Seametrics WMX SERIES, WMX101-168, WMX104-300, WMX104 Instructions Manual

Page 1
WMX-SERIES
9 001:2008
CERTIFIED COMPANY
ISO
MUNICIPAL/INDUSTRIAL MAGMETER INSTRUCTIONS
WMX-SERIES MUNICIPAL/INDUSTRIAL MAGMETER INSTRUCTIONS
WMX101-168
WMX104-300
Page 2
TABLE OF CONTENTS
General Information
General Information, Features ................................................................................................... Page 1
Specications
Specications, Flow Range ............................................................................................................ Page 3
Installation and Grounding
Positioning the Meter,
Straight Pipe Recommendations, Full Pipe Recommendations, Fittings,
Calibration, Chemical Injection, Installing Gaskets............................................................ Page 4
Tightening Flange Bolts, Metal Pipe Installations, Plastic Pipe Installations....................... Page 5
Straight Pipe Recommendations ................................................................................................ Page 6
Full Pipe Recommendations ...................................................................................................... Page 7
Inputs/Outputs and Operation
Power, Pulse Output, High Frequency, K-Factor, Display Reading ................................................... Page 8
Connections Diagrams
AO55/WMX101, FT420/WMX101, DL75 or DL76/WMX101 ........................................................... Page 9
Troubleshooting
Problem, Probable Cause, Things to Try .................................................................................... Back
TABLES, DIAGRAMS & CHARTS
Features ...................................................................................................................................Page 1
Specifications .......................................................................................................................... Page 3
Flow Range ............................................................................................................................. Page 3
Metal Pipe Installation, Plastic Pipe Installation ..................................................................... Page 5
Straight Pipe Recommendations ............................................................................................. Page 6
Full Pipe Recommendations .................................................................................................... Page 7
High Frequency Output ............................................................................................................. Page 8
Display Readings ..................................................................................................................... Page 9
Connections Diagrams ................................................................................................................................ Page 10
Troubleshooting ......................................................................................................................... Back
Page 3
GENERAL INFORMATION
The WMX-Series are anged electromagnetic owmeters for use in 3” to 12” pipe in municipal or industrial water and wastewater applications where propeller meters have typically been used in the past. Because the WMX has no moving parts and has electrodes designed to discourage fouling, this magmeter performs well and requires much less frequent maintenance in applications where debris would impede propeller meters. There is no rotor to stop turning or bearings to wear out. Minimal straight pipe requirements allow WMX­Series meters to be used in piping congurations where there is little space between the meter and an elbow.
In chemical injection applications, the chemical injection point must be placed downstream of the magmeter OR far enough upstream for complete mixing to occur before the uid reaches the meter.
The submersible units, -168 option, are rated IP68 (NEMA 6P) for applications where the meter may be under water up to a depth of 3 meters for prolonged periods of time.
Rate and total indication are standard on both models. Units are customer-selected and factory-set. No set-up is required. The WMX101 is externally powered with 8-32 Vdc at 30 mA max (see NOTE in Specications). Two Lithium 3.6V “AA” batteries provide auxiliary power during power failures, allowing the meter to continue recording ow rate and total without interruption for the duration of the outage. Where external power loss is infrequent, battery life exceeds 10 years.
The 20-foot power cable also provides pulse output for use with a variety of Seametrics and other displays and controls for remote reading, data logging, pulse-to-analog conversion, and telemetry applications. High frequency pulse rate (required for use with 4-20 mA converters) is standard; additional pulse rates are optional.
The WMX104 is a battery-operated unit for use when pulse output is not required. Two Lithium 3.6V “D” batteries provide power and are replaceable with an approximate 1-year life under continuous use. An optional input/output cable can be installed post-factory if needed for changing applications.
*Extended battery life is standard on all IP68 meters.
