For details about the combination, refer to
"Unit Combination Table" in the Appendix
of this manual.
IMPORTANT
These air conditioners employ new
refrigerant R410A.
Pay special attention when
servicing the unit.
REFERENCE NO.
SM700855-02
Page 4
SAFETY PRECAUTIONS
• Before doing repair work, please read the " SAFETY PRECAUTIONS" carefully and fully understand them.
• The precautionary items here are divided into " Warning" and " Caution" items.
Items in particular which may cause death or serious injury to the service personnel if the work is not performed correctly,
are included in the " Warning" table.
However, even precautionary items identified as " Caution" also have the potential for serious consequences
if not performed correctly.
Important safety precautions are described for all items in both categories. Be sure to carefully follow all of them.
• Symbol Indication
: This symbol indicates items to which we need to pay attention.
In this triangle, a definite precautionary item is described.
: This symbol indicates the item to be prohibited.
In or close to this circle, a prohibited item is described.
: This symbol indicates the items requiring special attention or instruction.
In or close to this circle, a prohibited item is described.
• After doing repair work, perform a test run to confirm that there are no abnormalities.
At the same time, explain the precautions in use to the user.
Warning
Before performing an overhaul, disconnect the power plug or power cable from the unit.
Performing the work with the power supplied to the unit, may cause an electric shock.
When repair work or circuit inspection that requires power supply for the air conditioner, is to be performed,
do not touch the charging section.
Doing so may cause an electric shock.
Prohibit
For the step-up capacitor attached to the electric section, perform the repair work after sufficiently discharging it.
Insufficient capacitor discharge may cause an electric shock.
Do not perform repair work on the electric sections with wet hands.
Doing so may cause an electric shock.
Do not start or stop the air conditioner by means of connecting or disconnecting the power plug.
Doing so may cause an electric shock or fire.
When conducting repair work only use components included in the parts list for the corresponding unit and perform
the work with the appropriate tools.
Incorrect or poor repair work may cause an electric shock or fire.
Never modify the unit.
Doing so may cause an electric shock or fire.
Perform all electric work according to local applicable regulations related to electrical equipment or interior wiring
regulation and make sure to use the exclusive circuit.
Insufficient capacity to the electric circuit or defective arrangement results may cause an electric shock or fire.
Make sure to replace any power cable or lead wire showing any signs of scratch or deterioration.
Failure to do so may cause an electric shock, overheating or fire.
Make sure that there is no dust on or slack in the power plug and insert fully into the socket.
Dust or incomplete connections may cause an electric shock or fire.
Do not damage or process the power cord, as it may cause an electric shock or fire.
Prohibit
Prohibit
Prohibit
Prohibit
For the wiring between the indoor unit and outdoor unit, securely fix the specified cable onto the terminal plate.
Poorly fixed wiring may cause a heat or fire.
After connecting the wiring between the indoor unit and outdoor unit, attach the terminal cover securely.
Incomplete attachment of the terminal cover may cause overheating or fire.
2
Page 5
Warning
If refrigerant gas blows off during the work, do not touch the refrigerant gas as it may cause frostbite.
If refrigerant gas leaks during the work, ventilate the room.
If refrigerant gas catches fire, harmful gas may be generated.
Do not mix any gas other than the specified refrigerant gas in the refrigerating cycle.
If air or other contaminants mix with the gas, pressure will become extremely high in the refrigerating cycle,
which may cause a unit breakdown."
When the welded section of the compressor intake or discharge pipe is to be disconnected, perform it in
a well-ventilated place after sufficiently recovering the refrigerant gas.
Any residue gas may jet out refrigerant or refrigerating machine oil, which may cause an injury.
When the work is to be performed in a high place (About 2 meters or more), make sure to wear a safety helmet,
gloves and safety belt. Insufficient safety gear may cause a serious injury in case of a fall.
When the unit is to be relocated, confirm that the new installation location has sufficient strength for the weight of the unit.
Insufficient strength of the installation location and incomplete installation work may cause an injury due to
the unit falling.
When the remote controller batteries are replaced, dispose of the old batteries out of the reach of children.
If a child swallows a battery, make sure that the child gets immediate medical attention.
Caution
Prohibit
Prohibit
Do not wash the air conditioner with water, as this may cause an electric shock or fire.
For the repair work in places with high humidity or moisture, make sure to ground the unit.
Failure to do so may cause an electric shock.
Confirm that the component attachment position, wiring condition, soldering condition and connector connection
are normal.
If not, it may cause overheating or fire.
Confirm that the temperature around the compressor is not too high, and then perform the repair work.
Failure to do so may cause a burn.
Perform welding work in a place with good ventilation.
If the work is performed in a poorly ventilated area, it might cause a lack of oxygen.
If the installation plate or attachment frame has deteriorated due to corrosion, etc., replace it.
Failure to do so may cause an injury due to the unit falling.
When the cleaning is to be performed, make sure to turn off the power and pull out the plug.
Touching the fan that is rotating at high speed may result in an injury.
When the indoor unit is to be removed, do not place it on an incline.
Doing so may cause wet furniture because water left inside may trickle down.
Do not hold the sharp end of the unit or the aluminum fins, as it may cause an injury to your hand or finger.
Prohibit
Prohibit
Prohibit
After repairs, make sure to measure the insulation resistance and confirm that the value is 1 Mohm or more.
Any insulation error may cause an electric shock.
After repairs, make sure to check the drainage of the indoor unit.
Inappropriate drainage may cause wet furniture and floors due to water leakage.
2-1. Unit Specifications
2-2. Major Component Specifications
2-3. Other Component Specifications
3. DIMENSIONAL DATA
4. REFRIGERANT FLOW DIAGRAM
4-1. Refrigerant Flow Diagram
5. PERFORMANCE DATA
5-1. Temperature Charts
5-2. Cooling Capacity
5-3. Heating Capacity
6. ELECTRICAL DATA
6-1. Electric Wiring Diagrams
7. FUNCTIONS
7-1. Explanation of Functions
7-2. Protective Functions
8. TROUBLESHOOTING
8-1. Precautions before Performing Inspection or Repair
8-2. Trouble Diagnosis by Error Monitop Lamps
8-3. Checking the Outdoor System
8-4. Trouble Diagnosis of Each Part
9. REFRIGERANT R410A:
SPECIAL PRECAUTIONS WHEN SERVICING UNIT
9-1. Characteristics of New Refrigerant R410A
9-2. Checklist before Servicing
9-3. Tools Specifically for R410A
9-4. Tubing Installation Procedures
9-5. In Case of Compressor Malfunction
9-6. In Case Refrigerant is Leaking
9-7. Charging Additional Refrigerant
9-8. Retro-Fitting Existing Systems
APPENDIX A INSTALLATION INSTRUCTIONS
APPENDIX B UNIT COMBINATION TABLES
5
Page 8
APPLICABLE INDOOR UNITS
Wall Mounted Type
Indoor Unit
KMHS0772
Multi-Outdoor Unit
KMHS0972KMHS1272KMHS1872KMHS2472
3-Room
4-Room
4-Room
CMH1972A
CMH2472A
CMH3172A
Semi-Concealed Type
Indoor Unit
Multi-Outdoor Unit
3-Room
4-Room
4-Room
CMH1972A
CMH2472A
CMH3172A
YES
YES
YES
XMHS0972
&
PNR-XS1872
YES
YES
YES
YES
YES
YES
XMHS1272
&
PNR-XS1872
YES
YES
YES
YES
YES
YES
XHS1872
&
PNR-XS1872
YES
YES
YES
YES
YES
YES
NO
YES
YES
6
Page 9
1. OPERATING RANGE
TemperatureIndoor Air Intake Temp.Outdoor Air Intake Temp.
1. The values shown in performance section and electrical rating section above are based on the following unit combination.
For other combination unit, please refer to the "Unit Combination Tables" in this manual.
Indoor Unit : KMHS0972 3units Outdoor Unit : CMH1972A 1unit
2. Rating conditions are: Cooling : Indoor air temp.80°F D.B./ 67°F W.BHeating : Indoor air temp.70°F D.B.
Outdoor air temp. 95°F D.B./ 75°F W.B.Outdoor air temp. 47°F D.B./ 43°F W.B.
< 230V >
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Compressor
Refrigerant / Amount charged at shipmentIbs (g)
Refrigerant Control
( 11,600 to 24,800 )
( 3.40 to 7.30 )
6.7
1,500
7.7
1,735
19,100
5.60
24,800
7.30
( 9,800 to 19,100 )
( 2.90 to 5.60 )
Shipping Volume
CoolingHeating
16,300
2,800
Net
Shipping
Package Dimensions
Weight
Height × Width × Depth
Height × Width × Depth
Ibs (kg)
Ibs (kg)
cu.ft (m
3
)
(mm)
inch
(mm)
3-Room Multi Outdoor Unit
Outdoor Unit
inch
-
-
187 to 253
Dimensions & Weight
Refrigerant Tubing Connections
Unit Dimensions
Electrical Rating
Sensible Capacity
Latent Capacity
WPower Input
V
A
Available Voltage Range
Running Amperes
Operation Sound (High) Cool / Heat
Narrow tube
Wide tube
Refrigerantinch (mm)
Tube Diameterinch (mm)
143.3
152.1
12.71
(65.0)
(69.0)
(0.36)
33-27/32 × 40-5/8 × 16-1/4
(860 × 1,032 × 413)
(740 × 900 × 320)
Outdoor Unit
29-1/8 × 35-7/16 × 12-19/32
1/4 (6.35) × 3
3/8 (9.52) × 3
ft (m)
dB-A
Max. allowable tubing length per unit
Flare Type
82 (25)
R410A / 6.17 (2,800)
Electric Expansion Valve
DC Twin Rotary (Inverter)
Fan SpeedsAuto (Hi, Me, Lo)
ControlMicroprocessor
Features
HSPF
Compressor Locked Rotor Amperes
BTU/Wh
50 / 52
BTU/h
Performance
-8.8
%Power Factor9898
A14.5
Type
BTU/h
kW
Total Capacity
BTU/h
SEERBTU/Wh16.4-
3Number of Connectable Indoor Units
3Number of Operatable Indoor Units
1. The values shown in performance section and electrical rating section above are based on the following unit combination.
For other combination unit, please refer to the "Unit Combination Tables" in this manual.
Indoor Unit : KMHS0972 3units Outdoor Unit : CMH1972A 1unit
2. Rating conditions are: Cooling : Indoor air temp.80°F D.B./ 67°F W.BHeating : Indoor air temp.70°F D.B.
Outdoor air temp. 95°F D.B./ 75°F W.B.Outdoor air temp. 47°F D.B./ 43°F W.B.
9
Page 12
Outdoor UnitCMH2472A
Indoor UnitKMHS0972
Type
Total Capacity
Sensible Capacity
Latent Capacity
Performance
Available Voltage Range
Running Amperes
EERBTU/h/W11.4COPW/W-3.8
SEERBTU/Wh16.5HSPF
Electrical Rating
Compressor Locked Rotor Amperes
Fuse or Circuit Breaker CapacityA20
ControlMicroprocessor
Fan SpeedsAuto (Hi, Me, Lo)
Compressor
Refrigerant / Amount charged at shipmentIbs (g)
Refrigerant Control
Operation Sound (High) Cool / Heat
Features
Refrigerant Tubing Connections
Max. allowable tubing length per unit
Refrigerantinch (mm)
Tube Diameterinch (mm)
Unit Dimensions
Height × Width × Depth
Package Dimensions
Height × Width × Depth
Weight
Dimensions & Weight
Shipping Volume
× 3
Narrow tube
Wide tube
Net
Shipping
4-Room Multi Outdoor Unit
4Number of Connectable Indoor Units
4Number of Operatable Indoor Units
1. The values shown in performance section and electrical rating section above are based on the following unit combination.
For other combination unit, please refer to the "Unit Combination Tables" in this manual.
Indoor Unit : KMHS0972 3units Outdoor Unit : CMH2472A 1unit
2. Rating conditions are: Cooling : Indoor air temp.80°F D.B./ 67°F W.BHeating : Indoor air temp.70°F D.B.
Outdoor air temp. 95°F D.B./ 75°F W.B.Outdoor air temp. 47°F D.B./ 43°F W.B.
10
Page 13
Outdoor UnitCMH2472A
Indoor UnitKMHS0972
Type
Total Capacity
Sensible Capacity
Latent Capacity
Performance
Available Voltage Range
Running Amperes
EERBTU/h/W11.4COPW/W-3.8
SEERBTU/Wh16.5HSPF
Electrical Rating
Compressor Locked Rotor Amperes
Fuse or Circuit Breaker CapacityA20
ControlMicroprocessor
Fan SpeedsAuto (Hi, Me, Lo)
Compressor
Refrigerant / Amount charged at shipmentIbs (g)
Refrigerant Control
Operation Sound (High) Cool / Heat
Features
Refrigerant Tubing Connections
Max. allowable tubing length per unit
Refrigerantinch (mm)
Tube Diameterinch (mm)
Unit Dimensions
Height × Width × Depth
Package Dimensions
Height × Width × Depth
Weight
Dimensions & Weight
Shipping Volume
× 3
Narrow tube
Wide tube
Net
Shipping
4-Room Multi Outdoor Unit
4Number of Connectable Indoor Units
4Number of Operatable Indoor Units
1. The values shown in performance section and electrical rating section above are based on the following unit combination.
For other combination unit, please refer to the "Unit Combination Tables" in this manual.
Indoor Unit : KMHS0972 3units Outdoor Unit : CMH2472A 1unit
2. Rating conditions are: Cooling : Indoor air temp.80°F D.B./ 67°F W.BHeating : Indoor air temp.70°F D.B.
Outdoor air temp. 95°F D.B./ 75°F W.B.Outdoor air temp. 47°F D.B./ 43°F W.B.
11
Page 14
Outdoor UnitCMH3172A
Indoor UnitKMHS0972
Type
Total Capacity
Sensible Capacity
Latent Capacity
Performance
Available Voltage Range
Running Amperes
EERBTU/h/W10.9COPW/W-4.0
SEERBTU/Wh17.2HSPF
Electrical Rating
Compressor Locked Rotor Amperes
Fuse or Circuit Breaker CapacityA20
ControlMicroprocessor
Fan SpeedsAuto (Hi, Me, Lo)
Compressor
Refrigerant / Amount charged at shipmentIbs (g)
Refrigerant Control
Operation Sound (High) Cool / Heat
Features
Refrigerant Tubing Connections
Max. allowable tubing length per unit
Refrigerantinch (mm)
Tube Diameterinch (mm)
Unit Dimensions
Height × Width × Depth
Package Dimensions
Height × Width × Depth
Weight
Dimensions & Weight
Shipping Volume
× 4
Narrow tube
Wide tube
Net
Shipping
4-Room Multi Outdoor Unit
4Number of Connectable Indoor Units
4Number of Operatable Indoor Units
1. The values shown in performance section and electrical rating section above are based on the following unit combination.
For other combination unit, please refer to the "Unit Combination Tables" in this manual.
Indoor Unit : KMHS0972 4units Outdoor Unit : CMH3172A 1unit
2. Rating conditions are: Cooling : Indoor air temp.80°F D.B./ 67°F W.BHeating : Indoor air temp.70°F D.B.
Outdoor air temp. 95°F D.B./ 75°F W.B.Outdoor air temp. 47°F D.B./ 43°F W.B.
12
Page 15
Outdoor UnitCMH3172A
Indoor UnitKMHS0972
Type
Total Capacity
Sensible Capacity
Latent Capacity
Performance
Available Voltage Range
Running Amperes
EERBTU/h/W10.9COPW/W-4.0
SEERBTU/Wh17.2HSPF
Electrical Rating
Compressor Locked Rotor Amperes
Fuse or Circuit Breaker CapacityA20
ControlMicroprocessor
Fan SpeedsAuto (Hi, Me, Lo)
Compressor
Refrigerant / Amount charged at shipmentIbs (g)
Refrigerant Control
Operation Sound (High) Cool / Heat
Features
Refrigerant Tubing Connections
Max. allowable tubing length per unit
Refrigerantinch (mm)
Tube Diameterinch (mm)
Unit Dimensions
Height × Width × Depth
Package Dimensions
Height × Width × Depth
Weight
Dimensions & Weight
Shipping Volume
× 4
Narrow tube
Wide tube
Net
Shipping
4-Room Multi Outdoor Unit
4Number of Connectable Indoor Units
4Number of Operatable Indoor Units
1. The values shown in performance section and electrical rating section above are based on the following unit combination.
For other combination unit, please refer to the "Unit Combination Tables" in this manual.
Indoor Unit : KMHS0972 4units Outdoor Unit : CMH3172A 1unit
2. Rating conditions are: Cooling : Indoor air temp.80°F D.B./ 67°F W.BHeating : Indoor air temp.70°F D.B.
Outdoor air temp. 95°F D.B./ 75°F W.B.Outdoor air temp. 47°F D.B./ 43°F W.B.
13
Page 16
2-2. Major Component Specifications
2-2-1. Outdoor Unit
Outdoor UnitCMH1972A
Control PCB
Part No.
Controls
Control Circuit Fuse
Compressor
Type
Compressor Model / Nominal Output
Compressor Oil ... Amount
Coil Resistance (Ambient Temp. 68 °F (20 °C))
Safety Device
CT (Peak current cut-off control)
Compressor Discharge Temp. Control
Operation cut-off control in abnormal ambient Temp.
Overload Relay
Operation Temp.
Run Capacitor
Crankcase Heater
Pints (cc)
Ohm
Model
Micro F
VAC
CB-CMH1972A
Microprocessor
250V 25A
DC Twin Rotary (Hermetic)
5KD240XAB21 / 1,700W
FV50S ... 1.91 (900)
U - V :
0.720
V - W :
W - U :
CS-7L-2515
Open : 239 °F (115 °C), Close : 212 °F (100 °C)
230V 30W
0.708
0.726
Yes
Yes
Yes
-
-
Fan
Type
Q'ty ... Dia.inch (mm)
Fan Motor
Type
Model ... Q'ty
No. of Poles
Rough Measure RPM (Cool / Heat)
Nominal Output
Coil Resistance
(Ambient Temp. 68 °F (20 °C))
Safety Device
Type
Over-Current Protection
Run Capacitor
Heat Exchanger Coil
Coil
Rows
Fins per inch
Face Area
Over-Heat Protection
W
Ohm
Micro F
VAC
2
ft
(m2)
Propeller
1 ... D18-1/8 (D460)
DC Motor
SIC-71FW-D490-1 ... 1
8
750 / 750
90
-
Internal Controller
Yes
Yes
-
-
Aluminum Plate Fin / Copper Tube
2
18.1
6.40 (0.595)
External FinishAcrylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
14
Page 17
Outdoor UnitCMH2472A
Control PCB
Part No.
