AYXP7FR
SERVICE MANUAL
S6512AYXP7FR/T
SPLIT TYPE
ROOM AIR CONDITIONER
INDOOR UNIT
MODELS
AY-XP7FR
AY-XP9FR
AY-XP12FR
In the interests of user-safety (Required by safety regulations in some countries) the set should
be restored to its original condition and only parts identical to those specified should be used.
CONTENTS
CHAPTER 1. SPECIFICATION
[1] SPECIFICATION............................................1-1
[2] EXTERNAL DIMENSION............................... 1-4
[3] WIRING DIAGRM ..........................................1-5
[4] ELECTRICAL PARTS....................................1-6
CHAPTER 2. EXPLAMATION OF CIRCUIT AND OPERATION
[1] BLOCK DIAGRAMS....................................... 2-1
[2] MICROCOMPUTER CONTROL SYSTEM ........2-3
[3] FUNCTION.....................................................2-8
CHAPTER 3. FUNCTION AND OPERATION OF PROTECTIVE PROCEDURES
[1] PROTECTION DEVICE FUNCTIONS AND
OPERATIONS................................................3-1
[2] AIR CONDITIONER OPERATION IN
THERMISTOR ERROR .................................3-3
[3] THERMISTOR TEMPERATURE CHAR-
ACTERISTICS ...............................................3-5
[4] HOW TO OPERATE THE OUTDOOR
UNIT INDEPENDENTLY................................3-6
OUTDOOR UNIT
AE-X7FR
AE-X9FR
AE-X12FR
[5] GENERAL TROUBLESHOOTING CHART ........3-6
[6] MALFUNCTION (PARTS) CHECK METH-
OD .................................................................3-8
[7] OUTDOOR UNIT CHECK METHOD...........3-10
[8] TROUBLESHOOTING GUIDE....................3-13
CHAPTER 4. REFRIGERATION CYCLE
[1] FLOW FOW REFRIGERANT ........................4-1
[2] STANDARD CONDITION..............................4-1
[3] TEMPERATURE AT EACH PART AND
PRESSURE IN 3-WAY VALVE......................4-1
[4] PERFORMANCE CURVES...........................4-2
CHAPTER 5. DISASSEMBLING PROCEDURE
[1] DISASSEMBLY OF INDOOR UNIT...............5-1
[2] DISASSEMBLY OF OUTDOOR UNIT...........5-7
REPLACEMENT P ARTS LIST
Parts marked with " " are important for maintaining the safety of the set. Be sure to replace these parts with specified ones for
maintaining the safety and performance of the set.
SHARP CORPORATION
This document has been published to be used
for after sales service only.
The contents are subject to change without notice.
AYXP7FR
AYXP7FR
CHAPTER 1. SPECIFICATION
Service Manual
[1] SPECIFICATION
1. AY-XP7FR – AE-X7FR
MODEL INDOOR UNIT OUTDOOR UNIT
ITEMS AY-XP7FR AE-X7FR
Cooling capacity(Min. > Max.) kW 2.1 (0.9 - 2.5)
Heating capacity(Min. > Max.) kW 2.4 (0.9 - 3.4)
Moisture removal(at cooling) Liters/h
Electrical data
Phase Single
Rated frequency Hz 50
Rated voltage V 230
Rated current ✩
(Min - Max.)
Rated input ✩
(Min - Max.)
Power factor ✩ Cool % 92
Compressor Type Hermetically sealed rotary type
Refrigerant system Evaporator Louver Fin and Grooved tube type
Noise level
(at cooling)
Fan system
Drive Direct drive
Air flow quantity
(at cooling)
Fan Cross flow fan Propeller fan
Connections
Refrigerant coupling Flare type
Refrigerant tube size Gas, Liquid 3/8", 1/4"
Drain piping mm O.D φ18
Others
Safety device Compressor: Thermal protector
Air filters Polypropylene net (Washable)
Net dimensions Width mm 790 730
Net weight kg 10 33
Cool A 2.5 (1.0 - 4.1)
Heat A 2.4 (0.9 - 4.5)
Cool W 530 (200 - 760)
Heat W 510 (160 - 1100)
Heat % 92
Model DA89X1F-23F
Oil charge 370cc (VG74)
Condenser Corrugate Fin and Grooved tube type
Control Expansion valve
Refrigerant (R410A) 830g
De-lce system Micro computer controled reversed systems
High dB(A) 37 45
Low dB(A) – –
Soft dB(A) 28 –
High m3/min. 8.0 23.2
Low m3/min. 6.8 –
Soft m3/min. 5.5 –
Fan motors: Thermal fuse
Fuse, Micro computer control
Height mm 278 540
Depth mm 198 250
1 – 1
2. AY-XP9FR – AE-X9FR
MODEL INDOOR UNIT OUTDOOR UNIT
ITEMS AY-XP9FR AE-X9FR
Cooling capacity(Min. > Max.) kW 2.64 (0.9 - 3.0)
Heating capacity(Min. > Max.) kW 3.1 (0.9 - 4.8)
Moisture removal(at cooling) Liters/h
Electrical data
Phase Single
Rated frequency Hz 50
Rated voltage V 230
Rated current ✩
(Min - Max.)
