Thank you for purchasing the ME-NET module (JW-21MN) for the SHARP programmable controller.
Read this manual thoroughly to completely familiarize yourself with the operation according to the
examples.
Keep this manual for future reference. We are confident that this manual will be helpful whenever
you encounter a problem.
Note
- This manual describes the JW-21MN that will be compatible with the JW30H. The JW-21MN that
is applied to JW30H has a 30Hn mark in front of the module.
Beside this, the JW-21MN has models with 30H marks and without 30H marks.
30Hn mark
(Compatible
with JW30H)
8
7
9
6
0
5
1
4
2
3
8
8
7
7
9
9
6
6
0
0
5
5
1
1
4
4
2
2
3
3
JW-21MNDescriptions
Can be used when installing the JW-21MN into JW30H
With 30Hn mark
control module: JW-31CUH/32CUH/33CUH (conventional
models) and JW-31CUH1/32CUH1/33CUH1/33CUH2
/33CUH3 (new models).
Can be used when installing the JW-21MN into JW30H
With 30H mark
control module (conventional models). When installing the
JW-21MN into the new models, the control module can be
used as conventional models.
The JW-21MN cannot be used with the JW30H control
No mark
module (both conventional and new models). It can be used
only with the JW20/JW20H control module.
- New functions in the revised edition in order to apply to JW30H are represented by the V2 mark.
Marks used in this manualDescriptions
V2
Functions that can be used when the JW-21MN (compatible with the
JW30H) is installed into the JW20/JW20H/JW30H.
- In this manual, programmable controller is referred to as "PC." Number and symbol in
parentheses added to address or setting value indications represent the following:
Octal··················· (8)
Hexadecimal······ (H)
Decimal·············· (D) or no indication
Note
- This manual was written with the utmost care. However, if you have any questions or inquiries
concerning the product, please feel free to contact our dealers or service agents.
- No part of this manual may be reproduced in any form without the written permission of Sharp
corporation.
- The contents of this manual are subject to change without prior notice.
Safety Precautions
Read this manual and attached documents carefully before installation, operation, maintenance and
checking in order to use the machine correctly. Understand all of the machine knowledge, safety
information, and cautions before starting to use. In this instruction manual, safety precautions are
ranked into "danger" and "caution" as follows.
Danger : Wrong handling may possibly lead to death or heavy injury.
Caution : Wrong handling may possibly lead to medium or light injury.
Even in the case ofCaution , a serious result may be experienced depending on the
circumstances. Anyway, important points are mentioned. Be sure to observe them strictly.
The picture signs of prohibit and compel are explained below.
: It means don’ts. For example, prohibition of disassembly is indicated as ().
: It means a must. For example, obligation of grounding is indicated as ().
1) Installation
Caution
- Use in the environments specified in the catalog, instruction manual, and user's manual.
Electric shock, fire or malfunction may be caused when used in the environments of high
temperature, high humidity, dusty or corrosive atmosphere, vibration or impact.
-Install according to the manual.
Wrong installation may cause drop, breakdown, or malfunction.
-Never admit wire chips or foreign matters.
Or fire, breakdown or malfunction may be caused.
2) Wiring
- Be sure to ground.
Unless grounded, electric shock or malfunction may be caused.
- Connect the rated power source.
Connection of a wrong power source may cause a fire.
- Wiring should be done by a qualified electrician.
Wrong wiring may lead to fire, breakdown or electric shock.
Compel
Caution
3) Use
- Don't touch the terminal while the power is being supplied or you may have an electric shock.
- Assemble the emergency stop circuit and interlock circuit outside of the programmable
controller. Otherwise breakdown or accident damage of the machine may be caused by the
trouble of the programmable controller.
- "RUN" or "STOP" during operation should be done with particular care by confirming safety.
Misoperation may lead to damage or accident of the machine.
- Turn on the power source in the specified sequence. Turning ON with wrong sequence may
lead to machine breakdown or accident.
4) Maintenance
- Don’t disassemble or modify the modules.
Or fire, breakdown or malfunction may be caused.
Danger
Caution
Prohibit
Caution
- Turn OFF the power source before detaching or attaching the module.
Or electric shock, malfunction or breakdown may be caused.