Controls
Control Circuit Fuse
Compressor
Type
Compressor Model / Nominal Output
Compressor Oil ... Amount
Coil Resistance (Ambient Temp. 68 °F (20 °C))
Safety Device
CT (Peak current cut-off control)
Compressor Discharge Temp. Control
Operation cut-off control in abnormal ambient Temp.
Overload Relay
Run Capacitor
Crankcase Heater
Pints (cc)
Ohm
Model
Operation Temp.
Micro F
VAC
CB-CMH2472A
Microprocessor
250V 25A
DC Twin Rotary (Hermetic)
5KD240XAB21 / 1,700W
FV50S ... 1.91 (900)
U - V :
0.720
V - W :
W - U :
0.708
0.726
Yes
Yes
Yes
CS-7L-2515
Open : 239 °F (115 °C), Close : 212 °F (100 °C)
-
-
230V 30W
Fan
Type
Q'ty ... Dia.inch (mm)
Fan Motor
Type
Model ... Q'ty
No. of Poles
Rough Measure RPM (Cool / Heat)
Nominal Output
Coil Resistance
(Ambient Temp. 68 °F (20 °C))
Safety Device
Type
Over-Current Protection
Over-Heat Protection
Run Capacitor
Heat Exchanger Coil
Coil
Rows
Fins per inch
Face Area
W
Ohm
Micro F
VAC
2
ft
(m2)
Propeller
1 ... D18-1/8 (D460)
DC Motor
SIC-71FW-D490-1 ... 1
8
750 / 750
90
-
Internal Controller
Yes
Yes
-
-
Aluminum Plate Fin / Copper Tube
2
18.1
6.40 (0.595)
External FinishAcrylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
15
Page 18
Outdoor UnitCMH3172A
Control PCB
Part No.
Controls
Control Circuit Fuse
Compressor
Type
Compressor Model / Nominal Output
Compressor Oil ... Amount
Coil Resistance (Ambient Temp. 68 °F (20 °C))
Safety Device
CT (Peak current cut-off control)
Compressor Discharge Temp. Control
Operation cut-off control in abnormal ambient Temp.
Overload Relay
Run Capacitor
Crankcase Heater
Pints (cc)
Ohm
Model
Operation Temp.
Micro F
VAC
CB-CMH3172A
Microprocessor
250V 25A
DC Twin Rotary (Hermetic)
5JD420XAB22 / 3,000W
FV50S ... 2.55 (1,200)
U - V :
0.435
V - W :
W - U :
0.441
0.452
Yes
Yes
Yes
CS-7L-2515
Open : 239 °F (115 °C), Close : 212 °F (100 °C)
-
-
230V 30W
Fan
Type
Q'ty ... Dia.inch (mm)
Fan Motor
Type
Model ... Q'ty
No. of Poles
Rough Measure RPM (Cool / Heat)
Nominal Output
Coil Resistance
(Ambient Temp. 68 °F (20 °C))
Safety Device
Type
Over-Current Protection
Over-Heat Protection
Run Capacitor
Heat Exchanger Coil
Coil
Rows
Fins per inch
Face Area
W
Ohm
Micro F
VAC
2
ft
(m2)
Propeller
1 ... D18-1/8 (D460)
DC Motor
SIC-71FW-D490-1 ... 1
8
800 / 750
90
-
Internal Controller
Yes
Yes
-
-
Aluminum Plate Fin / Copper Tube
2
18.1
7.75 (0.72)
External FinishAcrylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
16
Page 19
2-3. Other Component Specifications
Sensor Name
Outdoor air temp sensor
Outdoor heat exchanger sensor
AW / AN sensor
BW / BN sensor
CW / CN sensor
DW / DN sensor
Model No.
of sensor
TKS295B
TKS292B
TKS292B
TKS292B
TKS292B
TKS292B
40
35
30
25
20
Resistance (k ohm)
15
10
5
Quantity of Sensor
CMH1972ACMH2472ACMH3172A
1
1
1 / 1
1 / 1
1 / 1
0
1
1
1 / 1
1 / 1
1 / 1
1 / 1
1
1
1 / 1
1 / 1
1 / 1
1 / 1
0
Sensor Name
Compressor temp sensorTKS293B
Model No.
of sensor
200
180
160
140
120
100
Resistance (k ohm)
80
60
40
-
45142332415059 68
(
20)(-15)(-10) (-5) (0) (5) (10) (15) (20)
-
Temperature F ( C)
Quantity of Sensor
CMH1972ACMH2472ACMH3172A
11
1
20
0
32 50 68 86 104 122 140 158 176 194
(0) (10) (20)(30) (40)(50) (60)(70)(80) (90)
Temperature F ( C)
17
Page 20
Wide tube service valve
dia.3/8" (9.52) × 3
Narrow tube service valve
dia.1/4" (6.35) × 3
4-7/16
5-29/32 2-27/32 2-3/4
2-1/324-1/2
2-15/16
2-3/4
29-1/8(740)
23/32
1-13/16
35-7/16(900)
23-15/165-11/32
15/32
12-19/32(320)
13-19/32
14-17/32
11-17/32
ID:23/32
5-ID:15/16
1-3/8
2-15/16
2-1/16
3. DIMENSIONAL DATA
Outdoor Unit CMH1972A
Unit: inch(mm)
(852-0-0010-11200-0)
18
Page 21
Wide tube service valve
dia.1/2" (12.70) × 1
Narrow tube service valve
dia.1/4" (6.35) × 4
Wide tube service valve
dia.3/8" (9.52) × 3
4-7/16
5-29/32 2-27/32 2-3/4
2-3/4
2-1/324-1/2
2-15/16
2-3/4 2-3/4
29-1/8(740)
23/32
1-13/16
35-7/16(900)
23-15/165-11/32
15/32
12-19/32(320)
13-19/32
14-17/32
11-17/32
ID:23/32
5-ID:15/16
1-3/8
2-15/16
2-1/16
2-13/32
Outdoor Unit CMH2472A
Unit: inch(mm)
(852-0-0010-20400-0)
19
Page 22
Outdoor Unit CMH3172A
Unit: inch(mm)
(852-0-0010-20300-0)
Wide tube service valve
dia.1/2" (12.70) × 2
Narrow tube service valve
dia.1/4" (6.35) × 4
Wide tube service valve
dia.3/8" (9.52) × 2
4-7/16
5-29/32
2-1/324-1/2
2-15/16
2-3/4 2-3/4
35-1/32(890)
23/32
1-13/16
35-7/16(900)
23-15/165-11/32
15/32
12-19/32(320)
13-19/32
14-17/32
11-17/32
ID:23/32
5-ID:15/16
1-3/8
2-15/16
2-1/16
2-13/32
2-7/8 2-3/4 2-3/4
20
Page 23
4. REFRIGERANT FLOW DIAGRAM
4-1. Refrigerant Flow Diagram
Outdoor Unit CMH1972A
Indoor unitOutdoor unit
Wide tube
O.D.3/8"
O.D.3/8"
O.D.3/8"
Narrow tube
O.D.1/4"
O.D.1/4"
O.D.1/4"
Service valve on
wide tube
CW
BW
AW
Header
Service valve on
narrow tube
CN
BN
AN
StrainerHeader
Electric
expansion
valve
M
M
M
Sub
accumulator
4-way
valve
Defrost valve for
hot gas bypass
Main
accumulator
High pressure
switch
H.P.
S
Compressor
Heat exchanger
Cooling cycle
Heating cycle
Defrosting cycle
Insulation of Refrigerant Tubing
IMPORTANT
Because capillary tubing is used in the outdoor unit, both the
wide and narrow tubes of this air conditioner become cold. To
prevent heat loss and wet floors due to dripping of
condensation, both tubes must be well insulated with a
proper insulation material. The thickness of the insulation
should be a min.5/16"(8 mm).
After a tube has been insulated,
CAUTION
never try to bend it into a narrow
curve because it can cause the tube
to break or crack.
21
Thickness:
Min.5/16"(8 mm)
Wide tube
Insulation
Thickness:
Min.5/16"(8 mm)
Narrow tube
Page 24
Outdoor Unit CMH2472A
Indoor unitOutdoor unit
Wide tube
O.D.1/2"
O.D.3/8"
O.D.3/8"
O.D.3/8"
Narrow tube
O.D.1/4"
O.D.1/4"
O.D.1/4"
O.D.1/4"
Service valve on
wide tube
DW
CW
BW
AW
Service valve on
narrow tube
DN
CN
BN
AN
Header
Electric
expansion
valve
M
M
M
M
StrainerHeader
4-way
valve
Sub
accumulator
Defrost valve for
hot gas bypass
Main
accumulator
High pressure
switch
H.P.
S
Compressor
Heat exchanger
Cooling cycle
Heating cycle
Defrosting cycle
Insulation of Refrigerant Tubing
IMPORTANT
Because capillary tubing is used in the outdoor unit, both the
wide and narrow tubes of this air conditioner become cold. To
prevent heat loss and wet floors due to dripping of
condensation, both tubes must be well insulated with a
proper insulation material. The thickness of the insulation
should be a min.5/16"(8 mm).
After a tube has been insulated,
CAUTION
never try to bend it into a narrow
curve because it can cause the tube
to break or crack.
22
Thickness:
Min.5/16"(8 mm)
Wide tube
Insulation
Thickness:
Min.5/16"(8 mm)
Narrow tube
Page 25
Outdoor Unit CMH3172A
Indoor unitOutdoor unit
Wide tube
O.D.1/2"
O.D.1/2"
O.D.3/8"
O.D.3/8"
Narrow tube
O.D.1/4"
O.D.1/4"
O.D.1/4"
O.D.1/4"
Service valve on
wide tube
DW
CW
BW
AW
Service valve on
narrow tube
DN
CN
BN
AN
Header
Electric
expansion
valve
M
M
M
M
StrainerHeader
4-way
valve
Sub
accumulator
Defrost valve for
hot gas bypass
Main
accumulator
High pressure
switch
H.P.
S
Compressor
Heat exchanger
Cooling cycle
Heating cycle
Defrosting cycle
Insulation of Refrigerant Tubing
IMPORTANT
Because capillary tubing is used in the outdoor unit, both the
wide and narrow tubes of this air conditioner become cold. To
prevent heat loss and wet floors due to dripping of
condensation, both tubes must be well insulated with a
proper insulation material. The thickness of the insulation
should be a min.5/16"(8 mm).
After a tube has been insulated,
CAUTION
never try to bend it into a narrow
curve because it can cause the tube
to break or crack.
23
Thickness:
Min.5/16"(8 mm)
Wide tube
Insulation
Thickness:
Min.5/16"(8 mm)
Narrow tube
Page 26
5. PERFORMANCE DATA
5-1. Temperature Charts
5-1-1. Temperature Charts (CMH1972A)
Outdoor Unit CMH1972A Indoor Unit KMHS0772 ×1
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan)
(230V, 60Hz)
(1) Low pressure performance chart(1) High pressure performance chart
Heating Characteristics
(RH : 85%, Indoor fan speed : High fan)
(230V, 60Hz)
188
(1.3)
psig (MPaG)
174
(1.2)
160
(1.1)
Low pressure at wide tube service valve
146
(1.0)
Lo fanHi fanHH fan
p. 86°F (30°C
77
(25)
Indoor air tem
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
80°F (27°C)
75°F (24°C)
95
(35)
506
)
104
(40)
(3.5)
psig (MPaG)
434
(3.0)
362
(2.5)
High pressure at wide tube service valve
290
(2.0)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air temp. 73°F (23°C)
70°F (21°C)
63°F (17°C)
(2) Operating current performance chart(2) Operating current performance chart
Lo fanHi fanHH fan
5
4
Indoor air temp. 86°F (30°C)
86
(30)
80°F (27°C)
75°F (24°C)
95
(35)
104
(40)
3
Operating current (A)
2
77
(25)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
8
7
70°F (21°C
63°F (17°
C)
)
C)
6
Operating current (A)
5
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air te
mp. 73°F (23°
(3) Indoor discharge air performance chart(3) Indoor discharge air performance chart
140(60)
131(55)
122(50)
113(45)
104(40)
95(35)
86(30)
Indoor air tem
)
p. 73°F (23°C
70°F (21°C)
63°F (17°C)
68.0(20)
64.4(18)
60.8(16)
57.2(14)
53.6(12)
50.0(10)
Lo fanHi fanHH fan
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
46.4( 8)
Indoor discharge air temperature °F (°C)
77
(25)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
NOTE
• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on
the indoor unit type.
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
(In this case, be sure to stop all the indoor units where performance is not being checked.)
• The performance is for a tubing length of 24.6t (7.5m). If the tubing length is different, the performance chart will vary.
104
(40)
24
77(25)
Indoor discharge air temperature °F (°C)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Page 27
Outdoor Unit CMH1972A Indoor Unit KMHS0972 × 1
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan)
(230V, 60Hz)
Heating Characteristics
(RH : 85%, Indoor fan speed : High fan)
(230V, 60Hz)
(1) Low pressure performance chart(1) High pressure performance chart
188
(1.3)
psig (MPaG)
174
(1.2)
160
(1.1)
Low pressure at wide tube service valve
146
(1.0)
Lo fanHi fan
77
(25)
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
HH fan
104
(40)
506
(3.5)
psig (MPaG)
434
(3.0)
362
(2.5)
High pressure at wide tube service valve
290
(2.0)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air temp. 73
Indoor air temp. 73°F (23°C)
70°F (21°C)
70
63°F (17°C)
63
(2) Operating current performance chart(2) Operating current performance chart
Lo fanHi fan
6
5
4
Operating current (A)
3
77
(25)
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
HH fan
104
(40)
8
7
3
70
Indoor air temp. 7
Indoor air temp. 73°F (23°C)
6
Operating current (A)
5
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
70°F (21°C)
63
63°F (17°C)
F (23
°
F (21
°
F (17
°
F (23
°
F (21
°
F (17
°
C)
°
C)
°
C)
°
C)
°
C)
°
C)
°
(3) Indoor discharge air performance chart(3) Indoor discharge air performance chart
68.0(20)
64.4(18)
60.8(16)
57.2(14)
53.6(12)
50.0(10)
46.4( 8)
Indoor discharge air temperature °F (°C)
NOTE
• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on
the indoor unit type.
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
(In this case, be sure to stop all the indoor units where performance is not being checked.)
• The performance is for a tubing length of 24.6ft (7.5m). If the tubing length is different, the performance chart will vary.
Lo fanHi fan
77
(25)
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
HH fan
104
(40)
25
140(60)
131(55)
122(50)
Indoor air temp. 73
113(45)
104(40)
95(35)
86(30)
77(25)
Indoor discharge air temperature °F (°C)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air temp. 73°F (23°C)
°
F (23
°
°C)
°F (21
70
70°F (21°C)
°C)
°F (17
63
63°F (17°C)
C)
Page 28
Outdoor Unit CMH1972A Indoor Unit KMHS1272 ×1
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan)
(230V, 60Hz)
Heating Characteristics
(RH : 85%, Indoor fan speed : High fan)
(230V, 60Hz)
(1) Low pressure performance chart(1) High pressure performance chart
578
174
(1.2)
psig (MPaG)
160
(1.1)
146
(1.0)
Low pressure at wide tube service valve
132
(0.9)
Lo fanHi fan
77
(25)
Indoor air temp. 86°F (30°C
80°F (27°C)
75°F (24°C)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
HH fan
)
104
(40)
(4.0)
506
psig (MPaG)
(3.5)
C)
°
F (23
434
(3.0)
Indoor air temp. 73
Indoor air temp. 73°F (23°C)
F (21
°
20
70°F (21°C)
F (17
362
(2.5)
High pressure at wide tube service valve
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
°
63
63°F (17°C)
°
C)
°
C)
°
(2) Operating current performance chart(2) Operating current performance chart
10
Lo fanHi fan
6
5
4
Operating current (A)
Indoor air temp. 86°F (30°C)
)
80°F (27°C
75°F (24°C)
HH fan
9
8
7
6
5
Operating current (A)
4
C)
°
F (23
°
C)
°
F (21
C)
°
°
70
70°F (21°C)
F (17
Indoor air temp. 73
Indoor air temp. 73°F (23°C)
°
63
63°F (17°C)
3
77
(25)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
104
(40)
3
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
(3) Indoor discharge air performance chart(3) Indoor discharge air performance chart
68.0(20)
64.4(18)
60.8(16)
57.2(14)
53.6(12)
50.0(10)
46.4( 8)
Indoor discharge air temperature °F (°C)
Lo fanHi fan
77
(25)
Indoor air tem
80°F (27°C)
75°F (24°C)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
p. 86°F (30°C)
95
(35)
HH fan
104
(40)
NOTE
• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on
the indoor unit type.
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
(In this case, be sure to stop all the indoor units where performance is not being checked.)
• The performance is for a tubing length of 24.6ft (7.5m). If the tubing length is different, the performance chart will vary.
140(60)
131(55)
122(50)
113(45)
Indoor air temp. 73
104(40)
95(35)
86(30)
77(25)
Indoor discharge air temperature °F (°C)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air temp. 73°F (23°C)
C)
°
F (23
°
C)
°
F (21
°
°
70
70°F (21°C)
F (17
°
63
63°F (17°C
C)
)
26
Page 29
Outdoor Unit CMH1972A Indoor Unit KMHS1872 ×1
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan)
(230V, 60Hz)
Heating Characteristics
(RH : 85%, Indoor fan speed : High fan)
(230V, 60Hz)
(1) Low pressure performance chart(1) High pressure performance chart
174
(1.2)
psig (MPaG)
160
(1.1)
146
(1.0)
Low pressure at wide tube service valve
132
(0.9)
Lo fanHi fan
77
(25)
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
HH fan
104
(40)
578
(4.0)
psig (MPaG)
506
(3.5)
F (23
°
434
(3.0)
High pressure at wide tube service valve
362
(2.5)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air temp. 73
Indoor air temp. 73°F (23°C)
F (21
°
70
70°F (21°C
F (17
°
63
63°F (17°C)
C)
°
)
C)
°
C)
°
(2) Operating current performance chart(2) Operating current performance chart
8
Lo fanHi fan
7
6
Operating current (A)
5
77
(25)
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
HH fan
104
(40)
12
11
10
Indoor air temp. 73
9
8
Operating current (A)
7
6
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air temp. 73°F (23°C)
°
F (23
°
C)
°
F (21
°
70
70°F (21°C)
C)
°
F (17
°
63
63°F (17°C)
C)
(3) Indoor discharge air performance chart(3) Indoor discharge air performance chart
68.0(20)
64.4(18)
60.8(16)
57.2(14)
53.6(12)
50.0(10)
Indoor discharge air temperature °F (°C)
46.4( 8)
NOTE
• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on
the indoor unit type.
