In the interests of user-safety (Required by safety regulations in some countries) the set should
be restored to its original condition and only parts identical to those specified should be used.
UNIT INDEPENDENTLY................................ 3-5
[5]
GENERAL TROUBLESHOOTING CHART
Parts marked with "" are important for maintaining the safety of the set. Be sure to replace these parts with specified ones for maintaining the
safety and performance of the set.
CondenserCorrugate Fin and Grooved tube type
ControlCapillary tube
Refrigerant (R410A)690g
De-lce system Micro computer controled reversed systems
HighdB(A)3745
LowdB(A)31–
SoftdB(A)23–
Highm3/min.9.126.4
Lowm3/min.7.4–
Softm3/min.4.7–
Fan motors: Thermal fuse
Fuse, Micro computer control
Heightmm292540
Depthmm205250
NOTE: The conditions of star ”I” marked item are “ISO5151:1994(E )”, condition T1’.
1 – 1
2. AY-XP12LSR – AE-X12LSR
MODELINDOOR UNITOUTDOOR UNIT
ITEMSAY-XP12LSRAE-X12LSR
Rated cooling capacity (Min– Max.)kW3.5 (0.9 - 3.8)
Rated heating capacity (Min–Max.)kW4.0 (0.9 - 4.7)
Moisture removal (at cooling)Liters/h1.2
Electrical data
PhaseSingle
Rated frequencyHz50
Rated voltageV220-240
Rated current I
(Min - Max.)
Rated input I
(Min - Max.)
Power factor ICool%94
CompressorTypeHermetically sealed rotary type
Refrigerant systemEvaporatorLouver Fin and Grooved tube type
CondenserCorrugate Fin and Grooved tube type
ControlCapillary tube
Refrigerant (R410A)970g
De-lce system Micro computer controled reversed systems
HighdB(A)4048
LowdB(A)33–
SoftdB(A)23–
NOTE: The conditions of star ”I” marked item are “ISO5151:1994(E)”, condition T1’.
1 – 2
AYXP9LSR
250
165
167.5
136
81
730
72
540
299
324
515
12
37.5
4.5
58
135
14
[2] EXTERNAL DIMENSION
1. Indoor unit
Length unit [mm]
Remote controller
17.5
140
57
205
292
2. Outdoor unit
Length unit [mm]
1 – 3
[3] WIRING DIAGRM
1. Indoor unit
AYXP9LSR
2. Outdoor unit
1 – 4
AYXP9LSR
[4] ELECTRICAL PARTS
1. Indoor unit
DESCRIPTIONMODELREMARKS
Indoor fan motorMLA521AC Motor
Indoor fan motor capacitorDS401155BLSARC-HZA512JBZZ (400V-1.5μF)
TransformerVRK4119–290mARTRNPA030JBZZ
Fu1– QFS-IA 001KK ZZ (250V, 2.5A)
2. Outdoor Unit
DESCRIPTIONMODELREMARKS
Compressor43A23YBM&FJKED.C. brush-less motor
Outdoor fan motorMLB452AC Motor(AE-X12LSR)
Outdoor fan motorMLB453AC Motor(AE-X9LSR)
Outdoor fan motor capacitorDS441155XLTD440V, 1.5μF (AE-X9LSR) on PWB
Once the compressor stops operating, it will not restart for 180 seconds to protect the compressor.
Therefore, if the operating compressor is shut down from the remote
control and then turned back on immediately after, the compressor will
restart after a preset delay time.
(The indoor unit will restart operation immediately after the ON switch
is operated on the remote control.)
1.2. Cold air prevention control
When the air conditioner starts up in heating mode, the indoor unit fan
will not operate until the temperature of the indoor unit heat exchanger
reaches about 23°C in order to prevent cold air from blowing into the
room.
Also, the indoor unit fan operates at low speed until the temperature of
the indoor unit heat exchanger reaches about 38°C so that people in
the room will not feel chilly air flow.
1.5. Indoor unit overheat prevention control
During heating operation, if the temperature of the indoor unit heat
exchanger exceeds the indoor unit heat exchanger overheat prevention temperature (about 45 to 54°C) which is determined by the operating frequency and operating status, the operating frequency is
decreased by about 4 to 15 Hz. Then, this operation is repeated every
60 seconds until the temperature of the indoor unit heat exchanger
drops below the overheat protection temperature.
