Outer door latch 1pc
Outer door lock 1pc
Caster
Access port
Refrigeration circuit Cascade system
Power supply 230/240V, 50Hz, Single phase
Weight 288 kg
Battery
Accessories 1 set of key, 1 scraper
Optional components
VIP䠄Vacuum insulation panel䠅䠇Rigid polyurethane foamed-in place
High stage side䠖Hermetic rotary type, Output: 450W
Inventory rack (IR-220U, IR-224U), Drawer (MDF-50R),
Temperature recorder (MTR-G85/MTR-85H)
Back-up system (CVK-UB2): LCO
Interface board (MTR-480)
Data acquisition system (MTR-5000)
, (CVK-UBN2): LN2
2
- 1 -
Control specifications
Item Specifications
Temperature controller
Temperature setting range
Temperature display
Temperature sensor
High temperature alarm
Low temperature alarm
Filter alarm FILTER lamp illuminates and buzzer sounds intermittently.
Microcomputer, key-pad input
Non-volatile memory
-50䉝~-90䉝 (Unit: 1䉝)
LED (Unit: 1䉝)
Pt. 1000䃈
When chamber temperature deviates from set temperature+5䉝䡚+20䉝
(Factory default:+10䉝), ALARM lamp blinks and buzzer sounds after 15
minutes of delay.
Remote alarm contact: Normal Open, Normal close
Rated (max) 30VDC, 2A
Turns over after 15minutes of delay
When chamber temperature deviates from set temperature-5䉝䡚-20䉝
(Factory default:-10䉝), ALARM lamp blinks and buzzer sounds after 15
minutes of delay.
Remote alarm contact: Normal Open, Normal close
Rated (max) 30VDC, 2A
Turns over after 15minutes of delay
Door alarm
Power failure alarm
Remote alarm
Notice of battery life
Notice of condensing fan
motor life
STATUS function
Control panel
Key Lock
Self diagnosis function
When a door is open, DOOR lamp illuminates after predetermined delay
time elapses. (Factory default: 2minutes, Range:1~15minutes)
ALARM lamp blinks and buzzer sounds intermittently.
Remote alarm activates.
Allowable contact capacity䠖DC30V 2A䚸N.C.-COM䠈N.O.-COM
When temperature alarm or power failure alarm is occurred or any sensor
is failed, remote alarm contact turns over.
BATTERY lamp illuminates when battery accumulation time (2.8 years)
expires.
BATTERY lamp blinks when condensing fan motor accumulation time
(5.6 years) expires.
zNotice of Battery/condensing fan motor life
zAbnormal power supply voltage
zAbnormal ambient temperature
zOverloaded operation
Alarm lamp: ALARM
Filter check lamp: FILTER
Battery check lamp: BATTERY
Status monitor lamp: STATUS
Door check lamp: DOOR
Buzzer stop key: BUZZER
Alarm test key: ALARM TEST
Status key: STATUS
SET䠖Set key
: Digit shift key
: Numerical value shift key
Press digit shift key for 5 seconds to activate Key Lock mode.
L0: Unlock䚸L1: Lock
When temp. sensor or filter sensor or cascade sensor or AT sensor is
failed;
Error code is displayed, ALARM lamp illuminates, buzzer sounds and
remote alarm is active.
- 2 -
Item Specifications
Compressor protection
Compressor delay time
Performance specifications
Item Specifications
Cascade sensor temperature is higher than 䠉12䉝, L side compressor
turns off.
Cascade sensor temperature is lower than 䠉34䉝, L side compressor
turns on.
Overload relay
When filter sensor temperature is higher than +60䉝, H side compressor
turns off. (Substitution for pressure switch)
Range: 3~15 minutes (Unit: 1minute)
It is not settable delay time individually between H side compressor and L
side compressor.
Maximum cooling performance
Temperature control range
Power source 230V, 50Hz 240V, 50Hz
Rated power consumption 650W 700W
Noise level 47dB <A> (background noise; 20dB)
Maximum pressure 2030 kPa
-86䉝 at the center of the chamber 䠄AT䠖30䉝䚸No load䠅
䠉50䉝 to 䠉86䉝䠄AT䠖30䉝䚸No load䠅
- 3 -
Dimensions
(Innerdimensionsoftray)
(Innerdimensionsoftray)
Top
exitofpowercord
(Backside)
Front
Side
- 4 -
Refrigeration circuit
Framepipe
Pre-condenser
EXtank
CompressorL
Capillarytube
(EX)
CompressorH
Pre-condenser
Cascadesystem
Condenser
DryerH
Checkvalve
Accumulator
Pre-condenser
Suctionheat
exchanger
CapillarytubeH
Oilseparator
Cascadecondenser
Header
Hside
Lside
- 5 -
DryerH
Evaporator
CapillarytubeL
Cooling unit parts
Parts descriptions
Compressor
Power supply Single phase 230/240V, 50Hz Single phase 230/240V, 50Hz
Refrigeration oil
Cooling system
Condenser (type) Fin and tube type Cascade condenser
Condenser
Pre-condenser
Frame pipe
Evaporator䠄Type䠅
Accumulator
Capillary tube
Resistance 0.765MPa 0.343MPa 34psi
Length L 2000 mm 2500 mm 500 mm
Outside diameter OD
Inside diameter ID
Refrigerant
Dryer
Condensing fan
Condensing fan motor
Kind䠖Ze-NIUSL22SA
Forced air cooling 䠄Partially䠅,
Pre-condenser (DSH)
P6.35㽢3lines㽢12 columns,
Shell and tube, 䃥80 mm
R-404A Charged q’ty䠖 432g
n-Pentane Charged q'ty䠖 18g
Type: Dry core (D-SM)
䃥230mm, 4pcs. wings
H side L side
Type䠖C-1RN45L5A
Code䠖802 022 15
Charged q’ty䠖230cc
Fin 38pcs.
W250 mm
䃥4.76 mm
Cascade condenser
䃥38 mm
Ex. capillary
䃥2.0 mm 䃥2.0 mm 䃥2.4 mm
䃥0.9 mm 䃥0.9 mm 䃥1.2 mm
Material䠖ABS
Type䠖SV4-11AA5P
Specifications
Forced air cooling 䠄Partially䠅,
R-508 Charged q’ty䠖370g
(TP5R3)
n-Pentane Charged q'ty䠖 53g
Type: 4A-XH-6 Charged q’ty䠖58g
Type䠖KS240J1NS-4A1
Code䠖7FB-0-M101-011-05
Kind䠖Ze-NIUSL22SA
Charged q’ty䠖850cc
Oil cooler (OC)
Coil pipe (䃥6.35mm)
䇷
䇷
Tube on sheet type
䃥9.52 mm
䇷
䇷
- 6 -
Components on PCB
CN3
Remotealarmterminal
#1COM
#2N.O.
#3N.C.
