Siemens SED2-0.75/22B, SED2-0.55/22B, SED2-2.2/22B, SED2-3/22B, SED2-4/22B Operating Instructions Manual

...
SED2 variable speed drives
Operating instructions
CM1U5192en
01.2002
Siemens Building Technologies
HVAC Products
HVAC Products 01.2002
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Introduction 01.2002
Table of contents
1 Introduction ...................................................................................................7
1.1 Purpose of this document .............................................................................7
1.2 Validity...........................................................................................................7
1.3 Target audience............................................................................................7
1.4 Document structure.......................................................................................7
1.5 Referenced documents.................................................................................7
1.6 Document conventions..................................................................................8
1.7 Environmental compatibility and disposal.....................................................9
2 Safety instructions.......................................................................................11
2.1 General........................................................................................................11
2.2 Commissioning............................................................................................11
2.3 Operation.....................................................................................................12
2.4 Repairs........................................................................................................12
3 Mechanical installation................................................................................13
3.1 Installing the SED2 after extended storage.................................................13
3.2 Ambient conditions......................................................................................13
3.3 Mounting......................................................................................................14
3.3.1 Dimensions of SED2 drives with IP20/NEMA 0 rating ................................14
3.3.1.1 Dimensions of SED2 frame sizes A to C.....................................................14
3.3.1.2 Dimensions of SED2 footprint filters for frame sizes A to C........................15
3.3.1.3 Dimensions of SED2 frame sizes D to F.....................................................15
3.3.2 Dimensions of SED2 drives with IP54/NEMA 12 rating ..............................16
3.3.2.1 Dimensions of SED2 frame sizes B and C..................................................16
3.3.2.2 Dimensions of SED2 frame sizes D to F.....................................................16
3.3.3 Mounting SED2 drives with IP20/NEMA 0 rating ........................................17
3.3.4 Mounting SED2 drives with IP54 / NEMA 12 rating ....................................18
4 Electrical installation....................................................................................19
4.1 General........................................................................................................19
4.1.1 Maximum length of motor cables ................................................................19
4.1.2 Operation with ungrounded systems...........................................................19
4.1.2.1 Precautions for ungrounded systems (IT protective systems) .................... 19
4.1.3 Operation with a residual current device (RCD)..........................................22
4.2 EMC-compatible installation........................................................................23
4.2.1 EMC-compatible wiring ...............................................................................23
4.3 Mains and motor connections .....................................................................25
4.3.1 Access to connection terminals: Frame size A............................................26
4.3.2 Access to connection terminals: Frame sizes B and C...............................27
4.3.3 Access to connection terminals: Frame sizes D to F IP20..........................28
4.3.4 Power and motor terminals: Frame sizes A to F.........................................30
HVAC Products Introduction 01.2002
4.3.5 Power connection for drives with a built-in EMC filter ................................31
4.3.6 Tightening torque for connection terminals ................................................ 34
4.3.7 Cross-sections for power and motor cables ............................................... 34
4.3.8 Block diagram showing typical installation ................................................. 36
4.3.9 Direction of rotation .................................................................................... 36
4.3.10 Star or delta connection..............................................................................37
4.3.11 Connecting several motors......................................................................... 37
4.3.12 External motor overload protection.............................................................37
4.4 Control terminals ........................................................................................ 38
4.5 SED2 block diagram...................................................................................39
5 Commissioning........................................................................................... 41
5.1.1 DIP switch settings.....................................................................................42
5.1.1.1 Setting the DIP switches on the I/O module...............................................42
5.1.1.2 DIP switch settings on the control board .................................................... 42
5.2 Checklist prior to start.................................................................................43
5.3 Operator panels for the SED2 .................................................................... 43
5.3.1 Description of the basic operator panel (BOP)...........................................43
5.3.2 Description of the advanced operator panel (AOP).................................... 44
5.3.3 Exchanging the operator panels................................................................. 44
5.3.4 Buttons and their functions on the operator panel (BOP and AOP) .......... 45
5.4 Commissioning modes...............................................................................46
5.4.1 Overview of commissioning with the BOP or AOP.....................................46
5.4.2 Quick commissioning.................................................................................. 46
5.4.3 Motor data for parameterization ................................................................. 48
5.4.4 Commissioning with the BOP or AOP ........................................................ 48
5.4.4.1 Country-specific default settings for operation with the BOP .....................48
5.4.4.2 Setting parameters with the BOP or AOP ..................................................49
5.4.5 Resetting SED2 parameters to the factory settings....................................50
5.4.6 Basic operation with the BOP..................................................................... 50
5.4.7 10 Hz test ................................................................................................... 50
5.4.8 General operation.......................................................................................51
6 Programming..............................................................................................53
6.1 Introduction to the SED2 system parameters............................................. 53
6.1.1 General notes ............................................................................................. 53
6.2 Access to parameters.................................................................................53
6.2.1 Parameter access levels (P0003)............................................................... 53
6.2.2 Parameter filter (P004)...............................................................................53
6.2.3 Diagram for a parameter overview ............................................................. 54
6.3 Basic functions of the SED2.......................................................................55
6.3.1 Digital inputs............................................................................................... 55
6.3.2 Analog inputs..............................................................................................57
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Introduction 01.2002
6.3.3 Analog outputs............................................................................................60
6.3.4 Frequency setpoint (P1000)........................................................................62
6.3.5 Selecting the command source (P0700) .....................................................62
6.3.6 OFF functions..............................................................................................63
6.3.7 Control types...............................................................................................63
6.3.8 Communication ...........................................................................................63
6.4 HVAC functions of the SED2 ......................................................................64
6.4.1 PID controller ..............................................................................................64
6.4.2 Belt failure detection without sensor (P2181)..............................................65
6.4.3 Belt failure detection with sensor (P0400)...................................................67
6.4.4 Staging pumps or fans ................................................................................68
6.4.5 Temperature control with LG-Ni 1000 sensor .............................................72
6.4.6 Bypassing the VSD.....................................................................................73
6.4.7 Hibernation mode........................................................................................75
6.5 System parameter list for levels 1 to 3........................................................77
6.6 Overview of factory and user parameter settings......................................105
7 Troubleshooting ........................................................................................107
7.1 Troubleshooting using the operator panel.................................................107
7.2 Error messages.........................................................................................108
7.2.1 Error code list............................................................................................108
7.2.2 Warning code lists.....................................................................................111
8 Technical data for the SED2 .....................................................................113
8.1 General technical data..............................................................................113
8.2 Type-specific data.....................................................................................115
9 Appendix ...................................................................................................119
9.1 Options......................................................................................................119
9.1.1 Retrofitting EMC filters for VSD frame sizes A to C ..................................120
9.2 Applicable standards.................................................................................120
9.3 List of abbreviations..................................................................................121
9.4 Index .........................................................................................................123
HVAC Products Introduction 01.2002
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Introduction 01.2002
1 Introduction
1.1 Purpose of this document
These operating instructions contain all the information necessary to correctly mount, install, c ommission, and parameterize (programming) SED2 variable speed drives (VSD) as well as for effective and troublefree operation.
1.2 Validity
The operating instructions apply to all SED2 variable speed drives, frame sizes A to F. They are supplied with the product, and are part of the full range of SED2 VSD literature.
1.3 Target audience
This document is primarily intended for installers, electrical installers, service technicians, and operators or end users of HVAC plants (Heating, Ventilating, and Air Conditioning).
1.4 Document structure
The document is divided into the following sections: Chapter 1 Introduction
Chapter 2 Safety instructions Chapter 3 Mechanical installation Chapter 4 Electrical installation and wiring of the motor and VSD Chapter 5 Commissioning
Description of basic and advanced operator panels Quick commissioning
Chapter 6 Programming (parameterization)
Description of functions
System parameter list Chapter 7 Troubleshooting, warning and error code lists Chapter 8 Technical data Chapter 9 Appendix:
Applicable standards and declarations of conformity
List of abbreviations, index
1.5 Referenced documents
Getting Started Guide:
The Getting started guide is a brief multilingual guide to provide users fast access to all the basic information necessary to install, set up, and operate the VSD.
Target audience: Ins tallers, ins talling engineers, and commissioning engineers. Engineering manual: Documentation on bas ics.
This manual contains in-depth information on all technical matters relating to the SED2 VSD. Target audience: Project design engineers , planners, users of the product, technical staff, and service.
CM1G5192X
CM1J5192en
HVAC Products Introduction 01.2002
Data sheet
The data sheet contains a brief description of functions, notes on use, type codes, accessories, ordering information, technical data, and a range overview. Target audience: Project design engineers, planners, purchasing and sales staff, and service.
1.6 Document conventions
Information pointing at immediate danger is printed under the heading “Danger” with the symbol shown in the left margin. Failure to observe this information may result in severe physical injury or death or severe property damage.
Information under the heading “Warning” is shown with the symbol in the left margin.
Failure to observe this category of information may result in physical injury and/or property damage.
Information under the heading “Caution” is shown with the symbol in the left margin.
Failure to observe this type of information may result in property damage and/or loss of data.
Other important information (headed “Important” or “Note”) is shown on a gray background. Failure to observe this information will not result in any damage.
This relates to additional information important for the safety of personnel and equipment, or provides details of additional options or technical requirements.
Helpful information to simplify the use of the product for the user.
"Authorized personnel" are persons familiar with installing, mounting, commissioning, and operating the equipment, and aware of the associated hazards. Authorized personnel must satisfy the following requirements:
They must be trained and authorized to switch on, switch off, disconnect, and ground electric circuits, and to attach warning labels in accordance with the established safety instructions.
They must have training in the proper care and use of protective devices in accordance with all prevailing safety regulations.
They must be trained in and capable of administering first aid.
CM1N5192en
Danger
Warning
Caution
Important
Note
.
..
.
Tips
Authorized personnel
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Introduction 01.2002
1.7 Environmental compatibility and disposal
This product was developed and manufactured using materials and processes which take full account of environmental issues and which comply with our environmental standards. Please not the following for disposal at the end of the product life, or in the event of its replacement:
For disposal, this product is defined as waste from electrical and electronic equipment (“electronic waste”); do not dispose of it as household waste. This applies particularly to the PCB assembly.
Always use the most environmentally compatible method of disposal, in line with the state-of-the-art technology in environmental protection, recycling, and waste management.
Observe all local and applicable laws.
Always aim for maximum re-use of the basic materials at minimum environmental stress. Observe any notes on materials and disposal that may be attached to individual components.
Use local depots and waste management companies, or refer to your supplier or manufacturer to return used products or to obtain further information on environmental compatibility and waste disposal.
The law may mandate special handling of components such as electrolytic capacitors and LCD panels, or it may be environmentally desirable.
The variable speed drive is delivered in re-usable packaging. Please retain the packaging for later use or in case you need to return the product to the manufacturer.
General notes
Special electronic components
Packaging
10/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Introduction 01.2002
11/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Safety instructions 01.2002
2 Safety instructions
The following warnings and notes on danger are provided for your safety and as a means of preventing damage to the product or to any components of the connected machinery. This section contains general warnings, preventive measures, and danger warnings, which apply to all work on the SED2 variable speed drives. Specific warnings applicable to particular tasks are summarized at the beginning of each chapter and repeated throughout the chapter as necessary at the relevant points.
Please read this information carefully, as it is provided for your personal safety, and to help extend the life of the SED2 variable speed drive and any equipment connected to it.
Refer to section 1.6 Document conventions for information on the format of warning notes and as sociated symbols.
2.1 General
This equipment uses hazardous voltages and drives potentially dangerous rotating
mechanical parts. Non-c ompliance with warnings or failure to follow the instructions in this manual may put lives at risk , or result in severe physical injury, or serious damage to property/equipment.
Only authorized personnel may work on this equipment. They must first acquaint
themselves with all the safety instructions, and installation and operating instructions in this manual. Successful and safe operation of this device depends on its proper handling, installation, commissioning, and operation.
Prevent children and other unauthorized persons from accessing the equipment. The DC link capacitors remain charged with dangerous voltages for five minutes after
power has been switched off. Do not open the device for five minutes after switching off the supply voltage.
Use the equipment only for purposes as specified by the manufacturer. Unauthorized modifications and use of spare parts or accessories not supplied or recommended by the manuf acturer of this equipment may cause fires, electric shock, and physical injury.
Keep these operating instructions within easy reach of the equipment and make them available to all users.
2.2 Commissioning
Only authorized personnel trained in the setup, installation, commissioning, and
operation of the product may work on the product and plant.
Only hard-wired mains connections are permissible. Ground the VSD (IEC 536,
Class 1, NEC and other relevant industry standards).
If a residual current device (RCD) is to be used, it must be a type B device. Do not connect machines with a 3-phase power supply fitted with EMC filters to the
mains via an earth leakage current circuit breaker (ELCB) (see DIN VDE 0160, section 6.5).
Format of warnings
Warning
Risk of electric shock
Danger
Purpose
Availability of the operating instructions
12/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Safety instructions 01.2002
The following terminals may carry dangerous voltages even when the variable speed drive is not running: – Power supply terminals L1, L2, L3. – Motor terminals U, V, W. – Link terminals DC-, DC+/B+, DC/R+, B-.
To prevent inductive and capacitive interference, connect the power, motor, and control cables to the variable speed drive as illustrated and described in section 4.2.1 “EMC­compatible wiring“.
2.3 Operation
SED2 variable speed drives operate at high voltages. Emergency stop facilities in accordance with EN 60204 IEC 204 (VDE 0113) must
remain operative in all operating modes of the control equipment. Resetting the emergency stop facility may not cause an uncontrolled or undefined restart.
In cases where faults in the control equipment could cause significant equipment
damage or severe physical injury (e.g., potentially dangerous short circuits), take additional external precautions or provide facilities to ensure or enforce safe operation even in the event of a short circuit (e.g., independent limit switches, mechanical interlocks, etc.).
Certain parameter settings can cause an automatic restart of the variable speed
drive following an fault or supply voltage failure, provided the fault has been eliminated/acknowledged or the supply voltage has been restored.
The variable speed drive is capable of protecting the motor from overload. (Motor
overload protection in accordance with UL 508C, section 42). See P0610 and P0335.
Protection against motor overload can be instituted via an external PTC thermistors
(temperature variable conductor) via a special input (Class 14/15, see also section
4.3.12, page 37).
Do not use the variable speed drive as an “Emergency Stop” mechanism
(see EN60204, 9.2.5.4).
2.4 Repairs
Only the Siemens service, repair centers authorized by Siemens, or authorized
personnel fully acquainted with all the warnings and operating procedures as specified in this manual may repair this equipment.
Replace defective parts or components using parts from the relevant spare parts
list.
Disconnect the power supply before opening the device.
Danger
Caution
Danger
Danger
13/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Mechanical installation 01.2002
3 Mechanical installation
3.1 Installing the SED2 after extended storage
Recharge the capacitors in the variable speed drive following an ex tended period of storage. Remember to calculate the storage time from the date of manufacture, and not from the date of delivery. The required procedure varies according to the storage period and is described below.
Period of storage Required action Preparation time
1 year or less Recharging not required. No preparation 1 to 2 years Before issuing the “Run” command, connect the variable speed
drive to the supply voltage for one hour.
1 hour
2 to 3 years Use a variable AC power source.
1. Apply 25% of the input voltage for 30 minutes.
2. Increase the voltage to 50% for a further 30 minutes.
3. Increase the voltage to 75% for a further 30 minutes.
4. Increase the voltage to 100% for a further 30 minutes. The variable speed drive is then ready for operation.
2 hours
3 or more years Use a variable AC power source.
1. Apply 25% of the input voltage for 2 hours.
2. Increase the voltage to 50% for a further 2 hours.
3. Increase the voltage to 75% for a further 2 hours.
4. Increase the voltage to 100% for a further 2 hours. The variable speed drive is then ready for operation.
8 hours
3.2 Ambient conditions
IP20 IP54 Min. operating temperature –10 °C –10 °C Max. operating temperature +40 °C* +40 °C
* Be aware of the potential increase in temperature inside the control cabinet (derating necessary; refer to the engineering manual).
Max. 95%, non-condensing.
If you want to install the VSD at an altitude of more than 1000 m, derating is required. (Refer to the engineering manual).
Install the VSD vertically for optimum cooling. Do not obstruct the vents on the VSD. Additional ventilation may be required if the drive is mounted horizontally. If mounted vertically, VSDs with a protection standard of IP20 may be installed side by side. A minimum clearance of 100 mm is necessary above and below the VSD. VSD of class IP54 require greater clearances. See section 3.3.4 "Mounting SED2 drives with IP54 / NEMA 12 rating".
Do not install the VSD in the vicinity of powerful sources for electromagnetic radiation.
Temperature
Humidity
Height above sea level
Overheating
Electromagnetic radiation
14/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Mechanical installation 01.2002
Do not install the VSD in an environment containing atmospheric pollutants such as dust, corrosive gases, etc. Devices subject to protection standard IP20 need additional protection from dust, atmospheric pollutants, and water.
Do not install the VSD in a location where it might be exposed to repeated shock or vibration.
3.3 Mounting
The device must be grounded.
Extremely dangerous conditions can arise if you do not correctly ground the
variable speed drive.
To ensure safe operation of the equipment, authorized persons must install and
commission it in full compliance with the notes and warnings set out in these operating instructions.
Take particular note of general and regional installation and safety regulations
regarding work on sites with dangerous voltages (e.g. EN 50178), and of the relevant regulations f or the correct use of tools and personal protective equipment.
Dangerous voltages may occur at the following terminals even when the variable speed drive is not running:
- Power supply terminals L1, L2, L3.
- Motor connection terminals U, V, W, DC-, DC+/B+, DC/R+, B-.
- Link terminals DC-, DC+/B+, DC/R+, B-.
Do not open the device for five minutes after switching off the supply voltage.
3.3.1 Dimensions of SED2 drives with IP20/NEMA 0 rating
3.3.1.1 Dimensions of SED2 frame sizes A to C
Dimensions
Frame size
AA
1
BCC
1
A
173 200 73 149 192.5
B
202 213 149 172 222.5
C
245 261 185 195 250
A
1
B
C
C
1
5
1
5
2
J
0
1
A
Frame size A
A1
C1
5
1
9
2
J
0
2
B
C
A
Frame sizes B and C
Atmospheric pollution
Shock
Danger
Danger
15/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Mechanical installation 01.2002
3.3.1.2 Dimensions of SED2 footprint filters for frame sizes A to C
Dimensions in mm
Frame size
ABCGHI JK
A
200 73 43.5 60 160 56 187 22
B
213 149 50.5 138 174 120 200 24
C
245 185 55 174 204 156 232 35
B
I
K
A
J
H
G
C
5192J03
I
K
A
J
H
C
5192J04
B
G
Filter for frame size A Filter for frame sizes B and C
3.3.1.3 Dimensions of SED2 frame sizes D to F
Dimensions in mm
Frame size
ABC
D
520 275 245
E
650 275 245
F
850
(with filter
1150)
350 320
5
1
9
2
J
0
5
A
B
C
16/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Mechanical installation 01.2002
3.3.2 Dimensions of SED2 drives with IP54/NEMA 12 rating
3.3.2.1 Dimensions of SED2 frame sizes B and C
Dimensions in mm
Frame size
ABC
B
385 270 268
C
606
350
284
B
C
A
5
1
9
2
J
0
6
3.3.2.2 Dimensions of SED2 frame sizes D to F
Dimensions in mm
Frame size
ABC
D
685 360 353
E
885 360 453
F
1150 450 473
A
B
C
5
1
9
2
J
0
7
17/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Mechanical installation 01.2002
3.3.3 Mounting SED2 drives with IP20/NEMA 0 rating
H
H
H
W
W
Frame size A
Frame size B
Frame sizes D, E and F
5192M01en
Hole spacing
Frame size
H in mm W in mm
Mounting materials
Tightening
torque
A
160
* 187
-
*56
2 x M4 bolts 2 x M4 nuts 2
x M4 spring lock washers 2 x M4 washers or mounting on DIN rail
2.5 Nm
B
174
* 200
138
* 120
4
x M4 bolts 4 x M4 nuts 4
x M4 spring lock washers 4
x M4 washers
2.5 Nm
C
204
* 232
174
* 156
4
x M5 bolts 4 x M5 nuts 4
x M5 spring lock washers 4
x M5 washers
3.0 Nm
D 486 235
4
x M8 bolts 4 x M8 nuts 4
x M8 spring lock washers 4
x M8 washers
13 Nm
E
616.4 235
4
x M8 bolts 4 x M8 nuts 4
x M8 spring lock washers 4
x M8 washers
13 Nm
F
810
1110withfilter
300
4
x M8 bolts 4 x M8 nuts 4
x M8 spring lock washers 4
x M8 washers
25 Nm
* with footprint filter
A minimum clearance of 100 mm is required above and below each variable speed drive.
Drilling plan for SED2 IP20
Note
.
..
.
18/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Mechanical installation 01.2002
3.3.4 Mounting SED2 drives with IP54 / NEMA 12 rating
Hole spacing Clearance (mm)
Frame size
H (mm) W(mm) Top BottomSide
Mounting materials
Tightening torque
B 342.8 230 150 150 100
4xM6 bolts 4xM6 washers 4xM6 spring lock washers
5Nm
C 564 312.7 150 150 100
4xM6 bolts 4xM6 washers 4xM6 spring lock washers
5Nm
D 647 310 200 200 150
4xM8 bolts 4xM8 washers 4xM8 spring lock washers
13 Nm
E 847 310 200 200 150
4xM8 bolts 4xM8 washers 4xM8 spring lock washers
13 Nm
F 1112 400 300 250 150
4xM8 bolts 4xM8 washers 4xM8 spring lock washers
20 Nm
Drilling plan for SED2 IP54
W
H
5192M02
19/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Electrical installation 01.2002
4 Electrical installation
The VSD must be grounded.
To ensure safe operation of the equipment, authorized persons must install and
commission it in full compliance with the notes and warnings set out in these operating instructions.
Take particular note of general and regional installation and safety regulations
regarding work on sites with dangerous voltages (e.g. EN 50178), and of the relevant regulations f or the correct use of tools and personal protective equipment.
The cross-section of the ground bonding conductor must be at least equal to that of
the mains connection cables.
Dangerous voltages may occur at the following terminals even when the variable speed drive is not running:
- Power supply terminals L1, L2, L3.
- Motor terminals U, V, W, DC+, DC-.
- Link terminals DC-, DC+/B+, DC/R+, B-.
After switching off the supply voltage, wait at least 5 minutes before starting any installation or service work.
4.1 General
4.1.1 Maximum length of motor cables
The performance data given in the specifications cannot be guaranteed if the motor cables exceed the following lengths: 50 m for shielded cables
100 m for unshielded cables For devices featuring EMC filters, the maximum cable length is 25 m. For cables shorter than > 25 m, the EMC guideline for filtered devices does not apply.
If you connect several motors to one VSD, the individual motor lines must be added to the total line length.
4.1.2 Operation with ungrounded systems
SED2 variable speed drives with a protection standard of IP20 operate in ungrounded systems, and remain in operation when an input phase connects to ground. In the event of an output phase with a ground fault, the SED2 switches off and displays message F0001.
SED2 drives with a protection standard of IP54/NEMA 12 cannot be operated in ungrounded systems.
4.1.2.1 Precautions for ungrounded systems (IT protective systems)
In ungrounded systems, remove the Y capacitor, or break the connections to this capacitor and integrate an output choke. The following procedure shows how to remove or disconnect the capacitor.
Operation in ungrounded systems is possible only using the SED2, IP20, without filter.
Danger
Danger
Note
.
..
.
IP20/NEMA 0
IP54/NEMA 12
Important
20/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Electrical installation 01.2002
LK 700
1
2
5192Z01
Disconnecting the Y capacitor in SED2 drives, frame size A
21/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Electrical installation 01.2002
1
2
3
5192Z02
2021 22 2324 25
29 3017 26 27 2812 13 14 15 16
10 11678912345
ON
12
PE
5192Z03en
Torx driver T20
M4
Screw
Disconnecting the Y capacitor in SED2 drives, frame sizes BandC
Disconnecting the Y capacitor in SED2 drives, frame sizes DandE
22/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Electrical installation 01.2002
4.1.3 Operation with a residual current device (RCD)
M6
T30 Torx screwdriver
5192J17en
If a residual current device (also referred to as a GLCI or RCCB) is connected, the VSD operates without unwanted interruptions under the following conditions:
þ An RCD type B must be used. þ The RCD must have a threshold current of 300 mA. þ The neutral conductor in the system must be grounded. þ Each RCD supplies only one VSD and no other consumers. þ The output cables must not exceed 50 m in length (shielded) or 100 m
(unshielded).
Disconnecting the Y capacitor in SED2 drives, framesizeF
23/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Electrical installation 01.2002
4.2 EMC-compatible installation
The SED2 VSDs operate in environments where they may be exposed to high levels of electromagnetic interference (EMI). Normally, good installation practices ensure safe and interference-free operation. However, should problems associated with EMI occur, follow the guidelines below:
Ø
Ensure good electrical contact between the mounting plate and the metal housing of the VSD via the mounting screws.
Ø
Use serrated lock washers and electrically conductive mounting plates.