Once the temperature of the indoor unit heat exchanger drops below
the overheat protection temperature, the operating frequency is
increased by about 4 to 10 Hz every 60 seconds until the normal operation condition resumes.
If the temperature of the indoor unit heat exchanger exceeds the overheat protection temperature for 60 seconds at minimum operating frequency, the compressor stops operating and then restarts after about
180 seconds, and the abovementioned control is repeated.
1.6. Defrosting
1.6.1 Reverse defrosting
The defrost operation starts when the compressor operating time
exceeds 10 minutes during heating operation, as shown below, and
the outside air temperature and the outdoor unit heat exchanger temperature meet certain conditions. When the defrost operation starts,
the indoor unit fan stops. The defrost operation stops when the outdoor unit heat exchanger temperature rises to about 10°C or higher or
the defrosting time exceeds 10 minutes.
1.3. Indoor unit heat exchanger freeze prevention control
If the temperature of the indoor unit heat exchanger remains below
0°C for 4 consecutive minutes during cooling or dehumidifying operation, the compressor operation stops temporarily in order to prevent
freezing.
When the temperature of the indoor unit heat exchanger rises to 2°C
or higher after about 180 seconds, the compressor restarts and
resumes normal operation.
1.4. Outdoor unit 2-way valve freeze prevention control
If the temperature of the outdoor unit 2-way valve remains below 0°C
for 10 consecutive minutes during cooling or dehumidifying operation,
the compressor operation stops temporarily in order to prevent freezing.
When the temperature of the 2-way valve rises to 10°C or higher after
about 180 seconds, the compressor restarts and resumes normal
operation.
1.7. Outdoor unit overheat prevention control
During cooling operation, if the temperature of the outdoor unit heat
exchanger exceeds the outdoor unit heat exchanger overheat prevention temperature (about 55°C), the operating frequency is decreased
by about 4 to 15 Hz. Then, this operation is repeated every 60 seconds until the temperature of the outdoor unit heat exchanger drops to
about 54°C or lower.
Once the temperature of the outdoor unit heat exchanger drops to
about 54°C or lower, the operating frequency is increased by about 4
to 10 Hz every 60 seconds until the normal operation condition
resumes.
If the temperature of the outdoor unit heat exchanger exceeds the outdoor unit heat exchanger over heat protection temperature for (120 sec
: outdoor temperature ≥ 40°C, 60 sec : outdoor temperature < 40°C)
at minimum operating frequency, the compressor stops operating and
then restarts after about 180 seconds, and the abovementioned control is repeated.
2 – 7
AYXP9LSR
Modes and Temperature Settings
the figures in ( ) are temperature settings
1)Press the SWING button on the remote control once.
Tuvre will swing continuously.
2)Press the SWING button again when the vertical airflow louvre is at
the desir ed position.
The louvre will stop moving within the range shown in the diagram.
The adjusted position will be memoried and will be automatically set
to the same position when operated the next time.
AIR FLOW DIRECTION
he vertical airflow lo.
the vert
iam.
AIR FLOW DIRECTION
.
the vert
iam.
AIR FLOW DIRECTION
٨
٨
٨
"The remote control will display"
٨
1.8. Compressor overheat prevention control
If the temperature of the compressor exceeds the compressor overheat prevention temperature (110°C), the operation frequency is
decreased by about 4 to 10 Hz. Then, this operation is repeated every
60 seconds until the temperature of the compressor drops below the
overheat protection temperature (100°C).
Once the temperature of the compressor drops below the overheat
protection temperature, the operating frequency is increased by about
4 to 10 Hz every 60 seconds until the normal operation condition
resumes.
If the temperature of the compressor exceeds the overheat protection
temperature (for 120 seconds in cooling operation or 60 seconds in
heating operation) at minimum operating frequency, the compressor
stops operating and then restarts after about 180 seconds, and the
above mentioned control is repeated.
1.9. Startup control
When the air conditioner starts in the cooling or heating mode, if the
room temperature is 2°C higher than the set temperature (in cooling
operation) or 3.5°C lower (in heating operation), the air conditioner
operates with the operating frequency at maximum. Then, when the
set temperature is reached, the air conditioner operates at the oper ating frequency determined by fuzzy logic calculation, then enters the
normal control mode after a while.
