Siemens Cerberus Pyrotronics LP-30 Operation And Installation Instructions Manual

Operation and Installation Instructions
CERBERUS PYROTRONICS
Model LP-30
Remote Station Module
TM
Cerberus Division
Operation
The CERBERUS PYROTRONICSTM Model LP-30 Remote Station (Leased Line) module, is designed to transmit Alarm and Trouble signals from a protected property to a fire headquarters, central station, or other similar supervised control center, via leased telephone lines. It meets the requirements of NEMA Standards and NFP A Standard No. 72C for remote station protective signaling systems so that it may be used with a CERBERUS PYROTRONICSTM Model LLA-5 receiving unit or with any other annunciator designed to these same two standards. Actuation of the module is from an alarm output signal from any type ZU Zone Module or type TS Two Stage module, along with that from the main control panel.
The module contains solid state circuitry to supply 24 VDC power for the alarm signal and supervision of the dedicated lines. The unit, which has built-in surge protection, operates on the polarity reversal principle. Under normal operating conditions the supervisory or alarm signal current is held between 3mA and 9mA DC. The total maximum load resistance of the leased line circuit, including the receiving equipment, is 5K ohms. Two input activation terminals are provided for flexibility of programming. The LP-30 must be used with an LLM-1.
The module also contains a manually operated disconnect switch which prevents an alarm signal from being transmitted over the leased lines when desired or during system tests. Operation of the switch will illuminate the yellow Disconnect LED and cause a system trouble condition. The LED will remain illumi­nated during an alarm condition, and can be lamp tested by operating the disconnect switch.
Installation
1. Mount the module to the horizontal mounting brackets in the control enclosure.
2. Install the Model JA-5 (5 in long) bus connector cable assembly between receptacle P2 of the module and receptacle P1 of the module or control panel immediately preceding it on the bus.
Note: If the preceding module is on another row
in the enclosure, a JA-24 (24 in long) bus connector cable assembly will be re­quired.
3. Modules are to be bus-connected from right to left. For two-row enclosures, the modules in the lower row are to be connected from left to right. Succeeding rows are to be alternately con­nected, right to left, left to right, etc.
4. If a module is the last module in the system, install either a JS-30 (30 in long) or JS-64 (64 in long) bus connector assembly from the unused receptacle of the last module to terminal 41* of the CP-35 control panel. This completes the module supervision circuit.
5. Wire terminals as shown in the Typical Wiring illustration on the back of this sheet.
Troubleshooting
If a trouble condition is indicated in the LP-30, be sure the disconnect switch is returned to Normal position.
*Terminal 17 of CP-30
Terminal 15 of CP-31
Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, New Jersey 07932
P/N 315-021309-5
Siemens Building Technologies, Ltd. 50 East Pearce Street Richmond Hill, Ontario L4B 1B7 CN
P/N 315-021309-5
Loading...