Sanyo SAP-CMRV3656EH Technical & Service Manual

TECHNICAL & SERVICE MANUAL
OUTDOOR UNIT : SAP-CMRV3656EH
SAP-CMRV3656EH
DC INVERTER MULTI-SYSTEM AIR CONDITIONER
Outdoor Model No.
SAP-CMRV3656EH-F
Capacity
Product Code No.
1 852 355 48
REFERENCE NO. SM700847
< Applicable Indoor Units >
Wall mounted type
For details about the combination, refer to "Unit Combination Table" in the Appendix of this manual.
SAP-KRV96EHDSA SAP-KRV126EHDS
NOTE
SAP-KMRV76EH SAP-KMRV96EH SAP-KMRV126EH SAP-KRV186EH SAP-KRV246EH
Destination: Europe
RoHS
WARNING
This product does not contain any hazardous substances prohibited by the RoHS Directive.
• You are requested to use RoHS compliant parts for maintenance or repair.
• You are requested to use lead-free solder.
Do not vent R410A into atmosphere : R410A is a fluorinated greenhouse gas, covered by Kyoto Protocol, with a Global Warming Potential (GWP) = 1975.
F-GAS REGULATION (EC) No 842 / 2006
FILE NO.
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
SPECIAL PRECAUTIONS
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
CAUTION
CAUTION
WARNING
WARNING
Important! Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning. Follow each installation or repair step exactly as shown. Observe all local, state, and national electrical codes. Pay close attention to all warning and caution notices given in this manual.
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for
a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked. Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and
inadequate grounding can cause accidental injury or
death. Ground the unit following local electrical codes. Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard. Install a protective leakage breaker depending on the installation location (especially a damp or humid location). If a leakage breaker is not installed, electric shock can occur.
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing
In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the unit’s weight. It may be necessary to construct a strong wood or metal frame to provide added support.
In a Room
Properly insulate any tubing run inside a room to prevent "sweating" that can cause dripping and water damage to walls and floors.
In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
In a Snowy Area
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
Use the flare method for connecting tubing. Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then
tighten the nut with a torque wrench for a leak-free
connection. Check carefully for leaks before starting the test run.
When Servicing
Turn the power off at the main power box (mains) before opening the unit to check or repair electrical parts and wiring. Keep your fingers and clothing away from any moving parts. Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
Others
Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas. Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.
2
Table of Contents
APPLICABLE INDOOR UNITS
1. OPERATING RANGE
2. SPECIFICATIONS
2-1. Unit Specifications 2-2. Major Component Specifications 2-3. Other Component Specifications
3. DIMENSIONAL DATA
4. REFRIGERANT FLOW DIAGRAM
4-1. Refrigerant Flow Diagram
5. PERFORMANCE DATA
5-1. Te mperature Charts
6. ELECTRICAL DATA
6-1. Electric Wiring Diagrams
7. FUNCTIONS
7-1. Explanation of Functions 7-2. Protective Functions 7-3. Special Functions
8. TROUBLESHOOTING
8-1. Precautions before Performing Inspection or Repair 8-2. Self-Diagnostics 8-3. Checking the Outdoor System 8-4. Trouble Diagnosis of Each Part 8-5. Trouble Diagnosis of Fan Motor
9. REFRIGERANT R410A: SPECIAL PRECAUTIONS WHEN SERVICING UNIT
9-1. Characteristics of New Refrigerant R410A 9-2. Checklist before Servicing 9-3. Tools Specifically for R410A 9-4. Tubing Installation Procedures 9-5. In Case of Compressor Malfunction 9-6. In Case Refrigerant is Leaking 9-7. Charging Additional Refrigerant 9-8. Retro-Fitting Existing Systems
5
6
7 8 9
10
11
12
17
18 22 25
27 28 30 31 34
35 35 37 37 38 40 41 41
....................................................................................................
...................................................................................................................
.............................................................................................................
.......................................................................................
.......................................................................................
...................................................................................................................
...................................................................................................
............................................................................................................
....................................................................................................
....................................................................................................
...........................................................................................................
...............................................................................................................
...........................................................
..................................................................................................................
............................................................................................
..........................................................................................
..........................................................................................
.........................................................................
...................................................................................................
................................................................................................
............................................................................................
....................................................................................
............................................................................................
..........................................................................................
............................................................................................
Page
3
APPENDIX AINSTALLATION INSTRUCTIONS
APPENDIX BUNIT COMBINATION TABLES
A-1
A-2
.............................................................................
.................................................................................
Page
4
APPLICABLE INDOOR UNITS
SAP-CMRV3656EH
Multi-Outdoor Unit
Indoor Unit
YES YES YES YES YES5-Room
SAP­KMRV76EH
SAP­KMRV96EH
SAP­KMRV126EH
SAP­KRV186EH
SAP­KRV246EH
SAP-CMRV3656EH
Multi-Outdoor Unit
Indoor Unit
YES YES5-Room
SAP­KRV96EHDSA
SAP­KRV-126EHDS
NOTE
1. The table lists the wall-mounted type of indoor units as representative models.
2. For details on the applicable indoor units other than the wall-mounted type, refer to the catalog.
5
1. OPERATING RANGE
Maximum
Minimum
Maximum
Minimum
32 °C D.B. / 23 °C W.B.
