Siemens SIDOOR AT40, SIDOOR ATD400V, SIDOOR ATD400K, SIDOOR ATD400S, ATE250S System Manual

...
Page 1
Automatic Door Controls
SIDOOR
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
System Manual
siemens.com
06/2016Edition
Page 2

AT40, ATD400V, ATD400K, ATD4xxW,
ATD400S, ATE250S, ATD400T

___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
Automatic Door Controls
SIDOOR AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
System Manual
06/2016
A2B00096162
Introduction
1
General safety instructions
2
Product family
3
Areas of application
4
Product combinations
5
Controllers
6
Geared motors
7
Power supply
8
Connecting and commissioning
9
Additional units
10
Appendix
A
-AN
Page 3
Siemens AG Division Digital Factory Postfach 48 48 90026 NÜRNBERG GERMANY
A2B00096162-AN
Copyright © Siemens AG 2012 - 2016. All rights reserved

Legal information

Warning notice system
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
Qualified Personnel
personnel qualified
Proper use of Siemens products
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
Disclaimer of Liability
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage.
The product/system described in this documentation may be operated only by task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems.
Note the following:
documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions.
for the specific
06/2016 Subject to change
Page 4

Table of contents

1 Introduction ........................................................................................................................................... 11
2 General safety instructions .................................................................................................................... 14
3 Product family ....................................................................................................................................... 17
4 Areas of application .............................................................................................................................. 29
5 Product combinations............................................................................................................................ 32
6 Controllers ............................................................................................................................................ 33
3.1 Products ................................................................................................................................. 19
3.1.1 Controllers .............................................................................................................................. 19
3.1.2 Geared motors ....................................................................................................................... 21
3.1.3 Accessories ............................................................................................................................ 23
3.1.4 Power supply .......................................................................................................................... 26
3.1.5 Optional additional units ......................................................................................................... 27
3.1.6 Software ................................................................................................................................. 28
4.1 Elevators ................................................................................................................................ 29
4.2 Industrial applications ............................................................................................................ 30
4.3 Railways ................................................................................................................................. 31
6.1 Description ............................................................................................................................. 33
6.2 Drive functions ....................................................................................................................... 35
6.2.1 Overview ................................................................................................................................ 35
6.2.2 Light barrier ............................................................................................................................ 39
6.2.3 Motion detector ...................................................................................................................... 41
6.2.4 DCPS (Door Closed Position Sensor) ................................................................................... 41
6.2.5 DCOPS (door closed/opened position sensor) ...................................................................... 42
6.2.6 Type 2 ESPE .......................................................................................................................... 44
6.2.7 Pressure-sensitive edge (SR) ................................................................................................ 46
6.2.8 Gate interlocking .................................................................................................................... 47
6.2.9 Door locked ............................................................................................................................ 48
6.2.10 Nudge ..................................................................................................................................... 49
6.2.11 Stopping ................................................................................................................................. 49
6.2.12 Force and energy profiles (NDG mode) ................................................................................. 50
6.2.13 Slow driving curve profile ....................................................................................................... 51
6.2.14 Automatically delayed motion ................................................................................................ 52
6.2.15 Cord-operated switch ............................................................................................................. 53
6.2.16 DOOR CLOSE (command given via digital inputs) ............................................................... 54
6.2.17 DOOR OPEN (command given via digital inputs) ................................................................. 55
6.2.18 Partial opening ....................................................................................................................... 56
6.2.19 Restart after power failure ...................................................................................................... 57
6.2.20 Overload protection ................................................................................................................ 57
6.2.21 Vandalism protection/continuous door monitoring ................................................................. 58
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
4 System Manual, 06/2016, A2B00096162-AN
Page 5
Table of contents
6.2.22 Obstruction detection .............................................................................................................. 59
6.2.22.1 Obstruction detection CLOSE ................................................................................................. 59
6.2.22.2 Obstruction detection OPEN ................................................................................................... 60
6.2.22.3 SIDOOR ATD4xxW obstruction detection .............................................................................. 61
6.2.23 ImpulseDrive ........................................................................................................................... 65
6.2.24 Automatic ImpulseDrive .......................................................................................................... 66
6.2.25 ImpulseStop ............................................................................................................................ 67
6.2.26 Automatic ImpulseStop ........................................................................................................... 68
6.2.27 AssistedDrive .......................................................................................................................... 69
6.2.28 Automatic AssistedDrive ......................................................................................................... 70
6.2.29 Initial run/reference run (Power ON) ....................................................................................... 71
6.2.30 Positioning mode .................................................................................................................... 72
6.2.31 Belt break monitoring .............................................................................................................. 73
6.2.32 Emergency power mode ......................................................................................................... 74
6.2.33 Friction compensation ............................................................................................................. 75
6.2.34 Oscillation protection............................................................................................................... 76
6.2.35 Automatic energy limitation ..................................................................................................... 77
6.2.36 External closing force.............................................................................................................. 81
6.2.37 Push to open ........................................................................................................................... 82
6.2.38 Pull to close ............................................................................................................................. 82
6.2.39 Emergency release ................................................................................................................. 82
6.2.40 Learn run ................................................................................................................................. 83
6.2.41 Force limit for learn run ........................................................................................................... 85
6.2.42 Output transmission ................................................................................................................ 86
6.2.43 Free function blocks (FBLOCK) .............................................................................................. 87
6.2.43.1 Overview ................................................................................................................................. 87
6.2.43.2 Configuring the logic ............................................................................................................... 88
6.2.43.3 Digital and logical input signals ............................................................................................... 90
6.2.43.4 Special function blocks ........................................................................................................... 91
6.2.43.5 Discrepancy analysis block ..................................................................................................... 91
6.2.43.6 Basic blocks ............................................................................................................................ 91
6.2.43.7 Frequency analysis blocks ...................................................................................................... 92
6.2.43.8 On delay block ........................................................................................................................ 92
6.2.43.9 Counter block .......................................................................................................................... 93
6.2.44 Drive orders ............................................................................................................................ 94
6.3 S
afety concept ATD4xxW ....................................................................................................... 98
6.3.1 Safe force output ..................................................................................................................... 98
6.3.2 Safe speed observance (energy limiting) ............................................................................... 98
6.3.3 Safe input signals according to PLd ....................................................................................... 98
6.3.3.1 Internal signal routing.............................................................................................................. 99
6.3.3.2 Redundant antivalent signal logic with discrepancy analysis ................................................. 99
6.3.3.3 Frequency-based input signals ............................................................................................. 101
6.3.3.4 Two-hand operation concept (according to Cat. IIIA) ........................................................... 101
6.3.3.5 Emergency stop concept in accordance with stop category 1 ............................................. 103
6.3.3.6 Concept of fail-safe digital control (door OPEN/CLOSE) with emergency stop via 4
digital inputs .......................................................................................................................... 104
6.3.3.7 Concept of fail-safe digital control (door OPEN/CLOSE) with emergency stop via 3
digital inputs .......................................................................................................................... 107
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
5
Page 6
Table of contents
6.4 Operation and parameter assignment ................................................................................. 109
6.4.1 Service buttons / Minimal editor ........................................................................................... 110
6.4.1.1 Service buttons .................................................................................................................... 110
6.4.1.2 Minimal editor ....................................................................................................................... 113
6.4.2 Terminal module .................................................................................................................. 116
6.4.3 Operating options via additional units .................................................................................. 118
6.4.4 Parameter names................................................................................................................. 118
6.4.5 Navigation structure ............................................................................................................. 120
6.5 Installation ............................................................................................................................ 126
6.6 Connecting terminals and interfaces ................................................................................... 129
6.6.1 Wiring instructions ................................................................................................................ 129
6.6.2 Digital input signals .............................................................................................................. 131
6.6.3 Voltage output*..................................................................................................................... 134
6.6.4 Relay module ....................................................................................................................... 135
6.6.5 CAN module ......................................................................................................................... 140
6.6.6 USS/PROFIBUS/PROFINET module .................................................................................. 143
6.6.6.1 USS module ......................................................................................................................... 143
6.6.6.2 PROFIBUS module .............................................................................................................. 145
6.6.6.3 PROFINET module .............................................................................................................. 148
6.6.6.4 Wiring and connecting a PROFIBUS/USS connector.......................................................... 154
6.6.6.5 Wiring and connecting a PROFINET connector .................................................................. 156
6.6.6.6 Wiring and connecting relay outputs .................................................................................... 157
6.6.7 Sensors and external sensor interface module (ATD4xxW) ................................................ 159
6.6.7.1 Overview .............................................................................................................................. 159
6.6.7.2 Type 2 ESPE ........................................................................................................................ 160
6.6.7.3 Pressure-sensitive edge (SR) .............................................................................................. 161
6.6.7.4 Sensor function test ............................................................................................................. 162
6.6.7.5 Reaction times ..................................................................................................................... 163
6.6.7.6 Stopping distances ............................................................................................................... 163
6.6.8 Motor plug ............................................................................................................................ 164
6.7 Parameters ........................................................................................................................... 165
6.7.1 Driving curve ........................................................................................................................ 165
6.7.2 Forces .................................................................................................................................. 166
6.7.3 Parameter assignment (ATD4xxW) ..................................................................................... 170
6.7.3.1 Driving parameters ............................................................................................................... 171
6.7.3.2 Other parameters
.7.3.3 Fieldbus parameters ............................................................................................................ 174
6
................................................................................................................. 172
6.7.3.4 Calibration and function parameters .................................................................................... 175
6.7.3.5 Obstruction and reversing parameters ................................................................................ 177
6.7.3.6 FBLOCK parameters ........................................................................................................... 180
6.8 Diagnostics ........................................................................................................................... 183
6.8.1 Operating state display ........................................................................................................ 183
6.8.2 Fault management (ATD4xxW) ........................................................................................... 185
6.9 Communication to PROFIBUS ............................................................................................. 186
6.9.1 Communication .................................................................................................................... 186
6.9.1.1 Parameter assignment ......................................................................................................... 186
6.9.1.2 Configuration ........................................................................................................................ 189
6.9.1.3 Diagnostics ........................................................................................................................... 190
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
6 System Manual, 06/2016, A2B00096162-AN
Page 7
Table of contents
6.10 Communication to PROFINET .............................................................................................. 191
6.10.1 Parameterization/startup record ........................................................................................... 191
6.10.2 Configuration ......................................................................................................................... 193
6.10.3 Diagnostics ........................................................................................................................... 193
6.10.4 Device roles and provider-consumer model ......................................................................... 194
6.11 Structure of user data/process data ...................................................................................... 195
6.11.1 Parameter interface .............................................................................................................. 196
6.11.1.1 Parameter ID (PKE) .............................................................................................................. 197
6.11.1.2 Parameter index (IND) .......................................................................................................... 200
6.11.1.3 Parameter value (PWE) ........................................................................................................ 202
6.11.1.4 Parameter ID ......................................................................................................................... 203
6.11.1.5 Parameter description (PBE) ................................................................................................ 203
6.11.2 Process data ......................................................................................................................... 204
6.11.2.1 STW1 - control word (CtrlW) ................................................................................................. 205
6.11.2.2 TSW0 - technology control word 0 ........................................................................................ 206
6.11.2.3 TSW1 - technology control word 1 ........................................................................................ 206
6.11.2.4 TSW2 - technology control word 2 ........................................................................................ 207
6.11.2.5 ZSW1 - status word (StatW) ................................................................................................. 208
6.11.2.6 TZW0 - Technology status word 0 ........................................................................................ 209
6.11.2.7 TZW1 - Technology status word 1 ........................................................................................ 210
6.11.2.8 TZW2 - Technology status word 2 ........................................................................................ 212
6.11.2.9 TZW3 - Technology status word 3 ........................................................................................ 213
6.11.2.10 TZW4 - Technology status word 4 ........................................................................................ 214
6.11.2.11 TZW5 - Technology status word 5 ........................................................................................ 214
6.12 Local/master operation ......................................................................................................... 215
6.13 Master monitoring ................................................................................................................. 215
6.14 Sequential control ................................................................................................................. 216
6.15 Integration of SIMATIC S7 .................................................................................................... 218
6.15.1 Function block ....................................................................................................................... 219
6.15.1.1 "SIDOOR_CDat" data type ................................................................................................... 220
6.15.1.2 "SIDOOR_SDat" data type.................................................................................................... 221
6.15.2 Configuring PROFIBUS hardware (GSD file) ....................................................................... 222
6.15.3 Configuring PROFINET hardware (GSD file) ....................................................................... 222
6.
16 Technical specifications ........................................................................................................ 223
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
7
Page 8
Table of contents
7 Geared motors ..................................................................................................................................... 232
8 Power supply ....................................................................................................................................... 260
9 Connecting and commissioning ............................................................................................................ 280
7.1 Description ........................................................................................................................... 232
7.2 Installation ............................................................................................................................ 233
7.3 Connecting terminals ........................................................................................................... 238
7.3.1 Conductor assignment of the motor plug ............................................................................. 238
7.4 Technical specifications ....................................................................................................... 239
7.4.1 Dimension drawing of SIDOOR M2 with rubber-metal anti-vibration mount and
mounting bracket.................................................................................................................. 248
7.4.2 Dimension drawing of SIDOOR M3 / MDG180 DIN EN 45545-2 with rubber-metal anti-
vibration mount and mounting bracket ................................................................................. 249
7.4.3 Dimension drawing of SIDOOR MDG180 with rubber-metal anti-vibration mount and
mounting bracket.................................................................................................................. 250
7.4.4 Dimension drawing SIDOOR MEG250 ................................................................................ 251
7.4.5 Dimension drawing of SIDOOR M4 with rubber-metal anti-vibration mount and
mounting bracket.................................................................................................................. 253
7.4.6 Dimension drawing of SIDOOR MDG400 with rubber-metal anti-vibration mount and
mounting bracket.................................................................................................................. 254
7.4.7 Dimension drawing of SIDOOR M5 ..................................................................................... 255
7.4.8 Dimension drawing MDG400NMS ....................................................................................... 256
7.4.9 Dimension drawing of MDG motor cable ............................................................................. 257
7.4.10 Dimension drawing of deflector pulley with tensioning device and mounting bracket ......... 258
7.4.11 Dimension drawing of door clutch holder ............................................................................. 259
8.1 SIDOOR NT40 ..................................................................................................................... 260
8.1.1 Description ........................................................................................................................... 260
8.1.2 Installation ............................................................................................................................ 262
8.1.3 Connecting terminals ........................................................................................................... 263
8.1.4 Technical specifications ....................................................................................................... 265
8.2 SIDOOR Transformer .......................................................................................................... 268
8.2.1 Description ........................................................................................................................... 268
8.2.2 Installation ............................................................................................................................ 269
8.2.3 Connecting terminals ........................................................................................................... 270
8.2.4 Technical specifications ....................................................................................................... 271
8.3 Uninterruptible power supply (UPS) .................................................................................... 273
8.4 Direct voltage supply provided by customer ........................................................................ 276
8.4.1 Requirements for SIDOOR ATD400T power supply ........................................................... 276
8.4.2 Requirements for SIDOOR ATD4xxW power supply ........................................................... 277
8.4.3 Installation ............................................................................................................................ 279
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
8 System Manual, 06/2016, A2B00096162-AN
Page 9
Table of contents
10 Additional units ................................................................................................................................... 289
A Appendix............................................................................................................................................. 296
10.1 SIDOOR EMC FILTER ......................................................................................................... 289
10.1.1 Description ............................................................................................................................ 289
10.1.2 Installation ............................................................................................................................. 289
10.1.3 Connecting terminals ............................................................................................................ 290
10.1.4 Technical specifications ........................................................................................................ 291
10.2 SIDOOR Service Tool ........................................................................................................... 292
10.2.1 Description ............................................................................................................................ 292
10.2.2 Connection ............................................................................................................................ 292
10.2.3 Operation .............................................................................................................................. 293
10.2.4 Technical specifications ........................................................................................................ 294
A.1 Profiles and adjustment ranges ............................................................................................ 296
A.1.1 Profile name .......................................................................................................................... 296
A.1.2 SIDOOR M2 L / R ................................................................................................................. 297
A.1.2.1 SIDOOR AT40/ATD400S ..................................................................................................... 297
A.1.2.2 SIDOOR ATD400W .............................................................................................................. 298
A.1.2.3 SIDOOR M2 adjustment ranges ........................................................................................... 299
A.1.3 SIDOOR M3 L / R ................................................................................................................. 300
A.1.3.1 SIDOOR AT40/ATD400S ..................................................................................................... 300
A.1.3.2 SIDOOR ATD400K ............................................................................................................... 301
A.1.3.3 SIDOOR ATD400W .............................................................................................................. 302
A.1.3.4 SIDOOR ATD4xxW ............................................................................................................... 303
A.1.3.5 SIDOOR ATD400T ............................................................................................................... 304
A.1.3.6 SIDOOR M3 adjustment ranges ........................................................................................... 305
A.1.4 SIDOOR MDG180 L / R ........................................................................................................ 307
A.1.4.1 SIDOOR ATD4xxW ............................................................................................................... 307
A.1.4.2 Adjustment ranges SIDOOR MDG180 ................................................................................. 307
A.1.5 SIDOOR MDG180 L / R DIN EN 45545-2 ............................................................................ 307
A.1.5.1 SIDOOR ATD400T ............................................................................................................... 307
A.1.5.2 SIDOOR MDG180 DIN EN 45545-2 adjustment ranges ...................................................... 307
A.1.6 SIDOOR M4 L / R ................................................................................................................. 308
A.1.6.1 SIDOOR AT40/ATD400S ..................................................................................................... 308
A.1.6.2 SIDOOR ATD400K ............................................................................................................... 309
A.1.6.3 SIDOOR ATD400V ............................................................................................................... 310
A.1.6.4 SIDOOR ATD400W .............................................................................................................. 311
A.1.6.5 SIDOOR ATD4xxW ............................................................................................................... 312
A.1.6.6 SIDOOR ATD400T ............................................................................................................... 313
A.1.6.7 SIDOOR M4 adjustment ranges ........................................................................................... 314
A.1.7 SIDOOR MDG400 L / R ........................................................................................................ 316
A.1.7.1 SIDOOR ATD4xxW ............................................................................................................... 316
A.1.7.2 Adjustment ranges SIDOOR MDG400 ................................................................................. 316
A.1.8 SIDOOR MDG400NMS L / R ................................................................................................ 317
A.1.8.1 SIDOOR ATD4xxW ............................................................................................................... 318
A.1.8.2 SIDOOR MDG400NMS adjustment ranges.......................................................................... 319
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
9
Page 10
Table of contents
Index ................................................................................................................................................... 334
A.1.9 SIDOOR M5 L / R ................................................................................................................ 320
A.1.9.1 SIDOOR AT40 ..................................................................................................................... 320
A.1.9.2 SIDOOR ATD4xxW .............................................................................................................. 321
A.1.9.3 Adjustment ranges SIDOOR M5 .......................................................................................... 322
A.1.10 SIDOOR MEG250 ................................................................................................................ 324
A.1.10.1 SIDOOR ATE250S .............................................................................................................. 324
A.1.10.2 Adjustment ranges SIDOOR MEG250 ................................................................................ 325
A.2 Configuration record ............................................................................................................ 326
A.3 Standards, directives and laws ............................................................................................ 329
A.3.1 Safety ................................................................................................................................... 329
A.3.2 EMC ..................................................................................................................................... 329
A.3.3 Communications .................................................................................................................. 330
A.3.4 Application-specific standards ............................................................................................. 330
A.3.5 Protective devices ................................................................................................................ 331
A.4 Service & support ................................................................................................................. 333
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
10 System Manual, 06/2016, A2B00096162-AN
Page 11
1
Content of the System Manual
Target group
This System Manual describes SIDOOR door drives. A SIDOOR door drive consists of at least the following components:
● Controller
● Geared motor
● Power supply
Optional additional units can also be connected (for example, the SIDOOR Service Tool).
The individual products and their interactions are described in this System Manual.
The System Manual is intended for fitters, commissioning engineers, operators, service personnel, and configuration engineers who work on elevators, machine tools and railway doors.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
11
Page 12
Introduction
Firmware versions
as from
Controller
From firmware version
SIDOOR AT40
1.40
SIDOOR ATD400K RELAY LB
1.02
SIDOOR ATD400K RELAY RC
2.02
SIDOOR ATD401W
1.01
SIDOOR ATD410W
1.00
SIDOOR ATD420W
1.00
SIDOOR ATD430W
1.02
SIDOOR ATD400S
1.03
SIDOOR ATE250S
1.10
SIDOOR ATD400T RELAY
4.07
Note SIDOOR ATD4xxW firmware versions
You will find the current firmware versions for SIDOOR ATD4xxW Industry Online Support (
Figures
Information on the Internet
Parameter documentation
This System Manual applies to controllers
SIDOOR ATD400V RELAY 1.03
the following firmware versions:
controllers online at
http://support.automation.siemens.com/WW/view/en/50247080/133100).
The figures in this System Manual illustrate SIDOOR User Software Version 1.11 and the SIDOOR AT40 RELAY controller / CAN Version 1.40. The illustrations for other versions may differ slightly.
You can find more information about SIDOOR door drives and their applications on the Internet (www.siemens.com/sidoor).
After the optimal parameter settings have been determined, note them in the configuration record (see Appendix "Configuration record (Page 326)"). Have this record to hand when you call the Hotline.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
12 System Manual, 06/2016, A2B00096162-AN
Page 13
Introduction
History
Version
Change
10/2010
First edition
ler.
ler.
SIDOOR ATD4xxW controller firmware version 1.03 expanded.
Extension control device SIDOOR ATD4xxW firmware version 1.05.
ATD430W.
02/2014 Revised and expanded edition 04/2014 Edition revised and expanded to include the SIDOOR ATD420W control-
07/2014 Revised and expanded edition 11/2014 Edition revised and expanded to include the SIDOOR ATD430W control-
04/2015 Revised and expanded edition.
01/2016 Revised and expanded edition.
06/2016 Revised and expanded edition.
Extension control devices for NFPA environment ATD401W ATD420W,
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
13
Page 14
2
Qualified personnel
Working on the door drive
WARNING
Risk of injury due to dangerous electrical voltages and moving mechanical parts.
WARNING
Risk of injury due to moving mechanical parts
CAUTION
Risk of injury due to moving mechanical parts
Qualified personnel have the following qualifications:
Training, instruction or authorization to switch on and off electric circuits and devices/systems in compliance with safety engineering standards.
Training or instruction in the maintenance and use of appropriate safety equipment in compliance with safety engineering standards.
First aid training.
Disconnect the door drive by unplugging the power plug from the power supply before you start work on the door drive.
If power-operated guards are used, ensure that they have been tested prior to initial commissioning. Power-operated guards must also be tested annually.
If required by the drive application, suitable protective equipment must be installed for safe door interlocking.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
14 System Manual, 06/2016, A2B00096162-AN
Page 15
General safety instructions
Parameter assignment and configuration
WARNING
Risk of injury and material damage due to excessive forces of the door
Note Application-specific measures for emergency operation
In the event of a controller failu according to the application.
Modifications to the door drive
CAUTION
Loss of liability for defects and material damage
Exceeding the maximum static closing force and opening force, if present, may lead to injuries to persons or damage to the door drive and mechanical components of the door.
After commissioning, have the maximum static forces checked by the service personnel, and adjusted to the limit value if it is excessive.
Observe the limit values of the applicable standards and adjust the set values accordingly.
re, measures must be taken for emergency operation
Changes to the door drive lead to the loss of liability for defects and compensation rights, and the correct function of the door drive is no longer guaranteed.
Note the following rules:
Do not make any modifications to the door drive (motor, controller, power supply).
Do not make a permanent connection as this does not ensure a proper and required
necessary disconnection from the mains.
Do not remove the protective Schuko-type socket under any circumstances (for example by cutting it off).
The power supply cable (SIDOOR Transformer or SIDOOR NT40) cannot be replaced. Scrap the power supply if the supply cable is damaged.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
15
Page 16
General safety instructions
Notes for servicing
Security information
Note Using ATD410W, ATD420W und ATD430W fieldbus controllers
Installation in control cabinet only
The SIDOOR system should be included in the maintenance plan of the plant and be inspected in the course of the maintenance intervals specified there.
An inspection should cover the following points:
● Visual inspection of the controller for contamination and damage
● Visual inspection of the motor for dirt and damage
Visual and mechanical inspection of the mechanical system in as far as this belongs to
the SIDOOR elevator system. This includes checking the following components:
● Attachment of the motor holder, deflector pulley and mounting bracket
● Wear on the toothed belt
Check and remeasure the parameters for the safety-relevant force and energy settings
set during commissioning
Siemens provides products and solutions with industrial security functions that support the secure operation of plants, solutions, machines, equipment and/or networks. They are important components in a holistic industrial security concept. With this in mind, Siemens’ products and solutions undergo continuous development. Siemens recommends strongly that you regularly check for product updates.
For the secure operation of Siemens products and solutions, it is necessary to take suitable preventive action (e.g. cell protection concept) and integrate each component into a holistic, state-of-the-art industrial security concept. Third-party products that may be in use should also be considered. Please find further information on industrial security at (http://www.siemens.com/industrialsecurity) .
To stay informed about product updates as they occur, sign up for a product-specific newsletter. You can find more information on this at (http://support.automation.siemens.com) .
– to ensure access by authorized personnel only.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
16 System Manual, 06/2016, A2B00096162-AN
Page 17
3
SIDOOR
Overview of the product family
Software Kit)
Geared motor
Accessories
Power supply
Sliding door
Door control system is the general term for a controller of an access system.
The SIDOOR product family is primarily intended for operating sliding doors. Different versions of SIDOOR controllers enable both horizontal and vertical doors to be operated.
Door control systems are characterized by the fact that there are always two defined states: namely for the open and closed positions of the door. The door is always controlled between these two positions in accordance with the guidelines of the respective application.
In a defined learn run initiated by "one-button operation", the door system independently determines the values for the door width, the dynamic door weight and the drive direction of the geared motor, and stores these data in a non-volatile memory.
Controller
Optional additional unit (e.g. SIDOOR Service Tool, SIDOOR
Image 3-1 System setup
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
17
Page 18
Product family
Technologies
DC technology
EC technology
DC technology
EC technology
Controllers
SIDOOR ATD400V ✓ —
SIDOOR ATD400K ✓ —
SIDOOR ATD400W ✓ —
SIDOOR ATD4xxW ✓ —
SIDOOR ATD400S ✓ —
SIDOOR ATE250S — ✓
SIDOOR ATD400T ✓ —
Geared motors
SIDOOR M2 ✓ —
SIDOOR M3 ✓ —
SIDOOR MDG180 ✓ —
DIN EN 45545-2
SIDOOR MEG250 — ✓
SIDOOR M4 ✓ —
SIDOOR MDG400 NMS
SIDOOR MDG400 ✓ —
SIDOOR M5 ✓ —
Two different technologies are used in SIDOOR door control systems:
DC systems are two-phase driven, and have internal commutating brushes.
EC systems are three-phase driven, and are electronically commutated.
SIDOOR controllers and SIDOOR motors use the technologies as shown below:
Table 3- 1 Overview of technologies used
SIDOOR AT40
SIDOOR MDG180
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
18 System Manual, 06/2016, A2B00096162-AN
Page 19
Product family
3.1
Products
3.1.1

