Siemens CAB2-BD/-RD, CAB3-BD/-RD Installation Instructions Manual

Installation Instructions Models CAB2-BD/-RD and CAB3-BD/-RD
Medium and Large Enclosure Doors
INTRODUCTION The Models CAB2-BD/-RD and CAB3-BD/-RD Enclosure Doors from Siemens
Industry, Inc., are used with the CAB2-BB/-RB and CAB3-BB/-RB Enclosure Backboxes. Two doors, an outer and an inner, are required for each enclosure. The CAB2-BD and CAB3-BD outer and inner doors are black; the CAB2-RD and CAB3-RD outer doors are red and inner doors are black.
The outer door consists of the door frame and either two or three removable panels, depending on the enclosure size (two for the CAB2 and three for the CAB3). Each removable panel is secured to the door with 10-32 nuts. The removable panels may be clear (OD-LP), blank (OD-BP/-R), or vented (OD-GP/-R) depending on the applica­tion. The OD-BP-R and OD-GP-R panels are red. The outer door is attached to the backbox by hinge pins and secured to the backbox by keyed latch.
The inner door has two or three openings in it for the installation of an operator interface and other modules. There are eight threaded studs around each opening on the inner door. These threaded studs allow equipment installation on the door. The equipment is secured by 10-32 nuts. The inner door is permanently hinged left, is attached to the backbox by hinge pins, and is secured to the backbox by a ¼ turn fastener or a 10-32 x 1/2” screw (user provided), if desired.
CAB2-BD/-RD and CAB3-BD/-RD Enclosure Doors are for indoor use only in dry environments.
PRE-INSTALLATION Outer Door:
Determine the direction that the outer door is to open. If the door is to open to the left, no further action is required. If the door is to open to the right, the hinges must be moved to the right side of the backbox and the outer door lock must be moved to the left side of the outer door. (See page 2.)
Inner Door:
The handle for the inner door comes taped to the outside of the inner door. Remove the tape from the handle and from the door. To insert the handle, press the handle through the front of the opening in the inner door. It will snap into place. (Refer to Figure 1.)
P/N 315-033008-8
Siemens Industry, Inc.
Building Technologies Division
Figure 1 Inserting Handle Into Opening In Inner Door
INSTALLATION Outer door hinge and lock reversal (if required):
1. Note the location of the two rubber bumpers on the right side of the backbox, then remove them.
2. Remove the upper door hinge, turn the hinge upside down, and install on the right side of the backbox. (Refer to Figure 2.)
OUTER DOOR HINGE
Figure 2 Outer Door Hinge Revesal
Siemens Industry, Inc. Building Technologies Division
3. Repeat the above procedure for the lower door hinge.
P/N 315-033008-82
4. On the right side of the outer door, remove the ground strap. Reinstall the ground strap on the left side of the outer door. (Refer to Figure 5, page 4.)
5. Install the rubber bumpers on the left side of the backbox. (Refer to Figure 3.)
6. On the right side of the backbox, remove the lock bracket. Reinstall the lock bracket on the left side of the backbox. (Refer to Figure 3.)
RUBBER BUMPER
LOCK
BRACKET
Figure 3 Lock Bracket And Rubber Bumper Reversal
7. Remove the plug(s) for the lock(s) on the left side of the door. On the right side of the door, remove the lock(s). Reinstall the lock(s) on the left side of the door. Reinstall the plug(s) on the right side of the door.
PLUG
FOR
LOCK
LOCK
CAB
DOOR
Figure 4 Moving The Door Lock(s) And Plug(s)
Siemens Industry, Inc. Building Technologies Division
P/N 315-033008-83