Schneider ATV61HU22N4, ATV71HD18N4, ATV71H075N4, ATV61HD18N4, ATV71HU15N4 User Manual

Important information XXXXXX
Altivar 61/71/LIFT
Variable speed drives for synchronous and asynchronous motors
Safety integrated function manual
S1A91443
www.schneider-electric.com
Important information
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. If you have any suggestions for improvements or amendments or have found errors in this publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic or mechanical, including photocopying, without express written permission of Schneider Electric.
All pertinent state, regional, and local safety regulations must be observed when installing and using this product. For reasons of safety and to help ensure compliance with documented system data, only the manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant instructions must be followed.
Failure to use Schneider Electric software or approved software with our hardware products may result in injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
© 2013 Schneider Electric. All rights reserved.
2
S1A91443 02/2014

Table of contents

Table of contents
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
About the book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Chapter 1 Before you begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Qualification of personnel and use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Chapter 2 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Standards and Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Chapter 3 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
(STO) Safe Torque Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Chapter 4 Incompatibility with safety functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Prerequisites for using safety functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Chapter 5 Safety monitoring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
STO Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Chapter 6 Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Safety function capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Certified architectures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Process system SF - Case 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Process system SF - Case 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Process system SF - Case 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Connection diagram conforming to IEC 61508 and IEC 60204-1 . . . . . . . . . . . . . . . . . 37
Chapter 7 Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
ATV61 Product sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
ATV71 Product sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
S1A91443 02/2014 3
Table of contents
4
S1A91443 02/2014
§

Safety Information

Safety Information
Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists, which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER
DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death or serious
injury.
WARNING
WARNING indicates a potentially hazardous situation, which, if not avoided, can result in death, serious
injury or equipment damage.
CAUTION
CAUTION indicates a potentially hazardous situation, which, if not avoided, can result in injury or
equipment damage.
NOTICE
NOTICE, used without the safety alert symbol, indicates a potentially hazardous situation which, if not
avoided, can result in equipment damage.
PLEASE NOTE
The word "drive" as used in this manual refers to the controller portion of the adjustable speed drive as defined by NEC.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this product.
© 2013 Schneider Electric. All Rights Reserved.
S1A91443 02/2014 5
Safety Information
6
S1A91443 02/2014

About the book

At a Glance

Document Scope

Validity Note

Related Documents
About the book
The purpose of this document is to provide information about safety functions incorporated in Altivar 61/71/ LIFT. These functions allow you to develop applications oriented in the protection of man and machine. Please, read before the installation and programming manual.
This documentation is valid for the Altivar 61, Altivar 71, Altivar LIFT, Altivar 61Q, Altivar 71Q, Altivar 61 Plus and Altivar 71 Plus drives.
Title of Documentation Reference Number
ATV61E installation manual 55 kW (75 HP) ... 90 kW (125 HP) / 200 - 240 V 90 kW (125 HP) ... 630 kW (900 HP) / 380 - 480 V 90 kW (125 HP) ... 800 kW (800 HP) / 500 - 690 V
ATV71E Installation manual 55 kW (75 Hp) ... 75 kW (100 Hp) / 200 - 240 V 90 kW (125 Hp) ... 500 kW (700 Hp) / 380 - 480 V 90 kW (125 Hp) ... 630 kW (700 Hp) / 500 - 690 V
ATV61S Installation manual
0.37 kW (0.5 HP) ... 45 kW (60 HP) / 200 - 240 V
0.75 kW (1 HP) ... 75 kW (100 HP) / 380 - 480 V
2.2 kW (3 HP) ... 7.5 kW (10 HP) / 500 - 600 V
2.2 kW (3 HP) ... 90 kW (100 HP) / 500 - 690 V
ATV71S Installation manual
0.37 (0.5 HP) ... 45 kW (60 HP) / 200 - 240 V
0.75 (1 HP) ... 75 kW (100 HP) / 380 - 480 V
1.5 (2 HP) ... 7.5 kW (10 HP) / 500 - 600 V
1.5 (2 HP) ... 90 kW (100 HP) / 500 - 690 V
ATV61Q Mounting instructions 110 kW (150HP) ... 630 kW (800HP) / 380 - 480 V 110 kW (150HP) ... 800 kW (800HP) / 500 - 690 V
ATV71Q Mounting instructions 90 kW (125HP) ... 500 kW (700HP) / 380 - 480 V 90 kW (125HP) ... 630 kW (700HP) / 500 - 690 V
ATV61 Plus Configuration Guide 90 kW ... 1400 kW / 380 - 415 V 90 kW ... 1800 kW / 500 - 525 V 110 kW ... 2400 kW / 690 V
ATV71 Plus Configuration Guide 90 kW ... 1300 kW / 380 - 415 V 90 kW ... 1500 kW / 500 - 525 V 110 kW ... 2000 kW / 690 V
ATV61 Plus-Marine 630 kW ... 1400 kW / 380 - 415 V 800 kW ... 2400 kW / 690 V
760655
755849
760643
755843
8P02534
8P02535
8P02503
8P02504
8P02526
S1A91443 02/2014 7
Title of Documentation Reference Number
ATV71 Plus-Marine 500 kW ... 1300 kW / 380 - 415 V 630 kW ... 2000 kW / 690 V
ATV61_71 Atex manual AAV49434
ATV61 Programming manual 760649
ATV71 Programming_manual 755855
ATV_LIFT programming manual BBV19478
ATV61_71 Canopen manual 755865
ATV61_71 Cc-link manual AAV49429
ATV61_71 Ethernet manual 755879
ATV61_71 Ethernet TCP Daisy Chain manual AAV69931
ATV61_71 EthernetIP manual AAV68822
ATV61_71 FIPIO manual 755883
ATV61_71 Interbus manual 755871
ATV61_71 PROFIBUS DPv1 manual AAV52935
ATV61 Apogee FLN P1 manual BBV10543
ATV61 Bacnet manual 765274
ATV61 LonWorks_manual 765273
ATV61 metasys N2 manual AAV33578
ATV61 multi pump manual 765272
ATV61 communication parameters 760661
ATV71 communication parameters 755861
ATV71 Controller inside manual 757062
ATV71 Devicenet manual 755877
ATV71 Modbus integrated manual 755863
ATV71 Modbus jbus manual 755875
ATV71 Modbus plus manual 755869
ATV71 profibus manual 755873
ATV71 regen units manual 757361
ATV71 Uni-Telway manual 755867
ATV61 and 71 other option manuals: see www.schneider-electric.com.
8P02527
About the book
You can download the latest versions of the technical publications related to the Altivar 61 and 71 on
www.schneider-electric.com.
8
S1A91443 02/2014