ME-NET Module: JW-21MN
- User's Manual -
Chapter 1 Features and Functions
Chapter 2 Safety Precautions
Chapter 3 System Configuration
Chapter 4 Name and Function of Each Part
Chapter 5 Installation
Chapter 6 Processing of Cables
Chapter 7 Wiring Method
Chapter 8 Memory Address on the ME-NET
Chapter 9 Description for Data Link Operation
Chapter 10 Description for Computer Link Operation
Chapter 11 Setting of Switches and Parameters
Chapter 12 Errors and Countermeasures
Chapter 13 Replacement of the JW-21MN
Chapter 14 Support Tools
Chapter 15 Specifications
Chapter 16 Appendix
Alphabetical Index
Table of contents
Chapter 1: Features and Functions .......................................................................... 1-1
Chapter 2: Safety Precautions ...........................................................................2-1 to 3
12-2 Flag .......................................................................................................................................... 12-2
[1] Flag table ................................................................................................................................. 12-2
[2] In the case of a master station ................................................................................................. 12-3
[3] In the case of slave station 01 to 77(8) ...................................................................................... 12-4
[4] Monitor operation condition by each station PC ...................................................................... 12-5
12-3 Storage of error code ............................................................................................................... 12-6
Chapter 13: Replacement of the JW-21MN ............................................................ 13-1
Chapter 14: Support Tools ............................................................................... 14-1 to 2
Chapter 15: Specifications ............................................................................... 15-1 to 3
15-1 General specifications ............................................................................................................. 15-1
15-2 Communication specifications ................................................................................................. 15-1
15-3 Data link specifications ............................................................................................................ 15-2
15-4 Computer link specifications .................................................................................................... 15-3
Chapter 16: Appendix .....................................................................................16-1 to 16
16-1 Maintenance and check ........................................................................................................... 16-1
16-2 Recovery method at communication errors ............................................................................. 16-2
16-3 Table of parameter memory ..................................................................................................... 16-8
16-4 Special functions unique to the JW-21MN ............................................................................. 16-13
Chapter 1: Features and Functions
JW-21MN is a ME-NET module for JW20/JW20H/JW30H. Using this module, you can construct an MENET combining various FA equipment such as personal computer and robot.
Using this module, you can easily transmit and receive ON/OFF signals and data with devices that
have a network module which is compatible with the ME-NET specifications.
[When you want to install a JW-21MN in the JW30H, make sure to select one that is compatible with
the JW30H. (See precautions inside the front page of this manual.)]
(1) Data link function
- Send and receive an ON/OFF signal (relay link) and data (register link)
between modules on the ME-NET.
Number of linkage pointsLinkage method
Relay link2048 (256 bytes) in total
Register link 2048 bytes in total
*The amount of data that can be transmitted by one station is a maximum of 1024 bytes,
including both relay link and register link.
- In order to use memory effectively, the JW-21MN has a memory save function. When this
function is enabled, it only needs to receive the specifically required data.
.
(2) Computer link function
- Triggered on commands (instructions) from a host computer which has a network module
compatible with the ME-NET specifications, the JW-21MN starts reading and writing the memory
in the JW20/JW20H/JW30H.
- After an instruction is received from the host computer, the JW-21MN returns a response.
Therefore, the host computer is required to create an application program. For detailed
description of how to transmit instructions and receive responses, see the instruction manual for
the host computer.
1
(3) This module is available communication up to 64 stations. By using a cable, it can be
extended up to 1 km.
Reference
ME-NET is a communication network to link different brands of devices and equipment with different
models of facility control equipment. It has been developed under the support of Toyota Motor Co.,
Ltd.
1-1
Chapter 2: Safety Precautions
2-1 Installation
Do not install or store the JW-21MN in the following conditions.
- Direct sunlight
- Ambient temperature exceeding the range of 0 to 55 ˚C (Storage temperature : -20 to 70 ˚C)
- The relative humidity exceeding the range of 35 to 90%.
- Sudden temperature changes which may cause condensation.
- Corrosive or inflammable gas
- Vibration or hard jolts
Prior to installing or detaching the JW-21MN, make sure to turn OFF the power supply to the JW20/
JW20H/JW30H (main PC of the system).
All screws must be tightened firmly.
