This product manual contains the information
needed for the setup, installation, initial start up,
sanitation and maintenance of this ice machine.
Keep it for future reference.
There are 2 models covered in this manual:
• CME1356R, (5 evaporators)
• CME1656R, (6 evaporators)
TABLE OF CONTENTS
Specifications .................PAGE2
Condenser and Ice Machine Layouts .....PAGE3
Pre-Installation .................PAGE4
Location & Assembly .............PAGE5
Bin Control: Installation ............PAGE6
Bin Control ...................PAGE7
Be certain that the information applies to the model
in question. If no model is listed, the information
applies to all models.
This manual is organized in the same way as the
expected use of the machine, it begins with
specifications, goes thru unpacking and setup,
shows where everything is; continues with initial
start up, then describes how it works. After that is
the sanitation section, followed by service diagnosis
and repair.
Sanitation and Cleaning ........... PAGE 26
Additional Maintenance ........... PAGE 27
Additional Maintenance: Water Distributors . PAGE 28
Both of these ice machines are designed to be
installed indoors, in a controlled environment.
They can operate satisfactorily under a wide
variety of conditions. However, Do NOT operate
the machine in temperatures it has not been
designed for. Do NOT operate the machine above
or below the voltage limits for the particular model.
Do NOT operate the machine with too little or too
much water pressure.
Operational Limits
MinimumMaximum
Air Temperature50
Water Temperature40oF.100oF.
Water Pressure20 psi80 psi
Voltage (60 Hz)197253
Voltage (50 Hz)207253
Scotsman reserves the right to make design
changes and/or improvements at any time.
Specifications and designs are subject to change
without notice.
o
F.100oF.
Voltage note: The control system transformer in
the control box of this ice machine has two primary
taps, one for 208 volt power and one for 240 volt
power. The machine ships with the power supply
connected to the 208 volt tap. Change to the 240
volt tap when the voltage supplied to the unit is
greater than 229 volts.
Bins:
All models will fit a standard, 48" wide or wider
open top Scotsman Ice Storage Bin. Examples
include BH900, BH1100, BH1300, BH1600
In addition, there may be other bins that can be
used, check Scotsman’s sales literature for
application information.
Note: Slope-front bins must have an internal baffle.
Scotsman’s BH900 has the required baffle. Baffle
must be approximately in the position shown in the
diagram below.
Baffle
Scotsman assumes no liability or responsibility of
12.0"
any kind for products manufactured by Scotsman
that have been altered in any way, including the
4.0"
use of any parts and/or other components not
specifically approved by Scotsman.
BASIC INFORMATION
Dimensions
Model Number
CME1356RS-32F48 ½ “ x 24" x 28208-230/60/1ECR411-32A288 oz24.930
* The remote condenser is designed to work in temperatures from -20oF. to 120oF.
Maximum
Fuse Size
Use precharged tubing kits, RTE25 (25’) or RTE40 (40’) or RTE75 (75’). Select the length closest to the
needs of the particular installation.
The stacking kit required to place two like model cubers together is: KSCME6-LG-B. The kit required to
connect this ice machine to a central condenser is: RCKCME6-GX
November 2004
Page 2
Condenser and Ice Machine Layouts
2
.88 DIA. ELECTRICAL
INLET
DISCHARGE LINE
1/2" MALE CPLG.
CME1356R and CME1656R
29.50 in
74.9 cm
ERC411
.562 DIA.
MOUNTING
HOLES (4)
6.00 in
15.2 cm
CONDENSER FINS
23.54 in
59.7 cm
29.15 in
74.0 cm
MINIMUM FOR
UTILITY CONNECTIONS
2.75
38.47 in
97.7 cm
32.32 in
35.72 in
90.7 cm
15-0782-01CANCAUSEINJURYOR DEATH:DISCONNECT ALL REMOTE ELECTRICPOWERSUPPLIESBEFORESERVICING.RISKOFELECTRICSHOCK^MWARNING
2.84 in
7.2 cm
82.1 cm
28.07 in
71.2 cm
7.60 in
19.3 cm
6.10in
66.3 cm
MINIMUM BIN
TOP OPENING
24.71 in
62.7 cm
11.50 in
29.2 cm
14.56 in
36.9 cm
27.56 in
70.0 cm
29.19 in
74.1 cm
.65 in
1.7 cm
LIQUID LINE
3/8" MALE CPLG.
AIR FLOW
PLAN VIEW
18.75 in
47.6 cm
ICE
OPENING
6.00 in
15.2 cm
MINIMUM FOR
AIR VENTILATION
REMOTE CONDENSER
LIQUID LINE
3/8" MALE CPLG.
