Troubleshooting ......................................................................................................................... Back
Page 3
GENERAL INFORMATION
The WMX-Series are anged electromagnetic owmeters
for use in 3” to 12” pipe in municipal or industrial water and
wastewater applications where propeller meters have typically
been used in the past. Because the WMX has no moving
parts and has electrodes designed to discourage fouling, this
magmeter performs well and requires much less frequent
maintenance in applications where debris would impede
propeller meters. There is no rotor to stop turning or bearings
to wear out. Minimal straight pipe requirements allow WMXSeries meters to be used in piping congurations where there
is little space between the meter and an elbow.
In chemical injection applications, the chemical injection
point must be placed downstream of the magmeter OR far
enough upstream for complete mixing to occur before the
uid reaches the meter.
The submersible units, -168 option, are rated IP68 (NEMA 6P)
for applications where the meter may be under water up to a
depth of 3 meters for prolonged periods of time.
Rate and total indication are standard on both models. Units
are customer-selected and factory-set. No set-up is required.
The WMX101 is externally powered with 8-32 Vdc at 30
mA max (see NOTE in Specications). Two Lithium 3.6V
“AA” batteries provide auxiliary power during power failures,
allowing the meter to continue recording ow rate and total
without interruption for the duration of the outage. Where
external power loss is infrequent, battery life exceeds 10 years.
The 20-foot power cable also provides pulse output for use
with a variety of Seametrics and other displays and controls for
remote reading, data logging, pulse-to-analog conversion, and
telemetry applications. High frequency pulse rate (required
for use with 4-20 mA converters) is standard; additional pulse
rates are optional.
The WMX104 is a battery-operated unit for use when pulse
output is not required. Two Lithium 3.6V “D” batteries provide
power and are replaceable with an approximate 1-year life
under continuous use. An optional input/output cable can be
installed post-factory if needed for changing applications.
*Extended battery life is standard on all IP68 meters.
Tamper-evident security seal &
cross-drilled screws (2) for tamper-evidence
Internal Data Logger (Optional)
Power/Output cable port access, tamper-sealed
(NOTE: WMX101 comes with standard 20’ cable installed)
Welded steel epoxy-coated ow tube
316SS electrodes
Dual durometer rubber liner
Flanges, ANSI 150 lb. drilling
Equalization lug
WMX104
Page 1
Page 4
GENERAL INFORMATION
FEATURES Continued
Rate and total indicator
Tamper-evident security seal &
cross-drilled screws (2) for tamper-evidence
Internal Data Logger (Optional)
Power/Output cable port access, tamper-sealed
(NOTE: WMX101 comes with standard 20’ cable installed)
Powder-coated ductile cast iron body & electronics housing
Glass lled molded plastic liner
316SS electrodes
Flanges, ANSI 150 lb. drilling
Rate and total indicator
Tamper-evident security seal &
cross-drilled screws (2) for tamper-evidence
Power/Output cable port access, tamper-sealed
(NOTE: WMX101 comes with standard 20’ cable installed)
Internal Data Logger (Optional)
Powder-coated ductile cast iron electronics housing
Equalization lug
WMX104-300
(IP68 housing standard for 3” models)
Equalization lug
Page 2
IP68 Housing Option
(For 4”-10” meter;
standard for 3” models)
Page 5
SPECIFICATIONS
SPECIFICATIONS*
Pipe Sizes
Fittings
Pressure
Temperature Operating
Accuracy
Materials Body (3” Only)
Body (4”-12”)
Liner (3” Only)
Liner (4”-12”)
Electronics Housing
Electrodes
O-ring (3” Only)
Display
Power
Non-Operating
Digits
Units
3”,4”, 6”, 8”, 10”, 12”
ANSI 150 lb. drilling
150 psi (10.3 bar) working pressure
10˚ to 130˚ F (-12˚ to 54˚ C)
-40˚ to 158˚ F (-40˚ to 70˚ C)
+/- 1% of reading for ow between 10% to 100% of max ow
+/- 2% of reading for ow from cutoff to 10% of max ow
Ductile cast iron, powder coated
Welded steel, epoxy-coated
Noryl®
Santoprene/Polypropylene
Diecast aluminum, powder-coated (non-IP68) Ductile Cast Iron (IP68)
316 stainless steel
EPDM
Rate Total
5 8
Gallon/Minute, Liter/Minute, Liter/Second, Gallon, Gallon x 1000, Liter, Liter x 1000, Mega Liter,
Cubic Feet/Minute, Cubic Meter/Hour, Cubic Meters, Cubic Meter x 1000, Cubic Feet,
Million Gallon/Day, Mega Liter/Day Cubic Feet x 1000
WMX101: 8-32 Vdc at 30 mA max, with auxiliary battery for continuous operation during power failures
NOTE: Using an unregulated power supply >18 Vdc may damage the meter due to AC line input voltage uctuation
WMX104: 2 Lithium 3.6V “D” batteries, replaceable, 1 year life under continuous use.