Rated input ✩
(Min - Max.)
Power factor ✩ Cool % 92
Compressor Type Hermetically sealed rotary type
Refrigerant system Evaporator Louver Fin and Grooved tube type
Noise level
(at cooling)
Fan system
Drive Direct drive
Air flow quantity
(at cooling)
Fan Cross flow fan Propeller fan
Connections
Refrigerant coupling Flare type
Refrigerant tube size Gas, Liquid 3/8", 1/4"
Drain piping mm O.D φ18
Others
Safety device Compressor: Thermal protector
Air filters Polypropylene net (Washable)
Net dimensions Width mm 790 730
Net weight kg 10 33
Cool A 3.7 (1.0 - 4.8)
Heat A 3.5 (0.9 - 6.1)
Cool W 780 (200 - 960)
Heat W 730 (160 - 1400)
Heat % 91
Model DA89X1F-23F
Oil charge 370cc (VG74)
Condenser Corrugate Fin and Grooved tube type
Control Expansion valve
Refrigerant (R410A) 830g
De-lce system Micro computer controled reversed systems
High dB(A) 39 45
Low dB(A) – –
Soft dB(A) 28 –
High m3/min. 8.6 23.3
Low m3/min. 7.3 –
Soft m3/min. 5.5 –
Fan motors: Thermal fuse
Fuse, Micro computer control
Height mm 278 540
Depth mm 198 250
AYXP7FR
1 – 2
AYXP7FR
3. AY-XP12FR – AE-X12FR
MODEL INDOOR UNIT OUTDOOR UNIT
ITEMS AY-XP12FR AE-X12FR
Cooling capacity(Min. > Max.) kW 3.5 (0.9 - 3.8)
Heating capacity(Min. > Max.) kW 4.0 (0.9 - 6.0)
Moisture removal(at cooling) Liters/h
Electrical data
Phase Single
Rated frequency Hz 50
Rated voltage V 230
Rated current ✩
(Min - Max.)
Rated input ✩
(Min - Max.)
Power factor ✩ Cool % 95
Compressor Type Hermetically sealed rotary type
Refrigerant system Evaporator Louver Fin and Grooved tube type
Noise level
(at cooling)
Fan system
Drive Direct drive
Air flow quantity
(at cooling)
Fan Cross flow fan Propeller fan
Connections
Refrigerant coupling Flare type
Refrigerant tube size Gas, Liquid 3/8", 1/4"
Drain piping mm O.D φ18
Others
Safety device Compressor: Thermal protector
Air filters Polypropylene net (Washable)
Net dimensions Width mm 790 730
Net weight kg 10 37
Cool A 5.0 (1.1 - 8.2)
Heat A 4.8 (1.0 - 8.0)
Cool W 1090 (210 - 1300)
Heat W 1030 (180 - 1900)
Heat % 93
Model 5RS102XBE01
Oil charge 320cc (RB68A or Freol Alpha 68M)
Condenser Corrugate Fin and Grooved tube type
Control Expansion valve
Refrigerant (R410A) 1030g
De-lce system Micro computer controled reversed systems
High dB(A) 40 48
Low dB(A) – –
Soft dB(A) 28 –
High m3/min. 9.8 26.7
Low m3/min. 8.5 –
Soft m3/min. 6.9 –
Fan motors: Thermal fuse
Fuse, Micro computer control
Height mm 278 540
Depth mm 198 250
NOTE: The condition of star”✩ ” marked item are ‘ISO5151’ : 1994(E), contition T1.
