ENGLISH
Description
The PSU100P SITOP power supplies are provided for Indoor and Outdoor application, degree of protection IP67, protection class I.
Primary switched-mode power supplies for connection to 1-phase AC system (TN, TT system in accordance with VDE 0100 T 300 / IEC 364-3) with rated voltages of 120/230 V, 50/60 Hz;
+24 V DC output voltage, isolated, short-circuit-proof and idling-proof.
See also Figure 1
Safety notes
NOTICE
Appropriate transport, proper storage, mounting, and installation, as well as careful operation and service, are essential for the error-free, safe and reliable operation of the device/system.
Setup and operation of this device/system are permitted only if the instructions and warnings of the corresponding documentation are observed.
Only qualified personnel are allowed to install the device/system and set it into operation.
Assembling
Wall mounting.
The device must be mounted in such a way that the input and output terminals are at the bottom.
A clearance of at least 50 mm must be maintained above and 20mm in front of the device .
See also Figure 2
See also Figure 4
Bild 3: Input Output , Meldekontakt Figure 3: Input Output , signaling contact
Figure 3: Input Output , contact de signalisation Figura 3: Input Output , contatto di segnalazione Figura 3: Entradas Salidas , contacto de señalización
20
|
|
|
||
|
|
|
|
|
Bild 4: Freiraum für Kühlung |
|
|||
Figure 4: Required clearance for cooling |
|
|||
Figure 4: Espace libre pour refroidissement |
|
|||
Figura 4: Spazio libero per raffreddamento |
|
|||
Figura 4: Espacio libre para refrigeración |
|
Connecting
WARNING
Before installation or maintenance work can begin, the system's main switch must be switched off and measures taken to prevent it being switched on again. If this instruction is not observed, touching live parts can result in death or serious injury. It is only permissible to use an insulated screwdriver when actuating the potentiometer. For installation of the devices, the relevant country-specific regulations must be observed.
The supply voltage (1 AC 120/230 V) must be connected in accordance with IEC 60364 and EN 50178.
Instructions for UL compliant use: The input/output connection is to be made using UL-Listed (CYJV) connector/cable combination with minimum ratings of 300 V, 8 A, 60°C operating temperature.
The signal connection is to be made using UL-Listed (CYJV) connector/cable combination with minimum ratings of 240 V, 4 A, 60°C operating temperature.
Plug connectors are not included
Input :
cable connector 7/8"-16UN 3 Pol. E.g. Binder 99-2440-12-03
Output :
cable connector 7/8"-UN 4-Pol E.g. Binder 99-2443-12-04
Signaling Contact : cable connector M12, 4-Pol E.g. Binder 99-0429-14-04
See also Figure 3
Structure
AC input
DC output
Signaling contact
Indicator light (24 V OK)
Clearance for cooling