FEATURES
Rate and total indicator
Powder-coated diecast-aluminum electronics housing
Tamper-evident security seal & cross-drilled screws (2) for tamper-evidence
Internal Data Logger (Optional)
Power/Output cable port access, tamper-sealed
(NOTE: WMX101 comes with standard 20’ cable installed)
Welded steel epoxy-coated ow tube
316SS electrodes
Dual durometer rubber liner
Flanges, ANSI 150 lb. drilling
Equalization lug
WMX104
Page 1
Page 4
GENERAL INFORMATION
FEATURES Continued
Rate and total indicator
Tamper-evident security seal & cross-drilled screws (2) for tamper-evidence
Internal Data Logger (Optional) Power/Output cable port access, tamper-sealed (NOTE: WMX101 comes with standard 20’ cable installed)
Powder-coated ductile cast iron body & electronics housing
Glass lled molded plastic liner
316SS electrodes
Flanges, ANSI 150 lb. drilling
Rate and total indicator
Tamper-evident security seal & cross-drilled screws (2) for tamper-evidence
Power/Output cable port access, tamper-sealed (NOTE: WMX101 comes with standard 20’ cable installed)
Internal Data Logger (Optional) Powder-coated ductile cast iron electronics housing
Equalization lug
WMX104-300
(IP68 housing standard for 3” models)
Equalization lug
Page 2
IP68 Housing Option
(For 4”-10” meter; standard for 3” models)
Page 5
SPECIFICATIONS
SPECIFICATIONS*
Pipe Sizes
Fittings
Pressure
Temperature Operating
Accuracy
Materials Body (3” Only)
Body (4”-12”)
Liner (3” Only)
Liner (4”-12”)
Electronics Housing
Electrodes
O-ring (3” Only)
Display
Power
Non-Operating
Digits
Units
3”,4”, 6”, 8”, 10”, 12”
ANSI 150 lb. drilling
150 psi (10.3 bar) working pressure
10˚ to 130˚ F (-12˚ to 54˚ C)
-40˚ to 158˚ F (-40˚ to 70˚ C)
+/- 1% of reading for ow between 10% to 100% of max ow
+/- 2% of reading for ow from cutoff to 10% of max ow
Ductile cast iron, powder coated
Welded steel, epoxy-coated
Noryl®
Santoprene/Polypropylene
Diecast aluminum, powder-coated (non-IP68) Ductile Cast Iron (IP68)
316 stainless steel
EPDM
Rate Total
5 8
Gallon/Minute, Liter/Minute, Liter/Second, Gallon, Gallon x 1000, Liter, Liter x 1000, Mega Liter, Cubic Feet/Minute, Cubic Meter/Hour, Cubic Meters, Cubic Meter x 1000, Cubic Feet,
Million Gallon/Day, Mega Liter/Day Cubic Feet x 1000
WMX101: 8-32 Vdc at 30 mA max, with auxiliary battery for continuous operation during power failures NOTE: Using an unregulated power supply >18 Vdc may damage the meter due to AC line input voltage uctuation
WMX104: 2 Lithium 3.6V “D” batteries, replaceable, 1 year life under continuous use.
Pulse Output Signal
Pulse Rates
High Frequency (pulse/gal)
Conductivity
Empty Pipe Detection
Environmental
Regulatory
*Specications subject to change. Please consult our website for the most current data (www.seametrics.com).
WMX101: Current sinking pulse, opto-isolated, 30 Vdc at 10 mA max
WMX104: Pulse output available only with addition of post-factory output cable
High Frequency; 10 units/pulse; 100 units/pulse; 1000 units/pulse
3” 4” 6” 8” 10” 12”
25.228
>20 microSiemens/cm
Hardware/software, conductivity-based
NEMA 4X Standard (IP68 Option)
NSF-61 (3” ONLY)
16.362 6.307 3.344 2.150
FLOW RANGE (3” - 12”)
Meter
Size
Minimum
Maximum
3” 4” 6” 8” 10” 12”
Gal/Min Liter/Sec Gal/Min Liter/Sec Gal/Min Liter/Sec Gal/Min Liter/Sec Gal/Min Liter/Sec Gal/Min Liter/Sec
7.5 .47 12 .75 32 2 60 3.8 95 6 130 8.2
700 44.2 1,000 63 2,400 151.4 4,400 27 7. 6 7,000 441.6 10,000 630.9
1.530
Page 3
Page 6
INSTALLATION and GROUNDING
INSTALLATION
Caution: These ow sensors are not recommended
where installation fault may expose the ow sensor to boiler pressure and temperature. Maximum recommended temperature is 130˚ F.
Positioning the Meter. These meters can be installed horizontally, vertically, and in any radial position. Using a
check valve on the upstream side of the meter, and/or an air vent (vacuum relief valve) in the same, unobstructed run of pipe as the meter, is required in any installation where the meter may be exposed to suction when the system is not in normal operation. Suction can cause damage to the liner. Liner damage caused by suction, without the use of a check valve and/or air vent, may void the warranty.
