Seametrics FT520-86 Instructions Manual

FT520-86 Flow Rate Alarm Instructions rev b
General Information
The FT520 is a flowmeter monitor with added output and alarm features. It is designed for use with SeaMetrics flow meters and sensors, as well as other units which have a pulse or frequency output. It displays flow rate and total in large digits on an easily-read backlit display. Units are user selectable between gallons, cubic feet, and cubic meters.
The primary output of this unit is is a set of user­configurable alarm relays which can signal when a maximum or minimum flow is reached. Applica­tions tyically include detection of a pipeline failure or of a pump that has run dry. The dual relays can be connected to an alarm, auto dialer, or any other switch-controllable device.
In addition to the flow rate alarm, the FT520 has analog output (4-20 mA, 0-5 VDC or 0-10 VDC) and programmable pulse output. These can be used for data logging or to provide proportional chemical feed, using an externally-controlled metering pump.
Specifications
Power 115 VAC (220 VAC optional),
50/60 Hz; 12 VDC
Temperature 32° -130° F (0° - 55° C) Enclosure Precision cast aluminum,
NEMA 4X
Alarm Outputs Two Form C SPDT relay,
115 VAC 5A max
Max Pulse Output 100 mA at 60 VDC Memory Type Non-volatile EEPROM
auto-backup
Sensor Power 12 VDC, 10 mA Totalizer 8 digit Rate Display 5 digit Volume Units Gallons, cubic feet, cubic
meters, liters, million gallons
Time Units Minutes, hours Analog Output 4-20 mA, 0-5 VDC, 0-10 VDC,
opto-isolated
Sensor Input Open collector current sink,
ESD protected
Max Input Frequency 1,000 Hz Shipping Weight 7 lbs
Features
Easy-read
backlit display
Remote control terminals
(inside housing)
Rugged cast aluminum
housing
(wall or panel mount)
Start Stop
0.00 GPM
0.00 GAL
Set
Resume
Relay 1 Relay 2
Pulse
Output
Choice of
rate/volume units
Alarm output
indicator LED
Accessible
control
buttons
LT-11298-A Page 1 of 4
Installation
Displays
Wall Mounting. Using the four screws provided, attach
the two foot brackets to the sides of the enclosure. Then attach the unit to any secure surface by inserting screws through the mounting holes in the foot brackets.
Panel Mounting. Follow the dimensions given for “Panel Cutout” (see page 4). Be sure to include the four corner screw holes. After cutting and drilling, place the front plate on the front side of the panel with its gasket against the panel, and the remainder of the square housing on the back side. Slide the screws through the four holes drilled in the panel, and into the threaded holes in the housing. Tighten until the gasket is firmly compressed against the panel.
Expose T erminals. Remove the four screws which hold the front plate to its flange. Remove the front plate. The display board is attached to this front plate. It is also connected to the power board by a ribbon cable. For convenience, this cable can be disconnected while making connections. Connections can be made inside the enclosure, or the terminals can be unplugged for easier access, by gently tugging on them.
Caution: When the control is powered up, relay or analog outputs may be active. If this could be a hazard, wait to make external connections
!
until programming is com­plete.
Sensor Connection. Follow the “Connections” diagram
to connect either two or three wires from the flow meter or flow sensor.
Flow Alarm Connection. Connect the alarm devices to the appropriate relay terminals. Note that the relays have both normally-open (NO) and normally-closed (NC) con­tacts.
Analog Connection. This output can be configured 4­20 mA, 0-10 V or 0-5 V by placing a jumper in the cor­rect position on the analog header. The swith next to the header selects active (powered) or passive (unpowered) output. When using the 12 VDC powered input you may only select passive output.