Controllers

Versions
Controller
Article No.
Description
Elevators
Industrial applications

3.1 Products

Controllers are electronic controllers connected to the power supply via an external power supply unit (SIDOOR NT40, SIDOOR Transformer). They are generally connected to the higher-level controller via digital or fieldbus interfaces, and can be configured via a user interface.
The controllers are designed for different areas of application. The following table provides an overview of the available controllers.
SIDOOR AT40 RELAY 6FB1111-0AT10-3AT2
SIDOOR AT40 CAN 6FB1111-1AT10-3AT3
SIDOOR ATD400V RELAY 6FB1111-1AT10-3VE2
SIDOOR ATD400K RELAY LB 6FB1141-1AT10-3KU2
SIDOOR ATD400K RELAY RC 6FB1141-1AT11-3KU2
SIDOOR ATD401W 6FB1141-1AT11-3WE2
Controller for horizontal elevator doors, up to 600 kg door weight
Relay module
Controller for horizontal elevator doors, up to 600 kg door
weight
Serial interface to the higher-level controller (CAN mod- ule)
Controller for rising gate and rolling shutter doors in the elevator field of application, up to 400 kg door weight
Relay module
Controller for cold room gates, up to 400 kg door weight
1 DI for light barriers (LB)
Relay module
Controller for cold room gates, up to 400 kg door weight
1 DI for reed contact (RC)
Relay module
Controller for machine tools, up to 600 kg door weight
Relay module
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
19
Page 20
Product family
Controller
Article No.
Description
Railways
Platform screen doors
Interior railway doors
3.1 Products
SIDOOR ATD410W 6FB1141-4AT10-3WE2
SIDOOR ATD420W 6FB1141-2AT10-3WE2
SIDOOR ATD430W 6FB1141-3AT10-3WE2
SIDOOR ATD400S 6FB1131-0BM10-3AT3
SIDOOR ATE250S 6FB1231-0BM10-0AT3
Controller for machine tools, up to 600 kg door weight
USS bus interface to the higher-level controller (USS
module)
Controller for machine tools, up to 600 kg door weight
PROFIBUS interface to the higher-level controller
(PROFIBUS module)
Controller for machine tools, up to 600 kg door weight
PROFINET interface to the higher-level controller
(PROFIBUS module)
Controller for platform screen doors, up to 400 kg door weight
Serial interface to the higher-level controller via the SIDOOR AT-EB expansion unit
Controller for platform screen doors, up to 250 kg door weight
Serial interface to the higher-level controller via the SIDOOR AT-EB expansion unit
SIDOOR ATD400T RELAY 6FB1121-0BM13-3AT2
Controller for interior railway doors, up to 400 kg door weight
Relay module
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
20 System Manual, 06/2016, A2B00096162-AN
Page 21
Product family
3.1.2

Geared motors

Versions
Geared motor
Article No.
Description
3.1 Products
Geared motors form the maintenance-free drive unit in the door drive. The geared motors feature DC motors with non-self-locking gearing and are speed-controlled. The set force and speed limits are not exceeded. The power is transmitted by a gear rack or chain. Toothed belts or chains pass over a deflector pulley, and can be fitted with 2 clutch holders. This enables it to drive both single­sided and centrally-opening doors.
SIDOOR M2 L 6FB1103-0AT10-5MA0
SIDOOR M2 R 6FB1103-0AT11-5MA0
SIDOOR M3 L 6FB1103-0AT10-4MB0
SIDOOR M3 R 6FB1103-0AT11-4MB0
SIDOOR MDG180 L 6FB1103-0AT14-4MB0
SIDOOR MDG180 R 6FB1103-0AT13-4MB0
SIDOOR MDG180 L DIN EN 45545-2
SIDOOR MDG180 R DIN EN 45545-2
SIDOOR MEG250 L 6FB1233-0BM00-0MP0
SIDOOR MEG250 R 6FB1233-0BM01-0MP0
6FB1103-0AT16-4MB0
6FB1103-0AT15-4MB0
Geared motor, pinion left, max. 120 kg door weight
Cable length 1.5 m
Geared motor, pinion right, max. 120 kg door weight
Cable length 1.5 m
Geared motor, pinion left, max. 180 kg door weight
Cable length 1.5 m
Geared motor, pinion right, max. 180 kg door weight
Cable length 1.5 m
Geared motor, pinion left, max. 180 kg door weight
Without cable*
Geared motor, pinion right, max. 180 kg door weight
Without cable*
Geared motor, pinion left, max. 180 kg door weight
Cable length 1.5 m
Geared motor, pinion right, max. 180 kg door weight
Cable length 1.5 m
Electronically commutated geared motor, pinion left, max.
250 kg door weight
Cable length 1.5 m
Electronically commutated geared motor, pinion right,
max. 250 kg door weight
Cable length 1.5 m
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
21
Page 22
Product family
Geared motor
Article No.
Description
3.1 Products
SIDOOR M4 L 6FB1103-0AT10-3MC0
SIDOOR M4 R 6FB1103-0AT11-3MC0
SIDOOR MDG400 L 6FB1103-0AT14-3MC0
SIDOOR MDG400 R 6FB1103-0AT13-3MC0
SIDOOR M5 L 6FB1103-0AT10-3MD0
SIDOOR M5 R 6FB1103-0AT11-3MD0
SIDOOR MDG400 NMS L 6FB1103-0AT14-3MC1
SIDOOR MDG400 NMS R 6FB1103-0AT13-3MC1
* Cable can be ordered: See Section Accessories (Page 23)
Geared motor, pinion left, max. 400 kg door weight
Cable length 1.5 m
Geared motor, pinion right, max. 400 kg door weight
Cable length 1.5 m
Geared motor, pinion left, max. 400 kg door weight
Without cable*
Geared motor, pinion right, max. 400 kg door weight
Without cable*
Geared motor, pinion left, max. 600 kg door weight
Cable length 1.5 m
Geared motor, pinon right, max. 600 kg door weight
Cable length 1.5 m
Geared motor, without pinion, max. 400 kg door weight
Without cable*
Geared motor, without pinion, max. 400 kg door weight
Without cable*
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
22 System Manual, 06/2016, A2B00096162-AN
Page 23
Product family
3.1.3