Straight Pipe Recommendations. As with most flow
meters, the WMX requires some straight pipe before and after the meter for best accuracy. However, the ability of electromagnetic meters to average the ow across the entire pipe allows for shorter straight pipe recommendations than most mechanical meters (see page 4).
Full Pipe Recommendations. All magmeters require a method for determining that the pipe is empty, to prevent false reading. This meter is designed to go to zero reading if one or more electrodes is exposed. For highest accuracy, install the meter so that the pipe will be full when there is ow. If air bubbles may be present in the pipe or sludge accumulation is an issue, rotate the meter by one ange hole to position the control housing at a 45˚ angle (see diagrams on page 5).
Fittings. The WMX anges have standard ANSI 150 lb. drilling and mate with any other ANSI 150 lb. ange.
Installing Gaskets
GASKETS Gaskets are required at all junctions.
(Not applicable to 3” model.)
1. Select a suitable full-face gasket.
Only use at compressible gaskets (either pliable or hard ber will work).
Use a material compatible with the uid you will be using.
Thickness should be 1/8” - 1/4” (3 - 6 mm), depending on the atness of the pipe ange surface.
Inner diameter must be larger than opening in ow meter.
2. Be sure all mating surfaces are smooth and free of debris.
3. Install gaskets on each end of meter as shown in diagrams below. If using grounding rings, install one gasket on each side of the grounding ring.
Gaskets
Installation without gaskets
Calibration. The WMX is factory-calibrated and will not require any form of eld calibration.
Chemical Injection. When any magmeter, by any manufac­turer, is used in a chemical injection application, the chemical
injection point must be placed downstream of the magme­ter OR far enough upstream for complete mixing to occur
before the uid reaches the meter. When unmixed chemical alternates with water passing through the meter, the rapid changes in conductivity may cause sudden spikes and drops in the meter’s reading, resulting in inaccurate measurement. The magmeter will restabilize, however, with a steady ow of uid of uniform conductivity.
Caution: In chemical injection applications, install chemical injection point downstream of magmeter, or far enough upstream to allow complete mixing of uids before the meter.
Page 4
Grounding
Rings
Gaskets
Installation with gaskets
Page 7
INSTALLATION and GROUNDING
Tightening Flange Bolts
NOTE: Mating pipe anges must be ANSI 150# full face (FF) and/or raised face (RF).
1. Tighten ange bolts in an alternating pattern.
Tighten left ange bolt-1 to 20% recommended torque.
Tighten right ange bolt-1 to 20% of recommended torque.
Repeat steps a and b for each bolt in an alternating order, such as shown at right, tightening to 40%, then 60%, then 80%, and then 100%.
2. Test for leaks.
3. If needed, tighten further in 10% increments until leaking stops. DO NOT over-tighten. Over-tightening
can cause serious damage to the ow meter.
4. Recheck after 24 hours, adjusting if needed.
1
5
8
Equalization and Grounding
WARNING: ELECTRICAL SHOCK HAZARD
When the is installed in a plastic piping system, or when externally powered, the piping system must be grounded to meet national and local electrical safety codes. Failure to do so can result in electrocution.
Metal Pipe Installations. To equalize the electrical potential
of the uid, the meter, and the surrounding pipe, secure the ange plates (factory-installed on the equalization wire) to both pipe anges at one of the bolt holes, as shown below. Be sure the lock washer ts between the pipe ange and the ange plate. For the best electrical bonding, remove rust and paint to expose clean, bare metal where the equalization ange plate lock washer contacts the pipe ange. Connection must be inspected periodically for corrosion to maintain the necessary low resistance connection.
Meter Flange
Gasket
Pipe Flange
Lockwasher
Flange Plate
Equalization Lug
3
7
4
6
2
Suggested Tightening Sequence
Caution: Improper tightening sequence
can cause serious damage to the ow
meter.
• Do not tighten one side at a time.
• Do not tighten each bolt completely at one time.
SUGGESTED FLANGE BOLT TORQUE
Santoprene Liner
Pipe Size ft-lb Nm
3” 25 34
4” 20 27
6” 42 57
8” 65 88
10” 73 99
12” 97 132
Meter
Flange
Gaskets
Pipe Flange
Metal PipeMetal Pipe
Plastic Pipe Installations. When the meter is installed in a plastic piping system, grounding rings are recommended (except 3” pipe size), especially in the presence of electrical interference sources such as VFD pump drives. As shown in the diagram below, the equalization wires should then be connected to the grounding ring tabs instead of the ange bolts as in metal piping installations. Where lightning is a threat, or in severe electrical environments, an optional connection to a nearby equipment ground or ground rod may be advisable.