19 °C D.B. / 14 °C W.B.
27 °C D.B.
16 °C D.B.
43 °C D.B.
-
10 °C D.B.
24 °C D.B. / 18 °C W.B. _
D.B. /
-
15 °C W.B.
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Outdoor Unit:SAP-CMRV3656EH Indoor Unit :SAP-KMRV76EH, SAP-KMRV96EH, SAP-KMRV126EH
 SAP-KRV186EH, SAP-KRV246EH  SAP-KRV96EHDSA, SAP-KRV126EHDS
6
2. SPECIFICATIONS
2-1. Unit Specifications
Outdoor Unit SAP-CMRV3656EH Indoor Unit SAP-KMRV76EH
× 5
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks:
1. The values shown in perfromance section and electrical rating section above are based on the following unit combination.
For other combination unit, please refer to the "Unit Combination Table" in this manual.
Indoor Unit: SAP-KMRV76EH 5units Outdoor Unit: SAP-CMRV3656EH 1unit
2. Rating conditions are: Cooling: Indoor air temp. 27°C D.B. / 19°C W.B. Outdoor air temp.35°C D.B. / 24°C W.B.
Heating: Indoor air temp.20°C D.B.
Outdoor air temp.7°C D.B. / 6°C W.B.
Operation Sound Hi dB-A
Refrigerant Control
( 4.0 to 14.5 ) ( 13,600 to 49,500 )
12.6
2,860
12.6
2,860
10.0
34,100
12.0
40,900
( 3.5 to 11.5 ) ( 11,900 to 39,200 )
Shipping Volume
Cooling Heating
Cooling Heating
Net Shipping
Weight
Height
× Width × Depth
kg kg
m
3
mm
230V
198 to 264
Dimensions & Weight (Outdoor Unit)
Refrigerant Tubing Connections
Unit Dimensions
Electrical Rating
Air Circulation (High)
WPower Input
V A
Available Voltage Range Running Amperes
Narrow tube Wide tube
Refrigerant mm (in.)
Tube Diameter mm (in.)
97.0
103.0
0.50
910
× 940 × 340
6.35 (1/4")
× 5
9.52 (3/8")
× 3 + 12.7 (1/2") × 2
mMax. allowable tubing length per unit
Flare Type
30
Electric Expansion Valve
Compressor Refrigerant / Amount charged at shipment kg
DC Twin Rotary (Inverter)
R410A / 4.1
Controls Fan Speeds
Microprocessor
Auto (Hi / Variable)
Features (Outdoor Unit)
C.O.P. Compressor Locked Rotor Amperes
W/W
kW
Performance
- 4.20
50 53
%Power Factor 99 99
A 19.5
Type
Voltage Rating
BTU/h
Capacity
m
3
/h
5-Room Multi Outdoor Unit
E.E.R. W/W 3.50 -
Number of Connectable Indoor Units 5
Number of Operatable Indoor Units 5
Max. Capacity of Operating Indoor Units kW 17.55
Power Source 220 to 240V Single-Phase 50Hz
Height × Width × Depth mm
Package Dimensions
1,031 × 1,086 × 448
7
P.C.Board
Circuit Fuse
Controls
Part No.
Microprocessor
400V 3.15A
CB-CMRV3656EH
Control P.C.B
-
250V 25A
POW-CMRV3656EH-B1
Noise Filter P.C.B
-
-
POW-CMRV3656EH-C1
H.I.C.Board
1 ... D490
Propeller
DC Motor
SIC-71FW-D881-1 ... 1
8
-
81
750 / 700
Internal Controller
Yes Yes
-
-
Aluminum Plate Fin / Copper Tube
2
1.2
0.792
Fan
Q'ty ... Dia.
Type
mm
Fan Motor
Nominal Output Coil Resistance
Rough Measure RPM (Cool:Hi / Heat:Hi)
Type Model ... Q'ty No. of Poles
Safety Device
Type Over- Current Protection Over- Heat Protection
(Ambient Temp. 20 °C)
Run Capacitor Micro F
VAC
W
Ohm
Face Area
Coil
Rows Fin Pitch
Heat Exchanger Coil
m
2
mm
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
2-2. Major Component Specifications
2-2-1. Outdoor Unit
Outdoor Unit SAP-CMRV3656EH
C-9RVN273H0H / 2,700W
DC Twin Rotary (Hermetic)
Compressor
Compressor Model / Nominal Output
Type
FV68S ... 1,400Compressor Oil ... Amount CC
T - R:0.169Coil Resistance (Ambient Temp. 25 °C) Ohm T - S:0.169 R - S:0.169
Safety Device
YesCT (Peak current cut-off control) YesCompressor Discharge Temp. Control Yes
Operation cut-off control in abnormal ambient Temp.
