Scotsman CME1056R User Manual

Introduction
CME1056R
This product manual contains the information needed for the setup, installation, initial start up, sanitation and maintenance of this ice machine. Keep it for future reference.
Be certain that the information applies to the model in question. If no model is listed, the information applies to all models.
TABLE OF CONTENTS
Specifications ,,,,,,,,,,,,,PAGE2
Condenser and Ice Machine Layouts , PAGE 3
Pre-Installation ,,,,,,,,,,,,,PAGE4
Location & Assembly ,,,,,,,,,PAGE5
Stacking ,,,,,,,,,,,,,,,,PAGE6
Stacking ,,,,,,,,,,,,,,,,PAGE7
Bin Control: Installation ,,,,,,,,PAGE8
For The Installer: Remote Condenser , PAGE 9
Technicians Only: Harvest Cycle Sequence & Other Notes ,,,,,,,,,,,,,,PAGE24
Sanitation and Cleaning ,,,,,,,,PAGE25
Additional Maintenance ,,,,,,,,PAGE26
Additional Maintenance: Inlet Water Valve Screen
,,,,,,,,,,,,,,,,,,,,,PAGE27
Additional Maintenance: Ice Sensors, Condenser
,,,,,,,,,,,,,,,,,,,,,PAGE28
Service Diagnosis: Diagnostic Light Analysis
,,,,,,,,,,,,,,,,,,,,,PAGE29
Remote Condenser Location ,,,,,PAGE10
Coupling Instructions ,,,,,,,,,PAGE11
Head Pressure Control Add-On Kit , , PAGE 12
Electrical ,,,,,,,,,,,,,,,,PAGE13
Plumbing ,,,,,,,,,,,,,,,,PAGE14
After Utility Connections ,,,,,,,,PAGE15
Component Location and Function , , PAGE 16
AutoIQ Controller ,,,,,,,,,,,PAGE17
Initial Start Up ,,,,,,,,,,,,,PAGE18
Adjustments ,,,,,,,,,,,,,,PAGE19
How To Operate The AutoIQ Controller PAGE 20
How The Electronic Cuber Works , , , PAGE 21
How The Electronic Cuber Works , , , PAGE 22
Technicians Only: Freeze Cycle Sequence
,,,,,,,,,,,,,,,,,,,,,PAGE23
Service Diagnosis ,,,,,,,,,,,PAGE30
Service Diagnosis: Components,,,,PAGE31
Service Diagnosis ,,,,,,,,,,,PAGE32
PTCR Diagnosis ,,,,,,,,,,,,PAGE33
Operational Characteristics: CME1056R
,,,,,,,,,,,,,,,,,,,,,PAGE34
Removal and Replacement ,,,,,,PAGE35
Removal and Replacement ,,,,,,PAGE36
Removal and Replacement: AutoIQ Controller
,,,,,,,,,,,,,,,,,,,,,PAGE37
Removal and Replacement: Water Level Sensor
,,,,,,,,,,,,,,,,,,,,,PAGE38
Removal and Replacement ,,,,,,PAGE39
Refrigerant ,,,,,,,,,,,,,,,PAGE40
Before Calling for Service ,,,,,,,PAGE41
Parts Lists and Wiring Diagrams are in the section at the center of this manual.
May 2000
Page 1
CME1056R
Specifications
Both of these ice machines are designed to be installed indoors, in a controlled environment. They can operate satisfactorily under a wide variety of conditions. However, Do NOT operate the machine in temperatures it has not been designed for. Do NOT operate the machine above or below the voltage limits for the particular model. Do NOT operate the machine with too little or too much water pressure.
Operational Limits
Minimum Maximum
Air Temperature 50oF. 100oF.
Water Temperature 40oF. 100oF.
Water Pressure 20 psi 80 psi
Voltage (60 Hz) 197 253
Voltage (50 Hz) 207 253
Scotsman reserves the right to make design changes and/or improvements at any time. Specifications and designs are subject to change without notice.
