Sanyo SAP-KMV91G-S,SAP-KMV181G-S,SAP-CMV2441G Technical & Service Manual

TECHNICAL & SERVICE MANUAL
SAP-KMV91G ´ 3 + SAP-CMV2441G SAP-KMV181G
or
SAP-KMV91G
´ 4 + SAP-CMV2441G
INVERTER MULTI-SPLIT SYSTEM AIR CONDITIONER
SAP-KMV91G ´ 3
FILE NO.
REFERENCE NO. SM700420
W
Indoor Unit Outdoor Unit
SAP-KMV181G
or
SAP-KMV91G ´ 4
Indoor Model No. Product Code No.
SAP-KMV91G-S 1 852 066 82
SAP-KMV181G-S 1 852 066 83
Outdoor Model No. Product Code No.
SAP-CMV2441G 1 852 066 84
Destination: General (50Hz)
i
IMPORTANT! Please Read Before Starting
This air conditioning system meets strict safety and oper­ating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices given in this manual.
This symbol refers to a haz­ard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tub­ing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental
injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire
hazard.
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing…
…In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the unit’s weight. It may be necessary to construct a strong wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This pre­vents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak­free connection.
• Check carefully for leaks before starting the test run.
When Servicing
• Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
Others
• Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
• Confirm upon completing installation that no refriger­ant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.
WARNING
WARNING
CAUTION
CAUTION
ii
Table of Contents
Page
UNIT COMBINATION ................................................................................................................ iii
1. OPERATING RANGE................................................................................................................ 1
2. SPECIFICATIONS
2-1. Specifications in Combination with Indoor Units................................................................ 1
2-2. Unit Specifications ............................................................................................................. 3
2-3. Major Component Specifications....................................................................................... 8
2-4. Other Component Specifications....................................................................................... 9
3. DIMENSIONAL DATA................................................................................................................ 10
4. FREQUENCY CHARTS
4-1. Cooling Capacity................................................................................................................ 13
4-2. Frequency Characteristics.................................................................................................17
5. AIR THROW DISTANCE CHARTS............................................................................................ 18
6. REFRIGERANT FLOW DIAGRAM............................................................................................ 19
7. ELECTRICAL DATA
7-1. Electrical Characteristics.................................................................................................... 20
7-2. Electric Wiring Diagrams.................................................................................................... 22
7-3. Performance Charts........................................................................................................... 25
8. INSTALLATION INSTRUCTIONS
8-1. Installation Site Selection................................................................................................... 26
8-2. Remote Control Unit Installation Position........................................................................... 28
8-3. Recommended Wire Length and Diameter........................................................................ 29
8-4. Setting for Electric Current Suppressor ............................................................................. 30
8-5. Tubing Check Function....................................................................................................... 30
9. MAINTENANCE
9-1. Changing Address of Remote Control Unit in Indoor Unit ................................................. 32
9-2. Disconnecting and Connecting Positive Connector for Outdoor Unit................................. 33
9-3. Replacing Thermistors (on outdoor unit) for Electronic Expansion Valves ........................ 33
10. FUNCTIONS
10-1. Functions for Operation.................................................................................................... 34
10-2. Protective Functions......................................................................................................... 36
11. TROUBLESHOOTING
11-1. Operating State................................................................................................................ 37
11-2. Troubleshooting Using the Self-Diagnostic Monitor......................................................... 38
11-3. Fault Assessment of Indoor/Outdoor Unit........................................................................ 40
11-4. Checkpoints for Each Component and Check Procedure................................................ 41
11-5. Problems with Noise and Radio Interference................................................................... 44
12. CHECKING ELECTRICAL COMPONENTS
12-1. Measurement of Insulation Resistance............................................................................ 45
12-2. Checking Continuity of Fuse on PCB Ass’y..................................................................... 46
12-3. Checking Motor Capacitor................................................................................................ 46
INSTRUCTION MANUAL.......................................................................................... 47
APPENDIX
iii
UNIT COMBINATION
Combine indoor and outdoor units only as listed below.