Pulse Output Signal
Pulse Rates
High Frequency
(pulse/gal)
Conductivity
Empty Pipe Detection
Environmental
Regulatory
*Specications subject to change. Please consult our website for the most current data (www.seametrics.com).
WMX101: Current sinking pulse, opto-isolated, 30 Vdc at 10 mA max
WMX104: Pulse output available only with addition of post-factory output cable
High Frequency; 10 units/pulse; 100 units/pulse; 1000 units/pulse
where installation fault may expose the ow sensor to
boiler pressure and temperature. Maximum
recommended temperature is 130˚ F.
Positioning the Meter. These meters can be installed
horizontally, vertically, and in any radial position. Using a
check valve on the upstream side of the meter, and/or an air
vent (vacuum relief valve) in the same, unobstructed run of
pipe as the meter, is required in any installation where the
meter may be exposed to suction when the system is not in
normal operation. Suction can cause damage to the liner.
Liner damage caused by suction, without the use of a check
valve and/or air vent, may void the warranty.
Straight Pipe Recommendations. As with most flow
meters, the WMX requires some straight pipe before and
after the meter for best accuracy. However, the ability of
electromagnetic meters to average the ow across the entire
pipe allows for shorter straight pipe recommendations than
most mechanical meters (see page 4).
Full Pipe Recommendations. All magmeters require a
method for determining that the pipe is empty, to prevent false
reading. This meter is designed to go to zero reading if one
or more electrodes is exposed. For highest accuracy, install
the meter so that the pipe will be full when there is ow. If air
bubbles may be present in the pipe or sludge accumulation
is an issue, rotate the meter by one ange hole to position
the control housing at a 45˚ angle (see diagrams on page 5).
Fittings. The WMX anges have standard ANSI 150 lb. drilling
and mate with any other ANSI 150 lb. ange.
Installing Gaskets
GASKETS
Gaskets are required at all junctions.
(Not applicable to 3” model.)
1. Select a suitable full-face gasket.
• Only use at compressible gaskets (either pliable
or hard ber will work).
• Use a material compatible with the uid you will be
using.
• Thickness should be 1/8” - 1/4” (3 - 6 mm),
depending on the atness of the pipe ange
surface.
• Inner diameter must be larger than opening in ow
meter.
2. Be sure all mating surfaces are smooth and free of
debris.
3. Install gaskets on each end of meter as shown in
diagrams below. If using grounding rings, install one
gasket on each side of the grounding ring.
Gaskets
Installation without gaskets
Calibration. The WMX is factory-calibrated and will not require
any form of eld calibration.
Chemical Injection. When any magmeter, by any manufacturer, is used in a chemical injection application, the chemical
injection point must be placed downstream of the magmeter OR far enough upstream for complete mixing to occur
before the uid reaches the meter. When unmixed chemical
alternates with water passing through the meter, the rapid
changes in conductivity may cause sudden spikes and drops
in the meter’s reading, resulting in inaccurate measurement.
The magmeter will restabilize, however, with a steady ow of
uid of uniform conductivity.
Caution: In chemical injection applications, install
chemical injection point downstream of magmeter,
or far enough upstream to allow complete mixing of
uids before the meter.
Page 4
Grounding
Rings
Gaskets
Installation with gaskets
Page 7
INSTALLATION and GROUNDING
Tightening Flange Bolts
NOTE: Mating pipe anges must be ANSI 150# full face (FF)
and/or raised face (RF).
1. Tighten ange bolts in an alternating pattern.
• Tighten left ange bolt-1 to 20% recommended
torque.
• Tighten right ange bolt-1 to 20% of
recommended torque.
• Repeat steps a and b for each bolt in an
alternating order, such as shown at right,
tightening to 40%, then 60%, then 80%, and then
100%.