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
(In this case, be sure to stop all the indoor units where performance is not being checked.)
• The performance is for a tubing length of 24.6ft (7.5m). If the tubing length is different, the performance chart will vary.
Lo fanHi fan
77
(25)
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
HH fan
104
(40)
27
140(60)
131(55)
122(50)
113(45)
104(40)
95(35)
86(30)
Indoor discharge air temperature °F (°C)
77(25)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air temp. 73
Indoor air temp. 73°F (23°C)
°
F (23
°
°
F (21
°
70
70°F (21°C)
°
F (17
°
63
63°F (17°C)
C)
C)
C)
Page 30
Outdoor Unit CMH1972A Indoor Unit XMHS0972 ×1
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan)
(230V, 60Hz)
Heating Characteristics
(RH : 85%, Indoor fan speed : High fan)
(230V, 60Hz)
(1) Low pressure performance chart(1) High pressure performance chart
174
(1.2)
psig (MPaG)
160
(1.1)
146
(1.0)
Low pressure at wide tube service valve
132
(0.9)
Lo fanHi fan
77
(25)
Indoor air temp. 86
Indoor air temp. 86°F (30°C)
°
80
80°F (27°C)
°
75
75°F (24°C)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
F (27
F (24
C)
°
C)
°
95
(35)
F (30
°
HH fan
C)
°
104
(40)
506
(3.5)
psig (MPaG)
F (23
434
(3.0)
Indoor air temp. 73
362
(2.5)
High pressure at wide tube service valve
290
(2.0)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air temp. 73°F (23°C)
°
F (21
°
70
70°F (21°C)
F (17
°
63
63°F (17°C)
C)
°
C)
°
C)
°
(2) Operating current performance chart(2) Operating current performance chart
6
Lo fanHi fan
5
4
Operating current (A)
3
Indoor air tem
Indoor air tem
C)
°
F (27
°
80
80°F (27°C)
°
F (24
°
75
75°F (24°C)
p. 86
p. 86°F (30°C
C)
F (30
°
HH fan
)
C)
°
8
7
6
Operating current (A)
5
C)
°
F (23
°
3
C)
°
F (21
°
C)
°
70
70°F (21°C)
F (17
°
63
Indoor air temp. 7
Indoor air temp. 73°F (23°C)
63°F (17°C)
77
(25)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
104
(40)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
(3) Indoor discharge air performance chart(3) Indoor discharge air performance chart
68.0(20)
64.4(18)
60.8(16)
57.2(14)
53.6(12)
50.0(10)
46.4( 8)
Indoor discharge air temperature °F (°C)
Lo fanHi fan
77
(25)
Indoor air temp. 86
Indoor air temp. 86°F (30°C)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
F (30
°
°
F (27
°
80
80°F (27°C)
F (24
°
75
75°F (24°C)
HH fan
C)
°
C)
C)
°
104
(40)
NOTE
• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on
the indoor unit type.
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
(In this case, be sure to stop all the indoor units where performance is not being checked.)
• The performance is for a tubing length of 24.6ft (7.5m). If the tubing length is different, the performance chart will vary.
140(60)
131(55)
122(50)
113(45)
104(40)
95(35)
86(30)
77(25)
Indoor discharge air temperature °F (°C)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air temp. 73°
Indoor air temp. 73°F (23°C)
F (23
F (21
°
70
70°F (21°C)
°F (17
63
63°F (17°C)
C)
°
C)
°
C)
°
28
Page 31
Outdoor Unit CMH1972A Indoor Unit XMHS1272 ×1
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan)
(230V, 60Hz)
Heating Characteristics
(RH : 85%, Indoor fan speed : High fan)
(230V, 60Hz)
(1) Low pressure performance chart(1) High pressure performance chart
174
(1.2)
Lo fanHi fan
HH fan
578
(4.0)
160
psig (MPaG)
(1.1)
146
(1.0)
132
(0.9)
Low pressure at wide tube service valve
77
(25)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
86
(30)
95
(35)
104
(40)
506
psig (MPaG)
(3.5)
C)
°
F (23
434
(3.0)
Indoor air temp. 73
362
(2.5)
High pressure at wide tube service valve
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air temp. 73°F (23°C)
°
C)
°
F (21
°
70
70°F (21°C)
C)
°
F (17
°
63
63°F (17°C)
(2) Operating current performance chart(2) Operating current performance chart
10
Lo fanHi fan
6
5
4
Operating current (A)
3
77
(25)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
86
(30)
95
(35)
HH fan
104
(40)
9
8
7
6
5
Operating current (A)
4
3
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air tem
Indoor air tem
C)
°
F (23
°
C)
°
p. 73
p. 73°F (23°C)
F (21
°
70
70°F (21°C
C)
°
F (17
°
63
63°F (17°C)
)
(3) Indoor discharge air performance chart(3) Indoor discharge air performance chart
68.0(20)
64.4(18)
60.8(16)
57.2(14)
53.6(12)
50.0(10)
46.4( 8)
Indoor discharge air temperature °F (°C)
42.8( 6)
NOTE
• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on
the indoor unit type.
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
(In this case, be sure to stop all the indoor units where performance is not being checked.)
• The performance is for a tubing length of 24.6ft (7.5m). If the tubing length is different, the performance chart will vary.
Lo fanHi fan
77
(25)
80°F (27°C)
75°F (24°C)
mp. 86°F (30°
95
(35)
Indoor air te
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
HH fan
C)
104
(40)
29
140(60)
131(55)
C)
122(50)
113(45)
104(40)
95(35)
86(30)
77(25)
Indoor discharge air temperature °F (°C)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air temp. 73
Indoor air temp. 73°F (23°C)
°
°F (23
C)
°
F (21
°
C)
°
70
70°F (21°C)
F (17
°
63
63°F (17°C)
Page 32
Outdoor Unit CMH1972A Indoor Unit XHS1872 ×1
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan)
(230V, 60Hz)
Heating Characteristics
(RH : 85%, Indoor fan speed : High fan)
(230V, 60Hz)
(1) Low pressure performance chart(1) High pressure performance chart
174
(1.2)
160
psig (MPaG)
(1.1)
146
(1.0)
132
(0.9)
Low pressure at wide tube service valve
Lo fanHi fan
77
(25)
Indoor air tem
80°F (27°C)
75°F (24°C)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
p. 86°F (30°C)
95
(35)
HH fan
104
(40)
578
(4.0)
psig (MPaG)
506
(3.5)
°C)
F (23
434
(3.0)
Indoor air temp. 73
High pressure at wide tube service valve
Indoor air temp. 73°F (23°C)
362
(2.5)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
°
C)
°
F (21
°
70
70°F (21°C)
F (17
°
63
63°F (17°C)
C)
°
(2) Operating current performance chart(2) Operating current performance chart
Lo fanHi fan
7
6
5
Operating current (A)
4
77
(25)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
86
(30)
95
(35)
HH fan
104
(40)
12
11
C)
F (21
F (17
F (23
°
C)
°
C)
°
°
10
9
°
Indoor air temp. 73
Indoor air temp. 73°F (23°C)
70
8
Operating current (A)
7
6
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
70°F (21°C)
°
63
63°F (17°C)
(3) Indoor discharge air performance chart(3) Indoor discharge air performance chart
68.0(20)
64.4(18)
60.8(16)
57.2(14)
53.6(12)
50.0(10)
46.4( 8)
Indoor discharge air temperature °F (°C)
42.8( 6)
Lo fanHi fan
77
(25)
HH fan
Indoor air tem
80°F (27°C)
75°F (24°C)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
p. 86°F (30°C
95
(35)
)
104
(40)
NOTE
• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on
the indoor unit type.
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
(In this case, be sure to stop all the indoor units where performance is not being checked.)
• The performance is for a tubing length of 24.6ft (7.5m). If the tubing length is different, the performance chart will vary.
140(60)
131(55)
122(50)
113(45)
104(40)
95(35)
86(30)
Indoor discharge air temperature °F (°C)
77(25)
Indoor air temp. 73
Indoor air temp. 73°F (23°C)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
F (21
°
70
70°F (21°C
F (17
63°
63°F (17°C)
F (23
°
C)
°
C)
°
C)
°
)
30
Page 33
5-1-2. Temperature Charts (CMH2472A)
Outdoor Unit CMH2472A Indoor Unit KMHS0772 ×1
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan)
(230V, 60Hz)
(1) Low pressure performance chart(1) High pressure performance chart
Heating Characteristics
(RH : 85%, Indoor fan speed : High fan)
(230V, 60Hz)
188
(1.3)
psig (MPaG)
174
(1.2)
160
(1.1)
Low pressure at wide tube service valve
146
(1.0)
Lo fanHi fanHH fan
Indoor air temp. 86°F (30°C)
77
(25)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
80°F (27°C)
75°F (24°C)
104
(40)
506
(3.5)
psig (MPaG)
434
(3.0)
362
(2.5)
High pressure at wide tube service valve
290
(2.0)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air temp. 73
Indoor air temp. 73°F (23°C)
70
70°F (21°C)
63
63°F (17°C)
F (23
°
F (21
°
F (17
°
C)
°
C)
°
C)
°
(2) Operating current performance chart(2) Operating current performance chart
Lo fanHi fanHH fan
5
4
3
Operating current (A)
2
77
(25)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
86
(30)
95
(35)
104
(40)
8
7
C)
°
F (23
6
Operating current (A)
5
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air temp. 73
Indoor air temp. 73°F (23°C)
°
°
F (21
°
70
70°F (21°
F (17
°
63
63°F (17°C)
C)
C)
C)
°
(3) Indoor discharge air performance chart(3) Indoor discharge air performance chart
140(60)
131(55)
122(50)
113(45)
104(40)
95(35)
86(30)
Indoor air tem
Indoor air tem
°C)
F (23
°
p. 73
p. 73°F (23°C
°
F (21
°
70
70°F (21°C)
C)
°
F (17
°
63
63°F (17°C)
C)
)
68.0(20)
64.4(18)
60.8(16)
57.2(14)
53.6(12)
50.0(10)
Lo fanHi fanHH fan
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
46.4( 8)
Indoor discharge air temperature °F (°C)
77
(25)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
NOTE
• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on
the indoor unit type.
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
(In this case, be sure to stop all the indoor units where performance is not being checked.)
• The performance is for a tubing length of 24.6t (7.5m). If the tubing length is different, the performance chart will vary.
104
(40)
31
77(25)
Indoor discharge air temperature °F (°C)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Page 34
Outdoor Unit CMH2472A Indoor Unit KMHS0972 ×1
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan)
(230V, 60Hz)
Heating Characteristics
(RH : 85%, Indoor fan speed : High fan)
(230V, 60Hz)
(1) Low pressure performance chart(1) High pressure performance chart
188
(1.3)
psig (MPaG)
174
(1.2)
160
(1.1)
Low pressure at wide tube service valve
146
(1.0)
Lo fanHi fan
77
(25)
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
HH fan
104
(40)
506
(3.5)
psig (MPaG)
434
(3.0)
362
(2.5)
High pressure at wide tube service valve
290
(2.0)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air tem
Indoor air tem
p. 73
p. 73°F (23°C
70
70°F (21°C)
63
63°F (17°C)
(2) Operating current performance chart(2) Operating current performance chart
Lo fanHi fan
6
5
4
Operating current (A)
3
77
(25)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
86
(30)
Indoor air tem
80°F (27°C)
75°F (24°C)
p. 86°F (30°C)
95
(35)
HH fan
104
(40)
8
7
70
Indoor air temp. 73
Indoor air temp. 73°F (23°C)
6
Operating current (A)
5
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
70°F (21°C)
63°
63°F (17°C)
F (23
°
F (21
°
F (17
°
F (23
°
F (21
°
F (17
)
C)
°
C)
°
C)
°
C)
°
C)
°
C)
°
(3) Indoor discharge air performance chart(3) Indoor discharge air performance chart
68.0(20)
64.4(18)
60.8(16)
57.2(14)
53.6(12)
50.0(10)
46.4( 8)
Indoor discharge air temperature °F (°C)
NOTE
• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on
the indoor unit type.
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
(In this case, be sure to stop all the indoor units where performance is not being checked.)
• The performance is for a tubing length of 24.6ft (7.5m). If the tubing length is different, the performance chart will vary.
Lo fanHi fan
77
(25)
Indoor air temp. 86°F (30°C)
80°F (27°C)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
HH fan
75°F (24°C)
104
(40)
32
140(60)
131(55)
122(50)
Indoor air temp. 73
113(45)
104(40)
95(35)
86(30)
77(25)
Indoor discharge air temperature °F (°C)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air temp. 73°F (23°C)
°
F (23
°
°
F (21
°
70
70°F (21°C)
°
F (17
°
63
63°F (17°C)
C)
C)
C)
Page 35
Outdoor Unit CMH2472A Indoor Unit KMHS1272 ×1
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan)
(230V, 60Hz)
Heating Characteristics
(RH : 85%, Indoor fan speed : High fan)
(230V, 60Hz)
(1) Low pressure performance chart(1) High pressure performance chart
578
174
(1.2)
psig (MPaG)
160
(1.1)
146
(1.0)
Low pressure at wide tube service valve
132
(0.9)
Lo fanHi fan
77
(25)
Indoor air temp. 86°F (30°C
80°F (27°C)
75°F (24°C)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
HH fan
)
104
(40)
(4.0)
506
psig (MPaG)
(3.5)
C)
°
F (23
°
3
C)
434
(3.0)
Indoor air temp. 7
Indoor air temp. 73°F (23°C
362
(2.5)
High pressure at wide tube service valve
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
°
F (21
°
°
70
70°F (21°C)
F (17
°
63
63°F (17°C)
C)
)
(2) Operating current performance chart(2) Operating current performance chart
10
Lo fanHi fan
6
5
4
Operating current (A)
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
HH fan
9
8
7
6
5
Operating current (A)
4
Indoor air temp. 7
Indoor air temp. 73°F (23°C
)
C)
°
F (23
°
C)
3
°
F (21
°
70
70°F (21°C)
C)
°
F (17
°
63
63°F (17°C)
3
77
(25)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
104
(40)
3
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
(3) Indoor discharge air performance chart(3) Indoor discharge air performance chart
68.0(20)
64.4(18)
60.8(16)
57.2(14)
53.6(12)
50.0(10)
46.4( 8)
Indoor discharge air temperature °F (°C)
Lo fanHi fan
77
(25)
Indoor air te
80°F (27°C)
75°F (24°
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
mp. 86°F (30°
C)
95
(35)
HH fan
C)
104
(40)
NOTE
• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on
the indoor unit type.
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
(In this case, be sure to stop all the indoor units where performance is not being checked.)
• The performance is for a tubing length of 24.6ft (7.5m). If the tubing length is different, the performance chart will vary.
140(60)
131(55)
122(50)
113(45)
Indoor air tem
104(40)
95(35)
86(30)
77(25)
Indoor discharge air temperature °F (°C)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air tem
C)
°
F (23
C)
°
°
p. 73
p. 73°F (23°C)
F (21
°
°
70
70°F (21°C
F (17
°
63
63°F (17°C)
)
C)
33
Page 36
Outdoor Unit CMH2472A Indoor Unit KMHS1872 ×1
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan)
(230V, 60Hz)
Heating Characteristics
(RH : 85%, Indoor fan speed : High fan)
(230V, 60Hz)
(1) Low pressure performance chart(1) High pressure performance chart
174
(1.2)
psig (MPaG)
160
(1.1)
146
(1.0)
Low pressure at wide tube service valve
132
(0.9)
Lo fanHi fan
77
(25)
Indoor air tem
80°F (27°C)
75°F (24°C)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
p. 86°F (30°C)
95
(35)
HH fan
104
(40)
578
(4.0)
psig (MPaG)
506
(3.5)
434
(3.0)
High pressure at wide tube service valve
362
(2.5)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air temp. 73
Indoor air temp. 73°F (23°C)
°
F (23
°
°
F (21
°
°
70
70°F (21°C
F (17
°
63
63°F (17°C
C)
)
C)
)
C)
(2) Operating current performance chart(2) Operating current performance chart
8
Lo fanHi fan
7
6
Operating current (A)
5
77
(25)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
86
(30)
95
(35)
HH fan
104
(40)
12
11
10
Indoor air temp. 73
9
8
Operating current (A)
7
6
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air temp. 73°F (23°C)
°C)
F (23
°
C)
°
F (21
°
70
70°F (21°C)
C)
°
F (17
°
63
63°F (17°C)
(3) Indoor discharge air performance chart(3) Indoor discharge air performance chart
68.0(20)
64.4(18)
60.8(16)
57.2(14)
53.6(12)
50.0(10)
Indoor discharge air temperature °F (°C)
46.4( 8)
NOTE
• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on
the indoor unit type.
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
(In this case, be sure to stop all the indoor units where performance is not being checked.)
• The performance is for a tubing length of 24.6ft (7.5m). If the tubing length is different, the performance chart will vary.
Lo fanHi fan
77
(25)
Indoor air tem
80°F (27°C)
75°F (24°C)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
p. 86°F (30°C
95
(35)
HH fan
)
104
(40)
34
140(60)
131(55)
122(50)
113(45)
Indoor air temp. 73
104(40)
95(35)
86(30)
Indoor discharge air temperature °F (°C)
77(25)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air temp. 73°F (23°C)
°
F (23
°
F (21
°
70
70°F (21°C)
F (17
°
63
63°F (17°C)
C)
C)
°
C)
°
Page 37
Outdoor Unit CMH2472A Indoor Unit KMHS2472 ×1
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan)
(230V, 60Hz)
Heating Characteristics
(RH : 85%, Indoor fan speed : High fan)
(230V, 60Hz)
(1) Low pressure performance chart(1) High pressure performance chart
174
(1.2)
psig (MPaG)
160
(1.1)
146
(1.0)
Low pressure at wide tube service valve
132
(0.9)
Lo fanHi fan
77
(25)
Indoor air temp. 86°F (30°C
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
80°F (27°C)
75°F (24°C)
HH fan
)
104
(40)
578
(4.0)
psig (MPaG)
506
(3.5)
p. 73
p. 73°F (23°C)
434
Indoor air tem
Indoor air tem
(3.0)
High pressure at wide tube service valve
362
(2.5)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
F (21
°
70
70°F (21°C)
F (17
°
63
63°F (17°C)
°
°
°
F (23
C)
C)
C)
°
(2) Operating current performance chart(2) Operating current performance chart
9
Lo fanHi fan
8
7
Operating current (A)
6
77
(25)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
86
(30)
(35)
95
HH fan
104
(40)
14
13
12
Indoor air temp. 73
Indoor air temp. 73°F (23°C)
11
10
Operating current (A)
9
8
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
°C)
F (21
°
70
70°F (21°C)
F (17
°
63
63°F (17°C)
°
C)
°
F (23
°
C)
(3) Indoor discharge air performance chart(3) Indoor discharge air performance chart
68.0(20)
64.4(18)
60.8(16)
57.2(14)
53.6(12)
50.0(10)
Indoor discharge air temperature °F (°C)
46.4( 8)
NOTE
• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on
the indoor unit type.