2-2 Wiring
Make sure to use only the recommended types (see page 6-1) for cables, connectors, and
crimping tools. Cable and connector installation and changes must be performed only by specialists
approved by the ME-NET bureau.
When using connectors for branch or joint lines, provide jackets to protect connectors.
(When a connector touches with an external enclosure or the like, a communication error may
occur.)
2
"T" jacket
(insulation cover)
"L" jacket
(insulation cover)
Do not connect the ground terminal of the power supply module together with other equipment's
ground lines. Make sure to provide class-3 grounding.
When the JW-21MN is used without connecting a class-3 grounding, malfunctions by noise may
occur.
Communication cables should be arranged as far from any high voltage lines and strong power
lines as possible. Do not lay the communication cable parallel or proximate to these lines.
2-1
Communication cables should be laid from the master station to the slave station one by one.
Multiple wiring from one point or wiring without terminators may cause communication errors.
Joint using a
connector
2
Arrange total cable length within 1 km.
Arrange branch cable line from a trunk within 400 mm.
Prior to any electric welding around the JW-21MN, take out the coaxial cable from the JW-21MN.
While the coaxial cable is connected to the JW-21MN, any electric welding nearby the JW-21MN
will cause the welding current to enter the JW-21MN and may damage part of its circuit pattern.
JW-21MN
Turn "ON"
shield ground switch
FG
Coaxial cable
Wraparound current
(Note)
Electric welder
JW-21MN
Turn "ON"
shield ground switch
FG
Rack etc.
Note: In case enough conductivity is not
established.
2-2
2-3 Treatment
For ventilation, holes are provided in the cabinet to prevent a temperature rise. Do not block the
ventilation holes. Good ventilation is necessary.
Never allow a liquid such as water and chemical solution and a metallic object like a copper wire
inside the JW-21MN to avoid a possible hazard. Otherwise, it may be a cause of machine trouble.
When a trouble or abnormal condition such as overheat, fume, or smoke is met, stop the operation
immediately, and call your dealer or our service department.
2-4 Static electricity
In extremely dry circumstances, the human body may have excessive static current. This excessive
static current may damage parts in the JW-21MN's PC board. Therefore, prior to accessing the JW21MN, touch your hand to a grounded piece of metal to discharge the static current in your body.
2-5 Maintenance
Use a clean, dry cloth when cleaning the JW-21MN. Do not use volatile chemicals such as thinner or
alcohol as it may result in deformation and color fading.
2-6 Allocation of relay number
JW20/JW20H/JW30H which installs JW-21MN are laid out 16 points to the JW-21MN as a relay
number. These 16 points are dummy area which is not used in JW-21MN.
2
2-3
Chapter 3: System Configuration
- An example of system configuration using the JW-21MN as a master station
Robot
(8)
Slave station 77
(8)
Robot control section
ME-NET
module
Master station 00
JW20
JW20H
JW-21MN
JW30H
Slave station 01(8)
(8)
JW-21MN
Slave station 03
Personal computer
Slave station 02
(8)
Programmable controller
ME-NET module
ME-NET module
ME-NET (64 stations max., 1 km max.)
- An example of system configuration using some other module as a master station
Robot
Master station 00
JW50H
JW70H
JW-21MN
JW100H
(8)
Slave station 01
JW20
JW20H
JW30H
JW-21MN
Slave station 02
(8)
Programmable controller
ME-NET module
(8)
ME-NET (64 stations max., 1 km max.)
Slave station 03
Personal computer
ME-NET module
(8)
Slave station 77
Robot control section
ME-NET
module
(8)
3
3-1
Chapter 4: Name and Function of Each Part
Ventilation hole
(Prevent temperature rise inside)
Indication lamp
(See page 12-1)
Module number switch(UNITNO.)
(See page 11-2)
Station number switch(STANO.)
(See page 11-3)
Support tool connection connector
Connect a support tool
and set parameters
Communication cable
connection connector
(Connect master station and slave station)
ME-NET mark
Module insertion guide
(Insert into a rack panel)
Mode switch (MODE)
(See page 11-2)
(Front view)
Module retention screw
(For fixing on a rack panel)
30Hn
mark
(Applied to JW30H)
Rating plate
Switch
Module No. switch
UNIT
NO.
STANO.
STANO.