Ø
If a footprint EMC filter is used, fit it under the VSD and ground it via the metal backplate. When connecting the EMC filter to the inputs of the VSD, use shielded cables and make sure that they are correctly grounded using cable clamps.
4.2.1 EMC-compatible wiring
Ø
Use shielded cables also inside control cabinets.
Ø
Ensure that all equipment in the control cabinet is properly grounded. Thus, make sure that all equipment is connected by short, thick grounding conductors to a common grounding point (flat ribbon lines are best) or bus bar.
Ø
Ensure that any control equipment (e.g. PLC or BACS1) connec ted to a VSD is connected with a short, thick cable to the same ground or grounding point as the variable speed drive itself.
Ø
Use only shielded motor and control cables. The shielding must be continuous.
Ø
Connect motor and control cables to ground at both ends.
Ø
Lay control, mains, and motor cables separately by routing them in separate cable ducts and maintaining a minimum clearance of at least 200 mm (see diagram below). If you must cross cables, run them at an angle of 90° if possible.
Ø
Motor cables should be as short as possible and should not exceed 25 m.
Ø
Connect the neutral conductor for the motors controlled by the variable speed drives directly to the ground connection (PE) of the associated VSD.
Ø
Use flat ribbon cables, as they have a lower impedance at high frequencies.
Ø
Avoid pigtails. Use only grounding clamps to bond the screen (see diagram below).
5191Z01
Ø
Check that the contactors in the control cabinet are suppressed—either with RC circuits for AC contactors, or flywheel diodes for DC contactors—and fit the suppressors to the coils. Varistor surge voltage protectors are also effective. This is important if the contactors are controlled by the variable speed drive relay.
1
SPS: Programmable controllers BACS: Building automation and control system; sometimes incorrectly referred to as BMS (building
management system)
24/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Electrical installation 01.2002
L1 L2 L3 PE
BMS
SED2
wvu
5192Z04en
Min. 16 mm²
(4 AWG)...
compensatingcable
Install all cables on the same side of the plate
Min.200 mm
(7.8 inches)....
between control cables, motor cables and mains cables
Motor cable
Mains power supply
Min.10 mm² (6 AWG)...
PE: min.10 mm² (6 AWG)...
Remove cable
insulation
Controlcables
Grounding rail
Motor
5192J10
1
L1
L2
L3
2
6 3
4
5
1 Incoming mains cable 2 Control cable 3 Motor cable 4 Footprint filter 5 Metal backplate 6 Use suitable cable clamps to
ensure good conductive contact between the shield of the motor and control cables and the metal backplate
7 Connect the motor cable
shield to
.
Cable routing for frame sizes A to C, with footprint filter
25/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Electrical installation 01.2002
Shield connected with tube clips
Motor cable
Incoming mains voltage
5192J21us
4.3 Mains and motor connections
Warning and safety instructions
Check that the VSD and motor are correctly sized for the supply voltage. Check
that the VSD corresponds to at least the motor output.
Check that the mains cables are correctly sized for the anticipated use. Check that appropriate circuit breakers or fuses exist between the mains and the
variable speed drive.
Never use high voltage insulation test equipment on any cables connected to the variable speed drive.
Always isolate the power cables before connecting them to the VSD. Check that the terminal cover was replaced properly after connecting the power
and motor cables.
Never switch on the VSD with the cover open. Always use ins ulated tools when working on the incoming power supply and the
motor terminals.
Cable routing for frame sizes D to F, IP20 with EMC filter
Caution
Warning
Danger
26/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Electrical installation 01.2002
4.3.1 Access to connection terminals: Frame size A
To access the mains and motor terminals, first remove the operator panel, cover, and I/O module as illustrated below.
5192J08
1
5192J09
1
5192J16
2
1
Removing the operator panel (BOP or AOP)
Removing the terminal cover of the I/O module
27/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Electrical installation 01.2002
1
5192J20
2
4.3.2 Access to connection terminals: Frame sizes B and C
1
5192J12
Removing the I/O module
Removing the cover of the mains and motor terminals
28/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Electrical installation 01.2002
4.3.3 Access to connection terminals: Frame sizes D to F IP20
Refer to the relevant paragraph in Access to connection terminals: Frame size A.
3
1
2
5
6
4
5
1
9
2
J
1
3
Removing the operator panel (BOP or AOP)
Opening the housing: Frame sizes D and E
29/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Electrical installation 01.2002
2
3
4
1
5
1
9
2
J
1
4
5
6
Opening the housing: FramesizeF
30/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Electrical installation 01.2002
4.3.4 Power and motor terminals: Frame sizes A to F
(Ground)
PE
(Ground)
L1
L2
L3
DC+ DC-
UVW
5192Z05
DC
R+
B-
UVWDC- DC+B+DCR+B-
L3
L2
L1
PE
5192Z06
L1 L2 L3 DC- DC+B+DC
R+
B- U V W
PE
5192Z07
Terminal layout: Frame size A
Terminal layout: Frame sizes B and C
Terminal layout: Frame sizes D and E
31/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Electrical installation 01.2002
DC+DC+DC+DC- B-
R+ B+ B+
L3 U V WL2L1
PE
5192Z08
4.3.5 Power connection for drives with a built-in EMC filter
The SED2 drives with frame sizes A, B, and C are delivered with built-in ready-wired EMC footprint filters. Route the power supply to the terminals of the pre-installed footprint filter.
L
2
L
3
L
1
Incoming mains voltage
Ground
Filter output
5192J15en
Filter
The SED2 drives with frame sizes D, E, and F are delivered with built-in ready-wired EMC filters. Wire the power supply to the connections of the built-in filter. The diagrams below show how to access the mains connections of the built-in filter.
Terminal layout: FramesizeF
Power connection to the footprint filter for frame sizes A to C
Power connection at the integrated EMC filter for frame sizes D to F
32/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Electrical installation 01.2002
2
3
4
1
5
1
9
2
J
1
4
5
6
Access to the mains connection of the EMC filter for frame sizes DtoF
33/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Electrical installation 01.2002
4x
5
1
9
2
J
1
8
6x
5
1
9
2
J
1
9
34/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Electrical installation 01.2002
PE L1 L2 L3
L1
DC+BDC+
B
UV
L2 L3 W
DC- B- DC+
R+
View without cable entry guide and without lower terminal connection plate
Mainsvoltageinputs
EMC filter
5192Z09en
4.3.6 Tightening torque for connection terminals
Frame size
ABCD EF
Tightening torque
Nm 1.1 1.5 2.25 10 (max.) 10 (max.) 50
4.3.7 Cross-sections for power and motor cables
Input voltage range 200 V – 240 VAC, 3-phase
Output
rating
kW (hp)
Min. cross-
section of
supply cable
mm2(AWG)
Max. cross-
section of supply
cable
mm2(AWG)
Min. cross-
section of motor
cable
mm2(AWG)
Max. cross-
section of motor
cable
mm2(AWG)
0.37 (0.5) 1 (17) 2.5 (13) 1 (17) 2.5 (13)
0.55 (0.75)
1 (17) 2.5 (13) 1 (17) 2.5 (13)
0.75 (1) 1 (17) 2.5 (13) 1 (17) 2.5 (13)
1.1 (1.5) 1 (17) 6 (9) 1 (17) 6 (9)
1.5 (2)
1.5 (15) 6 (9) 1 (17) 6 (9)
2.2 (3) 2.5 (13) 6 (9) 1 (17) 6 (9) 3 (4) 4 (11) 10 (7) 1.5 (15) 10 (7) 4(5)
4 (11) 10 (7) 4 (11) 10 (7)
5.5 (7.5) 4 (11) 10 (7) 4 (11) 10 (7)
7.5 (10) 10 (7) 35 (2) 10 (7) 35 (2)
Connection terminals of SED2 frame size F, IP20, with built-in EMC filter
35/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Electrical installation 01.2002
Input voltage range 200 V – 240 VAC, 3-phase
Output
rating
kW (hp)
Min. cross-
section of
supply cable
mm2(AWG)
Max. cross-
section of supply
cable
mm2(AWG)
Min. cross-
section of motor
cable
mm2(AWG)
Max. cross-
section of motor
cable
mm2(AWG)
11 (15) 16 (5) 35 (2) 16 (5) 35 (2) 15 (20) 16 (5) 35 (2) 16 (5) 35 (2)
18.5 (25)
25 (3) 35 (2) 25 (3) 35 (2) 22 (30) 35 (2) 35 (2) 35 (2) 35 (2) 30 (40) 50 (0) 150 (-5) 50 (0) 150 (-5) 37 (50)
70 (-2) 150 (-5) 70 (-2) 150 (-5) 45 (60) 70 (-2) 150 (-5) 95 (-3) 150 (-5)
Input voltage range 380 V – 480 VAC, 3-phase
Output
rating
kW (hp)
Min. cross-
section of
supply cable
mm2(AWG)
Max. cross-
section of supply
cable
mm2(AWG)
Min. cross-
section of motor
cable
mm2(AWG)
Max. cross-
section of motor
cable
mm2(AWG)
0.37 (0.5)
1 (17) 2.5 (13) 1 (17) 2.5 (13)
0.55 (0.75) 1 (17) 2.5 (13) 1 (17) 2.5 (13)
0.75 (1)
1 (17) 2.5 (13) 1 (17) 2.5 (13)
1.1 (1.5)
1 (17) 2.5 (13) 1 (17) 2.5 (13)
1.5 (2) 1 (17) 2.5 (13) 1 (17) 2.5 (13)
2.2 (3)
1(17)6(9)1(17)6(9)
3(4)
1(17)6(9)1(17)6(9)
4(5) 1(17)6(9)1(17)6(9)
5.5 (7.5)
2.5 (13) 10 (7) 2.5 (13) 10 (7)
7.5 (10)
4(11) 10(7) 4(11) 10(7)
11 (15) 6 (9) 10 (7) 6 (9) 10 (7) 15 (20)
10 (7) 35 (2) 10 (7) 35 (2)
18.5 (25)
10 (7) 35 (2) 10 (7) 35 (2)
22 (30) 16 (5) 35 (2) 16 (5) 35 (2) 30 (40)
25 (3) 35 (2) 25 (3) 35 (2)
37 (50)
25 (3) 35 (2) 35 (2) 35 (2)
45 (60) 35 (2) 150 (-5) 35 (2) 150 (-5) 55 (75)
70 (-2) 150 (-5) 70 (-2) 150 (-5)
75 (100)
70 (-2) 150 (-5) 95 (-3) 150 (-5)
90 (125)
70 (-2) 150 (-5) 95 (-3) 150 (-5)
Input voltage range 500 V – 600 VAC, 3-phase
Output
rating
kW (hp)
Min. cross-
section of
supply cable
mm2(AWG)
Max. cross-
section of supply
cable
mm2(AWG)
Min. cross-
section of motor
cable
mm2(AWG)
Max. cross-
section of motor
cable
mm2(AWG)
0.75 (1)
1 (17) 10 (7) 1 (17) 10 (7)
1.1 (1.5)
1 (17) 10 (7) 1 (17) 10 (7)
1.5 (2)
1 (17) 10 (7) 1 (17) 10 (7)
2.2 (3)
1 (17) 10 (7) 1 (17) 10 (7)
3(4)
1 (17) 10 (7) 1 (17) 10 (7)
36/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Electrical installation 01.2002
Input voltage range 500 V – 600 VAC, 3-phase
Output
rating
kW (hp)
Min. cross-
section of
supply cable
mm2(AWG)
Max. cross-
section of supply
cable
mm2(AWG)
Min. cross-
section of motor
cable
mm2(AWG)
Max. cross-
section of motor
cable
mm2(AWG)
4(5)
1 (17) 10 (7) 1 (17) 10 (7)
5.5 (7.5)
1.5 (15) 10 (7) 1.5 (17) 10 (7)
7.5 (10)
2.5 (13) 10 (7) 2.5 (13) 10 (7)
11 (15)
4 (11) 10 (7) 4 (11) 10 (7)
15 (20)
6 (9) 35 (2) 6 (9) 35 (2)
18.5 (25)
6 (9) 35 (2) 6 (9) 35 (2)
22 (30)
10 (7) 35 (2) 10 (7) 35 (2)
30 (40)
16 (5) 35 (2) 16 (5) 35 (2)
37 (50)
25 (3) 35 (2) 16 (5) 35 (2)
45 (60)
25 (3) 150 (-5) 25 (3) 150 (-5)
55 (75)
50 (0) 150 (-5) 35 (2) 150 (-5)
75 (100)
70 (-2) 150 (-5) 50 (0) 150 (-5)
90 (125)
70 (-2) 150 (-5) 50 (0) 150 (-5)
4.3.8 Block diagram showing typical installation
L3 L2 L1
PE PE
L3
L2 L1
U
V
W
U
W
V
5192Z12en
EMC filter SED2
3-Phase
Motor
4.3.9 Direction of rotation
You can change the direction of rotation of the motor by cross-connecting two of the output conductors at the VSD or the motor.
5192V01
M
M
SED2
U V W
U V W
SED2
U V W
U V W
The direction of rotation can also be reversed via parameter P1820. See system parameter list.
Tip
37/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Electrical installation 01.2002
4.3.10 Star or delta connection
The required supply voltage and method of connection are indicated on the motor rating plate. In general, larger motors (400/690 V) are connected in a delta configuration and smaller motors (230/400 V) in a star configuration.
U1V1W
1
W
2U2V2
U1V
1
W
1
W
2
U
2
V
2
Motor terminal board
5192Z30en
4.3.11 Connecting several motors
You can use the SED2 to control several motors in parallel. Make sure, however, that all motors have the same rating. When multiple motors are connected, the motors connected in parallel cannot be operated individually.
When determining the required power, remember to take account of the total current from all the motors, i.e., the sum total of all ratings. Note the recommended length of the motor connection cable. The sum of all connection cables represents the total cable length.
SED2
M1M
2
M
3
M4M
n
5192Z10
å I
M1..M
n
I
SED2,max.
å P
M1..M
n
P
SED2,max.
4.3.12 External motor overload protection
14
15
SED2 Control terminals
5192Z11en
During operation below nominal speed, the cooling effect of the fans fitted to the motor shaft is reduced. For this reason, most motors require de-rating if operated continuously at low frequencies. To ensure that motors are protected from overheating under thes e conditions, mount a PTC temperature sensor to the motor and connect it to the control terminals of the variable speed drive.
To activate the switch-off function, set parameter P0601 to 1.
Important
Note
.
..
.
38/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Electrical installation 01.2002
4.4 Control terminals
Use only shielded cables for control cables. Route control cables in separate cable trunks at least 20 cm away from motor and power cables.
The control terminals are located on the I/O module. The I/O module is identical for all models. It is located under the operator panel.
To access the control terminals, remove first the relevant terminal covers. For frame size A, see section Access to connection terminals: Frame size A on page 26. For frame sizes B and C, see section Access to connection terminals: Frame sizes B and C on page 27.
To access the control terminals, remove the operator panel, the I/O module, and the I/O module terminal cover plate. See section Access to connection terminals: Frame sizes D to F on page 28.
General information
Location of the control terminals
Access to the control terminals: Frame sizes A to C
Access to the control terminals: Frame sizes DtoF,IP20
39/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Electrical installation 01.2002
4.5 SED2 block diagram
L1 L2 L3
B-Filter
PE
PE
U
V
W
PE PE
200 - 240 V 3 AC 380 - 480 V 3 AC 500 - 600 V 3 AC
AOUT1
D/A
20 21
22
AIN1
Motor PTC
BOP (Standard)
M
RS485
29 30
V: 0 - 10 V
2-10V
I: 0 - 20 mA
4-20mA
13
12
AOUT2
D/A
V: 0 - 10 V
2-10V
I: 0 - 20 mA
4-20mA
27
26
23 24
25
2
AIN2
0V
2
28
9
5
DIN 1
6
DIN 2
7
DIN 3
8
DIN 4
16
DIN 5
17
DIN 6
14
15
AOP (Optional)
L3L2L1
DC/R+
A/D
+10VDC +0VDC
1 2
3
DC/B+
LG-Ni 1000
4
3
V: 0 - 10 V
2-10V
I: 0 - 20 mA
4-20mA
A/D
LG-Ni 1000
11
10
V: 0 - 10 V
2-10V
I: 0 - 20 mA
4-20mA
0V
CPU
opto isolated
5192B01en
Relay Output 1
Relay Output 2
Isolated 50 mA@18..32VDC (output)
Isolated 0 V (output)
40/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Electrical installation 01.2002
41/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Commissioning 01.2002
5 Commissioning
Warnings
Only authorized personnel trained in the setup, installation, commissioning, and operation of the product may work on the product and plant.
SED2 variable speed drives operate at high voltages. Operation of electrical equipment inevitably involves the use of dangerous voltages
in some components.
Emergency stop facilities in accordance with EN 60204 IEC 204 (VDE 0113) must
remain operative in all operating modes of the control equipment. Resetting the emergency stop facility must not result in an uncontrolled or undefined restart.
In cases where faults in the control equipment could cause significant equipment
damage or severe physical injury (e.g. potentially dangerous short circuits), take additional external precautions or provide facilities to ensure or enforce safe operation even in the event of a short circuit (e.g. independent limit switches, mechanical interlocks, etc.).
Certain parameter settings may cause the variable speed drive to restart
automatically after a power failure.
For reliable motor overload protection, the motor parameters must be configured accurately.
The equipment incorporates internal motor overload protection in accordance with UL508C, section 42. Refer to P0610; I
2
t is the default for ON. Motor overload protection can also be provided via an external PTC temperature sensor (disabled by default, P0601).
The equipment is suitable for use in a circuit delivering max. 10,000 symmetrical amps (rms), and is designed for a maximum voltage of 230V/460V/575V when protected by a type H or K fuse.
Do not use the variable speed drive as an “emergency stop facility". (see EN60204, 9.2.5.4)
Danger
Caution
42/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Commissioning 01.2002
5.1.1 DIP switch settings
For all versions of the SED2, the DIP switches used to configure the analog inputs are located on the I/O module. The I/O module is located under the operator panel, to which it is connected either directly (frame sizes A to C, IP20) or via a cable (frame sizes D to E, and all IP54 models).
20 21 22 23 24 25
29 3017 26 27 2812 13 14 15 16
10 11678912345
ON
12
ON
12
DIP switches for analog inputs
DIP switches for setting mains frequency
5192Z13en
I/O module
SED2f rame size A
In all versions of the SED2, the DIP switches for setting the mains frequency and selecting US or European units of measurement are located on the control board under the I/O module.
5.1.1.1 Setting the DIP switches on the I/O module
DIP switch 1 Analog input 1: OFF position: Voltage 0 to 10 V
ON position: Current 0 to 20 mA
DIP switch 2 Analog input 2: OFF position: Voltage 0 to 10 V
ON position: Current 0 to 20 mA
Factory setting for both DIP switches: OFF = Voltage 0 to 10 V.
5.1.1.2 DIP switch settings on the control board
DIP switch 2: OFF position: European default settings (50 Hz, kW etc.).
ON position: North American default settings (60 Hz, hp, etc.). Factory setting: OFF = 50 Hz.
DIP switch 1 Not for customer use. This switch must be in the OFF position for
correct functioning of the VSD.
Location of the DIP switches
43/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Commissioning 01.2002
5.2 Checklist prior to start
What
üüüü
Is the output of the VSD motor rating? Is the operating voltage range ok? Is the rated voltage of the SED2 greater than the motor rated voltage? Is the cross-section of the mains cable correct? Are the cross-section and the length of the motor cables correct, and are
they connected properly? Are all control lines connected properly? Is the motor not blocked mechanically?
Is the medium (water) available for the pump actuator? (No dry run!) Is there no pumping or blowing against still open valves or dampers? Is the danger zone free of items or personnel?
5.3 Operator panels for the SED2
The SED2 comes with the Basic Operator Panel (BOP) mounted as standard. An advanced operator panel (AOP) is available as an option.
5192P01.jpg
Basic operator panel
5192P02.jpg
Advanced operator panel
5.3.1 Description of the basic operator panel (BOP)
The basic operator panel (BOP) provides access to the parameters of the VSD and allows for application-specific settings of the SED2. The parameters and measured values are shown in a 5-digit LCD display. The basic operator panel can be mounted directly onto the variable speed drive or, alternatively, it can be mounted into a control cabinet door using a special installation kit.
You cannot store parameter information with the basic operator panel. For i nformation on setting and changing parameters, refer to section 5.4.4.2 Setting
parameters with the BOP or AOP.
44/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Commissioning 01.2002
5.3.2 Description of the advanced operator panel (AOP)
The advanced operato r panel has the following additional functions as compared to the basic operator panel:
Multilingual and multi-line plain text display.
Displays units of measurement for speed, frequency, direction of motor rotation,
current, etc.
Comments on current parameters, error messages, etc.
Diagnostics menu for troubleshooting.
Main menu can be invoked directly by pressing the Fn and P keys simultaneously.
Load and store up to 10 parameter sets.
Communicate via RS232 or RS485 interfaces.
Programmable with PC without VSD (PC-AOP kit required).
Multi-dropcapability to control up to 31 SED2 variable speed drives.
7-day timer with 3 switching operations per day.
For more details, refer to the AOP operating instructions.
5.3.3 Exchanging the operator panels
See illustration in section Removing the operator panel (BOP or AOP) on page 26.
The BOP or AOP can be connected to or disconnected from the variable speed drive without switching off the power supply.
Tips
45/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Commissioning 01.2002
5.3.4 Buttons and their functions on the operator panel
(BOP and AOP)
Operator
panel/Button
Function Effects
Status display
The LCD (five-digit display for BOP, multi-line clear-text display for AOP) shows the settings used presently by the VSD or used to parameterize the VSD).
Start motor
Pressing this button starts the variable speed drive. This button is enabled for manual mode as part of the factory setting.
Stop motor
OFF1 Pressing this button stops the variable speed drive within the selected ramp-down time.
This button is enabled for manual mode as part of the factory setting.
OFF2 Pressing this button twice (or once with sustained pressure) causes the motor to coast
freely to a standstill. This function is enabled in the manual and automatic operating modes.
Changeover to manual control
Pressing this button while the VSD is running sets the input logic so that the operator controls the SED2. In this mode, none of the controlled variables have any influence on the control of the VSD.
Changeover to
automatic
control
In automatic mode, all I/Os are set to represent the system-dependent variables. No manual inputs are accepted.
The controller responds to changes depending on its parameter setting. However, it is possible to change system parameters in automatic mode.
Functions
This button allows for displaying additional information. Refer also to the section Buttonswith special functions in the AOP operating instructions.
Multiple display mode
When you press this button for 2 seconds during operation, the following information is displayed regardless of the parameter:
1. DC link voltage (indicated by d – units V).
2. Output current (A).
3. Output frequency (Hz).
4. Output voltage (indicated by o – units V).
5. The value selected in P0005. (If P0005 is configured to display any of the above (1 to 4), the value is not redisplayed).
Briefly press the key repeatedly to cycle through the above displays. Pressing again this button for a sustained time exits the multiple display mode.
Jump function
You can jump from any parameter (rXXXX or PXXXX) directly to r0000 by pressing the Fn button briefly. This allows you to modify another parameter if required. After jumping to r0000, press the Fn button again to return to the starting point.
AOP only
Pressing buttons Fn and P simultaneously opens the main menu.
Access to
parameters
Pressing this button allows you to: 1. Access the parameters, and 2.: Exit the parameter by accepting its value.
Increase value
Press this button to increase the value displayed. This button helps increase the current value during parameterization.
In manual mode, this button allows for increasing the speed (internal motor potentiometer).
Decrease value
Press this button to decrease the value displayed. This button helps decrease the current value during parameterization.
In manual mode, this button allows for decreasing the speed (internal motor potentiometer).
46/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Commissioning 01.2002
5.4 Commissioning modes
5.4.1 Overview of commissioning with the BOP or AOP
Mechanicaland electrical installation must be complete.
* Factory setting: 50 Hz. We recommend that you commission the VSD as shown in the diagram below.
However, experienced users may commission the equipment without the filter functions of P0004.
5.4.2 Quick commissioning
To achieve a structured procedure, it is important to use parameter P0010 for commissioning, and P0003 to select the number of parameters to be accessed. Parameter P 0010 allows you to select a group of parameters that can be used for quick commissioning. These include parameters for the motor data and for the motor ramp­up and ramp-down settings (ramp settings).
At the end of the quick commissioning procedure, select P3900. When set to 1, this parameter performs the necessary motor calculations and sets all remaining parameters (those not included under P0010 = 1) to the def ault values, including P0010=0 (if P0010 is set to 1, the VSD cannot start). This process is only possible in “quick commissioning” mode.
Prerequisites:
Note
.
..
.
Setting the mains frequency *
DIPswitch2:OFF=50Hz/ON=60Hz
Quick commissioning P0010=1
See section 5.4.2
Further commissioning via
P0004 (parameter filter) and P0003 access level
Refer to the parameter list for detailed information
on the parameters.
Check prior to start
See section 5.2 checklist prior to switch-on.
Einschalten
47/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Commissioning 01.2002
Quick commissioning flow chart
1
)
Motor-specific parameters – see drawing of motor rating plate below.