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
(In this case, be sure to stop all the indoor units where performance is not being checked.)
• The performance is for a tubing length of 24.6ft (7.5m). If the tubing length is different, the performance chart will vary.
Lo fanHi fan
77
(25)
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
HH fan
104
(40)
35
140(60)
131(55)
122(50)
p. 73
°C)
F (21
70°
70°F (21°C)
°
F (17
°
63
63°F (17°C)
p. 73°F (23°C)
C)
113(45)
Indoor air tem
104(40)
95(35)
86(30)
Indoor discharge air temperature °F (°C)
77(25)
Indoor air tem
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
F (23
°
C)
°
Page 38
Outdoor Unit CMH2472A Indoor Unit XMHS0972 ×1
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan)
(230V, 60Hz)
Heating Characteristics
(RH : 85%, Indoor fan speed : High fan)
(230V, 60Hz)
(1) Low pressure performance chart(1) High pressure performance chart
174
(1.2)
psig (MPaG)
160
(1.1)
146
(1.0)
Low pressure at wide tube service valve
132
(0.9)
Lo fanHi fan
77
(25)
Indoor air temp. 86
Indoor air temp. 86°F (30°C)
°
80
80°F (27°C)
°
75
75°F (24°C)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
F (27
F (24
C)
°
C)
°
95
(35)
F (30
°
HH fan
C)
°
104
(40)
506
(3.5)
psig (MPaG)
F (23
434
(3.0)
Indoor air temp. 73
362
(2.5)
High pressure at wide tube service valve
290
(2.0)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air temp. 73°F (23°C)
°
F (21
°
70
70°F (21°C)
F (17
°
63
63°F (17°C)
C)
°
C)
°
C)
°
(2) Operating current performance chart(2) Operating current performance chart
6
Lo fanHi fan
5
4
Operating current (A)
3
Indoor air tem
Indoor air tem
C)
°
F (27
°
80
80°F (27°C)
°
F (24
°
75
75°F (24°C)
p. 86
p. 86°F (30°C
C)
F (30
°
HH fan
)
C)
°
8
7
6
Operating current (A)
5
C)
°
F (23
°
3
C)
°
F (21
°
C)
°
70
70°F (21°C)
F (17
°
63
Indoor air temp. 7
Indoor air temp. 73°F (23°C)
63°F (17°C)
77
(25)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
104
(40)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
(3) Indoor discharge air performance chart(3) Indoor discharge air performance chart
68.0(20)
64.4(18)
60.8(16)
57.2(14)
53.6(12)
50.0(10)
46.4( 8)
Indoor discharge air temperature °F (°C)
Lo fanHi fan
77
(25)
Indoor air temp. 86
Indoor air temp. 86°F (30°C)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
F (30
°
°
F (27
°
80
80°F (27°C)
F (24
°
75
75°F (24°C)
HH fan
C)
°
C)
C)
°
104
(40)
NOTE
• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on
the indoor unit type.
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
(In this case, be sure to stop all the indoor units where performance is not being checked.)
• The performance is for a tubing length of 24.6ft (7.5m). If the tubing length is different, the performance chart will vary.
140(60)
131(55)
122(50)
113(45)
104(40)
95(35)
86(30)
77(25)
Indoor discharge air temperature °F (°C)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air temp. 73°
Indoor air temp. 73°F (23°C)
F (23
F (21
°
70
70°F (21°C)
°F (17
63
63°F (17°C)
C)
°
C)
°
C)
°
36
Page 39
Outdoor Unit CMH2472A Indoor Unit XMHS1272 ×1
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan)
(230V, 60Hz)
Heating Characteristics
(RH : 85%, Indoor fan speed : High fan)
(230V, 60Hz)
(1) Low pressure performance chart(1) High pressure performance chart
174
(1.2)
Lo fanHi fan
HH fan
578
(4.0)
160
psig (MPaG)
(1.1)
146
(1.0)
132
(0.9)
Low pressure at wide tube service valve
77
(25)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
86
(30)
95
(35)
104
(40)
506
psig (MPaG)
(3.5)
C)
°
F (23
434
(3.0)
Indoor air temp. 73
362
(2.5)
High pressure at wide tube service valve
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air temp. 73°F (23°C)
°
C)
°
F (21
°
70
70°F (21°C)
°C)
F (17
°
63
63°F (17°C)
(2) Operating current performance chart(2) Operating current performance chart
10
Lo fanHi fan
6
5
4
Operating current (A)
3
77
(25)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
86
(30)
95
(35)
HH fan
104
(40)
9
8
7
6
5
Operating current (A)
4
3
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air tem
Indoor air tem
C)
°
F (23
°
C)
°
p. 73
p. 73°F (23°C)
F (21
°
70
70°F (21°C
C)
°
F (17
°
63
63°F (17°C)
)
(3) Indoor discharge air performance chart(3) Indoor discharge air performance chart
68.0(20)
64.4(18)
60.8(16)
57.2(14)
53.6(12)
50.0(10)
46.4( 8)
Indoor discharge air temperature °F (°C)
42.8( 6)
NOTE
• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on
the indoor unit type.
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
(In this case, be sure to stop all the indoor units where performance is not being checked.)
• The performance is for a tubing length of 24.6ft (7.5m). If the tubing length is different, the performance chart will vary.
Lo fanHi fan
77
(25)
80°F (27°C)
75°F (24°C)
mp. 86°F (30°
95
(35)
Indoor air te
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
HH fan
C)
104
(40)
37
140(60)
131(55)
C)
122(50)
113(45)
104(40)
95(35)
86(30)
77(25)
Indoor discharge air temperature °F (°C)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air temp. 73
Indoor air temp. 73°F (23°C)
°
°F (23
C)
°
F (21
°
C)
°
70
70°F (21°C)
F (17
°
63
63°F (17°C)
Page 40
Outdoor Unit CMH2472A Indoor Unit XHS1872 ×1
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan)
(230V, 60Hz)
Heating Characteristics
(RH : 85%, Indoor fan speed : High fan)
(230V, 60Hz)
(1) Low pressure performance chart(1) High pressure performance chart
174
(1.2)
160
psig (MPaG)
(1.1)
146
(1.0)
132
(0.9)
Low pressure at wide tube service valve
Lo fanHi fan
77
(25)
Indoor air tem
80°F (27°C)
75°F (24°C)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
p. 86°F (30°C)
95
(35)
HH fan
104
(40)
578
(4.0)
psig (MPaG)
506
(3.5)
°C)
F (23
434
(3.0)
Indoor air temp. 73
High pressure at wide tube service valve
Indoor air temp. 73°F (23°C)
362
(2.5)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
°
C)
°
F (21
°
70
70°F (21°C)
F (17
°
63
63°F (17°C)
C)
°
(2) Operating current performance chart(2) Operating current performance chart
Lo fanHi fan
7
6
5
Operating current (A)
4
77
(25)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
86
(30)
95
(35)
HH fan
104
(40)
12
11
C)
F (21
F (17
F (23
°
C)
°
C)
°
°
10
9
°
Indoor air temp. 73
Indoor air temp. 73°F (23°C)
70
8
Operating current (A)
7
6
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
70°F (21°C)
°
63
63°F (17°C)
(3) Indoor discharge air performance chart(3) Indoor discharge air performance chart
68.0(20)
64.4(18)
60.8(16)
57.2(14)
53.6(12)
50.0(10)
46.4( 8)
Indoor discharge air temperature °F (°C)
42.8( 6)
Lo fanHi fan
77
(25)
HH fan
Indoor air tem
80°F (27°C)
75°F (24°C)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
p. 86°F (30°C
95
(35)
)
104
(40)
NOTE
• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on
the indoor unit type.
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
(In this case, be sure to stop all the indoor units where performance is not being checked.)
• The performance is for a tubing length of 24.6ft (7.5m). If the tubing length is different, the performance chart will vary.
140(60)
131(55)
122(50)
113(45)
104(40)
95(35)
86(30)
Indoor discharge air temperature °F (°C)
77(25)
Indoor air temp. 73
Indoor air temp. 73°F (23°C)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
F (21
°
70
70°F (21°C
F (17
63°
63°F (17°C)
F (23
°
C)
°
C)
°
C)
°
)
38
Page 41
5-1-3. Temperature Charts (CMH3172A)
Outdoor Unit CMH3172A Indoor Unit KMHS0772 ×1
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan)
(230V, 60Hz)
(1) Low pressure performance chart(1) High pressure performance chart
174
(1.2)
psig (MPaG)
146
(1.0)
118
(0.8)
Low pressure at wide tube service valve
(0.6)
Lo fanHi fanHi fanHH fan
Indoor air temp. 86°F (30°C)
90
77
(25)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
80°F (27°C
75°F (24°C)
95
(35)
)
104
(40)
(2) Operating current performance chart(2) Operating current performance chart
5
Lo fanHi fanHi fanHH fan
80°F (27°C)
4
Indoor air temp. 86°F (30°C)
Operating current (A)
75°F (24°C)
Heating Characteristics
(RH : 85%, Indoor fan speed : High fan)
(230V, 60Hz)
506
(3.5)
434
psig (MPaG)
(3.0)
Indoor air temp. 73
362
(2.5)
290
(2.0)
High pressure at wide tube service valve
218
(1.5)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
9
8
7
6
Operating current (A)
5
Indoor air temp. 73°F (23°C)
Indoor air temp. 73
Indoor air temp. 73°F (23°C)
F (17
°
63
63°F (17°C)
°C)
°F (23
F (21
°
70
70°F (21°C)
F (17
°
63
63°F (17°C)
F (23
°
C)
°
F (21
°
70
70°F (21°C)
C)
°
°
°C)
C)
C)
°
3
77
(25)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
104
(40)
4
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
(3) Indoor discharge air performance chart(3) Indoor discharge air performance chart
Lo fanHi fanHi fanHH fan
68.0(20)
64.4(18)
60.8(16)
57.2(14)
53.6(12)
50.0(10)
Indoor discharge air temperature °F (°C)
46.4( 8)
77
(25)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
Indoor air temp. 86°F (30°C)
86
(30)
80°F (27°C)
75°F (24°C)
95
(35)
104
(40)
140(60)
131(55)
122(50)
113(45)
104(40)
95(35)
86(30)
Indoor discharge air temperature °F (°C)
77(25)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air temp. 73
Indoor air temp. 73°F (23°C)
NOTE
• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on
the indoor unit type.
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
(In this case, be sure to stop all the indoor units where performance is not being checked.)
• The performance is for a tubing length of 24.6ft (7.5m). If the tubing length is different, the performance chart will vary.
°
F (23
°
°
F (21
°
70
70°F (21°C)
C)
°
F (17
63°
63°F (17°C)
C)
C)
39
Page 42
Outdoor Unit CMH3172A Indoor Unit KMHS0972 ×1
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan)
(230V, 60Hz)
Heating Characteristics
(RH : 85%, Indoor fan speed : High fan)
(230V, 60Hz)
(1) Low pressure performance chart(1) High pressure performance chart
506
174
(1.2)
psig (MPaG)
146
(1.0)
118
(0.8)
Low pressure at wide tube service valve
90
(0.6)
Lo fanHi fanHi fanHH fan
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C
77
(25)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
)
95
(35)
104
(40)
(3.5)
434
psig (MPaG)
(3.0)
Indoor air temp. 73
362
(2.5)
290
(2.0)
High pressure at wide tube service valve
218
(1.5)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air temp. 73°F (23°C)
C)
°
F (23
°
°
F (21
°
°
70
70°F (21°C)
F (17
°
63
63°F (17°C)
C)
C)
(2) Operating current performance chart(2) Operating current performance chart
5
Lo fanHi fanHi fanHH fan
4
Operating current (A)
)
80°F (27°C)
75°F (24°C)
Indoor air temp. 86°F (30°C
8
7
6
Operating current (A)
5
C)
°
F (23
°
C)
°
C)
°
F (21
°
70
70°F (21°C)
F (17
°
63
Indoor air temp. 73
Indoor air temp. 73°F (23°C)
63°F (17°C)
3
77
(25)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
104
(40)
4
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
(3) Indoor discharge air performance chart(3) Indoor discharge air performance chart
Lo fanHi fanHi fanHH fan
68.0(20)
64.4(18)
60.8(16)
57.2(14)
53.6(12)
50.0(10)
46.4( 8)
Indoor discharge air temperature °F (°C)
77
(25)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
86
(30)
95
(35)
104
(40)
NOTE
• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on
the indoor unit type.
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
(In this case, be sure to stop all the indoor units where performance is not being checked.)
• The performance is for a tubing length of 24.6ft (7.5m). If the tubing length is different, the performance chart will vary.
140(60)
131(55)
122(50)
Indoor air temp. 73
113(45)
104(40)
95(35)
86(30)
77(25)
Indoor discharge air temperature °F (°C)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air temp. 73°F (23°C)
F (23
°
C)
°
°F (21
°
70
70°F (21°C
F (17
°
63
63°F (17°C)
C)
°
)
C)
40
Page 43
Outdoor Unit CMH3172A Indoor Unit KMHS1272 ×1
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan)
(230V, 60Hz)
Heating Characteristics
(RH : 85%, Indoor fan speed : High fan)
(230V, 60Hz)
(1) Low pressure performance chart(1) High pressure performance chart
C)
F (21
F (17
°
°
C)
°
F (23
C)
°
°
)
174
(1.2)
psig (MPaG)
146
(1.0)
118
(0.8)
Low pressure at wide tube service valve
90
(0.6)
Lo fanHi fanHi fanHH fan
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
77
(25)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
104
(40)
506
(3.5)
434
psig (MPaG)
(3.0)
362
(2.5)
290
(2.0)
High pressure at wide tube service valve
218
(1.5)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
°
70
70°F (21°C)
Indoor air temp. 73
Indoor air temp. 73°F (23°C)
63
63°F (17°C
(2) Operating current performance chart(2) Operating current performance chart
6
Lo fanHi fanHi fanHH fan
5
4
Operating current (A)
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
13
12
11
70
70°F (21°C)
Indoor air temp. 73
Indoor air temp. 73°F (23°C)
10
9
Operating current (A)
8
F (23
°
C)
°
C)
F (21
°
°
°F (17
63
63°F (17°C)
C)
°
3
77
(25)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
(3) Indoor discharge air performance chart
Lo fanHi fanHi fanHH fan
68.0(20)
64.4(18)
60.8(16)
57.2(14)
53.6(12)
50.0(10)
46.4( 8)
Indoor discharge air temperature °F (°C)
77
(25)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
Indoor air temp. 86°F (30°C)
86
(30)
95
(35)
80°F (27°C)
75°F (24°C)
104
(40)
104
(40)
(3) Indoor discharge air performance chart
7
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
C)
°
F (23
F (21
°
F (17
°
°
C)
°
C)
°
140(60)
131(55)
122(50)
113(45)
104(40)
Indoor discharge air temperature °F (°C)
Indoor air temp. 73
Indoor air temp. 73°F (23°C)
70
70°F (21°C)
63
63°F (17°C)
95(35)
86(30)
77(25)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
NOTE
• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on
the indoor unit type.
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
(In this case, be sure to stop all the indoor units where performance is not being checked.)
• The performance is for a tubing length of 24.6ft (7.5m). If the tubing length is different, the performance chart will vary.
41
Page 44
Outdoor Unit CMH3172A Indoor Unit KMHS1872 ×1
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan)
(230V, 60Hz)
Heating Characteristics
(RH : 85%, Indoor fan speed : High fan)
(230V, 60Hz)
(1) Low pressure performance chart(1) High pressure performance chart
C)
°
F (23
°
3
C)
°
C)
°
174
(1.2)
psig (MPaG)
146
(1.0)
Indoor air temp. 86°F (30°C
118
(0.8)
Low pressure at wide tube service valve
90
(0.6)
77
(25)
80°F (27°C)
75°F (24°C)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
Lo fanHi fan
)
95
(35)
104
(40)
506
(3.5)
Indoor air temp. 7
Indoor air temp. 73°F (23°C)
434
psig (MPaG)
(3.0)
362
(2.5)
290
(2.0)
High pressure at wide tube service valve
218
(1.5)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
F (21
°
70
70°F (21°C)
F (17
°
63
63°F (17°C)
(2) Operating current performance chart(2) Operating current performance chart
9
8
7
6
Operating current (A)
5
Lo fanHi fan
80°F (27°C)
Indoor air temp. 86°F (30°C)
75°F (24°C)
14
13
Indoor air temp. 73
Indoor air temp. 73°F (23°C)
12
Operating current (A)
C)
°
F (23
°
C)
°
F (21
°
C)
°
70
70°F (21°C)
F (17
°
63
63°F (17°C)
4
77
(25)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
104
(40)
11
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
(3) Indoor discharge air performance chart(3) Indoor discharge air performance chart
C)
140(60)
131(55)
122(50)
113(45)
104(40)
95(35)
86(30)
77(25)
Indoor discharge air temperature °F (°C)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
C)
Indoor air temp. 7
Indoor air temp. 73°F (23°C)
°
F (21
°
70
70°F (21°C)
C)
°
F (17
°
63
63°F (17°C)
68.0(20)
64.4(18)
60.8(16)
57.2(14)
53.6(12)
50.0(10)
46.4( 8)
Indoor discharge air temperature °F (°C)
77
(25)
Indoor air temp. 86°F (30°C)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
Lo fanHi fan
80°F (27°C)
75°F (24°C)
95
(35)
104
(40)
NOTE
• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on
the indoor unit type.
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
(In this case, be sure to stop all the indoor units where performance is not being checked.)
• The performance is for a tubing length of 24.6ft (7.5m). If the tubing length is different, the performance chart will vary.
