint): p1070[0] = 2050[1]
Figure 3-6 Factory setting of CU240E-2 DP(-F) and CU240E-2 PN(-F) Control Units
Page 18
Installing
3.6 Factory setting of the CU240E-2 interfaces
CU240B-2 and CU240E-2 Control Units
18 Compact Operating Instructions, 01/2017, A5E39910322B AA
Control Units with USS interface
The fieldbus interface is not active.
--- No function.
DO x: p073x
AO 0: p0771[0]
DI x: r0722.x
AI 0: r0755[0]
Speed setpoint (main setpoint): p1070[0] = 755[0]
Figure 3-7 Factory setting of the CU240E-2 and CU240E-2 F Control Units
Changing the function of the terminals
The function of the terminals marked in color in the two figures above, can be set.
In order that you do not have to successively change terminal for terminal, several terminals can be jointly set using default settings ("p0015 Macro drive unit").
The terminal settings made in the factory described above correspond to the following default settings:
Default setting 12 (p0015 = 12): "Standard I/O with analog setpoint"
Default setting 7 (p0015 = 7): "Fieldbus with data set switchover"
Further default settings can be found in the Operating Instructions.
Overview of the manuals (Page 33)
Page 19
CU240B-2 and CU240E-2 Control Units Compact Operating Instructions, 01/2017, A5E39910322B AA
19
4
4.1
Tools to commission the converter
Operator panel
An operator panel is used to commission, troubleshoot and control the inverter, as well as to back up and transfer the inverter settings.
The
Intelligent Operator Panel (IOP)
is available for snapping onto the inverter, or as handheld with a connecting cable to the inverter. The graphics-capable plain text display of the IOP enables intuitive operation and diagnostics of the inverter.
The IOP is available in two versions:
● With European languages
● With Chinese, English and German
Additional information about the compatibility of the IOP and inverters is available in the Internet:
Compatibility of the IOP and Control Units (http://support.automation.siemens.com/WW/view/en/67273266)
The
Operator Panel BOP-2
for snapping onto the inverter has a two-line display for
diagnostics and operating the inverter.
Operating Instructions of the BOP-2 and IOP operator panels:
Overview of the manuals (Page 33)
PC tools
STARTER
and
Startdrive
are PC tools that are used to commission, troubleshoot and control the inverter, as well as to back up and transfer the inverter settings. You can connect the PC with the inverter via USB or via the PROFIBUS / PROFINET fieldbus.
Connecting cable (3 m) between PC and inverter: Article number 6SL3255-0AA00-2CA0
STARTER DVD: Article number 6SL3072-0AA00-0AG0
Startdrive DVD: Article number 6SL3072-4CA02-1XG0
STARTER (http://support.automation.siemens.com/WW/view/en/26233208)
Startdrive (http://support.automation.siemens.com/WW/view/en/68034568)
STARTER videos (http://www.automation.siemens.com/mcms/mc-drives/en/low-voltage-
inverter/sinamics-g120/videos/Pages/videos.aspx)
Startdrive tutorial (http://support.automation.siemens.com/WW/view/en/73598459)
Page 20
Commissioning
4.2 Commissioning with BOP-2 operator panel
CU240B-2 and CU240E-2 Control Units
20 Compact Operating Instructions, 01/2017, A5E39910322B AA
4.2
Commissioning with BOP-2 operator panel
Plugging on an operator panel
Procedure
To plug an Operator Panel on the Control Unit, proceed as follows:
1.
Locate the lower edge of the Operator Panel into the matching recess of the Control Unit.
2.
Plug the Operator Panel onto the inverter until the latch audibly engages.
You have plugged an operator panel onto the Control Unit.
T
he operator panel is ready for operation when you connect the inverter
to the power supply.
4.2.1
Quick commissioning with the BOP-2
Starting quick commissioning
Preconditions
The power supply is switched on.
The operator panel displays setpoints and actual values.
Procedure
Proceed as follows to carry out quick commissioning:
Press the ESC key.
Press one of the arrow keys until the BOP-2 displays the "SETUP" menu.
To start quick commissioning, in the "SETUP" menu, press the OK key.
