Scotsman CME1356R, CME1656R User Manual

Introduction
CME1356R and CME1656R
This product manual contains the information needed for the setup, installation, initial start up, sanitation and maintenance of this ice machine. Keep it for future reference.
There are 2 models covered in this manual:
CME1356R, (5 evaporators)
CME1656R, (6 evaporators)
TABLE OF CONTENTS
Specifications .................PAGE2
Condenser and Ice Machine Layouts .....PAGE3
Pre-Installation .................PAGE4
Location & Assembly .............PAGE5
Bin Control: Installation ............PAGE6
Bin Control ...................PAGE7
Be certain that the information applies to the model in question. If no model is listed, the information applies to all models.
This manual is organized in the same way as the expected use of the machine, it begins with specifications, goes thru unpacking and setup, shows where everything is; continues with initial start up, then describes how it works. After that is the sanitation section, followed by service diagnosis and repair.
Sanitation and Cleaning ........... PAGE 26
Additional Maintenance ........... PAGE 27
Additional Maintenance: Water Distributors . PAGE 28
Additional Maintenance: Inlet Water Valve
Screen .................... PAGE 29
Additional Maintenance: Ice Sensors,
Condenser .................. PAGE 30
Stacking ....................PAGE8
For The Installer: Remote Condenser .....PAGE10
Remote Condenser Location .........PAGE11
Coupling Instructions .............PAGE12
Head Pressure Control Add-On Kit ......PAGE13
Electrical ....................PAGE14
Plumbing ....................PAGE15
After Utility Connections ............PAGE16
Component Location and Function ......PAGE17
AutoIQ Controller ...............PAGE18
Initial Start Up .................PAGE19
Adjustments ..................PAGE20
How To Operate The AutoIQ Controller ....PAGE21
How The Electronic Cuber Works .......PAGE22
Technicians Only: Freeze Cycle Sequence . . PAGE 24
Technicians Only: Harvest Cycle Sequence & Other
Notes .....................PAGE25
Parts Lists and Wiring Diagrams are in the section at the center of this manual.
May 2000
Page 1
Service Diagnosis: Diagnostic Light Analysis PAGE 31
Service Diagnosis .............. PAGE 32
Service Diagnosis: Components ....... PAGE 33
Service Diagnosis .............. PAGE 34
PTCR ..................... PAGE 35
Operational Characteristics: CME1356R . . . PAGE 36
Operational Characteristics: CME1656R . . . PAGE 37
Removal and Replacement ......... PAGE 38
Removal and Replacement ......... PAGE 39
Removal and Replacement: AutoIQ Controller
........................ PAGE 40
Removal and Replacement: Water Level Sensor
........................ PAGE 41
Removal and Replacement ......... PAGE 42
Refrigerant .................. PAGE 43
Before Calling for Service .......... PAGE 45
CME1356R and CME1656R
Specifications
Both of these ice machines are designed to be installed indoors, in a controlled environment. They can operate satisfactorily under a wide variety of conditions. However, Do NOT operate the machine in temperatures it has not been designed for. Do NOT operate the machine above or below the voltage limits for the particular model. Do NOT operate the machine with too little or too much water pressure.
Operational Limits
Minimum Maximum
Air Temperature 50
Water Temperature 40oF. 100oF.
Water Pressure 20 psi 80 psi
Voltage (60 Hz) 197 253
Voltage (50 Hz) 207 253
Scotsman reserves the right to make design changes and/or improvements at any time. Specifications and designs are subject to change without notice.
o
F. 100oF.
Voltage note: The control system transformer in the control box of this ice machine has two primary taps, one for 208 volt power and one for 240 volt power. The machine ships with the power supply connected to the 208 volt tap. Change to the 240 volt tap when the voltage supplied to the unit is greater than 229 volts.
Bins:
All models will fit a standard, 48" wide or wider open top Scotsman Ice Storage Bin. Examples include BH900, BH1100, BH1300, BH1600
In addition, there may be other bins that can be used, check Scotsman’s sales literature for application information.
Note: Slope-front bins must have an internal baffle. Scotsman’s BH900 has the required baffle. Baffle must be approximately in the position shown in the diagram below.