3
F (23
°
°
42
Page 45
Outdoor Unit CMH3172A Indoor Unit KMHS2472 ×1
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan)
(230V, 60Hz)
Heating Characteristics
(RH : 85%, Indoor fan speed : High fan)
(230V, 60Hz)
(1) Low pressure performance chart(1) High pressure performance chart
174
(1.2)
psig (MPaG)
146
(1.0)
Lo fanHi fan
506
(3.5)
434
psig (MPaG)
(3.0)
362
(2.5)
Indoor air tem
Indoor air tem
F (21
°
70
70°F (21°C)
°
63
63°F (17°C)
p. 73
p. 73°F (23°C)
F (17
C)
°
F (23
°
C)
°
C)
°
118
(0.8)
Low pressure at wide tube service valve
90
(0.6)
77
(25)
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
104
(40)
290
(2.0)
High pressure at wide tube service valve
218
(1.5)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
(2) Operating current performance chart(2) Operating current performance chart
12
11
10
Operating current (A)
9
8
77
(25)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
Lo fanHi fan
Indoor air temp. 86°F (30°C)
80°F (27°C)
86
(30)
75°F (24°C
)
95
(35)
104
(40)
14
13
Indoor air temp. 73
Indoor air temp. 73°F (23°C)
12
Operating current (A)
11
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
C)
°
F (23
°
C)
°
C)
°F (21
°
70
70°F (21°C)
F (17
°
63
63°F (17°C)
(3) Indoor discharge air performance chart(3) Indoor discharge air performance chart
Lo fanHi fan
68.0(20)
64.4(18)
60.8(16)
57.2(14)
53.6(12)
50.0(10)
46.4( 8)
Indoor discharge air temperature °F (°C)
77
(25)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
86
(30)
Indoor air tem
p. 86°F (30°C
80°F (27°C)
75°F (24°C)
95
(35)
)
104
(40)
NOTE
• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on
the indoor unit type.
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
(In this case, be sure to stop all the indoor units where performance is not being checked.)
• The performance is for a tubing length of 24.6ft (7.5m). If the tubing length is different, the performance chart will vary.
140(60)
131(55)
122(50)
113(45)
104(40)
Indoor discharge air temperature °F (°C)
Indoor air temp. 7
Indoor air temp. 73°F (23°C)
F (21
°
70
70°F (21°C)
F (17
°
63
63°F (17°C)
95(35)
86(30)
77(25)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
C)
°
F (23
°
3
C)
°
C)
°
43
Page 46
Outdoor Unit CMH3172A Indoor Unit XMHS0972 ×1
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan)
(230V, 60Hz)
Heating Characteristics
(RH : 85%, Indoor fan speed : High fan)
(230V, 60Hz)
(1) Low pressure performance chart(1) High pressure performance chart
174
(1.2)
psig (MPaG)
146
(1.0)
118
(0.8)
Low pressure at wide tube service valve
90
(0.6)
Lo fanHi fanHi fanHH fan
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
77
(25)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
104
(40)
(3.5)
434
psig (MPaG)
(3.0)
Indoor air temp. 73
362
(2.5)
290
(2.0)
High pressure at wide tube service valve
218
(1.5)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air temp. 73°F (23°C)
C)
°
F (23
°
C)
°
F (21
°
C)
°
70
70°F (21°C)
F (17
°
63
63°F (17°C)
506
(2) Operating current performance chart(2) Operating current performance chart
Lo fanHi fanHi fanHH fan
5
80°F (27°C)
75°F (24°C)
8
C)
°
F (23
°
7
Indoor air temp. 73
6
Indoor air temp. 73°F (23°C)
C)
°
F (21
°
°
70
70°F (21°C)
F (17
63°
63°F (17°C)
C)
Operating current (A)
4
77
(25)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
Indoor air temp. 86°F (30°C)
86
(30)
95
(35)
104
(40)
Operating current (A)
5
4
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
(3) Indoor discharge air performance chart(3) Indoor discharge air performance chart
68.0(20)
64.4(18)
60.8(16)
57.2(14)
53.6(12)
50.0(10)
46.4( 8)
42.8( 6)
Indoor discharge air temperature °F (°C)
Lo fanHi fanHi fanHH fan
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
77
(25)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
104
(40)
NOTE
• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on
the indoor unit type.
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
(In this case, be sure to stop all the indoor units where performance is not being checked.)
• The performance is for a tubing length of 24.6ft (7.5m). If the tubing length is different, the performance chart will vary.
140(60)
131(55)
122(50)
Indoor air temp. 73
113(45)
104(40)
95(35)
86(30)
77(25)
Indoor discharge air temperature °F (°C)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
Indoor air temp. 73°F (23°C)
F (23
°
C)
°
F (21
°
70
70°F (21°C)
°
F (17
63°
63°F (17°C)
C)
°
C)
44
Page 47
Outdoor Unit CMH3172A Indoor Unit XMHS1272 ×1
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan)
(230V, 60Hz)
Heating Characteristics
(RH : 85%, Indoor fan speed : High fan)
(230V, 60Hz)
(1) Low pressure performance chart(1) High pressure performance chart
174
(1.2)
psig (MPaG)
146
(1.0)
118
(0.8)
Low pressure at wide tube service valve
90
(0.6)
Lo fanHi fanHi fanHH fan
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
77
(25)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
104
(40)
506
(3.5)
434
psig (MPaG)
(3.0)
Indoor air temp. 73
Indoor air temp. 73°F (23°C)
362
(2.5)
290
(2.0)
High pressure at wide tube service valve
218
(1.5)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
°
F (21
°
70
70°F (21°C)
°
F (17
°
63
63°F (17°C
C)
°
F (23
°
C)
)
C)
(2) Operating current performance chart(2) Operating current performance chart
Lo fanHi fanHi fanHH fan
6
5
Operating current (A)
4
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
13
12
11
10
Indoor air temp. 73
Indoor air temp. 73°F (23°C)
9
Operating current (A)
8
°
F (21
°
70
70°F (21°C)
°
F (17
°
63
63°F (17°C)
C)
C)
F (23
°
C)
°
77
(25)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
(3) Indoor discharge air performance chart
68.0(20)
64.4(18)
60.8(16)
57.2(14)
53.6(12)
50.0(10)
46.4( 8)
Indoor discharge air temperature °F (°C)
42.8( 6)
Lo fanHi fanHi fanHH fan
Indoor air temp. 86°F (30°C)
77
(25)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
95
(35)
80°F (27°C)
75°F (24°C)
104
(40)
104
(40)
(3) Indoor discharge air performance chart
7
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
140(60)
131(55)
122(50)
Indoor air temp. 73
Indoor air temp. 73°F (23°C)
113(45)
104(40)
95(35)
86(30)
77(25)
Indoor discharge air temperature °F (°C)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
°
F (21
°
70
70°F (21°C)
°
F (17
°
63
63°F (17°C
°C)
°F (23
C)
)
C)
NOTE
• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on
the indoor unit type.
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
(In this case, be sure to stop all the indoor units where performance is not being checked.)
• The performance is for a tubing length of 24.6ft (7.5m). If the tubing length is different, the performance chart will vary.
45
Page 48
Outdoor Unit CMH3172A Indoor Unit XHS1872 ×1
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan)
(230V, 60Hz)
Heating Characteristics
(RH : 85%, Indoor fan speed : High fan)
(230V, 60Hz)
(1) Low pressure performance chart(1) High pressure performance chart
174
(1.2)
psig (MPaG)
146
(1.0)
Indoor air temp. 86°F (30°C)
118
(0.8)
Low pressure at wide tube service valve
90
(0.6)
77
(25)
80°F (27°C)
75°F (24°C)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
Lo fanHi fan
95
(35)
104
(40)
506
(3.5)
434
Indoor air temp. 7
Indoor air temp. 73°F (23°C)
psig (MPaG)
(3.0)
362
(2.5)
290
(2.0)
High pressure at wide tube service valve
218
(1.5)
F (21
°
70
70°F (21°C)
F (17
°
63
63°F (17°C)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
C)
°
F (23
°
3
C)
°
C)
°
(2) Operating current performance chart(2) Operating current performance chart
9
8
7
6
Operating current (A)
5
77
(25)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
80°F (27°C)
Indoor air temp. 86°F (30°C)
75°F (24°C)
86
(30)
Lo fanHi fan
95
(35)
104
(40)
14
13
Indoor air temp. 7
Indoor air temp. 73°F (23°C)
12
Operating current (A)
11
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
°
F (23
°
3
°C)
°F (21
70
70°F (21°C)
C)
°
F (17
°
63
63°F (17°C)
C)
(3) Indoor discharge air performance chart(3) Indoor discharge air performance chart
140(60)
131(55)
C)
122(50)
Indoor air temp. 73
Indoor air temp. 73°F (23°C
113(45)
104(40)
95(35)
86(30)
77(25)
Indoor discharge air temperature °F (°C)
23
(-5)32(0)41(5)50(10)59(15)68(20)77(25)
°
F (21
°
70
70°F (21°C)
C)
°
F (17
°
63
63°F (17°C)
64.4(18)
60.8(16)
57.2(14)
53.6(12)
50.0(10)
46.4( 8)
42.8( 6)
39.2( 4)
Indoor discharge air temperature °F (°C)
77
(25)
Indoor air temp. 86°F (30°C)
86
(30)
Outdoor air temperature °F (°C)Outdoor air temperature °F (°C)
Lo fanHi fan
80°F (27°C)
75°F (24°C)
95
(35)
104
(40)
NOTE
• This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on
the indoor unit type.
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
(In this case, be sure to stop all the indoor units where performance is not being checked.)
• The performance is for a tubing length of 24.6ft (7.5m). If the tubing length is different, the performance chart will vary.
F (23
°
)
C)
°
46
Page 49
5-2. Cooling Capacity
Outdoor Unit : CMH1972A
Indoor Unit: KMHS0972 × 3
Power Supply : 230V Single Phase 60Hz
< Cooling Capacity >
RATING CAPACITY: 19,100 BTU/h AIR FLOW RATE:883 CFM
Above data does not take Freeze Prevention Protection during cooling operation into account.
For this reason, the value may vary from the actual cooling characteristics.
3. Above data represents the value when the operation frequency of a compressor is fixed.
47
Page 50
Outdoor Unit : CMH1972A
Indoor Unit: XMHS1272 × 3
Power Supply : 230V Single Phase 60Hz
< Cooling Capacity >
RATING CAPACITY: 17,400 BTU/h AIR FLOW RATE:706 CFM
Above data does not take Freeze Prevention Protection during cooling operation into account.
For this reason, the value may vary from the actual cooling characteristics.
3. Above data represents the value when the operation frequency of a compressor is fixed.
48
Page 51
Outdoor Unit : CMH2472A
Indoor Unit: KMHS0972 × 3
Power Supply : 230V Single Phase 60Hz
< Cooling Capacity >
RATING CAPACITY: 23,200 BTU/h AIR FLOW RATE:883 CFM
Above data does not take Freeze Prevention Protection during cooling operation into account.
For this reason, the value may vary from the actual cooling characteristics.
3. Above data represents the value when the operation frequency of a compressor is fixed.
49
Page 52
Outdoor Unit : CMH2472A
Indoor Unit: XHS1872 + XMHS1272 + XMHS1272
Power Supply : 230V Single Phase 60Hz
3. Above data represents the value when the operation frequency of a compressor is fixed.
Above data does not take Freeze Prevention Protection during cooling operation into account.
For this reason, the value may vary from the actual cooling characteristics.
NOTE
RATING CAPACITY: 22,000 BTU/h AIR FLOW RATE:812 CFM
3. Above data represents the value when the operation frequency of a compressor is fixed.
Above data does not take Freeze Prevention Protection during cooling operation into account.
For this reason, the value may vary from the actual cooling characteristics.
NOTE
RATING CAPACITY: 30,600 BTU/h AIR FLOW RATE:1,177 CFM
3. Above data represents the value when the operation frequency of a compressor is fixed.
Above data does not take Freeze Prevention Protection during cooling operation into account.
For this reason, the value may vary from the actual cooling characteristics.
NOTE
RATING CAPACITY: 28,600 BTU/h AIR FLOW RATE:883 CFM
3. Above data represents the value when the operation frequency of a compressor is fixed.
Above data does not take Defrost Operation, Overload Prevention Protection, and/or Cold Air
Prevention Protection during heating operation into account. For this reason, the value may vary
from the actual heating characteristics.
3. Above data represents the value when the operation frequency of a compressor is fixed.
Above data does not take Defrost Operation, Overload Prevention Protection, and/or Cold Air
Prevention Protection during heating operation into account. For this reason, the value may vary
from the actual heating characteristics.
NOTE
MFC308:ETAR WOLF RIAh/UTB000,42 :YTICAPAC GNITAR
ROODNIROODTUO
ENT. TEMP.
o
F (
o
.PMET TNEIBMA)C
o
F (oC)
0857075606.B.W
(15.6)(18.3)(21.1)(23.9)(26.7)
0 (-17.8)TH13,31013,30013,27013,24013,200
CI
1.101.151.211.271.32
3 (-16.1)TH13,76013,74013,72013,69013,650
CI
1.111.171.231.281.34
8 (-13.3)TH14,83014,82014,79014,76014,720
CI
1.141.201.261.331.39
13 (-10.6)TH15,95015,93015,91015,87015,830
CI
1.171.241.311.381.44
18 (-7.8)TH17,18017,16017,13017,09017,040
CI
1.201.281.351.431.50
23 (-5.0)TH18,47018,45018,42018,38018,320
CI
1.241.321.401.481.56
28 (-2.2)TH19,82019,80019,77019,72019,660
CI
1.271.361.451.541.62
33 (0.6)TH21,22021,19021,16021,10021,040
CI
1.311.401.501.591.68
38 (3.3)TH22,61022,58022,54022,48022,410
CI
1.341.441.541.651.74
43 (6.1)TH24,08024,050# 24,00023,94023,860
CI
1.381.491.601.701.81
48 (8.9)TH25,58025,54025,49025,42025,340
CI
1.421.531.651.761.87
53 (11.7)TH27,09027,05027,00026,92026,830
CI
1.581.701.701.821.94
58 (14.4)TH28,56028,52028,46028,38028,280
CI
1.501.621.751.882.01
63 (17.2)TH30,09030,04029,97029,88029,780
CI
1.551.681.811.952.08
65 (18.3)TH30,68030,63030,56030,47030,360
CI
1.561.701.841.982.11
54
Page 57
Outdoor Unit : CMH2472A
Indoor Unit: KMHS0972 × 3
Power Supply : 230V Single Phase 60Hz
3. Above data represents the value when the operation frequency of a compressor is fixed.
Above data does not take Defrost Operation, Overload Prevention Protection, and/or Cold Air
Prevention Protection during heating operation into account. For this reason, the value may vary
from the actual heating characteristics.
3. Above data represents the value when the operation frequency of a compressor is fixed.
Above data does not take Defrost Operation, Overload Prevention Protection, and/or Cold Air
Prevention Protection during heating operation into account. For this reason, the value may vary
from the actual heating characteristics.
NOTE
MFC819:ETAR WOLF RIAh/UTB004,82 :YTICAPAC GNITAR
ROODNIROODTUO
ENT. TEMP.
o
F (
o
.PMET TNEIBMA)C
o
F (oC)
0857075606.B.W
(15.6)(18.3)(21.1)(23.9)(26.7)
0(-17.8)TH16,03016,04016,05016,04016,020
CI
1.451.521.601.671.74
3(-16.1)TH16,55016,56016,57016,56016,540
CI
1.471.541.621.691.77
8(-13.3)TH17,79017,81017,82017,81017,790
CI
1.501.591.671.751.84
13 (-10.6)TH19,08019,10019,11019,10019,090
CI
1.551.641.731.821.90
18 (-7.8)TH20,50020,52020,53020,53020,510
CI
1.591.691.791.891.98
23 (-5.0)TH21,99022,01022,02022,01022,000
CI
1.641.751.851.962.06
28 (-2.2)TH23,53023,56023,57023,56023,540
CI
1.691.801.922.032.14
33 (0.6)TH25,13025,15025,16025,15025,130
CI
1.741.861.992.112.23
38 (3.3)TH26,70026,73026,74026,73026,090
CI
1.791.922.052.182.26
43 (6.1)TH28,36028,390#28,40028,39026,750
CI
1.851.982.122.262.26
48 (8.9)TH30,05030,07030,08030,07027,350
CI
1.902.052.202.342.26
53 (11.7)TH31,74031,77031,78031,19027,890
CI
2.112.272.272.382.26
58 (14.4)TH33,37033,40033,41031,73028,330
CI
2.022.182.352.382.26
63 (17.2)TH35,05035,08035,09032,17028,700
CI
2.092.262.432.382.26
65 (18.3)TH35,70035,73035,74032,31028,810
CI
2.122.292.472.382.26
56
Page 59
Outdoor Unit : CMH3172A
Indoor Unit: KMHS0972 × 4
Power Supply : 230V Single Phase 60Hz
3. Above data represents the value when the operation frequency of a compressor is fixed.
Above data does not take Defrost Operation, Overload Prevention Protection, and/or Cold Air
Prevention Protection during heating operation into account. For this reason, the value may vary
from the actual heating characteristics.
3. Above data represents the value when the operation frequency of a compressor is fixed.
Above data does not take Defrost Operation, Overload Prevention Protection, and/or Cold Air
Prevention Protection during heating operation into account. For this reason, the value may vary
from the actual heating characteristics.