Scotsman assumes no liability or responsibility of any kind for products manufactured by Scotsman that have been altered in any way, including the use of any parts and/or other components not specifically approved by Scotsman.
Bins:
All models will fit a standard, 30" wide or wider open top Scotsman Ice Storage Bin. Some examples are:
BH550
HTB555
Dispensers
ID200 or ID250, use adapter KBT44
Lancer 30” wide dispenser. Add adapter kit
KSTAT-MD.
Kits
BH800 bin: Add kits KBT23
BH900 bin: Add kits KBT22
In addition, there may be other bins and dispensers that can be used, check Scotsman’s sales literature for application information.
Stacking
Stacking two CME1056s together requires
use of stacking kit KSCME6-MD
Precharged Tubing:
25’ RTE25
40’ RTE40
75’ RTE75
Headmaster Kit:
The kit required to connect this ice machine to an approved central condenser is:
RCKCME6GX.
BASIC INFORMATION
Dimensions
Model Number
CME1056RS-32D 30½“x24"x28 208-230/60/1 ECR311-32A 208 oz 17.25 20
CME1056RS-3D same 208-230/60/3 ECR311-32A 208 oz 12.13 15
CME1056RS-6D same 230/50/1 ERC311-32A 208 oz
WxDxH (w/o bin)
Basic Electrical (volts/Hz/phase)
Use Condenser
* The remote condenser is designed to work in temperatures from -20oF. to 120oF.
Use precharged tubing kits, RTE25 (25’) or RTE40 (40’) or RTE75 (75’). Select the length closest to the needs of the particular installation.
March 2003
Page 2
Refrigerant Charge R-404A
Minimum Circuit Ampacity
Maximum Fuse Size
Condenser and Ice Machine Layouts
.88 DIA. ELECTRICAL INLET
DISCHARGE LINE 1/2" MALE CPLG.
29.50 in
74.9 cm
CME1056R
ERC311
.562 DIA. MOUNTING HOLES (4)
CONDENSER FINS
15-0782-01CANCAUSEINJURYOR DEATH:DISCONNECT ALL REMOTE ELECTRICPOWERSUPPLIESBEFORESERVICING.RISKOFELECTRICSHOCK^MWARNING
23.54 in
59.7 cm
29.15 in
74.0 cm
2.75
35.72 in
90.7 cm
2.84 in
7.2 cm
6.00 in
15.2 cm
38.47 in
97.7 cm
32.32 in
82.1 cm
28.07 in
71.2 cm
7.60 in
19.3 cm
MINIMUM FOR
UTILITY CONNECTIONS
24.71 in
62.7 cm
11.50 in
29.2 cm
14.56 in
36.9 cm
27.56 in
70.0 cm
29.19 in
74.1 cm
PLAN VIEW
.65 in
1.7 cm
LIQUID LINE 3/8" MALE CPLG.
AIR FLOW
2.70 in
6.9 cm
ICE
OPENING
REMOTE CONDENSER LIQUID LINE 3/8" MALE CPLG.
REMOTE CONDENSER DISCHARGE LINE 1/2" MALE CPLG.
21.75 in
55.2 cm
19.90 in
22.15 in
56.3 cm
50.5 cm
15.75 in
40.0 cm
SUMP DRAIN 3/4" F.P.T.
BACK VIEW
.88 DIA. KNOCKOUT ELECTRICAL INLET
20.12 in
51.1 cm
22.25 in
56.5 cm
10.75 in
27.3 cm
May 2000
Page 3
.88 DIA. KNOCKOUT REMOTE CONDENSER FAN
WATER INLET 3/8" FLARE
17.68 in
44.9 cm
4.31 in.