23.30 in
59.2 cm
22.65 in
57.5 cm
BACK VIEW
DUMP
VALVE
DRAIN
3/4" F.P.T.
REMOTE CONDENSER
DISCHARGE LINE
1/2" MALE CPLG.
WATER INLET
3/8" FLARE
May 2001
4.20 in
10.7 cm
ICE
OPENING
18.67 in
47.4 cm
Page 3
.88 DIA. KNOCKOUT
ELECTRICAL INLET
15.77 in
40.1 cm
21.77 in
55.3 cm
10.15 in
25.8 cm
2.50 in
6.4 cm
5.87 in
14.9 cm
17.87 in
45.4 cm
2.46 in
6.2 cm
3.81 in
9.7 cm
.88 DIA. KNOCKOUT
REMOTE CONDENSER FAN
23.87 in
60.6 cm
CME1356R and CME1656R
Pre-Installation
Other Applications:
Check sales literature for additional information.
Electrical:
Check the nameplate for electrical requirements.
The nameplate is located on the back of the ice
machine. If the information on the nameplate is
different from other published information, go by
the nameplate data.
While the model and
serial number are on
the nameplate, a
serial number plate is
located at the front of
the machine, behind
the left front panel
and to the right of the
purge valve.
Nameplate
Serial Number Plate
Water:
There is no such thing as pure water. All water
contains some impurities. There are two ways
water carries the impurities: suspended and
dissolved. Suspended solids can be filtered out.
Dissolved solids must be diluted or treated. Water
filters are recommended to remove suspended
solids. Some filters have treatment in them for
suspended solids. Check with a water treatment
service for a recommendation.
Cube Ice machines use more water than what
ends up in the bin as ice. While most water is used
during ice making, a portion is designed to “rinse"
out the water system to keep hard water scale
from clogging up the machine. That water rinse,
combined with water filters, prolongs the times
between needed water system cleaning.
Service Technicians: All models covered here
come set from the factory with at a “Standard”
water rinse. Standard water rinse is designed to be
compatible with typical water conditions. The
machine may be adjusted to a different water rinse
after start up. If the prior ice machine worked
acceptably well with the local water conditions,
leave the machine at the factory setting. If severe
water conditions are present, and water filters do
not solve the problem acceptably, adjust the
machine to use more water. If water conditions are
excellent, adjust the machine to use less water.
See the Adjustments section.
Note: Water use adjustments are customer
convenience adjustments; they are NOT factory
defects and are NOT covered by warranty.
May 2001
Page 4
Location & Assembly
CME1356R and CME1656R
Locate the ice machine indoors. A 6 inch minimum
clearance on the back and left sides is required for
the proper operation and service of this machine.
Locate the remote condenser as close as possible
to the ice machine. See page 11 for details.
Unpacking and Assembly:
Begin with unpacking the ice storage bin. Remove
the carton, and using part of the carton as a
cushion, tip the bin on its back to remove the skid
and attach the legs or casters. Note: Stacked
applications may not use casters.
Return the bin to an upright position. Check the bin
top gasket for gaps and tears, fill any in with food
grade sealant prior to placing the ice machine on
the bin.
Note: If recycling a prior bin, be sure that the bin
top gasket is in good condition or seal the ice
machine to the bin with food grade sealant.
Level the top edge of the bin front to back and left
to right.
If the ice machine has not been unpacked, do so
now. Remove the carton from the skid. Remove
shipping straps.
Remove the front panels and all packaging
materials.
After all packing materials have been removed
from the ice machine, lift or hoist the machine onto
the bin. Align the sides and back of the machine
with the sides and back of the bin.
Secure the ice machine to the bin with the two
metal straps and 4 bolts provided.
Cabinet Panel Removal:
1. Remove the front panel by removing the two
screws connecting the front panel to the machine.
2. Lift up at the front edge and push the top panel
back until it releases from the tabs connecting it to
the back panel.
3. Remove two screws at the front of each side
panel, and pull them forward until they release
from the tabs connecting them to the back panel.
Evaporator Cover:
To Remove
Evaporator Cover:
Push Up and Tilt Out
May 2001
Page 5
CME1356R and CME1656R
Bin Control: Installation
The bin control is a thermostat. It must be field
installed after the ice machine has been placed on
the bin.
Before starting, remove the left front panel and any
baffle in the bin.
1. Locate bin thermostat bulb.
2. Route bulb thru routing tube (located between
the compressor and the reservoir).