CN5
#1-#5SwitchPCB
#6-#7BuzzerPCB
CN4
#1-#2Temp.controlrelay
#3-#4Heaterrelay
#1-#2
Hcomprelay
CN9
MTR-480(option)
MTR-L03(option)
CN2
DisplayPCB
CN6
#1-#2Doorswitch
#5-#6ATsensor
#7-#8Filtersensor
CN7
#9-#10Cascadesensor
#1-#3
Switchingpowersupply
CN1
CN8
#1-#2Battery,Batteryswitch
#3-#4Powertransformer
- 7 -
CN11
#1-#3
Temp.sensor
Connections on PCB
The following shows the connections of connectors on the Temp. controller PCB.
Connector Connects to Usage
CN1 Switching power supply To supply the power to PCB.
CN2 Communication kit To connect to MTR-480/MTR-L03(option).
Remote alarm terminal
#1: COM.
CN3
#2: N.O.
#3: N.C.
#1-#2㸸Temp. control relay
CN4
#3-#4㸸Heater relay
#1-#5: Switch PCB
CN5
#6-#7: Buzzer
CN6 Display PCB To connect to each LED
#1-#2: Door switch
#5-#6: AT sensor
CN7
#7-#8: Filter sensor
#9-#10: Cascade sensor
#1-#2: Battery㸦#1:6V #2:Battery switch㸧
CN8
#3-#4: Transformer
Remote alarm contact outputs.
In normal condition, open between #1 and #2
and closed between #1 and #3.
To control chamber temperature (12VDC)
To supply the power to Cap. tube heater
(12VDC)
To connect to each switch
To connect to buzzer
To control door open and close
To detect ambient temperature
To detect temperature in condenser outlet pipe.
To detect temperature in cascade.
To supply the power during power failure
To supply the power to PCB.
CN9 #1-#2: H. Comp. relay To control compressor H ON/OFF (12VDC)
CN10 Unused
CN11 #1-#3: Temp. sensor To detect chamber temperature.
- 8 -
)
A
e
)
z
䃈
䃈
)
e
)
z
䃈
䃈
0
V
V
A
Electric Parts
MDF-U55V
Compressor (H
Rated voltage (50/60Hz
Winding resistance C-R(Main)5.95
C-S(Aux)14.76
Compressor (L
Rated voltage (50/60Hz
Winding resistance C-R(Main)2.7
C-S(Aux)4.9
Starting relay (H)
Pick up voltage185~217VAC
Drop out voltage60~120VAC
Starting relay (L)
Pick up voltage205~235VAC
Drop out voltage110VAC
Overload relay (L)
Action to the temp. (No current)ON:120䉝 OFF:61䉝
Action to the current (AT25Υ)20.5A
Operation time6~16sec.
Starting capacitor (H)Rating40uF, 300VAC
Starting capacitor (L)Rating160uF, 250VAC
Running capacitor (H)Rating15uF, 400VAC
Running capacitor (L)Rating12uF, 370VAC
Fan motor capacitorRating
Condensing fan motor
The following shows the temperature in thermal sensor (502AT-1) and its resistance value.
Temp.
(C)
Resistance
(kȐ)
Temp.
(C)
Resistance
(kȐ)
Temp.
(C)
Resistance
(kȐ)
Temp.
(C)
Resistance
(kȐ)
㸫50
㸫49
㸫48
㸫47
㸫46
㸫45
㸫44
㸫43
㸫42
㸫41
㸫40
㸫39
㸫38
㸫37
154.5
145.9
137.8
130.2
123.1
116.5
110.2
104.4
98.87
93.70
88.85
84.18
79.80
75.67
㸫36
㸫35
㸫34
㸫33
㸫32
㸫31
㸫30
㸫29
㸫28
㸫27
㸫26
㸫25
㸫24
㸫23
71.80
68.15
64.71
61.48
58.43
55.55
52.84
50.23
47.77
45.45
43.26
41.19
39.24
37.39
㸫22
㸫21
㸫20
㸫19
㸫18
㸫17
㸫16
㸫15
㸫14
㸫13
㸫12
㸫11
㸫10
㸫5
35.65 0 13.29
33.99 5 10.80
32.43 10 8.84
30.92 15 7.20
29.50 20 6.01
28.14 25 5.00
26.87 30 4.17
25.65 35 3.50
24.51 40 2.96
23.42 45 2.51
22.39 50 2.13
21.41 55 1.82
20.48 60 1.56
16.43 65 1.35
The following shows the temperature in thermal sensor (PT1000ȍ) and its resistance value.
Temp.
(C)
㸫140
㸫130
㸫120
㸫110
㸫100
㸫90
㸫80
Resistance
(Ȑ)
450.83
491.47
531.83
571.92
611.76
651.38
690.78
Temp.
(C)
㸫70
㸫60
㸫50
㸫40
㸫30
㸫20
㸫10
Resistance
(Ȑ)
729.99 0 1000.0
769.02 10 1038.0
807.87 20 1076.0
846.58 30 1113.8
885.13 40 1151.4
923.55 50 1189.0
961.84 60 1226.4
Temp.
(C)
Resistance
(Ȑ)
- 10 -
Wiring diagram
- 11 -
Circuit diagram
- 12 -
㻌
Control specifications
1. Key and Switch
BUZZER : In alarm condition, audible alarm silences when this key is pressed.
Remote alarm activates and message is not eliminated.
When a power failure is occurred (battery back-up), press this key to show a
chamber temperature for 5 seconds.
ALARM TEST : When this key is pressed, unit steps into Alarm Test mode with ALARM lamp
flashes, audible alarm sounds, digital LED is disappeared and remote alarm is
active.
By Auto Return function, unit will return to normal operation after approx.
90seconds elapse.
When an alarm test is performed and a battery switch is in off position, “E09”
will flash.
SET : Press this key to activate setting mode and 2
Press this key again to store a value to be changed.
STATUS : Press this key when STATUS lamp illuminates to show status code (‘-- 1’, ‘--2’
and ‘--3’) on the display.
(Digit shift key)
(Numerical value
shift key)
2. Temperature control
Setting range :
Display range : -180~50
How to set chamber
temperature:
Unacceptable setting
range :
3. Key Lock mode
Setting range : 0 (Unlock), 1 (Lock)
How to set Key Lock: In chamber temperature display, press key for 5 seconds to step to Key
4. Function mode
Setting range : 00~50
Display range : 00~59
00, 16 and 33~43, 44~49, 51~59 are unused.
How to set Function
mode :
Unacceptable setting
range :
Every time press this key to blink and change a digit among 1
flexibly.
If this key is pressed for 5 seconds when a chamber temperature is displayed,
Key Lock is active and “L_0” is displayed.
Every time press this key to blink a digit and increase numeric value one by
one.
If this key is pressed for 5 seconds when a chamber temperature is displayed,
Function mode is active and “F00” is displayed.
-50䉝~-90䉝
Press SET key and change a value by pressing key and key.
Press SET key again to memorize the value to be changed.
The value cannot be changed and audible alarm sounds for 1second, if a
value which is out of setting range is input and SET key is pressed.
Lock mode. (“L_0” or “L_1” is displayed. Factory default: L_0)
Change a value by pressing key and press SET key to memorize the
value to be changed.
In chamber temperature display, press key for 5 seconds to step㻌 to
Function mode and F00 is displayed.