2
)
Indicates parameters incorporating detailed lists of possible settings for use in special site applications. Refer to the engineering manual and operating instructions.
P0010 Start quick commissioning
0 Readyfor operation 1 Quick commissioning 30 Factory setting
Note
Always reset P0010 to "0" before operating the motor. If, after commissioning, P3900 = 1 is set, this is done automatically.
P0100 Operation for Europe/North America
0 Powerin kW; f default 50 Hz 1 Powerin hp; f default 60 Hz 2 Powerin PS; f default 60 Hz
Note
Use the DIP switch for settings 0 & 1 to allow for a permanent setting.
P0305 Rated motor current
1
)
0–2xVSDratedcurrent(A) Rated motor current (A) from rating plate
P0307 Rated motor power
1
)
0 kW – 2000 kW Rated motor power (kW) of rating plate. If P0100 = 1, the values are output in hp
P0310 Rated motor frequency
1
)
12 Hz – 650 Hz Rated motor frequency (Hz) from rating plate
P0700 Selection of command source
2
)
(on / off / reverse) 0Factorysetting 1 Basic operator panel 2 Terminal / digital inputs
P1000 Selection of frequency setpoint
2
)
0 Nofrequency setpoint 1 BOPfrequency control ↑↓ 2 Analog setpoint
P
1080Min. motor frequency
Sets the minimum motor frequency (0 – 650 Hz) at
w
hich the motor runs irrespective of the frequency setpoint. The value set here applies to both directions of rotation.
P
1082Max. motor frequency
Sets the maximum motor frequency (0 – 150Hz) at
w
hich the motor runs irrespective of the frequency setpoint. The value set here applies to both directions of rotation.
P
1120Ramp-up time
0s–650s Time taken for the motor to accelerate from standstill to maximum motor frequency.
P
1121Ramp-down time
0s–650s Time taken for the motor to decelarate from maximum motor frequency to standstill.
P
3900End quick commissioning
0 No quick commissioning (factory setting) 1 End quick commissioning with motor calculation
and resetting all other parameters to the factory setting (recommended)
2 End quick commissioning with motor calculation
and I/O reset (recommended)
3 End quick commissioning with motor calculation
but without I/O reset
P0304 Rated motor voltage
1
)
10 V – 2000 V Rated motor voltage (V) from rating plate
P0311 Rated motor speed
1
)
0 – 40.000 U/min Rated motor speed (U/min) from rating plate
P0003 Parameter access level
0 Customized Parameter List; see P0013 1 Standard: Access to most commonly used
parameters (factory setting)
2 Extended:Extended access, e.g., to VSD
I/O functions 3 Expert: For experienced users only 4 Service: For authorized service personnel only
(password protected)
48/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Commissioning 01.2002
5.4.3 Motor data for parameterization
50 Hz
230/400V
0.61 0.35 A
Cosj0.81
Cosj0.81
65%
0.12kW
2800 / min
3_Mot IEC 56 IM B3
Nr. ED510 3053 IP54 Rot KL 16
60 Hz 440V Y
0.34A
0.14 kW
3310 /min
S.F. -- 1.15
12.022 I.CI.F
P0308 P0310 P0304
P0309 P0305 P0311 P0307
5.4.4 Commissioning with the BOP or AOP
5.4.4.1 Country-specific default settings for operation with the BOP
Parameter Description Default setting for Europe (North America)
P0100
European or US op mode
0=50Hz,kW
(1 = 60Hz, hp) (2 = 60Hz, kW)
1,2
.
P0307 Nominal motor power Value in kW (hp)
Unit depends on the setting in P0100
2
.
P0310
Nominal motor frequency
50 Hz (60 Hz).
P0311 Nominal motor speed 1395 (1680) U/min (depends on model)3. P1082 Max. motor frequency 50 Hz (60 Hz).
1
Use DIP switch 2 under the BOP/AOP. This overwrites the above parameter settings.
2
This parameter can only be modified if P00010 = 1 (commissioning mode).
3
This parameter can only be modified if P00010 = 1 or 3.
49/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Commissioning 01.2002
5.4.4.2 Setting parameters with the BOP or AOP
The following describes how to change parameter P1082. Use this description as a guide to setting all other parameters with the BOP.
Step
Action
Resulting display
1
Press to access the parameters.
2
Press until P0004 is displayed.
3
Press to access the parameter value level.
4
Press or to display the required value.
5
Press to confirm and save the value.
6
Only the motor parameters are now visible for the user.
Step
Action
Resulting display
1
Press to access the parameters.
2
Press until P1082 is displayed.
3
Press to access the parameter value level.
4
Press or to display the required value.
5
Press to confirm and save the value.
6
Press to return to P0010.
Hz
P(1)
P0010
7
Press to access the parameter value level P0010.
Hz
P(1)
1
8
Press to restore the value to P0010 = 0.
Hz
P(1)
0
9
Press to save the parameter and exit the parameter value level.
Hz
P(1)
P0010
10
Press until r0000 is displayed.
11
Press to revert to the standard motor display (as defined by the customer).
Changing P0004 – parameter filter function
Changing an indexed value under P1082 – setting the maximum motor frequency
50/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Commissioning 01.2002
"Busy" signal
In some cases, the BOP displays for a maximum of 5 seconds while parameters are being changed. This means that the variable speed drive is busy
with higher-priority activities. You can change motor parameters only if P0010 = 1.
You can adjust individual digits in the display to quickly change a parameter value as follows: Make sure that you are at the level that allows for changing parameter values (see section 5.4.4.2 Setting parameters with the BOP or AOP).
1. Press
(function button) – the rightmost digit starts to flash.
2. Change the value of this digit by pressing the
/ buttons.
3. Pressing the
button again causes the next digit to start flashing.
4. Repeat steps 2 to 4 until the required value is displayed.
5. Press
to exit the parameter change level.
5.4.5 Resetting SED2 parameters to the factory settings
1. Parameter P0010 = 30 Parameter P0970 = 1
2. Now press
to restore the factory settings of the VSD.
The reset process takes approx imately 10 seconds. Refer to the default values in the system parameter list for the factory settings of the parameters.
5.4.6 Basic operation with the BOP
Ø
P0010 = 0 to ensure the correct initialization of the RUN command.
Ø
P0700[1] = 1 to enable the start/stop button on the BOP (factory setting).
Ø
P1000[1] = 1 to enable the motor potentiometer setpoints (factory setting).
1. Press the green button
to start the motor.
2. With the motor running, press
.
The motor speed increases to 50 Hz.
3. When the variable speed drive reaches 50 Hz, press
.
The moto r speed and the value displayed now decrease.
4. Use P1820 to change the direction of rotation. Note: You can also change the direction of rotation via an appropriately configured digital input.
5. To stop the motor, press the red “STOP” button
.
5.4.7 10 Hz test
The 10 Hz test helps check the installation of both motor and VSD. It helps verify the direction of rotation and the basic functions of the VSD. This ensures that a possible faulty installation of the power section is detected early on.
Testing with the BOP
1. Restore the factory settings in the SED2. Refer to section 5.4.5.
2. Press
to switch to manual operation.
3. Press
to switch the device on.
Notes
.
..
.
Changing individual digits of the parameters
Note
.
..
.
Prerequisites
51/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Commissioning 01.2002
Testing with the AOP
1. Restore the factory settings in the SED2.
2. Set parameter P700.1 from 1 to 4.
3. Press
.
4. Press
to switch to manual operation.
5. Press
to switch the device on.
5.4.8 General operation
The SED2 engineering manual contains a full description of the standard and extended parameters.
You can change motor parameters only if P0010 = 1. To start the motor, reset P0010 to 0. The variable speed drive has no mains isolating switch and is live as soon as
supply voltage is connected. It remains with the output disabled until you press or until it receives a digital ON signal.
If a BOP or AOP is used and the display of the output frequency is selected (P0005 =
21), the value on the display shows the setpoint and the actual value (0 Hz) alternating for the s topped VSD.
Important
Note
.
..
.
52/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Commissioning 01.2002
53/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Programming 01.2002
6 Programming
6.1 Introduction to the SED2 system parameters
6.1.1 General notes
You can change the parameters only via the basic operator panel (BOP), the advanced operator panel (AOP), or the serial interface.
The BOP or AOP can be used to enter and change parameters to define the required characteristics of the variable speed drive, such as motor data, ramp times, maximu m and minimum frequency, etc.
Ø
Read-only parameters are identified by the letter “r”inplaceofthe“P”.
Ø
P0010 = 1 initiates the “Quick commissioning” procedure.
Ø
The variable speed drive runs only if P0010 is set to 0 after access. This function is automatic if P3900 is greater than 0.
Ø
P0004 operates as a filter and allows access to the parameters according to their functionality.
Ø
If you attempt to change a parameter that cannot be changed under the current conditions (e.g., because it cannot be changed during operation or can only be
changed in the “quick commissioning” mode),
is displayed.
Ø
Busy signal
In some cases, the BOP displays
for a maximum of 5 seconds while parameters are being changed. This means that the variable speed drive is busy with higher-priority activities.
6.2 Access to parameters
6.2.1 Parameter access levels (P0003)
In total, there are four access levels. The three access levels available to the user are Standard, Extended, and Expert. Set the required access level with parameter P0003. For most applications, the Standard and Extended levels are sufficient.
The numb er of parameters displayed within each function group depends on the access level set in parameter P0003. The factory setting is P0003 = 1 (Standard). Refer to the engineering manual for detailed information about the parameters.
6.2.2 Parameter filter (P004)
You can further limit the selection of available parameters with parameter filter P0004. This filters the available parameters by their functionality. For example, if P0004 = 3, only the motor parameters are visible.
Some parameters are intended for commissioning only andcanbeviewedasa function of this filter. However, in order to set these parameters, set P0010 to 1 (quick commissioning).
Important
Note
.
..
.
54/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Programming 01.2002
6.2.3 Diagram for a parameter overview
L1 L2 L3
PE
PE
U V
W
PE PE
200 - 240 V 3 AC 380 - 480 V 3 AC 500 - 600 V 3 AC
AOUT1
D/A
20
21
22
Motor PTC
BOP (Standard)
M
CPU
RS485
29 30
V: 0 -10 V
2-10V
I: 0 - 20 mA
4-20mA
13
12
AOUT2
D/A
V: 0 -10 V
2-10V
I: 0 - 20 mA
4-20mA
27
26
23
24
25
LG Ni1000
28
9
5
DIN1
6
DIN2
7
DIN3
8
DIN4
16
DIN5
17
DIN6
14
15
AOP (Optional)
L3L2L1
DC/R+
+10VDC +0VDC
3
2
1
DC/B+
LG Ni1000
AIN1
2
AIN2
0V
2
A/D
4
3
V: 0 - 10 V
2-10V
I: 0 - 20 mA
4-20mA
A/D
11
10
V: 0 -10 V
2-10V
I: 0- 20 mA
4-20mA
0V
Analog Inputs 1+2
P0756 - P0762
Digital Input
P0700 Command source P0701- P0706 (P0705 counter)
P0722- P0725 (NPN - PNP)
Analog inputs 1+2 configured as digital input P0707- P0708
PTC
P0601
PID
P2200 P2201- P2231 P2240- r2260 P2253- P2305 P2264- r2272
EnablePID Fixed setpoint PID setpoint Standard setpoint PID feedback
Analog Output
r0770 - P0781
Drive Features
P1270 Enable essential mode P1210 - P1212 automatic restart
Communication
P2000 - r2091
DriveParameters
P0003 P0010 r0026 r0039 - P0040 P0100 r0206 - r0209 P1000- P1028 P1080-P1110
User acces level Commissioning parameter filter VSD DC link voltage Energy consumption meter US / Europe Performance data Frequency setpoint Frequency adjustment
Motor Parameters
r0021 - r0035 P0304 - P0313 P0340 P0601 - P0640 P1910 P2000
Motor performance data Standarddata Calculation of motor parameters Motor protection Motor data identification Reference frequency
DOUT
P0731 - P0732 R0747 - r0748
MMI (BOP)
r0000 P0005 r0019- r0039
AOP
Optional
5192B02en
Relay Output 1
Relay Output 2
Isolated 50 mA@18..32 VDC (output)
Isolated 0 V (output)
See AOP operating instructions
B filter
opto isolated
55/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Programming 01.2002
6.3 Basic functions of the SED2
6.3.1 Digital inputs
External switch-on and switch-off arrangements are required for stand-alone operation of variable speed drives. The digital input port provides six channels, which can be extended to eight by use of the two analog inputs. You can program the function of the digital inputs as required.
5
6
7
9
16
17
28
PNP
NPN
DIN1
DIN2
DIN3
DIN4
DIN5
DIN6
8
or
Isolated +24V (Output)
Isolated 0V (Output)
DC- isolated
5192Z17en
P0701 to P0706 Digital inputs 1 to 6
The available settings for each of the input channels are listed below:
0 Digital input disabled. 1 ON / OFF1 – OFF as per the ramp-down time defined in P1121. 2 ON + change direction of rotation / OFF1. 3 OFF2 – coast to standstill. 4 OFF3 – faster ramp-down (quick stop = ramp-down at power limit). 9 Error acknowledgement. 10 JOG right. 11 JOG left. 12 Reverse direction of rotation. 13 Motor potentiometer (MOP) higher (increased frequency). 14 Motor potentiometer (MOP) lower (reduced frequency). 15 Fixed setpoint (binary coded). 16 Fixed setpoint (binary coded + ON). 17 Fixed setpoint (binary-coded decimal + ON). 25 Enable DC braking. 26 Enable Essential Service. 27 Enable PID controller. 28 Bypass command input (in bypass mode). 29 External fault. 33 Disable additional frequency setpoint. 99 Enable BICO parameter-setting.
Index: Example for P0701, applies also to parameters P0702 to P0708.
P0701[0]: 1. command data set (CDS). P0701[1]: 2. command data set (CDS).
P0701[2]: 3. command data set (CDS).
Setting parameters for DIN1 to 6 (or DIN1…8)
(commissioning)
P0701
P0703
P0704
P0705
P0706
DIN1
DIN3
DIN5
DIN6
DIN4
DIN2
5192Z18en
P0725
0: = active low 1: = active high
Function
r0722
Function
Function
Function
Function
Function
Status digital inputs
56/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Programming 01.2002
Setting 99 (BICO) is intended for experienced users only. For more detailed information, refer to the SED2 engineering manual. Factory settings:
P0701
1
ON / OFF1.
P0702 12
Reverse (change dir. of rotation). P0703 9 Error acknowledgement. P0704 15
Fixed setpoint (binary coded). P0705 15
Fixed setpoint (binary coded). P0706 3 OFF2 – coast to standstill.
P0707 to P0708 Analog inputs 1 and 2 can be reconfigured with parameters P0707 and P0708 as digital inputs if required.
The following limit values apply to analog inputs configured as digital inputs:
1.6 VDC = Off.
4.0 VDC = On.
Factory setting: 0
1
2
3
4
DIN7
1
2
11
12
DIN8
5192Z15
Connection of the two analog inputs for use as additional digital inputs DIN7 and DIN8.
P0725 Operating mode for the digital inputs NPN or PNP
This parameter determines whether the digital inputs DIN1 to 6 are to be enabled by “logic 0” or “logic 1”. Possible settings:
0 NPN mode
Þ
active low.
1 PNP mode
Þ
active high (factory setting).
r0722 Check of the digital and analog inputs
This parameter can be used to check the functions of the digital and analog inputs. You can check the presence of a signal at the channel. When an active signal is present, the associated segment of the display lights up. The allocation of each of the inputs to a s pecific segment is illustrated below.
AIN2
AIN1
DIN6 DIN5
DIN4 DIN3
DIN2 DIN1
5192Z14
Note
.
..
.
57/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Programming 01.2002
Example of the display while testing the input signals:
5192Z29
DIN1= 0 DIN2= 1 DIN3= 1 DIN4= 0 DIN5= 1 DIN6= 1
AIN1 = 0 AIN2 = 1
6.3.2 Analog inputs
The analog inputs are used to send positioning, control, and feedback signals to the VSD and convert them to digital signals via A/D converters.
1
2
3
10
11
AIN1+
4
Minimum
4.7k
ΩΩΩΩ
AIN1-
AIN2+
AIN2-
5192Z19
+10 V
0V
A/D
A/D
The analog inputs AIN1 and AIN2 are specified as follows: Input level: 0 to 10 V or
0to20mA Resolution: 10 bit Read cycle: 10 ms
Set the analog inputs to 0 to 10 V or 0 to 20 mA via the 2 DIP switches on the I/O module.
Position DIP switch 1 DIP switch 2
ON
mA mA
OFF V V Factory setting for both DIP switches: OFF. Refer to s ection 5.1.1.1, Setting the DIP switches on the I/O module.
Setting the DIP switches on the I/O module
58/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Programming 01.2002
Input
type
SCAL
Input
ADC
deadband
Delay
Loss of signal
ADC
Smoothing time
P0753
1+2
Status
r0751
Input value
r0752
1+2
Smoothed
value
r0754
1+2
Value
+min/max
r0755
P0761
1+2
P0762
1+2
P0761
P0757
P0758
P0759
P0760
5192Z20en
P0756
Defines the type of analog input and enables analog input monitoring.
Possible settings:
0 Unipolar voltage input (0 to 10 V) (factory setting). 1 Unipolar voltage input with monitoring (0 to 10 V). 2 Unipolar current input (0 to 20 mA). 3 Unipolar current input with monitoring (0 to 20 mA). 5 LG-Ni 1000 sensor input (–10 to +10 V).
Important: The parameter setting must match the setting of the 2 DIP switches on
the I/O module.
Index:
P0756[0] : Analog input 1 (ADC 1).
P0756[1] : Analog input 2 (ADC 2).
Note on dependency:
This function is disabled if the analog scaling block is programmed to negative output setpoints (see P0757 to P0760).
Note on the monitoring function
If monitoring is enabled and the dead zone is defined (P0761), an error message appears (F0080) as soon as the analog input voltage drops below 50% of the dead zone voltage.
P0753 Defines the filter time in ms for the analog input.
Setting range: 0 to 10,000 ms Factory setting: 100 ms
Index:
P0753[0] : Analog input 1 (ADC 1). P0753[1] : Analog input 2 (ADC 2).
Note:
Increasing this time reduces (smoothes) the ripples but also slows down the response to the analog input.
P0757 – P0760 Parameters P0757 to P0760 are used to configure the input scaling for the analog inputs according to the following curve:
Parameter setting for AIN1 and AIN2
(commissioning)
Signal in %
Time in ms
59/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Programming 01.2002
ymax
y2
(P0760)
y1
(P0758)
x1
(P0757)
x2
(P0759)
%
V mA
ymin
10 20
-10
-20
Setting range
Parameter Unit
Point on x/y-axis
Min. Max.
Factory setting
P0757 V or mA x 1 value -20.0 20 0 P0758 % y1 value -99999.9 99999.9 0.0 P0759 V or mA x2 value -20 20 10 P0760 % y2 value -99999.9 -99999.9 100
The factory setting of the input scaling corresponds to 0 V = 0% and 10 V = 100%.
P0761
Defines the ADC dead zone for the analog inputs. Setting range: 0 to 20 V or mA Factory setting: 0
ymax
y2
y1
x1
x2
%
V mA
ymin
{
P761
10 20
-10
-20
{
Note: P0761[x] = 0: No enabled dead zone. The dead zone runs from 0 V(mA) to the value of P0761, if the values of P0758 and
P0760 (y-coordinate for ADC scaling) have the same sign. The dead zone is enabled from the intersec ting point (x-axis with ADC scaling curve) in both directions, if P0758 and P0760 have different signs. When using a configuration with neutral point in the center, Fmin (P1080) should be zero. There is no hysteresis at the end of the dead zone.
P0762 Defines the delay time in ms between the drop-off of the analog setpoint and the display of error message F0080.
Setting range: 0 to 10,000 ms Factory setting: 1000 ms
60/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Programming 01.2002
6.3.3 Analog outputs
The analog outputs primarily help display status variables such as output frequency, motor voltage, or present motor current within the scaleable range.
AOUT1
D/A
V: 0 -10 V
2-10V
I: 0 - 20mA
4-20mA
13
12
AOUT2
D/A
V: 0 -10 V
2-10V
I: 0- 20mA
4-20mA
27
26
AnalogOutput
r0770 - P0781
5192B03en
P0773
1+2
r0774
1+2
P0781
1+2
P0771
1+2
P0780
P0779
P0778
P0777
P0776
Function
SCAL
Output
Deadband
5192Z27en
Output:
Current or
voltage
r0770 Shows the number of available analog outputs.
P0771
Defines the physical status variable to be displayed as an analog signal. Possible settings:
21 Present output frequency (scaled to P2000), (factory setting). 24 Present VSD output frequency (scaled to P2000). 25 Present output voltage (scaled to P2001). 26 Present link voltage (scaled to P2001). 27 Present output current (scaled to P2002).
Index:
P0771[0]: Analog output 1 (DAC 1).
P0771[1]: Analog output 2 (DAC 2).
P0773
This parameter enables smoothing for the DAC input with a PT1 filter and determines the smoothing time in ms for the analog output signals. Setting range: 0 to 1000 ms Recommended setting: 100ms (factory setting)
Index:
P0773[0]: Analog output 1 (DAC 1). P0773[1]: Analog output 2 (DAC 2).
Note: The filter is disabled for P0773 = 0.
Parameter setting for AOUT1 and AOUT2
(commissioning)
Signal in %
Time in ms
61/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Programming 01.2002
r0774 Shows the analog output value (in V or mA) after filtering and scaling.
Index:
P0774[0]: Analog output 1 (DAC 1).
P0774[1]: Analog output 2 (DAC 2).
P0776
Defines the type of analog output. Possible settings:
0 Current output 0 to 20 mA (factory setting) 1 Voltage output 0 to 10 V
Note: The analog outputs are designed as current outputs within 0 to 20 mA. Both
analog outputs must be configured as the same type. Both channels are configured, e.g., as either current outputs with range 0 to 20 mA, or as voltage outputs with range 0 to 10 V.
P0777 to P0780: Define the output characteristic in %. The DAC scaling parameters (P0777 to P0781)
are used to set the output characteristics. They are configured according to the following curve.
Ausgangssignal (mA)
0
20
20 mA
P0780 y2
P0778 y1
P0777
x1
P0779
x2
100%(-100%)
Points P1 (x 1, y1) and P2 (x2, y2) are freely selectable.
Example:
The factory-set scaling is as follows: P1: 0.0%=0mAor0Vand P2: 100.0 % = 20 mA or 10 V.
Index:
P0777[0]: Analog output 1 (DAC 1). P0777[1]: Analog output 2 (DAC 2).
P0777: Defines x1 of the output characteristics (factory setting = 0.0). P0778: Defines y1 of the output characteristics (factory setting = 0). P0779: Defines x2 of the output characteristics (factory setting = 100). P0780: Defines y1 of the output characteristics (factory setting = 10).
62/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Programming 01.2002
P0781
Defines the DAC dead zone for the analog inputs. Setting range: 0 to 20 mA or 0 to10 V Factory setting: 0
ymax
y2
y1
x1
x2
%
V mA
ymin
{
P761
10 20
-10
-20
{
Index:
P0781[0]: Analog output 1 (DAC 1). P0781[1]: Analog output 2 (DAC 2).
6.3.4 Frequency setpoint (P1000)
Ø
Default setting: Terminal 3/2 (AIN+/ AIN–, 0 to 10 V corresponds to 0 to 50/60 Hz).
Ø
Additional settings: See P1000.
6.3.5 Selecting the c ommand source (P0700)
Possible settings for P0700: 0 Factory setting (BICO reset), resets all digital inputs to the factory settings
(possible only if P0701=99). 1 Operator panel BOP or AOP. 2 Control terminal bar (factory setting). 4 USS on BOP link. 5 USS on COM link. 6 CB on COM link.
Ø
Default setting: Terminal 5 (DIN 1, high).
Ø
Additional settings : See P0700 to P0708.
The ramp-up and ramp-down smoothing times influence the motor's start and stop behavior. Refer to the engineering manual, parameter list, parameters P 1120, P1121 for more information on these functions.
There are several ways to stop the motor: Default setting:
OFF1 Terminal 5 (DIN 1, low). OFF2 OFF button on BOP/AOP; sustained pressing of the OFF button
(2 seconds) or repeated pressing of the button (in case of default settings not possible without BOP/AOP).
Ø
Additional settings : See P0700 to P0708.
Ø
Default setting: Terminal 6 (DIN 2, high).
Ø
Additional settings : See P0700 to P0708.
Start motor
Notes
.
..
.
Stop motor
Reversal of the motor's direction of rotation
63/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Programming 01.2002
6.3.6 OFF functions
This command (by eliminating the ON command) stops the variable speed drive within the selected ramp-down time.
Parameters to change the ramp-down time: See P1121.
Ø
The ON and the consecutive OFF1 command must have the same source.
Ø
If the ON/OFF1 command is set for more than one digital input, only the last set
digital input is valid, e.g., DIN3 is enabled.
This command causes a free coasting of the motor to standstill (impulses for the power section of the VSD are disabled).