Outdoor Unit Indoor Unit Symbol of Indoor Unit Refer to
SAP-CMV2441G
SAP-KMV91G A to C
Fig. 1
SAP-KMV181G D
Outdoor Unit Indoor Unit Symbol of Indoor Unit Refer to
SAP-CMV2441G SAP-KMV91G A to D Fig. 2
D
C
B
A
Fig. 1
D
C
B
A
Fig. 2
1
1. OPERATING RANGE
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Maximum 32°C D.B. / 23°C W.B. 43°C D.B.
Minimum 19°C D.B. / 14°C W.B. 19°C D.B.
2. SPECIFICATIONS
2-1. Specifications in Combination with Indoor Units
2-1-1.
91: SAP-KMV91G 181: SAP-KMV181G
Refer to “8-4. Setting for Electric Current Suppressor” for switching between FREE/11/8.5A.
Free
NOTE
At 220V
Combination
Total cooling capacity
Total power input (W) Total current (A)
Indoor capacity (kW) (kW)
of indoor unit
Min ST Max Min ST Max Min ST Max 91 2.60 0.80 2.60 2.90 360 1020 1300 2.2 5.8 7.0 181 5.20 1.00 5.20 5.60 420 2070 2490 2.4 10.5 12.4 91 ´ 2 2.55 2.55 1.20 5.10 5.40 400 2020 2340 2.3 10.3 11.7 91 + 181 2.10 4.40 1.40 6.50 6.90 450 2570 3190 2.5 12.8 15.7 91 ´ 3 2.15 2.15 2.15 1.50 6.45 6.90 430 2420 3180 2.4 12.2 15.8 91 ´ 2 + 181 1.70 1.70 3.50 2.30 6.90 7.50 610 2370 3270 3.5 11.9 16.2 91 ´ 4 1.75 1.75 1.75 1.75 2.20 7.00 7.60 600 2450 3300 3.4 12.3 16.2 91 ´ 3 + 181 1.45 1.45 1.45 2.85 3.30 7.20 8.00 870 2310 3390 5.1 11.6 16.8
11A
Combination
Total cooling capacity
Total power input (W) Total current (A)
Indoor capacity (kW) (kW)
of indoor unit
Min ST Max Min ST Max Min ST Max 91 2.60 0.80 2.60 2.90 360 1020 1300 2.2 5.8 7.0 181 5.20 1.00 5.20 5.30 420 2070 2200 2.4 10.5 11.0 91 ´ 2 2.55 2.55 1.20 5.10 5.20 400 2020 2150 2.3 10.3 11.0 91+181 1.90 4.00 1.40 5.90 5.90 450 2210 2210 2.5 11.0 11.0 91 ´ 3 1.95 1.95 1.95 1.50 5.85 5.85 430 2200 2200 2.4 11.0 11.0 91 ´ 2 + 181 1.60 1.60 3.30 2.30 6.50 6.50 610 2220 2220 3.5 11.0 11.0 91 ´ 4 1.60 1.60 1.60 1.60 2.20 6.40 6.40 600 2220 2220 3.4 11.0 11.0 91 ´ 3 + 181 1.30 1.30 1.30 2.60 3.30 6.50 6.50 870 2170 2170 5.1 11.0 11.0
8.5A
Combination
Total cooling capacity
Total power input (W) Total current (A)
Indoor capacity (kW) (kW)
of indoor unit
Min ST Max Min ST Max Min ST Max 91 2.60 0.80 2.60 2.90 360 1020 1300 2.2 5.8 7.0 181 4.40 1.00 4.40 4.40 420 1640 1640 2.4 8.5 8.5 91 ´ 2 2.10 2.10 1.20 4.20 4.20 400 1650 1650 2.3 8.5 8.5 91+181 1.65 3.35 1.40 5.00 5.00 450 1670 1670 2.5 8.5 8.5 91 ´ 3 1.65 1.65 1.65 1.50 4.95 4.95 430 1660 1660 2.4 8.5 8.5 91 ´ 2 + 181 1.40 1.40 2.75 2.30 5.55 5.55 610 1670 1670 3.5 8.5 8.5 91 ´ 4 1.35 1.35 1.35 1.35 2.20 5.40 5.40 600 1670 1670 3.4 8.5 8.5 91 ´ 3 + 181 1.10 1.10 1.10 2.20 3.30 5.50 5.50 870 1630 1630 5.1 8.5 8.5
2
2-1-2.