Change a blinking 1
The value cannot be changed and audible alarm sounds for 1second, if a
value which is out of setting range is input and SET key is pressed.
st
digit by pressing key and key and press SET key.
nd
digit will blink on the display.
st
, 2nd and 3rd digit
- 13 -
5. Error codes
(1) Temp. sensor
Open circuit (E01):
Short circuit (E02):
(2) Cascade sensor
Open circuit (E03):
Short circuit (E04):
(3) Filter sensor
Open circuit (E05):
Short circuit (E06):
(4) AT sensor
Open circuit (E07):
(5) Battery SW is in
off position (E09):
E01: Temp. sensor is open circuited
E02: Temp. sensor is short circuited
E03: Cascade sensor is open circuited
E04: Cascade sensor is short circuited
E05: Filter sensor is open circuited
E06: Filter sensor is short circuited
E07: AT sensor is open circuited
E08: AT sensor is short circuited
E09: Battery switch is in off position
E10: Compressor temperature is abnormal
Short circuit(E08):
When a temp. sensor temperature is higher than 50䉝, E01 and 50䉝 are
displayed alternately and audible alarm sounds intermittently and remote
alarm contact is active.
Compressor is forcible to turn on.
Press BUZZER key to silence audible alarm.
When a temp. sensor temperature is lower than -170䉝, E02 and -170䉝~
-180䉝 are displayed alternately and audible alarm sounds intermittently and
remote alarm contact is active.
Compressor is forcible to turn on.
Press BUZZER key to silence audible alarm.
When a temperature in cascade sensor is lower than -65䉝, E03 and
chamber temperature are displayed alternately, audible alarm sounds
intermittently and remote alarm contact is active.
Both High and Low side compressors are turned off.
Press BUZZER key to silence audible alarm.
When a temperature in cascade sensor is higher than 60 䉝 , E04 and
chamber temperature are displayed alternately, audible alarm sounds
intermittently and remote alarm contact is active.
Both High and Low side compressor are turned off.
Press BUZZER key to silence audible alarm.
When a filter sensor temperature is lower than -60䉝, E05 and chamber
temperature are displayed alternately, audible alarm sounds intermittently
and remote alarm contact is active.
High side compressor is forcible to turn off.
Press BUZZER key to silence audible alarm.
When a temperature in filter sensor is higher than 130䉝, E06 and chamber
temperature are displayed alternately, audible alarm sounds intermittently
and remote alarm contact is active.
Press BUZZER key to silence audible alarm.
When a temperature in AT sensor is lower than -60䉝, E07 and chamber
temperature are displayed alternately, audible alarm sounds intermittently
and remote alarm contact is active.
Press BUZZER key to silence audible alarm.
When a temperature in AT sensor is higher than 60䉝, E08 and chamber
temperature are displayed alternately, audible alarm sounds intermittently
and remote alarm contact is active.
Press BUZZER key to silence audible alarm.
If you press ALARM TEST key when battery switch is in off position or
battery is unconnected, E09 is displayed.
- 14 -
(6)Compressor
abnormal
temperature (E10):
(7) Error code priority
6. Warning functions
Door alarm : When an outer door leaves open, DP54 (red lamp) illuminates. Audible alarm
High temp. alarm : When chamber temperature is equal or higher than set temperature + high
Low temp. alarm : When chamber temperature is equal or lower than set temperature - low
Power failure alarm : If a power failure is occurred or a power interrupts for 3 seconds when
7. Other functions
Auto Return : If there are not any key operations for 90 seconds when setting mode or Key
Ring Back : Audible alarm will sound after predetermined setting time elapses if it is
No.1: Cascade sensor error (E03, E04) … Compressor is forcible to turn off
No.2: Filter sensor error (E05, E06) … Impossible to protect compressor
No.3: Abnormal compressor temperature(E10) … Compressor temporary turns off
No.4:
No.5:
When a temperature in filter sensor is higher than 60䉝, E10 and chamber
temperature are displayed alternately and high side compressor is forcibly
turned off to notify compressor temperature is abnormal or fan motor is
locked.
Press BUZZER key to silence audible alarm.
When the temperature obtained from filter sensor temperature subtracts
ambient temperature, is equal or lower than 10䉝, compressor will turn on.
Temp. sensor error (E01, E02) … Compressor keeps turning on
AT sensor error (E07, E08) … Warming-up operation is forcible to be active
sounds intermittently after 1~15 minutes (Factory default: 2 minutes) elapse.
Audible alarm is not active simultaneously with remote alarm.
Press BUZZER key to silence audible alarm.(Ring Back is not active)
temp. alarm set temperature +1, ALARM lamp and LED flash, audible alarm
sounds intermittently and remote alarm is active after 10 minutes elapse.
When chamber temperature is equal or lower than set temperature, ALARM
lamp and LED go off, audible alarm silences, and remote alarm turns off.
Press BUZZER key to silence audible alarm, but not to activate remote alarm
simultaneously.
temp. alarm set temperature -1, ALARM lamp and LED flash, audible alarm
sounds intermittently and remote alarm is active after 10 minutes elapse.
When chamber temperature is equal or higher than set temperature, ALARM
lamp and LED go off, audible alarm silences, and remote alarm turns off.
Press BUZZER key to silence audible alarm, but not to activate remote alarm
simultaneously.
battery switch is in on-position, ALARM lamp blinks, audible alarm sounds
intermittently and remote alarm is active.
Press BUZZER key to display chamber temperature for 5 seconds.
When a power returns within 3 seconds since the power was interrupted,
microprocessor resets in default settings. Remote alarm is not active.
Press BUZZER key to silence audible alarm, but remote alarm keeps active.
Remote alarm will keep active until chamber temperature is stabled after the
power returns from power failure.
When a power interrupts, press BUZZER key to see chamber temperature
for 5 seconds.
Lock mode or Function mode is active, unit automatically returns to chamber
temperature display.
silenced by someone pressing BUZZER key.
- 15 -
Display of sensor
temperature:
Battery accumulation
time :
Condensing fan
motor accumulation
time :
Forcible operation of
capillary heater:
ROM version : F30: Display of current ROM version
8. STATUS function
(1) Display of STATUS code
STATUS lamp illuminates in the following conditions.
STATUS code will be displayed by pressing STATUS key when STATUS lamp
illuminates.
STATUS 1: When an ambient temperature is higher than 35.0䉝, or lower than 0䉝, ‘--1’
STATUS 2: When a power supply voltage is lower than 2.01VDC between TP7 and TP3,
STATUS 3: When running rate is higher than 95%, ‘--3’ is appeared on the display.
F12: 3 digits display of temp. sensor temperature (Unit:0.1䉝)
(Ex. -80.2䉝㻌 䊻㻌 Displayed as ‘80.2’)
F13: 3 digits display of cascade sensor temperature (Unit:1䉝)
(Ex. 67䉝㻌 䊻㻌 Displayed as ‘067’)
F14: 3 digits display of filter sensor temperature (Unit:1䉝)
(Ex. 67䉝㻌 䊻㻌 Displayed as ‘067’)
F15: 3 digits display of AT sensor temperature (Unit:1䉝)
(Ex. 30䉝㻌 䊻㻌 Displayed as ‘030’)
F03: 3 digits display of battery accumulation time
(Ex. 2years and 6months accumulated 䊻㻌 Displayed as ‘02.5’)
When battery accumulation time (2years and 8months, ’02.8’) expires,
BATTERY lamp illuminates.