NOTE
MFC000,1:ETAR WOLF RIAh/UTB000,23 :YTICAPAC GNITAR
ROODNIROODTUO
ENT. TEMP.
o
F (
o
.PMET TNEIBMA)C
o
F (oC)
0857075606.B.W
(15.6)(18.3)(21.1)(23.9)(26.7)
0 (-17.8)TH18,20018,18018,14018,10018,040
CI
1.481.551.631.701.77
3 (-16.1)TH18,80018,78018,74018,69018,640
CI
1.501.571.651.731.80
8 (-13.3)TH20,22020,20020,16020,12020,060
CI
1.541.621.701.791.87
13 (-10.6)TH21,69021,67021,63021,58021,520
CI
1.581.671.761.851.94
18 (-7.8)TH23,30023,28023,24023,19023,120
CI
1.631.731.821.922.02
23 (-5.0)TH24,98024,96024,92024,86024,790
CI
1.681.791.892.002.10
28 (-2.2)TH26,72026,69026,65026,60026,520
CI
1.741.851.962.072.19
33 (0.6)TH28,50028,47028,43028,37028,290
CI
1.801.922.042.162.27
38 (3.3)TH30,24030,22030,17030,11030,030
CI
1.861.982.112.242.36
43 (6.1)TH32,07032,050#32,00031,94031,850
CI
1.922.052.192.332.46
48 (8.9)TH33,90033,88033,83033,76033,680
CI
1.992.132.272.422.56
53 (11.7)TH35,72035,70035,65035,58035,490
CI
2.212.362.362.512.66
58 (14.4)TH37,45037,43037,38037,31037,220
CI
2.142.302.452.612.77
63 (17.2)TH39,19039,17039,12039,05038,960
CI
2.232.392.562.722.89
65 (18.3)TH39,86039,84039,79039,72039,630
CI
2.272.432.602.772.94
58
Page 61
6. ELECTRICAL DATA
6-1. Electric Wiring Diagrams
Outdoor Unit CMH1972A
BLK
REACTANCE
WHT
1 1
(1P)CONNECTOR
RV
4WAY
VALVE COIL
DEF
DEFROST
VALVE COIL
RELAY
6
WHT
1 1
(1P)
CONNECTOR
1
GRN/YEL
WHT
1
WHT
2
WHT
WHT
RED
1
RED
2
RED
1
RED
2
4
BLK
BLK
5
BLK
GRN/YEL
WHT
1
WHT
2
WHT
(2P)CONNECTOR
WHT
WHT
CRANKCASE
HEATER
WHT
BLK
1
BLK
2
(2P)CONNECTOR
BLK
BLK
1
BLK
2
(2P)CONNECTOR
BN THERMISTOR
YEL
4
YEL
3
YEL
2
YEL
1
BW THERMISTOR
AN THERMISTOR
YEL
4
YEL
3
YEL
2
YEL
1
AW THERMISTOR
THERMISTOR
OUTDOOR
BLK
4
BLK
3
YEL
2
YEL
1
THERMISTOR
COIL
BLK
BLK
SUPPLY
POWER
L2
L1
GND
1
2
TERMINAL PLATE
CORE
FERRITE
WHT
W
W
ACIN1
ACIN2
W
E
25A
WW
E1
W
L2 L1
W
HEATER0
W WW
RV1 RV0HEATER1
W W
DEF1 DEF0
4
3
B-TH
2
1
4
3
A-TH
2
1
4
3
2
1
COMP
COIL/OUTDOOR
1
1
2 2
THERMISTOR
COMPRESSOR
WHT
W
W
SI-A
SI-B
MV0
MV1
W
SICOM2
KS10
CONTROLLER
KS22
KS23FM
U
WVWWW
UNIT
UNIT
A INDOOR
123456789
BLK
BLK
GRY
BLK
YEL
RED
ORG
GRY
BLK
YEL
RED
ORG
WHT
BLU
5
5
4
4
3
3
MV0
2
2
1
1
5
5
4
4
3
3
MV1
2
2
1
1
SI-C
W
SICOM2
4
4
3
3
CN01
2
2
MV2C-TH
1
1
6
6
5
5
4
4
CN02
3
3
2
2
1
1
TERMINAL PLATE
RED
5
5
4
4
3
3
2
2
1
1
5
5
4
4
3
3
2
2
1
1
WHT
BLU
4
RED
3
WHT
2
BLK
1
WHT
6
BLK
5
BLU
4
RED
3
WHT
2
BLK
1
EXPANSION BOARD
BLU
8
RED
WHT
BLK
BLU
RED
WHT
BLK
ORG
WHT
BRN
BLU
RED
WHT
7
6
5
4
3
2
1
7
6
5
4
3
2
1
1 2 3 4 5 6 7
CORE
FERRITE
8
7
6
5
CN03
4
3
2
1
(7P)CONNECTOR
ORG
WHT
BRN
BLU
RED
WHT
3
3
2
2
1
1
8
7
6
5
4
3
2
1
7
6
5
4
3
2
1
BLU
WHT
RED (PNK)
TO INDOOR UNIT
B INDOOR
BLK
MAGNETIC COIL
MAGNETIC COIL
W
5
5
4
4
3
3
2
2
1
1
4
4
3
3
2
2
1
1
FM
BLU
WHT
RED (PNK)
(3P)CONNECTOR
UNIT
C INDOOR
WHT
BRN
GRY
5
5
BLK
4
4
YEL
3
3
RED
2
2
ORG
1
1
YEL
YEL
YEL
YEL
FAN MOTOR
R/V
CM
S/UC/W
GND
MV2
SWITCH
MOTOR
COMPRESSOR
WHT
MAGNETIC COIL
BLK
11
22
CN THERMISTOR
11
(2P)CONNECTOR
CW THERMISTOR
(2P)CONNECTOR
WHTWHT
BLK
BLK
HIGH PRESSURE
OVERLOAD
RELAY(OLR)
22
WHTWHT
RED
8FA2-5257-59100-1
59
Page 62
Outdoor Unit CMH2472A
BLK
REACTANCE
WHT
1 1
(1P)CONNECTOR
4WAY
VALVE COIL
DEFROST
VALVE COIL
1 1
RV
DEF
1
RELAY
6
GRN/YEL
WHT
WHT
WHT
(1P)
CONNECTOR
RED
RED
RED
RED
4
BLK
5
BLK
GRN/YEL
1
1
2
2
WHT
(2P)CONNECTOR
WHT
WHT
WHT
WHT
CRANKCASE
WHT
1
1
2
2
(2P)CONNECTOR
BLK
1
1
2
2
(2P)CONNECTOR
BN THERMISTOR
YEL
YEL
YEL
YEL
BW THERMISTOR
AN THERMISTOR
YEL
YEL
YEL
YEL
AW THERMISTOR
THERMISTOR
OUTDOOR
BLK
BLK
YEL
YEL
THERMISTOR
COIL
L1
BLK
1
TERMINAL PLATE
W
ACIN1
WW
E
W
E1
WHT
WHT
W
L2 L1
W
HEATER0
HEATER
BLK
BLK
W WW
RV1 RV0HEATER1
BLK
BLK
W W
DEF1 DEF0
4
4
3
3
B-TH
2
2
1
1
4
4
3
3
A-TH
2
2
1
1
4
4
3
3
2
2
1
1
COIL/OUTDOOR
1
1
BLK
BLK
THERMISTOR
COMPRESSOR
SUPPLY
POWER
L2
2
WHT
W
ACIN2
25A
COMP
2 2
GND
FERRITE
WHT
CORE
W
W
SI-A
SI-B
MV0
MV1
W
SICOM2
KS10
CONTROLLER
KS22
KS23FM
U
WVWWW
UNIT
UNIT
A INDOOR
123456789
BLK
BLK
GRY
BLK
YEL
RED
ORG
GRY
BLK
YEL
RED
ORG
WHT
BLU
5
5
4
4
3
3
MV0
2
2
1
1
5
5
4
4
3
3
MV1
2
2
1
1
SI-C
W
SICOM2
SI-D
4
4
3
3
CN01
2
2
MV2C-TH
1
1
6
6
5
5
4
4
MV3
CN02
3
3
2
2
1
1
TERMINAL PLATE
RED
5
5
4
4
3
3
2
2
1
1
5
5
4
4
3
3
2
2
1
1
WHT
BLU
4
RED
3
WHT
2
BLK
1
WHT
6
BLK
5
BLU
4
RED
3
WHT
2
BLK
1
EXPANSION BOARD
BLU
8
RED
WHT
BLK
BLU
RED
WHT
BLK
ORG
WHT
BRN
BLU
RED
WHT
7
6
5
4
3
2
1
7
6
5
4
3
2
1
1 2 3 4 5 6 7
CORE
FERRITE
8
7
6
5
CN03
4
3
D-TH
2
1
(7P)CONNECTOR
ORG
WHT
BRN
BLU
RED
WHT
3
3
2
2
1
1
(3P)CONNECTOR
8
7
6
5
4
3
2
1
7
6
5
4
3
2
1
BLU
WHT
RED (PNK)
B INDOOR
BLK
WHT
MAGNETIC COIL
MAGNETIC COIL
W
W
5
5
4
4
3
3
2
2
1
1
5
5
4
4
3
3
2
2
1
1
4
4
3
3
2
2
1
1
4
4
3
3
2
2
1
1
FM
FAN MOTOR
BLU
WHT
RED (PNK)
TO INDOOR UNIT
UNIT
UNIT
C INDOOR
101112
WHT
BRN
GRY
5
5
BLK
4
4
YEL
3
3
RED
MV2
2
2
ORG
1
1
GRY
5
5
BLK
4
4
YEL
3
3
RED
MV3
2
2
ORG
1
1
YEL
YEL
YEL
YEL
YEL
YEL
YEL
YEL
SWITCH
R/V
CM
S/UC/W
COMPRESSOR
D INDOOR
GND
GRY
WHT
MAGNETIC COIL
BLK
11
22
CN THERMISTOR
MAGNETIC COIL
11
(2P)CONNECTOR
CW THERMISTOR
DN THERMISTOR
(2P)CONNECTOR
DW THERMISTOR
BLK
BLK
HIGH PRESSURE
MOTOR
OVERLOAD
RELAY(OLR)
WHTWHT
22
WHTWHT
RED
8FA2-5257-59300-1
60
Page 63
Outdoor Unit CMH3172A
BLK
REACTANCE
WHT
1 1
(1P)CONNECTOR
4WAY
VALVE COIL
DEFROST
VALVE COIL
CORE
1 1
RV
DEF
1
RELAY
6
FERRITE
WHT
WHT
WHT
(1P)
CONNECTOR
RED
RED
RED
RED
4
BLK
5
BLK
GRN/YEL
GRN/YEL
1
1
2
2
WHT
(2P)CONNECTOR
WHT
WHT
WHT
WHT
CRANKCASE
WHT
1
1
2
2
(2P)CONNECTOR
BLK
1
1
2
2
(2P)CONNECTOR
BN THERMISTOR
YEL
YEL
YEL
YEL
BW THERMISTOR
AN THERMISTOR
YEL
YEL
YEL
YEL
AW THERMISTOR
THERMISTOR
OUTDOOR
BLK
BLK
YEL
YEL
THERMISTOR
COIL
L1
BLK
1
TERMINAL PLATE
W
ACIN1
WW
E
W
E1
WHT
WHT
W
L2 L1
W
HEATER0
HEATER
BLK
BLK
W WW
RV1 RV0HEATER1
BLK
BLK
W W
DEF1 DEF0
4
4
3
3
B-TH
2
2
1
1
4
4
3
3
A-TH
2
2
1
1
4
4
3
3
2
2
1
1
COIL/OUTDOOR
1
1
BLK
BLK
THERMISTOR
COMPRESSOR
SUPPLY
POWER
L2
2
WHT
WHT
W
ACIN2
25A
COMP
2 2
GND
W
W
SI-A
SI-B
MV0
MV1
W
SICOM2
KS10
CONTROLLER
KS22
KS23FM
U
WVWWW
UNIT
UNIT
A INDOOR
123456789
BLK
BLK
GRY
BLK
YEL
RED
ORG
GRY
BLK
YEL
RED
ORG
WHT
BLU
5
5
4
4
3
3
MV0
2
2
1
1
5
5
4
4
3
3
MV1
2
2
1
1
SI-C
W
SICOM2
SI-D
4
4
3
3
CN01
2
2
MV2C-TH
1
1
6
6
5
5
4
4
MV3
CN02
3
3
2
2
1
1
TERMINAL PLATE
RED
5
5
4
4
3
3
2
2
1
1
5
5
4
4
3
3
2
2
1
1
WHT
BLU
4
RED
3
WHT
2
BLK
1
WHT
6
BLK
5
BLU
4
RED
3
WHT
2
BLK
1
EXPANSION BOARD
BLU
8
RED
WHT
BLK
BLU
RED
WHT
BLK
ORG
WHT
BRN
BLU
RED
WHT
7
6
5
4
3
2
1
7
6
5
4
3
2
1
1 2 3 4 5 6 7
CORE
FERRITE
8
7
6
5
CN03
4
3
D-TH
2
1
(7P)CONNECTOR
ORG
WHT
BRN
BLU
RED
WHT
3
3
2
2
1
1
(3P)CONNECTOR
8
7
6
5
4
3
2
1
7
6
5
4
3
2
1
BLU
WHT
RED (PNK)
B INDOOR
BLK
WHT
MAGNETIC COIL
MAGNETIC COIL
W
W
5
5
4
4
3
3
2
2
1
1
5
5
4
4
3
3
2
2
1
1
4
4
3
3
2
2
1
1
4
4
3
3
2
2
1
1
FM
FAN MOTOR
BLU
WHT
RED (PNK)
TO INDOOR UNIT
UNIT
UNIT
C INDOOR
101112
WHT
BRN
GRY
5
5
BLK
4
4
YEL
3
3
RED
MV2
2
2
ORG
1
1
GRY
5
5
BLK
4
4
YEL
3
3
RED
MV3
2
2
ORG
1
1
YEL
YEL
YEL
YEL
YEL
YEL
YEL
YEL
SWITCH
R/V
CM
S/UC/W
COMPRESSOR
D INDOOR
GND
GRY
WHT
MAGNETIC COIL
BLK
11
22
CN THERMISTOR
MAGNETIC COIL
11
(2P)CONNECTOR
CW THERMISTOR
DN THERMISTOR
(2P)CONNECTOR
DW THERMISTOR
BLK
BLK
HIGH PRESSURE
MOTOR
OVERLOAD
RELAY(OLR)
WHTWHT
22
WHTWHT
RED
8FA2-5257-89400-1
61
Page 64
7. FUNCTIONS
7-1. Explanation of Functions
NOTE
The numerical values such as temperature, frequency, time and current in parentheses are an example
of CMH3172A and the values are different from the other models.
INITIAL
HEAT
Control/conditions
Breaker is ON.Power is supplied to the indoor and outdoor unit
The ON/OFF operation
button on the remote
controller is pressed.
The ON/OFF operation
button on the remote
controller is pressed.
If automatic operation mode has been selected
with the remote controller, operation begins in
HEAT, SENSOR DRY, or COOL mode
depending on the room temperature and
outdoor temperature at the time operation starts.
Depending on the operational mode, refer to the HEAT, SENSOR DRY, or COOL item.
Operation lamp illuminates.
Indoor fan is stopped to prevent cold air from
being emitted.
Outdoor unit begins operating after
forced-stop is canceled.
When the indoor coil temperature rises,
the compressor starts,
the outdoor fan starts,
and the indoor fan changes from "LL"
to the set fan speed.
Unit operationExplanation
control circuits, however the unit remains stopped.
Positioning of the outdoor unit electric expansion
valve is performed.
This applies in the case of automatic
HEAT/COOL operation.
The unit is forced to stop for 3 minutes after
the power is turned ON, or 3 minutes after the
compressor stops, in order to protect the
compressor.
The frequency is increased at the rate of 1 Hz
every 0.5 seconds.
Depending on the relationship between the
remote controller temperature setting and the
room temperature, the compressor may stop
temporarily (in other words, the thermostat
may turn OFF).
The room temperature
has reached the desired
temperature.
The thermostat turns
OFF.
The indoor and outdoor
temperatures are high.
When the frequency reaches Hz,frequency
increases are stopped for a period of seconds.
(Refor to Table 2 "Freguency control".)
The frequency then increases.
The indoor temperature and the remote
controller temperature setting are
approximately equal.
The indoor fan is stopped.
In order to protect the compressor, the outdoor
unit will not operate for 3 minutes after the
thermostat turns OFF, even if the room
temperature drops below the desired
temperature.
The frequency is not increased, even if
there is a difference between the room
temperature and the desired temperature.
In some cases, the frequency may be
decreased.
This is in order to stabilize the return of oil to the
compressor.
If the indoor and outdoor temperatures are high,
the current peak cut-off activates, stopping any
increases in frequency.
Operating frequency is stabilized in order to
maintain a comfortable environment.
The outdoor unit stops. (It does not stop if the
thermostat for another indoor unit is ON.)
Approximately 30 seconds after the
thermostat turns OFF, the indoor fan is
stopped.
The outdoor unit starts automatically after 3
minutes.
During these 3 minutes, a low-pressure
pressure balance is achieved, allowing the
compressor to start more easily.
The amount of heat pump exceeds the amount
of heat radiation from the room.
Therefore, there is no need to further increase
the compressor capacity, and the frequency is
stabilized or lowered.
62
Page 65
Control/conditions
Unit operationExplanation
HEAT
The thermostat turns ON.The unit operated before, and the temperature of
When defrost operation
begins, frost has formed
on the outdoor unit
(when the ambient air
temperature is low).
The indoor unit is stopped.
Non-stop defrost
Indoor fan : Stopped
Outdoor fan : Stopped
Compressor : 80 Hz
Solenoid valve (for hot gas bypass): ON
4-way valve : Remains ON
Operation lamp : Red and orange ON
alternately
the indoor heat exchanger is relatively warm.
Therefore,the fan speed may start at the set fan
speed at the same time that the thermostat turns
ON.
Defrost operation begins based on outdoor
heat exchanger temperature and outdoor
air temperature conditions.
Non-stop defrost (Refer to Fig. 1)
1. After HEAT operation begins, the temperature
of the outdoor heat exchanger is at or below the
L1 line for 35 minutes.
(If outdoor air temperature is less than 26.6 °F,
the time is 48 minutes)
2. After HEAT operation begins, the temperature
of the outdoor heat exchanger is at or below the
L2 line for 120 minutes.
The 4-way valve remains ON during defrost.
The outdoor fan stops and the solenoid
valve turns ON, allowing the refrigerant to
bypass the indoor unit.
The operating frequency during defrost is
80 Hz. (Frequency is lowered if the current
peak cut-off function is activated.)
The maximum length of a single defrost
operation is 12 minutes.
For the outdoor heat exchanger temperature
conditions for ending defrost, refer to Table 1.
Defrost releaseIndoor fan turns ON.
After 10 seconds, the solenoid valve
(for hot gas bypass) turns OFF.
When the cold air feel has disappeared,
the indoor fan starts and gradually increases
speed until it reaches the set speed.
STOP
[Clean defrost]
Defrost is performed
when the outdoor unit is
stopped, and the
temperature of the
outdoor unit coil is at or
below the L1 line.
(Refer to Fig. 1.)
Operation is restarted
within 4 hours (only when
AUTO mode is selected
with the remote
controller).
Operation starts after 4
hours or more have
passed.
All indicator lamps turn OFF. The indoor and
outdoor units stop.
Starts operating in the same operating mode
(HEAT) and with the same temperature
settings as before operation was stopped.
New operation begins based on the
temperature conditions at the time the
ON/OFF button is pressed.
Within 4 hours after operation was stopped, it is
assumed that there has been no significant
change in the indoor and outdoor temperatures,
and the previous conditions (HEAT) are stored.