If you wish to restore all of the parameters to the factory setting before the quick commissioning, proceed as follows:
1. Press the OK key.
2. Switchover the display using an arrow key: nO YES
3. Press the OK key.
Page 21
Commissioning
4.2 Commissioning with BOP-2 operator panel
CU240B-2 and CU240E-2 Control Units Compact Operating Instructions, 01/2017, A5E39910322B AA
21
When selecting an application class, the inverter assigns the appropriate default settings to the motor control:
Standard Drive Control (Page 22)
Dynamic Drive Control (Page 24)
● EXPERT: This procedure is described in the operating instructions.
Overview of the manuals (Page 33)
Selecting a suitable application class
When selecting an application class, the inverter assigns the appropriate settings to the motor control.
Application class
Standard Drive Control
Dynamic Drive Control
Characteristics
Typical settling time after a speed change: 100 ms … 200 ms
Typical settling time after a sudden load change: 500 ms
Standard Drive Control is suitable for the following re­quirements:
– Motor power
ratings < 45 kW
– Ramp-up time
0 Rated speed (dependent on the rated motor power): 1 s (0.1 kW) … 10 s (45 kW)
– Applications with constant load torque
without load surges
Standard Drive Control is insensitive to inaccu- rate motor data settings
Typical settling time after a speed change: < 100 ms
Typical settling time after a sudden load change: 200 ms
Dynamic Drive Con- trol controls and lim­its the motor torque
Torque accuracy that can be achieved: ± 5 % for 15 % … 100 % of the rated speed
We recommend Dynamic Drive Control for the following applications:
– Motor power ratings > 11 kW – For load surges of 10 % … >100 % of the
rated motor torque
Dynamic Drive Control is necessary for a ramp-up time 0 rated speed (dependent on the rated motor power): < 1 s (0.1 kW) … < 10 s (132 kW).
Application ex­amples
Pumps, fans, and compressors with flow char- acteristic
Wet or dry blasting technology
Mills, mixers, kneaders, crushers, agitators
Horizontal conveyor technology (conveyor
belts, roller conveyors, chain conveyors)
Basic spindles
Pumps and compressors with displacement
machines
Rotary furnaces
Extruder
Centrifuge
Motors that can be operated
Induction motors Induction and synchronous motors
Page 22
Commissioning
4.2 Commissioning with BOP-2 operator panel
CU240B-2 and CU240E-2 Control Units
22 Compact Operating Instructions, 01/2017, A5E39910322B AA
Application class
Standard Drive Control
Dynamic Drive Control
Power Modules that can be op­erated
PM240-2, PM240P-2
Max. output frequency
550 Hz 240 Hz
Torque control
Without torque control
Speed control with lower-level torque control
Commissioning
Contrary to "Dynamic Drive Control" a speed controller does not have to be set
In comparison to the "EXPERT" setting: – Simplified commissioning using preas-
signed motor data
– Reduced number of parameters
Standard Drive Control is preset for Power Modules, frame size A … frame size C
Reduced parameter quantity when compared to the "EXPERT" setting:
Dynamic Drive Control is preset for Power Modules, frame size D … frame size F
4.2.2
Standard Drive Control
Select the motor standard.
● KW 50HZ: IEC
● HP 60HZ: NEMA
KW 60HZ: IEC 60 Hz
Set the inverter supply voltage.
Select the motor type. If a 5-digit motor code is stamped on the motor rating plate, select the corresponding motor type with motor code.
Motors without motor code stamped on the rating plate:
INDUCT: Third-party induction motor
● 1L… IND: 1LE1, 1LG6, 1LA7, 1LA9 induction motors
Motors with motor code stamped on the rating plate:
1LE1 IND 100: 1LE1 . 9
● 1PC1 IND: 1PC1
● 1PH8 IND: Induction motor
● 1FP1: Reluctance motor
Depending on the inverter, the motor list in BOP-2 can deviate from the list shown above.
If you have selected a motor type with motor code, you must now enter the motor code. The inverter assigns the following motor data corresponding to the motor code.
If you do not know the motor code, then you must set the motor code = 0, and enter motor data from p0304 and higher from the rating plate.
Page 23
Commissioning
4.2 Commissioning with BOP-2 operator panel
CU240B-2 and CU240E-2 Control Units Compact Operating Instructions, 01/2017, A5E39910322B AA
23
87 Hz motor operation The BOP-2 only indicates this step if you selected IEC as the motor standard (EUR/USA, P100 = KW 50HZ).