Station No. switch
Mode switch
4
3
2
1
0
F
E
D
4
Factory
setting
8
7
9
6
0
5
1
4
2
3
8
7
9
6
0
5
1
4
2
3
×10
8
7
9
6
0
5
1
4
2
3
×1
5
6
7
8
9
MODE
A
B
C
0
0
0
2
Termination resistance switch (LT)
(See page 11-3)
Shield ground switch (LG)
(See page 11-4)
Module retention rib
(For fixing on a rack panel)
4
5
3
6
2
7
1
8
0
9
F
A
E
B
D
C
(Rear view)
4-1
Termination resistance
Shield ground switch
Ventilation hole
(Prevent temperature rise inside)
ON
OFF
ON
OFF
switch
LT
LG
OFF
ON
Chapter 5: Installation
MODE
ON
OFF
LT
LG
ON
OFF
Installation procedure
Turn "OFF" the power supply to the JW20/JW20H/JW30H.
Set the mode switch, the termination resistance switch, and the shield ground switch on
the rear side of the JW-21MN.
(See page 11-2 to 11-4 for settings)
(Rear view of the JW-21MN)
Applicable screwdriver
Mode switch
Termination
resistance switch
Shield ground switch
2to3mm
5
0.5mm
Hang the module retention rib of the JW-21MN on the retention rib insertion hole of the JW20/
JW20H/JW30H's basic rack panel, and press in the JW-21MN. Then tighten the module retention
screws at the top of the JW-21MN module using a Phillips screwdriver.
- The JW-21MN cannot be installed on the expansion rack panel.
- Number of installations of the JW-21MN on the same JW20/JW20H/JW30H basic rack panel should
be within 7 in total including other option module (including JW-21MN). Installation of more than seven
modules of the JW-21MN will not allow the JW20/JW20H/JW30H to function.
- Make sure to tighten the module retention screws securely. Looseness of the screws may cause
malfunctions.
5-1
Chapter 6: Processing of Cables
Make sure to use the qualified products shown below for cables and connectors. Cable and connector
installation and changes must be performed only by specialists approved by the ME-NET bureau.
Name
Cable
Crimping tools
Stripper for high frequency
Jacket
Insulation
tape
High frequency
coaxial cable
coaxial cable
"L" jacket
"T" jacket
Self-adhesive tape
Connector
Model
ME-5C-2V
ME-42H
Dice: 67-42H
CST-TM
The system consists of the
main body, a blade cassette,
and a blade setting gauge
ring) back and forth and the cable holder moves back
and forth accordingly. Confirm this movement of the
stripper first.
To hold the stripper, put your forefinger through the
hole and move the cam while pushing back and forth
with your thumb.
6
<Pressure setting>
Set the operation range of the cable holder by moving
the slider at the bottom of the body. Move to the left
to increase pressure.
In this example, set the slider to the cam wheel side’s
end (right side) to set the pressure to low.
Blade cassette
Front
Cam wheel
Rear
Blade (slashed area)
<Adjustment of blade cutting depth>
Adjust the cutting depth of the blade by turning the
two screws at both ends of the screw holder. Set
the blade position to within 1 mm from the cutting
surface of the blade cassette prior to adjusting the
cutting depth. For the cutting depth adjustment, use
the "blade setting gauge" supplied as an accessory
and match the blade position with the caved position
of the gauge. Then move the cam wheel forward
and secure firmly. Turn right lightly both adjustment
screws at either end of the screw holder for
adjustment. (Be careful not to break the blade setting
gauge as it is made of aluminum.)
(Fine adjustment is required to get the
optimum cutting depth.)
To the next page
Left
Slider
Screw holder
Within 1 mm
Set the blade to within
1 mm in order not to
damage the blade by
the blade setting gauge.
Cam wheel
Right
Blade setting gauge
6-2
Coating
(black)
External conductor
(meshed annealed copper wire)
Insulator
(semi-transparent)
From the previous page
<Cutting of coating, external conductor, and insulator>
Put a coaxial cable while remaining approximately 10 mm into
the cable stripper and securely tighten the cable with the middle
finger, ring finger, and little finger of your left hand in order to
hold stable during turning the stripper.
Put your right hand forefinger into the cam wheel and execute
the procedure in order from step 1 below.