10.9 cm
2.38 in
6.0 cm
4.75 in
12.1 cm
18.70 in
47.5 cm
ICE
OPENING
SIDE VIEW
24.00 in
61.0 cm
9.85 in
25.0 cm
1.63 in
4.1 cm
CME1056R
Pre-Installation
Other Applications:
Check sales literature for additional information.
Note: Slope-front bins must have an internal baffle. Scotsman HTB555 and BH550 have the required baffle. Baffle must be approximately in the position shown in the diagram below.
Baffle
12.0"
4.0"
Side View
Electrical:
Check the nameplate for electrical requirements. The nameplate is located on the back of the ice machine. If the information on the nameplate is different from other published information, go by the nameplate data.
While the model and serial number are on the nameplate, a
serial number plate is located at the front of the machine, behind the front panel and to the right
of the purge valve.
Water:
There is no such thing as pure water. All water contains some impurities. There are two ways water carries the impurities: suspended and dissolved. Suspended solids can be filtered out. Dissolved solids must be diluted or treated. Water filters are recommended to remove suspended solids. Some filters also have treatment in them for dissolved solids. Check with a water treatment service for a recommendation.
Cube Ice machines use more water than what ends up in the bin as ice. While most water is used during ice making, a portion is designed to “rinse" out the water system to keep hard water scale from clogging up the machine. That water rinse, combined with water filters, prolongs the times between needed water system cleaning.
Service Technicians: All models covered here come set from the factory with at a “Standard” water rinse. Standard water rinse is designed to be compatible with typical water conditions. The machine may be adjusted to a different water rinse after start up. If the prior ice machine worked acceptably well with the local water conditions, leave the machine at the factory setting. If severe water conditions are present, and water filters do not solve the problem acceptably, adjust the machine to use more water. If water conditions are excellent, adjust the machine to use less water. See the Adjustments section.
Note: Water use adjustments are customer convenience adjustments; they are NOT factory defects and are NOT covered by warranty.
Nameplate, on back panel
Serial Number Plate, remove front
panel to locate.
May 2000
Page 4
Location & Assembly
CME1056R
Locate the ice machine indoors. A 6 inch minimum clearance on the back and sides is required for the proper operation and service of this machine.
Locate the remote condenser as close as possible to the ice machine. See page 11 for details.
Unpacking and Assembly:
Begin with unpacking the ice storage bin. Remove the carton, and using part of the carton as a cushion, tip the bin on its back to remove the skid and attach the legs or casters. Note: Stacked
applications may not use casters.
Return the bin to an upright position. Check the bin top gasket for gaps and tears, fill any in with food grade sealant prior to placing the ice machine on the bin.
Note: If recycling a prior bin, be sure that the bin top gasket is in good condition or seal the ice machine to the bin with food grade sealant.
Level the top edge of the bin front to back and left to right.
Cabinet Panel Removal:
1. Remove the front panel by removing the two screws connecting the top of the front panel to the machine, then pull out at the bottom.
2. Lift up at the front edge and push the top panel back until it releases from the tabs connecting it to the back panel.
If the ice machine has not been unpacked, do so now. Remove the carton from the skid. Remove shipping straps.
Remove the front panels and all packaging materials.
After all packing materials have been removed from the ice machine, lift or hoist the machine onto the bin. Align the sides and back of the machine with the sides and back of the bin.
Secure the ice machine to the bin with the two metal straps and 4 bolts provided.
3. Remove two screws at the front of each side panel, and pull them forward until they release from the tabs connecting them to the back panel.
May 2000
Page 5
CME1056R
Stacking
Only like models may be stacked. Begin after the bottom unit has been placed on the ice storage bin and secured. Stacking requires heavy duty leg kits. Casters are NOT recommended.
Bottom Machine:
1. Remove front, side, and top panels.
2. Hang the plastic shield from the tabs on the stainless steel bracket.
3. Locate the two notches on the sides of the top edge of the freezing compartment.
Bracket
Mounting
Notch
11. Route the Stacking Kit wire harness from the back to the top and bottom machines thru the holes made in steps 8 and 9.