2. Test for leaks.
3. If needed, tighten further in 10% increments until
leaking stops. DO NOT over-tighten. Over-tightening
can cause serious damage to the ow meter.
4. Recheck after 24 hours, adjusting if needed.
1
5
8
Equalization and Grounding
WARNING: ELECTRICAL SHOCK HAZARD
When the is installed in a plastic piping
system, or when externally powered, the
piping system must be grounded to meet
national and local electrical safety codes.
Failure to do so can result in electrocution.
Metal Pipe Installations. To equalize the electrical potential
of the uid, the meter, and the surrounding pipe, secure the
ange plates (factory-installed on the equalization wire) to
both pipe anges at one of the bolt holes, as shown below.
Be sure the lock washer ts between the pipe ange and the
ange plate. For the best electrical bonding, remove rust
and paint to expose clean, bare metal where the equalization
ange plate lock washer contacts the pipe ange. Connection
must be inspected periodically for corrosion to maintain the
necessary low resistance connection.
Meter Flange
Gasket
Pipe Flange
Lockwasher
Flange Plate
Equalization Lug
3
7
4
6
2
Suggested Tightening Sequence
Caution: Improper tightening sequence
can cause serious damage to the ow
meter.
• Do not tighten one side at a time.
• Do not tighten each bolt completely at
one time.
SUGGESTED FLANGE BOLT TORQUE
Santoprene Liner
Pipe Sizeft-lbNm
3”2534
4”2027
6”4257
8”6588
10”7399
12”97132
Meter
Flange
Gaskets
Pipe
Flange
Metal PipeMetal Pipe
Plastic Pipe Installations. When the meter is installed in a
plastic piping system, grounding rings are recommended
(except 3” pipe size), especially in the presence of electrical
interference sources such as VFD pump drives. As shown in
the diagram below, the equalization wires should then be
connected to the grounding ring tabs instead of the ange
bolts as in metal piping installations. Where lightning is a
threat, or in severe electrical environments, an optional
connection to a nearby equipment ground or ground rod may
be advisable.
WMX101
External Power (WMX101). The WMX101 operates on 8 to
32 Vdc at 30 mA max external power (see WARNING in wiring
diagrams). The display reads “P” when external power is in
use (see illustration below).
The Lithium battery pack installed in the WMX101 serves as
backup in the event of a power failure, when it will keep the
meter operating without interruption for the duration of the
outage. When battery power in is use, the WMX101 display
continues to read out the rate and total, but the “P” indicating
external power is extinguished. When power resumes, the
WMX101 will seamlessly return to normal power mode, and
the “P” will again display.
When used for occasional emergency backup, battery life is
approximately ten years.
Pulse Output (WMX101). The WMX101 cable also provides
pulse output that can be used for remote reading, 4-20 mA
signal conversion, datalogging, and telemetry applications.
See page 7 for connection diagrams to Seametrics controls
and displays.
Pulse Output (WMX104). Pulse output capabilities are built
in to the WMX104, but cannot be utilized without the addition
of an optional output cable. A WMX104 can be retrotted with
this cable in the eld. IMPORTANT: When eld installing the
input/output cable, be sure to snugly tighten the cable strain
relief to prevent water ingress.
OPERATION
Caution: There are no user-adjustable
connections or settings inside the display
housing. Use caution when opening the
housing for a battery change, to avoid
damage to internal components.
Display Reading. The WMX display has two lines, the bottom
line for ow rate and the top line for accumulated total.
Measurement units are pre-ordered and factory-set and can
be changed in the eld only by an authorized individual.
Refer to the diagrams below to read your display.
Note: For data logger setup and operation, refer to Flow
Inspector Manual
Pulse rates are selected by the customer at time of order,
factory-set, and can only be changed in the field by an
authorized Seametrics dealer. Three pulse rates are possible:
One pulse per ten gallons (or liters), one pulse per thousand
gallons (or liters), or High Frequency (required for use with
4-20 mA converters; see below):
High Frequency Output/K-Factor
Meter Size Pulses per Gallon Pulses per Liter
3” 25.228 6.665
4” 16.362 4.323
6” 6.307 1.666
8” 3.344 0.883
10” 2.150 0.568
12” 1.530 0.405
WMX104
Battery Power (WMX104)*. The WMX104 is powered by a
non-rechargeable battery pack with an approximate 1-year life
under continuous use. Actual lifespan will vary from application
to application, depending on the duty cycle.