Internal conductor
(annealed copper single wire)
While holding the coaxial cable with your left hand, grip the
cable stripper so that it keeps a right angle against the coaxial
cable, and press out the cable stripper with your left hand’s
thumb.
When the adjustment
of the blade is not
required
Step 1
Press the cam wheel forward 3 times and turn
the stripper in the direction of arrow 2 to 3
times.
Step 2
Press the cam wheel forward 1 time and then
turn the stripper in the direction of arrow a
further 2 to 3 times.
Step 3
Press the cam wheel forward 1 more time and
turn the stripper in the direction of the arrow
another 2 to 3 times.
<Removal of coating, external conductor, and insulator>
If the stripper cannot be removed smoothly,
adjustment of the blade is not appropriate. In this
case slide the cam wheel backward and remove
the coaxial cable. Then adjust the blade.
6
10mm
<Fine adjustment of blade cutting depth>
When the cutting depth is too shallow or too deep, and
damages the external conductor or the internal conductor, turn
the screws on the screw holder and adjust the blade depth a
little.
To the next page
6-3
From the previous page
We recommend that in order to keep the adjusted
position of the adjustment screws, after completion
of adjustment for the coaxial cable and the screw
holder, write the screw position etc. on a sticker
and adhere it to the adjustment screws.
<Display of blade setting>
KADAEA
KEDAADFS
K
A
E
C
A
A
D
A
A
D
F
S
F
G
H
H
G
<Replacement of blades>
Blade cassette
Hold up the upper section of the screw holder with
a minus driver, and open the screw holder.
6
Remove the blade cassette and reinsert by turning
the current blade back side front or insert a new
blade cassette from its top.
Screw holder
<Processing of cable end>
Cut the internal conductor of the coaxial cable,
which is already cut by the stripper, using a nipper
etc. to the optimum dimension of 4 mm.
10mm±0.5mm
6-4
BA
A:10±0.5mm
B: 4±0.5mm
6-2 Connector crimping procedure
9
.
1
.
TT-237
TT
237
Required tools: Hand-held crimping tool
Model
Dice No.
Crimping width
: ME-42H
: 67-42H
: 10 mm
Connector: ME-GP-01
Processing procedure
<Insert a sleeve>
Put through a sleeve to an end-processed high
frequency coaxial cable.
<Crimping contact>
Insert a contact into the internal conductor and crimp.
Sleeve
Connector parts
Contact
A:10±0.5mm
B: 4±0.5mm
Shell
A
Sleeve
B
6
Put a contact into dice having a
diamond shape and closely stick its
end surface with the insulator and the
dice. Pull the moving frame to the
fixing frame side and crimp until the
ratchet is removed.
(Crimping width: 2.2 mm)
Widen a little
Crimp
Dice blade shape
2.2 mm
Closed contact
* Use the crimping tool in the direction
shown in the illustration right.
Using the crimping tool in the reverse
direction will not crimp correctly.
Internal conductor
Crimping dice
Moving frame
Insulator
Crimping dice
-
TT
237
9
.
.
1
Contact
Fixing frame
Contact
Closed
contact
To the next page
6-5
From the previous page
TT
237
<Fixing the connector>
Slightly widen the external conductor of the
coaxial cable, which is crimped to a contact on
the internal conductor, in order to smoothly enter
the shell inside the external conductor. Press in
the external conductor end of the coaxial cable
to just before the crimping part of the shell and
put the sleeve into the crimping section. Then
press in the coaxial cable until a “click” sound
can be heard. Confirm that the contact end point
touches your finger cushion.
Widen a little
Sleeve
Shell
Crimping section
Finger
<Crimping external conductor>
Crimp the external conductor.
6
Insert thoroughly the sleeve into the
Completely put into
the crimping section.
crimping section of the shell and crimp.
Put the sleeve in the hexagonal dice
and closely stick the shell to the
crimping dice. Pull the moving frame
to the fixing frame side while pressing
the coaxial cable and shell from both
10
Dice blade shape
sides, and crimp until the ratchet is
removed.
(Crimping width: 10 mm)
Dice blade shape
looking from this side
Crimping dice
Push
Closed contact
* Use the crimping tool in the direction
shown in the illustration right.
Using the crimping tool in the reverse
direction will not crimp correctly.
-
TT
237
9
.
.