Accessories

Accessories
Article No.
Description
motor is mounted
SIDOOR deflector pulley
6FB1104-0AT04-0AS0
Deflector pulley for deflecting the SIDOOR toothed belt
3.1 Products
SIDOOR rubber-metal anti­vibration mount
SIDOOR mounting bracket 6FB1104-0AT01-0AS0 Mounting bracket for mounting the SIDOOR rubber-metal
SIDOOR deflector unit 6FB1104-0AT03-0AS0
SIDOOR door clutch holder 6FB1104-0AT01-0CP0
SIDOOR toothed belt 6FB1104-0AT01-0AB0
6FB1104-0AT01-0AD0
6FB1104-0AT02-0AD0
6FB1104-0AT02-0AS0
6FB1104-0AT02-0CP0
6FB1104-0AT02-0AB0
6FB1104-0AT03-0AB0
6FB1104-0AT04-0AB0
Rubber-metal anti-vibration mount for quiet operation of
the door drive system
Recommended for mounting SIDOOR M4 R / L, MDG400
R / L, M5 R / L and MDG400 NMS R / L geared motors
Rubber-metal anti-vibration mount for quiet operation of
the door drive system
Recommended for mounting SIDOOR M2 R / L, M3 R / L,
MDG180 R / L, MDG180 R / L DIN EN 45545-2 and MEG250 R / L geared motors
anti-vibration mount on which, in turn, a SIDOOR geared
Mounting bracket with tensioning device for deflector
pulley
For mounting the SIDOOR deflector unit and for tension-
ing the SIDOOR toothed belt
Deflector unit with deflector pulley
For deflecting the SIDOOR toothed belt in the same
height and depth, aligned with motor drive pinion
Door clutch holder for 12 mm-wide toothed belt
For attaching both ends of the toothed belt, and for con-
necting the respective door panel to the toothed belt
Door clutch holder for 14 mm wide toothed belt
For attaching both ends of the toothed belt, and for con-
necting the respective door panel to the toothed belt
Single-toothed STS
Super Torque toothed belt
Length 4 m, width 12 mm.
Single-toothed STS
Super Torque toothed belt
Length 45 m, width 12 mm.
Single-toothed STS
Super Torque toothed belt
Length 4 m, width 14 mm.
Single-toothed STS
Super Torque toothed belt
Length 55 m, width 14 mm.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
23
Page 24
Product family
Accessories
Article No.
Description
3.1 Products
SIDOOR CABLE-RS485-MM-2m
SIDOOR CABLE-RS485-MM-5m
SIDOOR CABLE-RS485-MM-10m
SIDOOR CABLE AT-EB USB 6FB1124-0BM03-0CB0
SIDOOR CABLE-MDG-0.5m 6FB1104-0AT00-0CB5
SIDOOR CABLE-MDG-1.5m 6FB1104-0AT01-0CB5
SIDOOR CABLE-MDG-5m 6FB1104-0AT05-0CB0
SIDOOR CABLE-MDG-7m 6FB1104-0AT07-0CB0
SIDOOR CABLE-MDG-10m 6FB1104-0AT10-0CB0
SIDOOR CABLE-MDG-15m 6FB1104-0AT15-0CB0
6FB1124-0BM00-0CB0
6FB1124-0BM01-0CB0
6FB1124-0BM02-0CB0
Cable from the SIDOOR AT-EB expansion unit to the SIDOOR ATD400S (Can also be used to connect the SIDOOR AT-EB expan­sion unit to the SIDOOR ATE250S)
Cable length 2 m
Cable from the SIDOOR AT-EB expansion unit to the
SIDOOR ATD400S (Can also be used to connect the SIDOOR AT-EB to the SIDOOR ATE250S)
Cable length 5 m
Cable from the SIDOOR AT-EB expansion unit to the
SIDOOR ATD400S (Can also be used to connect the SIDOOR AT-EB expan­sion unit to the SIDOOR ATE250S)
Cable length 10 m
Programming cable to connect the USB adapter of the
SIDOOR Software Kit to the AT-EB
Cable length 2 m
Cable for connecting SIDOOR MDG180 R / L, MDG400 R
/ L / MDG400 NMS geared motors to SIDOOR ATD4xxW controllers
Cable length 0.5 m
Cable for connecting SIDOOR MDG180 R / L, MDG400 R
/ L / MDG400 NMS geared motors to SIDOOR ATD4xxW controllers
Cable length 1.5 m
Cable for connecting SIDOOR MDG180 R / L, MDG400 R
/ L / MDG400 NMS geared motors to SIDOOR ATD4xxW controllers
Cable length 5 m
Cable for connecting SIDOOR MDG180 R / L, MDG400 R
/ L / MDG400 NMS geared motors to SIDOOR ATD4xxW controllers
Cable length 7 m
Cable for connecting SIDOOR MDG180 R / L, MDG400 R
/ L / MDG400 NMS geared motors to SIDOOR ATD4xxW controllers
Cable length 10 m
Cable for connecting SIDOOR MDG180 R / L, MDG400 R
/ L / MDG400 NMS geared motors to SIDOOR ATD4xxW controllers
Cable length 15 m
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
24 System Manual, 06/2016, A2B00096162-AN
Page 25
Product family
Accessories
Article No.
Description
controller
cable
higher-level SIMATIC controller
controllers
3.1 Products
SIDOOR CABLE-MDG-20m 6FB1104-0AT20-0CB0
PROFIBUS FC bus connector RS 485
PROFIBUS FC Standard Cable GP
IE FC RJ45 plug 180 4X2 6GK1901-1BB11-2AB0 Plug connector with axial cable outlet (180°) for connecting
IE FC TP Standard Cable GP 6XV1878-2A Cable for connecting the SIDOOR ATD430W controller to the
DIN rail holder 6FB1144-0AT00-3AS0 DIN rail holder with fixing screws for SIDOOR ATD4xxW
6GK1500-0FC10 Bus connector with axial cable outlet (180°, 20m) for connect-
6XV1830-0EH10 PROFIBUS cable for connecting SIDOOR ATD410W and
Cable for connecting SIDOOR MDG180 R / L, MDG400 R
/ L / MDG400 NMS geared motors to SIDOOR ATD4xxW controllers
Cable length 20 m
ing SIDOOR ATD410W and SIDOOR ATD420W controllers to the USS / PROFIBUS bus cable
SIDOOR ATD420W controllers to the higher-level SIMATIC
the SIDOOR ATD430W controller to the PROFINET bus
You will find more accessories in the Industry Mall (http://www.siemens.com/siplus/mall)
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
25
Page 26
Product family
3.1.4

Power supply

Device selection
Power supply
Article No.
Description
SIDOOR NT40
6FB1112-0AT20-3PS0
SIDOOR Transformer
6FB1112-0AT20-2TR0
DC voltage supply (Page 276)
-
3.1 Products
SIDOOR power supplies connect the controllers to the respective application-specific power supply.
Power supply for controllers without an integrated power supply unit.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
26 System Manual, 06/2016, A2B00096162-AN
Page 27
Product family
3.1.5

Optional additional units

Selection of additional units
Additional unit
Article No.
Description
2.
control systems via the proprietary RS 485 interface.
data and the current firmware version.
3.1 Products
Additional units meet a range of customer requirements in order to ensure the universal implementation and maintenance of the system.
The additional units are easy to connect to a deenergized controller via the interfaces provided – and are available for use as soon as the power supply is connected.
SIDOOR EMC FILTER 6FB1104-0AT20-0AT0 A line filter must be installed in the DC power supply to the
SIDOOR ATD400T RELAY controller to comply with the EMC requirements for emitted interference set out in EN 50121-3-
SIDOOR AT-EB expansion unit (with FW1.10)
SIDOOR Service Tool 6FB1105-0AT01-6ST0 The SIDOOR Service Tool may be used to input door com-
6FB1135-2BM10-0CP0 The SIDOOR AT-EB expansion unit enables SIDOOR con-
trollers to be connected via a PROFIBUS DP interface, and makes additional input and output signals available.
The SIDOOR AT-EB expansion unit controls up to two door
mands, to change drive parameters and to read the learnt parameters, door states, input and output signals, service
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
27
Page 28
Product family
3.1.6

Software

Selection
Software
Article No.
Description
3.1 Products
The optional SIDOOR Software Kit facilitates user-friendly operation and detailed diagnostics via a PC.
SIDOOR Software Kit 6FB1105-0AT01-6SW0 The package includes the following components:
Installation CD (Software Kit) – Sidoor User Software – Siemens HCS12 Firmware Loader – Sidoor USB to UART Bridge driver – License provisions – SIDOOR Software Kit Operating Instructions
1 x USB adapter
1 x USB connecting cable
1x D-SUB connecting cable (9-pin, plug/socket)
1x D-SUB connecting cable (9-pin, socket/socket)
The contents of the SIDOOR Software Kit installation CD are also available as an Installation package (http://support.automation.siemens.com/WW/view/en/92418945) from Industry Online Support.
You can find more information about the SIDOOR Software Kit in the SIDOOR Software Kit Operating Instructions (http://support.automation.siemens.com/WW/view/en/92711247).
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
28 System Manual, 06/2016, A2B00096162-AN
Page 29
4
4.1

Elevators

SIDOOR AT40
SIDOOR ATD400V
SIDOOR door drives are drives for doors and gates in various areas of application. The controllers are optimally configured for their areas of application.
The following controllers are offered for elevator applications:
The comfort SIDOOR AT40 elevator door drive is an "intelligent" door drive with which cabin and shaft doors can be opened and closed at adjustable speeds and accelerations.
The SIDOOR ATD400V hoisting and rolling shutter drive for elevators is an "intelligent" door drive for the operation of vertical door systems on elevators.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
29
Page 30
Areas of application
4.2
Industrial applications
Industrial applications
SIDOOR ATD400K
SIDOOR ATD4xxW
SIDOOR ATD401W
SIDOOR ATD410W
USS bus
SIDOOR ATD420W
PROFIBUS DP
SIDOOR ATD430W
PROFINET IO

4.2 Industrial applications

We offer the following controllers for industrial applications:
The SIDOOR ATD400K RELAY LB and SIDOOR ATD400K RELAY RC industrial door drives offer the optimal drive solutions for cold room gates weighing up to 400 kg. The ATD400K RELAY LB model enables the connection of light barriers with "LB" logic, and the ATD400K RELAY RC model enables the direct connection of a cord-operated switch to open the gate.
Both drives meet the requirements of EN ISO 13849-1:2008 with regard to safety of machinery and EN 12453:2000, section 5.2 with regard to safety in use of power operated doors.
ATD4xxW machine tool door drives are "intelligent" door drives that can be used to operate protective doors on machine tools. The safe functions - force limitation, energy limitation and end position detection - fulfill the requirements according to DIN EN ISO 13849-1:2008 for Category 2 and Performance Level d. The drives are suitable for power-operated guards according to EN 953:1997+A1:2009 Section 5.2.5.2 "Actuating forces".
The SIDOOR ATD4xxW door controller enables connection to diverse fieldbus systems. This makes integration into the industrial//Simatic environment possible. PROFINET IO, PROFIBUS DP and USS are currently specified as fieldbuses. The PROFIBUS "variable­speed drives" profile is generally used as the higher-level device profile.
The "offline" relay variant can be used for simple automation tasks. As there is no possibility of interfacing to a bus, it provides a limited scope of functions.
The controller is interfaced to a
You can find more detailed information about the USS protocol online at Industry Online Support (http://support.automation.siemens.com/WW/view/de/24178253/0/en).
The (AT-PB). This is an intelligent module that comes with its own firmware.
interface is realized by means of a modular PROFIBUS module
by means of a modular USS module.
The (AT-PN). This is an intelligent module that comes with its own firmware.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
30 System Manual, 06/2016, A2B00096162-AN
interface is realized by means of a modular PROFINET module
Page 31
Areas of application
4.3
Railways
Platform screen doors
SIDOOR ATD400S
SIDOOR ATE250S
Interior railway doors
SIDOOR ATD400T

4.3 Railways

The contents and structure of the user data transferred by the fieldbus systems correspond to the PROFIBUS "variable speed drives" profile. Use of this profile is also the basis for integration of the controller in the industrial environment. Both communicative integration via a fieldbus system and safety-related aspects play an important role here.
SIDOOR ATD4xxW machine tool door drives enable connection of door closed/opened position sensors (DCOPS), simple light barriers, pressure-sensitive edges as well as type 2 light arrays in compliance with IEC 61496 (ESPE - electrosensitive protective equipment).
The SIDOOR ATD410W, SIDOOR ATD420W and SIDOOR ATD430W machine tool door drives are characterized by their many functions, including "AssistedDrive" (motor­assisted sliding of the door) and "ImpulseDrive" (automatic door movement initiated by applying light force).
We offer the following controllers for railway applications:
The SIDOOR ATD400S platform screen door drive is an "intelligent" door drive system which enables platform screen doors to be opened and closed at adjustable speeds and accelerations.
It is not suitable for stand-alone operation. External commands are only accepted via the serial interface. The SIDOOR ATD400S platform screen door drive must always be operated in conjunction with the AT-EB expansion unit.
The ATD400S platform screen door drive can drive doors with a total door panel weight of up to 400 kg.
The SIDOOR ATE250S platform screen door drive is an "intelligent" door drive which drives platform screen doors.
It is not suitable for stand-alone operation. External commands are only accepted via the serial interface. It has no control inputs (digital input signals). The SIDOOR ATE250S platform screen door drive must therefore always be operated in conjunction with a SIDOOR AT-EB.
The ATD250S platform screen door drive can drive doors with a total door panel weight of up to 250 kg.
The SIDOOR ATD250S platform screen door drive uses EC technology. See Section Product family (Page 17).
The SIDOOR ATD400T interior railway door drive is an "intelligent" door drive which enables gangway doors to be opened and closed at adjustable speeds and accelerations.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
31
Page 32
5
SIDOOR …
AT40
ATD400V
ATD400K
ATD4xxW
ATD400S
ATE250S
ATD400T
Geared motors
SIDOOR M2
— — — ✓ — —
SIDOOR M3
— ✓ — ✓
SIDOOR MDG180
— — — ✓ — — —
DIN EN 45545-2
SIDOOR MEG250
— — — — — ✓ —
SIDOOR M4
— ✓*
SIDOOR MDG400
— — — ✓ — — —
SIDOOR M5
— — ✓ — — —
Power supply
SIDOOR NT40
— ✓ — —
SIDOOR Transformer
— ✓
(Page 276)
Additional units
SIDOOR EMC FILTER
— — — — — — ✓
expansion unit
SIDOOR Software Kit
SIDOOR Service Tool
The following table shows which products you can combine with which controllers.
Table 5- 1 Overview of product combinations
SIDOOR MDG180
SIDOOR MDG400 NMS
DC voltage supply
SIDOOR AT-EB
* Please observe the note entitled "SIDOOR ATD400T relay (6FB1121-0BM13-3AT2) – supplementary technical specifications" in Section Technical specifications (Page 223).
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
32 System Manual, 06/2016, A2B00096162-AN
Page 33
6
6.1

Description

Overview
SIDOOR AT40 / ATD400V
Connecting terminals
Relay module / CAN module
Service buttons / Minimal editor
Terminal module
SIDOOR ATD400K / ATD400S / ATD400T
Connecting terminals
(not with ATD400S)
Service buttons / Minimal editor
Terminal module
Relay module / USS module / PROFIBUS module
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
33
Page 34
Controllers
SIDOOR ATD4xxW
Connecting terminals
Relay module/USS module/PROFIBUS module/PROFINET module
Service buttons/Minimal editor
Terminal module
SIDOOR ATE250S
Connecting terminals
Terminal module
6.1 Description
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
34 System Manual, 06/2016, A2B00096162-AN
Page 35
Controllers
6.2
Drive functions
6.2.1

Overview

Overview of drive functions
SIDOOR
AT40
ATD400V
ATD400K
ATD401W
ATD410W/ ATD420W/
ATD430W
ATD400S
ATE250S
ATD400T
LB
RC
Light barrier (Page 39)
✓1)
✓1)
✓ — —
✓2) — —
Motion detector (Page 41)
— — — — — — — — ✓
higher)
Type 2 ESPE (Page 44)
— — — — ✓3)
✓3) — —
higher)
Gate interlocking (Page 47)
— — — ✓ — — — — —
Door locked (Page 48)
— — — — — — — — ✓
Nudge (Page 49)
— — — — — — —
er)
(Page 51)
Stopping (Page 49)
(Page 52)
higher)