63
Page 66
exchanger temperature (°F)
Outdoor heat
(- 4)0
L2
L1
(21.2)
(19.4)
(-11.2)
(-13.0)
Outdoor air
temperature (°F)
Temperature of releasing
Defrost operation time
Heat exchanger
temperature for
releasing defrosting
*1 The temperature for releasing of defrosting is (68 °F) or higher when the
outdoor air temperature is less than 32 °F.
Less than 2 minutes2 minutes or more
No releasing57.2 °F or higher (*1)
COOL
Fig. 1
Control/conditions
The ON/OFF operation
button on the remote
controller is pressed.
The room temperature
has reached the
desired temperature.
The thermostat turns
OFF.
The thermostat turns
ON again.
Unit operationExplanation
The operation lamp illuminates.
The indoor fan operates at the set fan speed.
The outdoor unit stops.
The outdoor unit starts.
(Compressor and the outdoor fan start.)
When the frequency reaches Hz,
frequency increases are stopped for a period
of seconds. (Refer to Table 2.)
The frequency then increases.
The indoor temperature and the desired
temperature are approximately equal.
After the thermostat turns ON again, the
outdoor unit will not operate for 3 minutes,
even if the room temperature increases
above the desired temperature.
Table 1
The outdoor unit does not operate for 3 minutes
even after the breaker is turned ON.
The frequency is increased at the rate of 0.5
Hz every 1 seconds.
This is in order to stabilize the return of oil to the
compressor.
If the indoor and outdoor temperatures are high,
the current peak cut-off activates, stopping
any increases in frequency.
Operating frequency is stabilized in order to
maintain a comfortable environment.
The outdoor unit stops. (It does not stop if the
thermostart for another indoor unit is ON.)
After 3 minutes, the outdoor unit begins operating
automatically.
During these 3 minutes, a pressure balance is
achieved, allowing the compressor to start
more easily.
Freeze preventionIn order to protect against freezing, the
StopAll indicator lamps turn OFF. The indoor and
Operation is restarted
within 4 hours (only when
AUTO mode is selected
with the remote
controller).
Operation starts after 4
hours or more have
passed.
When the temperature of the indoor heat
exchanger drops to approximately 35.6 °F
or below, the compressor turns OFF, the
outdoor fan turns OFF, and the indoor fan
continues operating with no changes.
Approximately 3 minutes later, if the
temperature of the indoor heat exchanger
is adove 46.4 °F, the system returns to its
original conditions.
outdoor units stop.
Starts operating in the same operating mode
(COOL) and with the same temperature
settings as before operation was stopped.
New operating mode is determined based on
the temperature conditions at the time the
ON/OFF operation button is pressed.
compressor stops temporarily, until the
temperature of the indoor heat exchanger has
risen.
Within 4 hours after operation was stopped, it is
assumed that there has been no significant
change in the indoor and outdoor temperatures,
and the previous conditions (COOL) are stored.
64
Page 67
Frequency control
(1/f fluctuation fan)
Control/conditions
SENSOR
DRY
The ON/OFF operation
button on the remote
controller is pressed.
(Hz)
(25) Hz
(35) Hz
(45) Hz
(55) Hz
(senconds)
Outdoor air temperature is below 32 °F.
(120) seconds
(60) seconds
(60) seconds
(180) seconds
Table 2
Unit operationExplanation
The operation lamp illuminates.
The indoor fan operates at the set fan speed.
The outdoor unit stops.
The outdoor unit starts.
(Compressor and the outdoor fan start.)
When the frequency reaches Hz,
frequency increases are stopped for a period
of seconds. (Refer to Table 2.)
The outdoor unit does not operate for 3 minutes
even after the breaker is turned ON.
The frequency is increased at the rate of 0.5
Hz every 1 seconds.
This is in order to stabilize the return of oil to the
compressor.
The room temperature
reaches the desired
temperature, and there
is no need for further
cooling.
The room temperature is
59 °F or higher, and is
slightly too cold.
The room temperature is
below 59 °F.
The frequency then increases.
DRY operation starts
DRY A operation
The indoor fan changes between "Low"
and "LL" (very low) over a 6-minute cycle.
This is 1/f fluctuation fan operation.
(Refer to Fig. 2.)
DRY B operation
(1)
The indoor fan changes between "Low"
and "LL" (very low) over a 6-minute cycle.
This is 1/f fluctuation fan operation.
(2)
After appoximately 3 minutes, the
compressor turns OFF, the outdoor fan
turns OFF, and the indoor fan turns OFF.
(3)
After approximately 6 minutes, the
conditions return to (1).
Monitoring operation begins.
If the indoor and outdoor temperatures are high,
the current peak cut-off activates, stopping
any increases in frequency.
Operating frequency is stabilized in order to
maintain a comfortable environment.
Operates to effectively dehumidify the air while
not excessively reducing the indoor
temperature.
The indoor unit operates at 1/f fluctuation fan
operation, at a fan speed that does not cause
a chilly feeling.
The compressor operates on a 3-minutes ON,
6-minutes OFF cycle, to prevent the room
temperature from dropping too much.
When monitoring operation begins, the
compressor stops, and the indoor fan operates at
"LL" (very low) speed.
65
Page 68
1/f fluctuation fan
250
200
150
(Step)
100
50
0
6-minute cycle
Fig. 2
66
Page 69
< Low Ambient Cooling Operation >
When the outdoor air temperature reaches 57.2 °F (14 °C ) or less during the cooling operation,
the operation mode is switched to low ambient cooling operation.
When the mode is switched from cooling opration to low ambient cooling operation,
the compressor is stopped for 150 seconds temporarily.
When the mode has been switched to low ambient cooling operation,
the outdoor fan speed is lowered as the outdoor air temperature falls.
Outdoor fan speed [ rpm ]
When the outdoor air temperature reaches 62.6 °F (17 °C ) or more during the low ambient
cooling operation, the operation mode is switched to cooling operation.
The following protective actions are available to prevent the compressor from operating
with abnormal loads.
At that time, they initiate thermo-off ( stopping the outdoor unit ) of the air conditioner.
32 °F ( °C )
Outdoor air temperature
Outdoor air temp.
°F ( °C )
14 (-10)
8.6 (-13)
Compressor
Indoor fan
ONON
OFF
ON
67
Page 70
7-2. Protective Functions
NOTE
The numerical values such as temperature, frequency, time and current in parentheses are an example
of CMH3172A and the values are different from the other models.
7-2-1. Defrost Detection and Release
(1) Non-stop defrosting
Defrosting sequence4-way valve ON
Heating operation
Frost detection
Defrost detection occurs in either of the following cases:
The temperature of the heat exchanger remains at or below
the L1 line for 35 minutes after the start of HEAT operation.
The temperature of the heat exchanger remains at or below
the L2 line for 120 minutes after the start of HEAT operation.
L2
L1
Outdoor heat
(- 4)0
Outdoor air
temperature (°F)
( 21.2)
( 19.4)
(-11.2)
(-13.0)
exchanger temperature (°F)
NOTE
Non-stop defrosting
Releasing of defrosting
Compressor
Outdoor fan
Solenoid valve
(for hot gas bypass)
Indoor fan
Temperature of the outdoor heat exchanger is at or above the
temperature shown in the table below.
Defrost operation has continued for 12 minutes (max. length).
Temperature of releasing
Defrost operation time
Heat exchanger
temperature for
releasing defrosting
*1 The temperature for releasing of defrosting is (68 °F) or higher when the
outdoor air temperature is less than 32 °F.
(80 Hz) operation (4-way valve ON)
OFF
ON
OFF
Less than 2 minutes2 minutes or more
No releasing57.2 °F or higher (*1)
Defrost does not occur during HIGH POWER operation.
If other stopped indoor units are started during defrost operation, they begin operating in
defrost mode.
(2) Clean defrost
If all indoor units are stopped during HEAT operation, and frost is detected at the L1 line, and the
conditions for defrost are met, then defrost operation occurs, and the unit stops after defrost is completed.
68
Page 71
7-2-2. Current Control
The operating current may rise as a result of causes including increasing heating or cooling loads or decreases in power
voltage. In these cases, the operating frequency is automatically reduced, or operation is stopped, in order to control
the operating current so that it is (20 A) or less.
As a result:
Power breakers and fuses will not be tripped.
•
Operation can continue during this period with somewhat reduced heating or cooling capacity.
•
Operation at normal capacity is restored when the cause of the current rise is eliminated.
•
Description of function
Example of operation for heating
(20A)
(17A)
(16.6A)
Target
frequency
Power Point C
Point B
Point A
Frequency
FrequencyCurrent
Operates at the target frequency at Point A and below.
•
Stops increases to the frequency between Points A and B.
•
Reduces the frequency by 1 Hz per 0.5 seconds when Point B is exceeded.
•
Stops operation, and restarts it appoximately 3 minutes later, if Point C is exceeded.
•
(May operate when sudden voltage fluctuations occur. Indicates trouble.)
Stops operation
Approx.3 minutes
(1) Automatic frequency control
The operating frequency is reduced automatically, or operation is stopped, in order to control the operating
current so that it is at or below the values shown in the table below.
(20A)
HEAT
Point C (peak cut trip)
Point B (Hz reduction)
Point A (Hz increase prohibit)(16.6)
NOTE
During defrost operation, the COOL current setting value is used.
(20.0)(20.0)
(17.0)(17.0)
(16.6)
COOL
(2) Current control
The operating frequency upper limits shown in the figure below are established for frequency reduction and
increase-prohibit.
Current(A)
Trip
Hz reduction
Hz increase
prohibit
(16)
(15.6)
0
Example of operation during cooling
Hz increase prohibit
(30)
Hz reduction
Hz increase prohibit
Hz reduction
Frequency (Hz)
69
Page 72
7-2-3. Low Start Current
Operation starts at (8 Hz), and the start current is less than the normal operating current. This prevents the flickering
of fluorescent lights or television screens that occurs when ordinary A/C units start.
7-2-4. Compressor Temperature Control
To protect the compressor coil from overheating, the operating frequency is controlled based on the compressor
discharge temperature.
(°F)
Trip
(230)
5Hz every 30 sec. reduction
(223)
2Hz every 30 sec. reduction
(212)
Increase
No control
Compressor discharge temperature
(194)
*
Within the increase-prohibit range, the range changes
to the Hz reduction range (2 Hz every 30 seconds) if
the compressor temperature rises by 4 °F.
prohibit range
(Hz reduction)
7-2-5. Control at HEAT Start-up
If HEAT operation is started when the outdoor air temperature is 59 °F or below, the unit operates at the HEAT start-up
frequency (70 Hz or above).
Reset conditions
The compressor frequency exceeds the start-up frequency of (70 Hz).
(1)
The compressor thermostat is OFF.
(2)
Frequency reduction for indoor high-load control has occurred.
(3)
The outdoor air temperature is above 59 °F.
(4)
The main-unit switch on one or more indoor units is set to TEST run.
(5)
70
Page 73
8. TROUBLESHOOTING
8-1. Precautions before Performing Inspection or Repair
Both the indoor unit and outdoor unit include electronic control circuits.
Be sure to pay attention to the following before inspecting or repairing the outdoorside electronic circuits.
High-capacity electrolytic capacitors are used inside the outdoor unit controller (inverter). They retain an
electrical charge (charging voltage DC 311 V) even after the power is turned OFF, and some time is required
for the charge to dissipate.
Be careful not to touch any electrified parts before the control circuit board Power Lamp (red) turns OFF.
If the outdoor control circuit board is normal, approximately 180 seconds will be required for the charge to
dissipate. However, allow at least 30 minutes for the charge to dissipate if it is thought there might be trouble
with the outdoor control circuit board.
For example, if the outdoor control circuit board fuse has blown, approximately 30 minutes will be required to
discharge the high-capacity electrolytic capacitors.
71
Page 74
8-2. Trouble Diagnosis by Error Monitor Lamps
Warning
To prevent electric shock, do not inspect or repair until the Power Lamp on
the P.C.Board is turned off.
8-2-1. Location of the Error Monitor Lamps
Remove the top plate of outdoor unit and the cover of Electrical Component Box.
The Power Lamp and Error Monitor Lamps are located on the P.C.Board of Electrical Component Box. (Fig.1)
Heat ExchangerRear sideP.C.Board of Electrical Component Box.
Error Monitor Lamps
Power Lamp
ERR0
ERR1
ERR2
ERR3
Front side
Fig.1 View from top
8-2-2. Display of the Error Monitor Lamps
If a protective device has activated or there is a sensor failure in the outdoor unit, the 4 error monitor lamps on the
outdoor control circuit board will indicate the nature of the trouble.
: ON: OFF
Error Monitor Lamp
ERR0ERR1ERR2ERR3
Sensor for compressor discharge temp
Sensor for heat excharge temp
Sensor for branch pipe A (Narrow tube)
Sensor for branch pipe B (Narrow tube)
Sensor for branch pipe C (Narrow tube)
Sensor for branch pipe D (Narrow tube)
Outdoor temp sensor
Sensor for branch pipe A (Wide tube)
Sensor for branch pipe B (Wide tube)
Sensor for branch pipe C (Wide tube)
Sensor for branch pipe D (Wide tube)
Error Contents
HIC circuit trouble (current, temp)
Actuation of comp over load relay
Actuation of freeze protection function
Outdoor unit error. Detail of error message indicate on indoor LED
72
Page 75
8-3. Checking the Outdoor System
8-3-1. Checking the outdoor unit
No.
1
Apply 220 V AC between terminals L1 and L2 on the
•
Work procedure
outdoor unit terminal plate.
Short-circuit the T-RUN terminal to the COM terminal
•
2
of TEST/T-RUN terminals.
NOTE
If the above check items are okay, but the outdoor unit does not operate, there may be a faulty
connection between the indoor unit and the outdoor unit.
8-3-2. Checking the defrost operation
Using forced defrost operation to check this function.
No.
1
Connect a dummy resistor of 39 k ohm to the outdoor
•Non-stop defrost
coil temperature sensor connector.
Work procedure
Check items (unit operation)
The LED (red) on the control board must illuminate.•
The compressor, fan motor, 4-way valve, and solenoid
•
valve (for the hot gas bypass) must turn ON.
(They turn ON about (70) seconds later after the power
is turned ON.)
Check items (unit operation)
Indoor fan
CM
Solenoid valve
(for hot gas
bypass)
SettingSetting
30 sec.
LL
Stop
(80 Hz)
ON
10 sec.5 sec.
ONOFFOFF
73
Outdoor fan
Defrost startRelease
•
The maximum length of defrost operation is 12
OFFON
ON
minutes.
Defrost can also be released based on the below
conditions for the outdoor heat exchanger sensor.
Less than 2 minutes Not released
2 minutes or more 57.2 °F or higher (*1)
*1 However, the condition is (68 °F) or higher when
the outdoor air temperature is below 32 °F.
Page 76
8-4. Trouble Diagnosis of Each Part
8-4-1. Problems of Each Part and Inspection Points
For details about the inspection points, refer to the Inspection Points for Each Part.
Problems
Inspection
points
Self-Diagnostics check
Indoor controller
(control unit)
Indoor fan motor
Room temperature
sensor
Heat exchanger
temperature sensor
Indoor unitOutdoor unit
Inter-unit cable
Indoor unit
Indoor unit does not operate.
Operation lamp blinking.
Operation lamp does not illuminate.
Indoor fan dose not turn.
Outdoor unitOthers
Outdoor unit does not operate.
Outdoor fan dose not turn.
4-way valve does not operate.
The compressor (only) does not
operate.
The compressor stops on occasion.
The compressor speed does not
increase.
The outdoor air temperature is high,
however defrost operation occurs.
Defrost operation does not occur.
The electric expansion valve does
not operate.
Does not cool or cooling
No. of
Inspection
Points for
Each part
performance is inadequate.
Does not heat or heating
performance is inadequate.
Switch circuit board
Outdoor control circuit
board
Diode module
HIC
Electrolytic capacitor
Fuse
Compressor
Compressor protective
sensor
Outdoor fan motor
4-way valve
Coil thermistor
Electric expansion valve
(1)
(2)
(3)
(4)
(5)
(6)
(7)
Branch tubing
temperature sensor
(8)
74
Page 77
Problems
Inspection
points
Indoor unit
Indoor unit does not operate.
Operation lamp blinking.
Operation lamp does not illuminate.
Indoor fan dose not turn.
Outdoor unitOthers
Outdoor unit does not operate.
Outdoor fan dose not turn.
4-way valve does not operate.
The compressor (only) does not
operate.
The compressor stops on occasion.
The compressor speed does not
increase.
The outdoor air temperature is high,
however defrost operation occurs.
Defrost operation does not occur.
The electric expansion valve does
not operate.
Does not cool or cooling
No. of
Inspection
Points for
Each part
performance is inadequate.
Does not heat or heating
performance is inadequate.
Breaker
Refrigerant gas pressure
Others
8-4-2. Inspection Points for Each Part
(1) Outdoor control circuit board
Refer to "8-3-1. Checking the outdoor unit".
NOTE
(2) Fuse
Check it visually or the continuity with a tester.
(3) Compressor
Check for an open circuit in the compressor coil winding.
(4) Compressor protective sensor (compressor discharge temperature thermistor)
Check that the senseor is securely contained in the thermostart holder.
Do not remove or insert the outdoor control circuit board connector when power is being supplied to it.
(The controller will be damaged.)
(9)
(10)
(5) 4-way valve
Short-circuit the T-RUN terminal to the COM terminal of TEST/T-RUN terminals. Perfrom a test run of the unit
alone, and check whether the 4-way valve inside the outdoor unit produces a click sound.
(6) Coil thermistor
Check that the sensor is securely contained in the thermostat holder.
75
Page 78
(7) Electric expansion valve
When replacing the electric expansion valve and coil, be sure to attach the connectors in the correct positions.
Labels are applied to the valve body and coil, corresponding to the connector colors, to identify them.
Controller check
No voltage on circuit board
Check the illumination
of the red Power Lamp.
Replace the controller.
NOTE
Cool the main unit with
a damp cloth or other
means while welding.
When applying
vacuum, use the
special service magnet
and rotate at least 5
revolutions
counterclockwise to
fully open the electric
expansion valve.
Use a multi-meter to measure the voltage (12 V).
When the power is turned ON, the needle will move in the
Voltage varies
Check the coil resistance.
0 ohm
Replace the coil.
No temperature changeTemperature changes
Replace the electric
expansion valve.
Approx. 46 +/– 4 ohm
Open and close the
electric expansion valve
by hand to check it.
This part is normal.
following seguence in approximately 10 to 20 seconds for
each point.
*1
Check elsewhere.
Model No.Sequence
CMH1972A
CMH2472A
CMH3172A
Check the resistance between the gray lead
wire and the other wires.