91: SAP-KMV91G 181: SAP-CMV2441G
Refer to “8-4. Setting for Electric Current Suppressor” for switching between FREE/11/8.5A.
Free
NOTE
At 230V
Combination
Total cooling capacity
Total power input (W) Total current (A)
Indoor capacity (kW) (kW)
of indoor unit
Min ST Max Min ST Max Min ST Max 91 2.60 0.80 2.60 2.90 380 1070 1360 2.2 5.9 7.1 181 5.20 1.00 5.20 5.60 430 2120 2550 2.4 10.3 12.2 91 ´ 2 2.55 2.55 1.20 5.10 5.40 410 2080 2410 2.3 10.2 11.6 91 + 181 2.10 4.40 1.40 6.50 6.90 450 2570 3190 2.4 12.4 15.2 91 ´ 3 2.15 2.15 2.15 1.50 6.45 6.90 430 2430 3190 2.3 11.7 15.2 91 ´ 2 + 181 1.70 1.70 3.50 2.30 6.90 7.50 620 2400 3310 3.4 11.6 15.8 91 ´ 4 1.75 1.75 1.75 1.75 2.20 7.00 7.60 600 2450 3300 3.3 11.9 15.7 91 ´ 3 + 181 1.45 1.45 1.45 2.85 3.30 7.20 8.00 890 2360 3460 5.0 11.4 16.5
11A
Combination
Total cooling capacity
Total power input (W) Total current (A)
Indoor capacity (kW) (kW)
of indoor unit
Min ST Max Min ST Max Min ST Max 91 2.60 0.80 2.60 2.90 380 1070 1360 2.2 5.9 7.1 181 5.20 1.00 5.20 5.30 430 2120 2250 2.4 10.3 11.0 91 ´ 2 2.55 2.55 1.20 5.10 5.20 410 2080 2200 2.3 10.2 11.0 91 + 181 1.90 4.00 1.40 5.90 5.90 450 2210 2210 2.4 11.0 11.0 91 ´ 3 1.95 1.95 1.95 1.50 5.85 5.85 430 2210 2210 2.3 11.0 11.0 91 ´ 2 + 181 1.60 1.60 3.30 2.30 6.50 6.50 620 2250 2250 3.4 11.0 11.0 91 ´ 4 1.60 1.60 1.60 1.60 2.20 6.40 6.40 600 2220 2220 3.3 11.0 11.0 91 ´ 3 + 181 1.30 1.30 1.30 2.60 3.30 6.50 6.50 890 2210 2210 5.0 11.0 11.0
8.5A
Combination
Total cooling capacity
Total power input (W) Total current (A)
Indoor capacity (kW) (kW)
of indoor unit
Min ST Max Min ST Max Min ST Max 91 2.60 0.80 2.60 2.90 380 1070 1360 2.2 5.9 7.1 181 4.40 1.00 4.40 4.40 430 1680 1680 2.4 8.5 8.5 91 ´ 2 2.10 2.10 1.20 4.20 4.20 410 1700 1700 2.3 8.5 8.5 91 + 181 1.65 3.35 1.40 5.00 5.00 450 1670 1670 2.4 8.5 8.5 91 ´ 3 1.65 1.65 1.65 1.50 4.95 4.95 430 1670 1670 2.3 8.5 8.5 91 ´ 2 + 181 1.40 1.40 2.75 2.30 5.55 5.55 620 1690 1690 3.4 8.5 8.5 91 ´ 4 1.35 1.35 1.35 1.35 2.20 5.40 5.40 600 1670 1670 3.3 8.5 8.5 91 ´ 3 + 181 1.10 1.10 1.10 2.20 3.30 5.50 5.50 890 1660 1660 5.0 8.5 8.5
3
2-2. Unit Specifications
The following are the specifications with the electric current suppressor set to “FREE.” (Please refer to 8-4 for details)
Indoor unit SAP-KMV91G Outdoor unit SAP-CMV2441G
NOTE
No. of Indoor Units 1-unit type Power Source 220 – 230V ~ 50Hz
Cooling
Capacity
kW 2.6 (0.8 – 2.9)
BTU/h 8,900 (2,700 – 9,900) Air circulation (High) m3/h 430 Moisture removal (High) Liters/h 1.3 Voltage rating V 230 Available voltage range V 198 – 253 Running amperes A 5.9 (2.2 – 7.1) Power input W 1,070 (380 – 1,360) Power factor % 79 C.O.P. W/W 2.4 Compressor locked rotor amperes A 23 Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer ON/OFF 24-hours & Daily program, 1-hour OFF Fan speeds Indoor / Outdoor 3 and Auto / Auto (Variable)
Airflow direction (Indoor)
Horizontal Manual