3. Locate bin thermostat bracket.
4. Carefully position the thermostat bulb on the
bracket (see the diagram on the next page).
5. Fasten the bracket to the bottom of the ice
machine with the two 3-pronged knobs supplied
with the unit.
6. Pull back into the ice machine any excess
capillary tubing.
7. Return the baffle to the bin and continue with
the installation.
Note: If the machine is located at an altitude higher
than 2,000 ft., adjust the thermostat by removing
the plastic cover and rotating the adjustment screw
per the table.
Thermostat Bulb Routing Tube
Bin Thermostat Altitude Correction Table
CW Turns of Range Screw (under plastic cover)
FeetTurnsFeetTurns
200055
4000160
6000250
o
o
o
8000340
9000385
10000405
o
o
o
Use This Table to Adjust Thermostat
Bin
Thermostat
Body
Thermostat Bulb
Routing Tube
Bin Thermostat Bulb
Route Bin Thermostat Bulb Into Bin
May 2001
Page 6
Bin Control
Bin Thermostat
Bracket
Mount Bulb
Tip Here
CME1356R and CME1656R
Bin Thermostat
Capillary Tube
Mount Thermostat
Capillary Tube Here
Attach Thermostat Bulb to Bracket
Minimize Excess
Tube in Bin
Three-Pronged Knob
Thermostat and
Bracket
Attach Bracket to Bottom of Ice Machine
May 2001
Page 7
CME1356R and CME1656R
Stacking - Kit KSCME6-LG-B
Only like models may be stacked. Begin after the
bottom unit has been placed on the ice storage bin
and secured. Stacking requires heavy duty leg kits.
Casters are NOT recommended.
Note: Instructions are for either model.
Bottom Machine:
1. Remove front panel, left side panel, and top
panel.
2. Remove & discard top cover from over the
freezing compartment.
3. Install gasket materials to freezing
compartment:
Cut about 22" of gasket material from the roll in the
kit. Apply it to the back side top edge of the
freezing compartment.
Cut two lengths of gasket material to fit the right
side top edge of the freezing compartment and
apply them.
4. Place a bead of food grade sealant to the top of
the back wall’s gasket.
5. Place the shield bracket (has a large hole in the
center) from the kit over the center of the freezing
compartment.
Insert the tabs of the bracket into slots on the back
of the unit.
6. Secure bracket at the front with screws from the
kit.
7. Hang the plastic shields from the bracket
installed in the prior step. Use the slots in the
shields to hang them from the stainless steel
hooks.
Note: The notch in the bottom of the shield goes to
the front.
Note: The tabs on the shields must fit inside the
ice outlet port.
8. Check the position of the shields. They must
move freely and be vertical.
Note: The suction line may need to be moved
slightly so the tubing clears the bracket & shields.
9. Place a bead of food grade sealant onto the top
left edge of the freezing compartment.
10. Install the front-to-back support bracket over
the left edge of the freezing compartment.
11. Remove two existing screws and secure the
bracket to the: freezing compartment, back panel
and front channel with the 2 existing screws and 1
large and 4 small screws from the kit.
Both Machines:
12. Place the top ice machine onto the bottom one.
Secure together with hardware from the top
machine. Remove left front and left side panels.
13. At the back of the ice machines, on the
compressor end, remove the upper knock-out from
the bottom machine and the lower knock out from
the upper machine.
14. Place a strain relief (from the kit) into each
hole.
15. Insert wire harness from kit thru strain-relief
and hole in upper corner of the lower ice
machine’s back panel.
NOTE: Harness is marked which end goes to
which machine.
Bottom Machine:
16. Remove harness from controller terminal 7 and
bin thermostat.
17. Route wire harness in lower ice machine to the
controller. Connect to terminal #7. Plug the two
free wires onto the thermostat terminals #1 and #2.
18. Return left side panel to its original position on
the lower ice machine.
Top Machine:
19. Remove harness from controller terminal 7.
20. Route wire harness thru upper unit’s lower
knock-out hole and strain relief and continue
internally to the controller. Plug wire onto terminal
7 of the controller.
21. Return all panels and covers to their normal
positions.
22. Complete the balance of the installation.
Service Notes:
A. The shields must be positioned so they hang
vertically and move freely left to right. Their
purpose is to guide the ice past the bottom
machine’s evaporators and into its cube port.
B. The drain lines from each ice machine must be
kept separate.
May 2001
Page 8
Stacking
CME1356R and CME1656R
Gasket on
Plastic Walls of
Lower Unit
Gasket for Metal
Edges of Bottom
Unit
Front-to-Back
Support Bracket
Mounting Straps
and Hardware
Shield Hanger
Bracket
Shield
May 2001
Page 9
CME1356R and CME1656R
For The Installer: Remote Condenser
Locate the condenser as near as possible to the
interior location of the ice maker.