1 – 3
[2] EXTERNAL DIMENSION
1. Indoor unit
AYXP7FR
198 790
278
2. Outdoor unit
58
INVERTERAIRCONDITIONER
175
515
730
37.5
12
18.5
22.0
58
135
4.5
72
299
324
14
250
540
1 – 4
165
167.5
81
136
AYXP7FR
[3] WIRING DIAGRM
1. Indooa unit
2. Outdooa unit
2.1. AE-X7FR / AE-X9FR
2.2. AE-X12FR
420V
750μF
420V
750μF
1 – 5
AYXP7FR
[8] TROUBLESHOOTING GUIDE
1. Self-Diagnosis Function and Display Mode
To call out the content of the self-diagnosis memory, hold down the emergency operation button for more than 5 seconds when the indoor unit is not
operating.
• The number of indications displayed by the LEDs on the outdoor unit differs from that for the 2001 cooling unit models (for detailed display of malfunction information).
The display of malfunction No. differs from that of the 2001 cooling unit models. To show detailed malfunction information, two types of numbers
flash alternately. (example: "21" ←→ "-0")
1) The content of the self-diagnosis memory can be called out and displayed on the seven-segment display section on the indoor unit. (The error
data cannot be called out for display by the LED on the outdoor unit.)
2) If the power cord is unplugged from the AC outlet or the circuit breaker is turned off, the self-diagnosis memory loses the stored data.
a) The self-diagnosis display function of the indoor unit indicates the content of diagnosis by showing the error main category (number) and the
error sub-category (-number) alternately in 1-second intervals on the seven-segment display section of the indoor unit.
Example of self-diagnosis display on indoor unit: Compressor high-temperature error
'TTQTOCKPECVGIQT[ 'TTQTUWDECVGIQT[
b) The self-diagnosis display function of the outdoor unit indicates the error information by flashing LED1 on the outdoor unit according to the con-
tent of self-diagnosis.
The self-diagnosis display function of the outdoor unit is active only for about 3 to 10 minutes after self-diagnosis is performed during operation,
and the display returns to normal condition after this display period.
The content of self-diagnosis cannot be called out by the self-diagnosis display function of the outdoor unit.
Example of self-diagnosis display on outdoor unit: Compressor high-temperature error
ON
OFF
c) The content of diagnosis is transferred to the indoor unit via serial communication, but it does not trigger a complete shutdown operation.
: Flashes in 2-sec intervals (normal), : On, : Off, : Flashes 3 times in 0.2-sec intervals (When LED1 on the outdoor unit flashes in 2-sec
intervals, the outdoor unit is in normal condition.)
Nor-
mal
ing
Malfunction
No. dis-
played on
main unit
display sec-
tion *1
Sub-
Main
cate-
cate-
gory
gory
00 N o r m a l – –
Status of
indoor/
outdoor
units
Indoor/
outdoor
units in
operation
Indoor/
outdoor
units in
complete
shutdown
Indication
by LED1
on out-
door unit
*2
flash-
1 time 1 -0 Outdoor unit
1 sec 1 sec 1 sec 1 sec 1 sec 1 sec 0.6 sec 0.6 sec 0.6 sec 0.6 sec 1 sec
Content of diagnosis Inspection location/method Remedy
Main category Sub-category
Heat exchanger
thermistor
short-circuit
-1 Outside tempera-
-2 Suction thermistor
-3 2-way valve ther-
thermistor short-cir-
cuit error
ture thermistor
short-circuit error
short-circuit error
mistor short-circuit
error
(1) Measure resistance of the
outdoor unit thermistors.
(TH2 to TH5: Approx. 4.4
kΩ at 25° C)
(2) Check the lead wire of the
outdoor unit thermistor for
torn sheath and short-circuit.
(3) No abnormality found in
above inspections (1) and
(2).
1 sec 1 sec
(1) Replace the outdoor
unit thermistor assembly.
(2) Replace the outdoor
unit thermistor assembly.
(3) Replace the outdoor
unit control PWB
assembly.
