Siemens CERBERUS PYROTRONICS ALI-8 Installation Instructions Manual

Installation Instructions
Cerberus Division
CERBERUS PYROTRONICS
TM
Model ALI-8
The CERBERUS PYROTRONICS ALI-8 is an enclosure assembly that accom­modates up to eight TRI-60Ds to provide the interface between the MXL and the AnaLASER control panels (See also
Installation Instructions,
Fasten the enclosure securely to a clean, dry, shock-free, and vibration-free surface. Con­sider the following when mounting the box.
—Mounting height for visual and manual
access to the modules in the enclosure —Weight and size of the enclosure —Local mounting codes
P/N 315-092329).
TM
Model
TRI-60D
—The maximum cable length of 200 feet
(18 AWG) for the TRI-60Ds to the AnaLASER equipment
When mounting, position the backbox clear of obstruction so that the door can open freely and so that the modules are easily accessible.
TO INSTALL THE ALI-8
1. Slip the door off the hinges of the box and put it to one side temporarily.
2. Cover the opening in the door by placing the black metal plate over the studs located on the door.
Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, New Jersey 07932
P/N 315-093305-2
Figure 1
Enclosure for the ALI-8
Siemens Building Technologies, Ltd. 50 East Pearce Street Richmond Hill, Ontario L4B 1B7 CN
3. Fasten the plate to the door using the six 6-32 nuts provided.
4. (Refer to Figure 1.) Remove knockouts in the backbox where field wiring is required.
5. Place the interface plate over the four studs marked A in Figure 1, and secure it to the enclosure with the four 6-32 nuts provided.
6. Hold the empty enclosure against the wall at a height that provides easy access.
7. Mark drill points on the wall in the center of the two slots on the upper rear of the box.
8. Drill the two holes and screw in the top screws using 1/4" or 3/8" mounting hardware (user supplied). Leave a small gap between
the wall and each top screw.
9. Mount the enclosure on the two screws and then install the bottom screws.
10. Tighten all screws securely against the back wall of the enclosure.
11. Place the TRI-60Ds on the studs (marked B) of the interface plate in two rows of four across making sure that all of the screw terminals on the TRI-60Ds are facing in the same direction.
12. Fasten each TRI-60D to the interface plate using two 6-32 nuts provided.
13. Slip the door back on the hinges of the enclosure.
P/N 315-093305-2