External Power Indicator
(WMX101 Only)
Battery Power
(WMX104 Standard Operation)
(WMX101 Backup Operation)
No Power
Empty Pipe
“Low Batt” will display when there are approximately
three days of use left in the batteries (see illustration).
Replacement instructions come with the custom
battery pack available from your dealer or Seametrics.
Page 8
Low
Batt
Low Battery Indicator
(3 days remaining)
Meter Installed Backwards
Page 11
CONNECTIONS DIAGRAMS (WMX101)
The WMX101 requires a power source of 8 to 32 Vdc at 30
mA max (see WARNING). The WMX101 power cable also
serves as a pulse output if needed for remote reading, data
logging, signal conversion, or telemetry.
AO55/WMX101
Blue
Do
Not
{
Orange
Use
4-20 mA
Power
5
6
4
3
2
1
0
S
Sensor
Not
Used
Frequency
5
6
4
7
8
9
7
3
8
2
9
1
0
5
5
6
6
4
4
7
7
3
3
2
8
8
2
9
9
1
1
0
0
Power Supply
at 30 mA max
(see WARNING)
White (-)
Green (+)
Black
Red
(-) (+)
8-32 Vdc
AO55W Pulse-to-Analog Converter
FT420/WMX101
External Power Input Required - 12-32 Vdc
WMX101 Cable Color Codes
Orange and Blue: Serial Output (Do Not Use)
Green (+) and White (-): Pulse Output, 30 Vdc max, 10 mA max
Red (+) and Black (-): External Power, 8-32 Vdc at 30 mA max
Drain: Connect to earth ground (see WARNING)
WMX101 Cable
Shielded
Drain Wire
Direct Burial Cable
22 AWG Stranded
WARNING: Using an unregulated power
supply >18 Vdc may damage the meter
due to AC line input voltage uctuation.
WMX101
PASSTHRU
PULSE
SCALED
PULSE
Power
4-20 mA
Input
Sensor
Not
Used
FT420W Remote Rate/Total Display
DL75 or DL76/WMX101
Battery
-
S
+
Not
Used
Blue
Do
Not
{
Orange
Use
White (-)
Green (+)
Black
Red
(-) (+)
Power Supply
8-32 Vdc
at 30 mA max
(see WARNING)
Blue
Do
Not
{
Orange
Use
White (-)
Green (+)
Black
Red
Drain Wire
WMX101 Cable
Shielded
Direct Burial Cable
22 AWG Stranded
WARNING: Using an unregulated power
supply >18 Vdc may damage the meter
due to AC line input voltage uctuation.
WMX101 Cable
Shielded
Direct Burial Cable
22 AWG Stranded
WMX101
WMX101
DL75W or DL76W Data Logger
(-) (+)
Power Supply
8-32 Vdc
at 30 mA max
(see WARNING)
Drain Wire
WARNING: Using an unregulated power
supply >18 Vdc may damage the meter
due to AC line input voltage uctuation.
Page 9
Page 12
TROUBLESHOOTING
Problem
Blank Display
Flow rate steadily reads
zero when there is ow
Flow rate intermittently
drops when there is ow
Probable CauseTry...
Dead battery (WMX104)
No power plus dead battery (WMX101)
Replace battery pack
Replace battery pack, check power
connections
Flow is below cutoff (very low)
Pipe is not full
Meter is installed backwards
Reading will resume when ow increases
Reposition meter for full pipe (see page 4)
Note ow direction arrow, reverse meter
(display reads [ - ] )
Power connections reversed (WMX101)
Fluid conductivity <20microSiemens/cm
Pipe is not full
Change power connections
Select another ow meter
Reposition meter for full pipe (see page 4)
Jumpy reading
Meter reads, but no
pulse output (WMX101)
Output pulses missing
Missing or incorrect ground wire
Pulsing ow
Rapidly changing conductivity
(in chemical injection applications)
External device needs pull-up resistor
Reversed leads (polarity sensitive)
Meter not reading
Check for proper ground
Use external power source
(allows more ow averaging)
Install chemical injection line downstream
of meter (or far enough upstream to allow
complete mixing of uids before meter)
Add pull-up resistor
(For details, refer to ‘Connecting to PLCs’
Technical Bulletin at www.seametrics.com)
Change output connections
Check display
Seametrics • 19026 72nd Avenue South • Kent, Washington 98032 • USA