3 – 13
AYXP7FR
Status of
indoor/
outdoor
units
Indoor/
outdoor
units in
complete
shutdown
Indoor
unit in
operation
Outdoor
unit in
temporary stop
Indoor
unit in
operation
Outdoor
unit in
temporary stop
Indoor/
outdoor
units in
complete
shutdown
Indication
by LED1
on out-
door unit
*2
2 times 2 -0 Cycle tempera-
3 times 3 -0 Dry operation Temporary stop due
5 times 5 -0 Outdoor unit
Malfunction
No. dis-
played on
main unit
display sec-
tion *1
Sub-
Main
cate-
cate-
gory
gory
-1 Temporary stop due
-2 Temporary stop due
-3 Temporary stop due
-4 Temporary stop due
-1 Outside tempera-
-2 Suction thermistor
-3 2-way valve ther-
-4 Discharge ther-
Content of diagnosis Inspection location/method Remedy
Main category Sub-category
ture
thermistor
open-circuit
Compressor high-
temperature error
to compressor dis-
charge overheat *3
to outdoor unit heat
exchanger overheat
*3
to outdoor unit heat
exchanger overheat
*3
to 2-way valve
freeze *3
to dehumidifying
operation *3
Heat exchanger
thermistor open-cir-
cuit error
ture thermistor
open-circuit error
open-circuit error
mistor open-circuit
error
mistor open-circuit
error
(1) Check the outdoor unit air
outlet for blockage.
(2) Check if the power supply
voltage is 90 V or higher at
full power.
(3) Check the pipe connec-
tions for refrigerant leaks.
(4) Measure resistance of the
outdoor unit compressor
thermistor.
(TH1: Approx. 53 kΩ at
25° C)
(5) Check the expansion
valve for proper operation.
(Temporary stop for cycle protection)
(Temporary stop for cycle protection)
(Temporary stop for cycle protection)
(Temporary stop for cycle protection)
(Temporary stop for cycle protection)
(1) Check connector CN8 of
the outdoor unit thermistor for secure installation.
(2) Measure resistance of out-
door thermistors TH1 to
TH5.
(3) Check the lead wires of
thermistors TH1 through
TH5 on the outdoor unit
control PWB for open-circuit.
(4) No abnormality found in
above inspections (1)
through (3).
(1) Ensure unobstructed
air flow from the outdoor unit air outlet.
(2) Connect power sup-
ply of proper voltage.
(3) Charge the specified
amount of refrigerant.
(4) Replace the outdoor
unit compressor thermistor assembly.
(5) Replace the expan-
sion valve coil, expansion valve or outdoor
unit control PWB
assembly.
–
–
–
–
–
(1) Correct the installa-
tion.
(2) Replace the outdoor
unit thermistor assembly.
(3) Replace the outdoor
unit thermistor assembly.
(5) Replace the outdoor
unit control PWB
assembly.
3 – 14
AYXP7FR
Status of
indoor/
outdoor
units
Indoor/
outdoor
units in
complete
shutdown
Indoor/
outdoor
units in
complete
shutdown
Indoor/
outdoor
units in
complete
shutdown
Indication
by LED1
on out-
door unit
*2
6 times 6 -0 Outdoor unit DC DC overcurrent error (1) IPM continuity check (1) Replace the outdoor
7 times 7 -0 Outdoor unit AC AC overcurrent error (1) Check the outdoor unit air
9 times 9 -0 Outdoor unit
Malfunction
No. dis-
played on
main unit
display sec-
tion *1
Sub-
Main
cate-
cate-
gory
gory
-1 IPM pin level error Check the IPM is attached
-1 AC overcurrent error
-2 AC maximum cur-
-3 AC current defi-
-3 Torque control error (1) Check if the refr igerant
Content of diagnosis Inspection location/method Remedy
Main category Sub-category
(2) Check the IPM and heat
sink for secure installation.
(3) Check the outdoor unit fan
motor for proper rotation.
(4) No abnormality found in
above inspections (1)
through (3).
(5) No abnormality found in
above inspections (1)
through (4).
correctly to the outdoor
unit control PWB.
outlet for blockage.
(2) Check the outdoor unit fan
for proper rotation.
(1) IPM continuity check (1) Replace the outdoor
in OFF status
(1) Check the outdoor unit air
outlet for blockage.
(2) Check the outdoor unit fan
for proper rotation.
(1) Check if there is an open-
circuit in the secondary
winding of the current
transformer of the outdoor
unit control PWB.
(2) Check if the refrigerant
volume is abnormally low.
(3) Check if the refrigerant
flows properly.
(1) Check to make sure out-
door unit thermistor TH2
(heat exchanger) and TH5
(2-way valve) are installed
in correct positions.
(2) Measure resistance of
thermistors TH1 and TH5.
(3) Check the 4-way valve for
proper operation.
(4) No abnormality found in
above inspections (1)
through (3).
volume is abnormally low.
(2) Check the 4-way valve for
proper operation.