Baffle
Scotsman assumes no liability or responsibility of
12.0"
any kind for products manufactured by Scotsman that have been altered in any way, including the
4.0"
use of any parts and/or other components not specifically approved by Scotsman.
BASIC INFORMATION
Dimensions
Model Number
CME1356RS-32F 48 ½ “ x 24" x 28 208-230/60/1 ECR411-32A 288 oz 24.9 30
CME1356RS-3F same 208-230/60/3 ECR411-32A 288 oz 15.9 20
CME1356RS-6F same 230/50/1 ERC411-32A 288 oz 24.9 30
CME1656RS-32F same 208-230/60/1 ECR411-32A 288 oz 24.9 30
CME1656RS-3F same 208-230/60/3 ECR411-32A 288 oz 15.9 20
CME1656RS-6F same 230/50/1 ECR411-32A 288 oz 24.9 30
W x D x H (w/o bin)
Basic Electrical (volts/Hz/phase)
Use Condenser
Side View
Refrigerant Charge R-404A
Minimum Circuit Ampacity
* The remote condenser is designed to work in temperatures from -20oF. to 120oF.
Maximum Fuse Size
Use precharged tubing kits, RTE25 (25’) or RTE40 (40’) or RTE75 (75’). Select the length closest to the needs of the particular installation.
The stacking kit required to place two like model cubers together is: KSCME6-LG-B. The kit required to connect this ice machine to a central condenser is: RCKCME6-GX
November 2004
Page 2
Condenser and Ice Machine Layouts
2
.88 DIA. ELECTRICAL INLET
DISCHARGE LINE 1/2" MALE CPLG.
CME1356R and CME1656R
29.50 in
74.9 cm
ERC411
.562 DIA. MOUNTING HOLES (4)
6.00 in
15.2 cm
CONDENSER FINS
23.54 in
59.7 cm
29.15 in
74.0 cm
MINIMUM FOR
UTILITY CONNECTIONS
2.75
38.47 in
97.7 cm
32.32 in
35.72 in
90.7 cm
15-0782-01CANCAUSEINJURYOR DEATH:DISCONNECT ALL REMOTE ELECTRICPOWERSUPPLIESBEFORESERVICING.RISKOFELECTRICSHOCK^MWARNING
2.84 in
7.2 cm
82.1 cm
28.07 in
71.2 cm
7.60 in
19.3 cm
6.10in
66.3 cm
MINIMUM BIN TOP OPENING
24.71 in
62.7 cm
11.50 in
29.2 cm
14.56 in
36.9 cm
27.56 in
70.0 cm
29.19 in
74.1 cm
.65 in
1.7 cm
LIQUID LINE 3/8" MALE CPLG.
AIR FLOW
PLAN VIEW
18.75 in
47.6 cm
ICE
OPENING
6.00 in
15.2 cm
MINIMUM FOR
AIR VENTILATION
REMOTE CONDENSER LIQUID LINE 3/8" MALE CPLG.
23.30 in
59.2 cm
22.65 in
57.5 cm
BACK VIEW
DUMP VALVE DRAIN 3/4" F.P.T.
REMOTE CONDENSER DISCHARGE LINE 1/2" MALE CPLG.
WATER INLET 3/8" FLARE
May 2001
4.20 in
10.7 cm
ICE
OPENING
18.67 in
47.4 cm
Page 3
.88 DIA. KNOCKOUT ELECTRICAL INLET
15.77 in
40.1 cm
21.77 in
55.3 cm
10.15 in
25.8 cm
2.50 in
6.4 cm
5.87 in
14.9 cm
17.87 in
45.4 cm
2.46 in
6.2 cm
3.81 in
9.7 cm
.88 DIA. KNOCKOUT REMOTE CONDENSER FAN
23.87 in
60.6 cm
CME1356R and CME1656R
Pre-Installation
Other Applications:
Check sales literature for additional information.
Electrical:
Check the nameplate for electrical requirements. The nameplate is located on the back of the ice machine. If the information on the nameplate is different from other published information, go by the nameplate data.
While the model and serial number are on the nameplate, a serial number plate is located at the front of the machine, behind the left front panel and to the right of the purge valve.