CS-7LOverload Relay
Open : 115 °C, Close : 100 °C
Model
Operation Temp.
-Run Capacitor
-
Micro F
VAC
230V 25WCrankcase Heater
Acrylic baked-on enamel finishExternal Finish
8
2-3. Other Component Specifications
0
0102030405060708090
40
60
80
100
120
140
160
180
200
20
Resistance (k ohm)
Temperature (°C)
40
35
30
25
20
15
10
5
0
-20-15-
10-50 5101520
Temperature (°C)
Resistance (k ohm)
Outdoor air temp sensor
Outdoor heat exchanger sensor
AW / AN sensor
BW / BN sensor
CW / CN sensor
DW / DN sensor
EW / EN sensor
TKS295B
TKS334B
TKS334B
TKS334B
TKS334B
TKS334B
TKS334B
Model No.
of sensor
Sensor Name
1
1
1/1
1/1
1/1
1/1
1/1
Quantity of Sensor
SAP­CMRV3656EH
Compressor temp sensor TKS335B
Model No.
of sensor
Sensor Name
1
Quantity of Sensor
SAP­CMRV3656EH
9
Unit: mm (852-0-0010-18600-0)
3. DIMENSIONAL DATA
Outdoor Unit SAP-CMRV3656EH
AIR INTAKE
600
ID:18
5-ID:23.6
940 80
51 110
43
341
376
410
347
170
16
AIR DISCHARGE
AIR INTAKE
30
910
168 75 75 75 75
131 75 75 75 75
Wide tube service valve
dia.12.70 (1/2")
× 2
Wide tube service valve
dia.9.52 (3/8")
× 3
Narrow tube service valve
dia.6.35 (1/4")
× 5
10
Outdoor Unit SAP-CMRV3656EH
Insulation of Refrigerant Tubing
Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min. 8 mm.
After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack.
Wide tube
Thickness: Min. 8 mm
Insulation
Narrow tube
Thickness: Min. 8 mm
IMPORTANT
CAUTION
Compressor
4-way valve
Muffler
Main accumulator
Sub accumulator
Service valve on narrow tube
Service valve on wide tube
Wide tube
EN
DN
CN
BN
AN
EW
DW
CW
BW
AW
O.D.12.7mm
O.D.12.7mm
O.D.9.52mm
O.D.9.52mm
O.D.9.52mm
Narrow tube O.D.6.35mm
O.D.6.35mm
O.D.6.35mm
O.D.6.35mm
O.D.6.35mm
Heat exchanger
Cooling cycle
Heating cycle
Defrosting cycle
Indoor unit Outdoor unit
Defrost valve for hot gas bypass
Receiver tank
Strainer
S
M
M
M
Electric expansion valve
Header
Header
M
M
4. REFRIGERANT FLOW DIAGRAM
4-1. Refrigerant Flow Diagram
11
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan) (230V, 50Hz)
Heating Characteristics
(RH : 85%, Indoor fan speed : High fan) (230V, 50Hz)
(1) Low pressure performance chart (1) High pressure performance chart
(2) Operating current performance chart (2) Operating current performance chart
(3) Indoor discharge air performance chart (3) Indoor discharge air performance chart
• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type.
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.(In this case, be sure to stop all the indoor units where performance is not being checked.)
• The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary.
NOTE
Outdoor air temperature (°C) Outdoor air temperature (°C)
30 35 4025
Lo fan Mid fanHi fan
-5 0510 15 20 25
Operating current (A)
Operating current (A)
Outdoor air temperature (°C) Outdoor air temperature (°C)
30 35 40
4
5
3
25
-5 0510 15 20 25
8
9
7
6
5
4
Indoor discharge air temperature (°C)
Indoor discharge air temperature (°C)
Outdoor air temperature (°C) Outdoor air temperature (°C)
5
-5 0510 15 20 25
55
50
45
40
35
30
25
20
20
°
C
17
°
C
Indoor air temp.23
°
C
Indoor air temp.23°C
20°C
17°C
30 35 40
25
20
15
10
25
27
°
C
24
°
C
Indoor air temp.30
°C
Indoor air temp.30°C
27°C
24°C
20°C
17°C
24°C
27
°
C
24
°
C
Indoor air temp.30
°
C
Indoor air temp.30°C
27°C
24°C
20
°
C
17
°
C
Indoor air temp.23
°
C
Indoor air temp.23°C
20°C
17°C
27°C
Indoor air temp.30
°
C
Indoor air temp.30°C
Indoor air temp.23
°
CIndoor air temp.23°C
Low pressure at wide tube service valve
MPaG (kgf/cm
2
G)
High pressure at wide tube service valve
MPaG (kgf/cm
2
G)
1.0
(10.2)
1.2
(12.2)
0.8
(8.2)
0.6
(6.2)
3.5
(35.7)
3.0
(30.6)
2.5
(25.5)
2.0
(20.4)
1.5
(15.3)
5. PERFORMANCE DATA
5-1. Temperature Charts
Outdoor Unit SAP-CMRV3656EH Indoor Unit SAP-KMRV76EH × 1
Lo fan Mid fanHi fan
Lo fan Mid fanHi fan
12
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan) (230V, 50Hz)
Heating Characteristics
(RH : 85%, Indoor fan speed : High fan) (230V, 50Hz)
(1) Low pressure performance chart (1) High pressure performance chart
(2) Operating current performance chart (2) Operating current performance chart
(3) Indoor discharge air performance chart (3) Indoor discharge air performance chart
• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type.