6.2 Drive functions

This Section describes the complete range of drive functions of SIDOOR controllers. The following table provides an overview of the SIDOOR controllers and their individual drive functions.
Different drive functions have been implemented in the controllers according to their areas of application.
DCPS (Door Closed Position Sensor) (Page 41)
DCOPS (door closed/opened position sensor) (Page 42)
Pressure-sensitive edge (SR) (Page 46)
Force and energy profiles (NDG mode) (Page 50)
Slow driving curve profile
Automatically delayed motion
Cord-operated switch (Page 53)
DOOR CLOSE (command given via digital inputs) (Page 54)
✓1) ✓1)
3) 3)
✓4)
1) 3)
(V1.03
and high-
2) 3)
(V1.01 and
(V1.01 and
(V1.01 and
higher)
(V1.01 and
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
35
Page 36
Controllers
SIDOOR
AT40
ATD400V
ATD400K
ATD401W
ATD410W/ ATD420W/
ATD430W
ATD400S
ATE250S
ATD400T
LB
RC
higher)
higher)
(Page 57)
Overload protection (Page 57)
ing (Page 58)
(Page 59)
ImpulseDrive (Page 65)
— — — — — ✓ — — —
(Page 66)
ImpulseStop (Page 67)
— — — — — ✓ — — —
(Page 68)
AssistedDrive (Page 69)
— — — — — ✓ — — —
er ON) (Page 71)
higher)
(Page 73)
er)
(Page 75)
(Page 76)
(Page 77)
(Page 81)
Push to open (Page 82)
— — — — — — — — ✓
Pull to close (Page 82)
— — — — — — — — ✓
6.2 Drive functions
DOOR OPEN (command given via digital inputs) (Page 55)
Partial opening (Page 56)
Restart after power failure
Vandalism protec­tion/continuous door monitor-
Obstruction detection
Automatic ImpulseDrive
Automatic ImpulseStop
Automatic AssistedDrive (Page 70)
Initial run/reference run (Pow-
✓4)
(V1.01 and
(V1.01 and
Positioning mode (Page 72)
Belt break monitoring
Emergency power mode (Page 74)
Friction compensation
Oscillation protection
Automatic energy limitation
External closing force
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
36 System Manual, 06/2016, A2B00096162-AN
(V1.01 and
—6) —6) —6) —6) —6)
(V1.03
and high-
✓7) ✓7)
Page 37
Controllers
SIDOOR
AT40
ATD400V
ATD400K
ATD401W
ATD410W/ ATD420W/
ATD430W
ATD400S
ATE250S
ATD400T
LB
RC
Emergency release (Page 82)
Learn run (Page 83)
V1.05)
V1.05)
higher)
higher)
Drive orders (Page 94)
— — — — ✓ ✓ — — —
higher)
er)
higher)
Diagnostics
Terminal module (Page 116)
editor (Page 110))
(Page 292)
6.2 Drive functions
Force limit for learn run (Page 85)
Output transmission (Page 86)
Free function blocks (FBLOCK) (Page 87)
Auto-Hotspot
Two-hand operation
Emergency stop
Fail-safe digital control
(as of
V1.05)
(as of
(V1.03
and high-
(as of
V1.05)
(as of
(V1.01 and
(V1.01 and
(V1.01 and
(V1.01 and
higher)
(V1.01 and
7-segment display (see Sec­tion Service buttons / Minimal
SIDOOR Service Tool
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
✓5) ✓5)
37
Page 38
Controllers
SIDOOR
AT40
ATD400V
ATD400K
ATD401W
ATD410W/ ATD420W/
ATD430W
ATD400S
ATE250S
ATD400T
LB
RC
Update possible
1)
2)
3)
4)
5)
6)
cm). A belt break error is not displayed; the controller instead switches
7)
tion of function)
Drive function parameter assignment
ATD4xxW (firmware version 1.03 or higher)
6.2 Drive functions
SIDOOR Software Kit
✓5) 5)
(Page 28)
Light barrier and DCPS/DCOPS (ATD401W) cannot be implemented simultaneously. Light barrier and DCOPS can be implemented simultaneously by connecting to a fieldbus system. DCOPS, type 2 ESPE or pressure-sensitive edge cannot be implemented simultaneously. Evaluated by PLC. The connection to the SIDOOR AT-EB expansion unit must be severed. Monitoring of the travel distance (door width + 10
to Init mode and an initial move must be executed.
External closing force is not provided for the customer side, however it can be installed. (See the notes in the descrip-
The respective parameters for the drive functions are fixed for the SIDOOR AT40, ATD400V, ATD400K, ATD401W, ATD400S, ATE250S and ATD400T controllers and cannot be changed.
The drive functions listed above can be assigned parameters, calibrated and configured on SIDOOR ATD410W, ATD420W and SIDOOR ATD430W controllers. This is mainly done using the higher-level controller (parameter channel). Refer to the corresponding function descriptions for details of the parameters associated with the drive functions listed. You can find more detailed information about the parameters in Section Parameter assignment (ATD4xxW) (Page 170).
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
38 System Manual, 06/2016, A2B00096162-AN
The input signal wiring can be switched between two fixed configurations (see Digital input signals (Page 131)).
Page 39
Controllers
6.2.2

Light barrier

Description of function
Exception:
Connection and parameter assignment
SIDOOR AT40 / ATD400V / ATD400K (RELAY LB)
Note
The light barrier and implemented simultaneously.
SIDOOR ATD410W/ATD420W/ATD430W
Note
The light barrier signal is evaluated in the low (= not interrup
6.2 Drive functions
The input for the light barrier signal has the same function as the DOOR OPEN command.
If the door is open less than 1 cm, the light barrier signal is ignored. If no power is supplied at the light barrier input, this is interpreted as an interruption of the light barrier. The door cannot then close.
If the light barrier signal is interrupted while the DOOR CLOSE command is active, the door is moved in the OPEN direction. An interruption of the light barrier signal while the DOOR CLOSE command is inactive does not change the state.
The light barrier signal can be connected via "Input 1" (X6). See also Section Digital input signals (Page 131). The connected signal must be activated via the SIDOOR Service Tool
Main menu > General setup > Special parameters > Input 1
(
DCPS (Door Closed Position Sensor) (Page 41) functions cannot be
The sensor signal must be generated by the PLC as part of the process image. See Table 6­75 DCMD expansion bits (Page 207).
).
The status of the sequential control must be considered when using the LB signal. The process data (including the LB signal) are only valid in the status "S4: Z_ operation" (see Image 6-33 Sequential control state graph (Page 216)). The LB signal is evaluated in the low-active state, but is not tested during the sensor function test.
When not in operating status "S4: Z_ operation" (see Image 6-33 Sequential control state graph (Page 216)), the sensor signals are automatically assigned their resting signal value so that they have no effect on the system status.
The travel range within which the controller reacts to the light barrier signal can be restricted by parameter p1210. See Calibration and function parameters (Page 175).
You can find more detailed information on the light barrier in Section Overview (Page 159).
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
-active state and must therefore be assigned 1
ted).
39
Page 40
Controllers
Signals
Signal
Description
Light barrier is not interrupted and the door closes when the DOOR CLOSE command is present
* The response of SIDOOR ATD4xxW controllers also depends on the particular system mode. See
the table below.
Mode
Response
Learn run mode
Learn run is canceled and the drive is deenergized.
stopped
active "Close" drive order.
Reverses
In positioning mode, the drive is stopped via a ramp down.
stopped
active "Close" drive order.
6.2 Drive functions
1 (voltage applied)
0 (voltage not applied) Light barrier is interrupted and the door opens when the DOOR
CLOSE command is present*
Table 6- 1 Response of SIDOOR ATD4xxW controllers to an interrupted light barrier
Initial mode The system is
Normal mode
order. The system response to an obstruction detected while reversing
can be configured accordingly. The following drive order can be defined with parameter p1211 (see Section Calibration and func­tion parameters (Page 175)).
Special mode The system is
the system in conjunction with the active "Close" drive
via a ramp down in conjunction with the
via a ramp down in conjunction with the
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
40 System Manual, 06/2016, A2B00096162-AN
Page 41
Controllers
6.2.3

Motion detector

Description of function
Connection and parameter assignment
Signals
Signal
Description
1 (voltage applied)
Signal present at motion detector
6.2.4

DCPS (Door Closed Position Sensor)

Description of function
6.2 Drive functions
If a signal is active at the input of the connected motion detector, the door opens according to the set driving curve as long as the command is active. If the door is opened less than 1 cm, the motion detector signal is ignored. The door reaches the OPEN position at creep speed. After expiry of the hold-open time, the door can be closed by an explicit close command. If the parameter "Hold-open time after motion detector" is set to 0 s, the door can be closed immediately by an explicit close command. If the door is opened less than 1 cm, the motion detector signal is ignored.
The motion detector signal is connected via "Input 1" (X6). See also Section Digital input signals (Page 131).
The following wait time in the OPEN position can be parameterized separately from the normal open time. The parameter assignment is set via the parameter "Hold-open time after motion detector".
0 (voltage not applied) No signal present at motion detector
DCPS stands for Door Closed Position Sensor or DOOR CLOSED sensor. The Door Closed Position Sensor is not a special sensor, but an open or closed contact as far as the controller is concerned. If the contact is closed, the door is in the CLOSED position. The user is responsible for the design of the contact.
The DCPS enables the door to travel in normal operation immediately after the line voltage is switched on without an initialization run. This requires the door to be in the CLOSED position when the power is switched on. This enables the controller to be completely switched off if the elevator is not going to be used for a lengthy period, for example during the night.
If the contact remains closed although the door has left its CLOSED position, the controller switches to initial operation after 10 cm, and continues the movement at initial speed. The door does not resume moving at normal speed until after it has traveled to both end positions.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
41
Page 42
Controllers
Connection and parameter assignment
Note
The light barrier and DCPS functions cannot be implemented simultaneously.
Signals
Signal
Description
1 (voltage applied)
Door is in the CLOSED position
0 (voltage not applied)
Door is not in the CLOSED position
6.2.5

DCOPS (door closed/opened position sensor)

Description of function
Example sequence when using DCOPS
6.2 Drive functions
The DCPS signal can be connected via "Input 1" of the terminal X6. See also Section Digital input signals (Page 131). The connected signal must be activated via the SIDOOR Service
Main menu > General setup > Special parameters > Input 1
Tool (
).
"DCOPS" stands for door closed/opened position sensor. A door closed/opened position sensor can consist of two end position sensors (closed/open).
The DCOPS enables the door to travel immediately after the line voltage is switched on without an initialization run in normal operation.
When the DCOPS signal is active in initial mode, the controller switches directly to normal mode with a corresponding "Open" or "Close" drive order when an obstruction (end stop) is detected. To prevent the erroneous detection of a blocking obstruction as an end stop, the DCOPS signal must not be activated until 1 to 2 cm before the respective end stop.
1. Power ON
2. Controller is in the initial mode. No fault present. The system is in any position along the travel path.
3. An "Open" or "Close" door command is present.
4. The system opens or closes.
5. The DCOPS signal is activated as from 2 cm before the respective end stop.
6. The system reaches the end stop and detects it as an "obstruction".
7. The system switches to the normal mode and assumes the applicable "open" or "closed" status.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
42 System Manual, 06/2016, A2B00096162-AN
Page 43
Controllers
Connection and parameter assignment
Note
The type simultaneously.
SIDOOR ATD410W/ATD420W/ATD430W
Note
Image
6.2 Drive functions
The DCOPS signal can be connected to SIDOOR ATD4xxW controllers via "Input 1" of the terminal X6. See also Section Digital input signals (Page 131).
The connected signal must be activated via the SIDOOR Service Tool (
General setup > Special parameters > Input 1
).
Main menu >
2 ESPE, pressure-sensitive edge and DCOPS functions cannot be implemented
The DCOPS signal can be sent as shown in Image 6-26 Sensor signals (Page 159), via the process image (see Table 6-75 DCMD expansion bits (Page 207)) and/or via the local sensor input ("Input 1" via p4600 - see Table 6-38 Other parameters (Page 172)).
The status of the sequential control must be considered when using the DCOPS signal
(process image). The process data is only valid in the "S4: Z_ operation" state (see 6-33 Sequential control state graph (Page 216)).
The light barrier and DCOPS functions can be implemented simultaneously by
connecting to a fieldbus system (process image).
The DCOPS, type 2 ESPE or pressure-sensitive edge functions cannot be implemented
simultaneously as sensor functions at input 1.
You can find more detailed information on DCOPS in Section Overview (Page 159).
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
43
Page 44
Controllers
6.2.6

Type 2 ESPE

Function description
Connection and parameter assignment
Note
The DCOPS, type simultaneously as sensor functions at input
6.2 Drive functions
A light array / light curtain is the part of the electro-sensitive protective equipment (ESPE) that is connected to the machine controller and assumes a defined state when the sensing device is triggered during intended use.
A type 2 ESPE can be connected to SIDOOR ATD4xxW controllers via "Input 1" of the terminal X6.
If the SIDOOR controller's sensor logic is configured for ESPE, the "TestOUT" function test signal is output automatically at the terminal X100.1. See Section Sensor function test (Page 162).
The sensor type of the sensor connected to "Input 1" of terminal X6 can be configured as follows:
● Parameter p4600
Service menu:
The travel range within which the controller reacts to the OSSD signal can be restricted by parameter p1210 (see Section Calibration and function parameters (Page 175)).
You will find a circuit diagram and detailed information about the connection of a type 2 ESPE in Section Type 2 ESPE (Page 160).
MAIN MENU > General setup > Special parameters > Function Input 1
2 ESPE or pressure-sensitive edge functions cannot be implemented
1.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
44 System Manual, 06/2016, A2B00096162-AN
Page 45
Controllers
Signals
Signal
Description
1 (voltage applied)
Light curtain is not interrupted.
* The response of SIDOOR ATD4xxW controllers also depends on the particular system mode. See
the table below.
Mode
Response
Learn run mode
Learn run is canceled and the drive is deenergized.
stopped
"Close" drive order.
Reverses
In positioning mode, the drive is stopped via a ramp down.
stopped
"Close" drive order.
6.2 Drive functions
0 (voltage not applied) Light curtain is interrupted*.
Table 6- 2 Response of SIDOOR ATD4xxW controllers to an active light curtain signal
Initial mode The system is
Normal mode
The system response to an obstruction detected while reversing can be configured accordingly. The following drive order can be defined with parameter p1211 (see Section Calibration and function parameters (Page 175)).
Special mode The system is
the system in conjunction with the active "Close" drive order.
via a ramp down in conjunction with the active
via a ramp down in conjunction with the active
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
45
Page 46
Controllers
6.2.7

Pressure-sensitive edge (SR)

Function description
Connection and parameter assignment
Note
The DCOPS, type simultaneously as sensor functions at input 1.
6.2 Drive functions
The pressure-sensitive edge is connected to the machine control and assumes a defined state if the sensor device is addressed during proper operation.
The output signal switching device of the pressure-sensitive edge is connected to "Input 1" of the terminal X6.
If the SIDOOR controller's sensor logic is configured for a pressure-sensitive edge, the "TestOUT" function test signal is output automatically at the terminal X100.1. See Section Sensor function test (Page 162).
The sensor type of the sensor connected to "Input 1" of terminal X6 can be configured as follows:
● Parameter p4600
Service menu:
The travel range before the "Closed" position in which the controller responds to the pressure-sensitive edge's signal can be restricted by parameter p1210 (see Section Calibration and function parameters (Page 175)). The controller does not respond to the pressure-sensitive edge's signal in the range of ± 2 cm before the "Open" position.
You will find a circuit diagram and detailed information about connection of a pressure­sensitive edge in Section Pressure-sensitive edge (SR) (Page 161).
MAIN MENU > General setup > Special parameters > Function Input 1
2 ESPE or pressure-sensitive edge functions cannot be implemented
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
46 System Manual, 06/2016, A2B00096162-AN
Page 47
Controllers
Signals
Signal
Meaning
1 (high)
Pressure-sensitive edge is not interrupted and is fault-free.
* The response of SIDOOR ATD4xxW controllers also depends on the particular system mode. See
the table below.
Mode
Response
Learn run mode
Learn run is canceled and the drive is deenergized.
stopped
deenergized
junction with the active drive order.
20 cm
stopped
deenergized
stopped
deenergized
down.
Special mode
No response
6.2.8

Gate interlocking

Description of function
Signals
Signal
Description
1 (voltage applied)
Gate interlocking is active
0 (voltage not applied)
Gate interlocking is not active
6.2 Drive functions
0 (low) Pressure-sensitive edge is interrupted or defective*.
Table 6- 3 Response of SIDOOR ATD4xxW controllers to an active pressure-sensitive edge signal
Initial mode The system is
Normal mode The system reverses by
If the gate interlocking is active, the controller does not accept any control commands.
and then
The drive is during reversing.
In positioning mode, the drive is
and then
via a ramp down in con-
in conjunction with the active drive order.
if an obstruction is detected
and
via a ramp
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
47
Page 48
Controllers
6.2.9

Door locked

Description of function
Connection
Signals
Signal
Description
1 (voltage applied)
Door interlocking is active
6.2 Drive functions
If the "Door locked" command is active, the door control system responds as follows:
The door drive is torque-free.
The incoming commands "DOOR OPEN" and "Motion detector" are not evaluated by the
controller.
The hold-open time is cancelled.
● The keyboard lighting is deactivated.
After the "Door locked" command is revoked, the door system becomes active again after a delay of 3 s. The door then moves in the CLOSE direction.
The "Door locked" function is connected to "Input 2" (X6). See also Section Digital input signals (Page 131).
0 (voltage not applied) Door interlocking is not active
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
48 System Manual, 06/2016, A2B00096162-AN
Page 49
Controllers
6.2.10

Nudge

Description of function
Connection
Signals
Signal
Description
activated at the same time. The reversing unit is deactivated.
0 (voltage not applied)
The nudge command is not present.
6.2.11

Stopping

Function description
6.2 Drive functions
If a "Nudge" command is present, the reversing unit is deactivated. The input signals CLOSE and NUDGE must be active so that the NUDGE operating state is only effective in the closing direction. When an obstruction is detected, the torque is reduced after 1 s to the motor's holding shut torque limit.
The "Nudge" function is connected to "Input 2" (X6). See also Section Digital input signals (Page 131).
The function is only active in conjunction with the CLOSE input signal.
1 (voltage applied) The nudge command is present if the DOOR CLOSE command is
See Table 6-10 SIDOOR door drive shutdown/deceleration functions (limited system) (Page 95).
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
49
Page 50
Controllers
6.2.12

Force and energy profiles (NDG mode)