Vertical Auto Air filter Washable, Anti-mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 / 2,500 Refrigerant control Electrical expansion valve
Operation sound
Indoor – Hi / Me / Lo dB-A 39 / 35 / 31
Outdoor – Hi dB-A 47 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 20
Refrigerant tube
Narrow tube mm (in.) 6.35 (1/4) diameter
Wide tube mm (in.) 12.7 (1/2) Refrigerant tube kit / Accessories Optional / Hanging wall bracket
Indoor unit Outdoor unit
Unit dimensions Height mm 250 625
Width mm 790 880
Depth mm 174 295 Package dimensions Height mm 242 699
Width mm 850 1,126
Depth mm 312 401 Weight Net kg 7.0 63.0
Shipping kg 10.0 68.0 Shipping volume m
3
0.063 0.316
PerformanceElectrical RatingFeatures
Dimensions & Weight
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
4
Indoor unit SAP-KMV181G Outdoor unit SAP-CMV2441G
No. of Indoor Units 1-unit type Power Source 220 – 230V ~ 50Hz
Cooling
Capacity
kW 5.2 (1.0 – 5.6)
BTU/h 17,700 (3,400 – 19,100) Air circulation (High) m3/h 780 Moisture removal (High) Liters/h 2.7 Voltage rating V 230 Available voltage range V 198 – 253 Running amperes A 10.3 (2.4 – 12.2) Power input W 2,120 (430 – 2,550) Power factor % 90 C.O.P. W/W 2.5 Compressor locked rotor amperes A 23 Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer ON/OFF 24-hours & Daily program, 1-hour OFF Fan speeds Indoor / Outdoor 3 and Auto / Auto (Variable)
Airflow direction (Indoor)
Horizontal Manual
Vertical Auto Air filter Washable, Anti-mold + Air clean filter Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 / 2,500 Refrigerant control Electrical expansion valve
Operation sound
Indoor – Hi / Me / Lo dB-A 41 / 39 / 36
Outdoor – Hi dB-A 47 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 20
Refrigerant tube
Narrow tube mm (in.) 6.35 (1/4) diameter
Wide tube mm (in.) 9.52 (3/8) Refrigerant tube kit / Accessories Optional / Hanging wall bracket
Indoor unit Outdoor unit
Unit dimensions Height mm 285 625
Width mm 995 880
Depth mm 196 295 Package dimensions Height mm 363 699
Width mm 1,070 1,126
Depth mm 276 401 Weight Net kg 12.0 63.0
Shipping kg 15.0 68.0 Shipping volume m
3
0.108 0.316
PerformanceElectrical RatingFeatures
Dimensions & Weight
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
5
Indoor unit SAP-KMV91G + KMV181G Outdoor unit SAP-CMV2441G
No. of Indoor Units 2-unit type Power Source 220 – 230V ~ 50Hz
Cooling
Capacity
kW 6.5 (1.4 – 6.9)
BTU/h 22,200 (4,800 – 23,500) Air circulation (High) m3/h 1.210 Moisture removal (High) Liters/h 4.0 Voltage rating V 230 Available voltage range V 198 – 253 Running amperes A 12.4 (2.4 – 15.2) Power input W 2,570 (450 – 3,190) Power factor % 90 C.O.P. W/W 2.5 Compressor locked rotor amperes A
PerformanceElectrical Rating
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Indoor unit SAP-KMV91G ´ 2 Outdoor unit SAP-CMV2441G
No. of Indoor Units 2-unit type Power Source 220 – 230V ~ 50Hz