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.(In this case, be sure to stop all the indoor units where performance is not being checked.)
• The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary.
NOTE
Outdoor air temperature (°C) Outdoor air temperature (°C)
30 35 4025
Lo fan Mid fanHi fan
-5 0510 15 20 25
Operating current (A)
Operating current (A)
Outdoor air temperature (°C) Outdoor air temperature (°C)
30 35 40
4
5
3
25
-5 0510 15 20 25
7
8
6
5
4
Indoor discharge air temperature (°C)
Indoor discharge air temperature (°C)
Outdoor air temperature (°C) Outdoor air temperature (°C)
5
-5 0510 15 20 25
55
50
45
40
35
30
25
20
20
°
C
17
°
C
Indoor air temp.23
°
C
Indoor air temp.23°C
20°C
17°C
30 35 40
25
20
15
10
25
27
°
C
24
°
C
Indoor air temp.30
°C
Indoor air temp.30°C
27°C
24°C
Indoor air temp.23
°
C
Indoor air temp.23°
C
20°C
17°C
24°C
27
°
C
24
°
C
Indoor air temp.30
°
C
Indoor air temp.30°C
27°C
24°C
Indoor air tem
p.23
°
C
Indoor air tem
p.23°C
Outdoor Unit SAP-CMRV3656EH Indoor UnitSAP-KMRV96EH × 1 or SAP-KRV96EHDSA × 1
Indoor air temp.30
°
C
Indoor air temp.30°C
27°C
Low pressure at wide tube service valve
MPaG (kgf/cm
2
G)
High pressure at wide tube service valve
MPaG (kgf/cm
2
G)
1.0
(10.2)
1.2
(12.2)
0.8
(8.2)
0.6
(6.2)
3.5
(35.7)
3.0
(30.6)
2.5
(25.5)
2.0
(20.4)
1.5
(15.3)
Lo fan Mid fanHi fan
Lo fan Mid fanHi fan
17
°
C
17°C
20°C20°C
13
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan) (230V, 50Hz)
Heating Characteristics
(RH : 85%, Indoor fan speed : High fan) (230V, 50Hz)
(1) Low pressure performance chart (1) High pressure performance chart
(2) Operating current performance chart (2) Operating current performance chart
(3) Indoor discharge air performance chart (3) Indoor discharge air performance chart
• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type.
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.(In this case, be sure to stop all the indoor units where performance is not being checked.)
• The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary.
NOTE
Outdoor air temperature (°C) Outdoor air temperature (°C)
30 35 4025
-5 0510 15 20 25
Operating current (A)
Operating current (A)
Outdoor air temperature (°C) Outdoor air temperature (°C)
30 35 40
4
5
6
3
25
-5 0510 15 20 25
12
13
10
11
9
8
7
Indoor discharge air temperature (°C)
Indoor discharge air temperature (°C)
Outdoor air temperature (°C) Outdoor air temperature (°C)
5
-5 0510 15 20 25
55
50
45
40
35
30
25
20
20
°
C
17
°C
Indoor air temp.23
°
C
Indoor air temp.23°C
20°C
17°C
30 35 40
25
20
15
10
25
27
°
C
24
°
C
27°C
24°C
Indoor air temp.23
°
C
Indoor air temp.23°C
20°C
17°C
24°C
27
°
C
24
°
C
Indoor air temp.30
°
C
Indoor air temp.30°C
27°C
24°C
Indoor air temp.23
°
C
Indoor air temp.23°C
Outdoor Unit SAP-CMRV3656EH
Indoor air temp.30
°
C
Indoor air temp.30°C
27°C
Low pressure at wide tube service valve
MPaG (kgf/cm
2
G)
High pressure at wide tube service valve
MPaG (kgf/cm
2
G)
1.0
(10.2)
1.2
(12.2)
0.8
(8.2)
0.6
(6.2)
3.5
(35.7)
3.0
(30.6)
2.5
(25.5)
2.0
(20.4)
1.5
(15.3)
Lo fan Mid fanHi fan
Lo fan Mid fanHi fan
Lo fan Mid fanHi fan
Indoor air temp.30
°C
Indoor air temp.30°C
17
°
C
17°C
20°C20°C
Indoor UnitSAP-KMRV126EH × 1 or SAP-KRV126EHDS × 1
14
30 35 4025
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan) (230V, 50Hz)
Heating Characteristics
(RH : 85%, Indoor fan speed : High fan) (230V, 50Hz)
(1) Low pressure performance chart
(2) Operating current performance chart
(3) Indoor discharge air performance chart
• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type.