<Reset of battery accumulation time>
Step to F06 and change a value to ‘409’. Press SET key to reset
accumulation time to ’00.0’. BATTERY lamp goes off.
F32: 3 digits display of Condensing fan motor accumulation time
(Ex. 5years and 6months accumulated 䊻 Displayed as ’05.5’)
When condensing fan motor accumulation time (5years and 6monts,
‘05.6’) expires, BATTERY lamp flashes.
<Reset of battery accumulation time>
Step to F06 and change a value to ‘410’. Press SET key to reset
accumulation time to ’00.0’. BATTERY lamp goes off.
F18: Compressor is turned off and capillary heater is forcibly to turn on when
a value is changed to ‘000” in F18.
Capillary heater is forcibly to turn off once inputting ‘000’ again during a
power conducting to capillary heater.
It is impossible to conduct a power to capillary heater when a value is
changed to ‘001’.
Only compressor will be turned on every 18 hours.
(Ex. Ver. 1.00 䊻㻌 Displayed as “1.00”)
is appeared on the display.
‘-- 2’ is appeared on the display.
- 16 -
p
(2) Display sequence of STATUS code
(Ex.1) When all of three STATUS codes occur simultaneously;
‘ --‘ => ‘-- 1’ => ‘-- 2’ => 㻌 ‘-- 3’ => ‘--1’ …
(Ex.2) When STATUS 1 and 2 occur simultaneously;
‘ --‘ => ‘-- 1’ => ‘-- 2’ => 㻌 ‘-- 2’ => ‘--1’ …
When it elapses 90 seconds or when a unit returns from STATUS condition, chamber
temperature will be appeared on the display.
9. Running rate
Running rate: Obtained from (ON time / (ON time + OFF time)) x 100%
Definition: “ON time” means the reach time until P3.1 in IC5 is changed “Low” to “Hi”
“OFF time” means the reach time until P3.1 in IC5 is returned “Hi” to “Low”
Condition to measure running rate:
Cycle operation will start when a compressor turns on for the first time after it was
turned off when chamber temperature was lower than set temperature.
Running rate will be measured after 2 hours elapse since the unit was stabilized
in cycle operation.
ON time (Min.) = The time until P3.1 in IC5 first reaches from LOW to HIGH
OFF time (Min.) = The time until P3.1 in IC5 reaches from HIGH to LOW
Condition to calculate running rate:
ON time OFF time Running rate
= 0 = 0
> 0 = 0
= 0 > 0
> 0 > 0 0 ~ 100%
Impossible to calculate
(0%)
Note) Running rate cannot be measured when a chamber temperature is higher than set
temperature + 4.0䉝.
Measuring should be done until a chamber temperature is stabilized.
Diagnosed value of overload running rate:
Step to F20 and input ‘000’.
Chamber
temperature
Compressor turns off
for the first time
Chamber temperature
reaches set tem
Compressor turns on
for the first time.
Start to cycle run
2 hours 8 hours
erature.
Start to measure
running rate
Unit is stabilized in cycle operation.
Start to measure
running rate
Set
Running rate is measued every 8
hours until chamber temperature is
over set temperature+4.0䉝
- 17 -
10. Function mode
F00 Display of chamber temperature (Unused)
F01 Setting of high temperature alarm F02 Setting of low temperature alarm F03 Display of battery accumulation time F04 Setting of door alarm delay time F05 Setting of compressor delay time F06 Setting of service code (Code: 384), Reset of accumulation time F07 * Temperature sensor Zero Adjustment F08 * Cascade sensor Zero Adjustment
F09 * Compressor continuous running mode … Factory test mode (Unused)
F10 * Program running mode … Factory test mode (Unused)
F11 * PCB test mode … Factory test mode (Unused)
F12 * Display of temperature in temp. sensor F13 * Display of temperature in cascade sensor F14 * Display of temperature in filter sensor F15 * Display of temperature in AT sensor F16 * Display of chamber temperature (Unused) F17 * Display of model code and initialization of non-volatile memory F18 * Forcible operation for capillary heater F19 * Setting of capillary heater ON time … Factory use F20 * Setting of diagnosed value of overload running ratio … Factory use
F21 Setting of communication ID
F22 Setting of communication mode
F23 * Display of power supply voltage
F24 Remote alarm terminal output F25 Setting of Ring Back time
F26 * Display of actual operation ratio
F27 * Display of diagnosed value for overload running ratio
F28 * Display of delay time of permission to measure running rate (2 hrs timer)
F29 * Display of delay time of permission to measure running rate (8 hrs timer)
F30 * Display of ROM version
F31 * Setting of filter alarm
F32 Display of condensing fan motor accumulation time
F33~F43 Unused
F44 * Adjustment of power supply voltage display
F45~F49 Unused
F50 Setting of alarm delay time
F51~F59 Unused
Setting
procedure:
Diagnosed running rate
=(-(Set temp.)X0.9)+((ATX0.9-4.5䉝))-((Set temp.+85䉝) / 10))
You can know running status by the calculation for diagnosed running rate.
Diagnosis is done by comparing running rate for 8 hours operation after 2 hours
elapses since unit started cycle operation, with diagnosed running rate.
(Diagnosed running rate – running rate) < 0 … Normal (DP52 goes off)
(Diagnosed running rate – running rate) 䍻0 … Overload operation (DP52 illuminates)
222 = Running rate cannot be obtained by calculation. (DP52 goes off)
Diagnosis is done in every 8 hours.
Input service code ‘384’ in F06 prior to use function codes which are marked with *.
To cancel service code, input “000” in F06 or turn the power off.
In chamber temperature display, press key for 5 seconds to display “F00”.
Input Function code by pressing key and key.
Press SET key to be function mode available.
- 18 -
F00: <Purpose> Simply passing through if entered by mistake.
<Operation> Press SET key in “F00” display to return to chamber temperature
display.
F01: <Purpose> Setting of high temperature alarm
<Operation> Input F01 and press SET key to display “015” (Factory default).
Setting range is ‘005~020’.
Change a value by pressing key.
Press SET key to memorize the value and to return to chamber
temperature display.
F02: <Purpose> Setting of low temperature alarm
<Operation> Input F02 and press SET key to display “-10” (Factory default).
Setting range is “-05”~“-20”.
Change a value by pressing key.
Press SET key to memorize the value and to return to chamber
temperature display.
F03: <Purpose> Display of battery accumulation time
<Operation> Input F03 and press SET key to display alternately F03 with “00.0” (in
case battery used for 36days or less).
Press SET key to return to chamber temperature display.
F04: <Purpose> Setting of door alarm delay time
<Operation> Press SET key in “F04” to display ‘002’ (Factory default).
setting range is ‘001’~’015’.
Change a value by pressing key and key.
Press SET key to memorize the value and to return to chamber
temperature display.
F05: <Purpose> Compressor turns on with delay when a power is supplied or a power
returns from a power failure.
<Operation> Input “F05” and press SET key to display ‘003’ (Factory default).
Setting range is ‘003’~’015’. (Unit: Minute)
Change a value by pressing key and key.