Cooling
Capacity
kW 5.1 (1.2 – 5.4)
BTU/h 17,400 (4,090 – 18,400) Air circulation (High) m3/h 860 Moisture removal (High) Liters/h 2.6 Voltage rating V 230 Available voltage range V 198 – 253 Running amperes A 10.2 (2.3 – 11.6) Power input W 2,080 (410 – 2,410) Power factor % 89 C.O.P. W/W 2.5 Compressor locked rotor amperes A
PerformanceElectrical Rating
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
6
Indoor unit SAP-KMV91G ´ 3 Outdoor unit SAP-CMV2441G
No. of Indoor Units 3-unit type Power Source 220 – 230V ~ 50Hz
Cooling
Capacity
kW 6.45 (1.5 – 6.9)
BTU/h 22,000 (5,100 – 23,500) Air circulation (High) m3/h 1,290 Moisture removal (High) Liters/h 3.9 Voltage rating V 230 Available voltage range V 198 – 253 Running amperes A 11.7 (2.3 – 15.2) Power input W 2,430 (430 – 3,190) Power factor % 90 C.O.P. W/W 2.7 Compressor locked rotor amperes A
PerformanceElectrical Rating
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Indoor unit SAP-KMV91G ´ 2 + KMV181G Outdoor unit SAP-CMV2441G
No. of Indoor Units 3-unit type Power Source 220 – 230V ~ 50Hz
Cooling
Capacity
kW 6.9 (2.3 – 7.5)
BTU/h 23,500 (7,800 – 25,600) Air circulation (High) m3/h 1,640 Moisture removal (High) Liters/h 5.3 Voltage rating V 230 Available voltage range V 198 – 253 Running amperes A 11.6 (3.4 – 15.8) Power input W 2,400 (620 – 3,310) Power factor % 90 C.O.P. W/W 2.9 Compressor locked rotor amperes A
PerformanceElectrical Rating
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
7
Indoor unit SAP-KMV91G ´ 4 Outdoor unit SAP-CMV2441G
No. of Indoor Units 4-unit type Power Source 220 – 230V ~ 50Hz
Cooling
Capacity
kW 7.0 (2.2 – 7.6)
BTU/h 23,900 (7,500 – 25,900) Air circulation (High) m3/h 1,720 Moisture removal (High) Liters/h 5.2 Voltage rating V 230 Available voltage range V 198 – 253 Running amperes A 11.9 (3.3 – 15.7) Power input W 2,450 (600 – 3,300) Power factor % 90 C.O.P. W/W 2.9 Compressor locked rotor amperes A
PerformanceElectrical Rating
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Indoor unit SAP-KMV91G ´ 3 + KMV181G Outdoor unit SAP-CMV2441G
No. of Indoor Units 4-unit type Power Source 220 – 230V ~ 50Hz
Cooling
Capacity
kW 7.2 (3.3 – 8.0)
BTU/h 24,600 (11,300 – 27,300) Air circulation (High) m3/h 2,070 Moisture removal (High) Liters/h 6.6 Voltage rating V 230 Available voltage range V 198 – 253 Running amperes A 11.4 (5.0 – 16.5) Power input W 2,360 (890 – 3,460) Power factor % 90 C.O.P. W/W 3.1 Compressor locked rotor amperes A
PerformanceElectrical Rating
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
8
2-3. Major Component Specifications
Indoor unit SAP-KMV91G
Part No. POW-KMV91G Controls Microprocessor Control circuit fuse 250V – 3.15A
Remote Control Unit RCS-1MPS4E
Type Cross-flow Q’ty … Dia. and Length mm 1 … ø95 / L617 Fan motor model … Q’ty UF4-21B5PA-S … 1 No. of poles … rpm (230V, High) 4 … 1,350 Nominal output W 20 Coil resistance ½ BRN – WHT: 402