The OFF2 command may have one or several sources. By default, the OFF2 command is set to BOP/AOP. This source remains even if other sources are defined by one of the parameters P0700 to P0708.
6.3.7 Control types
The different control types of the SED2 control the relationship between the motor speed and the voltage supplied by the VSD. Below is a summary of the available control types.
Can be used for variable or constant torque applications such as delivery systems and positive displacer pumps.
This factory-set control mode can be used to improve performance and dynamic behavior of the motor.
This factory-set control mode can be used for variable torque load s uch as fans and pumps.
Refer to the engineering manual for information on this control mode.
This function automatically increases or decreases the motor voltage to locate the lowest possible energy consumption. This control mode is enabled as soon as the default setpoint speed is reached.
There is no slip compensation or resonance smoothing. The Imax controller relates to voltage instead of frequency.
A combination of P1300 = 1 and P1300 = 5.
6.3.8 Communication
A serial interface RS485 is integrated. A RS232 interface is integrated in the optional door mounting set for BOP/AOP. See section 9.1 Options.
USS, P1, and N2 protocols are implemented as part of the series. For detailed information, refer to the engineering manual.
OFF1
Notes
.
..
.
OFF2
Note
.
..
.
Linear V/f control P1300 = 0
Linear V/f control with flow control (FCC) P1300 = 1
Parabolic V/f control P1300 = 2
Multi-point V/F control P1300 = 3
Linear V/f control with energy saving mode P1300 = 4
V/f control for textile applications P1300 = 5
V/f control with FCC for textile applications P1300 = 6
64/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Programming 01.2002
6.4 HVAC functions of the SED2
The functions listed below were implemented specifically in the SED2 for HVAC applications.
6.4.1 PID controller
In order to achieve independent control within a stand-alone application by means of the SED2 VSD, Siemens SBT implemented a proven PID controller. This controller allows for temperature (LG-Ni 1000), pressure, and speed control. The factory settings for the implemented PID parameters are designed for pressure control. For temperature or speed control, the controller's time constants must be adjusted to the new control loop. See "Parameterizing the PID controller" below.
P2253
P2261 r2262
:setpointsource
: setpointfilter timeconstant : filtered setpoint
P2264
P2267 P2268 P2270
P2271
r2272 P2274
: feedback source
: feedback threshold max : feedback threshold min : function sequence
: transducer type
: scaled feedback : derivative time
: transient error signal :Pgain :Igain
: ramp-up/-down time of PID limit : PID output upperlimit : PID output lower limit : actuator opening time : actuator closing time
53.A = PID outputat lower limit
53.B = PID outputat upper limit
r2294: PID output
PID
CONTROLLER
r2273 P2280 P2285
P2293 P2291 P2292 P2304
P2305 P0731/P0732 : P0731/P0732 :
5192Z21en
Note:
The setpoint and the actual value signal are to be displayed as a percentage (%) or absolute value. Make sure, however, that the two signals match each other.
P2201
Enter fixed setpoint (or absolute value in %). The setpoint is active if switching command "ON" is sent to DIN1.
Analog input
Seethesectiononanaloginputsforthe parameter settings.
P2253
Set to value 2224 (fixed PI setpoint).
P0701[0]
Enter value 16 (sets DIN1 to ON with fixed setpoint; see section 6.3.1
Digital inputs).
P2253[0]
Set to 755 (setpoint is configured to AIN 1).
P0756[0]
Select the type of analog input 1 for the setpoint. See section Analog inputs.
P0757[0] to P0760[0]
Set scaling of AIN 1.
P0756[1]
Define the type of analog input 2 for the actual value signal (see section 6.3.2 Analog inputs).
Parameterizing the PID controller
(commissioning)
Fixed setpoint
External setpoint
65/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Programming 01.2002
P0757[1] to P0760[1]
Set the scaling of the actual value for analog input 2 (see section 6.3.2 Analog inputs).
P2264
Set to 755[1] (defines AIN2as actual value).
P2271
Define the reaction of the PID controller to the actual values (0=heating, 1=cooling).
P2200
Enable the PID controller (0=disable, 1=enable).
r2262
Check for setpoint (scaled PID setpoint in %). Note: VSD must be set to automatic control. DIN1 must be set to ON.
r2272
Check for actual value (scaled PID actual value in %).
Set and optimize
P2280 PID proportional gain and P2285 PID integration time.
Changeover to
automatic control.
6.4.2 Belt failure detection without sensor (P2181)
SED2
5192Z22en
Fan
Motor
This function allows for monitoring power transmission components such as drive belts. The function can also detect motor overload, e.g. in the case of jam. The actual frequency / torque curve is compared to a preprogrammed tolerance band (see P2182 to P2190) as part of this function. If the actual curve is outside the tolerance band, a warning or error message is generated.
Continued: Parameterizing the PID controller
66/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Programming 01.2002
Torque [Nm]
Frequency [Hz]
Threshold frequency 1 Threshold frequency 3
Threshold frequency 2
P2182 P2184
P2183
P2189 Upper torque threshold 3
P2190 unterer Lower torque threshold 3
P2187 Upper torque threshold 2
P2188 Lower torque threshold 2
P2185 Upper torque threshold 1
P2186 Lower torque threshold 1
5192D01en
The permissible frequency/torque area is defined by the zone shaded gray. The frequency limit values 1 to 3 define the areas used to compare the actual torque to the preset torque. Nine parameters define torque monitoring. Parameters (P2182 to P2184) define the frequency limit values to be set. Parameters (P2185 to P2190) limit the tolerance band compared to the present torque curve.
1. Frequency limit value parameter P2182 to P2184.
Setting the three frequency limit values: The 3 f requency limit values F1;F2;F3 determine a reasonable division across the required torque area. Set the values desired in the manual mode by pressing buttons
and read and write down the corresponding torque values via
parameter r0031. Factory setting: 5;30;50 Hz.
2. Set the desired reaction of drive belt failure detection via parameter P2181.
Possible settings for P2181:
0 Belt failure detection disabled (factory setting).
1 Warn low torque/speed.
2 Warn high torque/speed. 3 Warn high/low torque/speed. 4 Trip low torque/speed. 5 Trip high torque/speed. 6 Trip high/low torque/speed.
P2181 must be set before P2185 to P2190 (not to 0).
3. Set the torque limit value parameters P2185 to P2190 as follows: Add
±15% to the torque derived from the setting of the frequency limit values to
define a permissible tolerance band for the torque values. For allocation of variables, refer to the frequency/torque curve
.
Factory setting: 99999.0.
Frequency / torque curve
Parameterizing belt failure detection without sensor
(commissioning)
Note
67/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Programming 01.2002
4. Set the alarm delay parameter P2192:
P2192 allows for setting a delay (between 0 to 65 sec) before a warning or error message is generated. The parameter helps avoid false alarms caused by temporary transition states. This delay can also be used for belt failure detection via sensor.
Factory setting: 10 s.
5. In manual mode, vary the torque frequency in the selected range to check the function.
6. Changeover to automatic control.
6.4.3 Belt failure detection with sensor (P0400)
SED2
Fan
5192Z23en
Sensor
Motor
A simple sensor (inductive sensor) mounted to the drive unit (e.g. for a fan) supplies one pulse for each rotation. The pulse train generated this way—which can vary from 1 to 20,000 pulses per minute—is sent to the digital input DIN5 of the VSD. The frequency resulting from the pulse train is compared to the present output frequency of the VSD. Parameter P 0400 defines the encoder type. If parameter P0400 = 0 (factory setting), this type of belt failure detection is disabled and the variant "belt failure detection without sensor (P2182)“ is used instead.
Only digital input DIN5 works with a counter signal!
1. Determine the speed transformation ratio between the motor and the s haft driven by the belt.
2. Define the encoder type using parameter P0400. Possible settings for P0400: 0 Disabled (factory setting).
1 Single channel encoder. 2 Quadrature encoder without zero pulse. 3 External pulse train. 12 Quadrature encoder with zero pulse.
3. Use parameter P0409 to set the pulse rate (number of pulses/sec) generated by the sensor at nominal frequency (nominal speed) by including the transmission ratio determined in point 1.
Setting range: 1 to 500 Factory setting: 25
Note
.
..
.
Parameterizing belt failure detection with sensor
(commissioning)
68/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Programming 01.2002
4. Set the desired reaction of drive belt failure detection via parameter P2181.
Possible settings for P2181:
0 Belt failure detection disabled (factory setting).
1 Warn low torque/speed.
2 Warn high torque/speed. 3 Warn high/low torque/speed. 4 Trip low torque/speed. 5 Trip high torque/speed.
6 Trip high/low torque/speed.
Suggested setting: 1 Warn low torque/speed.
5. Use parameter P2191 to set the maximum permissible deviation of the pulse train frequency (actual value) generated by the sensor from the VSD output frequency (setpoint). If the tolerance band for frequency is exceeded, a warning or trip is generated.
Setting range: 0 to 20 Hz. Factory setting: 3 Hz.
6. In manual mode, vary the torque frequency in the selected range to check the function.
7. Changeover to automatic control.
6.4.4 Staging pumps or fans
The motor control staging allows to control up to two additional pumps or fans based on the integrated PID control system. The complete system comprises a pump (fan) controlled by the VSD, and up to two additional pumps (fans) switched by contactors or motor starters. The contactors or motor starters are controlled by relay switching contacts integrated in the VSD. The diagram below shows a typical pump system. A similar system comprising fans could be used f or ventilating systems.
MV M1 M2
Pressure sensor
to PID input of variable speed drive
Motor starterVariable
speed drive
Mains voltage
5192Z24en
MV: Motor, speed-controlled by SED2. M1: Motor,controlled by relay 1 DOUT1. M2: Motor,controlled by relay 2 DOUT2.
69/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Programming 01.2002
If MV runs at maximum frequency and the PID feedback shows that a higher speed is demanded in accordance with the staging, the VSD switches on one of the relay­controlled motors M1 or M2 (staging). To keep the controlled variable as constant as possible, and to compensate for the difference in output, the VSD must be decreased to minimum frequency. See the illustration below. During the staging process, PID control is suppressed.
If MV runs in parallel to M1 and M2 at a minimum frequency, and if the PID feedback demands an even lower speed, the VSD switches off one of the relay-controlled motors M1 or M2 (destaging). In this case, the VSD must increase the ramp from the minimum to the maximum frequency. In this phase, PID control is suppressed.
Motor 1
Motor 1
Motor 1
Motor 2
Motor 3
Motor 2
kW
Demand or volume flow
5192D02en
100%
Total power
Motor MV, controlled by SED2
Motor M1, switchedby relay 1
Motor M1, switchedby relay 2
100%
100%
Power
Power
Power
Switching sequence MV-M1 Switching sequence MV-M1-M2
t
t
t
t
5192D05en
Motor staging on output demand
Diagram from motor staging
70/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Programming 01.2002
As a rule, the factory settings can be used.
P2371
Defines the configuration of additional pumps or fans. Max. 2 pumps can be added. Factory setting: 0 Maximum setting: 2
P2372 Enable motor cycling
If this parameter is enabled, one or two motors are switched on or off—during staging, in addition to the speed-controlled motor—in a specified sequence based on the motor operating hours (parameter 2380). During staging, the motor having the lowest number of operating hours is first switched on. During destaging, the motor having the highest number of operating hours is first switched off.
In the case of different output of the motors to be switched on, the motor promising to best satisfy the demanded output is switched on first, regardless of its operating hours.
Factory setting: 0 (disabled).
P2373
Defines the staging hysteresis: Value in % of the PID setpoint. Setting range: 0 to 200 %
Factory setting: 20 %
P2374 Delay on staging
Setting range: 0 to 650 s Factory setting: 30 s
P2375 Delay on destaging
Setting range: 0 to 650 s Factory setting: 30 s
P2376 Overriding the delay on staging/destaging
The value of P2376 is set as a percentage of the PID setpoint. If the PID fault (P2273) exceeds this value, a motor is switched on or off, regardless of the delay time set in P2374 and P2375.
Setting range: 0 to 200 % Factory setting: 25 %
P2377
This parameter is used to lock the delay override (P2376) after staging or destaging for a specified period of time. This prevents a sec ond staging immediately following the first staging, that, for example, could have been triggered by the first staging.
Setting range: 0 to 650 s Factory setting: 30 s
Parameterizing motor staging
(commissioning)
71/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Programming 01.2002
P2378 Staging frequency
This parameter is defined as a particular percentage of the maximum output frequency. This determines the frequency used to switch on or off the relay (DOUT1 or DOUT2) during staging or destaging. See the diagram below.
t
t
f
f
5192D04en
PID Off
Relay On
PID On
PID Off Relay Off PID On
VSD freq.
VSD freq.
Staging freq.
Max. freq.
Min. freq.
Staging freq.
Max. freq.
Min. freq.
Factory setting: = 50 % (defined as a percentage = 100%, at fmax = 50 Hz).
P0731 (DOUT1) Function of the digital output 1 (relay 1)
Set parameter to 2379[0] (relay 1 to motor 1). Factory setting: 52.3 = VSD fault enabled.
P0732 (DOUT2) Function of the digital output 2 (relay 2)
Set parameter to 2379[1] (relay 2 to motor 2). Factory setting: 52.2 = VSD in operation.
Complete parameter setting by changing over to automatic control.
72/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Programming 01.2002
6.4.5 Temperature control with LG-Ni 1000 sensor
T
SED2
5
1
9
2
Z
2
6
Ni1000
Use the SED2 to directly measure the temperature by means of a passive temperature sensor of type LG-Ni 1000. Simple temperature control is possible accordingly. The sensor is connected to the VSD. The signal can be scaled according to requirements.
Same procedure as for commissioning analog inputs. The temperature sensor can be connected as follows to the analog inputs:
LG-Ni 1000 on AIN 1 Connection terminals: 2/4
LG-Ni 1000 on AIN 2 Connection terminals: 2/11
Note: When connecting a LG-Ni 1000 sensor, no other input signal can be processed
on the same channel, even if terminals 3 / 10 for an analog signal of 0 to 10 V are free.
P0757 to P0760, scaling
During scaling, the LG-Ni 1000 sensor's temperature range of –50 to 150 °C can be converted to %.
ymax
y2
(P0760)
y1
(P0758)
x1
(P0757)
x2
(P0759)
%
V mA
ymin
10 20
-10
-20
Example: LG-Ni 1000 on AIN1:
P0757[0] = –50 °C P0758[0] = –50% P0759[0] = 150 °C P0760[0] = 150%
Factory settings: P0757 = 0
P0758 = 0.0 P0759 = 10 P0760 = 100
Parameterization temperature control
(Commissioning notes)
73/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Programming 01.2002
6.4.6 Bypassing the VSD
There are applications demanding maximum motor output. Additionally, there are applications requiring a VSD bypass system for safety reasons. For these cases, the SED2 has an integrated bypass function.
SED2
Mains supply
Motor starters
Mechanical
interlock
5192Z25en
P1260
Defines the possible triggers for changing over to bypass operating mode. The following settings are possible:
0 Bypass disabled (factory setting). 1 Controlledby VSD trip. 2 Controlled by DIN, see P1266. 3 Controlled by DIN and VSD trip. 4 Controlled by VSD frequency. 5 Controlled by VSD frequency and VSD trip. 6 Controlled by VSD frequency and DIN. 7 Controlled by VSD frequency and DIN and VSD trip.
r1261
Read parameter for the bypass function showing how the motor is driven: The following states are possible:
Bit 00 Motor supplied by drive 0 Yes
1No
Bit 01 Motor supplied by mains 0 Yes
1No
P1262
Defines the time delay between changing over the VSD to bypass and vice-versa to demagnetize the motor. See bypass diagram below.
Setting range: 0 to 20 s Recommended setting: 1 s (factory se tting).
Parameterizing the bypass function
(commissioning)
74/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Programming 01.2002
P1263
Defines the time delay between the bypass alarm OFF and the bypass switching contactor OFF. See bypass diagram below.
Setting range: 0 to 300 s Recommended setting: 1 s (factory setting).
P1264
Defines the time delay between the bypass alarm ON and the VSD switching contactor OFF. See bypass diagram below.
Setting range: 0 to 300 s Recommended setting: 1 s (factory setting).
P1264 P1262 P1262P1263
t(s)
(Bypass request)
Bypass contactor
VSD contactor
Alarm
5192D03en
Complete parameter setting by changing over to automatic control.
Bypass time diagram
75/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Programming 01.2002
6.4.7 Hibernation mode
If the VSD reaches the hibernation setpoint in PID operating mode, the hibernation timer P2391 starts. After the timer has expired, the VSD drives the output frequency of the ramp to 0 Hz. See illustration below.
f
0%
T1 T2 T3 T4 T5
Output [Hz ]
P2392 Restart freq.
P2390 Hibernation freq.
Min. freq.
P2391
Hibernation timer
Hibernation
mode
Restart
Drive frequency
PID frequency
max. hibernation (-) error [%]
Time [s]
Time [s]
5192D06en
PID error[% ]
T1
Hibernation frequency reached. – Start of hibernation timer.
T2
Minimum output frequency reached.
T3
Output frequency decreased in accordance with the set ramp. –
PID control of the output frequency is interrupted.
T4
Output frequency = zero (motor standstill).
T3 to T5
The PID fault signal [%] is monitored. Note: – The polarity of the PID fault signal. – The polarity of the PID fault signal must match the sequence of the
controlled functions (cooling/heating or vice-versa). – The temperature setpoint can be below 0 °C. – The PID fault signal can be positive or negative.
T5
The VSD output frequency is again increased. – The PID control of the output frequency is again enabled.
76/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Programming 01.2002
P2390 Hibernation frequency setpoint [%]
Setting range:
± 200 %
Recommended setting: Value 15 to 20% greater than the minimum frequency. Note: The hibernation f unction is disabled if the hibernation setpoint is set to 0
(corresponds to the factory setting).
P2391 Hibernation timer [s]
Set the desired time T1 to T3 (before hibernation mode kicks in) (see diagram above). Setting range: 0 to 254 s
P2392 Restart PID controller deviation [%]
This parameter defines the PID controller deviation at which the motor is to restart. Setting range:
± 200 %
Note the signs according to the application (heating or cooling sequence). Complete parameter setting by changing over to automatic control.
Parameterizing the hibernation function
(commissioning)
Note
.
..
.
77/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Programming 01.2002
6.5 System parameter list for levels 1 to 3
r0000 Drive display
Displays the user selected output as defined in P0005.
Unit: - Min: - Def: - Max: -
Level 1
Note:
Pressing the "Fn" button for 2 seconds allows the user to view the values of DC link voltage, output current, output frequency, and chosen r0000 setting (defined in P0005).
r0002 Drive state
Displays actual drive state.
Unit: - Min: - Def: - Max: -
Level 3
Settings:
0=Commissioning mode (P0010=0) 1=Drive ready 2=Drive fault active
3=Drive starting (DC link precharging) 4=Drive running 5=Stopping (ramping down)
Dependency:
State 3 visible only while precharging DC link, and when externally powered communications board is fitted.
P0003 User access level
Defines user access level to parameter sets. The default setting (standard) is sufficient for most simple applications.
Unit: -- Min: 0 Def: 1 Max: 4
Level 1
Settings:
0=User defined parameter list - see P0013 for details 1=Standard: Access into frequently used parameters. 2=Extended: Access to e.g. variable speed drive I/O
functions.
3=Expert: For experienced users only 4=Service: Only for use by authorized service personal -
P0004 Parameter filter
Filters available parameters according to functionality to enable a more focussed approach to commissioning.
Unit: - Min: 0 Def: 0 Max: 22
Level 1
Example:
P0004=22 specifies that only PID parameters will be visible.
Settings:
0=All parameters 2=Variable speed drive 3=Motor 4=Speed sensor
5=Technol. application/units 7=Commands, binary I/O 8=ADC and DAC 10 =Setpoint channel / RFG
12 =Drive features 13 =Motor control 20 =Communication
21 =Alarms / warnings / monitoring 22 =Technology controller (e.g. PID)
Dependency:
Parameters marked "Quick Comm: Yes" in the parameter header can only be set when P0010=1 (Quick Commissioning).
Note:
The variable speed drive will start with any setting of P0004.
P0005 Display selection
Selects display for parameter r0000 (drive display).
Unit: - Min: 2 Def: 21 Max: 2294
Level 2
Settings:
21=Actual frequency 25=Output voltage 26=DC link voltage 27=Output current
Note:
These settings refer to read only parameter numbers ("rxxxx").
Details:
See relevant "rxxxx" parameter descriptions.
P0006 Display mode
Defines mode of display for r0000 (drive display).
Unit: - Min: 0 Def: 2 Max: 4
Level 3
Settings:
0=In Ready state alternate between setpoint and output
frequency. During run, display output frequency. 1=In Ready state display setpoint. In run display output freq. 2=In Ready state alternate between P0005 value and r0020
value. In run display P0005 value
3=In Ready state alternate between r0002 value and
r0020 value. In run display r0002 value
4=In all states just display P0005
Note:
When variable speed drive is not running, the display alternates between the values for "Not Running" and "Running". Per default, the setpoint and actual frequency values are displayed alternately.
P0010 Commissioning parameter filter
Filters parameters so that only those related to a particular functional group are selected.
Unit: - Min: 0 Def: 0 Max: 30
Level 1
Settings:
0=Ready 1=Quick commissioning 2=Variable speed drive
29 =Download 30 =Factory setting
Dependency:
Reset to 0 for variable speed drive to run. P0003 (user access level) also determines access to parameters.
Note:
If P3900 is not 0 (0 is the default value), this parameter is automatically reset to 0.
P0011 Lock for user-defined parameter
Unit: - Min: 0 Def: 0 Max: 65535
Level 3
Details:
See P0013 (user-defined parameter).
P0012 Key for user-defined parameter
Unit: - Min: 0 Def: 0 Max: 65535
Level 3
Details:
See P0013 (user-defined parameter).
P0013[20] User-defined parameter
Defines a limited set of parameters to which the end user will have access.
Unit: - Min: 0 Def: 0 Max: 65535
Level 3
78/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Programming 01.2002
Instructions:
1. Step 1: Set P0003=3 (expert user)
2. Step 2: Go to P0013 indices 0 to 16 (user list)
3. Step 3: Enter into P0013 index 0 to 16 the parameters required to be visible in the user-defined list. The following values are fixed and cannot be changed:
- P0013 index 19=12 (key for user defined parameter)
- P0013 index 18=10 (commissioning parameter filter)
- P0013 index 17= 3 (user access level)
4. Step 4: Set P0003=0 to activate the user defined parameter.
Dependency:
First, set P0011 ("lock") to a different value than P0012 ("key") to prevent changes to user-defined parameter. Then, set P0003 to 0 to activate the user-defined list. When locked and the user-defined parameter is activated, the only way to exit the user-defined parameter (and view other parameters) is to set P0012 ("key") to the value in P0011 ("lock").
Note:
Alternatively, set P0010=30 (commissioning parameter filter=factory setting) and P0970=1 (factory reset) to perform a complete factory reset. The default values of P0011 ("lock") and P0012 ("key") are the same.
r0018 Firmware version
Displays version number of installed firmware.
Unit: - Min: - Def: - Max: -
Level 3
r0019 CO/BO: BOP control word
Displays status of operator panel commands. The settings below are used as the "source" codes for keypad control when connecting to BICO input parameters.
Unit: - Min: - Def: - Max: -
Level 3
Bit fields:
Bit00 ON/OFF1 0 NO, 1 YES Bit01 OFF2: Electrical stop 0 YES, 1 NO Bit08 not used 0 NO, 1 YES Bit11 not used 0 NO, 1 YES Bit12 Hand Operation 0 NO, 1 YES Bit13 Motor potentiometer MOP up 0 NO, 1 YES Bit14 Motor potentiometer MOP down 0 NO, 1 YES Bit15 Auto Operation 0 NO, 1 YES
Note:
When BICO technology is used to allocate functions to panel buttons, this parameter displays the actual status of the relevant command. The following functions can be "connected" to individual buttons:
- ON/OFF1 - JOG - INCREASE
-OFF2 -REVERSE -DECREASE
r0020 CO: Act. frequency setpoint
Displays actual frequency setpoint (output from ramp function generator).
Unit: Hz Min: - Def: - M ax: -
Level 3
r0021 CO: Act. frequency
Displays actual variable speed drive output frequency (r0024) excluding slip compensation, resonance damping and frequency limitation.
Unit: Hz Min: - Def: - M ax: -
Level 3
r0022 Act. rotor speed
Displays calculated rotor speed based on variable speed drive output frequency [Hz] x 120 / number of poles.
Unit: 1/min Min: - Def: - Max: -
Level 3
Note:
This calculation makes no allowance for load-dependent slip.
r0024 CO: Act. output frequency
Displays actual output frequency (slip compensation, resonance damping and frequency limitation are included).
Unit: Hz Min: - Def: - Max: -
Level 3
r0025 CO: Act. output voltage
Displays [rms] voltage applied to motor.
Unit: V Min: - Def: - Max: -
Level 3
r0026[2] CO: Act. DC-link voltage
Displays DC-link voltage.
Unit: V Min: - Def: - Max: -
Level 3
r0027 CO: Act. output current
Displays [rms] value of motor current [A].