The harness is marked which end goes to which machine.
Push the strain reliefs into place from the back of the machines.
Follow local codes for 24 volt wire
4. Place the bracket over the notches of the freezing compartment.
5. Secure bracket to freezing compartment with screws from the kit (from the sides).
6. Locate gasket material in kit. Place a layer of gasket material on the top edge of the plastic freezing compartment.
7. Place the top ice machine onto the bottom one. Secure together with hardware from the top machine. Remove front and left side panels.
Upper Machine:
8. Knock out 1 hole in the lower left (viewed from the front) corner of the upper unit’s back panel.
Lower Unit:
9. Knock out 1 hole in the upper left (viewed from the front) corner of the lower unit’s back panel.
10. Position the strain reliefs over the wrapped portion of the stacking kit wire harness.
Bin Thermostat Mounted in
Machine
12. Route wire harness in lower ice machine to the controller. Connect to terminal #7. Plug the two free wires onto thermostat terminals #1 and #2
December 1998
Page 6
Stacking
CME1056R
13. Route the wire to the controller. Connect to terminal 7.
Thermostat
Routing
Hole
Thermostat
Bulb
Bottom Machine
14. Route the bulb of the thermostat thru the base of the unit into the bin.
15. Mount the bulb of the thermostat to the bracket from the kit.
16. Install the bin thermostat bracket onto the bottom of the machine.
17. Pull back excess cap tube and coil up in the machine.
18. Connect wires from harness to thermostat terminals.
Both Machines:
19. Return all panels and covers to their normal positions.
20. Complete the balance of the installation.
Thermostat &
Bracket
Mounted to
Ice Machine
Base
May 2000
Page 7
CME1056R
Bin Control: Installation
The bin control is a thermostat. It must be field installed after the ice machine has been placed on the bin.
Before starting, remove the front panel and any baffle in the bin.
1. Locate bin thermostat bulb.
3. Route bulb thru routing tube (located between the compressor and the reservoir).
6. Fasten the bracket to the bottom of the ice machine with the two 3-pronged knobs supplied with the unit.
7. Pull back into the ice machine any excess capillary tubing.
8. Return the baffle to the bin and continue with the installation.
Note: If the machine is located at an altitude higher than 2,000 ft., adjust the thermostat by removing the plastic cover and rotating the adjustment screw per the table.
4. Locate bin thermostat bracket.
5. Carefully position the thermostat bulb on the bracket.
Bin Thermostat Altitude Correction Table
CW Turns of Range Screw (under plastic cover)
Feet Turns Feet Turns
2000 55
4000 160
6000 250
o
o
o
8000 340
9000 385
10000 405
o
o
o
Use This Table to Adjust Thermostat
May 2000
Page 8
For The Installer: Remote Condenser
CME1056R
Locate the condenser as near as possible to the interior location of the ice maker.
Note: The location of the condenser relative to the ice machine is LIMITED by the specification on the following page.
Select the best available location, one that protects the condenser from extremes of dust, grease and sun.
Meet all applicable building codes.
Roof Attachment
Install and attach the remote condenser to the roof of the building, using the methods and practices of construction that conform to the local building codes, including having a roofing contractor secure the condenser to the roof.
Note: If using any other condenser besides the ERC311, its use must be approved by Scotsman, and a head pressure control valve must be connected to the condenser coil. The head pressure valve kit number is: RCKCME6
Precharged Line Routing
Do not connect the precharged tubing until all routing and forming of the tubing is complete. See the Coupling Instructions for final connections.
Note: Excess tubing may EITHER be coiled up INSIDE the building OR cut out prior to connection to the ice maker and condenser.
If the excess tubing is cut out, after re-brazing the tubing must be evacuated prior to connection to the ice maker or condenser.
If the excess tubing is to be coiled, spiral it horizontally to avoid excess trapping in the lines.
Note: A 36" service loop may be placed behind the ice machine.