Press SET key to memorize the value and to return to chamber
temperature display.
F06: <Purpose> Input of service code and reset of accumulation time
<Operation> Input F06 and press SET key to display ‘000’ (Factory default).
Set service code to “384” by pressing key and key.
Press SET key to memorize the value and to return to chamber
temperature display.
<Reset of battery accumulation time>
Input service code ‘384’ in F06.
Input ‘409’ to reset battery accmulation time and to return to chamber
temperature display. (Service code is cancelled)
<Reset of condensing fan motor accumulation time>
Input service code ‘384’ in F06.
Input ‘410’ to reset fan motor accumulation time and to return to
chamber temperature display. (Service code is cancelled)
<Cancel> Input F06 again and press SET key to display ‘384’.
Change to ‘000’ by pressing key and key.
Press SET key to memorize the value and to return to chamber
temperature display.
Turn a power off then on to change a value to ‘000’, but it is not stored
in non-volatile memory.
Note) Service code ‘384’ is stored in non-volatile memory during battery
back-up.
- 19 -
F07: <Purpose> To match a temp. sensor temperature with 1/2H air temperature
(Zero calibration of temp. sensor)
<Operation> Input service code in F06 prior to use this mode.
Input F07 and press SET key to display ‘00.0’ (Factory default).
Setting range is ‘-4.9’~’04.9’.
Change a value by pressing key and key.
Press SET key to memorize the value and to return to chamber
temperature display.
F08: <Purpose> To calibrate a cascade sensor temperature
<Operation> Input service code in F06 prior to use this mode.
Input F08 and press SET key to display ‘00.0’ (Factory default).
Setting range is ‘-9.9’~’09.9’.
Change a value by pressing key and key.
Press SET key to memorize the value and to return to chamber
temperature display.
F12: <Purpose> To display a temp. sensor temperature
<Operation> Input service code in F06 prior to use this mode.
Input F12 and press SET key to display alternately F12 and “XX.X”
(chamber temperature). Press SET key to return to chamber
temperature display. Decimal point is displayed in the 3 digits indication,
but minus “-“ is not displayed.
Ex) “-79.5䉝” 䊻㻌 Indicated as “79.5”
F13: <Purpose> To display a cascade sensor temperature
<Operation> Input service code in F06 prior to use this mode.
Input F13 and press SET key to display alternately F13 and “XXX”
(present temperature in cascade sensor). Press SET key to return to
chamber temperature display.
F14: <Purpose> To display a filter sensor temperature
<Operation> Input service code in F06 prior to use this mode.
Input F14 and press SET key to display alternately F14 and “XXX”
(present temperature in filter sensor). Press SET key to return to
chamber temperature display.
F15: <Purpose> To display an AT sensor temperature
<Operation> Input service code in F06 prior to use this mode.
Input F15 and press SET key to display alternately F15 and “XXX”
(present temperature in AT sensor). Press SET key to return to
chamber temperature display.
F16: <Purpose> Simply passing through if entered by mistake
<Operation> Press SET key in “F16” to return to chamber temperature display.
F17: <Purpose> Display of model code and initialization of non-volatile memory
<Operation> Service code should be input in F06 prior to use this mode.
Input F17 and press SET key to display ‘00X’.
Change a value by pressing key.
Press SET key to memorize and return to chamber temperature display.
Model code ‘008’: MDF-U55V
- 20 -
<Initial values in non-volatile memory> Zero Adjustment value for temperature sensor
Zero Adjustment value for cascade sensor
Capillary heater ON time
Auto Return
Chamber set temperature
Door alarm delay time
High temp. alarm
Low temp. alarm
Compressor delay time
Communication ID
Communication mode
Key Lock
Linkage between remote alarm and buzzer
Buzzer tone for filter alarm
Diagnosed value for STATUS 3
F18: <Purpose> Forcible operation for capillary heater
<Operation> Service code should be input in F06 prior to use this mode.
Input F18 and Press SET key to display ‘000’ (Factory default).
Change to alternative value ‘000’ or ‘001’ by press key and key.
Press SET key to memorize the value and return to chamber
temperature display.
000: Capillary heater is forcibly turned on, or
Capillary heater is forcibly turned off
001: Capillary heater is inoperative
F21: <Purpose> Setting of serial communication ID
<Operation> Input F21 and press SET key to display ‘000’ (Factory default).
Setting range is ‘001’ ~ ‘255” by pressing key and key.
Press SET key to return to chamber temperature display.
<Serial communication data>
Data
Display Unit
Chamber temperature -180.0 ~ +50.0
Cascade temperature -68.0 ~ +89.0
Power supply voltage 0.0 ~ 120.0
Filter temperature -68.0 ~ +160.0
Ambient temperature -68.0 ~ +89.0
Door 0/100 Close/Open
Capillary heater 0/100 Off/On
Compressor H 0/100 Off/On
Compressor L 0/100 Off/On
Power failure 0/100 Off/On
Running ratio 0~100, 222 %
Diagnosed value for overload operation 0~100, 999 %
2H timer counting 0~120 Minute
8H timer counting 0~480 Minute
Set temperature -90.0~-50.0
High temp. alarm set value +5.0~+20.0
Low temp. alarm set value -5.0~-20.0
Filter lamp 0/50 Off/On
Remote alarm 0/50 Off/On
Status lamp 0/50 Off/On
Remote control of set temperature -90.0~-50.0
: 0䉝
: 0䉝
: 8 minutes
: 30 minutes
: -80䉝
: 2 minutes
: +10䉝
: -10䉝
: 3 minutes
: 000
: 000
: OFF
: OFF
: OFF
: Fixed
䉝
䉝
㻑
䉝
䉝
䉝
䉝
䉝
䉝
- 21 -
F22: <Purpose> Setting of serial communication mode
<Operation> input F22 and press SET key to display ‘000’ (Factory default)
Change a value by pressing key and key.
Press SET key to memorize the value and return to chamber
temperature display.
Control mode (the 3
rd
digit)
0: Local (initial)
1: Remote
Baud rate (the 2
nd
digit)
0: 2400bps (initial)
1: 4800bps
2: 9600bps
Note) Setting value cannot be changed at control panel if control mode
is set to ‘Remote’.
F23: <Purpose> To display a power supply voltage (Unit: %)
<Operation> Service code should be input in F06 prior to use this mode.
Input F23 and press SET key to display alternately F23 with ‘xxx’
(present power supply voltage). Press SET key to return to chamber
temperature display.
F24: <Purpose> Linkage between remote alarm and buzzer
<Operation> Input F24 and Press SET key to display ‘000’ (Factory default).
Change a value by pressing key.
Press SET key to memorize the value and return to chamber
temperature display.
000: Remote alarm does not link with buzzer
001: Remote alarm links with buzzer
F25: <Purpose> Setting of Ring Back time
<Operation> Input F25 and press SET key to display “030” (Factory default).
Setting range is ‘000’~’060’.
Change a value by pressing key.
Press SET key to memorize the value and to return to chamber
temperature display.