Nameplate
Serial Number Plate
Water:
There is no such thing as pure water. All water contains some impurities. There are two ways water carries the impurities: suspended and dissolved. Suspended solids can be filtered out. Dissolved solids must be diluted or treated. Water filters are recommended to remove suspended solids. Some filters have treatment in them for suspended solids. Check with a water treatment service for a recommendation.
Cube Ice machines use more water than what ends up in the bin as ice. While most water is used during ice making, a portion is designed to “rinse" out the water system to keep hard water scale from clogging up the machine. That water rinse, combined with water filters, prolongs the times between needed water system cleaning.
Service Technicians: All models covered here come set from the factory with at a “Standard” water rinse. Standard water rinse is designed to be compatible with typical water conditions. The machine may be adjusted to a different water rinse after start up. If the prior ice machine worked acceptably well with the local water conditions, leave the machine at the factory setting. If severe water conditions are present, and water filters do not solve the problem acceptably, adjust the machine to use more water. If water conditions are excellent, adjust the machine to use less water. See the Adjustments section.
Note: Water use adjustments are customer convenience adjustments; they are NOT factory defects and are NOT covered by warranty.
May 2001
Page 4
Location & Assembly
CME1356R and CME1656R
Locate the ice machine indoors. A 6 inch minimum clearance on the back and left sides is required for the proper operation and service of this machine.
Locate the remote condenser as close as possible to the ice machine. See page 11 for details.
Unpacking and Assembly:
Begin with unpacking the ice storage bin. Remove the carton, and using part of the carton as a cushion, tip the bin on its back to remove the skid and attach the legs or casters. Note: Stacked
applications may not use casters.
Return the bin to an upright position. Check the bin top gasket for gaps and tears, fill any in with food grade sealant prior to placing the ice machine on the bin.
Note: If recycling a prior bin, be sure that the bin top gasket is in good condition or seal the ice machine to the bin with food grade sealant.
Level the top edge of the bin front to back and left to right.
If the ice machine has not been unpacked, do so now. Remove the carton from the skid. Remove shipping straps.
Remove the front panels and all packaging materials.
After all packing materials have been removed from the ice machine, lift or hoist the machine onto the bin. Align the sides and back of the machine with the sides and back of the bin.
Secure the ice machine to the bin with the two metal straps and 4 bolts provided.
Cabinet Panel Removal:
1. Remove the front panel by removing the two screws connecting the front panel to the machine.
2. Lift up at the front edge and push the top panel back until it releases from the tabs connecting it to the back panel.
3. Remove two screws at the front of each side panel, and pull them forward until they release from the tabs connecting them to the back panel.
Evaporator Cover:
To Remove
Evaporator Cover:
Push Up and Tilt Out
May 2001
Page 5
CME1356R and CME1656R
Bin Control: Installation
The bin control is a thermostat. It must be field installed after the ice machine has been placed on the bin.
Before starting, remove the left front panel and any baffle in the bin.
1. Locate bin thermostat bulb.
2. Route bulb thru routing tube (located between the compressor and the reservoir).
3. Locate bin thermostat bracket.
4. Carefully position the thermostat bulb on the bracket (see the diagram on the next page).
5. Fasten the bracket to the bottom of the ice machine with the two 3-pronged knobs supplied with the unit.
6. Pull back into the ice machine any excess capillary tubing.
7. Return the baffle to the bin and continue with the installation.
Note: If the machine is located at an altitude higher than 2,000 ft., adjust the thermostat by removing the plastic cover and rotating the adjustment screw per the table.
Thermostat Bulb Routing Tube
Bin Thermostat Altitude Correction Table
CW Turns of Range Screw (under plastic cover)
Feet Turns Feet Turns 2000 55 4000 160 6000 250
o
o
o
8000 340 9000 385 10000 405
o
o
o
Use This Table to Adjust Thermostat
Bin
Thermostat
Body
Thermostat Bulb
Routing Tube
Bin Thermostat Bulb
Route Bin Thermostat Bulb Into Bin
May 2001
Page 6
Bin Control
Bin Thermostat
Bracket
Mount Bulb
Tip Here
CME1356R and CME1656R
Bin Thermostat
Capillary Tube
Mount Thermostat
Capillary Tube Here
Attach Thermostat Bulb to Bracket
Minimize Excess
Tube in Bin
Three-Pronged Knob
Thermostat and
Bracket
Attach Bracket to Bottom of Ice Machine
May 2001
Page 7
CME1356R and CME1656R
Stacking - Kit KSCME6-LG-B
Only like models may be stacked. Begin after the bottom unit has been placed on the ice storage bin and secured. Stacking requires heavy duty leg kits. Casters are NOT recommended.