Equalization Lug
Grounding Ring
Gaskets
Plastic Pipe
#6, #8, or #12 AWG Stranded Copper Ground Wire < 5’
Grounding Ring Part Numbers:
4” = 100876 10” = 100879 6” = 100877 12” = 103288 8” = 100878
Grounding Ring Gaskets
Plastic Pipe
Ground Clamp
(Exothermically weld when corrosion is a concern)
Earth
8’ Ground Rod
Page 5
Page 8
STRAIGHT PIPE RECOMMENDATIONS
(X = diameter)
Reduced Pipe
Two Elbows In Plane
Two Elbows, Out Of Plane
1X
2X
WMX
1X
2X
WMX
1X
2X
Expanded Pipe
Swirling Flow
Propeller Meter
5X
5X
WMX
WMX
5X
1X
1X
WMX
1X
Swirling Flow
Partially Open
Buttery Valve
Page 6
WMX
Page 9
FULL PIPE RECOMMENDATIONS
Recommended:
Keep pipe full at meter for accuracy
WMX
WMX
Not Ideal:
Allows air pockets to form at meter
WMX
Recommended:
Keeps pipe full at meter for accuracy
WMX
Recommended:
Allows air to bleed off
Intermittent air
Electrode
moved from
top by rotating
meter
WMX
miss electrode
Electrodes free
from sediment
bubbles
build-up
WMX
Not Ideal:
Post-valve cavitation can create air pocket
WMX
Not Ideal:
Air can be trapped
Intermittent air
bubbles
pass over
electrode
Possible
sediment
build-up
WMX
Recommended:
Improved accuracy results from
unimpeded electrodes
Not Ideal:
Air bubbles and sediment on the
electrodes can affect accuracy
Page 7
Page 10
INPUTS/OUTPUTS and OPERATION
WMX101 External Power (WMX101). The WMX101 operates on 8 to
32 Vdc at 30 mA max external power (see WARNING in wiring diagrams). The display reads “P” when external power is in use (see illustration below).
The Lithium battery pack installed in the WMX101 serves as backup in the event of a power failure, when it will keep the meter operating without interruption for the duration of the outage. When battery power in is use, the WMX101 display continues to read out the rate and total, but the “P” indicating external power is extinguished. When power resumes, the WMX101 will seamlessly return to normal power mode, and the “P” will again display.
When used for occasional emergency backup, battery life is approximately ten years.
Pulse Output (WMX101). The WMX101 cable also provides pulse output that can be used for remote reading, 4-20 mA signal conversion, datalogging, and telemetry applications. See page 7 for connection diagrams to Seametrics controls and displays.
Pulse Output (WMX104). Pulse output capabilities are built in to the WMX104, but cannot be utilized without the addition of an optional output cable. A WMX104 can be retrotted with this cable in the eld. IMPORTANT: When eld installing the
input/output cable, be sure to snugly tighten the cable strain relief to prevent water ingress.
OPERATION
Caution: There are no user-adjustable connections or settings inside the display housing. Use caution when opening the housing for a battery change, to avoid
damage to internal components.
Display Reading. The WMX display has two lines, the bottom line for ow rate and the top line for accumulated total. Measurement units are pre-ordered and factory-set and can be changed in the eld only by an authorized individual.
Refer to the diagrams below to read your display.
Note: For data logger setup and operation, refer to Flow Inspector Manual
Pulse rates are selected by the customer at time of order, factory-set, and can only be changed in the field by an authorized Seametrics dealer. Three pulse rates are possible: One pulse per ten gallons (or liters), one pulse per thousand gallons (or liters), or High Frequency (required for use with 4-20 mA converters; see below):
High Frequency Output/K-Factor
Meter Size Pulses per Gallon Pulses per Liter 3” 25.228 6.665 4” 16.362 4.323 6” 6.307 1.666 8” 3.344 0.883 10” 2.150 0.568 12” 1.530 0.405
WMX104 Battery Power (WMX104)*. The WMX104 is powered by a
non-rechargeable battery pack with an approximate 1-year life under continuous use. Actual lifespan will vary from application to application, depending on the duty cycle.