Before you begin

Before you begin
What's in this Chapter?
This chapter contains the following topics:
Topic Page
Safety instructions 10
Qualification of personnel and use 12
1
S1A91443 02/2014 9

Safety instructions

The information provided in this manual supplements the product ma nuals. Carefully read the product manuals before using the product. Read and understand these instructions before performing any procedure with this drive.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
z Only appropriately trained persons who are familiar with and understand the contents of this manual and
z The system integrator is responsible for compliance with all local and national electrical code
z Many components of the product, including the printed circuit boards, operate with mains voltage. Do not
z Do not touch unshielded components or terminals with voltage present. z Motors can generate voltage when the shaft is rotated. Prior to performing any type of work on the drive
z AC voltage can couple voltage to unused conductors in the motor cable. Insulate both ends of unused
z Do not short across the DC bus terminals or the DC bus capacitors or the braking resistor terminals. z Before performing work on the drive system:
z Install and close all covers before applying voltage.
Failure to follow these instructions will result in death or serious injury.
Before you begin
DANGER
all other pertinent product documentation and who have received safety training to recognize and avoid hazards involved are authorized to work on and with this drive system. Installation, adjustment, repair and maintenance must be performed by qualified personnel.
requirements as well as all other applicable regulations with respect to grounding of all equipment.
touch. Use only electrically insulated tools.
system, block the motor shaft to prevent rotation.
conductors of the motor cable.
- Disconnect all power, including external control power that may be present.
- Place a "Do Not Turn On" label on all power switches.
- Lock all power switches in the open position.
- Wait 15 minutes to allow the DC bus capacitors to discharge. The DC bus LED is not an indicator of the absence of DC bus voltage that can exceed 800 Vdc.
- Measure the voltage on the DC bus between the DC bus terminals using a properly rated voltmeter to verify that the voltage is < 42 Vdc.
- If the DC bus capacitors do not discharge properly, contact your local Schneider Electric representative.
DANGER
UNINTENDED EQUIPMENT OPERATION
z Read and understand this manual before installing or operating the drive.
z Any changes made to the parameter settings must be performed by qualified personnel.
Failure to follow these instructions will result in death or serious injury.
WARNING
DAMAGED DRIVE EQUIPMENT
Do not operate or install any drive or drive accessory that appears damaged.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
10
S1A91443 02/2014
Before you begin
WARNING
LOSS OF CONTROL
z The designer of any control scheme must consider the potential failure modes of control paths and, for
critical control functions, provide a means to achieve a safe state during and after a path failure. Examples of critical control functions are emergency stop, overtravel stop, power outage, and restart.
z Separate or redundant control paths must be provided for critical control functions.
z System control paths may include communication links. Consideration must be given to the implications
of unanticipated transmission delays or failures of the link.
z Observe all accident prevention regulations and local safety guidelines.
z Each implementation of the product must be individually and thoroughly tested for proper operation before
1
being placed into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
1. For USA: Additional information, refer to NEMA ICS 1.1 (latest edition), “Safety Guidelines for the Application, Installation, and Maintenance of Solid State Control” and to NEMA ICS 7.1 (latest edition), “Safety Standards for Construction and Guide for Selection, Installation and Operation of Adjustable Speed Drive Systems.
CAUTION
INCOMPATIBLE LINE VOLTAGE
Before turning on and configuring the drive, ensure that the line voltage is compatible with the supply voltage range shown on the drive nameplate. The drive may be damaged if the line voltage is not compatible.
Failure to follow these instructions can result in injury or equipment damage.
NOTICE
RISK OF DERATED PERFORMANCE DUE TO CAPACITOR AGING
The product capacitor performances after a long time storage above 2 years can be degraded. In that case, before using the product , apply the following procedure:
z Use a variable AC supply connected between L1 and L2 (even for ATV61/71pppN4 references). z Increase AC supply voltage to have:
- 80% of rated voltage during 30 min
- 100% of rated voltage during 30 min
Failure to follow these instructions can result in equipment damage.
S1A91443 02/2014 11

Qualification of personnel and use

Qualification of personnel

Only appropriately trained persons who are familiar with and understand the contents of this manual and all other pertinent product documentation are authorized to work on and with this product. In addition, these persons must have received safety training to recognize and avoid hazards involved. These persons must have sufficient technical training, knowledge and experience and be able to foresee and detect potential hazards that may be caused by using the product, by changing the settings and by the mechanical, electrical and electronic equipment of the entire system in which the product is used.
All persons working on and with the product must be fully familiar with all applicable standards, directives, and accident prevention regulations when performing such work.

Intended use

The functions described in this manual are only intended for use with the basic product; you must read and understand the appropriate product manual.
The product may only be used in compliance with all applicable safety regulations and directives, the specified requirements and the technical data.
Prior to using the product, you must perform a risk assessment in view of the planned application. Based on the results, the appropriate safety measures must be implemented.
Since the product is used as a component in an entire system, you must ensure the safety of persons by means of the design of this entire system (for example, machine design).
Before you begin
Operate the product only with the specified cables and accessories. Use only genuine accessories and spare parts.
Any use other than the use explicitly permitted is prohibited and can result in hazards.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
The product must NEVER be operated in explosive atmospheres (hazardous locations, Ex areas).
12
S1A91443 02/2014

Overview

Overview

What's in this Chapter?

This chapter contains the following topics:
Topic Page
Introduction 14
Standards and Terminology 15
Basics 16
2
S1A91443 02/2014 13

Introduction

The safety function incorporated in Altivar 61/71/LIFT, allows you to develop applications oriented in the protection of man and machine.
Safety integrated function provides the following benefits:
z Replacement of external safety equipment z Reduced wiring efforts and space requirements z Reduced costs
The Altivar 61/71/LIFT drives are compliant with normative requirements to implement the safety function

Safety function as per IEC 61800-5-2

(STO) Safe Torque Off
The function purpose is to bring the motor into a no torque condition so it is relevant in terms of safety since no torque is available at the motor level. Power modules are inhibited and the motor coasts dow or prohibits the motor from starting.