1.10. Peak control
If the current flowing in the air conditioner exceeds the peak control
current (see the table below), the operation frequency is decreased
until the current value drops below the peak control current regardless
of the frequency control demand issued from the indoor unit based on
the room temperature.
Peak control current
Cooling operationHeating operation
Approx. 6.1 AApprox. 8.2 A
1.11. AUTOMATIC AIR CONDITIONING
In the AUTO mode, the temperature setting and mode are automatically selected according to the room temperature and outdoor temperature when the unit is turned on.
1.12. Airflow control
CAUTION:
Never attempt to adjust the louvres manually.
•Manual adjustment on the louvres can cause the unit to malfunction.
Position in the COOL or DRY mode for an extended period of time,
•When the vertical airflow louvre is positioned at the lowest
condensation may result.
1.12.1 COANDA Airflow
Press the COANDA AIRFLOW button during cooling or dry operat ion
when you do not want to feel cold air.
Vertical airflow louvre is set obliquely upward to deliver cool air to the
ceiling.
Press the button during heating operation. Vertical airflow louvre is set
downward to deliver the warm air down to the floor and warm you.
During operation, press the COANDA AIRFLOW button.
During operation, if the outdoor temperature changes, the temperature
settings will automatically slide as shown in the chart.
1.13. Difference of operation in Auto and Manual modes
In the Auto mode, the temperature setting is automatically determined based on the outside air temperature. In addition, the air conditioner operation
differs from the operation in the Manual mode as explained below.
Automatic temperature setting based on inside air temperature. Can be changed within ±2°C using remote control.
TO CANCEL
Press the COANDA AIRFLOW button again.
NOTE:
•The COANDA AIRFLOW setting is cancelled
When you press Full power button while COANDA AIRFLOW is set.
•If you want COANDA AIRFLOW operation in Full power mode,
press COANDA AIRFLOW button during Full power operation.
Can be changed
between 18 and 32°C
using remote control.
Can be changed
between 18 and 32°C
using remote control.
Automatic setting.
Can be changed
within ±2°C.
2 – 8
1.14. Dehumidifying operation control
27ºC
+0
+0.5
-1.0
-1.5
25ºC
25ºC
28ºC
22ºC
22ºC
Room Temperature
Preset temperature
-
The remote control will display”“
The temperature display will go off.
The green Full power lamp () on the unit will light up.
٨
٨
٨
The green Full power lamp () on the unit will turn off.
٨
Heating operationFan operation
24OC
Outside air temperature
Heating operation
Set temperature
Activation of
OFF timer
1hour
later
Max.
1.5 hours
later
Max.
2 hours
later
Timer setting
reached
1hour
later
Max.
1.5 hours
later
Max.
2 hours
later
Timer setting
reached
Activation of
OFF timer
Set temperature
-1
O
C
-1
O
C
-1
O
C
0.3
O
C
0.3
O
C
0.3
O
C
Cooling/dehumidifying operation
In the Dehumidifying mode, the temperature setting is automatically
determined based on the outside air temperature. In addition, the air
conditioner operation differs from the operation in the Manual mode as
explained below.
1.15. Full power Operation
In this operation, the air conditioner works at the maximum power to
make the room cool rapidly.
During operation, press the Full power button.
AYXP9LSR
1.17. Plasmacluster Ion function
The Plasmacluster Ion generator inside the air conditioner will release
positive and negative plasmacluster ions into the room.
ApproXimately the same numbers of positive and negative ions
released into the air will reduce some airborne mold.
If the Plasmacluster Ion generation function is operated together with
the air conditioner operation, the indoor unit fan speed and louver
direction are in accordance with the air conditioner settings.
If the Plasmacluster Ion generation function is used without operating
the air conditioning function, the indoor unit fan operates at a very low
speed and the upper louver is angled upward and the lower louver
remains horizontal. (The airflow volume and direction can be changed
by using the remote control.)
1.18. Power ON start
If a jumper cable is inserted in the location marked with HAJP on the
indoor unit control printed circuit board (control PCB), connecting the
power cord to an AC outlet starts the air conditioner in either cooling or
heating mode, which is determined automatically by the room temperature sensor.