5. Have the roofing contractor seal the holes in the
roof per local codes.
ERC311 Remote
Condenser
Electrical Power
Supply
Coil Excess
Tubing
Horizontally
Within the
Building
1. Each set of pre-charged tubing lines contains a
1
” diameter discharge line. Both ends of
2
3
“ diameter liquid line, and a
8
each line have quick connect couplings, the end without access valves goes to the ice maker.
Note: The openings in the building ceiling or wall, listed in the next step, are the minimum sizes recommended for passing the refrigerant lines through.
2. Have the roofing contractor cut a minimum hole for the refrigerant lines of 2“. Check local codes, a separate hole may be required for the electrical power supply to the condenser.
Caution: Do NOT kink the refrigerant tubing while routing it.
3. Route the refrigerant tubes thru the roof opening. Follow straight line routing whenever possible.
Typical Installation
May 2000
Page 9
CME1056R
Remote Condenser Location
Use the following for planning the placement of the condenser relative to the ice machine
Location Limits - condenser location must not exceed ANY of the following limits:
Maximum rise from the ice machine to the
condenser is 35 physical feet Maximum drop from the ice machine to the
condenser is 15 physical feet Physical line set maximum length is 100
feet. Calculated line set length maximum is 150.
Calculation Formula:
Drop = dd x 6.6 (dd = distance in feet)
Rise = rd x 1.7 (rd = distance in feet)
Horizontal Run = hd x 1 (hd = distance in
feet) Calculation: Drop(s) + Rise(s) + Horizontal
Run = dd+rd+hd = Calculated Line Length
Configurations that do NOT meet these requirements must receive prior written authorization from Scotsman.
Do NOT:
Route a line set that rises, then falls, then
rises. Route a line set that falls, then rises, then
falls.
Calculation Example 1:
The condenser is to be located 5 feet below the ice machine and then 20 feet away horizontally.
5 feet x 6.6 = 33. 33 + 20 = 53. This location would
be acceptable
Calculation Example 2:
The condenser is to be located 35 feet above and then 100 feet away horizontally.
35 x 1.7 = 59.5. 59.5 +100 = 159.5. 159.5 is
greater than the 150 maximum and is NOT acceptable.
rd
22.87"
dd
17.15"
Max 35’
Max 15’
Remote
Condenser
Located ABOVE
Ice Machine
Remote
Condenser
Located BELOW
Ice Machine
hd
40.35"
Condenser Distance &
Location Schematic
May 2000
Page 10
Coupling Instructions
CME1056R
The couplings on the ends of the pre-charged line sets are self-sealing when installed properly. Follow these instructions carefully.
These steps must be performed by an EPA Certified Type II or higher technician.
Initial Connections
1. Remove the protector caps and plugs. Wipe the seats and threaded surfaces with a clean cloth to remove any possible foreign matter.
2. Thoroughly lubricate the threads, o-rings, diaphragms and all internal coupling surfaces with polyolester refrigerant oil.
Clean and Lubricate Couplings
3. Position the fittings on the correct connections on the condenser and ice machine.
1
The
“ discharge line (schrader valve end)
2
goes to the remote condenser fitting marked “discharge line”.
3
The
“ liquid line (schrod valve end) goes to
8
the remote condenser fitting marked “liquid line”.
1
The
“ discharge line goes to the ice maker
2
fitting marked “discharge line”.
3
The
“ liquid line goes to the ice maker
8
fitting marked “liquid line”.
4b. Using two wrenches, one to rotate the swivel nut and one to hold the tubing in place, tighten each coupling.
It is CRITICAL that ONLY the NUT on the pre-charged tube be turned, or the diaphragms will be torn by the piercing knives and become loose in the refrigeration system causing severe operational problems.
Tighten Swivel Nut
Note: As the coupling is tightened, the diaphragms in the quick connect couplings will begin to be pierced. As that happens, there will be increased resistance to tightening the swivel nut.