Parameter assignment
Normal operation
NDG operation
Force limiting
p3683 "LimForceCls"
p3684 "LimForceEndCls"
Energy limiting
p1202 "KinEnergyLimCls"
p1203 "KinEnergyLimOp"
Speed limiting (influenced by energy limiting)
p3668 "MaxSpdCls"
p3664 "MaxSpdOp"
Drive order for profile switching
Switching profiles
Drive response in NDG mode
6.2 Drive functions
SIDOOR ATD4xxW controllers support two individually parameterizable force and energy profiles.
You can configure the following parameters equally via the parameter interface, the service tool and the terminal.
Table 6- 4 Force and energy profile parameter overview
p3682 "LimForceOp" p3685 "LimForceNdg"
p1204 "KinEnergyLimNdg"
p3672 "NdgSpd"
To switch to NDG mode, the DCMD expansion bit "NDG" must be set (see Table 6-75 DCMD expansion bits (Page 207)). In combination with an applicable DCMD drive order (see Table 6-74 DCMD signal (Page 206)), the drive travels with the NDG force and energy profile.
The drive switches over to the NDG force and energy profile when the corresponding drive order with expansion bit is active and the controller is in normal mode. If the NDG mode is activated or deactivated during travel, the system automatically stops with the configured braking ramp and continues moving with the applicable force and energy profile after having stopped.
Independent values, which are not influenced by the force and energy profiles described here, apply to force and energy limiting in the initial or learn run mode.
In NDG mode, all drive functions are supported without restriction.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
50 System Manual, 06/2016, A2B00096162-AN
Page 51
Controllers
6.2.13

Slow driving curve profile

Parameter assignment
Normal profile
Slow profile
Energy limiting
p1203 "KinEnergyLimOp"
p1204 "KinEnergyLimNdg"
(influenced by energy limiting)
p3668 "MaxSpdCls"
p3664 "MaxSpdOp"
p3672 "NdgSpd"
Drive order for profile switching
Switching profiles
Drive response
6.2 Drive functions
SIDOOR ATD4xxW controllers support a parameterizable, decelerated speed profile (slow profile), to which it is possible to switch over to flexibly.
You can configure the following parameters equally via the parameter interface, the service tool and the terminal.
Table 6- 5 Force and energy profile parameter overview
p1202 "KinEnergyLimCls"
Speed limiting
p3667 "SlowIniSpdOp" p3671 "SlowIniSpdCls"
To switch to the slow profile, the DCMD expansion bit "slow" (see Table 6-75 DCMD expansion bits (Page 207)) must be set. In combination with an applicable DCMD drive order (see Table 6-74 DCMD signal (Page 206)), the drive switches to the slow profile.
The drive switches over to the slow profile when the corresponding drive order with expansion bit is active and the controller is in normal mode. The slow profile can be activated or deactivated dynamically during travel. The system accelerates or brakes the drive automatically to the slow profile's speed according to the configured ramps.
Independent values, which are not influenced by the speed parameters described here, apply to the speed in the initial or learn run mode.
When the slow profile is active, all drive functions are supported without restriction.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
51
Page 52
Controllers
6.2.14

Automatically delayed motion

Description of function
SIDOOR ATD400T
SIDOOR ATD400S and SIDOOR ATE250S
Parameter assignment
SIDOOR ATD400T
SIDOOR ATD400S and SIDOOR ATE250S
6.2 Drive functions
If the "Open" / "Close" command is present, relay X13 is activated, and the door is not opened / closed until the preset timer "Time delay before movement" expires.
If the "Open" command is present, relay X11 is activated, and the door is not opened until the time delay of 250 ms expires.
The function can be activated with the SIDOOR Service Tool by setting a time for the parameter "Time delay before movement". If the parameter "Time delay before movement" is set to 0 ms, then the function is deactivated and the door is opened / closed without the timer.
The delay time is a fixed preset and cannot be parameterized.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
52 System Manual, 06/2016, A2B00096162-AN
Page 53
Controllers
6.2.15

Cord-operated switch

Description of function
Connection
Signals
Signal
Description
1 (voltage applied)
The cord-operated switch command is present and the door opens
closes
6.2 Drive functions
The cord-operated switch command has the same function as the GATE OPEN command. However, it also offers the option of partial opening. "Opening width in percent" and "Hold­open time cord operated switch" can be set in the Special parameters menu. The cord­operated switch command remains present until a new input signal is activated or the "Hold­open time cord operated switch" expires.
The "Nudge" function is connected to "Input 2" (X6). See also Section Digital input signals (Page 131).
0 (voltage not applied) The cord-operated switch command is not present and the door
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
53
Page 54
Controllers
6.2.16

DOOR CLOSE (command given via digital inputs)

Description of function
Exception ATD400K
Note
If the commands DOOR CLOSE and DOOR OPEN are present simultaneously, the door always
Exception SIDOOR ATD400S and SIDOOR ATE250S: the highest priority over all other control commands.
SIDOOR ATD410W/ATD420W/ATD430W
Note
As an alternative, the signal can also be evaluated via the PLC (process image).
Connection
Signals
Signal
Description
1 (voltage applied)
The DOOR CLOSE command is present
0 (voltage not applied)
The DOOR CLOSE command is not present
6.2 Drive functions
The DOOR CLOSE command must remain present continuously in order to close the door. After the door has closed, it is held in this position by the torque that can be adjusted by the parameter "Continuous torque CLOSE" as long as the command remains present.
arrives.
See also Section Free function blocks (FBLOCK) (Page 87).
: The DOOR CLOSE command remains present until a new input signal
moves in the OPEN direction.
The DOOR CLOSE command has
The "DOOR CLOSE" function is connected to "Input 3" (X6). See also Section Digital input signals (Page 131).
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
54 System Manual, 06/2016, A2B00096162-AN
Page 55
Controllers
6.2.17

DOOR OPEN (command given via digital inputs)

Description of function
Exceptions:
SIDOOR ATD400K:
SIDOOR ATD400S and SIDOOR ATE250S:
Note
If the commands DOOR CLOSE and DOOR always moves in the OPEN direction.
SIDOOR ATD410W/ATD420W/ATD430W
Note
As an alternative, the signal can also be evaluated via the PLC (process image).
Connection
Signals
Signal
Description
1 (voltage applied)
The DOOR OPEN command is present
0 (voltage not applied)
The DOOR OPEN command is not present
6.2 Drive functions
The DOOR OPEN command opens the door according to the set driving curve as long as the command is present. The door reaches the OPEN position at creep speed. Then, if the DOOR OPEN command is present, the door is held open by the torque that can be adjusted by the parameter "Continuous torque OPEN".
The DOOR OPEN command has priority over all other control commands.
command.
highest priority over all other control commands.
The DOOR OPEN command has no priority over any other control
The DOOR CLOSE command has the
OPEN are present simultaneously, the door
See also Section Free function blocks (FBLOCK) (Page 87).
The "DOOR OPEN" function is connected to "Input 3" (X6). See also Section Digital input signals (Page 131).
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
55
Page 56
Controllers
6.2.18

Partial opening

Description of function
Requirements for partial opening mode
Connection and parameter assignment
SIDOOR ATD401W
SIDOOR ATD410W/ATD420W/ATD430W
6.2 Drive functions
A second open position can be implemented using the "partial opening" drive function. A "partial opening" describes an opening movement with a set curve profile up to the partial opening position.
When partial opening is active, the learned or real door width is replaced with the parameterized partial opening width. All drive functions are supported in partial opening mode (e.g. curve profile, force and energy limiting, obstruction detection, etc.). Activating positioning mode overwrites partial opening mode.
If the drive is in the area between the first and second open positions when partial opening mode is activated, this is detected as an invalid area. In this area, the controller reduces the drive's speed automatically. The normal curve profile becomes active again as soon as the drive has moved out of the invalid area or has exited partial opening mode. The scenario described is not to be evaluated as a fault or an invalid situation.
The continuous torque in the opening direction is not applied at the virtual end stop of the second open position. The drive is stopped as long as the open command is present (winding short-circuited "source voltage brake").
The drive can only switch to partial opening mode if the corresponding drive order with expansion bit is active and the following conditions are met:
● The controller is in normal mode
● The drive is at a stop
Partial opening mode can only be terminated actively (reset of the DCMD expansion bit "partial") at standstill, but is terminated automatically if the controller switches to initial or learn run mode.
The partial opening width can be configured via the driving parameters or the terminal module (
The "Partial opening" function is connected to "Input 2" of terminal X6. See also Section Digital input signals (Page 131).
The partial open width is defined via the parameter p1206. See Section Calibration and function parameters (Page 175).
Main menu > General setup > Special parameters > Partly open width
).
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
56 System Manual, 06/2016, A2B00096162-AN
Page 57
Controllers
6.2.19

Restart after power failure

Description of function
SIDOOR ATD400T - Error response during the initialization run
SIDOOR ATD410W/ATD420W/ATD430W
6.2.20

Overload protection

Description of function
SIDOOR AT40
SIDOOR ATD4xxW
6.2 Drive functions
After a power failure, the controller has to redetermine the end positions of the door travel. To do this, the door travels at reduced speed (initial speed) until the controller has detected the OPEN and CLOSED end positions. The door then resumes traveling at normal speed.
The door travels at normal speed immediately if the DCPS (see Section DCPS (Door Closed Position Sensor) (Page 41)) or DCOPS (see Section DCOPS (door closed/opened position sensor) (Page 42)) is installed. In this case, the door must be in the CLOSED position for the restart.
During the initialization run, five attempts are made to travel through the stored door width. An error case is signaled by error "P.", and the door remains stationary in the presumed "closed" position.
After Power ON, the sequential control system is in the "S1: Switching On Inhibited" mode (see Image 6-33 Sequential control state graph (Page 216)).
If the drive motor placed under a high load with frequent DOOR OPEN and DOOR CLOSE commands in quick succession, the hold-open time is automatically lengthened. The next closing movement is delayed even if a DOOR CLOSE command is present, the 7-segment display (H401)/digital display (H1) shows "4". This function prevents thermal overloading of the motor.
Reversing the direction of rotation or restarting the controller several times puts a disproportionate strain on the drive motor.
The controller switches to motor protection mode for 30 seconds and does not accept any door commands. This state is signaled by a "4" on the 7-segment display (H401)/the digital display (H1).
This function prevents thermal overloading of the motor.
The fault "4" is generated if the drive is moved continuously in one direction for more than 65 s. This is intended to prevent thermal overloading of the motor. This can only arise in the event of extremely high levels of system friction, at maximum door width.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
57
Page 58
Controllers
6.2.21

Vandalism protection/continuous door monitoring

Description of function
SIDOOR ATD410W/ATD420W/ATD430W
Parameter assignment
SIDOOR ATD410W/ATD420W/ATD430W
6.2 Drive functions
The vandalism protection/continuous door monitoring function offers protection against undesired external system motion. If the motor is deenergized, the motor speed is monitored by the controller.
If the maximum speed of 250 mm/s is exceeded, the controller actively decelerates the motor to 50 mm/s, and then switches the drive back to "deenergize".
If the maximum configurable speed (p1200) is exceeded, the controller actively decelerates the motor to 50 mm/s, and then switches the drive back to "deenergize".
The "Continuous door monitoring" function is pre-installed and activated, and can be deactivated if necessary with parameter p1200. This is done by setting the value of parameter p1200 to "0". See Table 6-40 Calibration and function parameters (Page 175).
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
58 System Manual, 06/2016, A2B00096162-AN
Page 59
Controllers
6.2.22

Obstruction detection

6.2.22.1
Obstruction detection CLOSE
Description of function
SIDOOR ATD400S / ATE250S
SIDOOR ATD400T
SIDOOR ATD4xxW
6.2 Drive functions
If the door is obstructed in the CLOSE direction with a DOOR CLOSE command present, the door stops and reverses direction. After reaching the OPEN position, the door closes again at normal speed to within about 2 cm of the obstruction. It then travels at reduced speed (initial speed) against the obstruction before reversing again. This function is repeated continuously, as long as the obstruction remains. Once the obstruction has been cleared, the door travels at reduced speed to approximately 2 cm past the stored position of the obstruction, and then continues the rest of the way at normal closing speed.
If the door is obstructed in the CLOSE direction with a DOOR CLOSE command present, the door presses against the obstruction with the set closing force. If the obstruction remains present for more than one second, then the ATD400S controller reduces the motor current to the rated current of the motor, and the force is reduced correspondingly. The ensuing force is never greater than 150 N. This function is repeated continuously as long as the obstruction remains present. Once the obstruction has been cleared, the door travels at reduced speed to approximately 2 cm past the stored position of the obstruction, and then continues the rest of the way at normal closing speed.
If the door is obstructed in the CLOSE direction with a DOOR CLOSE command present, the door stops and reverses direction. After reaching the OPEN position, the door closes again at normal speed to within about 2 cm of the obstruction. It then travels at reduced speed (initial speed) against the obstruction before reversing again.
This function is repeated as many times as specified in the parameter "Number of obstruction CLOSE retries before wait mode". During this time the obstruction is detected at the same position ± 3 cm.
The door then remains stationary in this position. An OPEN signal cannot be accepted as an external door command. A "completed" signal is then output on the keyboard lighting.
After the time specified by the parameter "Time delay in wait mode CLOSE" another attempt is made to move in the CLOSE direction. This function is repeated continuously, as long as the obstruction remains.
Once the obstruction has been cleared, the door travels at reduced speed to approximately 2 cm past the stored position of the obstruction, and then continues the rest of the way at normal closing speed.
See Section SIDOOR ATD4xxW obstruction detection (Page 61).
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
59
Page 60
Controllers
6.2.22.2
Obstruction detection OPEN
Description of function
Exceptions: SIDOOR ATD400S / ATE250S
SIDOOR ATD4xxW
6.2 Drive functions
The door stops if it is obstructed in the "OPEN" direction when the DOOR OPEN command is present. After approximately 2 s, the door automatically tries to reach the OPEN position again. This action is repeated a maximum of 3 times. The door then remains stationary in this position. If the DOOR OPEN command is canceled, the close command given, and the DOOR OPEN command is then repeated, the door travels at normal speed to within about 2 cm of the stored position of the obstruction, and then up to the obstruction at reduced speed. The door drive stops at the obstruction, and the opening action is repeated another 3 times. If the obstruction has been removed beforehand, the door travels at reduced speed to approximately 2 cm past the stored position of the obstruction, and then continues to the OPEN position at normal speed.
If the door is obstructed in the OPEN direction with a DOOR OPEN command present, the door presses against the obstruction with the set opening force. If the obstruction remains present for more than one second, then the SIDOOR ATD400S controller reduces the motor current to the rated current of the motor, and the force is reduced correspondingly. This function is repeated continuously, as long as the obstruction remains.
Once the obstruction has been cleared, the door travels at reduced speed to approximately 2 cm past the stored position of the obstruction, and then continues the rest of the way at normal closing speed.
See Section SIDOOR ATD4xxW obstruction detection (Page 61).
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
60 System Manual, 06/2016, A2B00096162-AN
Page 61
Controllers
6.2.22.3
SIDOOR ATD4xxW obstruction detection
Description of function
SIDOOR ATD401W (SIDOOR ATD4xxW factory default, firmware version 1.03 or higher)
SIDOOR ATD410W/ATD420W/ATD430W (up to firmware version 1.03)
in the opening direction
in the closing direction
Note SIDOOR ATD4xxW obstruction detection (firmware version 1.03 or higher)
The behavior of the obstruction detection of ATD4xxW controllers corresponds to that of the SIDOOR ATD401W controller.
The factory controllers is parameterizable.
The factory parameterizable.
6.2 Drive functions
If the controller detects an obstruction in the opening or closing direction with the aid of obstruction detection, it reverses once by 20 cm, starts an attempt to retract and then switches to wait mode. Slow obstruction approach, force obstruction detection and stop obstruction detection are active.
If the controller detects an obstruction
detection, three retries are initiated, each offset by 2 s.
If the controller detects an obstruction
detection, it reverses by 20 cm and starts an attempt to retract. This operation is repeated twice and is offset by 2 s in each case.
The controller then switches to wait mode. Slow obstruction approach, force obstruction detection and stop obstruction detection are active in both cases.
by means of obstruction
by means of obstruction
-set obstruction behavior of SIDOOR ATD410W, ATD420W and ATD430W
-set obstruction behavior of the SIDOOR ATD401W controller is not
A detected obstruction is signaled by the DBLOCK signal (see Table 6-83 DBLOCK signal (Page 211)).
The subsequent response to a detected obstruction depends on the user-defined parameter assignment. The following properties can be configured separately for the opening and closing directions:
● Obstruction detection
● Direct response
● Behavior following an obstruction
Basically, the same parameters are available for both drive directions. This means that either the same or different obstruction behavior can be configured for each direction.
The obstruction detection is a dynamic system that responds as a function of both position and time. The obstruction detection is dynamically activated or deactivated according to these dependencies. You will find more detailed information in Section Expert configuration (Page 64).
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
61
Page 62
Controllers
Obstruction detection process
Force obstruction detection
Stop obstruction detection
Overcome obstruction
Example
Parameter assignment
6.2 Drive functions
The obstruction detection is based on two processes that are independent of the direction: force obstruction detection and stop obstruction detection.
The following definitions are based on the speeds and are thus independent of the direction.
The obstruction detection systems assume that the system is actively being moved (drive order).
The current speed is > 90 mm/s, and drops by more than 90 mm/s in comparison to the maximum speed reached during the current movement.
If the system then moves for the set duration (p3854 and/or p3871) at the upper force limitation, a force obstruction is detected in the current drive direction.
If the current speed is less than 10 mm/s for the set duration (p3853 and/or p3870), a stop obstruction is detected in the current drive direction.
The overcome obstruction system can be used to overcome a blocking obstruction by repeated pushing. The system remains active as long as the initial drive order is not actively changed.
1. The drive order "close" is present.
2. The system closes.
3. An obstruction is detected before the end stop "closed" is reached.
4. The second of four retries is made.
5. The drive order "close" is overwritten by any other drive order.
6. The retry system is immediately exited.
7. The system responds according to the new drive order.
The number of retries to overcome the obstruction can be set in parameter p3860 or p3877. If the number is set to "0", the overcome obstruction system is disabled in the corresponding direction.
A variable waiting time can be configured before each retry (p3861 or p3878).
The type of drive control during this wait time can be "stop" or "deenergize" (p3862 or p3879).
After the configured number of retries have been made, wait mode is activated (see the following Section "Wait mode"). A following drive order can also be configured, which is activated at the same time as the switch to wait mode (p3863 or p3880).
While the retry system is active, any external change to a drive order (see Table 6-74 DCMD signal (Page 206)) immediately ends all open retry actions (including the cancelation of wait mode).
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
62 System Manual, 06/2016, A2B00096162-AN
Page 63
Controllers
Reversing (Retraction attempt)
Parameter assignment
Note
A reverse due to a drive order being changed is part of the basic software, and is not
affected by the reversing on account of an obstruction described here (Open → Close, Close → Open).
Combination of retry and reverse
6.2 Drive functions
When an obstruction is detected, the obstruction reversing system can be used to initiate an immediate full or partial reverse - a retraction attempt. This system is simply termed "reverse". The system remains active as long as the initial drive order is not actively changed. You can find an example of this in Section Overcome obstruction (Page 62).
The number of reversals (retraction attempts) can be defined in parameters p3864 and p3881. If the number is set to "0", the obstruction reversing system is disabled in the corresponding direction.
A variable wait time can be configured (p3865 and p3882) after each retraction attempt (on reaching the corresponding reverse target position). The drive remains stopped during the wait time.
The reversing distance or the type of reverse (full or partial reverse) can be configured to an accuracy of ±2 cm in parameters p3866 and p3883.
If the system is obstructed while reversing, all still open reversing actions are immediately ended, and wait mode is activated (see Wait mode (Page 64)). A following drive order can also be configured in parameters p3867 and p3884, which is activated at the same time as the switch to wait mode.
After the configured number of reversing operations/retraction attempts have been made, wait mode is activated (see Wait mode (Page 64)). A following drive order can also be configured, which is activated at the same time as the switch to wait mode (p3868 and p3885).
While the obstruction reversing system is active, any change in an external drive order (see Table 6-74 DCMD signal (Page 206)) immediately ends all open reversing actions (including the cancelation of wait mode).
The reverse and retry systems can be combined. The combination is subject to the following rules:
A reverse is made after executing the configured number of retries. The action is
repeated for the number of configured reverses.
● Parameters p3863 and p3880 have no effect when reversing is activated.
● Wait mode becomes active after the last reverse.
If the number of retries and reversing operations is set to "0", the "retry" following drive
order has a higher priority than the "reverse" drive order.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
63
Page 64
Controllers
Slow obstruction approach
Wait mode
Note
If the parameters p3860 and DBLCWAIT becomes active immediately after an obstruction is detected.
Expert configuration
Parameter assignment
Function configuration
Lead times
Range restriction
before reaching
after leaving
before
after
6.2 Drive functions
The position of the last obstruction in the drive direction is automatically stored in the system. The speed is automatically reduced to the corresponding creep speed (p3670 or p3666) on approaching this position. The system calculates a braking ramp so that the reduced speed is reached at the set distance (parameter p3855 or p3872) from the stored position of the obstruction. If the obstruction can be overcome, the system adjusts the speed after the same distance back to the "normal" driving curve.
Slow obstruction approach can be activated or deactivated for each drive direction in parameter p3850.
Wait mode is activated according to the configurations of the overcome obstruction system and the obstruction reversing system. If the system is in wait mode, this is ended any external change to a drive order. Wait mode is signaled by the process data signal "DBLCWAIT" (see "Table 6-84 DBLCWAIT signal (Page 211)").
The obstruction detection system has been designed so that it can be adapted to the widest range of system environments, structures and properties. The following parameters are mainly provided for such adaptations, and have to be changed for standard systems.
p3864, or p3877 and p3881 are set to "0", the signal
Stop and force obstruction detection can be deactivated for each drive direction in parameter p3850 (bits 0 and 1, and 4 and 5 respectively). The counting of obstructions can also be suppressed for each drive direction (bits 2 and 5).
After a drive order is changed or the direction of motion is reversed, the obstruction detection is activated after a variable ON-delay time (p3852 and p3869).
Obstruction detection is suppressed in a variable range
the relevant end
stop (p3856 and p3873).
It is also suppressed
the relevant end stop (p3857 and p3874).
Force obstruction detection, in particular, is suppressed and p3875). It is suppressed in a variable range p3876).
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
64 System Manual, 06/2016, A2B00096162-AN
the creep distance (p3858
the last obstruction (p3859 and
Page 65
Controllers
6.2.23