Rated motor voltage
Rated motor current
Rated motor power
Rated motor frequency
Rated motor speed
Motor cooling:
● SELF: Natural cooling
FORCED: Forced-air cooling
● LIQUID: Liquid cooling
NO FAN: Without fan
Select the basic setting for the motor control:
● VEC STD: Constant load; typical applications include conveyor drives
PUMP FAN: Speed-dependent load; typical applications include pumps and fans
Select the default setting for the interfaces of the inverter that is suitable for your application. The available default settings can be found in the operating instructions.
Overview of the manuals (Page 33)
Figure 4-1 Minimum and maximum motor speed
Figure 4-2 Ramp-up and ramp-down time of the motor
Ramp-down time after the OFF3 command
Page 24
Commissioning
4.2 Commissioning with BOP-2 operator panel
CU240B-2 and CU240E-2 Control Units
24 Compact Operating Instructions, 01/2017, A5E39910322B AA
Motor data identification Select the method which the inverter uses to measure the data of the connected motor:
● OFF: No motor data identification
STILL: Default setting: Measure the motor data at standstill. The inverter switches off the
motor after the motor data identification has been completed.
Complete quick commissioning as follows:
1. Switchover the display using an arrow key: nO YES
2. Press the OK key.
You have completed quick commissioning.
4.2.3
Dynamic Drive Control
Select the motor standard.
● KW 50HZ: IEC
● HP 60HZ: NEMA
KW 60HZ: IEC 60 Hz
Set the inverter supply voltage.
Select the motor type. If a 5-digit motor code is stamped on the motor rating plate, select the corresponding motor type with motor code.
Motors without motor code stamped on the rating plate:
INDUCT: Third-party induction motor
● 1L… IND: 1LE1, 1LG6, 1LA7, 1LA9 induction motors
Motors with motor code stamped on the rating plate:
1LE1 IND 100: 1LE1 . 9
● 1PC1 IND: 1PC1
● 1PH8 IND: Induction motor
● 1FP1: Reluctance motor
Depending on the inverter, the motor list in BOP-2 can deviate from the list shown above.
If you have selected a motor type with motor code, you must now enter the motor code. The inverter assigns the following motor data corresponding to the motor code.
If you do not know the motor code, then you must set the motor code = 0, and enter motor data from p0304 and higher from the rating plate.
87 Hz motor operation The BOP-2 only indicates this step if you selected IEC as the motor standard (EUR/USA, P100 = KW 50HZ).
Rated motor voltage
Page 25
Commissioning
4.2 Commissioning with BOP-2 operator panel
CU240B-2 and CU240E-2 Control Units Compact Operating Instructions, 01/2017, A5E39910322B AA
25
Rated motor current
Rated motor power
Rated motor frequency
Rated motor speed
Motor cooling:
SELF: Natural cooling
FORCED: Forced-air cooling
● LIQUID: Liquid cooling
NO FAN: Without fan
Select the basic setting for the motor control:
● OP LOOP: Recommended setting for standard applications
CL LOOP: Recommended setting for applications with short ramp-up and ramp-down
times. This setting is not suitable for hoisting gear and cranes/lifting gear.
HVY LOAD: Recommended setting for applications with a high break loose torque.
Select the default setting for the interfaces of the inverter that is suitable for your application. The available default settings can be found in the operating instructions.
Overview of the manuals (Page 33)
Figure 4-3 Minimum and maximum motor speed
Figure 4-4 Ramp-up and ramp-down time of the motor
Ramp-down time after the OFF3 command
Page 26
Commissioning
4.2 Commissioning with BOP-2 operator panel
CU240B-2 and CU240E-2 Control Units
26 Compact Operating Instructions, 01/2017, A5E39910322B AA
Motor data identification: Select the method which the inverter uses to measure the data of the connected motor:
OFF: Motor data is not measured.
STIL ROT: Recommended setting: Measure the motor data at standstill and with the motor rotating.
The inverter switches off the motor after the motor data identification has been completed.
STILL: Default setting: Measure the motor data at standstill.
The inverter switches off the motor after the motor data identification has been completed.
Select this setting if the motor cannot rotate freely – for example, if the traversing range is mechanically limited.
ROT: Measure the motor data with the motor rotating.
The inverter switches off the motor after the motor data identification has been completed.
ST RT OP: setting same as STIL ROT.
The motor accelerates to the currently set setpoint after the motor data identification.
STILL OP: setting same as STILL.