Note: The location of the condenser relative to the
ice machine is LIMITED by the specification on the
following page.
Select the best available location, one that protects
the condenser from extremes of dust, grease and
sun.
Meet all applicable building codes.
Roof Attachment
Install and attach the remote condenser to the roof
of the building, using the methods and practices of
construction that conform to the local building
codes, including having a roofing contractor secure
the condenser to the roof.
Note: If using any other condenser besides the
ERC411, its use must be approved by
Scotsman, and a head pressure control
valve must be connected to the
condenser coil. The head pressure
valve kit number is: RCKCME6
Precharged Line Routing
Do not connect the precharged tubing
until all routing and forming of the tubing
is complete. See the Coupling
Instructions for final connections.
1. Each set of pre-charged tubing lines contains a
3
“ diameter liquid line, and a
8
1
” diameter
2
discharge line. Both ends of each line have quick
connect couplings, the end without access valves
goes to the ice maker.
Note: The openings in the building ceiling or wall,
listed in the next step, are the minimum sizes
recommended for passing the refrigerant lines
through.
2. Have the roofing contractor cut a minimum hole
for the refrigerant lines of 2“. Check local codes, a
separate hole may be required for the electrical
power supply to the condenser.
Caution: Do NOT kink the refrigerant tubing while
routing it.
3. Route the refrigerant tubes thru the roof
opening. Follow straight line routing whenever
possible.
Note: Excess tubing may EITHER be coiled up
INSIDE the building OR cut out prior to connection
to the ice maker and condenser.
If the excess tubing is cut out, after re-brazing the
tubing must be evacuated prior to connection to
the ice maker or condenser.
If the excess tubing is to be coiled, spiral it
horizontally to avoid excess trapping in the lines.
Note: A 36" service loop may be placed behind the
ice machine.
5. Have the roofing contractor seal the holes in the
roof per local codes.
ERC411 Remote
Condenser
Electrical
Power Supply
Coil Excess
Tubing
Horizontally
Within the
Building
Typical Installation
May 2001
Page 10
Remote Condenser Location
CME1356R and CME1656R
Use the following for planning the placement of the
condenser relative to the ice machine
Location Limits - condenser location must not
exceed ANY of the following limits:
Maximum rise from the ice machine to the
·
condenser is 35 physical feet
Maximum drop from the ice machine to the
·
condenser is 15 physical feet
Physical line set maximum length is 100 feet.
·
Calculated line set length maximum is 150.
·
Calculation Formula:
Drop = dd x 6.6 (dd = distance in feet)
·
Rise = rd x 1.7 (rd = distance in feet)
·
Horizontal Run = hd x 1 (hd = distance in feet)
·
Calculation: Drop(s) + Rise(s) + Horizontal Run
·
= dd+rd+hd = Calculated Line Length
Configurations that do NOT meet these
requirements must receive prior written
authorization from Scotsman.
Do NOT:
Route a line set that rises, then falls, then rises.
·
Route a line set that falls, then rises, then falls.
·
Calculation Example 1:
The condenser is to be located 5 feet below the ice
machine and then 20 feet away horizontally.
5 feet x 6.6 = 33. 33 + 20 = 53. This location would
be acceptable
Calculation Example 2:
The condenser is to be located 35 feet above and
then 100 feet away horizontally.
35 x 1.7 = 59.5. 59.5 +100 = 159.5. 159.5 is
greater than the 150 maximum and is NOT
acceptable.
Operating a machine with an unacceptable
configuration will void the refrigeration system
warranty.
hd
22.87"
rd
17.15"
Max 35’
Max 15’
Remote
Condenser
Located ABOVE
Ice Machine
Remote Condenser
Located BELOW Ice
Machine
dd
40.35"
Condenser
Distance &
Location
Schematic
May 2001
Page 11
CME1356R and CME1656R
Coupling Instructions
The couplings on the ends of the pre-charged line
sets are self-sealing when installed properly.
Follow these instructions carefully.
These steps must be performed by an EPA
Certified Type II or higher technician.
Initial Connections
1. Remove the protector caps and plugs. Wipe the
seats and threaded surfaces with a clean cloth to
remove any possible foreign matter.
2. Thoroughly lubricate the threads, o-rings,
diaphragms and all internal coupling surfaces with
polyolester refrigerant oil.
Clean and Lubricate Couplings
3. Position the fittings on the correct connections
on the condenser and ice machine.