Notation

The graphic display terminal (reference VW3A1101) menus are shown in square brackets.
Example: [COMMUNICATION]
The integrated 7-segment display terminal menus are shown in round brackets.
Example: (COM-)
Parameter names are displayed on the graphic display terminal in square brackets.
Example: [Fallback speed]
Parameter codes are displayed on the integrated 7-segment display terminal in round brackets.
Example: (LFF)
Overview
14
S1A91443 02/2014
Overview

Standards and Terminology

Technical terms, terminology and the corresponding descriptions in this manual are intended to use the terms or definitions of the pertinent standards.
In the area of drive systems, this includes, but is not limited to, terms such as "safety function", "safe state", "fault", "fault reset", "failure", "error", "error message", "warning", "warning message", etc.
Among others, these standards include:
z IEC 61800 series: "Adjustable speed electrical power drive systems" z IEC 61508 series Ed.2: "Functional safety of electrical/electronic/programmable electronic safetyrelated
systems"
z EN 954-1 Safety of machinery - Safety related parts of control systems z EN ISO 13849-1 & 2 Safety of machinery - Safety related parts of control systems

EC Declaration of Conformity

The EC Declaration of Conformity for the EMC Directive can be obtained on www.schneider-electric.com

ATEX certification

The ATEX certificate can be obtained on www.schneider-electric.com

Certification for functional safety

The integrated safety function is compatible and certified following IEC 61800-5-2 Ed.1 Adjustable speed electrical power drive systems – Part 5-2 : Safety requirements – Functional
IEC 61800-5-2 as a product standard, sets out safety-related considerations of Power Drive Systems Safety Related “PDS (SR) s” in terms of the framework of IEC 61508 series Ed.2 of standards.
Compliance with IEC 61800-5-2 standard, for the following described safety function, will facilitate the incorporation of a PDS(SR) (Power Drive System with safety-related functions) into a safety-related control system using the principles of IEC 61508, or the ISO 13849-1, as well as the IEC 62061 for process-systems and machinery.
The defined safety function is:
z SIL 2 capability in compliance with IEC 61800-5-2 and IEC 61508 series Ed.2. z Performance Level “d” in compliance with ISO 13849-1. z Compliant with the Category 3 and 4 of European standard ISO 13849-1 (EN 954-1).
Also refer to Safety function capability, page 29
The safety demand mode of operation is considered in high demand or continuous mode of operation according to the IEC 61800-5-2 standard.
The certificate for functional safety is accessible on www.schneider-electric.com.
.
S1A91443 02/2014 15

Basics

Functional Safety

Automation and safety engineering are two areas that were completely separated in the past but recently have become more and more integrated.
Engineering and installation of complex automation solutions are greatly simplified by integrated safety functions.
Usually, the safety engineering requirements depend on the application.
The level of the requirements results from the risk and the hazard potential arising from the specific application.

IEC 61508 standard

The standard IEC 61508 "Functional safety of electrical/electronic /programmable electronic safety-related systems" covers the safety-related function. Instead of a single component, an entire function chain (for example, from a sensor through the logical processing units to the actuator) is considered as a unit. This function chain must meet the requirements of the specific safety integrity level as a whole. Systems and components that can be used in various applications for safety tasks with comparable risk levels can be developed on this basis.

SIL - Safety Integrity Level

The standard IEC 61508 defines 4 safety integrity levels (SIL) for safety functions. SIL1 is the lowest level and SIL4 is the highest level. A hazard and risk analysis serves as a basis for determining the required safety integrity level. This is used to decide whether the relevant function chain is to be considered as a safety function and which hazard potential it must cover.
Overview

PFH - Probability of a dangerous Hardware Failure per Hour

To maintain the safety function, the IEC 61508 standard requires various levels of measures for avoiding and controlling detected faults, depending on the required SIL. All components of a safety function must be subjected to a probability assessment to evaluate the effectiveness of the measures implemented for controlling detected faults. This assessment determines the PFH (probability of a dangerous failure per hour) for a safety system. This is the probability per hour that a safety system fails in a hazardous manner and the safety function cannot be correctly executed. Depending on the SIL, the PFH must not exceed certain values for the entire safety system. The individual PFH values of a function chain are added. The result must not exceed the maximum value specified in the standard.
SIL Safety Integrity Level
4
3
2
1
Probability of a dangerous Failure per Hour (PFH) at high demand or continuous demand
10
10
10
10
-9
… <10
-8
… <10
-7
… <10
-6
… <10
-8
-7
-6
-5

PL - Performance level

The standard IEC 13849-1 defines 5 Performance levels (PL) for safety functions. “a” is the lowest level and “e” is the highest level. Five level (a, b, c, d, e) correspond to different values of average probability of dangerous failure per hour.
Performance level
e
d
c
b
a
Probability of a dangerous Hardware Failure per Hour
10
10
10
3*10
10
-8
… <10
-7
… <10
-6
… <3*10
-5
… <10-4
-6
… <10
-7
-6
-6
-5
16
S1A91443 02/2014
Overview

HFT - hardware detected fault tolerance and SFF - Safe Failure Fraction

Depending on the SIL for the safety system, the IEC 61508 standard and SFF, Safe Failure Fraction requires
a specific hardware detected fault tolerance HFT in connection with a specific proportion of safe failures SFF (safe failure fraction). The hardware detected fault tolerance is the ability of a system to execute the required safety function in spite of the presence of one or more hardware detected faults. The SFF of a system is defined as the ratio of the rate of safe failures to the total failure rate of the system. According to IEC 61508, the maximum achievable SIL of a system is partly determined by the hardware detected fault tolerance HFT and the safe failure fraction SFF of the system. IEC 61508 distinguishes two types of subsystems (type A subsystem, type B subsystem). These types are specified on the basis of criteria which the standard defines for the safety-relevant components.
SFF HFT type A subsystem HFT type B subsystem
012 012 < 60% SIL1 SIL2 SIL3 --- SIL1 SIL2 60% … < 90% SIL2 SIL3 SIL4 SIL1 SIL2 SIL3 60% … < 99% SIL3 SIL4 SIL4 SIL2 SIL3 SIL4
u 99%
SIL3 SIL4 SIL4 SIL3 SIL4 SIL4

Detected fault avoidance measures

Systematic errors in the specifications, in the hardware and the software, usage detected faults and maintenance detected faults of the safety system must be avoided to the maximum degree possible. To meet these requirements, IEC 61508 specifies a number of measures for detected fault avoidance that must be implemented depending on the required SIL. These measures for detected fault avoidance must cover the entire life cycle of the safety system, i.e. from design to decommissioning of the system.
S1A91443 02/2014 17
Overview
18
S1A91443 02/2014

Description

Description

What's in this Chapter?