When a circuit breaker is used to control the ON/OFF operation,
please insert a jumper as described above.
1.19. ON timer
The ON timer can be activated by pressing the ON timer button. When
the ON timer is activated, the operation start time is adjusted based on
fuzzy logic calculations 1 hour before the set time so that the room
temperature reaches the set temperature at the set time.
TO CANCEL
Press the Full power button again.
The Full power operation will also be cancelled when the operation
mode is changed, or when the unit is turned off.
NOTE:
•The air conditioner will operation at “Extra HIGH” fan speed for 5
minutes, and then shift to “HIGH” fan speed.
• You can not set the temperature or fan speed during the Full power
operation.
• To turn off the Full power lamp, press the DISPLAY button.
1.16. Self Clean operation
Heating or Fan operation and Cluster operation are performed simultaneously.
The judgment of whether Heating or Fan operation is used is based on
the outside air temperature at 3 minutes after the start of internal
cleaning.
The operation stops after 40 minutes.
• During this operation the horizontal louver moves and stays two posi-
tions.
It turns to the lower direction and stays for 30 minutes.
Next moves upward and stays for 10 minutes.
1.20. OFF timer
The OFF timer can be activated by pressing the OFF timer button.
When the OFF timer is set, the operation stops after the set time.
When this timer is set, the compressor operating frequency lowers for
quieter operation, and the room temperature is gradually varied after
one hour (reduced 1°C three times (max. 3°C) in heating, or increased
0.3°C three times (max. 1°C) in cooling or dehumidifying operation) so
that the room temperature remains suitable for comfortable sleeping.
1.21. Auto restart
When power failure occurs, after power is recovered, the unit will automatically restart in the same setting which were active before the
power failure.
1.21.1 Setting not memorized
• Timer setting
• Full power operation setting
• Self clean operation
2 – 9
AYXP9LSR
1
3
SSR2
R39
Q11
Microcomputer output
1
4
Cluster unit
JPC1
JPC2
AC220-240V
12V
R34
PAM drive circuit block diagram
Reactor L1
[PAM drive circuit]
+
Microcomputer (IC1)
AC
230V
Compressor
Noise
filter
AC clock
detection
circuit
DB1
IPM
DB2
Compressor
position
detector
IGBT
drive
circuit
IGBT
Overvoltage
detection
circuit
1.21.2 Disabling auto restart function
By removing (cutting) jumper O (JP O) on the printed circuit board
(PCB), the auto restart function can be disabled.
2. Explanation of cluster circuit
The cluster unit generates cluster ions, which are circulated throughout the room by the air flow created by the blower fan (indoor unit fan motor) in
the air conditioner unit.
1) When microcomputer output turns "H," the Q11 output changes to "Lo," turning ON the SSR2 and applying 100 V to the cluster unit for the generation of cluster ions (positive and negative ions).
3. Outline of PAM circuit
3.1. PAM (Pulse Amplitude Modulation)
The PAM circuit varies the compressor drive voltage and controls the rotation speed of the compressor.
The IGBT shown in the block diagram charges the energy (electromotive force) generated by the reactor to the electrolytic capacitor for the inverter
by turning ON and OFF.
When the IGBT is ON, an electric current flows to the IGBT via the reactor (L1) and diode bridge (DB2).
When the IGBT turns OFF, the energy stored while the IGBT was ON is charged to the voltage doubler capacitor via the diode bridge (DB1).
As such, by varying the ON/OFF duty of the IGBT, the output voltage is varied.
2 – 10
AYXP9LSR
Stored energy
Reactor
L1
DB1
DB2
IGBT
IGBT ON
IGBT OFF
AC voltage waveform
AC voltage and current waveform when PAM is ON
AC current waveform
IGBT ON period
Zero-cross detection
AC voltage waveform
AC current waveform
AC voltage and current waveforms when PAM is OFF
AC voltage waveform
Clock
IGBT ON
A
BC
A
B
C
50Hz
11mS
1.0mS
0.25 2.3mS
CDQWV
CDQWV
3.2. High power factor control circuit
This circuit brings the operating current waveform closer to the waveform of commercial power supply voltage to maintain a high power factor.