Unit:A Min:- Def:- Max:-
Level 3
r0031 CO: Act. torque
Displays motor torque.
Unit: Nm Min: - Def: - M ax: -
Level 3
r0032 CO: Act. power
Displays motor power.
Unit: - Min: - Def: - Max: -
Level 3
Dependency:
Value is displayed in [kW] or [hp] depending on setting for P0100 (operation for Europe / North America).
79/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Programming 01.2002
r0035 CO: Act. motor temperature
Displays measured motor temperature.
Unit: °C Min: - Def: - Max: -
Level 3
r0039 CO: Energy consumption meter [kWh]
Displays electrical energy used by variable speed drive since display was last reset (see P0040 - reset energy consumption meter).
Unit: kWh Min: - Def: - Max: -
Level 3
Dependency:
Value is reset when P3900=1 (end quick commissioning), P0970=1 (factory reset) or P0040=1 (reset energy consumption meter).
P0040 Reset energy consumption meter
Resets value of parameter r0039 (energy consumption meter) to zero.
Unit: - Min: 0 Def: 0 Max: 1
Level 3
Settings:
0=No reset 1=Reset r0039 to 0.
Dependency:
No reset until "P" is pressed.
r0052 CO/BO: Act. status word 1
Displays first active status word of variable speed drive (bit format) and can be used to diagnose variable speed drive status.
Unit: - Min: - Def: - Max: -
Level 3
Bit fields:
Bit00 Drive ready 0 NO, 1 YES Bit01 Drive ready to run 0 NO, 1 YES Bit02 Drive running 0 NO, 1 YES Bit03 Drive fault active 0 NO, 1 YES Bit04 OFF2 active 0 YES, 1 NO Bit05 OFF3 active 0 YES, 1 NO Bit06 ON inhibit active 0 NO, 1 YES Bit07 Drive warning active 0 NO, 1 YES Bit08 Deviation setp/act value 0 YES, 1 NO Bit09 PZD control 0 NO, 1 YES Bit10 Maximum frequency reached 0 NO, 1 YES Bit11 Warning: Motor current limit 0 YES, 1 NO Bit12 Motor holding brake active 0 NO, 1 YES Bit13 Motor overload 0 YES, 1 NO Bit14 Motor runs direction right 0 NO, 1 YES Bit15 VSD drive overload 0 YES, 1 NO
Note:
Output of Bit3 (Fault) will be inverted on digital output high=No Fault).
r0053 CO/BO: Act. status word 2
Displays second status word of variable speed drive (in bit format).
Unit: - Min: - Def: - Max: -
Level 3
Bit fields:
Bit00 DC brake active 0 NO, 1 YES Bit01 Act. freq. r0024 > P2167 0 NO, 1 YES Bit02 Act. freq. r0024 > P1080 0 NO, 1 YES Bit03 Act. current r0027 >= P2170 0 NO, 1 YES Bit04 Act. freq. r0024 > P2155 0 NO, 1 YES Bit05 Act. freq. r0024 <= P2155 0 NO, 1 YES Bit06 Act. freq. r0024 >= setpoint 0 NO, 1 YES Bit07 Act. Vdc r0026 < P2172 0 NO, 1 YES Bit08 Act. Vdc r0026 > P2172 0 NO, 1 YES Bit09 Ramping finished 0 NO, 1 YES Bit10 PID output r2294 < P2291 0 NO, 1 YES Bit11 PID output r2294 >= P2291 0 NO, 1 YES Bit14 Download data set 0 from AOP 0 NO, 1 YES Bit15 Download data set 1 from AOP 0 NO, 1 YES
r0054 CO/BO: Act. control word 1
Displays first control word of variable speed drive and can be used to diagnose which commands are active.
Unit: - Min: - Def: - Max: -
Level 3
Bit fields:
Bit00 ON/OFF1 0 NO, 1 YES Bit01 OFF2: Electrical stop 0 YES, 1 NO Bit02 OFF3: Fast stop 0 YES, 1 NO Bit03 Pulse enable 0 NO, 1 YES Bit04 RFG enable 0 NO, 1 YES Bit05 RFG start 0 NO, 1 YES Bit06 Setpoint enable 0 NO, 1 YES Bit07 Fault acknowledge 0 NO, 1 YES Bit08 JOG right 0 NO, 1 YES Bit09 JOG left 0 NO, 1 YES Bit10 Control from PLC 0 NO, 1 YES Bit11 Reverse (setpoint inversion) 0 NO, 1 YES Bit13 Motor potentiometer MOP up 0 NO, 1 YES Bit14 Motor potentiometer MOP down 0 NO, 1 YES Bit15 CDS Bit 0 (Local/Remote-Hand/Auto) 0 NO, 1 YES
r 0055 CO/BO: Add. act. control word
Displays additional control word of variable speed drive and can be used to diagnose which commands are active.
Level 3
80/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Programming 01.2002
Unit: - Min: - Def: - Max: -
Bit fields:
Bit00 Fixed frequency Bit 0 0 NO, 1 YES Bit01 Fixed frequency Bit 1 0 NO, 1 YES Bit02 Fixed frequency Bit 2 0 NO, 1 YES Bit03 Fixed frequency Bit 3 0 NO, 1 YES Bit08 PID enabled 0 NO, 1 YES Bit09 DC brake enabled 0 NO, 1 YES Bit11 Droop 0 NO, 1 YES Bit12 Not Used 0 NO, 1 YES Bit13 External fault 1 0 YES, 0 NO
r0056 CO/BO: Status of motor control
Displays status of motor control (V/f status), which can be used to diagnose variable speed drive status.
Unit: - Min: - Def: - Max: -
Level 3
Bit fields:
Bit00 Init. control finished 0 NO, 1 YES Bit01 Motor demagnetizing finished 0 NO, 1 YES Bit02 Pulses enabled 0 NO, 1 YES Bit03 Voltage soft start select 0 NO, 1 YES Bit04 Motor excitation finished 0 NO, 1 YES Bit05 Starting boost active 0 NO, 1 YES Bit06 Acceleration boost active 0 NO, 1 YES Bit07 Frequency is negative 0 NO, 1 YES Bit08 Field weakening active 0 NO, 1 YES Bit09 Volts setpoint limited 0 NO, 1 YES Bit10 Slip frequency limited 0 NO, 1 YES Bit11 F_out > F_max Freq. limited 0 NO, 1 YES Bit12 Phase reversal selected 0 NO, 1 YES Bit13 I-max controller active 0 NO, 1 YES Bit14 Vdc-max controller active 0 NO, 1 YES Bit15 Vdc-min controller active 0 NO, 1 YES
r0061 CO: Act. rotor speed
Displays current speed detected by encoder.
Unit: Hz Min: - Def: - M ax: -
Level 3
r0086 CO: Act. active current
Displays active (real part) of motor current.
Unit:A Min:- Def:- Max:-
Level 3
Dependency:
Applies when V/f control is selected in P1300 (control mode); otherwise, the display shows the value zero.
P0100 Europe / North America
Determines whether power settings (e.g. nominal rating plate power - P0307) are expressed in [kW] or [hp]. The default settings for the nominal rating plate frequency (P0310) and maximum motor frequency (P1082) are also set automatically here, in addition to reference frequency (P2000).
Unit: - Min: 0 Def: 0 Max: 2
Level 1
Settings:
0=Europe [kW], frequency default 50 Hz 1=North America [hp], frequency default 60 Hz 2=North America [kW], frequency default 60 Hz The setting of DIP switch 2 under the I/O board determines the validity of settings 0 and 1 for P0100 according to the following table:
DIP 2 Setting Meaning P0100 Setting Meaning
Off [kW], frequency default 50 [Hz] Overwrites 1 [hp], frequency default 60 [Hz] On [hp], frequency default 60 [Hz] Overwrites 0 [kW], frequency default 50 [Hz]
Dependency:
Stop drive first (i.e. disable all pulses) before you change this parameter. P0010=1 (commissioning mode) enables changes to be made. Changing P0100 resets all rated motor parameters as well as other parameters that depend on the rated motor parameters (see P0340 - calculation of motor parameters).
Note:
P0100 setting 2 (==> [kW], frequency default 60 [Hz]) is not overwritten by the setting of DIP switch 2 (see table above).
r0200 Act. power stack code number
Identifies hardware variant
Unit: - Min: - Def: - Max: -
Level 3
Note:
Parameter r0200=0 indicates that no power stack has been identified.
r0206 Rated variable speed drive power [kW] / [hp]
Displays nominal rated motor power from the variable speed drive.
Unit: - Min: - Def: - Max: -
Level 3
Dependency:
Value is displayed in [kW] or [hp] depending on setting for P0100 (operation for Europe / North America).
r0207 Rated variable speed drive current
Displays maximum continuous output current of the variable speed drive.
Unit:A Min:- Def:- Max:-
Level 3
r0208 Rated variable speed drive voltage
Displays nominal AC supply voltage of the variable speed drive.
Unit: V Min: - Def: - Max: -
Level 3
Value:
r0208=230 : 200 - 240 V +/- 10 % r0208=400 : 380 - 480 V +/- 10 % r0208=575 : 500 - 600 V +/- 10 %
81/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Programming 01.2002
r0209 Maximum variable speed drive current
Displays maximum output current of the variable speed drive.
Unit:A Min:- Def:- Max:-
Level 3
P0304 Rated motor voltage
Nominal motor voltage [V] from rating plate. The following diagram shows a typical rating plate with the locations of the relevant motor data.
Unit: V Min: 10 Def: 230 Max: 2000
Level 1
Dependency:
Changeable only when P0010=1 (quick commissioning).
P0305 Rated motor current
Nominal motor current [A] from rating plate.
Unit: A Min: 0.01 Def: 3.25 Max: 10000.00
Level 1
Dependency:
Changeable only when P0010=1 (quick commissioning). Depends also on P0320 (motor magnetization current).
Note:
For asynchronous motors, the maximum value is defined as the maximum variable speed drive current (r0209). For synchronous motors, the maximum value is defined as twice the maximum variable speed drive current (r0209). The minimum value is defined as 1/32 times variable speed drive rated current (r0207).
P0307 Rated motor power
Nominal motor power [kW/hp] from rating plate.
Unit: - Min: 0.01 Def: 0.75 Max: 2000.00
Level 1
Dependency:
If P0100=1 ([kW],frequency default 50 Hz), values will be in [hp]. Changeable only when P0010=1 (quick commissioning).
P0308 Rated motor cosPhi
Nominal motor power factor (cosPhi) from rating plate.
Unit: - Min: 0.000 Def: 0.000 Max: 1.000
Level 3
Dependency:
Changeable only when P0010=1 (quick commissioning). Visible only when P0100=0 or 2, (motor power entered in [kW]). Setting 0 causes internal calculation of value (see r0332).
P0309 Rated motor efficiency
Nominal motor efficiency in [%] from rating plate.
Unit: % Min: 0.0 Def: 0.0 Max: 99.9
Level 3
Dependency:
Changeable only when P0010=1 (quick commissioning). Visible only when P0100=1, (i.e. motor power entered in [hp]). Setting 0 causes internal calculation of value (see r0332).
Note:
P0309=100 % corresponds to superconducting
P0310 Rated motor frequency
Nominal motor frequency [Hz] from rating plate.
Unit: Hz Min: 12.00 Def: 50.00 Max: 650.00
Level 1
Dependency:
Changeable only when P0010=1 (quick commissioning). The pole pair number is recalculated automatically if parameter is changed.
P0311 Rated motor speed
Nominal motor speed [rpm] from rating plate.
Unit: 1/min Min: 0 Def: 0 Max: 40000
Level 1
Dependency:
Changeable only when P0010=1 (quick commissioning). Setting 0 causes an internal calculation of value. Required for V/f control with speed controller. Slip compensation in V/f control requires the rated motor speed for correct operation. The pole pair number is recalculated automatically if the parameter is changed.
r0313 Motor pole pairs
Displays the number of motor pole pairs that the variable speed drive is currently using for internal calculations.
Unit: - Min: - Def: - Max: -
Level 3
Value:
r0313=1 : 2-pole motor r0313=2 : 4-pole motor, etc.
Dependency:
Recalculated automatically when P0310 (rated motor frequency) or P0311 (rated motor speed) is changed.
P0340 Calculation of motor parameters
Calculates various motor parameters, including:
Unit: - Min: 0 Def: 0 Max: 4
Level 3
Data:
Calculates various motor parameters, including:
Motor weight P0344 (Level 3)
Magnetization time P0346 (Level 3)
Demagnetization time P0347 (Level 3)
Stator resistance P0350 (Level 2)
Reference frequency P2000 (Level 2)
Reference current P2002 (Level 3).
Settings:
0=No calculation 1=Complete parameterization 2=Calc. equivalent circuit data
3=Calc. V/f 4=Calc. only controller setting
Note:
This parameter is required during commissioning to optimize the variable speed drive performance.
P0350 Stator resistance (line-to-line)
Stator resistance value in [Ohms] for the connected motor (from line-to-line). The parameter value includes the cable resistance.
Unit: Ohm Min: 0.00001 Def: 4.0 Max: 2000.0
Level 3
82/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Programming 01.2002
Data:
Stator resistance value in [Ohms] for the connected motor (from line-to-line). The parameter value includes the cable resistance. There are three ways to determine the value for this parameter:
1. Calculate using P0340=1 (data entered from rating plate) or P3900=1,2 or 3 (end of quick commissioning).
2. Measure using P1910=1 (motor data identification - value for stator resistance is overwritten).
3. Measure manually using an Ohmmeter.
Note:
Since measured line-to-line, this value may appear to be higher (up to 2 times higher) than expected. The value entered in P0350 (stator resistance) is the one obtained by the method last used.
r0395 CO: Total stator resistance [%]
Displays stator resistance of motor as [%] of combined stator/cable resistance.
Unit: % Min: - Def: - Max: -
Level 3
Note:
100% means: Z
rated motor
=
P0304 (rated motor voltage) P0305 (rated motor current)
P0400 Select encoder type
Selects encoder type.
Unit: - Min: 0 Def: 0 Max: 12
Level 3
Settings:
0=disabled 1=Single channel encoder 2=Quadrature encoder without zero pulse
3=External pulse train 12=Quadrature encoder with zero pulse
Note:
The term “quadrature” in settings 2 and 12 refers to 2 periodic functions separated by a quarter cycle or 90 degrees.
P0409 Pulses per second at rated frequency
Sets number of pulses per second at rated speed.
Unit: - Min: 1 Def: 25 Max: 500
Level 3
P0501[2] Type of sensor
Defines type of process variable sensor that each analog input is to be configured for. Note that setting this parameter will in turn set P0756 (analog input mode). To switch between voltage and current analog input modes also requires the DIP switches on the terminal board to be set correctly. See description for P0756.
Unit: - Min: 0 Def: 0 Max: 51
Level 2
Settings:
0=No sensor selected 1=Sensor type QBE620 P1 2=Sensor type QBE620 P10 3=Sensor type QBE620 P16 4=Sensor type QBE620 P25 5=Sensor type QBE620 P40 6=Sensor type QBE620 P4 7=Sensor type QBE620 P5 8=Sensor type QBE621 P10U 9=Sensor type QBE621 P25U
10=Sensor type QBE63 DP01 11=Sensor type QBE63 DP02 12=Sensor type QBE63 DP05 13=Sensor type QBE63 DP1 14=Sensor type QBE64 DP4 15=Sensor type 0 TO 1 INCH WC 16=Sensor type 0 TO 2 INCH WC 17=Sensor type 0 TO 2.5 INCH WC 18=Sensor type 0 TO 3 INCH WC 19=Sensor type 0 TO 5 INCH WC
20=Sensor type 0 TO 10 INCH WC 21=Sensor type 0 TO 10 PSI 22=Sensor type 0 TO 15 PSI 23=Sensor type 0 TO 25 PSI 24=Sensor type 0 TO 30 PSI 25=Sensor type 0 TO 50 PSI 26=Sensor type 0 TO 60 PSI 27=Sensor type 0 TO 100 PSI 28=Sensor type 0 TO 150 PSI 29=Sensor type Al Ni 1000: -50 to 150 °C
Details:
See P0753 and P0756 to P0762 (ADC conditioning).
P0506[10] Parameterlist
This parameter performs no function within the variable speed drive. It is a storage place for use with the AOP for a list of parameters to scale.
Unit: - Min: 0 Def: 754 Max: 4000
Level 3
Index:
P0506[0] : Parameter 1 P0506[1] : Parameter 2 P0506[2] : Parameter 3
P0506[3] : Parameter 4 P0506[4] : Parameter 5 P0506[5] : Parameter 6
P0506[6] : Parameter 7 P0506[7] : Parameter 8 P0506[8] : Parameter 9
P0506[9] : Parameter 10
P0507[3] Scalar values
This parameter performs no function within the variable speed drive. It is a storage place for use with the AOP to scale particular parameters.
Unit: - Min: 0 Def: 1.0 Max: 9999.9
Level 3
Index:
P0507[0] : Scalar numerator P0507[1] : Scalar denominator P0507[2] : Scalar offset
P0508[4] Unit
This parameter performs no function within the variable speed drive. It is a storage place for use with the AOP to store a string for unit.
Unit: - Min: 0 Def: 0 Max: 65535
Level 3
Index:
P0508[0] : Unit character 1 P0508[1] : Unit character 2 P0508[2] : Unit character 3 P0508[3] : Unit character 4
P0509[12] String
This parameter performs no function within the variable speed drive. It is a storage place for use with the AOP to store a string for parameter unit description
Unit: - Min: 0 Def: 0 Max: 65535
Level 3
Index:
P0509[0] : String char 1 P0509[1] : String char 2 P0509[2] : String char 3
P0509[3] : String char 4 P0509[4] : String char 5 P0509[5] : String char 6
P0509[6] : String char 7 P0509[7] : String char 8 P0509[8] : String char 9
P0509[9] : String char 10 P0509[10] : String char 11 P0509[11] : String char 12
P0601 Motor temperature sensor
Selects motor temperature sensor.
Unit: - Min: 0 Def: 0 Max: 2
Level 3
Settings:
0=No sensor 1=PTC thermistor 2=KTY84
Dependency:
If “no sensor” is selected, motor temperature monitoring occurs based on the estimated value of the thermal motor model.
83/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Programming 01.2002
P0610 Motor I2t temperature reaction
Defines reaction when motor temperature reaches warning threshold.
Unit: - Min: 0 Def: 2 Max: 2
Level 3
Settings:
0=No reaction, warning only 1=Warning and Imax reduction (results in reduced output freq.) 2=Warning and trip
(F0010)
P0640 Motor overload factor [%]
Defines reaction when motor temperature reaches warning threshold.
Unit: % Min: 10.0 Def: 110.0 Max: 400.0
Level 3
Dependency:
Limited to maximum variable speed drive current or to 400 % of rated motor current (P0305), whichever is lower.
P0700[2] Selection of command source
Selects digital command source.
Unit: - Min: 0 Def: 2 Max: 6
Level 1
Settings:
0=Factory default setting 1=BOP (keypad)
2=Terminal 4=USS on BOP link
5=USS on COM link 6=CB on COM link
Index:
P0700[0] : 1st command data set (CDS) P0700[1] : 2nd command data set (CDS)
Note:
Changing this parameter resets (to default) all settings on item selected. For example: Changing form 1 to 2 resets all digital inputs to default settings.
P0701[2] Function of digital input 1
Selects function of digital input 1.
Unit: - Min: 0 Def: 1 Max: 99
Level 2
Settings:
0=Digital input disabled 1=ON/OFF1 2=ON reverse /OFF1 3=OFF2 - coast to standstill 4=OFF3 - quick ramp-down 9=Fault acknowledge 10 =JOG right
11 =JOG left 12 =Reverse 13 =MOP up (increase freq.) 14 =MOP down (decrease freq.) 15 =Fixed setpoint (direct selection) 16 =Fixed setpoint (direct selection + ON) 17 =Fixed setpoint (binary coded selection+ON)
25 =DC brake enable 26 =Enable Essential Service 27 =Enable PID 29 =External trip 33 =Disable additional freq setpoint 99 =Enable BICO parameterization
Index:
P0701[0] : 1st command data set (CDS) P0701[1] : 2nd command data set (CDS)
Dependency:
Setting 99 (enable BICO parameterization) requires P0700 (command source) or P3900 (end of quick commissioning)=1, 2 or P0970 (factory reset)=1 in order to reset.
Note:
Setting 99 (BICO) for expert use only
P0702[2] Function of digital input 2 Level 2
Selects function of digital input 2.
Unit: - Min: 0 Def: 12 Max: 99
Detail:
See P0701 (function of digital input1).
P0703[2] Function of digital input 3 Level 2
Selects function of digital input 3.
Unit: - Min: 0 Def: 9 Max: 99
Detail:
See P0701 (function of digital input1).
P0704[2] Function of digital input 4 Level 2
Selects function of digital input 4.
Unit: - Min: 0 Def: 15 Max: 99
Detail:
See P0701 (function of digital input1).
P0705[2] Function of digital input 5 Level 2
Selects function of digital input 5 (via analog input)
Unit: Min: 0 Def: 15 M ax: 99
Detail:
See P0701 (function of digital input1).
P0706[2] Function of digital input 6 Level 2
Selects function of digital input 6 ( via analog input)
Unit: _ Min: 0 Def: 29 Max: 99 Detail:
See P0701 (function of digital input1).
P0707[2] Function of digital input 7
Selects function of digital input 7 (via analog input)
Unit: - Min: 0 Def: 0 Max: 99
Level 3
Settings:
0=Digital input disabled 1=ON/OFF1 2=ON reverse /OFF1 3=OFF2 - coast to standstill 4=OFF3 - quick ramp-down 9=Fault acknowledge
10 =JOG right 11 =JOG left 12 =Reverse 13 =MOP up (increase freq.) 14 =MOP down (decrease freq.)
25 =DC brake enable 26 =Enable Essential Service 29 =External trip 33 =Disable additional freq setpoint 99 =Enable BICO parameterization
Index:
P0707[0] : 1st command data set (CDS) P0707[1] : 2nd command data set (CDS)
Dependency:
Signals about 4V are active, signals below 1.6 V are inactive.
Note:
Signals above 4 V are active, signals below 1.6 V are inactive.
Details:
See P0701 (function of digital input 1).
P0708[2] Function of digital input 8
Selects function of digital input 8 (via analog input)
Unit: - Min: 0 Def: 0 Max: 99
Level 3
Detail:
See P0707 (function of digital input7).
84/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Programming 01.2002
P0718 CO/BO: Hand / Auto
Selects function of digital input 8 (via analog input)
Unit: - Min: 0 Def: 0 Max: 1
Level 3
r0722 CO/BO: Binary input values
Displays status of digital inputs.
Unit: - Min: - Def: - Max: -
Level 3
Bit fields:
Bit00 Digital input 1 0 OFF, 1 ON Bit01 Digital input 2 0 OFF, 1 ON Bit02 Digital input 3 0 OFF, 1 ON Bit03 Digital input 4 0 OFF, 1 ON Bit04 Digital input 5 0 OFF, 1 ON Bit05 Digital input 6 0 OFF, 1 ON Bit06 Digital input 7 (via ADC 1) 0 OFF, 1 ON Bit07 Digital input 8 (via ADC 2) 0 OFF, 1 ON
Note:
Segment is lit when signal is active.
P0725 PNP / NPN digital inputs
Switches between active high (PNP) and active low (NPN). This is valid for all digital inputs simultaneously. The following is valid by using the internal supply:
Unit: - Min: 0 Def: 1 Max: 1
Level 3
Settings:
0=NPN mode ==> low active 1=PNP mode ==> high active
P0731[2] BI: Function of digital output 1
Defines source of digital output 1.
Unit: - Min: 0.0 Def: 52.3 Max: 4000.0
Level 2
Settings:
52.0 Drive ready 0 Closed
52.1 Drive ready to run 0 Closed
52.2 Drive running 0 Closed
52.3 Drive fault active 0 Closed
52.4 OFF2 active 1 Closed
52.5 OFF3 active 1 Closed
52.6 Switch on inhibit active 0 Closed
52.7 Drive warning active 0 Closed
52.8 Deviation setpoint/actual value 1 Closed
52.9 PZD control (Process Data Control) 0 Closed
52.A Maximum frequency reached 0 Closed
52.B Warning: Motor current limit 1 Closed
52.C Motor holding brake (MHB) active 0 Closed
52.D Motor overload 1 Closed
52.E Motor running direction right 0 Closed
52.F VSD drive overload 1 Closed
53.0 DC brake active 0 Closed
53.1 VSD frequency less switch off limit 0 Closed
53.2 VSD frequency less minimum freq. 0 Closed
53.3 Current greater or equal than limit 0 Closed
53.4 Act. freq. greater comparison freq. 0 Closed
53.5 Act. freq. less comparison freq. 0 Closed
53.6 Act. freq. greater/equal setpoint 0 Closed
53.7 Voltage less than threshold 0 Closed
53.8 Voltage greater than threshold 0 Closed
53.A PID output at lower limit (P2292) 0 Closed
53.B PID output at upper limit (P2291) 0 Closed
Index:
P0731[0] : 1st command data set (CDS) P0731[1] : 2nd command data set (CDS)
P0732[2] BI: Function of digital output 2
Defines source of digital output 2.