External Power Indicator
(WMX101 Only)
Battery Power
(WMX104 Standard Operation)
(WMX101 Backup Operation)
No Power
Empty Pipe
“Low Batt” will display when there are approximately three days of use left in the batteries (see illustration). Replacement instructions come with the custom battery pack available from your dealer or Seametrics.
Page 8
Low Batt
Low Battery Indicator
(3 days remaining)
Meter Installed Backwards
Page 11
CONNECTIONS DIAGRAMS (WMX101)
The WMX101 requires a power source of 8 to 32 Vdc at 30 mA max (see WARNING). The WMX101 power cable also serves as a pulse output if needed for remote reading, data logging, signal conversion, or telemetry.
AO55/WMX101
Blue
Do
Not
{
Orange
Use
4-20 mA
Power
5
6
4
3
2
1
0
S
Sensor
Not
Used
Frequency
5
6
4
7
8
9
7
3
8
2
9
1
0
5
5
6
6
4
4
7
7
3
3 2
8
8
2
9
9
1
1
0
0
Power Supply
at 30 mA max
(see WARNING)
White (-) Green (+)
Black
Red
(-) (+)
8-32 Vdc
AO55W Pulse-to-Analog Converter
FT420/WMX101
External Power Input Required - 12-32 Vdc
WMX101 Cable Color Codes
Orange and Blue: Serial Output (Do Not Use) Green (+) and White (-): Pulse Output, 30 Vdc max, 10 mA max Red (+) and Black (-): External Power, 8-32 Vdc at 30 mA max Drain: Connect to earth ground (see WARNING)
WMX101 Cable
Shielded
Drain Wire
Direct Burial Cable 22 AWG Stranded
WARNING: Using an unregulated power supply >18 Vdc may damage the meter due to AC line input voltage uctuation.
WMX101
PASSTHRU
PULSE
SCALED
PULSE
Power
4-20 mA
Input
Sensor
Not
Used
FT420W Remote Rate/Total Display
DL75 or DL76/WMX101
Battery
-
S
+
Not
Used
Blue
Do
Not
{
Orange
Use
White (-)
Green (+)
Black
Red
(-) (+)
Power Supply
8-32 Vdc
at 30 mA max
(see WARNING)
Blue
Do
Not
{
Orange
Use
White (-)
Green (+)
Black
Red
Drain Wire
WMX101 Cable
Shielded Direct Burial Cable 22 AWG Stranded
WARNING: Using an unregulated power supply >18 Vdc may damage the meter due to AC line input voltage uctuation.
WMX101 Cable
Shielded Direct Burial Cable 22 AWG Stranded
WMX101
WMX101
DL75W or DL76W Data Logger
(-) (+)
Power Supply
8-32 Vdc
at 30 mA max
(see WARNING)
Drain Wire
WARNING: Using an unregulated power supply >18 Vdc may damage the meter due to AC line input voltage uctuation.
Page 9
Page 12
TROUBLESHOOTING
Problem
Blank Display
Flow rate steadily reads zero when there is ow
Flow rate intermittently drops when there is ow
Probable Cause Try...
Dead battery (WMX104)
No power plus dead battery (WMX101)
Replace battery pack
Replace battery pack, check power
connections
Flow is below cutoff (very low)
Pipe is not full
Meter is installed backwards
Reading will resume when ow increases
Reposition meter for full pipe (see page 4)
Note ow direction arrow, reverse meter
(display reads [ - ] )
Power connections reversed (WMX101)
Fluid conductivity <20microSiemens/cm
Pipe is not full
Change power connections
Select another ow meter
Reposition meter for full pipe (see page 4)
Jumpy reading
Meter reads, but no pulse output (WMX101)
Output pulses missing
Missing or incorrect ground wire
Pulsing ow
Rapidly changing conductivity (in chemical injection applications)
External device needs pull-up resistor
Reversed leads (polarity sensitive)
Meter not reading
Check for proper ground
Use external power source (allows more ow averaging)
Install chemical injection line downstream of meter (or far enough upstream to allow complete mixing of uids before meter)
Add pull-up resistor (For details, refer to ‘Connecting to PLCs’ Technical Bulletin at www.seametrics.com)
Change output connections
Check display
Seametrics • 19026 72nd Avenue South • Kent, Washington 98032 • USA
(P) 253.872.0284 • (F) 253.872.0285 • 1.800.975.8153 • www.seametrics.com
LT-65200289r1.2 20161020
10/20/16
Loading...