Siemens CSI Host Driver Installation Instructions Manual

Page 1
Installation Instructions
Document No. 565-718
December 15, 2009
CSI Host Drive
These installationinstructionscovertheconnection of the CSI Host Driver to the CSI System. For hardware installation of the PXC Modular, see document number 553-638.
r for PXC Modular
Product Description
The CSI Host Driver enables communication between the APO GEE CSI system.
®
Automation System and the
Product Numbers
PXC00-PE96.A PXC Modular RS-485 or Ethernet
ALN, 96 FLN nod es
PXC00-E96.A PXC Modular with BACnet/IP
ALN and BACnet MS/TP ALN, 96 FLN nodes
PXC100-PE96.A PXC Modular RS-485 or Ethernet
ALN, TX-I/O Support, 96 FLN nodes
PXC100-E9
PXX-485.3
LSM-INT-CSIHOST License for CSI Host PXC
6.A
PXC Modula and BACnet Support, 9
Expansion Module, three RS-485 FLN connections
Modular Driver
r B ACnet/IP ALN MS/TP ALN, TX-I/O
6 FLN nodes
Warning/Caution Notations
WARNING:
Personal injury/loss of life may occur if you do not follow the procedures as specied.
CAUTION:
Equipment d occur if you as specied
Expected I
The expected installation time is 30 minutes.
amage or loss of data may
do not follow the procedures
.
nstallation Times
Required Tools and Materials
Flat-blade screwdriver (1/8-inch blade width).
Wire strip
Cabling and connectors. See the Connecting the CSI Host Driver to the CSI System section.
pers.
CAUTION:
Always wear an electro-static discharge wrist strap and discharge accumulated static before touching eld panel components.
Accessories
538-670 538-675 536-004
tem Number: 565-718, Rev. AA
I
Trunk Int Trunk Interface II, 230V Modem Cable, DB-9 Female/DB-25
Male, Serial
erface II, 115V
Prerequisites
Driver hardware is installed according to its respective installation instructions.
•FLNTerm
Depending on the type of installation, other prerequisites may have to be completed.
ination blocks installed, if any.
P
age 1 of 4
Page 2
Document No. 565-718 Installation Instruction s December 15, 2009
Connecting the CSI Host Driver to the CSI System
Follow these s to the CSI sys
1. Make cable s per diagram in Figure 1 o r Figure 2.
teps to connect the CSI Host Driver
tem:
S
FLN
-
+
POWER
S
-
FLN
+
TAPE BACK
SHIELD
CSI DCU or
PCU Controller
GW1173R3
with RS-232 Port
RS-485 TRUNK CABLE (MAX 4000 ft/1200 m;
STANDARD 24 AWG LOW CAPACITANCE)
2. Install the Tr Figure 1 or Fig
3. Connect cables per diagram in Figure 1 or Figure 2.
4. Plug in the power supply for the Trunk Interface II per diagram in Figure 1 or Figure 2.
DRIVER
EACH FLN CONNECTOR REQUIRES
GROUND WIRE TO EARTH
POWER PACK
TRUNK INTERFACE II
RS-232 PORT
(25-PIN FEMALE)
237
235
RS-232 PORT (9-PIN MALE)
(P/N 538-583)
CABLE: 25-PIN MALE TO 9-PIN FEMALE
unk Interface II per diagram in
ure 2.
IF DRIVER
IS LESS THAN
50 CABLE FEET
(15 m)
FROM CSI PANEL
PLACE THE TRUNK
INTERFACE II
IN THE MBC
ENCLOSURE
(P/N 536-004)
Figure 1. Connecting the Driver to the CSI System (Recommended).
age 2 of 4
P
iemens Industry, Inc.
S
Page 3
Document No. 565-718
Installation Instructions
December 15, 2009
TAPE BACK
SHIELD
S
FLN
-
+
EACH FLN CONNECTOR REQUIRES
RS-485 TRUNK CABLE (MAX 4000 ft/1200 m;
STANDARD 24 AWG LOW CAPACITANCE)
POWER
S
-
FLN
+
+
1
TB2
-
2
PORT B
DRIVER
POWER PACK
TRUNK INTERFACE II
RS-232 PORT
(25-PIN FEMALE)
23 7
PORT A
78010 (HOST) TAP
GROUND WIRE TO EARTH
(P/N 538-583)
IF DRIVER IS
LESS THAN
50 CABLE FEET
(15 m)
FROM CSI PANEL
PLACE THE TRUNK
INTERFACE II
IN THE MBC
ENCLOSURE
CABLE: 25-PIN MALE TO 9-PIN FEMALE
(P/N 536-004)
NULL MODEM CONNECTOR:
9-PIN (MALE) TO 9-PIN (MALE)
9-PIN RIBBON CABLE
CSI PART #CBL004
TO CSI
GW1132R3
LAN
Figure 2. Connecting the Driver to the CSI System via 78010 (Host) Tap.
iemens Industry, Inc.
S
age 3 of 4
P
Page 4
Document No. 565-718 Installation Instruction s December 15, 2009
Information in this document is based on specications believed correct at the time of publication. The right is reserved to make changes as design improvements are introduced. Product or company names mentioned herein may be the trademarks of their respective owners. © 2009 Siemens Industry, Inc.
iemens Industry, Inc.
S
000 Deereld Parkway
1
uffalo Grove, IL 60089-4513
B
.S.A.
U
our feedb ack is important to us. If you have
Y
omments abo ut this document, send them to
c
BT_technical.editor.us.sbt@siemens.com.
S
ocument No. 565-718
D
ountry of Origin: US
C
age 4 of 4
P
Loading...