1
Insulation test of shell and contact
Using a tester, check the conductivity
between the internal conductor and
the external conductor in the
connector. When the indication of
the tester shows ¥ ohms, the
insulation is appropriate.
Conductivity test
After short-circuiting the one end
of the connector crimped to the
coaxial cable, check that
conductivity is attained.
<Insulation test>
<Conductivity test>
6-6
Chapter 7: Wiring Method
7-1 Cable trunk and branch lines
On the illustration of the cable wiring below, a bold line means a trunk and the thin lines branched
from the trunk with a "T" shape are called branch lines.
400mm max.
The length of branch lines branched from the trunk should be within 400 mm.
Branch line
Trunk cable
7
400mm
Total cable length should be within 1 km.
Branch line
Trunk cable
7-2 Relaying of trunk cables
To relay trunk cables, use the straight joint (ME-JJ-01).
ME-JJ-01
Relaying of trunk cables should be limited to indispensable cases only. Inadvertent relaying of trunk
cables may cause a communication fault such as a weakened signal level due to contact resistance
in the junction connector (straight).
Junction
Junction
7-1
7-3 Cable wiring procedure in control panel
(1) Fixing of the cable
In order not to put any force on the cable and the
JW-21MN, fasten the cable to an line nearby input of
a control panel or a "T" branch point to the JW21MN using saddles etc.
(2) Extra length of cable
Provide an extra length of the cable of 2 to 3 m
inside a control panel for easier processing of the
cable end and easier wiring when changing module
positions.
7
(3) Connection to the JW-21MN
The connector to the JW-21MN should be turned
right to secure locking, not merely inserted.
Communication cable
connection connector
Saddle
JW-21MN
Saddle
Anextralengthof
cableof2to3m
(4) Insulation cover
When the connector touches with a high voltage
section or external enclosures, communication
errors may occur. Make sure to install an insulation
cover.
"T" jacket
(insulation cover)
"L" jacket
(insulation cover)
(5) Grounding of power supply module (JW-22PU/31PU)
Make sure to use a class-3 grounding to connect the GND terminal of the power supply module.
- If the power supply module is not grounded, the JW-21MN cannot conduct with the ground after
turning "ON" the shield ground switch.
When using a JW-31PU AC power supply module
Class-3
grounding
POWER
INPUT
100-120VAC
HALT
OUTPUT
100-120VAC
(24VDC)
1A
SHORT
GND
L
Power input terminal for
85 to 132 VAC
N
GND (ground) terminal
Halt output terminal
7-2
(6) Bending radius of the signal cable should be less than 45 mm (outside).
R45 or larger
- Specification of the cable manufacturer is that bending radius should be 6x of the cable finish
outside diameter (approx. 7.5 mm).
(7) When you install morethan one module of the JW-21MN into one programmable controller, we
recommend to put identification tag on each dable.
7
(8) Before transport or store the JW-21MN, put a protection cap on the connector of the JW-21MN.
7-3
7-4 Waterproof and insulation processing of connectors
In order to prevent water intrusion into the "T" branch connectors and the straight connectors, we
recommend to wind a self-adhesive tape and provide waterproof processing for them. For insulation
purposes, cover these connectors with jackets.
(1) "T" branch connector
To wind a self-adhesive tape, cut the tape at about 10 cm each and start winding from position .
Start winding cut tapes from and as well.
Self-adhesive tape
T’s
7
(2) Straight connector
To wind the self-adhesive tape, cut the tape at about 15 cm each and start winding from position
.
Self-adhesive tape
Straight
Remarks
Prior to adhering the tape, clean the surface of the connectors and stick the adhesive side of
the tape on the connector surface. Wind to lightly spread on the connector surface, and overlap
with the next wrap to half of the tape width. Wind the tape for each wrap evenly so that the
connector metal portion is completely covered with the tape.
Be careful not to excessively stretch the tape.
7-4
7-5 Wiring of cables at outside control panels
Do not bundle the coaxial cable (the trunk and branch lines) together with power cables, and
separate from power cables at least by 100 mm. Do not put the coaxial cable into a power line wired
duct. The best way is to put the communication line in an independent duct.
Be careful that the coaxial cable does not receive any load by laying under a heavy weight such as
other cables.
When other cables run in the same duct as the coaxial cable, run the coaxial cable on the top
position.