ImpulseDrive

Description of function
Parameter assignment
Note
Configuring ImpulseDrive detection directly affects the au automatic AssistedDrive and the automatic AssistedStop system.
Requirements for ImpulseDrive detection
Distance-based ImpulseDrive analysis
6.2 Drive functions
The ImpulseDrive analysis process detects and evaluates external impulses applied to the door system (for example, slight force exerted on the door in the opening or closing direction).
In conjunction with the automatic ImpulseDrive system (see Section Automatic ImpulseDrive (Page 66)), a heavy door can be set in motion by applying a slight force to the door handle or door frame.
When the process detects an external impulse, corresponding status information (see Table 6-87 IMPDRVIncr signal (Page 212) and Table 6-88 IMPDRVVelo signal (Page 212)) is generated.
The ImpulseDrive detection properties can be individually parameterized to enable adaption to different door systems.
The detection algorithm consists of a distance and a speed component. The sensitivity levels of both components can be parameterized separately (p1221 and p1222). A parameterizable lead time (p1220) is added to the detection algorithm to prevent problems caused by the spring effects of sealing or rubber lips.
See Table 6-40 Calibration and function parameters (Page 175).
tomatic ImpulseDrive, the
● Parameters are matched to the target system
● Controller is not in learn run
Drive command is "deenergize" ("DCMD := 0")
● No obstruction has been detected in the detected direction of motion
The analysis is based on the increments of the motor encoder in relation to an internal reference value. This reference value is always specified when the door command is changed to "deenergize" within the "S4: Z_operation" system state (see Image 6-33 Sequential control state graph (Page 216)) and the lead time (p1220) has expired.
The sensitivity level can be specified in parameter p1221. The higher it is, the higher the number of increments counted before the signal IMPDRVInc changes to high (active).
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
65
Page 66
Controllers
Speed-based ImpulseDrive analysis
6.2.24

Automatic ImpulseDrive

Function description
Note
The configuration of ImpulseDrive detection directly affects the automatic ImpulseDrive system.
6.2 Drive functions
The analysis is based on the increments of the motor encoder or the actual speed derived from it. The evaluation is only made in the "S4: Z_operation" system state (see Image 6-33 Sequential control state graph (Page 216)) after the door command has been changed to "deenergize" and the lead time (p1220) has expired.
Both analyses use a sign to distinguish the directions.
The automatic ImpulseDrive system generates a drive order based on ImpulseDrive detection.
If the ImpulseDrive analysis process detects an external impulse, the automatic ImpulseDrive system generates a drive order with a normal drive profile. Both ImpulseDrive detection output signals, IMPDRVVelo and IMPDRVIncr, are evaluated. If an enable command is present, the automatic system initiates opening or closing with a normal drive profile.
The automatic ImpulseDrive can only be used with an active enable. The enabling signal (DCMD := 7) is an element of the DCMD signal (see Table 6-74 DCMD signal (Page 206)).
Image 6-1 Automatic ImpulseDrive system
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
66 System Manual, 06/2016, A2B00096162-AN
Page 67
Controllers
6.2.25

ImpulseStop

Function description
Parameter assignment
6.2 Drive functions
The ImpulseStop analysis process detects and analyzes external forces acting on the door system/drive system.
In conjunction with the automatic ImpulseStop system (see Section Automatic ImpulseStop (Page 68)), a door can be stopped with a light tug against the direction of travel.
The process signals when an external opposing force (force with an opposite direction vector to that of the door movement) acts on the door or the drive. It is signaled by the ASStp signal (see Table 6-90 ASStp signal (Page 213)).
The detection properties of ImpulseStop can be individually parameterized, thus enabling the feature to be adapted to different door systems. The limit values for detecting an external opposing force can be specified for each drive direction with the following parameters:
● p1240 in the opening direction
● p1241 in the closing direction
The parameters define a proportion of the learned reference value for each direction. This proportion is added to the reference value, and thus forms the limit value for detecting ImpulseStop.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
67
Page 68
Controllers
6.2.26

Automatic ImpulseStop

Function description
Note
Configuring ImpulseDrive analysis and detection system.
Note
The automatic ImpulseStop is a dynamic function. It can be enabled and disabled during a door movement.
6.2 Drive functions
The automatic ImpulseStop system is an expansion of the automatic ImpulseDrive system. This means that all the properties, configurations and preconditions defined for it are also applicable here.
The system can be activated by the "ImpulseStop" expansion bit (see Table 6-75 DCMD expansion bits (Page 207)) in conjunction with automatic ImpulseDrive enabling (see Table 6-74 DCMD signal (Page 206)).
If the "ImpulseStop" expansion bit is active, the automatic ImpulseDrive system works in the slow drive profile. The drive orders "slow open" and "slow close" are generated instead of "open" and "close" respectively. The active drive order is canceled ("deenergized") as soon as the ImpulseStop analysis/detection signals a corresponding opposing force (the rising signal edge is decisive).
directly affects the automatic ImpulseStop
Image 6-2 Automatic ImpulseStop system
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
68 System Manual, 06/2016, A2B00096162-AN
Page 69
Controllers
6.2.27

AssistedDrive

Function description
Parameter assignment
Note
The config system.
Prerequisites for AssistedDrive
Initial mode
Normal mode
Slow drive profile
6.2 Drive functions
AssistedDrive is an analysis process that detects and analyzes external forces acting on the door or drive system.
In conjunction with the automatic AssistedDrive system (see Section Automatic AssistedDrive (Page 70)), a door can be moved with motor assistance without the need for buttons or sensors.
AssistedDrive signals (see Table 6-89 ASDRV signal (Page 213)) whenever an external assisting force (force with the same direction vector as that of the door movement) acts on the door or the drive.
The detection properties of AssistedDrive can be individually parameterized, thus enabling the feature to be adapted to different door systems. The thresholds for the detection of external opposing forces can be specified for each drive direction with the following parameters:
● p1231 in the opening direction
● p1232 in the closing direction
The "slow" speed profile is adjusted with both of the following driving parameters:
● p3666 in the opening direction
● p3669 in the closing direction
See Table 6-37 Driving parameters (Page 171).
uration of AssistedDrive detection directly affects the automatic AssistedDrive
AssistedDrive detection is only active during the following internal system states:
(closing, closed, opening and open)
(closing, partial closure, closed, opening, partial opening and open)
(DCMD – expansion bit "slow", see Table 6-75 DCMD expansion bits
(Page 207))
If the system switches into one of the three system states, the signal ASDrv is always set to active. The actual threshold analysis of the motor current starts after the parameterized switch-off delay (p1230) and as soon as the value of the square of the difference between the setpoint and actual speeds falls below 70 mm/s.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
69
Page 70
Controllers
Note
The falling edge of the ASDRV signal can only be reached when the difference between the setpoint and actual speeds falls below the defined value. Therefore a speed and/ adjustment of the system may be required.
6.2.28

Automatic AssistedDrive

Function description
6.2 Drive functions
The result of the analysis is output by the signal state ASDrv. The falling signal edge therefore indicates that the assisting force has become too low. Assisted mode can be exited. This signal is independent of the drive direction.
or force
The automatic AssistedDrive system is composed of both the ImpulseDrive and AssistedDrive detection systems.
On the one hand, ImpulseDrive is used to generate a corresponding drive order with a normal drive profile. On the other hand, the drive order is canceled ("deenergized") with the aid of AssistedDrive.
To do this, automatic AssistedDrive evaluates the edges of the IMPDRVIncr, IMPRDRVVelo and ASDR signals.
The automatic AssistedDrive system can only be used with an active enable. The enabling signal for the automatic AssistedDrive system (DCMD := 6) is an element of the DCMD signal (see Table 6-74 DCMD signal (Page 206)). This ensures the unambiguity of the active drive order at all times.
Image 6-3 Automatic AssistedDrive system
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
70 System Manual, 06/2016, A2B00096162-AN
Page 71
Controllers
Note
After the automatic AssistedDrive system has canceled a drive order on account of an inadequate assisting force, ImpulseDrive detection becomes active again. ImpulseDrive lead time (p1220) must be taken into account. It directly affects the signal chain of the automatic AssistedDrive system.
Note
Configuring ImpulseDrive and AssistedDrive detection directly affects the automatic AssistedDrive
6.2.29

Initial run/reference run (Power ON)

Description of function
speed
Force limitation
Using an end position sensor
6.2 Drive functions
However, the
system.
After Power ON, the controller is in initial mode. Initial mode is necessary because there is no absolute value encoder. After Power ON, the controller must therefore verify the end stops that have been previously learned (= reference run). As long as both end stops have not been verified by reaching them, the drive only moves with a decelerated travel profile (initial travel profile). Force limitation is active in accordance with the learned parameters (friction compensation is active).
The
After Power ON, the sequential control system is in the "S1:Z_switching on inhibited" state (see Sequential control (Page 216)).
You can skip initial mode by connecting a DCOPS end position sensor (Door Closed/Opened Position Sensor). Depending on the application, 1 end position sensor can be used in the open or closed position or 2 end position sensors can be used in both end positions. The responsibility for verification of the learned end positions is thus transferred to the user (see Section DCOPS (door closed/opened position sensor) (Page 42)).
of the initial run is defined by the parameters p3667 and p3671.
during the initial run is defined by the parameters p3682 and p3683.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
71
Page 72
Controllers
6.2.30

Positioning mode

NOTICE
Obstruction detection
Activation
Sensors
Motor protection
6.2 Drive functions
Positioning mode serves to absolutely position the drive. The positioning system calculates a travel profile for the optimum movement of the drive to the required target position on the basis of the driving parameters and the current distance from the target position. Positioning mode does not include any position control and operates with an accuracy of 1 cm. The source voltage brake is activated once the target position has been reached. After the target position has been reached, the door can be moved ±2 cm out of the target position before the drive returns to the target position. The positioning system operates with hysteresis. The drive responds dynamically (including reversing) to changes in the target position data while keeping to the values parameterized for force and energy limiting.
The obstruction detection system (see Section Obstruction detection (Page 59)) is not active in positioning mode.
Positioning mode can only be activated from normal mode and at standstill via the "positioning" door command. It can be modified by the "NDG" and "slow" door command extensions. The target position is transferred as the DESTPOS signal (see Table 6-77 DESTPOS signal (Page 207)) in technology control word 2 (TSW2) of the process image. The target position is automatically limited to the learned door boundaries.
Sensor signals are evaluated in positioning mode. You will find the response of the controller/drive to the applicable sensor signals in Section Type 2 ESPE (Page 44) or Pressure-sensitive edge (SR) (Page 46).
To protect the motor, a monitoring function is active that switches off (deenergizes) the drive if the specified target position cannot be reached, e.g. due to an obstruction.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
72 System Manual, 06/2016, A2B00096162-AN
Page 73
Controllers
6.2.31

Belt break monitoring

Description of function
Mode
Controller
Distance
Initial operation
SIDOOR ATD4xxW
50 cm (p1201)
SIDOOR ATD400T
50 cm
Normal operation
SIDOOR ATD4xxW
50 cm (p1201)
SIDOOR ATE250S
10 cm
SIDOOR ATD400T
50 cm
Parameter assignment
SIDOOR ATD4xxW
6.2 Drive functions
The function detects a torn belt. The detection is active in normal mode and initial mode.
A torn belt is detected when the door movement exceeds the defined distance* (in the opening or closing direction).
* The distance is defined as follows:
SIDOOR ATE250S 10 cm
Max. door width +
Learnt door width +
Belt break detection is suppressed if parameter p1201 is set to "0". In this case, there is no fault or fault reaction on the part of the controller.
The status code "t" signals a torn belt. The controller changes to the "S6: Z_Fault" status (see Image 6-33 Sequential control state graph (Page 216)).
If the parameter set of the controller is invalid, the maximum possible door width of 5 m is used as the door width.
See Table 6-40 Calibration and function parameters (Page 175).
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
73
Page 74
Controllers
6.2.32

Emergency power mode

Description of function
Parameter assignment
SIDOOR ATD410W/ATD420W/ATD430W
Signals
Signal
Meaning
1 (voltage applied)
Emergency power mode active
6.2 Drive functions
If the line voltage fails, the connected emergency power module sends a signal to the controller. The speed-reduced driving curve profile (slow open und slow close) is automatically used in emergency power mode. Emergency power mode cannot be exited until the controller has reached the closed or open state in normal mode.
By way of the factory default, the "emergency power mode" function block is already linked to Input 0 (terminal X5 – "Accumulator Mode").
Emergency power mode is mapped as a special function block and can be linked dynamically as required. See Section Free function blocks (FBLOCK) (Page 87).
0 (voltage not applied) Emergency power mode not active
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
74 System Manual, 06/2016, A2B00096162-AN
Page 75
Controllers
6.2.33