000: Not Ring Back
010: 10 minutes
020: 20 minutes
030: 30 minutes
040: 40 minutes
050: 50 minutes
060: 60 minutes
F26: <Purpose> Display of running ratio (Unit: %)
<Operation> Service code should be input in F06 prior to use this mode.
Input F26 and press SET key to display alternately F26 with “XXX”
(Present running rate).
Press SET key to return to chamber temperature display.
F27: <Purpose> Display of diagnosed value for overload running ratio
<Operation> Service code should be input in F06 prior to use this mode.
Input F27 and press SET key to display alternately F27 with “XXX”
(present diagnosed value for overload running ratio).
‘000’ is displayed before it accumulates 480 minutes in 8H timer.
Factory default is ‘095’ which is the fixed, except in case diagnosed
value is obtained from calculation in F20.
Press SET key to return to chamber temperature display.
- 22 -
F28: <Purpose> Display of delay time to start measuring running ratio
(2hrs timer; 000~120 min)
<Operation> Service code should be input in F06 prior to use this mode.
Input F28 and press SET key to display alternately F28 with ‘xxx’
(present count value for delay time to start measuring running rate).
Press SET key to return to chamber temperature display.
When a delay time expires (a value reaches to ‘120’), unit will start
measuring running ratio.
F29: <Purpose> Display of delay time to start diagnosing running ratio
(8hrs timer; 000~480 min)
<Operation> Service code should be input in F06 prior to use this mode.
Input F29 and press SET key to display alternately F29 with ‘xxx’
(present counting value for delay time to start diagnosing running ratio).
Press SET key to return to chamber temperature display.
8hours timer start counting after 2hours timer expires.
When a delay time expires (a value reaches to ‘480’), unit will start
diagnosing running ratio.
F30: <Purpose> ROM version is displayed
<Operation> Service code should be input in F06 prior to use this mode.
Input F30 and press SET key to display alternately F30 with “X.XX”
(present ROM version).
Press SET key to return to chamber temperature display.
F31: <Purpose> Setting of buzzer during filter alarm occurs
<Operation> Service code should be input in F06 prior to use this mode.
Input F31 and press SET key to display “001” (Factory default).
Change to alternative value ‘000’ or ‘001’ by pressing key.
Press SET key to revert to chamber temperature display.
000: Off
001: On
F32: <Purpose> Display of accumulation time of condensing fan motor
<Operation> Service code should be input in F06 prior to use this mode.
Input F32 and press SET key to display alternately F32 with ‘xx.x’
(accumulation time).
Press SET key to return to chamber temperature display.
F44: <Purpose> Adjustment for difference of power supply voltage
<Operation> Input F44 and press SET key to display ‘000’ (Factory default).
Setting range is ‘000’~’003’.
Press SET key to return to chamber temperature display.
Input value Adjustment of display
000 0% (Power supply voltage is not increased)
001 3% increased
002 5% increased
003 7% increased
F50: <Purpose> Setting of alarm delay time
<Operation> Input F50 and press SET key to display ‘015’ (Factory default).
Setting range is ‘000’~’015’.
Change a value by pressing key and key.
Press SET key to memorize the value and to return to chamber
temperature display.
- 23 -
11. Compressor control (differential) value
Compressor H:
Turns on when a chamber temperature is set temperature -0.4䉝.
Compressor L
:
1) Turns on when compressor H turns on and a cascade sensor temperature is -34䉝.
2) Turns on after 3 minutes elapse since compressor H turned on
Compressor H, L
:
Turns off when a chamber temperature is set temperature -1.6䉝
Interval:
1 minute *
* ‘Interval’ means that a period one of compressor either H or L turns on after another one was
turned on.
Note) Compressor L does not turn on until 1 minute elapses since compressor H turned on,
if a temperature in cascade sensor is lower than -34䉝.
Chamber
temp.
(䠬䠲)
PV=SV-0.4
PV=SV-1.4
1min or over
3min. or over
䠄Comp. delay䠅
PV=SV-0.4
PV=SV-1.4
3min. or over
䠄Comp. delay䠅
1min or over
Cascade
temp.
(CT)
CT=-34䉝
CT=-34䉝
Comp. H
Comp. L
Comp. H&L OFF
Comp. L ON
Comp. H&L OFF
Comp. L ON
Comp. H ON
Comp. H ON
<Operational chart of compressor H/L during cycle>
Protection for compressor H:
Compressor H turns off to prevent it from being warmed up that is caused by fan motor lock.
Filter sensor temperature:
Compressor H turns off when a filter sensor temperature is higher than 60䉝. It will turn on again
when the filter sensor temperature is lower than ambient temperature +10䉝.
SV
SV-0.4䉝
SV-1.4䉝
CT=-34䉝
- 24 -
12. Delay time
Compressor delay time
Compressor H or L will be active after predetermined delay time elapses in case it turned off during
cycle operation. Compressor delay time is changeable in F05.
Temperature alarm delay time
When high or low temperature alarm is triggered, buzzer and remote alarm are active after
predetermined delay time elapses. Temperature alarm delay time is changeable in F01(high temp.
alarm) or F02 (low temp. alarm).
* Note) ALARM lamp illuminates and “F01” or “F02” is displayed without delay.
Door alarm delay time
When an outer door is ajar, audible alarm sounds after predetermined delay time elapses.
Door alarm delay time is settabled in F04.
Power failure alarm delay time
When a power is interrupted by power failure, power failure alarm will be occurred after 3 seconds
elapses.
Power failure alarm delay time is unchangeable.
13. Prevention for oil logging in capillary
Purpose:
Capillary heater which mounts on capillary is powered and both compressor H and L are turned off
to prevent capillary from oil logging.
Action:
Both compressor H and L are turned off and capillary heater relay (CN4: 3-4) is active.
Frequency:
8 minutes in every 18 hours (Setting time are changeable in F19)
Timing of action:
(1) After 9 seconds elapses since both compressor H and L are turned off during cycle operation.
(2) Forcible termination of operation for both compressor H and L if they keep running for 60
Forcible operation of capillary heater
Forcible operation of capillary heater is settable in F18.
14. Sensor offset
Offset value:
(1) Temperature sensor: +1.3䉝 (Changeable in F07)
(2) Cascade sensor: +/-0.0䉝 (Changeable in F08)
(3) Filter sensor: +/-0.0䉝
(4) AT sensor: +/-0.0䉝
15. Remote alarm terminal
Operation
When a unit is in alarming condition, remote alarm contact (RLY2) switches the position.
minutes after they were ordered to stop operation.
:
Normal Open Close
In alarm Close Open
(Factory default: 3 minutes)
(Factory default: 15 minutes)
(Factory default: 2 minutes)
(3 seconds fixed)
:
Between 1 and 2
(N.O.)
CN3
Between 1 and 3
(N.C.)
- 25 -
16. Actions and settings after reset
Momentary power interruption:
Actions and settings after unit retrieves from power failure alarm:
17. Lamp and display
Lamp specifications:
<Control PCB>
Actions and settings when a power is supplied (Power on reset)
Alarm Off
Compressor Off
Remote alarm Off
Ring Back 30 minutes
Door alarm delay time 2 minutes
Timer Reset
2H, 8H timer Reset (0)
Counting time during compressor L is inactive Reset
Setting data Read by non-volatile memory
When a chamber temperature is lower than set temperature+10䉝, it is diagnosed that unit is
in momentary power interruption.