(Ambient temp. 20°C)
PNK – WHT: 506
Run capacitor
µF
VAC
Controller
PCB
Fan & Fan Motor
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Indoor unit SAP-KMV181G
Part No. POW-KMV181G Controls Microprocessor Control circuit fuse 250V – 3.15A
Remote Control Unit RCS-1MPS4E
Type Cross-flow Q’ty … Dia. and Length mm 1 … ø88 / L617 Fan motor model … Q’ty UF2-31A5P-S … 1 No. of poles … rpm (230V, High) 2 … 1,440 Nominal output W 30 Coil resistance ½ BRN – WHT: 130
(Ambient temp. 20°C)
WHT – PNK: 170
Run capacitor
µF 2.0
VAC 440
Controller
PCB
Fan & Fan Motor
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Part No. POW-CMV2441G (B) Control circuit fuse 250V – 3A Type Rotary (hermetic) Compressor model … Q’ty C-7RV113H0W … 1 / 80831080 Nominal output W 700 Compressor oil … Amount cc SUNISO 4GSD-T … 600 Coil resistance ½ C – R: 0.684 (Ambient temp. 25°C) C – S: 0.686 Run capacitor µF
… Q’ty VAC — Type Propeller Q’ty … Dia. mm 1 … ø400 Fan motor model … Q’ty KFG6S-41B5P … 1 No. of poles … rpm (230V, High) 6 … 720 Nominal output W 40
½ WHT – BRN: 150
Coil resistance WHT – YEL: 89
YEL – PNK: 166
Run capacitor
µF 2.0
VAC 440
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
CompressorFan & Fan Motor
Controller
PCB
Outdoor unit SAP-CMV2441G
9
2-4. Other Component Specifications
Indoor unit SAP-KMV91G and SAP-KMV181G
Thermistor (Coil sensor) DTN-TKS150Y
Resistance k½ 25°C 58.3
Thermistor (Room sensor) DTN-TKS150Y
Resistance k½ 25°C 5.0±3%
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Thermistor (Air sensor) PBC-41E-S14
Resistance k½ 0°C 15
Thermistor (Compressor sensor) PTC-51H-S1
Resistance k½ 50°C 20
Thermistor (Electric exp. valve sensor) PBC-41E-S25
Resistance k½ 0°C 15
PTC Thermistor (TH) 912X24E400XR-A
Resistance ½ (at 25°C) 40
Outdoor unit SAP-CMV2441G
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
10
790
250
174 (3)
Narrow tube ø6.35 (1/4")
Wide tube ø9.52 (3/8")
Drain hose ø18
58.5
132
41.0
41.0
Center of tubing hole (2 places)
Remote control unit
23
61
182
3. DIMENSIONAL DATA
Indoor unit SAP-KMV91G
Unit: mm
11
Indoor unit SAP-KMV181G
28545
995
45
147.5 147.5
196 (3)
Remote control unit
Center of tubing hole (2 places)
Narrow tube ø6.35 (1/4")
Drain hose ø18
Wide tube ø12.7 (1/2")
23
61
182
Unit: mm
12
Outdoor unit SAP-CMV2241G
963 963
609
Air discharge
Air intake
Air intake
136 35
625
30072.5
334
310
16
125
8
Narrow tube service valve 4-ø6.35 (1/4") Wide tube service valve 3-ø9.52 (3/8") Wide tube service valve 1-ø12.7 (1/2")
83.0
Service valve narrow tube
Service valve wide tube
Service valve narrow tube
Service valve wide tube
1/4" (ø6.35) 3/8" (ø9.52)
Unit A
1/4" (ø6.35) 3/8" (ø9.52)
Unit B
1/4" (ø6.35) 3/8" (ø9.52)
Unit C
1/4" (ø6.35) 1/2" (ø12.7)
Unit D
SAP-KMV91G
SAP-KMV181G or SAP-KMV91G*
* A tube joint (ø12.7 to 9.52) is needed
when SAP-KMV91G is installed. Please consult your dealer or installer.