Note: Instructions are for either model.
Bottom Machine:
1. Remove front panel, left side panel, and top panel.
2. Remove & discard top cover from over the freezing compartment.
3. Install gasket materials to freezing compartment:
Cut about 22" of gasket material from the roll in the kit. Apply it to the back side top edge of the freezing compartment.
Cut two lengths of gasket material to fit the right side top edge of the freezing compartment and apply them.
4. Place a bead of food grade sealant to the top of the back wall’s gasket.
5. Place the shield bracket (has a large hole in the center) from the kit over the center of the freezing compartment.
Insert the tabs of the bracket into slots on the back of the unit.
6. Secure bracket at the front with screws from the kit.
7. Hang the plastic shields from the bracket installed in the prior step. Use the slots in the shields to hang them from the stainless steel hooks.
Note: The notch in the bottom of the shield goes to the front.
Note: The tabs on the shields must fit inside the ice outlet port.
8. Check the position of the shields. They must move freely and be vertical.
Note: The suction line may need to be moved slightly so the tubing clears the bracket & shields.
9. Place a bead of food grade sealant onto the top left edge of the freezing compartment.
10. Install the front-to-back support bracket over the left edge of the freezing compartment.
11. Remove two existing screws and secure the bracket to the: freezing compartment, back panel and front channel with the 2 existing screws and 1 large and 4 small screws from the kit.
Both Machines:
12. Place the top ice machine onto the bottom one. Secure together with hardware from the top machine. Remove left front and left side panels.
13. At the back of the ice machines, on the compressor end, remove the upper knock-out from the bottom machine and the lower knock out from the upper machine.
14. Place a strain relief (from the kit) into each hole.
15. Insert wire harness from kit thru strain-relief and hole in upper corner of the lower ice machine’s back panel.
NOTE: Harness is marked which end goes to which machine.
Bottom Machine:
16. Remove harness from controller terminal 7 and bin thermostat.
17. Route wire harness in lower ice machine to the controller. Connect to terminal #7. Plug the two free wires onto the thermostat terminals #1 and #2.
18. Return left side panel to its original position on the lower ice machine.
Top Machine:
19. Remove harness from controller terminal 7.
20. Route wire harness thru upper unit’s lower knock-out hole and strain relief and continue internally to the controller. Plug wire onto terminal 7 of the controller.
21. Return all panels and covers to their normal positions.
22. Complete the balance of the installation.
Service Notes:
A. The shields must be positioned so they hang vertically and move freely left to right. Their purpose is to guide the ice past the bottom machine’s evaporators and into its cube port.
B. The drain lines from each ice machine must be kept separate.
May 2001
Page 8
Stacking
CME1356R and CME1656R
Gasket on
Plastic Walls of
Lower Unit
Gasket for Metal
Edges of Bottom
Unit
Front-to-Back
Support Bracket
Mounting Straps
and Hardware
Shield Hanger
Bracket
Shield
May 2001
Page 9
CME1356R and CME1656R
For The Installer: Remote Condenser
Locate the condenser as near as possible to the interior location of the ice maker.
Note: The location of the condenser relative to the ice machine is LIMITED by the specification on the following page.
Select the best available location, one that protects the condenser from extremes of dust, grease and sun.
Meet all applicable building codes.
Roof Attachment
Install and attach the remote condenser to the roof of the building, using the methods and practices of construction that conform to the local building codes, including having a roofing contractor secure the condenser to the roof.