Do not run the coaxial cable outdoors as it may cause damage to the JW-21MN due to inductive
lightning or atmospheric charge during lightning.
7-6 Check after wiring
Check the items below after completion of wiring.
Check contents
1The recommended connector types are used.
7
2The connectors are securely locked.
3The connectors are insulated by "T" jacket or "L" jacket.
4The recommended coaxial cable type is used.
5Curved radius of the coaxial cables are more than 45 mm.
6Noheavy load is on the coaxial cables.
The coaxial cable is not bundled with a power line cable.
7
(Away from power line cables more than 100mm.)
8Length oh branch lines is shorter than 400mm.
9Total length of the cable is less than 1km.
Settings of the termination resistance switch and the shield ground switch are as
10
per the drawings.
7-5
7-7 Wiring method for adding a communication station
(1) Branching method
When branching a line for an additional station, be sure to branch from the trunk using a T
connector.
Never branch from a branch line.
(2) Station number of the additional station
Station number
(8)
0 2
Trunk
cable
Station number
Branch
line
0 3
(8)
Addition
Station number
(8)
0 2
Station number
(8)
0 2
Trunk
cable
Station number
(8)
0 6
Station number
(8)
0 6
Station number
Junction
Station number
0 3
0 3
(8)
(8)
Branch line
7
Station number of the newly added station should be next largest number from the current largest
numbered station. Each station should not be required to be arranged in order of each station’s
number.
01(8)
02(8)
03(8)
Addition
Sequential number
00(8)
01(8)
02(8)
03(8)06(8)
means the termination resistance switch being turned "ON."
04(8)00(8)
04(8)
05(8)
05(8)
7-6
(3) Notes
When adding a communication station, follow the items below.
No.
Branch from the trunk cable.
1
Don’t use the same station number
2
twice.
Check the termination resistance
3
switch.
Provide extra length for the
4
expansion cable.
Do not exceed the 1 km limit for total
5
length of the cable.
Change the layout drawing for
6
installation.
Do not overlap with any PC’s
7
communication area.
Set the parameter memory of the
master station and that of the newly
8
added station.
ItemReason
Another branch line from a branch line may not give
appropriate communication by reflection wave.
The use of the same station number twice may cause
communication errors.
When the newly added station becomes a termination of
the circuit, change the setting of the LT switch.
Have enough cable length in order to provide easy wiring.
Longer wiring may cause communication error by signal
attenuation.
Maintain the added work data for future maintenance use.
When the communication area or the flag area of the
added station overlaps with other addresses in use,
communication errors may occur.
Without setting the parameter memory of the master
station and that of the slave station, the added station
cannot communicate.
7
7-7
Chapter 8: Memory Address on the ME-NET
The ME-NET employs a system for addressing individual memory banks in all of the connected
equipment by allocating address throughout the ME-NET. Therefore, the top address in any link area
which will contain in the data link parameters and memory addresses used for computer link
instructions must be a valid memory address in the ME-NET.
The relationship between memory addresses in Sharp PCs (JW20/JW20H/JW30H) and those on the
ME-NET are shown below.
8-1 Memory address for data links
The memory addresses(8) on the ME-NET correspond to the file addresses(8) in a Sharp PC (JW20/
JW20H/JW30H).
(1) Memory address map (against JW20/JW20H)
JW20/20H addressME-NET address
Byte address
1 address = 1
point
I/O relay00000 to 03777
Byte address
(8)
1 address = 8
コ 0000 to コ 0377
points
File address
(8)
1 address = 8
000000 to 0003770000 to 00FF000000 to 000377
points
(8)
Byte unit:
Hexadecimal
Byte unit: Octal
Auxiliary relay04000 to 06777
Latched relay07000 to 07777
General-purpose
relay
TMR/CNT contact
point
TMR/CNT current
value
Register
Self diagnosis
result storage
register
10000 to 15777
T-C000 to T-C777001600 to 0017770380 to 03FF001600 to 001777
コ 0400 to コ 0677
コ 0700 to コ 0777
コ 1000 to コ 1577
b0000 to b1777002000 to 0037770400 to 07FF002000 to 003777
09000 to 09777004000 to 0047770800 to 09FF004000 to 004777
19000 to 19777005000 to 0057770A00 to 0BFF005000 to 005777
29000 to 29777006000 to 0067770C00 to 0DFF006000 to 006777
39000 to 39777007000 to 0077770E00 to 0FFF007000 to 007777
49000 to 49777010000 to 0107771000 to 11FF010000 to 010777
59000 to 59777011000 to 0117771200 to 13FF011000 to 011777
69000 to 69777012000 to 0127771400 to 15FF012000 to 012777
79000 to 79777013000 to 0137771600 to 17FF013000 to 013777
89000 to 89777014000 to 0147771800 to 19FF014000 to 014777
99000 to 99777015000 to 0157771A00 to 1BFF015000 to 015777
E0000 to E1777016000 to 0177771C00 to 1FFF016000 to 017777
000400 to 0006770100 to 016F000400 to 000677
000700 to 0007770170 to 01FF000700 to 000777
001000 to 0015770200 to 0037F001000 to 001577
8
- For details about the address range of relay link, register link, and the JW-21MN flag, see page
11-11 in this manual.