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.(In this case, be sure to stop all the indoor units where performance is not being checked.)
• The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary.
NOTE
Outdoor air temperature (°C)
Mid fanHi fan
Operating current (A)
Outdoor air temperature (°C)
30 35 40
6
5
7
8
9
4
25
Indoor discharge air temperature (°C)
Outdoor air temperature (°C)
5
30 35 40
25
20
15
10
25
27
°
C
24
°
C
Indoor air tem
p.30
°C
Indoor air tem
p.30°C
27°C
24°C
24°C
27
°
C
24
°
C
Indoor air te
mp.30
°
C
Indoor air te
mp.30°C
27°C
24°C
Outdoor Unit SAP-CMRV3656EH Indoor Unit SAP-KRV186EH × 1
Mid fanHi fan
Indoor air temp.30
°
C
Indoor air temp.30°C
Mid fanHi fan
27°C
Low pressure at wide tube service valve
MPaG (kgf/cm
2
G)
1.0
(10.2)
1.2
(12.2)
0.8
(8.2)
0.6
(6.2)
-5 0510 15 20 25
60
55
50
45
40
35
30
25
Indoor air temp.23
°
C
Indoor air temp.23°C
(1) High pressure performance chart
(2) Operating current performance chart
(3) Indoor discharge air performance chart
Outdoor air temperature (°C)
-5 0510 15 20 25
Operating current (A)
Outdoor air temperature (°C)
-5 0510 15 20 25
14
12
13
15
Indoor discharge air temperature (°C)
Outdoor air temperature (°C)
20
°C
17
°
C
20°C
17°C
Indoor air temp.23
°
C
Indoor air temp.23°C
20°C
17°C
High pressure at wide tube service valve
MPaG (kgf/cm
2
G)
3.5
(35.7)
3.0
(30.6)
2.5
(25.5)
2.0
(20.4)
1.5
(15.3)
20
°
C
17
°
C
Indoor air temp.23
°
C
Indoor air temp.23°C
20°C
17°C
15
-5 0510 15 20 25
60
55
50
45
40
35
30
25
Indoor air temp.23
°
C
Indoor air temp.23°C
30 35 4025
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan) (230V, 50Hz)
Heating Characteristics
(RH : 85%, Indoor fan speed : High fan) (230V, 50Hz)
(1) Low pressure performance chart (1) High pressure performance chart
(2) Operating current performance chart (2) Operating current performance chart
(3) Indoor discharge air performance chart (3) Indoor discharge air performance chart
• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type.
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.(In this case, be sure to stop all the indoor units where performance is not being checked.)
• The performance is for a tubing length of 7.5 m. If the tubing length is different, the performance chart will vary.
NOTE
Outdoor air temperature (°C) Outdoor air temperature (°C)
Mid fanHi fan
-5 0510 15 20 25
Operating current (A)
Outdoor air temperature (°C)
30 35 40
9
8
10
11
12
25
Indoor discharge air temperature (°C)
Indoor discharge air temperature (°C)
Outdoor air temperature (°C) Outdoor air temperature (°C)
5
20
°C
17
°
C
20°C
17°C
30 35 40
25
20
15
10
25
27
°
C
24
°
C
Indoor air temp.30
°C
Indoor air temp.30°C
27°C
24°C
Indoor air temp.23
°
C
Indoor air temp.23°C
20°C
17°C
27
°
C
24
°
C
Indoor air tem
p.30
°
C
Indoor air tem
p.30°C
27°C
24°C
Outdoor Unit SAP-CMRV3656EH Indoor Unit SAP-KRV246EH × 1
Mid fanHi fan
Indoor air temp.30
°
C
Indoor air temp.30°C
Mid fanHi fan
24°C
27°C
Low pressure at wide tube service valve
MPaG (kgf/cm
2
G)
High pressure at wide tube service valve
MPaG (kgf/cm
2
G)
1.0
(10.2)
1.2
(12.2)
0.8
(8.2)
0.6
(6.2)
3.5
(35.7)
3.0
(30.6)
2.5
(25.5)
2.0
(20.4)
1.5
(15.3)
Operating current (A)
Outdoor air temperature (°C)
-5 0510 15 20 25
14
12
13
15
20
°
C
17
°
C
Indoor air temp.23°
C
Indoor air temp.23°C
20°C
17°C
16
WARNING
To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts.