(3) check to see compressor
type is correct.
cooling/heating
switchover
rent error
ciency error
Thermistor installa-
tion error or 4-way
valve error
unit control PWB
assembly.
(2) Correct the installa-
tion (tighten the
screws).
(3) Replace the outdoor
unit fan motor.
(4) Replace the outdoor
unit control PWB
assembly.
(5) Replace the compres-
sor.
Replace the outdoor
unit control PWB
assembly.
(1) Ensure unobstructed
air flow from the outdoor unit air outlet.
(2) Check the outdoor unit
fan motor.
unit control PWB
assembly.
(1) Ensure unobstructed
air flow from the outdoor unit air outlet.
(1) Check the outdoor unit
fan motor.
(1) Replace the outdoor
unit control PWB
assembly.
(2) Charge the specified
amount of refrigerant.
(3) Correct refrigerant
clogs.
(2-way valve, 3-way
valve, pipe, expansion valve)
(1) Correct the installa-
tion.
(2) Replace the ther-
mistor assembly.
(3) Replace the 4-way
valve.
(4) Replace the outdoor
unit control PWB
assembly.
(1) Change the specified
amount of refrigerant.
(2) Replace the 4-way
valve.
(3) Replace the compres-
sor with the correct
part.
3 – 15
AYXP7FR
Status of
indoor/
outdoor
units
Indoor/
outdoor
units in
complete
shutdown
Indoor/
outdoor
units in
complete
shutdown
Indoor/
outdoor
units in
complete
shutdown
Indoor/
outdoor
units in
operation
Indoor
unit in
operation
Outdoor
unit in
complete
shutdown
Indication
by LED1
on out-
door unit
*2
11
times
13
times
14
times
Malfunction
No. dis-
played on
main unit
display sec-
tion *1
Sub-
Main
cate-
cate-
gory
gory
11 -0 Outdoor unit DC
13 -0 DC compressor Compressor startup
-1 Compressor rota-
14 -0 Outdoor unit
-1 PAM clock error (1) Check the PAM clock for
17 -0 Wires between
18 -0 Serial short-circuit (1) Check the wires between
-1 Serial erroneous wir-
Content of diagnosis Inspection location/method Remedy
Main category Sub-category
fan
PAM
units
Outdoor unit DC fan
rotation error
error
tion error
(120° energizing
error)
PAM over voltage
error
Compressor rota-
tion error
Serial open-circuit (1) Check the wires between
Outdoor unit does
not turn on due to
erroneous wiring
ing
(1) Check connector CN3 of
the outdoor unit DC fan
motor for secure installation.
(2) Check the outdoor unit fan
motor for proper rotation.
(3) Check fuse FU3. (3) Replace the outdoor
(4) Outdoor unit control PWB (4) Replace the outdoor
(1) Check the colors (red,
white, orange) of the compressor cords for proper
connection. (PWB side,
compressor side)
(2) Check if the IPM terminal
resistance values are uniform.
(3) No abnormality found in
above inspections (1) and
(2).
(4) No abnormality found in
above inspections (1)
through (3).
(1) Check the AC power sup-
ply voltage for fluctuation.
(2) No abnormality found in
above inspection (1).
proper input.
units.
(2) Check voltage between
Nos. 1 and 2 on the
indoor/outdoor unit terminal boards.
(1) Check the wires between
units.
(2) Check the outdoor unit
fuse.
(3) Check 15-V, 13-V and 5-V
voltages on the PWB.
Check resistance between
IPM terminals.
(4) Check pins No. 5 and 7 of
connector CN3 of the outdoor unit fan motor for
short-circuit.
(5) Outdoor unit control PCB (5) Replace the outdoor
units.
(1) Check the wires between
units.
(1) Correct the installa-
tion.
(2) Replace the outdoor
unit fan motor.
unit control PWB
assembly.
unit control PWB
assembly.
(1) Correct the installa-
tion.
(U: Red, V: White, W:
Orange)
(2) Replace the outdoor
unit control PWB
assembly.
(3) Replace the outdoor
unit control PWB
assembly.
(4) Replace the compres-
sor.
(1) Connect stable power
supply.
(2) Replace the outdoor
unit control PWB
assembly.
(1) Replace the outdoor
unit control PWB
assembly.
(1) Connect stable power
supply.
(2) Replace the outdoor
unit control PCB
assembly.
(1) Correct the wiring.
(2) Replace the fuse/out-
door unit control PCB
assembly.