After the motor data identification, the motor accelerates to the currently set setpoint.
Complete quick commissioning:
● Switch over the display using an arrow key: nO → YES
● Press the OK key.
You have completed quick commissioning.
4.2.4
Identifying the motor data and optimizing the closed-loop control
The inverter has several techniques to automatically identify the motor data and optimize the speed control.
To start the motor data identification routine, you must switch-on the motor via the terminal strip, fieldbus or from the operator panel.
WARNING
Risk of death due to machine motion while motor data identification is active
For the stationary measurement, the motor can make several rotations. The rotating measurement accelerates the motor up to its rated speed. Secure dangerous machine parts before starting motor data identification:
Before switching on, ensure that nobody is working on the machine or located within its working area.
Secure the machine's work area against unintended access.
Lower hanging/suspended loads to the floor.
Page 27
Commissioning
4.2 Commissioning with BOP-2 operator panel
CU240B-2 and CU240E-2 Control Units Compact Operating Instructions, 01/2017, A5E39910322B AA
27
Preconditions
You selected a method of motor data identification during quick commissioning, e.g. measuring motor data while the motor is stationary.
When quick commissioning is complete, the inverter issues alarm A07991.
The motor has cooled down to the ambient temperature.
An excessively high motor temperature falsifies the motor data identification results.
Procedure when using the BOP-2 operator panel
To start the motor data identification, proceed as follows:
Press the HAND/AUTO key.
The BOP-2 displays the symbol indicating manual operation.
Switch on the motor.
During motor data identification, "MOT-ID" flashes on the BOP-2.
If the inverter again outputs alarm A07991, then it waits for a new ON command to start the rotating measurement.
If the inverter does not output alarm A07991, switch off the motor as described below, and switch over the inverter control from HAND to AUTO.
Switch on the motor to start the rotating measurement.
During motor data identification, "MOT-ID" flashes on the BOP-2.
The motor data identification can take up to 2 minutes depending on the rated motor power.
Depending on the setting, after motor data identification has been completed, the inverter switches off the motor - or it accelerates it to the setpoint.
If required, switch off the motor.
Switch the inverter control from HAND to AUTO.
You have completed the motor data identification.
Page 28
Commissioning
4.3 Connecting the inverter to the fieldbus
CU240B-2 and CU240E-2 Control Units
28 Compact Operating Instructions, 01/2017, A5E39910322B AA
4.3
Connecting the inverter to the fieldbus
Where can I find instructions for the fieldbus connection of the inverter?
Instructions for connecting to a fieldbus can be downloaded from the Internet:
● Application examples (http://support.automation.siemens.com/WW/view/en/60733299)
Operating Instructions: CU240B/E-2 operating instructions
(https://support.industry.siemens.com/cs/ww/en/view/109478828)
"Fieldbuses" function manual: Manuals for the Control Unit (http://support.automation.siemens.com/WW/view/en/30563628/133300)
Description files for fieldbuses
The description files are electronic device data sheets which contain all the required information of a higher-level controller. You can configure and operate the inverter on a fieldbus with the appropriate description file.
Generic Station Description for PROFIBUS: GSD (http://support.automation.siemens.com/WW/view/en/23450835)
GSD Markup Language for PROFINET: GSDML (http://support.automation.siemens.com/WW/view/en/26641490)
Ethernet/IP: EDS (http://support.automation.siemens.com/WW/view/en/78026217)
Alternative for the download for GSD and GSDML
GSD and GSDML are saved in the inverter. If you set p0804 = 12, then the inverter writes the GSD or the GSDML to the memory card that has been inserted. For instance, you can transfer the file to a PC from the memory card.
Examples for telegrams via PROFIBUS and PROFINET
Telegram 1:
STW1
Control word 1
ZSW1
Status word 1
PZD01/02
Process data 16-bit
NSOLL_A
Speed setpoint
NIST_A
Speed actual value
Page 29
Commissioning
4.3 Connecting the inverter to the fieldbus
CU240B-2 and CU240E-2 Control Units Compact Operating Instructions, 01/2017, A5E39910322B AA
29
Control word 1 (STW1), PZD receive word 1 (word: r2050[0], bits: r2090.00 … r2090.15)
Bit
Meaning
Explanation
0 0 = OFF1 The motor brakes with the ramp-down time p1121 of the ramp-function generator.