6. ELECTRICAL DATA
6-1. Electric Wiring Diagrams
Outdoor UnitSAP-CMRV3656EH
8FA2-5250-52600-3
BLK
1 1
2
123
4
123
4
123
4
123
4
567
8
567
8
9
10
4132110987654321
9
10
4
1
2
2
1
1
2
2
3
3
4
4
5
1 2 1 2 3 4 551 2 1 2 3
1 2 3
1 2 3
1 3
1 3
1 3
1 34 5
321109
1
2
1
2
1
2
1
2
3
4
3
4
55
8765432
1
2
+++
+
HIC- E
E1E2E3
HIC+
DC+
DC-
HIC- HIC+ DC+ DC-
BD2
+
+ + + +
w
w w
BD1
wL1w
L2
TH01
CN13
HIC-2
(WHT)
CN07
HIC-2
(WHT)
CN23
CT
(BRN)
POWER LED
ERROR MONITOR
F02
3.15A/400V (T3.15 AL400V)
ERR0
ERR1
ERR2
ERR2
CN06
A-B
(WHT)
DC- DC+ CN31
FM2
(RED)
FAN MOTOR
CRANKCASE
HEATER
DEFROST VALVE
COIL
4WAY VALVE
COIL
TERMINAL PLATE
TERMINAL (2P)
REACTOR
CN11
SI
(WHT)
CN30
FM1
(RED)
CN12
ACIN
(BLU)
CN08
HIC-1
(WHT)
CN16
OLR
(WHT)
CN05
MV-E
(YEL)
CN04
MV-D
(BLU)
(RED)
CN03
MV-C
(BLK)
CN02
MV-B
(WHT)
CN01
MV-A
(WHT)
CN17
T-RUN/TEST
(YEL)
CN28
TH-E
(BLU)
CN27
TH-D
(RED)
CN26
TH-C
(BLK)
CN25
TH-B
(WHT)
CN24
TH-A
(WHT)
CN22
COMP
(YEL)
CN21
GAIKI
(BLK)
CN20
COIL
CN12
HIC-1
(WHT)
W
T
R S
V U
HIC BOARD
CONTROL P.C.BOARD
ON
SW02
1 2
NOISE FILTER P.C.BOARD
w
w
+ + +
1
2
+
+ +
B02
(BRN)
CN02
CT
(WHT)
CN03
A-B
DCOUT- DCOUT+
w w
OUT1 OUT2
B01
REACTOR
FIN TEMPERATURE
THERMISTOR
FERRITE
CORE
MAGNETIC COIL
COMPRESSOR
MOTOR
OVERLOAD RELAY
(OLR)
M
MS
3~
BLU
BRN
YEL
GRY
WHT
BLK
WHT
WHT
WHT
WHT
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
WHT
WHT
BLK
BLK
BLK
BLK
BLK
BLK
RED
WHT
WHT
ORG
RED
YEL
BLK
GRY
1
2
1
1
1
2
2
3
3
4
4
5
5
2
3
4
3
4
55
MAGNETIC COIL
MAGNETIC
COIL
MAGNETIC
COIL
MAGNETIC
COIL
E-W THERMISTOR
E-N THERMISTOR
M
M
ORG
RED
YEL
BLK
GRY
WHT
RED
BLU
GRN
ORG
RED
YEL
BLK
GRY
1
1
2
2
3
3
4
4
5
5
M
ORG
RED
YEL
BLK
GRY
1
1
2
2
3 1 2 3
3
4
4
1
1
2
2
3
3
4
4
5
5
M
ORG
RED
YEL
BLK
GRY
M
BRN
WHT
ORG
RED
BLU
YEL
YEL
YEL
YEL
D-W THERMISTOR
D-N THERMISTOR
1
1
2
2
3
3
4
4
YEL
YEL
YEL
YEL
C-W THERMISTOR
C-N THERMISTOR
1
1
2
2
3
3
4
4
YEL
YEL
YEL
YEL
B-W THERMISTOR
B-N THERMISTOR
1
1
2
2
3
3
4
4
YEL
YEL
YEL
YEL
A-W THERMISTOR
A-N THERMISTOR
COMPRESSOR
THERMISTOR
OUTDOOR
THERMISTOR
COIL
THERMISTOR
1
1
2
2
3
3
4
4
YEL
YEL
1
1
2
2
BLK
BLK
1
1
2
2
BLK
BLK
1
1
2
2
11223344556677
YEL
YEL
YEL
YEL
1 3
1 3
CN13
HEATER
(ORG)
1 3
1 3
CN14SV(BLK)
1 3
1 3
CN15
RV
(WHT)
6 5
6 5
4 3
4 3
2 1
2 1
BLK
WHT
BRN
BRN
BLU
BLU
BLU
BLU
F01
25A/250V
(T25 AL250V)
GRNwGRNwGRN
w
ACIN1wACIN2 w
L
N
L
N
L1
L2
123
GRN
BLK
WHT
BLK
123
123
123
123
POWER
SUPPLY
1-230V 50Hz
TO INDOOR
UNIT No.E
CONNECTING
TO INDOOR
UNIT No.D
CONNECTING
TO INDOOR
UNIT No.C
CONNECTING
TO INDOOR
UNIT No.B
CONNECTING
TO INDOOR
UNIT No.A
CONNECTING
WHT
ORG
GRY
BRN
BLU
RED
GRN/YEL
ON
SW01
1 2
BLK
WHT
FERRITE
CORE
FERRITE
CORE
17
7. FUNCTIONS
7-1. Explanation of Functions
Control/conditions
INITIAL
Breaker is ON. Power is supplied to the indoor and outdoor unit
control circuits, however the unit remains stopped. Positioning of the outdoor unit electric expansion valve is performed.