(3) Replace the outdoor
unit control PCB
assembly.
(4) Replace the outdoor
unit fan motor.
unit control PCB
board.
(1) Correct the wiring.
(1) Correct the wiring.
3 – 16
AYXP7FR
Status of
indoor/
outdoor
units
Indoor/
outdoor
units in
complete
shutdown
Indoor/
outdoor
units in
operation
Indoor/
outdoor
units in
operation
Indication
by LED1
on out-
door unit
*2
Malfunction
No. dis-
played on
main unit
display sec-
tion *1
Sub-
Main
cate-
cate-
gory
gory
19 -0 Indoor unit fan Indoor unit fan error (1) Check the indoor fan
20 -0 Indoor unit con-
88 Control and dis-
Content of diagnosis Inspection location/method Remedy
Main category Sub-category
motor for proper rotating
operation.(Check fan
lock.)
(2) Check the lead wire of the
indoor fan motor for opencircuit.
(3) Check CN1 of the indoor
unit fan motor for secure
installation.
(4) No abnormality found in
above inspections (1)
through (3).
EEPROM data error (EEPROM read data
trol PCB
play PCB
Communication
error
error)
(1) Check for disconnected
connector between control
PCB and display PCB,
and open-circuit in lead
wires.
(2) Check that control PCB
outputs signals correctly.
(1) Replace the indoor fan
motor.
(2) Replace the indoor fan
motor.
(3) Correct the installa-
tion of CN1 of the
indoor fan motor.
(4) Replace the indoor
unit control PWB.
Replace the indoor
unit control PWB.
(1) Insert connectors cor-
rectly, or replace control PWB.
(2) Replace control PWB.
3 – 17
Malfunction indications due to erroneous wiring during air conditioner installation
Inter-unit wiring error mode Symptom
1 Indoor unit relay
Malfunction diagnosis display
Indoor
unit
1
N
2
1
N
2
Outdoor
unit
Turns On momentarily, then turns Off.
"18-1"
AYXP7FR
2 Indoor unit relay
1
Indoor
N
unit
2
3 Indoor unit relay
1
Indoor
N
unit
2
4 Indoor unit relay
1
Indoor
N
unit
2
5 Indoor unit relay
1
Indoor
N
unit
2
1
N
2
1
N
2
1
N
2
1
N
2
Outdoor
unit
Outdoor
unit
Outdoor
unit
Outdoor
unit
Malfunction diagnosis display
Malfunction diagnosis display
Malfunction diagnosis display
Malfunction diagnosis display
Relays turns Off after about 30 minutes.
None
(Displays "18-0" when malfunction code is called out.)
Relays turns Off after about 30 minutes.
None
(Displays "18-0" when malfunction code is called out.)
Turns On momentarily, then turns Off.
"18-1"
Turns On momentarily, then turns Off.
"18-1"
3 – 18
[4] PERFORMANCE CURVES
NOTE
1) Indoor fan speed: Hi
2) Vertical adjustment louver "45° ”, Horizontal adjustment louver "front"
3) Indoor air temp. : Cooling 27° C, Heating 20°C
4) Power source : 230V, 50Hz
1. AY-XP7FR
1.1. At Cooling 1.2. At Heating
AYXP7FR
600
500
400
Input(W)
300
2.6
2.4
2.2
2.0
Cooling capacity(kW)
25 30 35 40
Outside air temp.(ºC)
600
500
400
Input(W)
3.0
2.5
2.0
1.5
Heating capacity(kW)
-5 0 7 51 0
2. AY-XP9FR
2.1. At Cooling 2.2. At Heating
900
800
700
Input(W)
600
800
700
600
Input(W)
Outside air temp.(ºC)
3.2
3.0
2.8
2.6
2.4
Cooling capacity(kW)
25 30 35 40
Outside air temp.(ºC)
4 – 2
3.5
3.0
2.5
2.0
Heating capacity(kW)
-5 0 5 7 10
Outside air temp.(ºC)
AYXP7FR
3. AY-XP12FR
3.1. At Cooling 3.2. At Heating
1200
1200
1100
1000
Input(W)
900
1100
1000
900
Input(W)
800
4.0
3.8
3.6
3.4
3.2
Cooling capacity(kW)
25 30 35 40
Outside air temp.(ºC)
4.5
4.0
3.5
3.0
2.5
Heating capacity(kW)
-5 0 5 7 10
Outside air temp.(ºC)
4 – 3