Schneider Electric TP-1011 Series, TP-1031 Series Catalog Page

Typical Applications
TP-1011, TP-1031 Series
TP-10X1
R BC
1
TP-1031
R B C
1
56
4
2 1 4 5
1
3
2
Actuator
Blue
7
2
Red
8
H
G
3
1 Make 100 ohm resistor and jumper
connections on 24 V actuators only.
2
Transformer leads on line voltage actuators only.
3
Marked L1 and L2 on line voltage actuators. Built-in transformer required.
R Closes on temperature drop (rise for TP-1031
and rotates actuator CCW.
B Closes on temperature rise (drop for TP-1031)
and rotates actuator CW. C Common 1 Feedback 4 & 5 10 degrees F, 24 Vac night depression resiston
on TP-1011.
Typical Actuators:
MP-361, MP-371, MP-381, MP-382 MP-475, MP-485, MP-486 MP-2113-600, MP-2150-500
Figure 1 Typical Wiring for TP-1011 (Heating) and TP-1031 (Cooling).
2
TP-1011
R BC
2 1 4 5
W
SC
Summer/Winter
Changeover
Switch
1 Make 100 ohm resistor and jumper
connections on 24 V actuators only.
2
Transformer leads on line voltage actuators only.
3
Marked L1 and L2 on line voltage actuators. Built-in transformer required.
R Closes on temperature drop (rise for TP-1031
and rotates actuator CCW.
B Closes on temperature rise (drop for TP-1031)
and rotates actuator CW. C Common 1 Feedback 4 & 5 10 degrees F, 24 Vac night depression resiston
on TP-1011.
Typical Actuators:
MP-361, MP-371, MP-381, MP-382 MP-475, MP-485, MP-486 MP-2113-600, MP-2150-500
56
4
3
2
Actuator
1
Blue
7
8
1
H
G
2
Red
3
Figure 2 Typical Wiring of TP-10x1s for Summer/Winter.
F-27382-1 © Copyright 2006 TAC. All Rights Reserved. 269