The inverter switches off the motor at standstill.
0 → 1 = ON The inverter goes into the "ready" state. If, in addition bit 3 = 1, then the inverter
switches on the motor.
1
0 = OFF2
Switch off the motor immediately, the motor then coasts down to a standstill.
1 = No OFF2
Precondition in order to be able to switch on the motor using bit 0 (ON command).
2
0 = Quick stop (OFF3)
The motor brakes with the OFF3 ramp-down time p1135 down to standstill.
1 = No quick stop (OFF3)
Precondition in order to be able to switch on the motor using bit 0 (ON command).
3
0 = Inhibit operation
Switch off the motor immediately → motor coasts down to a standstill.
1 = Enable operation
Precondition in order to be able to switch on the motor using bit 0 (ON command).
4
0 = Disable RFG
The inverter immediately sets its ramp-function generator output to 0.
1 = Do not disable RFG
The ramp-function generator can be enabled.
5
0 = Stop RFG
The output of the ramp-function generator stops at the actual value.
1 = Enable RFG
The output of the ramp-function generator follows the setpoint.
6 0 = Inhibit setpoint The inverter brakes the motor with the ramp-down time p1121 of the ramp-function
generator.
1 = Enable setpoint
Motor accelerates with the ramp-up time p1120 to the setpoint.
7 0 → 1 = Acknowledge faults Acknowledge fault. If the ON command is still active (bit 0 = 1), the inverter
switches to "closing lockout" state.
8, 9
Reserved
10
0 = No control via PLC
The inverter ignores the process data from the fieldbus.
1 = Control via PLC
Control via fieldbus, the inverter accepts the process data from the fieldbus.
11 1 = Direction reversal Invert setpoint in the inverter.
12
Not used
13 1 = MOP up Increase the setpoint saved in the motorized potentiometer.
14
1 = MOP down
Reduce the setpoint saved in the motorized potentiometer.
15 Reserved Changes over between settings for different operation interfaces (command data
sets).
Page 30
Commissioning
4.4 Frequently required parameters
CU240B-2 and CU240E-2 Control Units
30 Compact Operating Instructions, 01/2017, A5E39910322B AA
Status word 1 (ZSW1), PZD send word 1 (word: p2051[0], bits: p2080[0] … p2080[15])
Bit
Meaning
Comments
0
1 = Ready to start
Power supply switched on; electronics initialized; pulses locked.
1 1 = Ready Motor is switched on (ON/OFF1 = 1), no fault is active. With the command "Enable
operation" (STW1.3), the inverter switches on the motor.
2
1 = Operation enabled
Motor follows setpoint. See control word 1, bit 3.
3 1 = Fault active The inverter has a fault. Acknowledge fault using STW1.7.
4
1 = OFF2 inactive
Coast down to standstill is not active.
5
1 = OFF3 inactive
Quick stop is not active.
6
1 = Closing lockout active
It is only possible to switch on the motor after an OFF1 followed by ON.
7
1 = Alarm active
Motor remains switched on; no acknowledgement is necessary.
8 1 = Speed deviation within the
tolerance range
Setpoint / actual value deviation within the tolerance range.
9
1 = Master control requested
The automation system is requested to accept the inverter control.
10 1 = Comparison speed reached
or exceeded
Speed is greater than or equal to the corresponding maximum speed.
11
1 = torque limit reached
Comparison value for current or torque has been reached or exceeded.
12
1 = Holding brake open
Signal to open and close a motor holding brake.
13 0 = Alarm, motor overtempera-
ture
--
14
1 = Motor rotates clockwise
Internal inverter actual value > 0
0 = Motor rotates counter-
clockwise
Internal inverter actual value < 0
15 0 = Alarm, inverter thermal
overload
4.4
Frequently required parameters
Parameter
Explanation
p0015
Macro drive unit Set defaults for inputs and outputs via a macro.