Unit: mm
13
4. FREQUENCY CHARTS
4-1. Cooling Capacity
Indoor unit SAP-KMV91G and SAP-KMV181G Outdoor unit SAP-CMV2441G
1) Rating conditions in cooling and heating mode are: Cooling Indoor: 27°C D.B. / 19°C W.B.
Outdoor: 35°C D.B. / 24°C W.B.
2) Fan speed: High
NOTE
0
0 20 40 60 80 100 120 140 160
1
2
3
4
5
6
7
Operating frequency (Hz)
Cooling capacity (kW)
15 5242
2.6
0
0 20 40 60 80 100 120 140 160
1
2
3
4
5
6
7
Operating frequency (Hz)
Cooling capacity (kW)
15 9073
5.2
Single-unit operation
SAP-KMV91G
SAP-KMV181G
14
1) Rating conditions in cooling and heating mode are: Cooling Indoor: 27°C D.B. / 19°C W.B.
Outdoor: 35°C D.B. / 24°C W.B.
2) Fan speed: High
NOTE
Two-unit operation
SAP-KMV91G ´ 2
SAP-KMV91G + SAP-KMV181G
0
0 20 40 60 80 100 120 140 160
1
2
3
4
5
6
7
Operating frequency (Hz)
Cooling capacity (kW)
15 8570
5.1
0
0 20 40 60 80 100 120 140 160
1
2
3
4
5
6
7
Operating frequency (Hz)
Cooling capacity (kW)
15 85
6.5
15
1) Rating conditions in cooling and heating mode are: Cooling Indoor: 27°C D.B. / 19°C W.B.
Outdoor: 35°C D.B. / 24°C W.B.
2) Fan speed: High
NOTE
Three-unit operation
SAP-KMV91G ´ 3
SAP-KMV91G ´ 2 + SAP-KMV181G
0
0 20 40 60 80 100 120 140 160
1
2
3
4
5
6
7
Operating frequency (Hz)
Cooling capacity (kW)
15 81
6.45
0
0 20 40 60 80 100 120 140 160
1
2
3
4
5
6
7
8
Operating frequency (Hz)
Cooling capacity (kW)
22 77
6.9
16
1) Rating conditions in cooling and heating mode are: Cooling Indoor: 27°C D.B. / 19°C W.B.
Outdoor: 35°C D.B. / 24°C W.B.