- The addresses that can be used vary with PC model in which the JW-21MN is installed and with
the memory capacity of the PC. For details, see the instruction manual for a particular PC.
8-1
(2) Memory address map (against JW30H)
JW30H addressME-NET address
Byte address
1 address=1point
Relay00000 to 15777
TRM/CNT contact
point
T-C0000 to T-C0777001600 to 0017770380 to 03FF001600 to 001777
TMR/CNT current
value
(8)
Byte address
1 address = 8
コ 0000 to コ 1577
b0000 to b1777002000 to 0037770400 to 07FF002000 to 003777
09000 to 09777004000 to 0047770800 to 09FF004000 to 004777
19000 to 19777005000 to 0057770A00 to 0BFF005000 to 005777
29000 to 29777006000 to 0067770C00 to 0DFF006000 to 006777
39000 to 39777007000 to 0077770E00 to 0FFF007000 to 007777
49000 to 49777010000 to 0107771000 to 11FF010000 to 010777
points
File address
(8)
1 address = 8
point
(8)
Byte unit:
Hexadecimal
Byte unit: Octal
000000 to 0015770000 to 037F000000 to 001577
Register
59000 to 59777011000 to 0117771200 to 13FF011000 to 011777
69000 to 69777012000 to 0127771400 to 15FF012000 to 012777
79000 to 79777013000 to 0137771600 to 17FF013000 to 013777
89000 to 89777014000 to 0147771800 to 19FF014000 to 014777
8
99000 to 99777015000 to 0157771A00 to 1BFF015000 to 015777
E0000 to E5777016000 to 0237771C00 to 27FF016000 to 023777
Register (storable
error history)
TMR/CNT current
value
Expansion relay20000 to 75777
TMR/CNT contact
point
T-C1000 to T-C1777
E6000 to E7777024000 to 0257772800 to 2BFF024000 to 025777
b2000 to b3777026000 to 0277772C00 to 2FFF026000 to 027777
コ 2000 to コ 7577
コ 7600 to コ 7777
030000 to 0355773000 to 3B7F030000 to 035577
035600 to 0357773B80 to 3BFF035600 to 035777
File 1000000 to 0377771-000 to 3FFF000000 to 037777
File 2000000 to 1777772-000 to FFFF000000 to 177777
File 3000000 to 1777773-000 to FFFF000000 to 177777
000000 to 17777710-000 to FFFF000000 to 177777
000000 to 177777 11-000 to 3FFFF 000000 to 177777
000000 to 1777771F-000 to FFFF000000 to 177777
000000 to 17777720-000 to FFFF000000 to 177777
000000 to 17777721-000 to FFFF000000 to 177777
File
register
File 10
(H)
File 10
(H)
::::
File 1F
(H)
File 20
(H)
File 21
(H)
::::
File 2C
(H)
000000 to 1777772C-000 to FFFF000000 to 177777
* ME-NET addresses for file 10 to 2C(H) are out of the range the ME-NET specification.
These are special addresses for the JW-21MN.
- As for address setting range of relay link, register link, and flag of the JW-21MN, see page 11-12
in this manual.
- Available addresses vary with PC model on which the JW-21MN is installed and its capacity. For
details, see an instruction manual for each PC.
8-2
Loading...
+ 84 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.