Unit: -
Min: 0.0
Def: 52.2 Max: 4000.0
Level 2
Details:
See P0731 (function of digital output 1).
r0747 CO/BO: State of digital outputs
Displays status of digital outputs (also includes inversion of digital outputs via P0748).
Unit: - Min: - Def: - Max: -
Level 3
Bit fields:
Bit00 Digital output 1 energized 0 NO, 1 YES Bit01 Digital output 2 energized 0 NO, 1 YES
Dependency:
Bit 0= Relay de-energized / contacts open Bit 1= Relay energized / contacts closed
P0748 Invert digital outputs
Defines high and low states of relay for a given function.
Unit: - Min: 0 Def: 0 Max: 7
Level 3
Bit fields:
Bit00 Invert digital output 1 0 NO, 1 YES Bit01 Invert digital output 2 0 NO, 1 YES
r0752[2] Act. input of ADC [V] or [mA]
Displays smoothed analog input value in volts before the characteristic block.
Unit: - Min: - Def: - Max: -
Level 2
Index:
r0752[0] : Analog input 1 (ADC 1) r0752[1] : Analog input 2 (ADC 2)
P0753[2] Smooth time ADC
Defines filter time (PT1 filter) in [ms] for analog input.
Unit: ms Min: 0 Def: 100 Max: 10000
Level 3
Index:
P0753[0] : Analog input 1 (ADC 1) P0753[1] : Analog input 2 (ADC
Note:
Increasing this time (smooth) reduces jitter but slows down response to the analog input.
r0754[2] Act. ADC value after scaling [%]
Shows smoothed value of analog input in [%] after scaling block.
Unit: % Min: - Def: - Max: -
Level 2
Index:
r0754[0] : Analog input 1 (ADC 1) r0754[1] : Analog input 2 (ADC 2)
Dependency:
P0757 to P0760 define range (ADC scaling)
85/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Programming 01.2002
r0755[2] CO: Act. ADC after scaling [4000h]
Displays analog input, scaled using ASPmin and ASPmax.
Unit: - Min: - Def: - Max: -
Level 3
Data:
The analog setpoint (ASP) from the analog scaling block can vary from min. analog setpoint (ASPmin) to a max. analog setpoint (ASPmax) as shown in P0757 (ADC scaling). The largest magnitude (value without sign) of ASPmin and ASPmax defines the scaling of 16384.
Example:
ASPmin=300 %, ASPmax=100 % then 16384 represents 300 %. This parameter will vary from 5461 to 16364 ASPmin=-200 %, ASPmax=100 % then 16384 represents 200 %. This parameter will vary from –16384 to +8192
Index:
r0755[0] : Analog input 1 (ADC 1) r0755[1] : Analog input 2 (ADC 2)
Note:
This value is used as an input to analog BICO connectors. ASPmax represents the highest analog setpoint (this may be at 10 V) ASPmin represents the lowest analog setpoint (this may be at 0 V)
Details:
See parameters P0757 to P0760 (ADC scaling)
P0756[2] Type of ADC
Defines type of analog input and also enables analog input monitoring.
Unit: - Min: 0 Def: 0 Max: 5
Level 2
Data:
Defines type of analog input and also enables analog input monitoring. To switch over from voltage to current analog input it is not sufficient to merely modify parameter P0756. Rather, the DIPs on the terminal board must also be set to the correct position. The DIP settings are as follows:
- OFF=voltage input (10 V)
- ON =current input (20 mA) Allocation of DIPs to analog inputs is as follows:
- DIP on left (DIP 1)= Analog input 1
- DIP on right (DIP 2)= Analog input 2
Settings:
0=Unipolar voltage input (0 to +10 V) 1=Unipolar voltage input with monitoring (0 to 10 V) 2=Unipolar current input (0 to 20 mA)
3=Unipolar current input with monitoring (0 to 20 mA) 4=Bipolar voltage input (-10 V to +10 V) 5=LG-Ni 1000 sensor input
Index:
P0756[0] : Analog input 1 (ADC 1) P0756[1] : Analog input 2 (ADC 2)
Dependency:
Function disabled if analog scaling block programmed to output negative setpoints (see P0757 to P0760).
Note:
When monitoring is enabled and a deadband defined (P0761), a fault condition will be generated (F0080) if the analog input voltage falls below 50 % of the deadband voltage.
Details:
See P0757 to P0760 (ADC scaling).
P0757[2] Value x1 of ADC scaling [V / mA]
Parameters P0757 - P0760 configure the input scaling
Unit: - Min: -50.0 Def: 0 Max: 150.0
Level 2
Data:
Parameters P0757 - P0760 configure the input scaling where:
Analog setpoints represent a [%] of the normalized frequency in P2000.
Analog setpoints may be larger than 100 %
ASP max represents highest analog setpoint (this may be at 10 V).
ASP min represents lowest analog setpoint (this may be at 0 V).
Default values provide a scaling of 0 V=0 %, and 10 V=100 %.
Index:
P0757[0] : Analog input 1 (ADC 1) P0757[1] : Analog input 2 (ADC 2
P0758[2] Value y1 of ADC scaling
Sets value of Y1 in [%] as described in P0757 (ADC scaling)
Unit: % Min: -99999.9 Def: 0.0 Max: 99999.9
Level 2
Index:
P0758[0] : Analog input 1 (ADC 1) P0758[1] : Analog input 2 (ADC 2)
Dependency:
Affects P2000 to P2003 (reference frequency, voltage, current or torque) depending on which setpoint is to be generated.
P0759[2] Value x2 of ADC scaling [V / mA]
Sets value of X2 as described in P0757 (ADC scaling)
Unit: - Min: -50.0 Def: 10 Max: 150.0
Level 2
Index:
P0759[0] : Analog input 1 (ADC 1) P0759[1] : Analog input 2 (ADC 2
P0760[2] Value y2 of ADC scaling
Sets value of Y2 in [%] as described in P0757 (ADC scaling)
Unit: % Min: -99999.9 Def: 100.0 Max: 99999.9
Level 2
Index:
P0760[0] : Analog input 1 (ADC 1) P0760[1] : Analog input 2 (ADC 2)
Dependency:
Affects P2000 to P2003 (reference frequency, voltage, current or torque) depending on which setpoint is to be generated.
P0761[2] Width of ADC deadband [V / mA]
Defines width of deadband on analog input. The diagrams below explain its use
Unit: - Min: 0 Def: 0 Max: 150.0
Level 3
Index:
P0761[0] : Analog input 1 (ADC 1) P0761[1] : Analog input 2 (ADC 2)
Note:
P0761[x]=0 : No deadband active. Deadband starts from 0 V to value of P0761, if both values of P0758 and P0760 (y coordinates of ADC scaling) are positive or negative respectively. However, deadband is active in both directions from point of intersection (x axis with ADC scaling curve), if sign of P0758 and P0760 are opposite. Fmin (P1080) should be zero when using center zero setup. There is no hysteresis at the end of the deadband.
P0771[2] CI: DAC Level 2
Defines function of the 0 - 20 mA analog output.
86/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Programming 01.2002
Unit: - Min: 0:0 Def: 21:0 Max: 4000:0
Settings:
21 CO: Act. frequency (scaled to P2000) 24 CO: Act. output frequency (scaled to P2000) 25 CO: Act. output voltage (scaled to P2001)
26 CO: Act. DC-link voltage (scaled to P2001) 27 CO: Act. output current (scaled to P2002)
Index:
P0771[0] : Analog output 1 (DAC 1) P0771[1] : Analog output 2 (DAC 2)
P0773[2] Smooth time DAC
Defines smoothing time [ms] for analog output signal. This parameter enables smoothing for DAC input using a PT1 filter.
Unit: ms Min: 0 Def: 100 Max: 1000
Level 3
Index:
P0773[0] : Analog output 1 (DAC 1) P0773[1] : Analog output 2 (DAC 2)
Dependency:
P0773=0: Deactivates filter.
R0774[2] Act. DAC value [V] or [mA]
Shows value of analog output in [V] or [mA] after filtering and scaling.
Unit: - Min: - Def: - Max: -
Level 3
Index:
r0774[0] : Analog output 1 (DAC 1) r0774[1] : Analog output 2 (DAC 2)
P0776 Type of DAC
Defines type of analog output.
Unit: - Min: 0 Def: 1 Max: 1
Level 3
Settings:
0 Current output 1 Voltage output
Note:
The analog output is designed as a current output with a range of 0...20 mA. For the ECB variant, the two analog output channels must be of the same type i.e. both channels are current outputs with a range of 0...20 mA or both channels are defined as voltage outputs with a range of 0...10 V.
P0777[2] Value x1 of DAC scaling
Defines x1 output characteristic in [%]. Scaling block is responsible for adjustment of output value defined in P0771 (DAC connector input). Parameters of DAC scaling block (P0777 ... P0781) work as follows:
Unit: % Min: -99999.0 Def: 0.0 Max: 99999.0
Level 2
Data:
Defines x1 output characteristic in [%]. Scaling block is responsible for adjustment of output value defined in P0771 (DAC connector input).
Index:
P0777[0] : Analog output 1 (DAC 1) P0777[1] : Analog output 2 (DAC 2)
Dependency:
Affects P2000 to P2003 (reference frequency, voltage, current or torque) depending on which setpoint is to be generated.
P0778[2] Value y1 of DAC scaling
Defines y1 of output characteristic.
Unit: - Min: 0 Def: 0 Max: 20
Level 2
Index:
P0778[0] : Analog output 1 (DAC 1) P0778[1] : Analog output 2 (DAC 2)
P0779[2] Value x2 of DAC scaling Level 2
Defines x2 of output characteristic in [%].
Unit: % Min: -99999.0 Def: 100.0 Max: 99999.0
Index:
P0779[0] : Analog output 1 (DAC 1) P0779[1] : Analog output 2 (DAC 2)
Dependency:
Affects P2000 to P2003 (reference frequency, voltage, current or torque) depending on which setpoint is to be generated.
P0780[2] Value y2 of DAC scaling Level 2
Defines y2 of output characteristic.
Unit: - Min: 0 Def: 10 Max: 20 Index:
P0780[0] : Analog output 1 (DAC 1) P0780[1] : Analog output 2 (DAC 2)
P0781[2] Width of DAC deadband
Sets width of dead-band in [mA] or [V] for analog output.
Unit: - Min: 0 Def: 0 Max: 20
Level 3
Index:
P0781[0] : Analog output 1 (DAC 1) P0781[1] : Analog output 2 (DAC 2)
P0809[3] Copy Command Data Set
Calls 'Copy command data set' function.
Unit: - Min: 0 Def: 0 Max: 2
Level 3
Index:
P0809[0] : Copy from CDS P0809[1] : Copy to DDS P0809[2] : Start copy
Note:
Start value in index 2 is automatically reset to '0' after execution of function
P0810 BI: CDS bit 0 (Local / Remote)
Selects command source from which to read Bit 0 for selecting a BICO data set (see control word 1, Bit 15).
Unit: - Min: 0:0 Def: 718:0 Max: 4095:0
Level 3
Note:
Bit 1 is also relevant for BICO data set selection.
P0918 CB address
Defines address of CB (communication board) or address of the other option modules.
Unit: - Min: 0 Def: 3 Max: 65535
Level 3
Data:
Defines address of CB (communication board) or address of the other option modules. There are two ways to set the bus address: 1 via DIP switches on the PROFIBUS module 2 via a user-entered value
87/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Programming 01.2002
Note:
Possible PROFIBUS settings: 1 ... 125 0, 126, 127 are not allowed The following applies when a PROFIBUS module is used: DIP switch =0 Address defined in P0918 (CB address) is valid DIP switch not=0 DIP switch setting has priority and P0918 indicates DIP switch setting.
P0927 Parameter changeable via Level 3
Specifies the interfaces which can be used to change parameters.
Unit: - Min: 0 Def: 15 Max: 15
Example:
b - - n n" (bits 0, 1, 2 and 3 set) in the default setting means that parameters can be changed via any interface. "b - - r n" (bits 0, 1 and 3 set) would specify that parameters can be changed via PROFIBUS/CB, BOP and USS on COM link (RS485 USS) but not via USS on BOP link (RS232)
Bit fields:
Bit00 PROFIBUS / CB 0 NO, 1 YES Bit01 BOP 0 NO, 1 YES
Bit02 USS on BOP link 0 NO, 1 YES Bit03 USS on COM link 0 NO, 1 YES
r0947[8] Last fault code
Displays fault history according to the diagram below
Unit: - Min: - Def: - Max: -
Level 3
Data:
Displays fault history, where: "F1" is the first active fault (not yet acknowledged). "F2" is the second active fault (not yet acknowledged). "F1e" is the occurrence of the fault acknowledgement for F1 & F2. This moves the value in the 2 indices down to the next pair of indices, where they are stored. Indices 0 & 1 contain the active faults. When faults are acknowledged, indices 0 & 1 are reset to 0.
Example:
If the variable speed drive trips on undervoltage and then receives an external trip before the undervoltage is acknowledged, you will obtain: Index 0=3 Undervoltage Index 1=85 External trip Whenever a fault in index 0 is acknowledged (F1e), the fault history shifts as indicated in the diagram above.
Index:
r0947[0] : Recent fault trip --, fault 1 r0947[1] : Recent fault trip --, fault 2 r0947[2] : Recent fault trip -1, fault 3
r0947[3] : Recent fault trip -1, fault 4 r0947[4] : Recent fault trip -2, fault 5 r0947[5] : Recent fault trip -2, fault 6
r0947[6] : Recent fault trip -3, fault 7 r0947[7] : Recent fault trip -3, fault 8
Dependency:
Index 2 used only if second fault occurs before first fault is acknowledged.
r0948[12] Fault time
Time stamp to indicate when the fault has occurred. P2114 (run-time counter) or P2115 (real time clock) are the possible sources of the time stamp.
Unit: - Min: - Def: - Max: -
Level 3
Data:
Time stamp to indicate when the fault has occurred. P2114 (run-time counter) or P2115 (real time clock) are the possible sources of the time stamp.
Example:
The time is taken from P2115 if this parameter has been updated with the real time. If not, P2114 is used
Index:
r0948[0] : Recent fault trip --, fault time seconds+minutes r0948[1] : Recent fault trip –, fault time hours+days r0948[2] : Recent fault trip --, fault time month+year r0948[3] : Recent fault trip --1, fault time seconds+minutes r0948[4] : Recent fault trip --1, fault time hours+days r0948[5] : Recent fault trip --1, fault time month+year
r0948[6] : Recent fault trip -2, fault time seconds+minutes r0948[7] : Recent fault trip -2, fault time hours+days r0948[8] : Recent fault trip -2, fault time month+year r0948[9] : Recent fault trip -3, fault time seconds+minutes r0948[10] : Recent fault trip -3, fault time hours+days r0948[11] : Recent fault trip -3, fault time month+year`
Note:
P2115 can be updated via AOP, Starter, Drive Monitor, etc.
r0949[8] Fault value
Displays drive fault values. It is for service purposes and indicate the type of fault reported. The values are not documented. They are listed in the code where faults are reported.
Unit: - Min: - Def: - Max: -
Level 3
Index:
r0949[0] : Recent fault trip --, fault value 1 r0949[1] : Recent fault trip --, fault value 2 r0949[2] : Recent fault trip -1, fault value 3 r0949[3] : Recent fault trip -1, fault value 4
r0949[4] : Recent fault trip -2, fault value 5 r0949[5] : Recent fault trip -2, fault value 6 r0949[6] : Recent fault trip -3, fault value 7 r0949[7] : Recent fault trip -3, fault value 8
P0952 Total number of faults
Displays number of faults stored in P0947 (last fault code).
Unit: - Min: 0 Def: 0 Max: 8
Level 3
Dependency:
Setting 0 resets fault history (changing to 0 also resets parameter P0948 - fault time).
r0967 Control word 1
Displayscontrol word 1.
Unit: - Min: - Def: - Max: -
Level 3
Bit fields:
Bit00 ON/OFF1 0 NO, 1 YES Bit01 OFF2: Electrical stop 0 YES, 1 NO Bit02 OFF3: Fast stop 0 YES, 1 NO Bit03 Pulse enable 0 NO, 1 YES Bit04 RFG enable 0 NO, 1 YES Bit05 RFG start 0 NO, 1 YES Bit06 Setpoint enable 0 NO, 1 YES Bit07 Fault acknowledge 0 NO, 1 YES Bit08 JOG right 0 NO, 1 YES Bit09 JOG left 0 NO, 1 YES Bit10 Control from PLC 0 NO, 1 YES Bit11 Reverse (setpoint inversion) 0 NO, 1 YES
88/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Programming 01.2002
Bit13 Motor potentiometer MOP up 0 NO, 1 YES Bit14 Motor potentiometer MOP down 0 NO, 1 YES Bit15 CDS Bit 0 (Local/Remote-Hand/Auto) 0 NO, 1 YES
r0968 Status word 1
Displays active status word of variable speed drive (in binary) and can be used to diagnose which commands are active.
Unit: - Min: - Def: - Max: -
Level 3
Bit fields:
Bit00 Drive ready 0 NO, 1 YES Bit01 Drive ready to run 0 NO, 1 YES Bit02 Drive running 0 NO, 1 YES Bit03 Drive fault active 0 NO, 1 YES Bit04 OFF2 active 0 YES, 1 NO Bit05 OFF3 active 0 YES, 1 NO Bit06 ON inhibit active 0 NO, 1 YES Bit07 Drive warning active 0 NO, 1 YES Bit08 Deviation setp. / act. value 0 YES, 1 NO Bit09 PZD control 0 NO, 1 YES Bit10 Maximum frequency reached 0 NO, 1 YES Bit11 Warning: Motor current limit 0 YES, 1 NO Bit12 Motor holding brake active 0 NO, 1 YES Bit13 Motor overload 0 YES, 1 NO Bit14 Motor runs direction right 0 NO, 1 YES Bit15 VSD drive overload 0 YES, 1 NO
P0970 Factory reset
P0970 = 1 resets all parameters to their default values.
Unit: - Min: 0 Def: 0 Max: 1
Level 1
Settings:
0=Disabled 1=Parameter reset
Dependency:
First set P0010=30 (factory settings) Stop drive (i.e. disable all pulses) before you can reset parameters to default values.
Note:
The following parameters retain their values after a factory reset: P0918 (CB address), P2010 (USS baud rate) and P2011 (USS address)
P0971 Transfer data from RAM to EEPROM
Transfers values from RAM to EEPROM when set to 1.
Unit: - Min: 0 Def: 0 Max: 1
Level 3
Settings:
0=Disabled 1=Start transfer
Note:
All values in RAM are transferred to EEPROM. Parameter is automaticallyreset to 0 (default)aftersuccessful transfer.
P1000[2] Selection of frequency setpoint
Selects frequency setpoint source. In the table of possible settings below, the main setpoint is selected from the least significant digit (i.e., 0 to 6) and any additional setpoint from the most significant digit (i.e., x0 through to x6).
Unit: - Min: 0 Def: 2 Max: 77
Level 1
Data:
Selects frequency setpoint source. In the table of possible settings below, the main setpoint is selected from the least significant digit (i.e., 0 to 6) and any additional setpoint from the most significant digit (i.e., x0 through to x6).
Example:
Setting 12 selects main setpoint (2) derived from analog input with additional setpoint (1) taken from the motor potentiometer.
Settings:
1 Motor potentiometer setpoint 2 Analog input
3 Fixed frequency setpoint 4 USS on BOP link
5 USS on COM link 6 Communication board (CB) on COM link
Settings:
0=No main setpoint 1=MOP setpoint 2=Analog setpoint 3=Fixed frequency 4=USS on BOP link 5=USS on COM link 6=CB on COM link 7=Analog setpoint 2 10=No main setpoint + MOP setpoint 11=MOP setpoint + MOP setpoint 12=Analog setpoint + MOP setpoint 13=Fixed frequency + MOP setpoint 14=USS on BOP link + MOP setpoint 15=USS on COM link + MOP setpoint 16=CB on COM link + MOP setpoint 17=Analog setpoint 2 + MOP setpoint 20=No main setpoint + Analog setpoint 21=MOP setpoint + Analog setpoint 22=Analog setpoint + Analog setpoint 23=Fixed frequency + Analog setpoint 24=USS on BOP link + Analog setpoint 25=USS on COM link + Analog setpoint 26=CB on COM link + Analog setpoint 27=Analog setpoint 2 + Analog setpoint 30=No main setpoint + Fixed frequency
40=No main setpoint + USS on BOP link 41=MOP setpoint + USS on BOP link 42=Analog setpoint + USS on BOP link 43=Fixed frequency + USS on BOP link 44=USS on BOP link + USS on BOP link 45=USS on COM link + USS on BOP link 46=CB on COM link + USS on BOP link 47=Analog setpoint 2 + USS on BOP link 50=No main setpoint + USS on COM link 51=MOP setpoint + USS on COM link 52=Analog setpoint + USS on COM link 53=Fixed frequency + USS on COM link 54=USS on BOP link + USS on COM link 55=USS on COM link + USS on COM link 56=CB on COM link + USS on COM link 57=Analog setpoint 2 + USS on COM link 60=No main setpoint + CB on COM link 61=MOP setpoint + CB on COM link 62=Analog setpoint + CB on COM link 63=Fixed frequency + CB on COM link 64=USS on BOP link + CB on COM link 65=USS on COM link + CB on COM link 66=CB on COM link + CB on COM link 67=Analog setpoint 2 + CB on COM link 70=No main setpoint + Analog setpoint 2
89/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Programming 01.2002
31=MOP setpoint + Fixed frequency 32=Analog setpoint + Fixed frequency 33=Fixed frequency + Fixed frequency 34=USS on BOP link + Fixed frequency 35=USS on COM link + Fixed frequency 36=CB on COM link + Fixed frequency 37=Analog setpoint 2 + Fixed frequency
71=MOP setpoint + Analog setpoint 2 72=Analog setpoint + Analog setpoint 2 73=Fixed frequency + Analog setpoint 2 74=USS on BOP link + Analog setpoint 2 75=USS on COM link + Analog setpoint 2 76=CB on COM link + Analog setpoint 2 77=Analog setpoint 2 + Analog setpoint 2
Index:
P1000[0] : 1st command data set (CDS) P1000[1] : 2nd command data set (CDS)
Note:
Single digits denote main setpoints that have no additional setpoint.
P1001 Fixed frequency 1
Defines fixed frequency setpoint 1.
Unit: Hz Min: -650.0 Def: 0.00 Max: 650.00
Level 3
There are 3 types of fixed frequencies:
1. Direct selection (P0701 - P0706=15) In this mode of operation 1 digital input selects 1 fixed frequency. If several inputs are active together, the selected frequencies are summed, e.g., FF1 + FF2 + FF3 + FF4 + FF5 + FF6.
2. Direct selection + ON command (P0701 - P0706=16) The fixed frequency selection combines the fixed frequencies with an ON command. In this mode of operation 1 digital input selects 1 fixed frequency. If several inputs are active together, the selected frequencies are summed, e.g., FF1 + FF2 + FF3 + FF4 + FF5 + FF6.
3. Binary coded selection + ON command (P0701 - P0706=17) Select up to 16 fixed frequencies using this method. Select the fixed frequencies according to the following table:
DIN4 DIN3 DIN2 DIN1
OFF Inactive Inactive Inactive Inactive
P1001 FF1 Inactive Inactive Inactive
Active
P1002 FF2 Inactive Inactive
Active
Inactive
P1003 FF3 Inactive Inactive
Active Active
P1004 FF4 Inactive
Active
Inactive Inactive
P1005 FF5 Inactive
Active
Inactive
Active
P1006 FF6 Inactive
Active Active
Inactive
P1007 FF7 Inactive
Active Active Active
P1008 FF8
Active
Inactive Inactive Inactive
P1009 FF9
Active
Inactive Inactive
Active
P1010 FF10
Active
Inactive
Active
Inactive
P1011 FF11
Active
Inactive
Active Active
P1012 FF12
Active Active
Inactive Inactive
P1013 FF13
Active Active
Inactive
Active
P1014 FF14
Active Active Active Active
Data:
P1015 FF15
Active Active Active Active
Dependency:
Select fixed frequency operation (using P1000). Variable speed drive requires ON command to start in the case of direct selection (P0701 to P0706=15).
Note:
Fixed frequencies can be selected using the digital inputs, and can also be combined with an ON command.
P1002-P1015 Fixed frequency 2 through 15
Defines fixed frequency setpoint 2.
Unit: Hz Min: -650.00 Def: See Note below Max: 650.00
Level 3
Details:
See P1001 (fixed frequency 1). Default fixed frequency setpoint values are as follows:
Fixed Frequency Default Fixed Frequency Default Fixed Frequency Default
1 0.00 6 25.00 11 50.00 2 5.00 7 30.00 12 55.00 3 10.00 8 35.00 13 60.00 4 15.00 9 40.00 14 65.00
Note:
5 20.00 10 45.00 15 65.00
P1016 to P1019
Fixed frequency mode - Bit 0 through 3
Fixed frequencies can be selected in three different modes. Parameter P1016 defines the mode of selection Bit 0.