Alarm Off
Compressor Off
Remote alarm On
Door alarm delay time 2 minutes
Timer Reset
2H, 8H timer Reset (0)
Counting time during compressor L is inactive Reset
Setting data Read by non-volatile memory
Lamp Color Lamp status Unit status
DP1 Orange
DP2 Green
DP3 Red
DP4 (Unused)
DP6 Green
<Display PCB>
Lamp Color Lamp status Unit status
DP51 Red Flash Alarming
DP52 Green On Status 1 or 2 or 3 is occurred
DP53 Orange On Filter alarm is occurred
DP54 Red On Door is ajar
DP55 Orange
DP56 (Unused)
On Not in alarm
Off High/low temp. alarm, sensor failure, power failure
On Compressor L is active
Off Compressor L is inactive
On Capillary heater is active
Off Capillary heater is inactive
On Compressor H is active
Off Compressor H is inactive
On Notice of battery life
Flash Notice of fan motor life
- 26 -
Examples of display:
Chamber temp. -79.5䉝
Set temp. -80.0䉝
Function㻌㻌㻌 F03
Service code㻌㻌㻌 384
Set value㻌㻌㻌 004
Key Lock㻌㻌㻌 L_0
Buzzer tone:
Alarms (except door alarm) Intermittent tone
Key operation Click tone
Set value memory Click tone
Out of settable range Continuous tone (1 second)
Door alarm Intermittent tone (Shorter interval than other alarms)
Decimal point of chamber temp. -80.0
Sensor offset㻌㻌㻌 -5.0
Operation monitoring㻌㻌LCP
Error 㻌㻌㻌㻌 E01
Accumulation time㻌㻌8H timer 135
- 27 -
Parts layout
Control panel
Inner door handle
Temp. sensor with cover
Temp. sensor
without cover
Door latch "Close"
Door latch "Open"
Filter
AT sensor
- 28 -
<Cooling unit - Rear bottom side><Cooling unit - Left bottom side>
Oil separatorCompressor LCompressor HCondensing fan motor
Filter sensor
Fan motor condenser12P terminalRemote alarm terminal
Breaker switchBattery switch
<Electric Box - Right bottom side>
Oil separator
Heater relay
Transformer
Starting relay LH comp relaySwitching power supply
Starting relay H
Temp. controller PCB
Temp. control relay
Starting capacitor L
Starting capacitor H
Running capacitor LRunning capacitor H
- 29 -
Test data
40
20
0
]
䉝
-20
-40
-60
Temperature[
-80
-100
0246810
Note) Following data are the reference only.
AT30䉝 Pull-down & Pull-up Temperture
230V50Hz䚷Pull-down
Pull-up
Time[hour]
60
40
20
]
0
䉝
-20
-40
-60
Temperature[
-80
-100
-120
0246810
AT35䉝 Pull-down Tempertures
1/2䠤
H䚷EVA䚷OUT
L EVA䚷IN
L䚷EVA䚷OUT
Time[hour]
- 30 -
AT35䉝䚷Pull-down Pressure䚷䠄1ij230V50Hz䠅
4
㻴㼋㻼㼐㼇㻹㻼㼍㼉
3.5
3
2.5
2
1.5
Pressure[MPa]
1
0.5
0
0246810
Time[hour]
㻴㼋㻼䡏㼇㻹㻼㼍㼉
㻸㼋㻼㼐㼇㻹㻼㼍㼉
㻸㼋㻼䡏㼇㻹㻼㼍㼉
1000
900
800
700
600
500
400
Input[W]
300
200
100
AT35䉝䚷Pull-down䚷Current-Input
10
9
8
7
6
W䚷䠄50Hz䠅
A䚷䠄50Hz䠅
0
01234567
Time[hour]
5
4
3
2
1
0
Current[A]
- 31 -
᳑
Temperature uniformity - 17points measuring
Notes) These data are the reference only.
Back
Top of interior
Front
(2)
(5)
(3)(1)
(16)
10mmH
(4)
69mm᳂
Upper area measuring points
(1)~(4): 69mm(H)lower from "Top of interior",
30mm(D) away and 43mm(W) away
from each corner
(5): Center and 69mm(H) lower from
"Top of interior"
Upper shelf
(7)
(6)
Middle shelf
Mullion
Lower shelf
(12)
(11)
Bottom of interior
(17)
(10)
(15)
(8)
10mmH
(13)
43mmW
(9)
10mmH
69mm᳂
(14)
D
30mmD
H
(16): Center and 10mm(H) upper from
"Upper shelf"
Middle area measuring points
(6)~(9): 10mm(H) upper from "Middle shelf",
30mm(D) away and 43mm(W) away
from each corner
(10): Center and 10mm(H) upper from
"Middle shelf"
Bottom area measuring points
(11)~(14): 69mm(H) upper from "Bottom of
interior", 30mm(D) away and
43mm(W) away from each corner
(15): Center and 69mm(H) upper from "Bottom
of interior"
Left
(17): Center and 10mm(H) upper from "Lower
shelf"
Right
- 32 -
Temperature Uniformity (Reference Data)
p
p
䉝
f
k
g
g
k
r
k
g
g
k
r
k
g
g
k
r
f
k
g
g
k
r
k
g
g
k
r
k
g
g
k
r
p
l
(
y
f
f
a
f
f
a
䠘Conditions䠚
Ambient tem
Load: Unloaded
䠘Tem
Temperature of the cycle in each area (SV=-80
䐟
䐠
䐡
䐢
䐣
䐤
䐥
䐦
䐧
䐨
䐩
䐪
䐫
䐬
䐭
䐮
䐯
erature: 20/30䉝
erature distribution䠚
Left front-75.7-81.0-78.4±2.7
Left bac
Ri
ht front-73.7-80.2-77.0±3.3
Ri
Upper areaMiddle areaBottom are
Center of Upper shel
Center of Lower shel
Average
ht bac
Cente
Left front-78.1-80.6-79.4±1.3
Left bac
Ri
ht front-78.0-80.6-79.3±1.3
Ri
ht bac
Cente
Left front-77.0-79.4-78.2±1.2
Left bac
Ri
ht front-76.4-78.5-77.5±1.1
Ri
ht bac
Cente
Ambient temperature 20䉝
Maximum Minimum
-77.7-84.2-81.0±3.3
-77.0-83.6-80.3±3.3
-76.7
-80.0-83.2-81.6±1.6
-79.8-83.2-81.5±1.7
-79.7
-77.8-80.6-79.2±1.4
-77.0-79.9-78.5±1.5
-78.3-80.7-79.5±1.2
-80.0-82.0-81.0±1.0
-80.0-81.3-80.7±0.6
---79.6 -
䚸air temperature)
Unit:䉝
230V/50Hz
Middle o
cycle
-81.7-79.2±2.5
-81.9-80.8±1.1
Differential
䐟
䐠
䐡
䐢
䐣
䐤
䐥
䐦
䐧
䐨
䐩
䐪
䐫
䐬
䐭
䐮
䐯
Note:This data does not re
Upper areaMiddle area
Bottom are
Center of Upper shel
Center of Lower shel
Average
Left front-75.0-79.1-77.1±2.1
Left bac
Ri
ht front-74.7-79.5-77.1±2.6
Ri
ht bac
Cente
Left front-77.7-80.0-78.9±1.2
Left bac
Ri
ht front-77.4-79.7-78.6±0.9
Ri
ht bac
Cente
Left front-76.2-79.1-77.7±1.5
Left bac
Ri
ht front-77.5-80.9-79.2±1.5
Ri
ht bac
Cente
䠘Amount of power consumption䠚
Amount of power consumption when driving at cyc
Ambient temperature 30䉝
230V/50Hz
Maximum Minimum
-76.8-81.3-79.1±2.3
-76.8
-77.1-82.2-79.7±2.4
-79.5-82.2-80.9±1.4
-79.3
-79.0-80.7-79.9±1.4
-77.7-80.9-79.3±1.6
-78.4-82.0-80.2±1.7
-78.4-81.4-79.9±1.8
-78.8-80.6-79.7±0.9
-79.5-81.0-80.3±0.8
---79.2 -
resent a guarantee of product performance.