Friction compensation

Description of function
Recording of measurement data
in the opening direction
in the closing direction
Calculations
Note
The friction force is not taken into account in the parameterized torques p3679, p3680 an
6.2 Drive functions
The friction force profile of the door system is recorded with the current measuring device of the controller. The measurement data for both the opening and closing directions is recorded during the learn run.
The recording of measurement data because the door movement is not constant throughout the total range. The ranges are:
Travel path ≤ 25 cm
– The measurement data in this range are recorded in the second opening movement
Travel path > "End of weight determination"
– The measurement data in this range are recorded after the weight determination has
and after reaching the speed trigger level (learn run speed). As from this moment, the door movement is almost constant. The measurement data are recorded every 2 cm, the first measured value is recorded 2 cm after the trigger level position (transient distance).
finished and the speed trigger level has been reached (learn run speed). As from this moment, the door movement is almost constant. The measurement data are recorded every 2 cm, the first measured value is recorded 2 cm after the trigger level position (transient distance).
is divided into two subranges
The measurement data are recorded movement within the learn run and after reaching the speed trigger level (learn run speed). As from this moment, the door movement is almost constant. The measurement data are recorded every 2 cm, the first measured value is recorded 2 cm after the trigger level position (transient distance). The measured values are recorded until the system reaches the "Cutter distance CLOSE" range (p3663).
1. The values "MEAN FRICTION FORCE OPEN/CLOSE [A]" and "STANDARD DEVIATION
OPEN/CLOSE [A]" in the "open" and "closed" positions are calculated on the basis of the measurement data.
2. The values calculated in step 1 are converted to a force [N] with the aid of the motor
constants [N/A]
3. The force calculated in step 2 is added internally to the parameterized forces p3682,
p3683, p3684, and p3685
d p3681 (effective in the end stops) in order to avoid unnecessary heating of the motor.
throughout the entire closing
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
75
Page 76
Controllers
Note
The corresponding internal force value, which is the result of the addition of the parameterized force value and the calculated friction force, is limited of the respective parameter.
6.2.34

Oscillation protection

End position "open"
End position "closed"
6.2 Drive functions
to the maximum value
The oscillation protection prevents permanent oscillation of the door at the end stop.
If the system is pressed out of the end position with the drive order "open" present, the system detects that the "open" position has been left, and attempts to return to the end stop with the set static opening force.
After reaching the end stop, the drive is energized with the set continuous torque.
The behavior described may be repeated five times (oscillation). After the fifth repetition, the drive is energized for 30 s with the set continuous torque without any response to further oscillations. After a protective period of 30 s, the system responds once again to corresponding oscillations.
If the system is pressed out of the end position with the drive order "close" present, the system detects that the "closed" position has been left, and attempts to return to the end stop with the set static cutter force.
After reaching the end stop, the drive is energized with the set cutter press-on torque. After 2 s, the cutter press-on torque is limited to the set continuous torque.
The behavior described may be repeated five times (oscillation). After the fifth repetition, the drive is energized for 30 s with the set continuous torque without any response to further oscillations. After a protective period of 30 s, the system responds once again to corresponding oscillations.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
76 System Manual, 06/2016, A2B00096162-AN
Page 77
Controllers
6.2.35

Automatic energy limitation

Description of function
WARNING
Risk of injury due to moving mechanical parts
SIDOOR ATD4xxW
not
Force and energy profiles (ATD4xxW)
6.2 Drive functions
SIDOOR controllers have a system that automatically limits the kinetic energy in the closing direction.
Independently of the maximum closing speed automatically determined during the learn run, the kinetic energy of the door in the closing direction has to be checked by the commissioning engineer after a learn run.
According to EN 81, the kinetic energy of the door in the closing direction must not exceed 10 joules while the reversing device is enabled.
Without enabled reversing device, the kinetic energy of the door in the closing direction must not exceed 4 joules according to EN 81 and each closing operation must be signaled acoustically. The signal sound is not part of the SIDOOR system and must be secured externally and made available by the operator.
The set maximum closing speed and the nudging speed must be reduced accordingly.
Check the final application-specific limit values and adjust the limit values accordingly.
SIDOOR ATD4xxW controllers include a system that automatically limits the kinetic energy in the opening and closing directions.
The energy limitation values are specified in the parameters p1202 (in the closing direction) and p1203 (in the opening direction). After a successfully completed learn run, the speed values of driving parameters p3668 and p3664 are determined and overwritten according to the determined weight and configured energy limitation.
The automatic energy limitation can be suppressed by setting the corresponding energy limiting parameter to "0". Suppressed energy limiting means that the respective speed is overwritten by the learn run.
See Section Force and energy profiles (NDG mode) (Page 50).
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
77
Page 78
Controllers
Speed limit curve (in the closing direction*)
6.2 Drive functions
*SIDOOR ATD4xxW: Opening and closing directions
The speed limit curve is the characteristic that determines the maximum permissible door speed (closing speed), v the maximum kinetic energy of the door in the closing direction must not exceed 10 joules.
W
= 1/2 m ∙ v² = 10 J.
KIN
Example from the following speed limit curve:
, as a function of the total door panel weight. According to EN 81,
max
Total door panel weight m = 180 kg => v
Image 6-4 Speed limit curve for WKIN=10J
= 0.33 m/s.
max
If the reversing device is switched off, the maximum kinetic energy must not exceed 4 joules.
W
= 1/2 m ∙ v² = 4 J.
KIN
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
78 System Manual, 06/2016, A2B00096162-AN
Page 79
Controllers
Adjustment ranges
6.2 Drive functions
Example from the following speed limit curve:
Total door panel weight m = 180 kg => v
Image 6-5 Speed limit curve for WKIN=4J
= 0.21 m/s.
max
You will find the adjustment ranges in Section Profiles and adjustment ranges (Page 296).
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
79
Page 80
Controllers
Maximum speeds
Maximum speeds [mm/s] depending on door weight and energy limiting
Door weight
[kg]
Energy [J]
4
10
25
50
75
100
50
400
632
1000
1414
1732
2000
100
283
447
707
1000
1225
1414
150
200
200
316
500
707
866
1000
250
179
283
447
632
775
894
300
163
258
408
577
707
816
350
151
239
378
535
655
756
400
141
224
354
500
612
707
450
133
211
333
471
577
667
500
126
200
316
447
548
632
550
121
191
302
426
522
603
600
115
183
289
408
500
577
Parameter assignment
SIDOOR ATD4xxW
6.2 Drive functions
The table below shows the maximum speeds depending on door weight and energy limiting:
Table 6- 6
The energy limitation values are specified in both of the following parameters:
231 365 577 816 1000 1155
● In closing direction: p1202
● In opening direction: p1203
Parameter assignment is possible via the driving parameters or the terminal module.
If one of the two energy limitation parameters is set to 0, the speed limitation is suppressed according to the kinetic energy.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
80 System Manual, 06/2016, A2B00096162-AN
Page 81
Controllers
6.2.36

External closing force

Description of function
WARNING
Risk of injury due to moving mechanical parts
SIDOOR ATD400S and SIDOOR ATE250S
SIDOOR ATD400T
Description Permissible total door panel weight with a maximum spring force
of 80 N: System friction of 10 to 70 N is allowed for
Inclination 0°
Inclination 5°
Inclination 10°
acceleration)
(a
max
= 1.3 m/s²)
(a
max
= 0.4 m/s²)
(a
max
= 0.3 m/s²)
acceleration)
(a
max
= 0.9 m/s²)
(a
max
= 0.9 m/s²)
(a
max
= 0.9 m/s²)
6.2 Drive functions
Closing mechanisms in the form of a counterweight or a spring are permissible for a particular system.
You will find the permissible counterweights in Section Technical specifications (Page 223).
Make sure that with an additional external closing force the sum of external closing force and force set in the controller does not exceed the maximum force limit of 150 N (according to EN 81).
Check the final application-specific limit values and adjust the limit values accordingly.
An external closing force on the user side is not provided for in SIDOOR ATD400S and SIDOOR ATE250S controllers. However, an external closing force (counterweight, spring) can be installed.
This must be taken into account in the parameter assignment of the door control system.
Table 6- 7 Permissible total door panel weight for SIDOOR ATD400T with SIDOOR M3 / MDG180
DIN EN 45545-2 geared motor
Single-panel door system with spring
(The spring force affects the
Single-panel door system without spring
Twin-panel door system with spring
(The spring force affects the
Twin-panel door system without spring
180 kg (a
= 1.3 m/s²)
max
180 kg
180 kg (a
= 0.9 m/s²)
max
180 kg
140 kg (a
= 0.3 m/s²)
max
180 kg
180 kg (a
= 0.9 m/s²)
max
180 kg
80 kg (a
= 0.3 m/s²)
max
120 kg
180 kg (a
= 0.9 m/s²)
max
180 kg
The grade resistance on twin-panel doors compensates for the inclination.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
81
Page 82
Controllers
6.2.37

Push to open

Description of function
6.2.38

Pull to close

Description of function
6.2.39

Emergency release

Description of function
WARNING
An emergency release can only be actuated if the following conditions are met:
not
6.2 Drive functions
The controller automatically detects a DOOR OPEN command if a door is pulled manually in the opening direction by more than 2 cm.
The controller automatically detects a DOOR CLOSE command if a door is pulled manually by more than 2 cm in the closing direction.
Neither a DOOR OPEN nor a DOOR CLOSE command is present,
The service buttons are not pressed.
The terminal module, SIDOOR Service Tool and SIDOOR User Software are
Quick setup or General setup menu items or one of their sub-menus.
The door has come to a complete stop.
The door drive is only torque-free if these conditions are fulfilled. The force required to open the door is less than 300 N in accordance with the requirement of EN 81.
in the
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
82 System Manual, 06/2016, A2B00096162-AN
Page 83
Controllers
6.2.40

Learn run

Description of function
Note
For the M4, MDG400, MDG400 NMS and M5 motors, the must be checked prior to each learn run and adjusted if necessary.*
Types of learn run (via learn run button)
When the line voltage is applied
During operation
6.2 Drive functions
A learn run serves to determine and store the characteristics of a particular system.
* SIDOOR ATD4xxW
Two types of learn run can be made if the learn run button is pressed as follows:
If the learn run button is operated directly when the line voltage is applied, the connected motor type is learned. All driving parameters and force and energy limiting parameters are automatically reset to their factory defaults before the learn run is begun. The learn run determines the door width, weight and friction. The speed in NDG mode and the maximum closing and opening speeds are also limited as a function of the determined weight and parameterized energy limiting. Friction compensation is also coordinated with the determined door parameters.
output transmission (Page 86)
Application examples: initial commissioning or when commissioning a new motor type
If the learn run button is actuated during ongoing operation, a learn run is started to determine the door's width, weight and friction. The speed in NDG mode and the maximum closing and opening speeds are also limited as a function of the determined weight and parameterized energy limiting. Friction compensation is also coordinated with the determined door parameters. The driving parameters and force and energy limiting parameters are retained.
Application examples: modifying the properties of the door system (door width or friction)
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
83
Page 84
Controllers
Learning in new motors (ATD4xxW)
Note
If a learn run is started with a new mo connected one, for safety reasons the energy limiting parameters (p1202, p1203 and p1204) and internal friction compensation are reset for all driving parameters.
For the M4, MDG400. MDG400 NMS and M5 moto be configured. For the M4, MDG400 and M5 motors, set the default value to 176 mm/rev.*
The learn run does not start when a value is set outside the permitted value range for the output transmission (for example, de
Starting a learn run via the learn run button
Interrupting the learn run (SIDOOR ATD4xxW, ATE250S)
6.2 Drive functions
The learned motor type is stored in the controller and compared with the connected motor when the controller is switched on. The controller's operating status display shows the status code "5" if the learned motor type differs from the connected one. A new learn run (when the line voltage is applied) or a special learn run is needed to learn in the new motor type.
SIDOOR ATD4xxW controllers enable learning of a new motor type by means of a special learn run, which can be started as follows:
DCMD "Start learn run" (see Table 6-74 DCMD signal (Page 206)) and DCMD "special" expansion bit (see Table 6-75 DCMD expansion bits (Page 207))
In the service terminal via
MAIN MENU > General setup > Start learn run with new motor
tor and if the learned motor type differs from the
fault value: 0).
* SIDOOR ATD4xxW
You can start a learn run via the learn run button (S401/S1*). Proceed as described in Section Service buttons (Page 110).
* SIDOOR ATE250S
rs, the output transmission [mm/rev] must
Users can interrupt the learn run. The system signals an interrupted learn run through the door fault status and by changing to a special mode. The operating status display shows the warning "_". See Section Operating state display (Page 183).
The following actions interrupt an active learn run:
● Repeated operation of the learn run button (S401/S1*)
● Operating the OPEN or CLOSE service buttons (S402/S2* or S403/S3*)
Door command change (except "deenergized") via the terminal, the service interface or
the fieldbus system**
Interruption of the ESPE or the pressure-sensitive edge**
* SIDOOR ATE250S
** SIDOOR ATD4xxW
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
84 System Manual, 06/2016, A2B00096162-AN
Page 85
Controllers
Querying determined values
SIDOOR ATD4xxW
6.2.41

Force limit for learn run

Description of function
Note
The force only needs to be adjusted for smooth door system has a door weight <100 kg and ma
Connection and parameter assignment
SIDOOR ATD410W / ATD420W / ATD430W
6.2 Drive functions
The values determined for the effective weight and the door width can be queried via the terminal module.
SIDOOR ATD4xxW controllers also enable querying via the following parameters:
● Effective weight: r2101
● Door width: r2103
Force that is active during the learn run. The force limit is active in the closing and opening direction.
The parameter depends on the existing output transmission. The force limit is set to the maximum value by default.
The force limit can be configured via the terminal module (
Special parameters > Force limit for learn run
The force limit is set via the parameter p1242. See section Calibration and function parameters (Page 175) for more on this.
-running door systems. A smooth-running ximum frictional forces of <20N.
Main menu > General setup >
).
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
85
Page 86
Controllers
6.2.42

Output transmission

Description of function
Door weight [kg]
200
X X X
n.r.
300
X
X
n.r.
n.r.
400
X
n.r.
n.r.
n.r.
n.r. not recommended
Note
For the M4, MDG400 and M5 motors, set default value to 176 mm/rev.
Note
The output tr
Note
The determined door width has to be checked after each learn run.
Note Activation of the learn run via the bus interface
The learn run can only be started when an al the door width should then be read back via the parameter r2103 and checked.
Connection and parameter assignment
SIDOOR ATD410W / ATD420W / ATD430W
6.2 Drive functions
For the M4, MDG400. MDG400 NMS and M5 motors, the output transmission must be configured. The output transmission describes the transformation of rotational into translational motion. Therefore: The distance [mm] that the door travels with one revolution [rev] of the transmission output shaft. The output transmission can be adjusted within the range 0...384 mm/rev. The permitted values are between 88...384 mm/rev. The default value for a newly trained motor type is 0 mm/rev.
Output transmission [mm/rev]
< 200 < 250 < 300 < 384
100 X X X X
ansmission should be checked before each learn run and adjusted if necessary.
The force limit can be configured via the terminal module (
Special parameters > Output transmission
lowable value has been entered. The value for
Main menu > General setup >
).
The output transmission is set via the parameter p4602. See section Calibration and function parameters (Page 175) for more on this.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
86 System Manual, 06/2016, A2B00096162-AN
Page 87
Controllers
6.2.43

Free function blocks (FBLOCK)