Unit: - Min: 1 Def: 1 Max: 3
Level 3
Details:
Parameter P1016 defines the mode of Bit 0, Parameter P1017 defines the mode of Bit 1, Parameter P1018 defines the mode of Bit 2, and Parameter P1019 defines the mode of Bit 3.
Settings:
1=Direct selection 2=Direct selection + ON command 3=Binary coded selection + ON command
Note:
See table in P1001 (fixed frequency 1) for a description of how to use fixed frequencies.
P1020[2] to P1023[2]
BI: Fixed frequency selection Bit 0
Defines origin of fixed frequency selection.
Unit: - Min: 0:0 Def: 0:0 (P1023 = 722:3) Max: 4000:0
Level 3
Settings:
P1020= 722.0 ==> Digital input 1 P1021= 722.1 ==> Digital input 2
P1022= 722.2 ==> Digital input 3 P1023= 722.3 ==> Digital input 4
P1026= 722.4 ==> Digital input 5 P1028= 722.5 ==> Digital input 6
Index:
P1020[0] : 1st command data set (CDS) for Bit 0 P1021[0] : 1st command data set (CDS) for Bit 1 P1022[0] : 1st command data set (CDS) for Bit 2 P1023[0] : 1st command data set (CDS) for Bit 3
P1020[1] : 2nd command data set (CDS) for Bit 0 P1021[1] : 2nd command data set (CDS) for Bit 1 P1022[1] : 2nd command data set (CDS) for Bit 2 P1023[1] : 2nd command data set (CDS) for Bit 3
90/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Programming 01.2002
Dependency:
Accessible only if P0701 - P0706=99 (function of digital inputs=BICO)
r1024 CO: Act. fixed frequency Level 3
Displays sum total of selected fixed frequencies.
Unit: Hz Min: - Def: - M ax: -
P1025 Fixed frequency mode - Bit 4
Direct selection or direct selection + ON for bit 4.
Unit: - Min: 1 Def: 1 Max: 2
Level 3
Settings:
1=Direct selection 2=Direct selection + ON command 3=Binary coded selection + ON command
Details:
See parameter P1001 for description of how to use fixed frequencies.
P1026[2] BI: Fixed frequency selection Bit 4
Defines origin of fixed frequency selection.
Unit: - Min: 0:0 Def: 722:4 Max: 4000:0
Level 3
Index:
P1026[0] : 1st command data set (CDS) P1026[1] : 2nd command data set (CDS)
Dependency:
Accessible only if P0701 - P0706=99 (function of digital inputs=BICO).
Details:
See P1020 (fixed frequency selection Bit 0) for most common settings.
P1027 Fixed frequency mode - Bit 5
Direct selection or direct selection + ON for bit 5.
Unit: - Min: 1 Def: 1 Max: 2
Level 3
Settings:
1=Direct selection 2=Direct selection + ON command 3=Binary coded selection + ON command
Details:
See parameter P1001 for description of how to use fixed frequencies.
P1028[2] BI: Fixed frequency selection Bit 5
Defines origin of fixed frequency selection.
Unit: - Min: 0:0 Def: 722:5 Max: 4000:0
Level 3
Index:
P1028[0] : 1st command data set (CDS) P1028[1] : 2nd command data set (CDS)
Dependency:
Accessible only if P0701 - P0706=99 (function of digital inputs=BICO).
Details:
See P1020 (fixed frequency selection Bit 0) for most common settings.
P1031 Setpoint memory of the MOP
Saves last motor potentiometer setpoint (MOP) that was active before OFF command or power down.
Unit: - Min: 0 Def: 1 Max: 1
Level 3
Settings:
0=PID-MOP setpoint will not be stored 1=PID-MOP setpoint will be stored (P2240 is updated)
Note:
On next ON command, motor potentiometer setpoint will be the saved value in parameter P1040 (setpoint of the MOP).
P1032 Inhibit reverse direction of MOP
Inhibits reverse setpoint selection.
Unit: - Min: 0 Def: 1 Max: 1
Level 3
Settings:
0=Reserve direction is allowed 1=Reserve direction inhibited
Dependency:
Motor potentiometer (P1040) must be chosen as main setpoint or additional setpoint (using P1000).
Note:
It is possible to change motor direction using the motor potentiometer setpoint (increase / decrease frequency either by using digital inputs or BOP/AOP keypad up / down).
P1040 Setpoint of the MOP
Determines setpoint for motor potentiometer control (P1000 = 1).
Unit: Hz Min: -650.00 Def: 10.00 Max: 650.00
Level 2
Note:
If motor potentiometer setpoint is selected either as main setpoint or additional setpoint, the reverse direction will be inhibited by default of P1032 (inhibit reverse direction of MOP). To re-enable reverse direction, set P1032=0
r1050 CO: Act. Output frequency of the MOP
Display output frequency of motor potentiometer setpoint ([Hz]).
Unit: Hz Min: - Def: - M ax: -
Level 3
r1078 CO: Total frequency setpoint
Displays sum of main and additional setpoints in [Hz].
Unit: Hz Min: - Def: - M ax: -
Level 3
P1080 Min. Frequency
Sets minimum motor frequency [Hz] at which motor will run irrespective of frequency setpoint.
Unit: Hz Min: 0.00 Def: 10.00 Max: 650.00
Level 1
Note:
Value set here is valid both for clockwise and for counter-clockwise rotation. Under certain conditions (e.g. ramping, current limiting), motor can run below minimum frequency.
P1082 Max. Frequency
Sets maximum motor frequency [Hz] at which motor will run irrespective of the frequency setpoint.
Unit: Hz Min: 0.00 Def: 50.00 Max: 150.00
Level 1
Dependency:
Limited internally to 200 Hz or 5 * rated motor frequency (P0305) when P1300 >= 20 (control mode=vector control). The value is displayed in r0209 (maximum frequency).
Note:
The value set here is valid for both clockwise and counter-clockwise rotation. The maximum output frequency of variable speed drive can be exceeded if one of the following is active: Slip compensation=f
max
+ f
slip comp max
,or
Flying restart=f
max
+ f
slip nom
Maximum motor speed is subject to mechanical limitations.
91/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Programming 01.2002
P1091 to P1094
Skip frequency 1 through 4
Defines skip frequency 1 which avoids effects of mechanical resonance and suppresses frequencies within +/- P1101 (skip frequency bandwidth).
Unit: Hz Min: 0.00 Def: 0.00 Max: 650.00
Level 3
Details:
Defines the skip frequency which avoids effects of mechanical resonance and suppresses frequencies within +/- P1101 (skip frequency bandwidth). P1091 defines skip frequency 1, P1092 defines skip frequency 2, P1093 defines skip frequency 3, and P1094 defines skip frequency 4.
Note:
Stationary operation is not possible within the suppressed frequency range; the range is merely passed through (on the ramp). For example, if P1091=10 Hz and P1101=2 Hz, it is not possible to operate continuously between 10 Hz +/- 2 Hz (i.e. between 8 and 12 Hz)
P1101 Skip frequency bandwidth
Delivers frequency bandwidth to be applied to skip frequencies (in [Hz]).
Unit: Hz Min: 0.00 Def: 2.00 Max: 10.00
Level 3
Details:
Delivers frequency bandwidth to be applied to skip frequencies (in [Hz]).
Note:
See P1091 through P1094 (skip frequencies 1 through 4).
P1110[2] BI: Inhibit neg. freq. setpoint
Inhibits direction reversal, thus preventing a negative setpoint from causing motor from running in reverse. Instead, it will run at minimum frequency (P1080) in the normal direction.
Unit: - Min: 0:0 Def: 1:0 Max: 4000:0
Level 3
Details:
Inhibits direction reversal, thus preventing a negative setpoint from causing motor from running in reverse. Instead, it will run at minimum frequency (P1080) in the normal direction
Settings:
0=Disabled 1=Enabled
Index:
P1110[0] : 1st command data set (CDS) P1110[1] : 2nd command data set (CDS)
Note:
It is possible to disable all reverse commands (i.e. the command is ignored). To do this, set P0719=0 (remote selection of command/setpoint source) and define the command sources (P1113) individually. This function does not disable the "reverse" command function; rather, a reverse command causes motor to run in the normal direction as described above.
P1120 Ramp-up time
Time taken for motor to accelerate from standstill up to maximum motor frequency (P1082) when no rounding is used.
Unit: s Min: 0.00 Def: 10.00 Max: 650.00
Level 1
Details:
Setting the ramp-up time too short can cause the variable speed drive to trip (overcurrent). If an external frequency setpoint with set ramp rates is used (e.g. from a PLC), the best way to achieve optimum drive performance is to set ramp times in P1120 and P1121 slightly shorter than those of the PLC.
P1121 Ramp-down time Level 1
Time taken for motor to decelerate from maximum motor frequency (P1082) down to standstill when no rounding is used.
Unit: s Min: 0.00 Def: 30.00 Max: 650.00
Details:
Setting the ramp-down time too short can cause the variable speed drive to trip (overcurrent (F0001) / overvoltage (F0002)).
P1135 OFF3 ramp-down time
Defines ramp-down time from maximum frequency to standstill for OFF3 command.
Unit: s Min: 0.00 Def: 5.00 Max: 650.00
Level 3
Details:
Defines ramp-down time from maximum frequency to standstill for OFF3 command.
Note:
This time may be exceeded if the VDC_max. level is reached.
P1140[2] BI: RFG enable
Defines command source of RFG enable command (RFG: ramp function generator).
Unit: - Min: 0.00 Def: 1.0 Max: 4000.0
Level 3
Index:
. P1140[0] : 1st command data set (CDS)
P1140[1] : 2nd command data set (CDS)
P1141[2] BI: RFG start
Defines command source of RFG start command (RFG: ramp function generator).
Unit: - Min: 0.00 Def: 1.0 Max: 4000.0
Level 3
Index:
. P1141[0] : 1st command data set (CDS)
P1141[1] : 2nd command data set (CDS)
P1142[2] BI: RFG enable setpoint
Defines command source of RFG enable setpoint command (RFG: ramp function generator).
Unit: - Min: 0.00 Def: 1.0 Max: 4000.0
Level 3
Index:
. P1142[0] : 1st command data set (CDS)
P1142[1] : 2nd command data set (CDS)
P1200 Flying start
Starts variable speed drive onto a spinning motor by rapidly changing the output frequency of the variable speed drive until the actual motor speed has been found. Then, the motor runs up to setpoint using the normal ramp time.
Unit: - Min: 0 Def: 0 Max: 6
Level 3
Details:
Starts variable speed drive onto a spinning motor by rapidly changing the output frequency of the variable speed drive until the actual motor speed has been found. Then, the motor runs up to setpoint using the normal ramp time.
92/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Programming 01.2002
Settings:
0 =Flying start disabled 1 =Flying start is always active, start in direction of setpoint 2 =Flying start is active if power on, fault, OFF2, start in
direction of setpoint
3 =Flying start is active if fault, OFF2, start in direction of
setpoint
4 =Flying start is always active, only in direction of setpoint 5 =Flying start is active if power on, fault, OFF2, only in
direction of setpoint
6 =Flying start is active if fault, OFF2, only in direction of
setpoint
Note:
Useful for motors with high inertia loads. Settings 1 to 3 search in both directions. Settings 4 to 6 search only in direction of setpoint. Flying start must be used in cases where the motor may still be turning (e.g. after a short mains break) or can be driven by the load. Otherwise, overcurrent trips will occur
P1202 Motor-current: Flying start
Defines search current used for flying start.
Unit: % Min: 10 Def: 100 Max: 200
Level 3
Details:
Defines search current used for flying start. Value is in [%] based on rated motor current (P0305).
Note:
Reducing the search current may improve performance for flying start if the inertia of the system is not very high.
P1203 Search rate: Flying start
Sets factor by which the output frequency changes during flying start to synchronize with turning motor. This value is entered in [%] relative to the default time factor defines the initial gradient in the curve below (and thus influences the time taken to search for the motor frequency): fmax + 2 f slip
Unit: % Min: 10 Def: 100 Max: 200
Level 3
Details:
Sets factor by which output frequency changes during flying start to synchronize with turning motor. Enter this value in [%] relative to default time factor (which defines the initial gradient and influences time taken to search for motor frequency). The search time is the time taken to search through all possible frequencies (between [f_max+2*f_slip] and 0 Hz). P1203=100 % is defined as giving a rate of 2 % of f_slip,nom / [ms]. P1203=200 % would result in a rate of frequency change of 1 % of f_slip,nom / [ms].
Example:
For a motor with 50 Hz, 1350 rpm, 100 % would produce a maximum search time of 600 ms. If the motor is turning, the motor frequency is found in a shorter time.
Note:
A higher value produces a flatter gradient and thus a longer search time. A lower value has the opposite effect.
P1210 Automatic restart
Enables restart after a mains break or after a fault.
Unit: - Min: 0 Def: 1 Max: 5
Level 3
Settings:
0=Disabled 1 =Trip reset after power on: P1211 disabled 2 =Restart mains break; power on: P1211 disabled
3 =Restart after fault/mains break: P1211 enabled 4 =Restart after mains break: P1211 enabled 5 =Restart mains break/fault/power on: P1211 disabled
Dependency:
Auto restart requires constant ON command (e.g. via a digital input wire link).
Caution:
Settings 2 to 5 can cause the motor to restart unexpectedly
Note:
Flying start must be used in cases where the motor may still be turning (e.g. after a short mains break) or can be driven by the load (P1200).
P1211 Number of restart attempts
Specifies number of times the variable speed drive will attempt to restart if P1210 (flying start) is activated.
Unit: - Min: 0 Def: 3 Max: 10
Level 3
P1212 Time to first restart
Selects the time before the variable speed drive is restarted for the first time if P1210 is activated.
Unit: s Min: 0 Def: 30 Max: 1000
Level 3
P1213 Restart time increment
Selects the amount the restart time is increment for each restart of the variable speed drive if P1210 is activated.
Unit: s Min: 0 Def: 30 Max: 1000
Level 3
P1230[2] BI: Enable DC braking
Enables DC braking via a signal applied from an external source. Function remains active while external input signal is active. DC braking causes the motor to s top rapidly by applying a DC braking current (current applied also holds shaft s t ationary). When the DC braking signal is applied, the variable speed dri ve output pulses are blocked and the DC current is not applied until the motor has been sufficiently demagnetized.
Unit: - Min: 0:0 Def: 0:0 Max: 4000:0
Level 3
Details:
Enables DC braking via a signal applied from an external source. Function remains active while external input s ignal is active. DC braking causes the motor to s top rapidly by applying a DC braking current (current applied also holds shaft stationary). When the DC braking signal is applied, the variabl e speed drive output pulses are blocked and the DC current is not applied until the motor has been sufficiently demagnetized.
Settings:
722.0=Digital input 1 (requires P0701 set to 99, BICO)
722.1=Digital input 2 (requires P0702 set to 99, BICO)
722.2=Digital input 3 (requires P0703 set to 99, BICO)
722.3=Digital input 4 (requires P0704 set to 99, BICO)
722.4=Digital input 5 (requires P0705 set to 99, BICO)
93/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Programming 01.2002
722.5=Digital input 6 (requires P0706 set to 99, BICO)
722.6=Digital input 7 (via analog input 1, requires P0707 set to 99)
722.7=Digital input 8 (via analog input 2, requires P0708 set to 99)
Index:
P1230[0] : 1st command data set (CDS) P1230[1] : 2nd command data set (CDS)
Caution2:
Frequent use of long periods of DC braking can cause the motor to overheat.
Note:
This delay time is set in P0347 (demagnetization time). If this delay is too short, overcurrent trips can occur.
P1232 DC braking current
Defines the level of DC current in [%] relative to the rated motor current (P0305).
Unit: % Min: 0 Def: 100 Max: 250
Level 3
P1233 Duration of DC braking
Defines duration for which DC injection braking is to be active following an OFF1 command.
Unit: s Min: 0 Def: 0 Max: 250
Level 3
Value:
P1233=0 : Not active following OFF1. P1233=1 - 250 : Active for the specified duration.
Caution
Frequent use of long periods of DC braking can cause the motor to overheat.
Note:
The DC braking function causes the motor to stop rapidly by applying a DC braking current (the current applied also holds the shaft stationary). When the DC braking signal is applied, the variable speed drive output pulses are blocked and the DC current not applied until the motor has been sufficiently demagnetized (demagnetization time is calculated automatically from motor data).
P1236 Compound braking current
Defines DC level superimposed on AC waveform. The value is entered in [%] relative to rated motor current (P0305)..
Unit: % Min: 0 Def: 0 Max: 250
Level 3
Value:
P1236=0 : Compound braking disabled. P1236=1 - 250 : Level of DC braking current defined as a [%] of rated motor current (P0305).
Dependency:
Active after OFF1 / OFF3 command.
Note:
Increasing the value will generally improve braking performance; however, if you set the value too high, an overcurrent trip may result.
P1240 Configuration of Vdc controller
Enables / disables Vdc controller.
Unit: - Min: 0 Def: 0 Max: 3
Level 3
Details:
The Vdc controller dynamically controls the DC link voltage to prevent overvoltage trips on high inertia systems.
Settings:
0 =Vdc controller disabled 1 =Vdc-max controller enabled
2 =Vdc-min controller (Kinetic buffering) enabled 3 =Vdc-max and Vdc-min controller enabled
Note:
Vdc max automatically increases ramp-down times to keep the DC-link voltage (r0026) within limits (P2172) Vdc min is activated if DC-link voltage falls below minimum level. The kinetic energy of the motor is then used to buffer the DC-link voltage, thus causing deceleration of the drive.
P1260 Source of changeover control
Selects the possible sources for contactor changeover control
Unit: - Min: 0 Def: 0 Max: 7
Level 2
Settings:
0 Bypass disabled 1 Controlled by variable speed drive trip 2 Controlled by DIN - see P1266 3 Controlled by DIN & variable speed drive trip 4 Controlled by variable speed drive frequency 5 Controlled by variable speed drive frequency & variable speed drive trip 6 Controlled by variable speed drive frequency & DIN 7 Controlled by variable speed drive frequency & DIN & variable speed drive trip
r1261 BO: Contactor control word
Output word from the bypass feature that allows external connections to be made.
Unit: - Min: - Def: - Max: -
Level 2
Bit fields:
Bit00 Motor supplied by drive 0 YES, 1 NO Bit01 Motor supplied by mains 0 YES, 1 NO
P1262 Bypass dead time
Time delay between switching contactors to allow motor to allow motor to demagnetize.
Unit: s Min: 0 Def: 1.000 Max: 20.000
Level 2
P1263 De-Bypass time
Time delay before a request to switch back to the variable speed drive is acted on.
Unit: s Min: 0 Def: 1.0 Max: 300.0
Level 2
P1264 Bypass time
Time delay before a request to switch to mains is acted on.
Unit: s Min: 0 Def: 1.0 Max: 300.0
Level 2
P1265 Mains frequency
Mains frequency.
Unit: Hz Min: 12.00 Def: 50.00 Max: 650.00
Level 2
P1266 BI: Bypass command
Mains frequency.
Unit: - Min: 0:0 Def: 0:0 Max: 4000:0
Level 2
94/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Programming 01.2002
P1270[2] BI: Enable essential service
Unit: - Min: 0:0 Def: 0:0 Max: 4000:0
Level 3
P1300 Control mode
Controls relationship between speed of motor and voltage supplied by the variable speed drive as illustrated in the diagram below
Unit: - Min: 0 Def: 1 Max: 23
Level 3
Details:
Controls relationship between speed of motor and voltage supplied by variable speed drive.
Settings:
0 =V/f with linear charac. 1=V/fwithFCC 2 =V/f with parabolic charac. 3 =V/f with programmable charac.
4 =V/f with ECO mode 5 =V/f for textile applications 6 =V/f with FCC for textile applications 19 =V/f control with independent
voltage setpoint
20 =not used 21 =not used 22 =not used 23 =not used
Dependency:
The value is displayed in r0209 (maximum frequency).
Note:
P1300=1 : V/f with FCC * Maintains motor flux current for improved efficiency * If FCC is chosen, linear V/f is active at low frequencies. P1300=2 : V/f with a quadratic curve * Suitable for centrifugal fans / pumps
P1310 Continuous boost
Defines the boost level in [%] relative to P0305 (rated motor current) applicable to both linear and quadratic V/f curves according to the diagram below:
Unit: % Min: 0.0 Def: 50.0 Max: 250.0
Level 3
Details:
Defines boost level in [%] relative to P0305 (rated motor current) applicable to both linear and quadratic V/f curves.
Dependency:
Setting in P0640 (motor overload factor [%]) limits the boost.
Note:
The boost values are combined when continuous boost (P1310) used in conjunction with other boost parameters (acceleration boost P1311 and starting boost P1312). However priorities are allocated to these parameters as follows: P1310 > P1311 > P1312 Increasing the boost levels increases motor heating (especially at standstill).
P1311 Acceleration boost
Applies boost in [%] relative to P0305 (rated motor current) following a positive setpoint change and drops back out once the setpoint is reached.
Unit: % Min: 0.0 Def: 0.0 Max: 250.0
Level 3
Details:
Applies boost in [%] relative to P0305 (rated motor current) following a positive setpoint change and drops back out once the setpoint is reached.
Dependency:
Setting in P0640 (motor overload factor [%]) limits boost.
Note:
Acceleration boost can help to improve response to small positive setpoint changes.
P1312 Starting boost
Applies a constant linear offset (in [%] relative to P0305 (rated motor current)) to active V/f curve (either linear or quadratic) after an ON command and is active until setpoint is reached for the first time. This is useful for starting loads with high inertia.
Unit: % Min: 0.0 Def: 0.0 Max: 250.0
Level 3
Details:
Applies a constant linear offset (in [%] relative to P0305 (rated motor current)) to active V/f curve (either linear or quadratic) after an ON command and is active until setpoint is reached for the first time. This is useful for starting loads with high inertia. Setting the starting boost (P1312) too high will cause the variable speed drive to limit the current, which will in turn restrict the output frequency to below the setpoint frequency.
Dependency:
Setting in P0640 (motor overload factor [%]) limits boost.
Note:
Increasing the boost levels increases motor heating.
Σ
Boosts = 300 / l
mot*Rs Priorities are allocated to the boost parameters as follows: P1310 > P1311 > P1312
P1335 Slip compensation
Dynamically adjusts output frequency of variable speed drive so that motor speed is kept constant independent of motor load.
Unit: % Min: 0.0 Def: 0.0 Max: 600.0
Level 3
Details:
Dynamically adjusts output frequency of variable speed drive so that motor speed is kept constant independent of motor load.
Value:
P1335= 0 % : Slip compensation disabled.
P1335=100 % : This uses the motor data and motor model to add the rated slip frequency rated motor speed and rated
motor current.
Note:
Gain adjustment enables fine-tuning of the actual motor speed (see P1460 - gain speed control). 100%=standard setting for warm stator
P1336 Slip limit
Compensation slip limit in [%] relative to r0330 (rated motor slip), which is added to frequency setpoint.
Unit: % Min: 0 Def: 250 Max: 600
Level 3
Details:
Compensation slip limit in [%] relative to r0330 (rated motor slip), which is added to frequency setpoint.
Dependency:
Slip compensation (P1335) active.
r1337 CO: V/f slip frequency
Displays actual compensated motor slip as [%]
Unit: % Min: - Def: - Max: -
Level 3
95/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Programming 01.2002
Details:
Displays actual compensated motor slip as [%
Dependency:
Slip compensation (P1335) active.
P1499 Scaling acceleration torque control
Enters scaling of acceleration in [%] for sensorless torque control (SLVC) at low frequencies.
Unit: % Min: 0.0 Def: 100.0 Max: 400.0
Level 3
Details:
Enters scaling of acceleration in [%] for sensorless torque control (SLVC) at low frequencies.
P1800 Pulse frequency
Sets pulse frequency of power switches in the variable speed drive. The frequency can be changed in steps of 2 kHz. Pulse frequencies > 4 kHz selected on 380-480 V units reduce the maximum continuous motor current.
Unit: kHz Min: 2 Def: 4 Max: 16
Level 2
Details:
Sets pulse frequency of power switches in variable speed drive. The frequency can be changed in steps of 2 kHz. Pulse frequencies > 4 kHz selected on 380-480 V units reduce the maximum continuous motor current.
Dependency:
Minimum pulse frequency depends on P1082 (maximum frequency) and P0310 (rated motor frequency).
Note:
At 4 kHz, full output current is obtained up to 50 degrees C (CT mode);over 50 degrees C, full output may be obtained at 8kHz. If silent operation is not absolutely necessary, lower pulse frequencies may be selected to reduce variable speed drive losses and radio-frequency emissions. Under certain circumstances, the variable speed drive may reduce the switching frequency to provide protection against over-temperature (see P0290, Level 3).
r1801 CO: Act. switching frequency
Actual pulse frequency of power switches in variable speed drive.
Unit: kHz Min: - Def: - Max: -
Level 3
Note:
Actual pulse frequency of power switches in variable speed drive. Under certain conditions (variable speed drive overtemperature, see P0290), this can differ from the values selected in P1800 (pulse frequency).