-81.6-79.2±2.4
-82.1-80.7±1.2
Middle o
cycle
Differential
SV=-80䉝䠅
Unit䠖kWh/da
Ambient temp. 30䉝Ambient temp. 20䉝
230V/50Hz
11.08
230V/50Hz
12.63
- 33 -
䠘Temperature distribution䠚
䉝
f
k
g
g
k
r
k
g
g
k
r
k
g
g
k
r
f
k
g
g
k
r
k
g
g
k
r
k
g
g
k
r
l
(
y
f
a
f
a
f
f
Temperature of the cycle in each area (SV=-70
Ambient temperature 20䉝
Maximum Minimum
䐟
䐠
䐡
䐢
䐣
䐤
䐥
䐦
䐧
䐨
䐩
䐪
䐫
䐬
䐭
䐮
䐯
䐟
䐠
䐡
䐢
䐣
䐤
䐥
䐦
䐧
䐨
䐩
䐪
䐫
䐬
䐭
䐮
䐯
Upper areaMiddle area
Bottom are
Center of Upper shel
Center of Lower shel
Average
Upper areaMiddle area
Bottom are
Center of Upper shel
Center of Lower shel
Average
Left front-67.6-74.7-71.2±3.6
Left bac
Ri
ht front-66.0-73.3-69.7±3.7
Ri
ht bac
Cente
Left front-66.7-70.3-68.5±1.8
Left bac
Ri
ht front-66.1-69.6-67.9±1.8
Ri
ht bac
Cente
Left front-62.4-64.8-63.6±1.2
Left bac
Ri
ht front-61.7-63.9-62.8±1.1
Ri
ht bac
Cente
Left front-68.6-77.4-73.0±4.4
Left bac
Ri
ht front-65.6-72.9-69.3±3.7
Ri
ht bac
Cente
Left front-66.0-69.8-67.9±1.9
Left bac
Ri
ht front-65.5-69.0-67.3±1.8
Ri
ht bac
Cente
Left front-61.3-63.5-62.4±1.1
Left bac
Ri
ht front-60.5-62.7-61.6±1.1
Ri
ht bac
Cente
-69.3-78.3-73.8±4.5
-68.4-77.2-72.8±4.4
-68.0
-69.5-75.0-72.3±2.8
-69.5-74.3-71.9±2.4
-68.8
-64.3-67.5-65.9±1.6
-62.1-65.1-63.6±1.5
-63.8-66.1-65.0±1.2
-69.0-72.7-70.9±1.9
-66.1-67.7-66.9±0.8
---68.7 -
Ambient temperature 30䉝
Maximum Minimum
-66.9-73.9-70.4±3.5
-68.0-76.5-72.3±4.3
-67.5
-69.0-74.6-71.8±2.8
-68.9-74.0-71.5±2.6
-68.2
-63.4-66.4-64.9±1.5
-61.1-64.4-62.8±1.7
-62.8-65.0-63.9±1.1
-68.2-72.0-70.1±1.9
-65.2-67.0-66.1±0.9
---68.0 -
䚸air temperature)
Unit:䉝
230V/50Hz
Middle o
cycle
-75.5-71.8±3.8
-72.6-70.7±1.9
230V/50Hz
Middle o
cycle
-75.0-71.3±3.8
-72.3-70.3±2.1
Differential
Differential
Note:This data does not represent a guarantee of product performance.
䠘Amount of power consumption䠚
Amount of power consumption when driving at cyc
Ambient temp. 20䉝
230V/50Hz
8.57
Ambient temp. 30䉝
SV=-70䉝䠅
Unit䠖kWh/da
230V/50Hz
9.96
- 34 -
<Temperatures during cycle operation>
-70
-72
-74
-76
]
-78
䉝
-80
-82
Temperature[
-84
-86
-88
-90
0.00.51.01.52.02.53.0
䐣䐯
Condition: SV-80䉝, AT30䉝
䐭
Time[hour]
䐮
䐨
-70
-72
-74
-76
]
-78
䉝
-80
-82
Temperature[
-84
-86
-88
-90
0.00.51.01.52.02.53.0
䐣
Condition: SV-80䉝, AT20䉝
䐯
䐮
Time[hour]
䐨
䐭
- 35 -
-60
Condition: SV-70䉝, AT30䉝
䐯
]
䉝
-62
-64
-66
-68
-70
-72
䐮
Temperature[
-74
-76
-78
-80
0.00.51.01.52.02.53.0
䐣
䐨
Time[hour]
䐭
-60
Condition: SV-70䉝, AT20䉝
-62
-64
-66
]
-68
䉝
-70
-72
Temperature[
-74
-76
-78
-80
0.00.51.01.52.02.53.0
䐣
Time[hour]
䐨
䐮
䐯
䐭
- 36 -
<Sample load test>
Conditions: 500ml water x 180 bottles 䠄90L䠅
Measuring points: a, b, c, d, L eva-out, H eva-out
Ambient temperature: 30䉝
䠄䉝䠅
40
20
-20
Front
4th shelf: 500ml x 45bottles
a
3rd shelf: 500ml x 45bottles
b
2nd shelf: 500ml x 45bottles
c
1st shelf: 500ml x 45bottles
d
Pull-down data AT:30䉝
Load d
0
H eva out
-40
Temperature
-60
-80
-100
0 1020304050607080
Load a
- 37 -
Load c
Time䠄hr䠅
L eva out
Load b
Temperature[䉝]
t
)
10
Temperature changes (SV-80䉝 䊻 SV-70䉝䊻-80䉝) 䚷AT30䉝
0
H eva out
-10
-20
-30
-40
-50
-60
-70
-80
-90
L eva out
Load d
Load a
Load b
Load c
0100200300400500600700800
Pull-up data AT30䉝
Time[min]
40
30
20
10
0
-10
䠄䉝䠅
-20
-30
-40
-50
Temperature
-60
-70
-80
-90
-100
0 102030405060708090
H䚷eva out
L eva ou
Load a
Load b
Load d
Load c
Time(hr
- 38 -
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.