The ON/OFF operation button on the remote controller is pressed.
If automatic operation mode has been selected with the remote controller, operation begins in
HEAT, SENSOR DRY, or COOL mode
depending on the room temperature and outdoor temperature at the time operation starts.
Depending on the operational mode, refer to the HEAT, SENSOR DRY, or COOL item.
This applies in the case of automatic HEAT/COOL operation.
HEAT
Unit operation Explanation
The ON/OFF operation button on the remote controller is pressed.
The unit is forced to stop for 5 minutes after the power is turned ON, or 5 minutes after the compressor stops, in order to protect the compressor.
The frequency is increased at the rate of 1 Hz
every 0.5 seconds.
Operation lamp illuminates.
Indoor fan is stopped to prevent cold air from being emitted.
Outdoor unit begins operating after forced-stop is canceled.
the compressor starts.
the outdoor fan starts.
This is in order to stabilize the return of oil to the compressor.
When the frequency reaches Hz,frequency
increases are stopped for a period of seconds.
(Refor to Table 2 "Freguency control".)
If the indoor and outdoor temperatures are high, the current peak cut-off activates, stopping any
increases in frequency.
The frequency then increases.
The thermostat turns OFF.
The outdoor unit stops. (It does not stop if the thermostat for another indoor unit is ON.)
Approximately 30 seconds after the thermostat turns OFF, the indoor fan is stopped.
The indoor fan is stopped.
The indoor and outdoor temperatures are high.
The outdoor unit starts automatically after 5 minutes.
During these 5 minutes, a low-pressure pressure balance is achieved, allowing the compressor to start more easily.
In order to protect the compressor, the outdoor unit will not operate for 5 minutes after the thermostat turns OFF, even if the room temperature drops below the desired temperature.
The room temperature has reached the desired temperature.
Operating frequency is stabilized in order to
maintain a comfortable environment.
The indoor temperature and the remote controller temperature setting are
approximately equal.
The thermostat turns ON. The unit operated before, and the temperature of
the indoor heat exchanger is relatively warm. Therefore,the fan speed may start at the set fan speed at the same time that the thermostat turns ON.
The indoor fan is started.
Depending on the relationship between the remote controller temperature setting and the room temperature, the compressor may stop temporarily (in other words, the thermostat may turn OFF).
When the indoor coil temperature rises, the indoor fan changes from "LL" to the set fan speed.
The amount of heat pump exceeds the amount of heat radiation from the room. Therefore, there is no need to further increase
the compressor capacity, and the frequency is
stabilized or lowered.
The frequency is not increased, even if
there is a difference between the room temperature and the desired temperature.
In some cases, the frequency may be
decreased.
18
Control/conditions
HEAT
When defrost operation begins, frost has formed on the outdoor unit (when the ambient air temperature is low).
Defrost operation begins based on outdoor heat exchanger temperature and outdoor air temperature conditions. Non-stop defrost (Refer to Fig. 1)
1. After HEAT operation begins, the temperature of the outdoor heat exchanger is at or below the L1 line for 48 minutes. (If outdoor air temperature is less than –3 °C, the time is 48 minutes)
2. After HEAT operation begins, the temperature of the outdoor heat exchanger is at or below the L2 line for 120 minutes.
The 4-way valve remains ON during defrost.
Non-stop defrost
Unit operation Explanation
The outdoor fan stops and the solenoid valve turns ON, allowing the refrigerant to bypass the indoor unit.
Indoor fan : Stopped
Outdoor fan : Stopped
Compressor : 70 Hz
Solenoid valve (for hot gas bypass): ON
4-way valve : Remains ON
Operation lamp : Red and orange ON
alternately
Defrost release Indoor fan turns ON.
After 10 seconds, the solenoid valve (for hot gas bypass) turns OFF.
When the cold air feel has disappeared, the indoor fan starts and gradually increases speed until it reaches the set speed.
STOP
[Clean defrost]
Defrost is performed when the outdoor unit is stopped, and the temperature of the outdoor unit coil is at or below the L1 line.
(Refer to Fig. 1.)
All indicator lamps turn OFF. The indoor and outdoor units stop.
The operating frequency during defrost is 70 Hz. (Frequency is lowered if the current
peak cut-off function is activated.)
The maximum length of a single defrost operation is 12 minutes.
For the outdoor heat exchanger temperature conditions for ending defrost, refer to Table 1.
Operation is restarted within 4 hours (only when AUTO mode is selected with the remote controller).
Within 4 hours after operation was stopped, it is assumed that there has been no significant change in the indoor and outdoor temperatures, and the previous conditions (HEAT) are stored.
Starts operating in the same operating mode (HEAT) and with the same temperature settings as before operation was stopped.
Operation starts after 4 hours or more have passed.
Outdoor heat
exchanger temperature
Fig. 1
Outdoor air temperature
(–20) 0
(– 6) (– 7)
(– 16)
(– 25)
L2
L1
New operation begins based on the temperature conditions at the time the ON/OFF button is pressed.
