Siemens Cerberus Pyrotronics NIM-1M Installation Instructions Manual

Page 1
CERBERUS PYROTRONICS
Model NIM-1M Network Interface Modem Module
Cerberus Division
OPERATION
The CERBERUS PYROTRONICSTM Model NIM-1M plug-in modem board mounts to and is connected to the NIM-1W board to provide modem communication capability for an MXL System XNET network.
The modem transmission line connected to the NIM-1M can only be Style 4 and can be made using standard 18 AWG shielded twisted pair or data grade phone lines.
Note: A pair of NIM-1W / NIM-1M board sets is
referred to as a bridge in this document.
INSTALLATION
Remove all system power before installation, first battery and then AC. To power up, connect AC
first, then the battery.
Setting the Switches
Before mounting the NIM-1M modem module on the NIM-1W, set all the switches and configuration jumpers on both modules. Refer to the NIM-1W Installation Instructions, P/N 315-099106 for informa­tion on setting the switches on the NIM-1W.
NIM-1M SETTINGS
The NIM-1M has three configuration headers (refer to Figure 1). The NIM-1Ms are always connected in board sets, or pairs, with NIM-1Ws to form the bridge. Designate one board set as NIM-1M LOCAL and the other as NIM-1M REMOTE. Program the NIM-1Ms as shown in Table 1.
1ELBAT
sM1-MINEHTGNIMMARGORP
LACOLM1-MINETOMERM1-MIN
1PJ
2PJ
3PJ
NO
NO
FFO
1PJ
2PJ
3PJ
NO
FFO
NO
Mounting
The NIM-1M is mounted on the NIM-1W with 4 nylon spacers.
1. Snap the 4 nylon spacers into place in the holes on the underside of the NIM-1M board in the positions indicated in Figure 2.
2. Position the 4 spacers on the NIM-1M over the 4 holes on the component side of the NIM-1W. Refer to Figure 3 for representative location of the NIM-1M on the NIM-1W. Press the spacers firmly into place in the NIM-1W one at a time.
Figure 1 NIM-1M Module Board
Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, New Jersey 07932
P/N 315-099105-1
Cable Connections from NIM-1M to NIM-1W
The NIM-1M has a cable attached to the underside of the board that connects to JP2 of the NIM-1W. The cable plug is polarized and connects one way only. Refer to Figure 3 for the location of JP2.
Siemens Building Technologies, Ltd. 50 East Pearce Street Richmond Hill, Ontario L4B 1B7 CN
Page 2
P2
1
2
3
TB1
P1
JP2
JP3
JP1
BOARD
Figure 2 Installing the Spacers on the NIM-1M Module Board
NIM-1W
MW
JP4
1
87654321
SW1
JP2
12
9
10
D4 D5
ANY
ANY
TRBL
ENABLE
NIM-1M
INSERT 4 NYLON SPACERS
IN HOLES
IN POSITIONS INDICATED BY ARROWS
ON UNDERSIDE OF
P2
1
2
3
TB1
P1
NIM-1M
JP2
JP3
JP1
P6
+
W
X
87654321
SW2
JP1
D8
XMIT
Figure 3 Mounting the NIM-1M Module Board on the NIM-1M Module Board
ELECTRICAL CONNECTIONS
Note: All connections to the NIM-1W / NIM-1M
board set are power limited to NFPA 70 per NEC 760. All connections are also supervised.
NIM-1M Modem Connections
Modem connection to the NIM-1M can be made through the standard RJ11 jack (P2) or through TB1 (refer to Figure 2). If TB1 is used, connect TB1-1 TIP Local to TB1-1 TIP Remote and TB1-2 RING Local to TB1-2 RING Remote. P1 is for factory use only.
TB1 terminal assignments are as follows:
TB1-1 TIP TB1-2 RING TB1-3 LOCAL EARTH GROUND
TB1-3 must be connected to local earth ground. If shielded cable is used, connect shield to local earth ground at one side of modem connection only.
Note: When an MXL XNET network using the model
Refer to the NIM-1W Installation Instructions, P/N 315-099106, to continue with the installation of the NIM-1W / NIM-1M board set.
NIM-1W with model NIM-1M board set is brought on line, there may be some delay in network communications while the modems on the model NIM-1M board establish com­munications. This may cause a temporary system trouble which can be cleared once communications are established.
P/N 315-099105-1