·
1
The
“ discharge line (schrader valve end)
2
goes to the remote condenser fitting marked
“discharge line”.
3
·
The
“ liquid line (schrader valve end) goes to
8
the remote condenser fitting marked “liquid
line”.
·
The “ discharge line goes to the ice maker
fitting marked “discharge line”.
·
The “ liquid line goes to the ice maker fitting
marked “liquid line”.
Final Connections:
4a. Begin to tighten the couplings together by
hand. Continue to turn the swivel nuts by hand
until it is certain that the threads are properly
engaged.
4b. Using two wrenches, one to rotate the swivel
nut and one to hold the tubing in place, tighten
each coupling.
Tighten Swivel Nut
It is CRITICAL that ONLY the NUT on the
pre-charged tube be turned, or the diaphragms will
be torn by the piercing knives and become loose in
the refrigeration system causing severe
operational problems.
Note: As the coupling is tightened, the diaphragms
in the quick connect couplings will begin to be
pierced. As that happens, there will be increased
resistance to tightening the swivel nut.
4c. Continue tightening the swivel nut until it
bottoms out or a very definite increase in
resistance is felt (no threads should be showing).
Do NOT overtighten.
5. Use a marker or pen to mark a line on the
coupling nut and unit panel. Then tighten the
coupling nut an additional one-quarter turn. The
line will show the amount that the nut turns.
Note: The system charge is contained in the
receiver tank of the ice machine. Only
“holding" charges are present in the
“pre-charged" tubing or the condenser.
Rotate Swivel Nut ¼ Turn More
6. After all connections have been made, and after
the liquid line valve has been opened (do not open
yet), check the couplings for leaks.
May 2001
Page 12
Head Pressure Control Add-On Kit
CME1356R and CME1656R
Kit: RCKCME6GX
Required when a CME1656R or CME1356R is to
be connected to a Remote Condenser that is not
equipped with a Head Pressure Control Valve
2. Locate correct position on condenser: The
RCKCME6GX can fit either a Mac G series or a
Mac X series condenser.
3. Use metal box as a template, mark the positions
of 4 holes to be drilled to mount the box to the
condenser.
4. Drill four .157" (#22 or 5/32" bit) dia. holes.
5. Remove plastic covers from the condenser’s
quick connects and those to be used to connect to
the condenser.
6. Thoroughly clean and lubricate the threads and
diaphragms of both the condenser’s and the kit’s
quick connects. Use Polyolester oil.
7. Mount the box to the condenser with the screws
from the kit.
8. Start the swivel nuts by hand.
Use a back up wrench to be certain that the
·
tubing is NOT ROTATING. Only the SWIVEL
NUTS should be rotating!
Then use an adjustable wrench to tighten them
·
until no threads are seen AND a very definite
resistance is felt.
9. Mark the positions of the swivel nuts to the
condenser panel.
10. Rotate the swivel nuts additional one-quarter
turn.
11. Place cover on metal box & secure with screws.
12. Finish the balance of the installation. Ice
machine’s precharged line sets will now connect to
the quick connect fittings on the metal box instead
of the condenser’s.
Connections to
Central Condenser
Central
RCKCME6GX
G series
Pre-Charged
Lines from
Ice Machine
X Series
May 2001
Page 13
CME1356R and CME1656R
Electrical
All models must be installed with the correct wire
size and type per the National Electric Code.
Locate the nameplate on the back of the cabinet
and find the numbers for Voltage, Phase, Minimum
Circuit Ampacity and Maximum Fuse Size. Either
fuses or HACR type circuit breakers may be used.
The ice maker is designed to operate on its own
electrical circuit and must be individually fused.
Voltage variation must not exceed the limits listed
on page 2.
The remote condenser is designed to be powered
from the ice machine. A separate knockout hole
has been provided in the ice maker electrical
junction box.
Remote Condenser
Power Connection
Note: Central Condensers connected to more than
one refrigeration system will likely have a wiring
scheme to control the fan motor. Follow those
directions for condenser wiring.
Electrical connections are made in the junction box
in the back of the cabinet.
1. Remove the junction box cover.
2. Knock out both holes for a field supplied strain
relief.
3. Install wires and strain reliefs per code. Note:
Condenser fan motor wires are tagged.
4. Connect to wires and secure ground wire to
ground screw inside junction box.
All external wiring should conform to the national,
state and local electrical code requirements.
Usually an electrical permit and the services of a
licensed electrician will be required.
Interconnecting
Wire
Power Supply
May 2001
Page 14
Loading...
+ 31 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.