This chapter contains the following topics:
Topic Page
(STO) Safe Torque Off 20
3
S1A91443 02/2014 19

(STO) Safe Torque Off

Frequency
Actual
frequency
Time
(STO)
activation
The purpose of this function is to bring the motor into a no torque condition with motor coasts down or prohibits the motor from starting. So it is relevant in terms of safety since no torque is available at the motor level.
The logic input “PWR” is always assigned to this function.
The (STO) status is accessible with the drive.

(STO) Normative reference

The normative definition of (STO) function is in §4.2.2.2 of the IEC 61800-5-2 (on the 07/2007 version):
"Power, that can cause rotation (or motion in the case of a linear motor), is not applied to the motor. The PDS(SR)(Power Drive System with safety-related functi ons) will not provide energy to the motor which can generate torque (or force in the case of a linear motor).
NOTE 1 This safety function corresponds to an uncontrolled stop in accordance with stop category 0 of IEC 60204-1.
NOTE 2 This safety function may be used where safe torque off (STO) is required to help prevent an unexpected start-up.
NOTE 3 In circumstances where external influences (for example, falling of suspended loads) are present, additional measures (for example, mechanical brakes) ma y be necessary to help prevent any hazard.
NOTE 4 Electronic means and contactors are not adequate for protection against electric shock, and additional measures for isolation may be necessary."
Description

Safety function (SF) level required for (STO) function

Configuration SIL
(STO) with Preventa module SIL 2 PL "d"
The Preventa module is required for the machine environment because:
z For the machine environment (IEC60204-1 & Machine Directive), reset shall not initiate a restart in any
cases. One of the most constringent case is when PWR (STO) is activated, then the power supply is switch off. In this case, if (STO) is deactivated during the loss of supply, the motor do not have to restart automatically. The Preventa module can help prevent a spurious restart in the previous condition. So the Preventa module is mandatory for machine applications.
z E_stop of several BDM in a PDS: the Preventa module has some safety outputs for application which
requires one or several safety outputs.
For other environments, the Preventa module is not required, except if the application requires it: System fallback position.
(Safety Integrity Level)
according to IEC 61-508
PL
(Performance Level)
according to ISO-13849
20
S1A91443 02/2014

Incompatibility with safety functions

Incompatibility with safety functions

What's in this Chapter?

This chapter contains the following topics:
Topic Page
Prerequisites for using safety functions 22
4
S1A91443 02/2014 21

Prerequisites for using safety functions

Some parameters have to be fulfilled for a proper operation:
z Motor size is adequate to the application and is not in the limit of its capacity z Speed drive size has been properly chosen for the electrical mains, sequence, motor and application and
it is not in the limit of their catalogued capacities.
z If required, the adequate options are used. Example: like dynamic brake resistor or motor inductor. z The drive is properly setting up for the right speed loop and torque characteristics for the application; the
speed profile of the reference is mastered by the drive control loop.
Incompatibility with safety functions
22
S1A91443 02/2014
Incompatibility with safety functions

Fault Inhibition

For some kind of detected fault, [Fault inhibit assign.] (InH) can be requested to avoid the drive to stop
when the fault occurred. The fault inhibition goal is not compatible with the safe function behavior.
When a safe function is activated, detected fault generated by the safe function PrA can’t be inhibited.

Factory settings

If the drive is in safe mode and you active the factory settings only non safety parameters will be downloaded in the drive. Safe parameters are not impacted by factory settings.
S1A91443 02/2014 23
Incompatibility with safety functions
24
S1A91443 02/2014

Safety monitoring

Safety monitoring

What's in this Chapter?

This chapter contains the following topics:
Topic Page
STO Function 26
5
S1A91443 02/2014 25

STO Function

Description

Safety monitoring
When the dedicated PWR logical input is activated, the output power bridge of the drive is locked by the Hardware in order to avoid any torque in the motor. The output power bridge of the drive is also locked by a redundant software and hardware channel.
When the STO Function is active, the drive locks its output power bridge in order to avoid any torque in the motor.
When a fault is detected into the hardware of the STO Function, the drive trips and locks its output power bridge by the redundant hardware and software channel, even if the PWR Input is not activated.
If STO is Active, then Power Bridge is locked by Software and STO status (PrA) is activated and displayed.
If STO is Active and an error is detected, the drive trips in PrF detected fault.
26
S1A91443 02/2014

Technical data

Technical data

What's in this Chapter?

This chapter contains the following topics:
Topic Page
Electrical Data 28
Safety function capability 29
Certified architectures 31
Process system SF - Case 1 32
Process system SF - Case 2 33
Process system SF - Case 3 35
Connection diagram conforming to IEC 61508 and IEC 60204-1 37
6
S1A91443 02/2014 27

Electrical Data

LI1
LI5
+24
0V
A1
ATV71Hppppp
PWR
+10
AI1+
AI2
AI1-
COM
COM
AO1
LI3
LI2
LI6
LI4
Reference potentiometer
0 ± 10 V or X-Y mA
0 ± 10 V or X-Y mA
A1
ATVp1Hppppp
SW1
Ext
Source
Sink
Int
LI1
LI5
+24
0V
LI3
LI2
LI6
LI4
A1
ATVp1Hppppp
SW1
Ext
Source
Sink
Int
LI1
LI5
+24
0V
LI3
LI2
LI6
LI4
+24 V
0 V
24 V c supply
The Logic inputs and Logic outputs of the drive can be wired for logic type 1 or logic type 2.
Logic Type Active state
1 Output draws current (Sink)
2 Output supplies flows from the input Current
Safe function only used in source mode, sink is not compatible with safe functions. Signal inputs are protected against reverse polarity, outputs are short-circuit protected. The inputs and outputs are galvanically isolated.