6.2.43.1
Overview
Digital and logical input signals (Page 90)
Basic blocks (Page 91)
Digital and logical input signals (Page 90)
Frequency analysis blocks (Page 92)
Special function blocks (Page 91)
On delay block (Page 92)
Discrepancy analysis block (Page 91)
Counter block (Page 93)
6.2 Drive functions
In some applications it is necessary to control the drive via digital signals. To this end, you can configure an individual logic using the logic elements shown in the following figure.
Image 6-6 FBLOCK overview
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
87
Page 88
Controllers
6.2.43.2
Configuring the logic
Example logic
Factory defaults
Note Factory settings of ATD4xxW (firmware version 1.03 or higher)
A logical connection not set in the case of ATD4xxW controllers (firmware version 1.03 or higher).
6.2 Drive functions
The free function blocks are configured at the parameter level. The input of a function block can be linked to any output by entering the output's Q number in the input's REF parameter.
The outputs' Q numbers can be found in Image 6-6 FBLOCK overview (Page 87).
The REF parameters can be found in Table 6-45 FBLOCK-REF parameters (Page 182).
The following figure shows an example logic. In the example logic, the level-controlled outputs of the digital inputs DI3 and DI2 and a 1 ("high") are linked via the FBLOCK "AND0" with the FBLOCK "Fault acknowledgement".
Image 6-7 Example logic
The special "emergency power mode" function block is already linked to the level-controlled output of the digital input DI0 (terminal X5) by virtue of the factory default settings. The Q number 4 is stored in the REF parameter of the input p20124 for this.
between the "emergency power mode" function block and DI0 (X5) is
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
88 System Manual, 06/2016, A2B00096162-AN
Page 89
Controllers
Drive orders
15 … 8
7 6 5 4 3 2 1
0
DCMD
DCMD expansion
Example
p100 "DefCmdMode"
Note
If the controller is to be operated
must be diverted → p100 "DefCmdMode" = 2 (FBLOCK).
Parallel drive orders
Parallel door command expansion bits
6.2 Drive functions
In parallel with logical signal combination, a drive order can be assigned to the Q outputs. Door commands that are assigned to the outputs are only active as long as the assigned output is active (jog mode). A drive order is composed of a door command "DCMD" and an optional door command expansion bit "DCMD expansion".
Drive order = door command + door command expansion bit
Both commands are expressed as 16-bit values. The structure of the DCMD and DCMD expansion bit fields corresponds to the technology control world 1 (TSW 1) signals of the same names, see Table 6-73 Technology control word 1 (TSW1) (Page 206). The "LB" and "DCOPS" and expansion bits are not evaluated here.
The value 0x0301
The value 0x0215
The default command mode is defined by the factory setting is for command issuing via the bus system to be active (exception: ATD401W). This means that the drive orders of the FBLOCK system are only valid in the drive state "S4: Z_OPERATION" (see Image 6-33 Sequential control state graph (Page 216)).
You will find more detailed information in Section Drive orders (Page 94).
Door commands that are active during a processing cycle are assigned the following priorities:
Stop > Open > Close
All other door commands are determined on the basis of the processing sequence.
corresponds to the "close slowly" drive order.
hex
corresponds to the "slow, partial opening in NDG mode" drive order.
hex
parameter. The default
without a bus connection (offline), default command issuing
The door command expansion bits that are active during a processing cycle are combined (logically ORed).
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
89
Page 90
Controllers
Signal processing
6.2.43.3
Digital and logical input signals
Digital input signals
Level-controlled
Note ATD4xxW (firmware version 1.03 or higher)
The signals of the digital inputs are additionally provided in an inverted form.
Edge-controlled
Note
Latched drive orders are processed separately and are stored as door commands with an associated door command expansion bit. Any other, unlatched door command apart from "deenergized" o
6.2 Drive functions
All outputs are recalculated in each processing cycle (10 ms) on the basis of the current input signal states. The cycle's output signals are calculated exactly in the order of the Q numbers (beginning with Q0). If the output Q22 ("NOT0") is used as the input signal of "AND0", its output Q17 is not recalculated until the next cycle.
The controller possesses 5 digital inputs (with 30 ms debouncing), which can be combined with any function blocks and/or can be combined directly with drive orders. Drive orders that are assigned to the level-controlled input signals are only active as long as the assigned digital input is active (jog mode).
Each digital input can also be evaluated with edge control. Note that edge-controlled signals are available for the current processing cycle only. Drive orders that are assigned directly to the edge-controlled input signals are, therefore, "latched" automatically. "Latched" means that the drive orders are stored and stay active until they are overwritten by another drive order. These elements are marked as shown in Image 6-6 FBLOCK overview (Page 87).
verwrites or clears the latched drive order including the expansion bit.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
90 System Manual, 06/2016, A2B00096162-AN
Page 91
Controllers
Logical input signals
Logical signal source
Description
Q0
Logical 0 "low"
Q1
Logical 1 "high"
Q33
Motor deenergized
Q35
System opened
Q36
System closed
Q37
Fault
Q38
System in normal mode
6.2.43.4
Special function blocks
6.2.43.5
Discrepancy analysis block
6.2.43.6
Basic blocks
6.2 Drive functions
To be able to map internal dependencies in the logic, selected system states are made available as logical input signals.
Q34 Motor stopped
An active system fault can be acknowledged by means of the special "fault acknowledgement" function block. The acknowledgement is triggered after the input signal has been active for at least 5 s.
The controller's emergency power mode can be activated by means of the special "emergency power mode" function block. You will find further details of the emergency power mode in Section Emergency power mode (Page 74).
The discrepancy analysis block "AND0" has four time-monitored inputs, two of which are negated or inverted. The output signal at Q17 behaves according to the following rules:
The output signal only becomes active if all inputs were activated synchronously within the time defined via parameter p4610.
The output signal becomes inactive as soon as at least one input signal has become inactive.
The output signal can only be reactivated after all input signals have been inactive.
The basic function blocks "AND", "OR", "NOT" and "XOR" are provided to be able to map basic logical combinations.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
91
Page 92
Controllers
6.2.43.7
Frequency analysis blocks
Input signal
Output signal
The output signal changes after 3 detected signal periods after the 4th edge
1 Hz frequency detection:
0.5 Hz frequency detection:
6.2.43.8
On delay block
6.2 Drive functions
An input signal can be analyzed for specific frequencies and duty factors via the "FRQ" frequency blocks. Two identical frequency analysis blocks are available, capable of detecting frequencies of 1 Hz and 0.5 Hz with a duty factor of 20 %.
The detection criteria and the valid tolerances are described in detail in the following figure.
An input tolerance of (±) 40 ms is assumed.
Duty cycle: 20 % (17 to 23 %)
– T = 1000 ms (±2 %) – ton = 200 ms – t
= 800 ms
off
– Pulse/pulse ratio V = 25 %
– T = 2000 ms (±2 %) – t
= 400 ms
on
– t
= 1600 ms
off
– Pulse/pulse ratio V = 25 %
Image 6-8 Frequency-based input signal detection
The outputs Q24 or Q26 become active when the analysis algorithm detects a frequency of 1 Hz with a 20 % duty factor in the input signal. The outputs Q25 or Q27 become active when the analysis algorithm detects a frequency of 0.5 Hz with a 20 % duty factor in the input signal.
The maximum response time at the output, i.e. the time after which the system can detect an error or a deviation in the input signal frequency, corresponds to the period of the frequency to be detected. Accordingly, a frequency of 1 Hz results in a maximum response time of 1 s and a frequency of 0.5 Hz results in a maximum response time of 2 s.
The "OnDELAY" block delays the input signal at the output Q28 by 2 s and at the output Q29 by 5 s.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
92 System Manual, 06/2016, A2B00096162-AN
Page 93
Controllers
6.2.43.9
Counter block
6.2 Drive functions
The "COUNTER" block increments the internal counter value in the event of a positive edge at the input.
The maximum counter value is 2. The counter value is reset in the event of an overflow:
0 → 1 → 2 → 0
● Counter value 0 → output Q30 active
● Counter value 1 → output Q31 active
● Counter value 2 → output Q32 active
After the controller has been switched on, the counter value is initialized automatically with 0. You can reset the counter value to 0 via the "reset" input. As long as the "reset" input is active, the counter value is 0.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
93
Page 94
Controllers
6.2.44

Drive orders

Drive order = door command + door command expansion bit
Combinations
Door com­mand expan­sion bit
Door command
command)
(Page 70)
(Page 66)
(Page 51)
(Page 68)
(Page 50)
tive)
(Page 56)
(Page 42)
(Page 39)
Not a door command (Deenergize)
"Special stop" drive order
6.2 Drive functions
The drive is controlled by means of drive orders. A drive order is composed of the following:
The following table shows the combination of the door command and the door command expansion bit that lead to modification of the applicable door command. In the case of combinations/fields that are not marked, only the door command is effective. In the case of some drive orders, the dependence of the normal, initial or learn run modes must also be considered.
Table 6- 8 Combining door command and door command expansion bit
Deenergize
(not a door
Slow
ImpulseStop (Page 67)
x x x x x
Automatic
Stop Open Close Automatic
AssistedDrive
Automatic
ImpulseDrive
ImpulseStop
Positioning
(Page 72)
Learn run (Page 83)
NDG
Special Corresponds
Partial
DCOPS
LB sensor
x x x x x
to Deener-
gize (source
voltage
brake inac-
x x x x
x x x
x x x x x x x x
The system evaluates the Deenergized (no current) door command as "inactive" or "not a door command".
The door command with the highest priority is Stop. The status following the ramp stop can be defined by means of the "special" door command expansion bit: source voltage brake activated or deenergized (corresponds to coasting down or no current).
You can find more information on individual drive orders in the Sections linked in the "Combining door commands and door command expansion bits" table.
Learn run
with a new
motor
(Page 83)
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
94 System Manual, 06/2016, A2B00096162-AN
Page 95
Controllers
Shutdown/deceleration functions
do not
Function
Description
safety-related limit areas).
system (e.g. gearing).
Function
Description
mand/Deenergize
Special stop
active).
"RevRampClsToOp"). The following behavior is dependent on the current system status.
6.2 Drive functions
In an unlimited system, the shutdown and deceleration functions are split into the following: "rapid stop", "ramp stop" and "coasting down". These definitions system because these are to be considered as limited systems.
Table 6- 9 Shutdown/deceleration functions in an unlimited system
Rapid stop Decelerates the drive to standstill with the maximum braking ramp (taking into account technical and
Ramp stop Same meaning as rapid stop, but a configured ramp is used to decelerate the drive to standstill. Coasting down The drive is not actively braked, it can run freely and is only slowed by the friction inherent in the
In SIDOOR systems, coasting down is equivalent to the Deenergize (no current) door command. For safety reasons, however, direct coasting down must not take place due to the limits implemented in a door system (safety reasons). This is why the following definitions apply to the SIDOOR door drive:
apply in a door
Table 6- 10 SIDOOR door drive shutdown/deceleration functions (limited system)
Not a door com-
Stop Decelerates the drive to standstill with a configured ramp (p3674 "DecRampOp" or p3677
Reverse Direction of travel reversal by local sensor (e.g. light curtain and pressure-sensitive edge) or "Open →
Decelerates the drive to standstill with a configured ramp (p3674 "DecRampOp" or p3677 "DecRampCls") and then assumes free running mode.
"DecRampCls") and then assumes virtual short-circuit mode (50 % PWM → source voltage brake
Close" or "Close → Open" drive order change. Decelerates the drive to standstill with a configured ramp (p3675 "RevRampOpToCls" or p3678
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
95
Page 96
Controllers
Sources of drive orders
Drive order source
Description
Service button
tion (Page 215)). The Deenergize drive order is active where no button is pressed.
S401 (learn run)
The button can be released once the learn run has started. The learn
S402
S403 The Close drive order is active as long as the button is pressed.
Software Kit (PC) and Service Tool or local terminal
Service Tool or local terminal
Software Kit (PC)
Process data (USS,
PROFIBUS, PROFINET)
FBLOCK system (digital INPUT1,
2, 3, 4 and X5)
Process data
Technology control word 1.
FBLOCK system
p100 "DefCmdMode"
setting is for command issuing via the bus system to be active (exception: ATD401W). This means that
without a bus connection (offline)
(FBLOCK).
6.2 Drive functions
Activating a service button results an immediate switchover to the local mode (see Local/master opera-
If S401 is pressed for approx. 5 s in the Power ON state, the special learn run (learn run with new motor) drive order is activated. You can find additional information in Learn run (Page 83).
run can be canceled at any time (see Learn run (Page 83)).
The Open drive order is active as long as the button is pressed.
Some menu areas of the terminal are categorized as being safety-related. Follow the instructions in Chapter Local/master operation (Page 215). The Stop drive order is activated within this area.
You can also activate the "Open", "Close", "NDG Close", "Learn run" and "Learn run with new motor" drive orders using the terminal (
Main menu > General setup or Quick setup
)
Drive orders can be simulated via the "Drive orders" window. The following applies to the ATD4xxW:
Open → "Open" drive order
Close → "Close" drive order Nudge → "NDG close" drive order Stop → "Stop" drive order
Drive orders can be sent via the process image. To this end, the DCMD (door command) and DCMD expansion bit (door command expansion bit) signals are defined in TSW1 – Drive orders are part of control words and are valid only when the drive is in the "S4: Z_OPERATION state (see Image 6-33 Sequential control state graph (Page 216)).
The digital inputs of the SIDOOR controller can be combined with drive orders via the parameterizable FBLOCK logic (see Free function blocks (FBLOCK) (Page 87)).
The default command mode is defined by the
FBLOCK drive orders are only valid in the "S4: Z_OPERATION" drive state (see Image 6-33 Sequen­tial control state graph (Page 216)).
If the controller is to be operated of the drive state), default command issuing must be diverted to FBLOCK → p100 "DefCmdMode" = 2
parameter. The default factory
(FBLOCK drive orders independent
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
96 System Manual, 06/2016, A2B00096162-AN
Page 97
Controllers
Prioritization of door command sources
Priority
Door command source
Remarks
High
1.
Service buttons S401, S402 and S403
Commands issued locally on the controller
(digital INPUT1, 2, 3, 4 and X5)
(edge-controlled drive orders "latched")
the FBLOCK system (latched drive orders)
Mutual prioritization of door commands
Priority
Door command
Remarks
→ coasting down/deenergized with highest priority
2.
Open
3.
Close
Positioning
5.
Learn run
Learn run can be interrupted
→ coasting down/deenergized with high priority via "special stop" drive order
6.2 Drive functions
Door commands can be issued via different sources. A higher-priority drive order overwrites a lower-priority drive order. The service interfaces generally have the highest priority because they are intended for commissioning and service purposes.
Table 6- 11 Prioritization of door command sources
2. Software Kit (PC) and Service Tool or local terminal
3. Process data (USS, PROFIBUS, PROFINET)
FBLOCK system
Low 4. FBLOCK system
Commands issued locally via the service terminal or the PC tool
Drive orders are mutually prioritized
Only in the case of edge-controlled digital input signals of
When a command is issued via the process image, there can be no mutual prioritization of door commands because the corresponding DCMD signal is based on an enumerative structure and therefore only ever one door command can be active. Prioritization is applied in the case of interconnections within the FBLOCK system or the service buttons, for example.
Table 6- 12 Prioritization of the door commands
High 1. Stop The source voltage brake is deactivated after the ramp stop via the "special"
expansion bit
4. Automatic AssistedDrive, Automatic ImpulseDrive,
Low 6. Deenergize Neutral door command corresponds to the idle state, equivalent to inactive
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
Same priority (internal processing sequence determines the drive order)
97
Page 98
Controllers
6.3
Safety concept ATD4xxW
6.3.1

Safe force output

6.3.2

Safe speed observance (energy limiting)

6.3.3

Safe input signals according to PLd

6.3 Safety concept ATD4xxW

The SIDOOR controllers ATD4xxW dispose of an extensive safety package. The safety functions fulfill the requirements according to DIN EN ISO 13849-1 Cat 2 PL d (Performance Level).
The scope of the safety functions includes:
● Safe force output
● Safe speed observance (energy limiting)
● Safe input signals
The maximum forces configured by the user must always be observed for safety reasons. The safe force output of the SIDOOR system ensures that the torque output by the motor does not increase in case of an error. Unintentional increases in the torque are recognized and result in a defined error response.
The speeds configured by the user must always be observed for safety reasons. The safe speed observance of the SIDOOR system ensures that the energy of the door does not increase in case of an error. Unintentional increases in speed are recognized and result in a defined error response.
SIDOOR ATD4xxW controllers have five digital inputs (see Auto-Hotspot) through which safety-related signals can also be sent. This Section describes two different methods for transferring safety-related signals to the controller.
Two concepts are also presented for two-hand operation and emergency stop applications.
The concepts described in this Section for implementing safe input signals according to PLd (Performance Level d) enable detection of the following faults:
● Discontinuity of one single terminal
Short-circuit between any two terminals
Stuck-at fault (short-circuit to 1 and 0 in the case of an isolated input or an interrupted
output)
● Static signal "0" and "1" at all inputs and outputs, individually or simultaneously
● Parasitic oscillation of outputs
● Modification of characteristic values (e.g. input/output voltage of analog devices)
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
98 System Manual, 06/2016, A2B00096162-AN
Page 99
Controllers
6.3.3.1
Internal signal routing
No components capable of oscillation and internal pull-up circuit
0M
Ground potential 1
1M
Ground potential 2
2M
Ground potential 3
6.3.3.2
Redundant antivalent signal logic with discrepancy analysis
6.3 Safety concept ATD4xxW
The following figure illustrates the input terminals and the internal wiring to the processor. The input signals are located at processor port M. Separate reference potentials 0M, 1M and 2M can each be defined for Input 2, Input 3, Input 4 and for Input 1 and Input 0. The input signals are provided with internal pull-ups and there are no components between the input terminals and the processor that are capable of oscillation.
Image 6-9 Internal wiring of input terminals
In the case of 1oo2 evaluation, the sensor is routed to two different, mutually antivalent channels and is therefore evaluated by the controller twice. The discrepancy analysis is performed between the two channels of the 1oo2 evaluation in the controller. If there is a discrepancy between the input signals after expiry of the parameterized discrepancy time, e.g. due to breakage of a sensor cable, the internal signal is set to "0". The discrepancy analysis at the input channels is performed with the "AND0" discrepancy analysis block (see Section Auto-Hotspot). This special kind of signal routing achieves PLd and enables both high availability and error detection.
The following graphics show an example of 2-channel antivalent wiring of a sensor (antivalent).
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T System Manual, 06/2016, A2B00096162-AN
99
Page 100
Controllers
Antivalent connection of an antivalent sensor to two channels
6.3 Safety concept ATD4xxW
A 2-channel sensor is required for the signal (1oo2 evaluation)
Image 6-10 Antivalent connection of a sensor (type 1) to two channels
Image 6-11 Antivalent connection of a sensor (type 2) to two channels*
* Two 1-channel sensors can also be connected as an alternative.
AT40, ATD400V, ATD400K, ATD4xxW, ATD400S, ATE250S, ATD400T
100 System Manual, 06/2016, A2B00096162-AN
Loading...