r0018
Control Unit firmware version
p0096
Application class
0: Expert
1: Standard Drive Control
2: Dynamic Drive Control
p0100
IEC/NEMA mot stds
0: Europe 50 [Hz]
1: NEMA motor (60 Hz, US units)
2: NEMA motor (60 Hz, SI units)
p0304
Rated motor voltage [V]
p0305
Rated motor current [A]
p0307
Rated motor power [kW] or [hp]
p0310
Rated motor frequency [Hz]
p0311
Rated motor speed [rpm]
Page 31
Commissioning
4.4 Frequently required parameters
CU240B-2 and CU240E-2 Control Units Compact Operating Instructions, 01/2017, A5E39910322B AA
31
Parameter
Explanation
p0601
Motor temperature sensor type
Terminal 14 T1 motor (+) 0: No sensor (factory setting)
1: PTC (→ P0604)
2: KTY84 (→ P0604) 4: Bimetal
Terminal 15
T2 motor (-)
p0625
Motor ambient temperature during commissioning
[° C]
p0640
Current limit [A]
r0722
Digital inputs status
.0
Terminal 5
DI 0
Selection of the possible settings:
.1
Terminal 6
DI 1
p0840 ON/OFF (OFF1) p0844 no coast down (OFF2) p0848 no quick stop (OFF3) p0855 unconditionally release holding brake p1020 fixed speed setpoint selection bit 0 p1021 fixed speed setpoint selection bit 1 p1022 fixed speed setpoint selection bit 2 p1023 fixed speed setpoint selection bit 3 p1035 motorized potentiometer raise set­point p1036 motorized potentiometer lower set­point p2103 acknowledge faults p1055 jog bit 0
p1056 jog bit 1
p1110 inhibit negative direction p1111 inhibit positive direction p1113 setpoint inversion p1122 bypass ramp-function genera­tor p1140 enable/inhibit ramp-function generator p1141 continue/freeze ramp-function generator p1142 enable/inhibit setpoint p1230 DC braking activation p2103 acknowledge faults p2106 external fault 1 p2112 external alarm 1
p2200 technology controller enable
.2
Terminal 7
DI 2
.3
Terminal 8
DI 3
.4
Terminal 16
DI 4
.5
Terminal 17
DI 5
.11
Terminal 3, 4
AI 0
.12 Terminal 10, 11 AI 1
p0730
Signal source for terminal DO 0
Selection of the possible settings:
Terminals 19, 20 (NO contact)
Terminals 18, 20 (NC contact)
52.0 ready for switching on
52.1 ready for operation
52.2 operation enabled
52.3 fault present
52.4 coast down active (OFF2)
52.5 quick stop active (OFF3)
52.7 alarm present
52.14 motor rotates forwards
53.0 DC braking active
53.1 n_act > p2167 (n_off)
53.2 n_act ≤ p1080 (n_min)
53.3 I_act > p2170
53.4 n_act > p2155
53.5 n_act ≤ p2155
53.6 n_act ≥ n_set
53.10 technology controller output at lower limit
53.11 technology controller output at
upper limit
p0731
Signal source for terminal DO 1
Terminals 21, 22 (NO contact)
p0732
Signal source for terminal DO 2
Terminals 24, 25 (NO contact) Terminals 23, 25 (NC contact)
r0755
Analog inputs actual value [%]
[0]
Terminals 3, 4
AI 0 [1]
Terminals 10, 11
AI 1
p0756
Analog input type
0: Unipolar voltage input (0 V …+10 V) 1: Unipolar voltage input monitored (+2 V... +10 V) 2: Unipolar current input (0 mA …+20 mA) 3: Unipolar current input monitored (+4 mA …+20 mA)
4: Bipolar voltage input (-10 V...+10 V)
[0]
AI 0
[1] AI 1
p0771
Analog outputs signal source
Selection of the possible settings:
[0] Terminals 12, 13 AO 0 0: Analog output locked
21: Speed actual value 24: Output frequency, smoothed
25: Output voltage, smoothed 26: DC link voltage smoothed 27: Actual current value (smoothed
absolute value)
[1] Terminals 26, 27 AO 1
p0776
Analog outputs, type
0: Current output (0 mA … +20 mA) 1: Voltage output (0 V … +10 V) 2: Current output (+4 mA ... +20 mA)
[0]
AO 0
[1]
AO 1
Page 32
Commissioning
4.4 Frequently required parameters
CU240B-2 and CU240E-2 Control Units
32 Compact Operating Instructions, 01/2017, A5E39910322B AA
Parameter
Explanation
p0922
PROFIdrive telegram selection
p1001
Fixed speed setpoint 1
p1002
Fixed speed setpoint 2
p1003
Fixed speed setpoint 3
p1004
Fixed speed setpoint 4
p1058
Jog 1 speed setpoint
p1059
Jog 2 speed setpoint
p1070
Main setpoint
Selection of the possible settings:
0: Main setpoint = 0 755[0]: Analog input 0