Power Connection. Connect AC or DC power as desired to the appropriate terminals. For safety, if using AC power, be sure to connect the ground terminal provided to a good earth ground. If using DC power, be
SETTINGSOPERATION MODE
0 GPM 0 GAL
Flow
SET
Rate
SET
SET
SET
SET 20 mA RATE
SET
SET
Low Flow Alarm:
SET
0.0 GPM
High Flow Alarm:
SET
SET
SET
0.0 GPM
TO CLEAR TOTAL
SET
PRESS UP & LEFT
return to
SET
operation mode
Set Decimal
0.00
Set K-factor
Set Pulse Out
1.00 Gal
123456 GPM
60.00
GAL
MINUTE
sure to use a Seametrics PC1 (part number 05040) or comparable 12 V 500 mA power supply.
Replace the front panel, taking care to reconnect the ribbon cable if it has been disconnected. When power is switched on, the display should light up immediately
with meaningful letters or digits.
Settings
Set Units. Press . Use to select volume
units. Use to select the particular unit desired (gallons, liters, etc.). Then use to switch to time units. Again, select the unit desired. Press for
next menu item. Set K-Factor. The unit will not function properly
until this number is entered. It is simply the number of pulses which the flow meter or flow sensor puts out per gallon of liquid. It is marked on the Model/ Serial tag of SeaMetrics flow meters and flow sensor fittings. On adjustable flow sensors, the K­factor must be taken from the chart in the flow
sensor instructions, based on pipe size. Press for next menu item.
Set Pulse Out. An output pulse is activated at the selected volume intervals if this feature is in use.
Otherwise, it does not need to be set. Press for next menu item.
2 of 4
Set 20 mA Out. The SET 20mA RATE programs the flow rate at which the output is 20 mA, 5 V or 10
V. Use and to set the maximum flow rate for full scale output. Press
for next menu item.
Set Low Alarm. Use and to set the desired minimum flow rate. Low alarm corresponds to alarm relay one (see Connections diagram). Press for next menu item.
Set High Alarm. Use and to set the desired maximum flow rate. High alarm corresponds to
alarm relay two (see Connections diagram). Press
for next menu item.
Clear Total. This function resets the running total back to zero. To reset to zero, press and
simultaneously, or press and the total will remain the same. The “Start/Stop” and “Resume” keys are not used in flow alarm mode.
Operation
The last press of the key returns the unit to operation mode (see “Displays” diagram).
Flow Monitoring. The “Rate indication gives the current rate of flow. “Total is a running total of flow which increases indefinitely unless it is reset (see procedure under “Settings”).
Alarms. Alarm relay two activates when flow reaches the high alarm set point. Because of the built-in hysteresis, the relay does not deactivate until the flow rate has reached 10% below the high alarm set point. Similarly, alarm relay one activates when flow reaches the low alarm set point, and does not deactivate until flow returns to 10% above the low alarm set point.
Connections
Pulse Outputs
(for metering pumps)
-Autodialer
-Pump
-Alarm
-Valve Shutoff
Hot
Neut
110 VAC
Gnd
Alternate
12 VDC power
PC1 power supply
P/N 05040
Pulse 1
Pulse 2
Alarm 1
Alarm 2
Main
power fuse
250mA
part # 26926
Customer Supplies 1A Fuse
NO COM
NC
NO
COM
NC
Ribbon connector
from display board
RESUME
COM
BATCH
+
s1
+
5V
10V
4-20mA
Jumpers
s2
Active
+
A
P
Passive
Analog Switch
Analog Jumper
A
utput
B
An O
RED
WHITE
BLACK
Resume Start/Stop
Power signal Sensor Input
Ground
0-5 V or 0-10 V or 4-20 mA
Remote Controls
Dry contact
Meter
3 of 4
Repair
The only field-repairable component on the FT522 is the fuse. If failure is due to a cause other than a blown fuse, it is necessary to replace the entire board stack. Contact your distributor for information.
Panel Cut-out Dimensions
!
Caution: Always disconnect power to the unit before opening the terminal cover. Do not reconnect power until all connections have been made and the terminal cover has been replaced.
1/4" holes (4 required)
gasket
5.50"
6.03"
5.50"
PANEL CUTOUT
6.03"
4 of 4
20419 80th Ave. So., Kent WA. 98032 USA
Phone: 253-872-0284 Fax: 253-872-0285
www.seametrics.com 1-800-975-8153
Loading...