Note: If using any other condenser besides the ERC411, its use must be approved by Scotsman, and a head pressure control valve must be connected to the condenser coil. The head pressure valve kit number is: RCKCME6
Precharged Line Routing
Do not connect the precharged tubing until all routing and forming of the tubing is complete. See the Coupling Instructions for final connections.
1. Each set of pre-charged tubing lines contains a
3
“ diameter liquid line, and a
8
1
” diameter
2
discharge line. Both ends of each line have quick connect couplings, the end without access valves goes to the ice maker.
Note: The openings in the building ceiling or wall, listed in the next step, are the minimum sizes recommended for passing the refrigerant lines through.
2. Have the roofing contractor cut a minimum hole for the refrigerant lines of 2“. Check local codes, a separate hole may be required for the electrical power supply to the condenser.
Caution: Do NOT kink the refrigerant tubing while routing it.
3. Route the refrigerant tubes thru the roof opening. Follow straight line routing whenever possible.
Note: Excess tubing may EITHER be coiled up INSIDE the building OR cut out prior to connection to the ice maker and condenser.
If the excess tubing is cut out, after re-brazing the tubing must be evacuated prior to connection to the ice maker or condenser.
If the excess tubing is to be coiled, spiral it horizontally to avoid excess trapping in the lines.
Note: A 36" service loop may be placed behind the ice machine.
5. Have the roofing contractor seal the holes in the roof per local codes.
ERC411 Remote
Condenser
Electrical
Power Supply
Coil Excess
Tubing
Horizontally
Within the
Building
Typical Installation
May 2001
Page 10
Remote Condenser Location
CME1356R and CME1656R
Use the following for planning the placement of the condenser relative to the ice machine
Location Limits - condenser location must not exceed ANY of the following limits:
Maximum rise from the ice machine to the
·
condenser is 35 physical feet
Maximum drop from the ice machine to the
·
condenser is 15 physical feet
Physical line set maximum length is 100 feet.
·
Calculated line set length maximum is 150.
·
Calculation Formula:
Drop = dd x 6.6 (dd = distance in feet)
·
Rise = rd x 1.7 (rd = distance in feet)
·
Horizontal Run = hd x 1 (hd = distance in feet)
·
Calculation: Drop(s) + Rise(s) + Horizontal Run
·
= dd+rd+hd = Calculated Line Length
Configurations that do NOT meet these requirements must receive prior written authorization from Scotsman.
Do NOT:
Route a line set that rises, then falls, then rises.
·
Route a line set that falls, then rises, then falls.
·
Calculation Example 1:
The condenser is to be located 5 feet below the ice machine and then 20 feet away horizontally.
5 feet x 6.6 = 33. 33 + 20 = 53. This location would
be acceptable
Calculation Example 2:
The condenser is to be located 35 feet above and then 100 feet away horizontally.
35 x 1.7 = 59.5. 59.5 +100 = 159.5. 159.5 is
greater than the 150 maximum and is NOT acceptable.
Operating a machine with an unacceptable configuration will void the refrigeration system warranty.
hd
22.87"
rd
17.15"
Max 35’
Max 15’
Remote
Condenser
Located ABOVE
Ice Machine
Remote Condenser
Located BELOW Ice
Machine
dd
40.35"
Condenser Distance &
Location
Schematic
May 2001
Page 11
CME1356R and CME1656R
Coupling Instructions
The couplings on the ends of the pre-charged line sets are self-sealing when installed properly. Follow these instructions carefully.
These steps must be performed by an EPA Certified Type II or higher technician.
Initial Connections
1. Remove the protector caps and plugs. Wipe the seats and threaded surfaces with a clean cloth to remove any possible foreign matter.
2. Thoroughly lubricate the threads, o-rings, diaphragms and all internal coupling surfaces with polyolester refrigerant oil.
Clean and Lubricate Couplings
3. Position the fittings on the correct connections on the condenser and ice machine.
·
1
The
“ discharge line (schrader valve end)
2
goes to the remote condenser fitting marked “discharge line”.
3
·
The
“ liquid line (schrader valve end) goes to
8
the remote condenser fitting marked “liquid line”.
·
The “ discharge line goes to the ice maker fitting marked “discharge line”.
·
The “ liquid line goes to the ice maker fitting marked “liquid line”.