Control connection diagrams

Technical data
Current flows to the input
Current (Source)

Logic input switch (SW1)

The logic input switch (SW1) is used to adapt the operation of the logic inputs to the technology of the programmable controller outputs.
• Set the switch to Source (factory setting) if using PLC outputs with PNP transistors.
• Set the switch to Sink Int or Sink Ext if using PLC outputs with NPN transistors.
• Switch SW1 set to “Source” position
UNINTENDED EQUIPMENT OPERATION
Prevent accidental grounding of logic inputs wired in "sink logic". Accidental grounding can result in unintended activation of drive functions.
Protect the signal conductors against damage that could result in unintentional conductor grounding.
Failure to follow these instructions will result in death or serious injury.
• Switch SW1 set to “Source” position and use of an external power supply for the LIs
DANGER
28
S1A91443 02/2014
Technical data

Safety function capability

Safety functions of PDS (SR) are part of a global system

If qualitative and quantitative objectives of safety set by the final application requires to make some adjustments to use the safety functions in a safe way, then the integrator of the BDM is responsible of these complementary evolutions (for example management of the mecanichal brake on the motor).
Also, the output information generated by the utilization of safety functions (default relay activation, relay of brake logic command, errors codes or information on the display, …) aren't considering safety informations.Machine application
Function (STO)
Configuration
Standard
IEC 61800-5-2 /
IEC 61508 /
IEC 62061 (1) SIL2 CL
EN 954-1 (2) Category 3
(STO)
with Preventa
XPS AF or equivalent
SIL2

Process application

ISO 13849-1 (3)
IEC 60204-1 Category stop 0
(1) Because the standard IEC 62061 is an integration standard, this standard distinguishes the global safety function (which is classify SIL2 for ATV61/71/LIFT according to diagrams Process system SF - Case 1, page 32 Case 2, page 33
(2) According to table 6 of IEC 62061 (2005)
(3) According to table 4 of EN13849-1 (2008)
Function (STO)
Configuration
Standard
IEC 61800-5-2 /
IEC 61508 /
IEC 62061 (1) SIL2 CL
(1) Because the standard IEC 62061 is an integration standard, this standard distinguishes the global safety function (which is classify SIL2 for ATV61/71/LIFT according to diagrams Process system SF - Case 1, page 32 Case 2, page 33
Category 3
PL "d"
and Process system SF -
) from components which constitute the safety function (which is classify SIL2 CL for ATV61/71/LIFT)
(STO)
SIL2
and Process system SF -
) from components which constitute the safety function (which is classify SIL2 CL for ATV61/71/LIFT)

Input signals safety functions

Input signals safety functions
Logic 0 (Ulow) Vdc < 2
Logic 1 (Uhigh) Vdc > 17
Impedance (24V) kΩ 1.5
Debounce time ms < 1
Response time of safety function ms < 10
S1A91443 02/2014 29
Units Value for
(STO)

Synthesis of the dependability study

Standard Input size 2 - 5 size 6 - 8 size 9 - 10 size 11 -15 size 23 -24
IEC61508 Ed.2
IEC 62061 (1) EN 954-1 (2)
ISO 13849-1 (3)
(1) Because the standard IEC 62061 is an integration standard, this standard distinguishes the global safety function (which is classify SIL2 for ATV61/71/LIFT according to diagrams Process system SF - Case 1, page 32
and Process system SF - Case 2, page 33 ) from components which constitute the safety function
(which is classify SIL2 CL for ATV61/71/LIFT)
(2) According to table 6 of IEC 62061 (2005)
(3) According to table 4 of EN13849-1 (2008)
Preventive annual activation of the safety function is recommended. However the safety levels are reached with lower margins without annual activation.
Note: The table above is not sufficient to evaluate the PL of a PDS. The PL evaluation has to be done at the
system level. The fitter or the integrator of the BDM has to do the system PL evaluation by including sensors
data with numbers from the table above.
Technical data
SFF 92% 91% 91% 91% 92 %
PFH
Type BBBBB
HFT 11111
DC avg 70,40% 68,30% 71,20% 69,70% 69,70%
SIL capability 22222
SIL CL capability 22222
Category 33333
PL ddddd
Category 33333
MTTFd in years 1800 1900 1750 1850 1850
1 E-8 h
-1
1 E-8 h
-1
1 E-8 h
-1
1 E-8 h
-1
1 E-8 h
-1

Drive sizes table

Please refer to the tables, page 39

EN ISO 13849 standard

This European Standard specifies the validation process, including both analysis and testing, for the safety functions and categories for the safety-related parts of control systems. Descriptions of the safety functions and the requirements for the categories are given in EN 954-1 (ISO 13849-1) which deals the general principles for design. Some requirements for validation are general and some are specific to the technology used. EN ISO 13849-2 also specifies the conditions under which the validation by testing of the safety-related parts of control systems should be carried out.
Isolation distances and interval are sized at least according to IEC 60264-1. See the following table

Printed circuits boards/assemblies

Fault considered Fault exclusion Remarks
Short-circuit between two adjacent tracks/pads
Open-circuit of any track None -
for correspondence between product sizes and references.
Short-circuits between adjacent conductors in accordance with remarks 1) to 3).
The base material used is according to IEC 60249 and the creep­age distances and clearances are dimensioned at least to IEC 60664-1: 1992 with at least pollution/installation category III. The printed side(s) of the assembled board is covered with an ag­oing-resistant varnish or a protective layer covering all conductor paths in accordance with IEC 60664-3 All enclosures of the safety-related parts of the control system, in­cluding those mounted remotely, should provide a degree of pro­tection of at least IP54 [see EN 60529 (IEC 60529)], when mounted as specified.
30
S1A91443 02/2014
Technical data

Certified architectures

NOTE: For the certification relative to functional aspects, only the PDS(SR) (Power Drive System with safety-
related functions) will be in consideration, and not the complete system in which fits into to help to ensure the functional safety of a machine or a system/process.
These are the two architectures certified:
z Process system SF - Case 1, page 32 z Process system SF - Case 2, page 33 z Process system SF - Case 3, page 35 z Safety according to IEC 61508 and IEC 60204-1, page 37
Safety functions of PDS (SR) (Power Drive System with safety-related functions) are part of a global system.
If qualitative and quantitative objectives of safety set by the final application require to make some adjustments to use the safety functions in a safe way, then the integrator of the BDM (background debug module) is responsible of these complementary evolutions (for example management of the mechanical brake on the motor).
Also, the output information generated by the utilization of safety functions (default relay activation, relay of brake logic command, errors codes or information on the display, …) are not considering safety informations.
S1A91443 02/2014 31
Technical data
S2
A1 23 33Y2 13
A2
PE
14 24 34
Y43
Y44
Y1
K2K1
48 V, 115 V, 230 V
K1
K2
T
ESC
XPS AC
S1
F1
L1
N
U / T1
V / T2
W / T3
R / L1
U1
W1
V1
M
3 a
S / L2
T / L3
A1
(1)
(4)
ATVp1Hppppp
+24
PWR
R1A
R1C
R1B
LI1
LI6
LI2
P0
PA / +
PB
PC / -
(2)
(3) (3)
Logic