Because of the capacitor input, when the PAM circuit is OFF, the phase of the current waveform deviates from the voltage waveform as shown below.
To prevent this deviation, a current is supplied during the periods indicated by "O" in the diagram.
To determine the length of period to supply a current, the zero-cross timing of the AC input voltage is input to the microcomputer via the clock circuit.
The power source frequency is also determined at the same time.
The IGBT turns ON after the time length determined by the zero-cross point to supply a current to the IGBT via the reactor.
This brings the current waveform closer to the voltage waveform in phase.
As described above, the ON/OFF operation of the IGBT controls the increase/decrease of the compressor power supply voltage (DC voltage) to
improve the compressor efficiency and maintain a high power factor by keeping the current phase closer to that of the supply voltage.
3.2.1 Detailed explanation of PAM drive circuit sequence
3.2.2 AC clock (zero-cross) judgment
• The clock circuit determines the time from one rising point of the clock waveform to the next rising point.
The detected clock waveform is used to judge the power source frequency (50Hz).
• The zero-cross of the AC voltage is judged as the rising of the clock waveform, as shown in the diagram above.
3.2.3 IGBT ON start time (delay time B)
• Based on the zero-cross of the AC voltage, the IGBT turns ON after a delay time set according to the power source frequency.
3.2.4 IGBT ON time (C)
• After the above delay time, the IGBT turns ON to supply a current to the reactor.
• The ON time of the IGBT determines the amount of energy (level of DC voltage rise) supplied to the reactor.
DC voltage level in each operation mode (varies depending on external load conditions)
– Cooling operation --- 220 to 290 V
2 – 11
AYXP9LSR
R125
270K
C10C9
R126
270K
R127
13K
R128
13K
0V
0V
5V
(Overvoltage detection)
During abnormal voltage output
IC
69
3.3. PAM protection circuit
To prevent excessive voltage of PAM output from
damaging the IPM and electrolytic capacitor as well
as the control printed circuit board (PCB), this circuit
monitors the PAM output voltage and turns off the
PAM control signal and PAM drive immediately
when an abnormal voltage output is generated. At
the same time, it shuts off the compressor operation.
The protection voltage level is as follows.
3.3.1 Details of troubleshooting procedure
for PAM
1) PAM shutdown due to error
1) When the DC voltage detection circuit sends a
signal exceeding the specified voltage to the
microcomputer
DC voltage of 400 V or higher
DC voltage of 184 V or less.
– When an error is detected
• PAM IGBT turns OFF.
• Compressor turns OFF.
• All units shut down compietely when the error occurs four times.
2) When the outdoor unit clock waveform differs from the specified value immediately before the PAM IGBT turns ON
When there is no clock waveform input
When a clock signal of other than specified power source frequency (50Hz) is input
– When an error is detected
• PAM IGBT does not turn ON.
• Compressor operates normally.
• Complete shutdown does not occur.
2) PAM error indication
In case of error “1)”
– An error signal is sent to the indoor unit as soon as an error is generated.
• Malfunction No. 14-0 is indicated when the error code is called out by the indoor unit's self-diagnosis function.
– The LED on the outdoor unit flashes 14 times when an error is generated.
• The LED continues flashing in the 14-time cycle even after the compressor stops operating.
• The LED turns off (data is deleted from the memory) when the outdoor unit power is turned off.
In case of error “2)”
– An error signal is sent to the indoor unit as soon as an error is judged.
• Malfunction No. 14-1 is indicated when the error code is called out by the indoor unit's self-diagnosis function.
– The LED on the outdoor unit flashes 14 times when an error is judged.
• The LED on the outdoor unit flashes in normal pattern when the compressor stops operating.
(Compressor OFF or Thermostat OFF from remote control)
* When a user complains that the air conditioner does not provide sufficient cool air or warm air
In addition t o conventional er ror-generating reasons, there is a possibility that the PAM IGBT does not turn ON even if the compressor is operating.
In that case, the DC voltage does not rise even though the compressor is operating, and lowers to the 180-VDC level.
– Check items
• Clock circuit check
•PAM IGBT check
• Fuse (Fu6) open-circuit check
2 – 12
Loading...
+ 42 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.