P1820 Reverse output phase sequence
Changes direction of motor rotation without changing setpoint polarity.
Unit: - Min: 0 Def: 0 Max: 1
Level 3
Settings:
0=OFF 1=ON
Dependency:
If positive and negative revolution is enabled, frequency setpoint is directly used. If both positive and negative revolution are disabled, reference value is set to zero.
Details:
See P1000 (select frequency setpoint).
P1910 Select motor data identification
Performs stator resistance measuring.
Unit: - Min: 0 Def: 0 Max: 20
Level 3
Settings:
0=Disabled 1=Identification of all parameters with parameter change
2=Identification of all parameters without parameter change 20=Set voltage vector
Dependency:
N o measurement if motor data incorrect. P1910=1 : Calculated value for stator resistance (see P0350) is overwritten. P1910=2 : Values already calculated are not overwritten.
Note:
Before selecting motor data identification, "Quick commissioning" has to be performed in advance. Once enabled (P1910=1), A0541 generates a warning that the next ON command will initiate measurement of motor parameters. When choosing the setting for measurement, observe the following:
1. "With parameter change" means that the value is actually adopted as P0350 parameter setting and applied to the control as well as being shown in the read-only parameters below.
2. "Without parameter change" means that the value is only displayed, i.e. shown for checking purposes in the read­only parameter r1912 (identified stator resistance). The value is not applied to the control.
r1912[3] Identified stator resistance
Displays measured stator resistance value (line-to-line) in [ohm].
Unit: Ohm Min: - Def: - Max: -
Level 3
Index:
r1912[0] : U_phase r1912[1] : V_phase r1912[2] : W_phase
Note:
This value is measured using P1910=1 or 2 , i.e., identification of all parameters with/without change.
P2000 Reference frequency
Full-scale frequency setting used by serial link (corresponds to 4000H), analog I/O and P/D controller.
Unit: Hz Min: 1.00 Def: 50.00 Max: 650.00
Level 2
P2001 Reference voltage
Full-scale output voltage (i.e. 100 % ) used over serial link (corresponds to 4000H).
Unit: V Min: 10 Def: 1000 Max: 2000
Level 3
Example:
P0201=230 specifies that 4000H received via USS denotes 230 V.
P2002 Reference current
Full-scale output current used over serial link (corresponds to 4000H).
Unit: A Min: 0.10 Def: 0.10 Max: 10000.00
Level 3
r2004 Reference power
Full-scale reference power used over the serial link (corresponds to 4000H).
Unit: - Min: - Def: - Max: -
Level 3
96/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Programming 01.2002
P2009[2] USS normalization
Min: 0 Def: 0 Max: 1
Level 3
Settings:
0=Disabled 1=Enabled
Index:
P2009[0] : Serial interface COM link P2009[1] : Serial interface BOP link
Note:
If enabled, the main setpoint (word 2 in PZD) is not interpreted as 100 %=4000H, but as "absolute" instead (e.g. 4000H=16384 means 163.84 Hz ).
P2010[2] USS baudrate
Sets baud rate for USS communication.
Unit: - Min: 4 Def: 6 Max: 12
Level 3
Settings:
4= 2400 baud 5= 4800 baud 6= 9600 baud
7= 19200 baud 8= 38400 baud
9= 57600 baud 10=76800 baud
11= 93750 baud 12= 115200 baud
Index:
P2010[0] : Serial interface COM link P2010[1] : Serial interface BOP link
P2011[2] USS address
Sets a unique address for variable speed drive.
Unit: - Min: 0 Def: 0 Max: 31
Level 3
Index:
P2011[0] : Serial interface COM link P2011[1] : Serial interface BOP link
Note:
You can connect up to a further 30 variable speed drives via the serial link (i.e. 31 variable speed drives in total) and control them with the USS serial bus protocol.
P2014[2] USS telegram off time
Defines a time T_off after which a fault will be generated (F0070) if no telegram is received via the USS channels.
Unit: ms Min: 0 Def: 0 Max: 65535
Level 3
Index:
P2014[0] : Serial interface COM link P2014[1] : Serial interface BOP link
Note:
By default (time set to 0), no fault is generated (i.e. watchdog disabled).
P2040 CB telegram off time
Defines time after which a fault will be generated (F0070) if no telegram is received via the link (SOL).
Unit: ms Min: 0 Def: 20 Max: 65535
Level 3
Dependency:
Setting 0=watchdog disabled
P2041[5] CB parameter
Configures a communication board (CB).
Unit: - Min: 0 Def: 0 Max: 65535
Level 3
Index:
P2041[0] : CB parameter 0 P2041[1] : CB parameter 1
P2041[2] : CB parameter 2 P2041[3] : CB parameter 3
P2041[4] : CB parameter 4
Note:
See relevant communication board manual for protocol definition and appropriate settings
r2050[8] CO: PZD from CB
Displays PZD received from communication board (CB).
Unit: - Min: - Def: - Max: -
Level 3
Index:
r2050[0] : Received word 0 r2050[1] : Received word 1 r2050[2] : Received word 2
r2050[3] : Received word 3 r2050[4] : Received word 4 r2050[5] : Received word 5
r2050[6] : Received word 6 r2050[7] : Received word 7
Note:
The control words can be viewed as bit parameters r2032 and r2033.
P2051[8] CI: PZD to CB
Connects PZD to CB. This parameter allows the user to define the source of status words and actual values for the reply PZD.
Unit: - Min: 0:0 Def: 52:0 Max: 4000:0
Level 3
Settings:
Status word 1=52 CO/BO: Act. status word 1 (see r0052) Actual value 1= 21 variable speed drive output frequency (see r0021) Other BICO settings are possible
Index:
P2051[0] : Transmitted word 0 P2051[1] : Transmitted word 1 P2051[2] : Transmitted word 2
P2051[3] : Transmitted word 3 P2051[4] : Transmitted word 4 P2051[5] : Transmitted word 5
P2051[6] : Transmitted word 6 P2051[7] : Transmitted word 7
r2053[5] CB identification
Displays identification data of the communication board (CB). The different CB types (r2053[0]) are given in the Enum declaration.
Unit: - Min: - Def: - Max: -
Level 3
Settings:
0=No CB option board 1=PROFIBUS DP
2=DeviceNet 56 not defined
Index:
r2053[0] : CB type (PROFIBUS=1) r2053[1] : Firmware version r2053[2] : Firmware version detail
r2053[3] : Firmware date (year) r2053[4] : Firmware date (day/month)
r2054[7] CB diagnosis
Displays diagnostic information of communication board (CB).
Unit: - Min: - Def: - Max: -
Level 3
Index:
r2054[0] : CB diagnosis 0 r2054[1] : CB diagnosis 1 r2054[2] : CB diagnosis 2
r2054[3] : CB diagnosis 3 r2054[4] : CB diagnosis 4
r2054[5] : CB diagnosis 5 r2054[6] : CB diagnosis 6
97/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Programming 01.2002
P2100[3] Alarm number selection
Selects up to 3 faults or warnings for non-default reactions.
Unit: - Min: 0 Def: 0 Max: 65535
Level 3
Example:
If you want F0005 to perform an OFF3 instead of an OFF2, set P2100[0]=5, then select the desired reaction in P2101[0] (in this case, set P2101[0]=3).
Note:
All fault codes have a default reaction to OFF2. Some fault codes caused by hardware trips (e.g. overcurrent) cannot be changed from the default reactions.
P2101[3] Stop reaction value
Sets drive stop reaction values for fault selected by P2100 (alarm number stop reaction). This indexed parameter specifies the special reaction to the faults/warnings defined in P2100 indices 0 to 2.
Unit: - Min: 0 Def: 0 Max: 5
Level 3
Details:
Sets drive stop reaction values for fault selected by P2100 (alarm number stop reaction). This indexed parameter specifies the special reaction to the faults/warnings defined in P2100 indices 0 to 2.
Settings:
0=No reaction, no display 1=OFF1 stop reaction
2=OFF2 stop reaction 3=OFF3 stop reaction
4=No reaction warning only 5=Goto fixed frequency 15
Note:
Settings 0 - 3 only are available for fault codes. Settings 0 and 4 only are available for warnings. Index 0 (P2101) refers to fault/warning in index 0 (P2100).
r2110[4] Warning number
Displays warning information.
Unit: - Min: - Def: - Max: -
Level 3
Details
Displays warning information. A maximum of 2 active warnings (indices 0 and 1) and 2 historical warnings (indices 2 and 3) may be viewed.
Index:
r2110[0] : Recent Warnings --, warning 1 r2110[1] : Recent Warnings --, warning 2
r2110[2] : Recent Warnings -1, warning 3 r2110[3] : Recent Warnings -1, warning 4
Note:
The keypad will flash while a warning is active. The LEDs indicate the warning status in this case. If an AOP is in use, the display will show number and text of the active warning. Indices 0 and 1 are not stored.
P2111 Total number of warnings
Displays number of warning (up to 4) since last reset. Set to 0 to reset the warning history.
Unit: - Min: 0 Def: 0 Max: 4
Level 3
Details:
Displays number of warning (up to 4) since last reset. Set to 0 to reset the warning history.
r2114[2] Run time counter
Displays run time counter. It is the total time the drive has been powered up. Every time you do power cycle, it will save the value then restore it and the counter carries on ticking.
Unit: - Min: - Def: - Max: -
Level 3
Details:
Displays run time counter. See P0948 (fault time).
P2115[3] AOP real time clock
Displays AOP real time.
Unit: - Min: 0 Def: 0 Max: 65535
Level 3
Details:
Displays run time counter. See P0948 (fault time).
P2181 Belt failure detection mode
Sets belt failure detection mode. This function allows detection of mechanical failure of the drive train, e.g. a broken drive belt. It can also detect conditions which cause an overload, such as a jam.
Unit: - Min: 0 Def: 0 Max: 6
Level 3
Details:
Sets belt failure detection mode. This function allows detection of mechanical failure of the drive train, e.g. a broken drive belt. It can also detect conditions which cause an overload, such as a jam.
Settings:
0=Belt failure detection disabled 1=Warn low torque/speed 2=Warn high torque/speed
3=Warn high/low torque/speed 4=Trip low torque/speed
5=Trip high torque/speed 6=Trip high/low torque/speed
P2182 Belt threshold frequency 1
Sets a frequency threshold 1 for comparing actual torque to torque the envelope for belt failure detection.
Unit: Hz Min: 0.00 Def: 5.00 Max: 650.00
Level 3
Details:
Sets a frequency threshold F1 for comparing actual torque to torque the envelope for belt failure detection. The frequency torque envelope is defined by 9 parameters - 3 are frequency parameters (P2182 - P2184), and the other 6 define the low and high torque limits (P2185 - P2190) for each frequency.
Note:
The torque is unlimited below P2182, and above P2184. Normally P2182 <= lower torque limit (P1521), and P2184 >=upper torque limit (P1520).
P2183 Belt threshold frequency 2
Sets a threshold F2 for comparing actual torque to torque the envelope for belt failure detection.
Unit: Hz Min: 0.00 Def: 30.00 Max: 650.00
Level 3
Details:
Sets a threshold F2 for comparing actual torque to torque the envelope for belt failure detection.
Note:
See P2182 (belt threshold frequency 1).
P2184 Belt threshold frequency 3
Sets a threshold F3 for comparing actual torque to torque the envelope for belt failure detection.
Level 3
98/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Programming 01.2002
Unit: Hz Min: 0.00 Def: 50.00 Max: 650.00
Details:
Sets a threshold F3 for comparing actual torque to torque the envelope for belt failure detection.
Note:
See P2182 (belt threshold frequency 1).
P2185, P2187, P2189
Upper torque threshold 1, 2, and 3
Upper limit threshold value 1 for comparing actual torque.
Unit: Nm Min: 0.0 Def: 99999.0 Max: 99999.0
Level 3
Details:
Upper limit threshold value for comparing actual torque.
Note:
See P2182 (belt threshold frequency).
P2186, P2188, P2190
Lower torque threshold 1, 2, and 3
Lower limit threshold value 1 for comparing actual torque.
Unit: Nm Min: 0.0 Def: 0.0 Max: 99999.0
Level 3
Details:
Lower limit threshold value for comparing actual torque.
Note:
See P2182 (belt threshold frequency).
P2191 Belt failure speed tolerance
P2191 defines the allowed speed variation bandwidth between the variable speed drive frequency, and the speed reference from the pulse train. When the speed of the driven machine varies by more than this amount, a trip or warning is given.
Unit: Hz Min: 0.00 Def: 3.00 Max: 20.00
Level 3
Details:
P2191 defines the allowed speed variation bandwidth between the variable speed drive frequency, and the speed reference from the pulse train. When the speed of the driven machine varies by more than this amount, a trip or warning is given.
P2192 Time delay for belt failure
P2192 defines a delay before warning/trip becomes active. It is used to eliminate events caused by transient conditions. It is used for both methods of fault detection.
Unit: s Min: 0 Def: 10 Max: 65
Level 3
Details:
P2192 defines a delay before warning/trip becomes active. It is used to eliminate events caused by transient conditions. It is used for both methods of fault detection.
r2197 CO/BO: Monitoring word 1
Monitoring word 1 which indicates the state of monitor functions. Each bit represents one monitor function.
Unit: - Min: - Def: - Max: -
Level 3
Bit fields:
Bit00 Act. freq. r0024 <= P1080 0 NO, 1 YES Bit01 Act. freq. r0024 <= P2155 0 NO, 1 YES Bit02 Act. freq. r0024 > P2155 0 NO, 1 YES Bit03 Act. freq. r0024 > zero 0 NO, 1 YES Bit04 Act. freq. r0024 >= setp. 0 NO, 1 YES Bit05 Act. freq. r0024 <= P2167 0 NO, 1 YES Bit06 Act. freq. r0024 >= P1082 0 NO, 1 YES Bit07 Act. freq. r0024 == setp. 0 NO, 1 YES Bit08 Act. current r0068 >= P2170 0 NO, 1 YES Bit09 Act. unfilt. Vdc < P2172 0 NO, 1 YES Bit10 Act. unfilt. Vdc > P2172 0 NO, 1 YES Bit11 No load condition 0 NO, 1 YES
r2198 CO/BO: Monitoring word 2
Monitoring word 2 which indicates the state of monitor functions. Each bit represents one monitor function.
Unit: - Min: - Def: - Max: -
Level 3
Bit fields:
Bit00 | n,filtered r2169 | < P2157 0 NO, 1 YES Bit01 | n,filtered r2169 | > P2157 0 NO, 1 YES Bit02 | n,filtered r2169 | < P2159 0 NO, 1 YES Bit03 | n,filtered r2169 | > P2159 0 NO, 1 YES Bit04 | n,set | < P2161 0 NO, 1 YES Bit05 n,set > 0 0 NO, 1 YES Bit06 Motor blocked 0 NO, 1 YES Bit07 Motor stalled 0 NO, 1 YES Bit08 | I,act r0068 | < P2170 0 NO, 1 YES Bit09 |T,act| > P2174 & setpoint reached 0 NO, 1 YES Bit10 | T,act | > P2174 0 NO, 1 YES Bit11 Belt failure warning 0 NO, 1 YES Bit12 Belt failure trip 0 NO, 1 YES
P2200[2] BI: Enable PID controller
The PID mode allows the user to enable/disable the PID controller. Setting to 1 enables the PID closed-loop controller.
Unit: - Min: 0:0 Def: 0:0 Max: 4000:0
Level 2
Details:
PID mode Allows user to enable/disable the PID controller. Setting to 1 enables the PID closed-loop controller.
Index:
P2200[0] : 1st command data set (CDS) P2200[1] : 2nd command data set (CDS)
Dependency:
Setting 1 automatically disables normal ramp times set in P1120 and P1121 and the normal frequency setpoints. Following an OFF1 or OFF3 command, however, the variable speed drive frequency will ramp down to zero using the ramp time set in P1121 (P1135 for OFF3).
99/126
Siemens Building Technologies SED2 variable speed drives CM1U5192en HVAC Products Programming 01.2002
Note:
The PID setpoint source is selected using P2253. The PID setpoint and the PID feedback signal are interpreted as [%] values (not [Hz]). The output of the PID controller is displayed as [%] and then normalized into [Hz] through P2000 (reference frequency) when PID is enabled. In level 3, the PID controller source enable can also come from the digital inputs in settings 722.0 to 722.2 for DIN1 to DIN3 or from any other BiCo source. The minimum and maximum motor frequencies (P1080 and P1082) as well as the skip frequencies (P1091 to P1094) remain active on the variable speed drive output. However, enabling skip frequencies with PID control can produce instabilities.
P2201 through P2215
Fixed PID setpoint 1 through 15
Defines fixed PID setpoint 1
Unit: % Min: -200.00 Def: See Note Below Max: 200.00
Level 3
Defines fixed PID setpoint 1. In addition, you can set any of the digital input parameters to fixed PID setpoint via the digital inputs (P0701 - P0706). There are three selection modes for the PID fixed setpoint:
1. Direct selection (P0701=15 or P0702=15, etc) In this mode of operation, 1 digital input selects one PID fixed setpoint.
2. Direct selection with ON command (P0701=16 or P0702=16, etc.) Description as for 1), except that this type of selection issues an ON command concurrent with any setpoint selection.
3. Binary Coded Decimal selection with ON command (P0701 - P0706=17) Using this method to select the PID Fixed Setpoint allows you to choose up to 16 different PID setpoints. The setpoints are selected according to the following table:
DIN4 DIN3 DIN2 DIN1
OFF Inactive Inactive Inactive Inactive
P2201 FF1 Inactive Inactive Inactive
Active
P2202 FF2 Inactive Inactive
Active
Inactive
P2203 FF3 Inactive Inactive
Active Active
P2204 FF4 Inactive
Active
Inactive Inactive
P2205 FF5 Inactive
Active
Inactive
Active
P2206 FF6 Inactive
Active Active
Inactive
P2207 FF7 Inactive
Active Active Active
P2208 FF8
Active
Inactive Inactive Inactive
P2209 FF9
Active
Inactive Inactive
Active
P2210 FF10
Active
Inactive
Active
Inactive
P2211 FF11
Active
Inactive
Active Active
P2212 FF12
Active Active
Inactive Inactive
P2213 FF13
Active Active
Inactive
Active
P2214 FF14
Active Active Active Active
Details:
P2215 FF15
Active Active Active Active
Dependency:
P2000=1 required in user access level 2 to enable setpoint source. In mode 1 (above): ON command required to start motor (enable pulses). In mode 2 (above): If inputs programmed to PID fixed setpoint and selected together, the selected setpoints are summed. You may mix different types of frequencies; however, remember that they will be summed if selected together. P2201=100 % corresponds to 4000 hex.
Default fixed PID setpoint values are as follows: Fixed PID Default Fixed PID Default Fixed PID Default
1 0.00 6 50.00 11 100.00 2 10.00 7 60.00 12 110.00 3 20.00 8 70.00 13 120.00 4 30.00 9 80.00 14 130.00
Note:
5 40.00 10 90.00 15 130.00
P2216, P2217, P2218, P2219
Fixed PID setpoint mode - Bit 0, Bit 1, Bit 2, and Bit 3
Fixed frequencies for PID setpoint can be selected in three different modes. Parameter P1016 defines the mode of selection bit 0.
Unit: - Min: 1 Def: 1 Max: 3
Level 3
Settings:
1=Direct selection 2=Direct selection + ON command 3=Binary coded selection + ON command
P2220[2] BI: Fixed PID setpoint select Bit 0
Defines command source of fixed PID setpoint selection bit 0.
Unit: - Min: 0:0 Def: 0:0 Max: 4000:0
Level 3
Settings:
722.0=Digital input 1 (requires P0701 set to 99, BICO)
722.1=Digital input 2 (requires P0702 set to 99, BICO)
722.2=Digital input 3 (requires P0703 set to 99, BICO)
722.3=Digital input 4 (requires P0704 set to 99, BICO)
722.4=Digital input 5 (requires P0705 set to 99, BICO)
722.5=Digital input 6 (requires P0706 set to 99, BICO)
722.6=Digital input 7 (via analog input 1, requires P0707 set to 99)
722.7=Digital input 8 (via analog input 2, requires P0708 set to 99)
Index:
P2220[0] : 1st command data set (CDS) P2220[1] : 2nd command data set (CDS)
100/126 Siemens Building Technologies SED2 variable speed drives CM1U5192en
HVAC Products Programming 01.2002
P2221[2]. P2222[2], P2223[2]
BI: Fixed PID setpoint select Bit 1, Bit 2, and Bit 3
Defines command source of fixed PID setpoint selection bit 1.
Unit: - Min: 0:0 Def: 0:0 (P2223[2]:722.3 Max: 4000:0
Level 3
Settings:
722.0=Digital input 1 (requires P0701 set to 99, BICO)
722.1=Digital input 2 (requires P0702 set to 99, BICO)
722.2=Digital input 3 (requires P0703 set to 99, BICO)
722.3=Digital input 4 (requires P0704 set to 99, BICO)
722.4=Digital input 5 (requires P0705 set to 99, BICO)
722.5=Digital input 6 (requires P0706 set to 99, BICO)
For P2221: For P2222: For P2223:
Index:
P2221[0]: 1st command data set (CDS) P2221[1]: 2nd command data set (CDS)
P2222[0]: 1st command data set (CDS) P2222[1]: 2nd command data set (CDS)
P2223[0]: 1st command data set (CDS) P2223[1]: 2nd command data set (CDS)
r2224 CO: Act. fixed PID setpoint
Displays total output of PID fixed setpoint selection.
Unit: % Min: - Def: - Max: -
Level 3
Note:
r2224=100 % corresponds to 4000 hex.
P2225, P2227 Fixed PID setpoint mode - Bit 4 and Bit 5
Direct selection or direct selection + ON Bit 4 for PID setpoint.
Unit: - Min: 1 Def: 1 Max: 2
Level 3
Settings:
1=Direct selection 2=Direct selection + ON command 3=Binary coded selection + ON command
P2226[2]­P2228[2]
BI: Fixed PID setpoint select Bit 4 and Bit 5
P2226[2] Min: 0:0 Def: 722:4 Max: 4000:0 P2227 Min: 1 Def: 1 Max: 2 P2228[2] Min: 0 Def: 722:5 Max: 4000:0
Level 3
Settings:
722.0=Digital input 1 (requires P0701 set to 99, BICO)
722.1=Digital input 2 (requires P0702 set to 99, BICO)
722.2=Digital input 3 (requires P0703 set to 99, BICO)
722.3=Digital input 4 (requires P0704 set to 99, BICO)
722.4=Digital input 5 (requires P0705 set to 99, BICO)
722.5=Digital input 6 (requires P0706 set to 99, BICO)
For P2226: For P2228:
Index:
P2226[0]: 1st command data set (CDS) P2226[1]: 2nd command data set (CDS)
P2228[0]: 1st command data set (CDS) P2228[1]: 2nd command data set (CDS)
P2231 Setpoint memory of PID-MOP
Setpoint memory.
Unit: - Min: 0 Def: 1 Max: 1
Level 3
Settings:
0=PID-MOP setpoint will not be stored 1=PID-MOP setpoint will be stored (P2240 is updated)
Dependency:
If 0 selected, setpoint returns to value set in P2240 (setpoint of PID-MOP) after an OFF command If 1 is selected, active setpoint is 'remembered' and P2240 updated with current value.
Note:
See P2240 (setpoint of PID-MOP).
P2232 Inhibit rev. direct. of PID-MOP
Inhibits reverse setpoint selection when PID motor potentiometer is chosen either as a main setpoint of additional setpoint (using P1000).
Unit: - Min: 0 Def: 1 Max: 1
Level 3
Details:
Inhibits reverse setpoint selection when PID motor potentiometer is chosen either as a main setpoint of additional setpoint (using P1000)
Settings:
0=Reserve direction is allowed 1=Reserve direction inhibited
Note:
Setting 0 enables a change of motor direction using the motor potentiometer setpoint (increase/decrease frequency either by using digital inputs or motor potentiometer up/down buttons.
P2240[2] Setpoint of PID-MOP
Setpoint of the motor potentiometer. Allows user to set a digital PID setpoint in [%].
Unit: % Min: -200.00 Def: 10.00 Max: 200.00
Level 3
Settings:
722.0=Digital input 1 (requires P0701 set to 99, BICO)
722.1=Digital input 2 (requires P0702 set to 99, BICO)
722.2=Digital input 3 (requires P0703 set to 99, BICO)
722.3=Digital input 4 (requires P0704 set to 99, BICO)
722.4=Digital input 5 (requires P0705 set to 99, BICO)
722.5=Digital input 6 (requires P0706 set to 99, BICO)
722.6=Digital input 7 (via analog input 1, requires P0707 set to 99)
722.7=Digital input 8 (via analog input 2, requires P0708 set to 99)
19.D =Keypad UP cursor
Dependency:
To change setpoint:
1. Use UP / DOWN key on BOP or
2. Set P0702/P0703=13/14 (function of digital inputs 2 and 3)
Note:
P2240=100 % corresponds to 4000 hex.
r2250 CO: Output setpoint of PID-MOP
Displays output setpoint of motor potentiometer in [%].
Level 3
Loading...