2) Fan speed: High
NOTE
Four-unit operation
SAP-KMV91G ´ 4
SAP-KMV91G ´ 3 + SAP-KMV181G
0
0 20 40 60 80 100 120 140 160
1
2
3
4
5
6
7
8
Operating frequency (Hz)
Cooling capacity (kW)
22
0
0 20 40 60 80 100 120 140 160
1
2
3
4
5
6
7
8
Operating frequency (Hz)
Cooling capacity (kW)
7.2
73
17
4-2. Frequency Characteristics
230V, 50Hz
Cooling mode
90
80
70
70
60
50
40
30
20
60
50
40
30
20
10
A
Sound pressure level (dB)
C 31.5 63 125 250 500
1/1 Oct. Center frequency (Hz)
1000 2000 4000 8000
Hi Low
90
80
70
70
60
50
40
30
20
60
50
40
30
20
10
A
Sound pressure level (dB)
C 31.5 63 125 250 500
1/1 Oct. Center frequency (Hz)
1000 2000 4000 8000
Hi Low
90
80
70
70
60
50
40
30
20
60
50
40
30
20
10
A
Sound pressure level (dB)
C 31.5 63 125 250 500 1000 2000 4000 8000
1/1 Oct. Center frequency (Hz)
Hi
SAP-KMV91G
SAP-CMV2441G
SAP-KMV181G
18
5. AIR THROW DISTANCE CHARTS
Indoor unit SAP-KMV91G
Room air temp.: 27°C Fan speed: High
1
2
3
4
123456789
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
: Flap angle 0¡ : Axis air velocity 0¡ : Flap angle 30¡ : Axis air velocity 30¡
Indoor unit SAP-KMV181G
Room air temp.: 27°C Fan speed: High
1
2
3
4
123456789
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
: Flap angle 0¡ : Axis air velocity 0¡ : Flap angle 30¡ : Axis air velocity 30¡
19
6. REFRIGERANT FLOW DIAGRAM
Indoor unit SAP-KMV91G ´ 3 + SAP-KMV181G or SAP-KMV91G ´ 4 Outdoor unit SAP-CMV2441G
M
M
M
M
M
Main electric
expansion valve
Wide tube side nipple ø12.7
Nipple
ø9.52
Tube joint
(ø12.79.52)
*
Where a tube joint is used
(KMV181KMV91)
Outdoor unit Indoor unit
Muffler
Main
accumulator
Secondary
accumulator
Compressor
Muffler
EC
P
Outdoor heat exchanger
Narrow tube service valve
Wide tube service valve
Wide tube side nipple
Wide tube side nipple
Wide tube side nipple
Wide tube side nipple
ø9.52
ø9.52
ø9.52
Narrow tube side nipple
Narrow tube side nipple
Narrow tube side nipple
Narrow tube side nipple
ø6.35
ø6.35
ø6.35
ø6.35
ø12.7
A
B
C
*
D
A
B
C
D
Heat Exchenger (A)
(B)
(C)
(D)
Electric expansion valve
Electric expansion valve
Electric expansion valve
Electric expansion valve
A
B
D
C
Cooling cycle and defrosting cycle
Receiver
tank
Insulation of Refrigerant Tubing
To prevent heat loss and wet floors due to dripping of condensa­tion water, both the wide and narrow tubes must be well insu- lated with a proper insulation material. The thickness of the insulation should be a minimum 8 mm.
IMPORTANT
CAUTION
After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack.
Wide tube
Thickness: Min. 8 mm
Insulation
Narrow tube
Thickness: Min. 8 mm
Unit: mm
20
7. ELECTRICAL DATA
7-1. Electrical Characteristics
The values in the table below indicate the sum of indoor and outdoor units during normal running condition.
Set electric current suppressor to either “FREE/11/8.5A”.
230V Single-phase 50Hz
Rating conditions: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B.
Full load conditions: Indoor air temperature 32°C D.B. / 23°C W.B. Outdoor air temperature 43°C D.B.
Indoor unit SAP-KMV91G Outdoor unit SAP-CMV2441G
Under “FREE” setting
NOTE
Number of indoor units
1 unit
KMV91G
Rating conditions
Running amp. A 5.9 Power input kW 1,070
Full load conditions
Running amp. A 7.1 Power input kW 1,300
Number of indoor units
1 unit
KMV181G
Rating conditions
Running amp. A 10.3 Power input kW 2,120
Full load conditions
Running amp. A 12.5 Power input kW 2,580
Indoor unit SAP-KMV181G Outdoor unit SAP-CMV2441G
Number of indoor units
2 units
KMV91G ´ 2
Rating conditions
Running amp. A 10.2 Power input kW 2,080
Full load conditions
Running amp. A 12.3 Power input kW 2,530
Indoor unit SAP-KMV91G ´ 2 Outdoor unit SAP-CMV2441G
Number of indoor units
2 units
KMV91G + KMV181G
Rating conditions
Running amp. A 12.4 Power input kW 2,570
Full load conditions
Running amp. A 15.0 Power input kW 3,120
Indoor unit SAP-KMV91G + KMV181G Outdoor unit SAP-CMV2441G
Loading...