Final Connections:
4a. Begin to tighten the couplings together by hand. Continue to turn the swivel nuts by hand until it is certain that the threads are properly engaged.
4b. Using two wrenches, one to rotate the swivel nut and one to hold the tubing in place, tighten each coupling.
Tighten Swivel Nut
It is CRITICAL that ONLY the NUT on the pre-charged tube be turned, or the diaphragms will be torn by the piercing knives and become loose in the refrigeration system causing severe operational problems.
Note: As the coupling is tightened, the diaphragms in the quick connect couplings will begin to be pierced. As that happens, there will be increased resistance to tightening the swivel nut.
4c. Continue tightening the swivel nut until it bottoms out or a very definite increase in resistance is felt (no threads should be showing). Do NOT overtighten.
5. Use a marker or pen to mark a line on the coupling nut and unit panel. Then tighten the coupling nut an additional one-quarter turn. The line will show the amount that the nut turns.
Note: The system charge is contained in the receiver tank of the ice machine. Only “holding" charges are present in the “pre-charged" tubing or the condenser.
Rotate Swivel Nut ¼ Turn More
6. After all connections have been made, and after the liquid line valve has been opened (do not open yet), check the couplings for leaks.
May 2001
Page 12
Head Pressure Control Add-On Kit
CME1356R and CME1656R
Kit: RCKCME6GX
Required when a CME1656R or CME1356R is to be connected to a Remote Condenser that is not equipped with a Head Pressure Control Valve
Required Tools: Screwdriver; Drill; 5/32" drill bit; Two Adjustable Wrenches; POE Oil
1. Remove cover from metal box.
2. Locate correct position on condenser: The RCKCME6GX can fit either a Mac G series or a Mac X series condenser.
3. Use metal box as a template, mark the positions of 4 holes to be drilled to mount the box to the condenser.
4. Drill four .157" (#22 or 5/32" bit) dia. holes.
5. Remove plastic covers from the condenser’s quick connects and those to be used to connect to the condenser.
6. Thoroughly clean and lubricate the threads and diaphragms of both the condenser’s and the kit’s quick connects. Use Polyolester oil.
7. Mount the box to the condenser with the screws from the kit.
8. Start the swivel nuts by hand.
Use a back up wrench to be certain that the
·
tubing is NOT ROTATING. Only the SWIVEL NUTS should be rotating!
Then use an adjustable wrench to tighten them
·
until no threads are seen AND a very definite resistance is felt.
9. Mark the positions of the swivel nuts to the condenser panel.
10. Rotate the swivel nuts additional one-quarter turn.
11. Place cover on metal box & secure with screws.
12. Finish the balance of the installation. Ice machine’s precharged line sets will now connect to the quick connect fittings on the metal box instead of the condenser’s.
Connections to
Central Condenser
Central
RCKCME6GX
G series
Pre-Charged
Lines from
Ice Machine
X Series
May 2001
Page 13
CME1356R and CME1656R
Electrical
All models must be installed with the correct wire size and type per the National Electric Code. Locate the nameplate on the back of the cabinet and find the numbers for Voltage, Phase, Minimum Circuit Ampacity and Maximum Fuse Size. Either fuses or HACR type circuit breakers may be used.
The ice maker is designed to operate on its own electrical circuit and must be individually fused. Voltage variation must not exceed the limits listed on page 2.
The remote condenser is designed to be powered from the ice machine. A separate knockout hole has been provided in the ice maker electrical junction box.
Remote Condenser
Power Connection
Note: Central Condensers connected to more than one refrigeration system will likely have a wiring scheme to control the fan motor. Follow those directions for condenser wiring.
Electrical connections are made in the junction box in the back of the cabinet.
1. Remove the junction box cover.
2. Knock out both holes for a field supplied strain relief.
3. Install wires and strain reliefs per code. Note: Condenser fan motor wires are tagged.
4. Connect to wires and secure ground wire to ground screw inside junction box.
All external wiring should conform to the national, state and local electrical code requirements. Usually an electrical permit and the services of a licensed electrician will be required.
Interconnecting
Wire
Power Supply
May 2001
Page 14
Loading...
+ 31 hidden pages