Process system SF - Case 1

Connection diagrams conforming to standards EN 954-1 category 3, ISO 13849-1 and IEC/EN 61508 capacity SIL2, stopping category 0 in accordance with standard IEC/EN 60204-1

This connection diagram is suitable for use with machines with a short freewheel stop time (machines with low inertia or high resistive torque). When the stop request is activated, the motor power supply is cut immediately and it stops in accordance with category 0 of standard IEC/EN 60204-1.
Note: This diagram must be used for hoisting applications if a mechanical brake is controlled by an ATV71.
A contact on the Preventa XPS AC module must be inserted in the brake control circuit to engage it safely when the (STO) Safe Torque Off function is activated.
32
(1)Line choke (if used) (2)Standardized coaxial cable, type RG174/U according to MIL-C17 or KX3B according to NF C 93-550,
external diameter 2.54 mm /0.09 in., maximum length 15 m / 49.21 ft. The cable shielding must be earthed (3)Use cable ends DZ5CE020 (yellow) on wires connected to PWR and +24 inputs (4)Braking resistor (if used)
- Standard EN 954-1 category 3 and ISO 13849-1 require the use of a dual-contact stop button (S1).
- S1 is used to activate the Power Removal safety function.
- S2 is used to initialize the Preventa module when powering up or after an emergency stop. ESC enables the use of other initialization conditions for the module.
- One Preventa module can be used for the STO function on several ATV61/71/LIFT drives.
- A logic output on the Preventa module can be used to indicate reliably that the drive is operating in safe conditions.
Note:
For preventive maintenance, the STO function must be activated at least once a year. The drive power supply must be turned off and then on again before carrying out this preventive maintenance. The drive logic output signals cannot be considered as safety-type signals. Install interference suppressors on all inductive circuits near the drive or coupled to the same circuit (relays, contactors, solenoid valves, etc).
Choice of associated components:
Please refer to the catalog.
S1A91443 02/2014
Technical data

Process system SF - Case 2

Connection diagram conforming to standards EN 954-1 category 3, ISO 13849-1 and IEC/EN 61508 capacity SIL2, stopping category 1 in accordance with standard IEC/EN 60204-1

This connection diagram is suitable for use with machines with a long freewheel stop time (machines with high inertia or low resistive torque).
WARNING
LOSS OF CONTROL
This diagram must not be used for hoisting applications. Use process system SF - Case 1.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
When the stop request is activated, deceleration of the motor, controlled by the drive, is requested first. Then, after a time delay corresponding to the deceleration time, the STO function is activated.
Example:
- 2-wire control
- LI1 assigned to forward
- LI2 assigned to reverse
L1
F1
(max. 4 A)
N
S1
A1 13 57 67
XPS-ATE
T
(1)
S11S21
B1
S12
K1 K2
S22
Time (s)
Timer 2
Timer 1
LOGIC
K1
23
K3
K1
A2
PE
(1)
S2
S33
K3
K2
K2 K4K1
K3 K4
Y1 Y2 Y3 Y4 Y5 14 24 6858
ESC
K2
K4
77
78 Y88 Y89 Y90 Y91
(A1/A2)
(S12)
+24V
Y+
(S22)
to PLC
c
(Stop1)
A1
ATVp1Hppppp
U1
R / L1
U / T1
3 a
V1
M
S / L2
V / T2
W1
(2)
T / L3
W / T3
(1)
LI1
P0
LI2
PA / +
(3)
PC / -
PWR
(4)(4)
+24
R1A
R1B
R1C
LI6
PB
(5)
(1)In this example, the logic inputs LIp are wired as “Source” but can be wired as “Sink Int” or “Sink Ext”. (2)Line choke (if used) (3)Standardized coaxial cable, type RG174/U according to MIL-C17 or KX3B according to NF C 93-550, external
diameter 2.54 mm /0.09 in., maximum length 15 m / 49.21 ft. The cable shielding must be earthed. (4)Use cable ends DZ5CE020 (yellow) on wires connected to PWR and +24 inputs (5)Braking resistor (if used)
S1A91443 02/2014 33
Technical data
- Standard EN 954-1 category 3 and ISO 13849-1 require the use of a dual-contact stop button (S1).
- S1 is used to activate the STO function.
- S2 is used to initialize the Preventa module when powering up or after an emergency stop. ESC enables the use of other initialization conditions for the module.
- One Preventa module can be used for the STO function on several ATV61/71/LIFT drives. In this case the time delay must be set to the longest stopping time.
- A logic output on the Preventa module can be used to indicate reliably that the drive is operating in safe conditions.
Note:
For preventive maintenance, the STO function must be activated at least once a year. The drive power supply must be turned off and then on again before carrying out this preventive maintenance. The drive logic output signals cannot be considered as safety-type signals. Install interference suppressors on all inductive circuits near the drive or coupled to the same circuit (relays, contactors, solenoid valves, etc).
Choice of associated components:
Please refer to the catalog.
34
S1A91443 02/2014
Technical data

Process system SF - Case 3

Multi-drive conforming to standards EN 954-1 category 3, ISO 13849-1 and IEC/EN 61508 capacity SIL2, stopping category 1 in accordance with standard IEC/EN 60204-1