1024: Fixed setpoint
1050: Motorized potentiometer 2050[1]: PZD 2 from the fieldbus
p1080
Minimum speed [rpm]
p1082
Maximum speed [rpm]
p1120
Ramp-function generator ramp-up time [s]
p1121
Ramp-function generator ramp-down time [s]
p1300
Open-loop/closed-loop control operating mode
Selection of the possible settings:
0: U/f control with linear characteristic 1: U/f control with linear characteristic and
FCC
2: U/f control with parabolic charac­teristic
20: Speed control (without encoder)
p1310
Starting (voltage boost) permanent
p1800
Pulse frequency setpoint
p1900
Motor data identification and rotating measurement
0: Locked 1: Identify motor data and optimize the speed controller 2: Identify motor data (at standstill) 3: Optimize the speed controller (rotating in operation) 11: Ident. motor data and opt. speed controller, change to operation (not available with PM230 or PM250 Power Module) 12: Identify motor data (at standstill), change to operation (not available with PM230 or PM250 Power Mod-
ule)
p2030
Fieldbus interface protocol selection
The possible settings depend on the Control Unit:
0: No protocol 1: USS 2: Modbus RTU
3: PROFIBUS
5: BacNet 7: PROFINET 8: P1
10: EtherNet/IP
r2050
Words received via fieldbus (16 bit) r2050[0]: PZD01 … r2050[11]: PZD12
p2051
Words sent via fieldbus (16 bit) p2051[0]: PZD01 … p2051[16]: PZD17
p2080
Binector-connector converter, status word 1 p2080[0]: Bit 0 … p2080[15]: Bit 15
r2090
PROFIdrive PZD1 receive bit-by-bit (control word 1) r2090.00: Bit 0 … r2090.15: Bit 15
Page 33
CU240B-2 and CU240E-2 Control Units Compact Operating Instructions, 01/2017, A5E39910322B AA
33
More information
5
5.1
Overview of the manuals
Manuals with additional information that can be downloaded:
CU240B/E-2 Compact Operating Instructions
(https://support.industry.siemens.com/cs/ww/en/view/109477361)
Commissioning the inverter (this manual)
C
U240B/E-2 operating instructions
(https://support.industry.siemens.com/cs/ww/en/view/109482994)
Installing, commissioning and maintaining the inverter. Advanced commissioning.
E
MC installation guideli
ne
(ht
tp://support.automation.siemens.com/WW/view/en/60612658)
EMC-compliant control cabinet design, potential equalization and cable routing
C
U240B/E-2 List Manual
(https://support.industry.siemens.com/cs/ww/en/view/109482961)
Parameter lists, alarms and faults. Graphic function diagrams.
"
Fieldbus" function manual
(https://support.industry.siemens.com/cs/ww/en/view/109477369)
Configuring fieldbuses.
"
Safety Integrated" function manual
(https://support.industry.siemens.com/cs/ww/en/view/109477367)
Commissioning and optimizing safety functions.
BO
P-2 operating instructions
(https://support.industry.siemens.com/cs/ww/en/view/42185248)
Using the operator panel.
Page 34
More information
5.2 Technical support
CU240B-2 and CU240E-2 Control Units
34 Compact Operating Instructions, 01/2017, A5E39910322B AA
IOP operating instructions (https://support.industry.siemens.com/cs/ww/en/view/109478559)
Using the operator panel, door mounting kit for mounting an IOP.
Application manual IOP (https://support.industry.siemens.com/cs/ww/en/view/109483443)
The commissioning wizards in the IOP
Power Module Installation Manual (https://support.industry.siemens.com/cs/ww/en/ps/13224/man)
Installing Power Modules, reactors and filters. Technical data, maintenance.
Accessories manual (https://support.industry.siemens.com/cs/ww/en/ps/13225/man)
Installation descriptions for inverter components, e.g. line reactors or line filters. The printed installation descriptions are supplied together with the components.
5.2
Technical support
+49 (0)911 895 7222
+44 161 446 5545
+39 (02) 24362000
+34 902 237 238
+33 (0) 821 801 122
You can find additional telephone numbers for Technical Support in the Internet:
Product support (http://www.siemens.com/automation/service&support)
Page 35
Page 36
Loading...