Siemens 6EP1333 -7CA00, 6EP1334 -7CA00 User guide

0 (0)
Siemens 6EP1333 -7CA00, 6EP1334 -7CA00 User guide

SITOP PSU100P

6EP1333-7CA00 24 V / 5 A 6EP1334-7CA00 24 V / 8 A

Operating Instructions (compact)

Bild 1: Ansicht Geräte

Figure 1: View of units

Figure 1: Vue des appareils

Figura 1: Vista degli apparecchi

Figura 1: Vista de aparatos

Bild 2: Maßbild

Figure 2: Dimensions

Figure 2: Dimensions

Figura 2: Dimensione

Figura 2: plano acotado

ENGLISH

Description

The PSU100P SITOP power supplies are provided for Indoor and Outdoor application, degree of protection IP67, protection class I.

Primary switched-mode power supplies for connection to 1-phase AC system (TN, TT system in accordance with VDE 0100 T 300 / IEC 364-3) with rated voltages of 120/230 V, 50/60 Hz;

+24 V DC output voltage, isolated, short-circuit-proof and idling-proof.

See also Figure 1

Safety notes

NOTICE

Appropriate transport, proper storage, mounting, and installation, as well as careful operation and service, are essential for the error-free, safe and reliable operation of the device/system.

Setup and operation of this device/system are permitted only if the instructions and warnings of the corresponding documentation are observed.

Only qualified personnel are allowed to install the device/system and set it into operation.

Assembling

Wall mounting.

The device must be mounted in such a way that the input and output terminals are at the bottom.

A clearance of at least 50 mm must be maintained above and 20mm in front of the device .

See also Figure 2

See also Figure 4

Bild 3: Input Output , Meldekontakt Figure 3: Input Output , signaling contact

Figure 3: Input Output , contact de signalisation Figura 3: Input Output , contatto di segnalazione Figura 3: Entradas Salidas , contacto de señalización

20

 

 

 

 

 

 

 

 

Bild 4: Freiraum für Kühlung

 

Figure 4: Required clearance for cooling

 

Figure 4: Espace libre pour refroidissement

 

Figura 4: Spazio libero per raffreddamento

 

Figura 4: Espacio libre para refrigeración

 

Connecting

WARNING

Before installation or maintenance work can begin, the system's main switch must be switched off and measures taken to prevent it being switched on again. If this instruction is not observed, touching live parts can result in death or serious injury. It is only permissible to use an insulated screwdriver when actuating the potentiometer. For installation of the devices, the relevant country-specific regulations must be observed.

The supply voltage (1 AC 120/230 V) must be connected in accordance with IEC 60364 and EN 50178.

Instructions for UL compliant use: The input/output connection is to be made using UL-Listed (CYJV) connector/cable combination with minimum ratings of 300 V, 8 A, 60°C operating temperature.

The signal connection is to be made using UL-Listed (CYJV) connector/cable combination with minimum ratings of 240 V, 4 A, 60°C operating temperature.

Plug connectors are not included

Input :

cable connector 7/8"-16UN 3 Pol. E.g. Binder 99-2440-12-03

Output :

cable connector 7/8"-UN 4-Pol E.g. Binder 99-2443-12-04

Signaling Contact : cable connector M12, 4-Pol E.g. Binder 99-0429-14-04

See also Figure 3

Structure

AC input

DC output

Signaling contact

Indicator light (24 V OK)

Clearance for cooling