This connection diagram is suitable for use with machines with a long freewheel stop time (machines with high inertia or low resistive torque).
.
WARNING
LOSS OF CONTROL
This diagram must not be used for hoisting applications. Use process system SF - Case 1.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
L1
F1
(max. 4 A)
A1 13 57 67
XPS-ATE
T
(1)
A2
PE
(1)
N
S2
S11S21
S33
B1
S1
S12
K1 K2
K3
S22
Time (s)
LOGIC
Timer 2
Timer 1
K1 K2
K2 K4K1
K3 K4
Y1 Y2 Y3 Y4 Y5 14 24 6858
ESC
23
K1
K2
77
K3
K4
78 Y88 Y89 Y90 Y91
(A1/A2)
(S12)
+24V
Y+
(S22)
to PLC
c
(Stop1)
A1
ATVp1Hppppp
A1
ATVp1Hppppp
U1
U1
R / L1
U / T1
3 a
R / L1
U / T1
3 a
V1
V1
M
M
S / L2
V / T2
S / L2
V / T2
W1
W1
(3)
T / L3
W / T3
(3)
T / L3
W / T3
LI2
PA / +
LI2
PA / +
(4)
(5) (5)
LI6
PB
PC / -
(6)
(4)
LI6
PB
PC / -
(6)
PWR
(5) (5)
PWR
+24
R1A
R1B
R1C
+24
R1A
R1B
R1C
(2)
LI1
P0
(2)
LI1
P0
(1) 115/230 V ~ only. (2) In this example, the logic inputs LIo are wired as "Source" but can be wired as "Sink Int" or "Sink Ext".
(3) Line choke (if used) (4) Standardized coaxial cable, type RG174/U according to MIL-C17 or KX3B according to NF C 93-550, external diameter
2.54 mm /0.09 in., maximum length 15 m / 49.21 ft. The cable shielding must be earthed.
S1A91443 02/2014 35
Technical data
(5) Use cable ends DZ5CE020 (yellow) on wires connected to PWR and +24 inputs. (6) Braking resistor (if used)
When the stop request is activated, deceleration of the motor, controlled by the drive, is requested first. Then, after a time delay corresponding to the deceleration time, the STO function is activated.
Example:
- 2-wire control
- LI1 assigned to forward.
- LI2 assigned to reverse.
- Standard EN 954-1category 3 and ISO 13849-1 require the use of a dual-contact stop button (S1).
- S1 is used to activate the STO function.
- S2 is used to initialize the Preventa module when powering up or after an emergency stop. ESC enables the use of other initialization conditions for the module.
- One Preventa module can be used for the STO safety function on several ATV61/71/LIFT drives. In this case the time delay must be set to the longest stopping time.
A Logic output on the Preventa module can be used to indicate reliably that the drive is operating in safe conditions.
Note: For preventive maintenance, the STO function must be activated at least once a year. The drive power
supply must be turned off and then on again before carrying out this preventive maintenance. The drive logic output signals cannot be considered as safety-type signals.
Install interference suppressors on all inductive circuits near the drive or coupled to the same circuit (relays, contactors, solenoid, valves, etc).
Choice of associated components:
Please refer to the catalog.
36
S1A91443 02/2014
Technical data
S1
U / T1
V / T2
W / T3
R / L1
U1
W1
V1
M
3 a
S / L2
T / L3
A1
(1)
(4)
ATVp1Hppppp
+24
PWR
R1A
R1C
R1B
LI1
LI6
LI2
P0
PA / +
PB
PC / -
(3) (3)
(2)

Connection diagram conforming to IEC 61508 and IEC 60204-1

Connection diagram conforming to the standard IEC/EN61508 Capacity SIL2, Stopping category 0 in accordance with the standard IEC/EN 60204-1, without protection against supply interruption or voltage reduction an d subsequent rotation.

S1: Emergency Stop (1)Line choke (if used) (2)Standardized coaxial cable, type RG174/U according to MIL-C17 or KX3B according to NF C 93-550,
external diameter 2.54 mm /0.09 in., maximum length 15 m / 49.21 ft. The cable shielding must be earthed (3)Use cable ends DZ5CE020 (yellow) on wires connected to PWR and +24 inputs (4)Braking resistor (if used)
S1A91443 02/2014 37
Technical data
38
S1A91443 02/2014

Appendix

Appendix

What's in this Chapter?

This chapter contains the following topics:
Topic Page
ATV61 Product sizes 40
ATV71 Product sizes 44
7
S1A91443 02/2014 39

ATV61 Product sizes

Correspondence table

This table allows making the correspondence between the size and the reference of the drive.
Supply Voltage
200 – 240 V
Power
Reference
ATV61H075M3
ATV61HU15M3
ATV61HU22M3
ATV61HU30M3
ATV61HU40M3
ATV61HU55M3
ATV61HU75M3
ATV61HD11M3X
ATV61HD15M3X
ATV61HD18M3X
ATV61HD22M3X
ATV61HD30M3X
ATV61HD37M3X
ATV61HD45M3X
ATV61HD55M3X
ATV61HD75M3X
ATV61HD90M3X
Appendix
Size 2
Size 3
Size 4
Size 5
Size 6
Size 7
Size 8
(5A – 5B)
p p
p p p
p
p p p
p p
(7A – 7B)
p p p
Size 9
p p
Size 11
Size 10
p
Size 12
Size 13
Size 14
Size 15
40
S1A91443 02/2014
Appendix
Power Supply Voltage
380 – 480 V
Reference
ATV61H075N4
ATV61HU15N4
ATV61HU22N4
ATV61HU30N4
ATV61HU40N4
ATV61HU55N4
ATV61HU75N4
ATV61HD11N4
ATV61HD15N4
ATV61HD18N4
ATV61HD22N4
ATV61HD30N4
ATV61HD37N4
ATV61HD45N4
ATV61HD55N4
ATV61HD75N4
ATV61HD90N4
ATV61HC11N4
ATV61HC13N4
ATV61HC16N4
ATV61QC11N4
ATV61QC13N4
ATV61QC16N4
ATV61HC20N4
ATV61HC22N4
ATV61HC25N4
ATV61HC28N4
ATV61HC31N4
ATV61QC20N4
ATV61QC25N4
ATV61QC31N4
ATV61HC40N4
ATV61HC50N4
ATV61HC63N4
ATV61QC40N4
ATV61QC50N4
ATV61QC63N4
Size 2
p p p
Size 3
p p
Size 4
p p
Size 5
(5A – 5B)
p p p
Size 6
p
Size 7
(7A – 7B)
p p
Size 8
p p p
Size 9
p p
Size 10
p
Size 11
Size 12
Size 13
Size 14
Size 15
p p p p
p p
p p p p p p
p p
p p p p
S1A91443 02/2014 41
Power Supply Voltage
500 – 690 V
Reference
ATV61HU30Y
ATV61HU40Y
ATV61HU55Y
ATV61HU75Y
ATV61HD11Y
ATV61HD15Y
ATV61HD18Y
ATV61HD22Y
ATV61HD30Y
ATV61HD37Y
ATV61HD45Y
ATV61HD55Y
ATV61HD75Y
ATV61HD90Y
ATV61HC11Y
ATV61HC13Y
ATV61HC16Y
ATV61HC20Y
ATV61QC13Y
ATV61QC16Y
ATV61QC20Y
ATV61HC25Y
ATV61HC31Y
ATV61HC40Y
ATV61QC25Y
ATV61QC31Y
ATV61QC40Y
ATV61HC50Y
ATV61HC63Y
ATV61HC80Y
ATV61QC50Y
ATV61QC63Y
ATV61QC80Y
Size 2
Size 3
Size 4
Size 5
(5A – 5B)
Size 6
p p p p p p p p p
Size 7
(7A – 7B)
Size 8
p p p p p
Size 9
Size 10
p p p p p p p
Appendix
Size 11
Size 12
Size 13
Size 14
Size 15
p p p p p p
p p p p p p
42
S1A91443 02/2014
Appendix
Power Supply Voltage
380 – 415 V
500 V
690 V
Reference
Size 23
ATV61EXppC63N4 ATV61EXppC71N4
p p
ATV61EMppC63N4 p ATV61EMppC71N4 p ATV61EMppC90N4 p ATV61EMppM11N4 p ATV61EMppM13N4 p ATV61EMppM14N4 p ATV61EXppC90N4 ATV61EXppM11N4 ATV61EXppM13N4 ATV61EXppM14N4 ATV61EXppC63N ATV61EXppC71N ATV61EXppC90N
p p p
ATV61EXppM11N ATV61EXppM13N ATV61EXppM15N ATV61EXppM18N ATV61EXppC80Y p ATV61EXppM10Y p ATV61EXppM12Y p ATV61EMppC80Y p ATV61EMppM10Y p ATV61EMpp
M12Y p ATV61EXppM15Y p ATV61EXppM18Y p ATV61EXppM21Y p ATV61EXppM24Y p ATV61EMppM15Y p ATV61EMppM18Y p ATV61EMppM21Y p ATV61EMppM24Y p
Size 24
p p p p
p p p p
S1A91443 02/2014 43