4c. Continue tightening the swivel nut until it bottoms out or a very definite increase in resistance is felt (no threads should be showing). Do NOT overtighten.
5. Use a marker or pen to mark a line on the
coupling nut and unit panel. Then tighten the coupling nut an additional one-quarter turn. The line will show the amount that the nut turns.
6. After all connections have been made, and after
the liquid line valve has been opened (do not open yet), check the couplings for leaks.
Note: The system charge is contained in the receiver tank of the ice machine. Only “holding" charges are present in the “pre-charged" tubing or the condenser.
Final Connections:
4a. Begin to tighten the couplings together by hand. Continue to turn the swivel nuts by hand until it is certain that the threads are properly engaged.
May 2000
Page 11
Rotate Swivel Nut ¼ Turn More
CME1056R
Head Pressure Control Add-On Kit
Kit: RCKCME6GX
Required when a CME1056R is to be connected to a Remote Condenser that is not equipped with a Head Pressure Control Valve
Required Tools: Screwdriver; Drill; 5/32" drill bit; Two Adjustable Wrenches; POE Oil
1. Remove cover from metal box.
2. Locate correct position on condenser: The RCKCME6GX can fit either a Mac G series or a Mac X series condenser.
3. Use metal box as a template, mark the positions of 4 holes to be drilled to mount the box to the condenser.
4. Drill four .157" (#22 or 5/32" bit) dia. holes.
5. Remove plastic covers from the condenser’s quick connects and those to be used to connect to the condenser.
6. Thoroughly clean and lubricate the threads and diaphragms of both the condenser’s and the kit’s quick connects. Use Polyolester oil.
8. Start the swivel nuts by hand.
Use a back up wrench to be certain that the
tubing is NOT ROTATING. Only the SWIVEL NUTS should be rotating!
Then use an adjustable wrench to tighten
them until no threads are seen AND a very definite resistance is felt.
9. Mark the positions of the swivel nuts to the condenser panel.
10. Rotate the swivel nuts additional one-quarter turn.
11. Place cover on metal box & secure with screws.
12. Finish the balance of the installation. Ice machine’s precharged line sets will now connect to the quick connect fittings on the metal box instead of the condenser’s.
7. Mount the box to the condenser with the screws from the kit.
Central
Condenser
Connections
to Central
Condenser
RCKCME6GX
on G series
RCKCME6GX
on X series
March 2003
Page 12
Pre-Charged Lines
from Ice Machine
connect here
Electrical
CME1056R
All models must be installed with the correct wire size and type per the National Electric Code. Locate the nameplate on the back of the cabinet and find the numbers for Voltage, Phase, Minimum Circuit Ampacity and Maximum Fuse Size. Either fuses or HACR type circuit breakers may be used.
The ice maker is designed to operate on its own electrical circuit and must be individually fused. Voltage variation must not exceed the limits listed on page 2.
The remote condenser is designed to be powered from the ice machine. A separate knockout hole has been provided in the ice maker electrical junction box.
Remote Condenser
Power Connection
Note: Central Condensers connected to more than one refrigeration system will likely have a wiring scheme to control the fan motor. Follow those directions for condenser wiring.
Electrical connections are made in the junction box in the back of the cabinet.
1. Remove the junction box cover.
2. Knock out both holes for a field supplied strain
relief.
Note: An external junction box may be mounted to the back of the machine. Holes are pre-drilled for a open back box such as Scotsman part number 12-2374-01.
3. Install wires and strain reliefs per code. Note:
Condenser fan motor wires are tagged.
4. Connect to wires and secure ground wire to
ground screw inside junction box.
All external wiring should conform to the national, state and local electrical code requirements. Usually an electrical permit and the services of a licensed electrician will be required.
Interconnecting
Wires
Power
Supply
Power OUT
Power IN
May 2000
Page 13
Loading...
+ 28 hidden pages