Temperature of releasing
*1 The temperature for releasing of defrosting is (20 °C) or higher when the
outdoor air temperature is less than 0 °C.
Defrost operation time
Heat exchanger temperature for releasing defrosting
Less than 2 minutes 2 minutes or more
No releasing 14 °C or higher (*1)
19
Control/conditions
COOL
The ON/OFF operation button on the remote controller is pressed.
The room temperature has reached the desired temperature.
The outdoor unit does not operate for 5 minutes even after the breaker is turned ON.
This is in order to stabilize the return of oil to the compressor.
Frequency control
(Hz)
(26) Hz
(35) Hz
(45) Hz
(55) Hz
The outdoor unit starts.
(Compressor and the outdoor fan start.)
When the frequency reaches Hz, frequency increases are stopped for a period
of seconds. (Refer to Table 2.)
If the indoor and outdoor temperatures are high, the current peak cut-off activates, stopping
any increases in frequency.
The frequency then increases.
Operating frequency is stabilized in order to
maintain a comfortable environment.
The indoor temperature and the desired
temperature are approximately equal.
The thermostat turns ON again.
After 5 minutes, the outdoor unit begins operating automatically.
During these 5 minutes, a pressure balance is achieved, allowing the compressor to start more easily.
After the thermostat turns ON again, the outdoor unit will not operate for 5 minutes, even if the room temperature increases above the desired temperature.
Operation is restarted within 4 hours (only when AUTO mode is selected with the remote controller).
Within 4 hours after operation was stopped, it is assumed that there has been no significant change in the indoor and outdoor temperatures, and the previous conditions (COOL) are stored.
Starts operating in the same operating mode (COOL) and with the same temperature settings as before operation was stopped.
Operation starts after 4 hours or more have passed.
New operating mode is determined based on the temperature conditions at the time the ON/OFF operation button is pressed.
Stop All indicator lamps turn OFF. The indoor and
outdoor units stop.
Freeze prevention In order to protect against freezing, the
compressor stops temporarily, until the temperature of the indoor heat exchanger has risen.
The thermostat turns OFF.
The outdoor unit stops. (It does not stop if the thermostart for another indoor unit is ON.)
Unit operation Explanation
The operation lamp illuminates.
The indoor fan operates at the set fan speed.
The outdoor unit stops.
When the temperature of the indoor heat exchanger drops to approximately 2 °C or below, the compressor turns OFF, the outdoor fan turns OFF, and the indoor fan continues operating with no changes.
Approximately 5 minutes later, if the temperature of the indoor heat exchanger is adove 8 °C, the system returns to its original conditions.
The frequency is increased at the rate of 0.5
Hz every 1 seconds.
Outdoor air temperature is below 0 °C.
(120) seconds
(60) seconds
(60) seconds
(180) seconds
(senconds)
Outdoor air temperature is 0 °C or higher.
(60) seconds
(30) seconds
(30) seconds
(90) seconds
20
Control/conditions
SENSOR DRY
(1/f fluctuation fan)
The ON/OFF operation button on the remote controller is pressed.
The outdoor unit does not operate for 5 minutes even after the breaker is turned ON.
This is in order to stabilize the return of oil to the compressor.
The outdoor unit starts.
(Compressor and the outdoor fan start.)
When the frequency reaches Hz, frequency increases are stopped for a period
of seconds. (Refer to Table 2.)
DRY B operation
If the indoor and outdoor temperatures are high, the current peak cut-off activates, stopping
any increases in frequency.
The frequency then increases.
Unit operation Explanation
The operation lamp illuminates.
The indoor fan operates at the set fan speed.
The outdoor unit stops.
The room temperature reaches the desired temperature, and there is no need for further cooling.
Operating frequency is stabilized in order to
maintain a comfortable environment.
The room temperature is 15 °C or higher, and is slightly too cold.
The compressor operates on a 3-minutes ON, 6-minutes OFF cycle, to prevent the room temperature from dropping too much.
DRY operation starts
DRY A operation
The room temperature is below 15 °C.
1/f fluctuation fan
250
200
6-minute cycle
Fig. 2
150
100
(Step)
50
0
When monitoring operation begins, the compressor stops, and the indoor fan operates at "LL" (very low) speed.
Monitoring operation begins.
The indoor fan changes between "Low" and "LL" (very low) over a 6-minute cycle. This is 1/f fluctuation fan operation. (Refer to Fig. 2.)
The indoor fan changes between "Low" and "LL" (very low) over a 6-minute cycle. This is 1/f fluctuation fan operation.
After appoximately 3 minutes, the compressor turns OFF, the outdoor fan turns OFF, and the indoor fan turns OFF.
After approximately 6 minutes, the conditions return to (1).
(1)
(2)
(3)
The frequency is increased at the rate of 0.5
Hz every 1 seconds.
Operates to effectively dehumidify the air while not excessively reducing the indoor temperature.
The indoor unit operates at 1/f fluctuation fan operation, at a fan speed that does not cause a chilly feeling.
21
Loading...
+ 49 hidden pages