ATV71 Product sizes

Correspondence table

This table allows making the correspondence between the size and the reference of the drive.
Supply Voltage
200 – 240 V
380 – 480 V
Power
Appendix
Reference
ATV71H037M3 p
ATV71H075M3 p ATV71HU15M3 p ATV71HU22M3 p ATV71HU30M3 p ATV71HU40M3 p ATV71HU55M3 p ATV71HU75M3 p
ATV71HD11M3X p ATV71HD15M3X p ATV71HD18M3X p ATV71HD22M3X p ATV71HD30M3X p ATV71HD37M3X p ATV71HD45M3X p ATV71HD55M3X p ATV71HD75M3X p
ATV71H075N4 p ATV71HU15N4 p ATV71HU22N4 p ATV71HU30N4 p ATV71HU40N4 p ATV71HU55N4 p ATV71HU75N4 p ATV71HD11N4 p ATV71HD15N4 p ATV71HD18N4 p ATV71HD22N4 p ATV71HD30N4 p ATV71HD37N4 p ATV71HD45N4 p ATV71HD55N4 p ATV71HD75N4 p ATV71HD90N4 p ATV71HC11N4 p ATV71HC13N4 p ATV71QD90N4 p ATV71QC11N4 p ATV71QC13N4 p ATV71HC16N4 p ATV71HC20N4 p ATV71HC25N4 p ATV71HC28N4 p ATV71QC16N4 p ATV71QC20N4 p ATV71QC25N4 p ATV71HC31N4 p ATV71HC40N4 p ATV71HC50N4 p
ATV71QC31N4 ATV71QC40N4 p ATV71QC50N4 p
Size 2
Size 3
Size 4
Size 5
Size 6
Size 7
Size 8
(5A – 5B)
(7A – 7B)
Size 9
Size 11
Size 10
Size 12
Size 13
Size 14
Size 15
p
44
S1A91443 02/2014
Appendix
Power Supply Voltage
500 – 690 V
Reference
Size 2
Size 3
Size 4
Size 5
Size 6
Size 7
Size 8
(5A – 5B)
(7A – 7B)
Size 9
Size 10
Size 11
Size 12
Size 13
Size 14
ATV71HU22Y p ATV71HU30Y p ATV71HU40Y p ATV71HU55Y p ATV71HU75Y p ATV71HD11Y p ATV71HD15Y p ATV71HD18Y p ATV71HD22Y p ATV71HD30Y p ATV71HD37Y p ATV71HD45Y p ATV71HD55Y p ATV71HD75Y p ATV71HD90Y p ATV71HC11Y p ATV71HC13Y p ATV71HC16Y p ATV71QC11Y p ATV71QC13Y p ATV71QC16Y p ATV71HC20Y p ATV71HC25Y p ATV71HC31Y p ATV71QC20Y p ATV71QC25Y p ATV71QC31Y p ATV71HC40Y p ATV71HC50Y p ATV71HC63Y p ATV71QC40Y p ATV71QC50Y p ATV71QC63Y p
Size 15
S1A91443 02/2014 45
Power Supply Voltage
380 – 415 V
500 V
690 V
Reference
Size 23
ATV71EXppC50N4 ATV71EXppC63N4 ATV71EMppC63N4
p p p
ATV71EXppC71N4 ATV71EXppC90N4 ATV71EXppM11N4 ATV71EXppM13N4 ATV71EMppC71N4 ATV71EMppC90N4 ATV71EMppM11N4 ATV71EMppM13N4 ATV71EXppC50N ATV71EXppC63N ATV71EXppC80N
p p p
ATV71EXppC90N ATV71EXppM11N ATV71EXppM13N ATV71EXppM15N ATV71EXppC63Y p ATV71EXppC80Y p ATV71EXppM10Y p ATV71EMppC63Y p ATV71EMppC80Y p ATV71EMppM10Y p ATV71EXpp
M12Y p ATV71EXppM15Y p ATV71EXppM18Y p ATV71EXppM20Y p ATV71EMppM12Y p ATV71EMppM15Y p ATV71EMppM18Y p ATV71EMppM20Y p
Appendix
Size 24
p p p p p p p p
p p p p
46
S1A91443 02/2014
ATV61_71_LIFT_Safety_function_manual_EN_S1A91443_03
S1A91443 02/2014
Loading...