Resistance is OK if it is 46 + / – 4ohm at 68 °F
MV0MV1
MV0MV1MV2MV3
Use the special service magnet and
rotate 5 revolutions clockwise to fully
close the valve.
Then start the unit and measure the
temperature at the inlet and outlet
tubes of the electric expansion valve.
If the temperature difference is large,
the valve is closed.
Then rotate 5 revolutions
counterclockwise to open the valve.
Operation is normal if the temperature
difference between the 2 tubes drops.
MV2
*1 If you have manually checked the electric expansion valve, be sure to reapply the outdoor power after you have
replaced the wiring. (The position of the elecric expansion valve will changed.)
76
Page 79
(8) Branch tubing temperature sensor
Check that the sensor is securely contained in the thermostat holder.
(9) Breaker
Check whether or not the breaker has been tripped.
Check that the breakers and fuses used are of the specified capacity.
Check that the breaker and its line are exclusive for A/C use.
(10) Refrigerant gas pressure
Start a COOL test run, and messure the temperatures of the A/C intake air and discharge air. Compare the values
with the performance charts.
If the values are higher than the performance charts:
Check for refrigerant shortage or blockage of the refrigerant circuit.
< Assessment of refrigerant shortage >
1. The pressure in the low-pressure section is 5 MPa or more below the value in the performance charts.
2. There is little condensation on the indoor heart exchanger, which overall appears dry.
< Distinguishing between refrigerant shortage and refrigerant circuit blockage >
If the pressure in the low-pressure section does not change when the circuit is charged 2 to 3 times with
refrigerant gas (0.44 lbs each time), or if the change is small, then the problem may not be
refrigerant shortage.
The problem may be a blockage of the refrigerant circuit.
1. Check that there is no internal leakage inside the 4-way valve:
At the low-pressure side tubing, check that there is no temperature difference between the intake and
discharge of the 4-way valve.
2. Check that the electric expansion valve is not blocked. Check as described on the preceding page.
77
Page 80
8-5. Trouble Diagnosis of Fan Motor
This outdoor DC fan motor contains an internal control PCB. Therefore, it is not possible to measure the coil
resistance, and the following procedure should be used to check the motor.
Perform the trouble diagnosis by Test Run mode described on Installation Instructions of indoor unit.
Important:
[Trouble symptom 1] The fan does not stop when the outdoor unit stops. Outdoor unit controller trouble
[Trouble symptom 2] The fan motor does not rotate when the outdoor unit is operating.
(Diagnostic procedure)
(Diagnostic results)
(Reference)DC motor connector pin arrangement
(A) Turn OFF the power before connecting or disconnecting the motor connectors.
(B) When performing voltage measurement at the outdoor controller connector for (3) in the table
below, the DC motor will trip and voltage output will stop approximately 10 seconds after
operation is started. For this reason, to measure the voltage again, first turn OFF the outdoor
unit power, then, measure the voltage in Test Run mode.
* Disconnect the motor connectors and measure the voltage at the DC motor connectors on the outdoor
unit controller (3 locations).
Measurement location
(1) Vm-Gnd: Between pin 1 and pin 4
(2) Vcc-Gnd: Between pin 5 and pin 4
(3) Vsp-Gnd: Between pin 7 and pin 4
All of the above measured values are normal. Fan motor trouble (Replace the motor.)
Any one of the above measured values is not normal. Outdoor unit controller trouble
Pin 1: Vm (red)
Pin 2: Not used
Pin 3: Not used
Pin 4: Gnd (blue)
Pin 5: Vcc (brown)
Pin 6: PG (white)
Pin 7: Vsp (orange)
DC 230V or more
DC 14V or more
After fluctuating 4 times between DC 1.7 to 6.1V
(1 sec. ON) and DC 0 V (1 sec. OFF), the DC
motor trips.
(Replace the controller .)
Normal value
[Trouble symptom 3] Motor rotates for some time (several seconds), but then quickly stops, when the outdoor
unit operates.
(There is trouble in the system that provides feedback of motor rotation speed from the
motor to the outdoor unit controller.)
[Trouble symptom 4] Fan motor rotation speed does not change during outdoor unit operation.
[Trouble symptom 5] Fan motor rotation speed varies excessively during outdoor unit operation.
(Remedy for symptom 3 to 5)
It is not possible to identify whether the trouble is outdoor unit controller trouble or motor trouble.
Therefore, first replace the outdoor unit controller, then (if necessary) replace the DC motor.
78
Page 81
9. REFRIGERANT R410A:
SPECIAL PRECAUTIONS WHEN SERVICING UNIT
9-1. Characteristics of New Refrigerant R410A
9-1-1. What is New Refrigerant R410A?
R410A is a new refrigerant that contains two types of pseudo-non-azeotropic refrigerant mixture. Its
refrigeration capacity and energy efficiency are about the same level as the conventional refrigerant, R22.
9-1-2. Components (mixing proportions)
HFC32 (50%) / HFC125 (50%)
9-1-3. Characteristics
Less toxic, more chemically stable refrigerant
The composition of refrigerant R410A changes whether it is in a gaseous phase or liquid phase. Thus, when
there is a refrigerant leak the basic performance of the air conditioner may be degraded because of a change in
composition of the remaining refrigerant. Therefore, do not add new refrigerant. Instead, recover the
remaining refrigerant with the refrigerant recovery unit. Then, after evacuation, totally recharge the specified
amount of refrigerant with the new refrigerant at its normal mixed composition state (in liquid phase).
When refrigerant R410A is used, the composition will differ depending on whether it is in gaseous or liquid
phase, and the basic performance of the air conditioner will be degraded if it is charged while the refrigerant is in
gaseous state. Thus, always charge the refrigerant while it is in liquid phase.
CAUTION
Ether-type oil is used for compressor oil for R410A-type units, which is different
from the mineral oil used for R22. Thus more attention to moisture prevention and
faster replacement work compared with conventional models are required.
79
Page 82
9-2. Checklist before Servicing
Use a clutch-type flare tool for R410A or the conventional flare tool. Note that sizes of the resultant flares differ
between these two tools. Where a conventional flare tool is used, make sure to observe A Specification (amount of
extrusion) by using the flare spacer.
Flare tool for R410AConventional flare tool (for R22)
0 to 0.0196"
(0 to 0.5 mm)
D
Flare tool for R410A
A
Conventional flare tool (R22)
D
0.0472"
(1.2 mm)
Spacer
A
Refrigerant R410A is more easily affected by dust or moisture compared with R22, thus be sure to temporarily
cover the ends of the tubing with caps or tape prior to installation.
Never use 0.0276" (0.7 mm)-thick copper tubing or tubing which is less than 0.0315" (0.8 mm) in thickness, since
air conditioners with R410A are subject to higher pressure than those using R22 and R407C.
No addition of compressor oil for R410A
No additional charge of compressor oil is permitted.
No use of refrigerant other than R410A
Never use a refrigerant other than R410A.
If refrigerant R410A is exposed to fire
Through welding, etc., toxic gas may be released when R410A refrigerant is exposed to fire. Therefore, be sure
to provide ample ventilation during installation work.
Caution in case of R410A leak
Check for possible leak points with the special leak detector for R410A. If a leak occurs inside the room,
immediately provide thorough ventilation.
80
Page 83
9-3. Tools Specifically for R410A
For servicing, use the following tools for R410A
Tool DistinctionTool Name
Gauge manifold
Charging hose
Gas leak detector
Refrigerant cylinder
Charging cylinder
Refrigerant recovery unit
Tools specifically for R410A
Vacuum pump with anti-reverse flow (*1)
(Solenoid valve-installed type, which prevents oil from flowing back into the
unit when the power is off, is recommended.)
Vacuum pump (*2)...can be used if the following adapter is attached.
Vacuum pump adapter (reverse-flow prevention adapter) (*3).
(Solenoid valve-installed adapter attached to a conventional vacuum pump.)
Electronic scale for charging refrigerant
Flare tool
Bender
Tools which can be commonly used for R22,
R407C, and R410A
CAUTION
To prevent other refrigerants (R22, R407C) from being mistakenly charged to this unit, shape and external
diameter of the service port screw has been altered.
<External diameter of service port> R410A : 5/16"
R22, R407C : 1/4"
The above tools specifically for R410A must not be used for R22 and R407C.
Doing so will cause malfunction of the unit.
For the above vacuum pump (*1, *2) and vacuum pump adapter (*3), those for
R22-type units can be used for R410A-type. However, they must be used
exclusively for R410A and never alternately with R22 and R407C.
Torque wrench
Cutter, reamer
Welding tool, nitrogen gas cylinder
9-4. Tubing Installation Procedures
When the tubes are connected, always apply HAB oil on the flare portions to improve the sealing of tubing.
The following is the HAB oil generally used:
Esso: ZERICE S32
NOTE
For details on tubing installation procedures, refer to the installation manuals attached to the indoor
unit and outdoor unit.
81
Page 84
9-5. In Case of Compressor Malfunction
CAUTION
Should the compressor malfunction, be sure to make the switch to a replacement
compressor as quickly as possible.
Use only the tools indicated exclusively for R410A. See "9-3. Tools Specifically
for R410A."
9-5-1. Procedure for Replacing Compressor
(1) Recovering refrigerant
Any remaining refrigerant inside the unit should not be
released to the atmosphere, but recovered using the
refrigerant recovery unit for R410A.
Do not reuse the recovered refrigerant, since it will contain
impurities.
(2) Replacing Compressor
Soon after removing seals of both discharge and suction
tubes of the new compressor, replace it quickly.
(3) Checking for sealing
(1) Recover refrigerant
OK
(2) Replace compressor
OK
Use nitrogen gas for the pressurized gas, and never use a
refrigerant other than R410A. Also do not use oxygen or
any flammable gas.
(4) Evacuation
Use a solenoid valve-installed vacuum pump so that
even if power is cut off in the middle of evacuation of air
due to a power interruption, the valve will prevent the
pump oil from flowing back.
The equipment may be damaged if moisture remains in
the tubing, thus carry out the evacuation thoroughly.
When using a vacuum pump with exhaust air volume more
than 0.883 cu.ft./min. and ultimate vacuum pressure rate
of 50 micron Hg.
Standard time for evacuation
Length of tubing
Evacuation time
Less than 33 ft. (10 m)
More than 10 minutes
(3) Check for sealing
OK
(4) Evacuation
OK
(5) Recharge
More than 33 ft. (10 m)
More than 15 minutes
82
Page 85
(5) Recharging
Configuration and characteristics of cylinders
Be sure to charge the specified amount of
refrigerant in liquid state using the service port
of the wide tube service valve. The proper
amount is listed on the unit's nameplate.
When the entire amount cannot be charged all at
once, charge gradually while operating the unit in
Cooling Operation.
CAUTION
Never charge a large amount
of liquid refrigerant at once to
the unit. This may cause
damage to the compressor.
When charging with a refrigerant cylinder, use an
electronic scale for charging refrigerant. In this
case, if the volume of refrigerant in the cylinder
becomes less than 20% of the fully-charged
amount, the composition of the refrigerant starts
to change. Thus, do not use the refrigerant if
the amount in the charging cylinder is less
than 20%.
Also, charge the minimum necessary amount to
the charging cylinder before using it to charge
the air conditioning unit.
Valve
Liquid
Single valve
Charge liquid refrigerant with
cylinder in up-side-down position.
Fig. 1
Valve
Example:
In case of charging refrigerant to a unit requiring
1.68 lb. (0.76 Kg) using a capacity of a 22 lb. (10
Kg) cylinder, the minimum necessary amount for
the cylinder is:
For the remaining refrigerant, refer to the
instructions of the refrigerant manufacturer.
If using a charging cylinder, transfer the specified
amount of liquid refrigerant from the refrigerant
cylinder to the charging cylinder.
Prepare an evacuated charging cylinder
beforehand.
CAUTION
To prevent the composition
of R410A from changing,
never bleed the refrigerant
gas into the atmosphere
while transferring the
refrigerant. (Fig. 3)
Charging
cylinder
Open
Liquid
Single valve (with siphon tube)
Charge with cylinder in normal position.
Fig. 2
NO!
Liquid
Refrigerant
cylinder
Do not use the refrigerant if the amount in the
charging cylinder is less than 20%.
Fig. 3
83
Page 86
9-6. In Case Refrigerant is Leaking
CAUTION
Never attempt to charge additional refrigerant when refrigerant has been leaking
from the unit. Follow the procedure described below to locate points of leaks and
carry out repairs, then recharge the refrigerant.
(1) Detecting Leaks
Use the detector for R410A to locate refrigerant leak
points.
(2) Recovering refrigerant
Never release the gas to the atmosphere; recover
residual refrigerant using the refrigerant recovery unit for
R410A, instead.
Do not reuse the recovered refrigerant because its
composition will have been altered.
(3) Welding leaking points
Confirm again that no residual refrigerant exists in the unit
before starting welding.
Weld securely using flux and wax for R410A.
Prevent oxide film from forming inside the tubes utilizing
substitution with nitrogen (N2) in the refrigerant circuit of
the unit. Leave ends of tubes open during welding.
(1) Detect leaks
OK
(2) Recover refrigerant
OK
(3) Weld leaking points
OK
(4) Checking for sealing
Use nitrogen gas for the pressurized gas, and never use
a refrigerant other than R410A. Also do not use oxygen or
any flammable gas.
(5) Evacuation
Use a solenoid valve-installed vacuum pump so that
even if power is cut off in the middle of evacuation of air
due to a power interruption, the valve will prevent the
pump oil from flowing back.
The equipment may be damaged if moisture remains in
the tubing, thus carry out the evacuation thoroughly.
When using a vacuum pump with exhaust air volume
more than 0.883 cu.ft./min. and ultimate vacuum pressure
rate of 50 micron Hg.
Standard time for evacuation
Length of tubing
Evacuation time
(6) Recharging
Less than 33 ft. (10 m)
More than 10 minutes
(4) Check for sealing
OK
(5) Evacuation
OK
(6) Recharge
More than 33 ft. (10 m)
More than 15 minutes
Recharge unit in the same manner explained on the
previous page "(5) Recharging."
84
Page 87
9-7. Charging Additional Refrigerant
9-7-1. When Tubes are Extended
Observe the proper amount of refrigerant as stated in this service manual or the installation manual that came
with the indoor unit. Charge additional refrigerant in liquid state only.
CAUTION
Never charge additional refrigerant if refrigerant is leaking from the unit. Follow
instructions given in "9-6. In Case Refrigerant is Leaking" and completely carry out
repairs. Only then should you recharge the refrigerant.
9-8. Retro-Fitting Existing Systems
9-8-1. Use of Existing Units
Never use new refrigerant R410A for existing units which use R22. This will cause the air conditioner to
operate improperly and may result in a hazardous condition.
9-8-2. Use of Existing Tubing
If replacing an older unit that used refrigerant R22 with a R410A unit, do not use its existing tubing. Instead,
completely new tubing must be used.
85
Page 88
APPENDIX A
INSTALLATION INSTRUCTIONS
CMH1972A
CMH2472A
CMH3172A
(II-852-6-4190-507-00-0)
A-1
Page 89
CAUTION
For Outdoor Unit
INSTALLATION INSTRUCTIONS
– Inverter Multi Split System Air Conditioner –
This air conditioner uses the new refrigerant R410A.
NOTE
Contents
IMPORTANT!
Please Read Before Starting .................................. 2
1-1. Tools Required for Installation (not supplied)
1-2. Accessories Supplied with Unit
1-3. Optional Copper Tubing Kit
1-4. Type of Copper Tube and Insulation Material
1-5. Additional Materials Required for Installation
2.INSTALLATION SITE SELECTION ................... 4
2-1. Indoor Unit
2-2. Connecting Indoor Units
2-3. Outdoor Unit
2-4. Baffle Plate for the Outdoor Unit
2-5. Outer Dimensions of Outdoor Unit
2-6. Diagram of Outdoor Unit Installation
3.INSTALLATION PROCESS .............................. 15
3-1. Embedding the Tubing and Wiring
3-2. Use of the Flaring Method
3-3. Flaring Procedure with a Flare Tool
3-4. Caution before Connecting Tubes Tightly
3-5. Tubing Connections
3-6. Insulation of Refrigerant Tubing
3-7. Taping the Tubes
3-8. Finishing the Installation
Be sure to connect indoor and outdoor units
only in combinations that are listed in the
combination table(s) included in the outdoor
unit package.
Connecting any other model may result in
operation failure and malfunction.
5-1. General Precautions on Wiring
5-2. Recommended Wire Length and Diameter
5-3. Wiring System Diagram
5-4. How to Connect Wiring to the Terminal
5-5. Wiring Instructions for the Outdoor Unit
The illustrations are based on the typical appearance of
a standard model. Consequently, the shape may differ
from that of the air conditioner that you are installing.
SANYONorth America CorporationIn Canada
Commercial Solutions DivisionSANYO Canada Inc.
2055 Sanyo Ave., San Diego201 Creditview Road, Woodbridge
CA 92154, U.S.A.Ontario, L4L 9T1, Canada
Page 90
IMPORTANT!
CAUTION
WARNING
WARNING
CAUTION
Please Read Before Starting
When Installing…
This air conditioning system meets strict safety and operating
standards.As the installer or service person, it is an important
part of your job to install or service the system so it operates
safely and efficiently.
For safe installation and trouble-free operation,you
must:
G
Carefully read this instruction booklet before beginning.
G
Follow each installation or repair step exactly as shown.
G
Observe all local, state, and national electrical codes.
G
Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard
or unsafe practice which can
result in severe personal injury
or death.
This symbol refers to a hazard
or unsafe practice which can
result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions.If you require help for a
special problem, contact our sales/service outlet or your
certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to
follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. ONLY A
QUALIFIED, EXPERIENCED ELECTRICIAN
SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing
are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this
system. Carefully refer to the wiring diagram and these
instructions when wiring. Improper connections and
inadequate grounding can cause accidental injury or
death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
When Transporting
Be careful when picking up and moving the indoor and outdoor units.Get a partner to help, and bend your knees when
lifting to reduce strain on your back.Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
…In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the
unit’s weight.It may be necessary to construct a strong
wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent
“sweating”that can cause dripping and water damage to
walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a
solid, level foundation for the outdoor unit.This prevents
water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a
metal frame.Provide a suitable air baffle.
…In a Snowy Area
Install the outdoor unit on a raised platform that is higher
than drifting snow.Provide snow vents.
When Connecting Refrigerant Tubing
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of
the flare and union tubes before connecting them, then
tighten the nut with a torque wrench for a leak-free
connection.
• Check carefully for leaks before starting the test run.
When Servicing
• Turn the power OFF at the main power box (mains) before
opening the unit to check or repair electrical parts and
wiring.
• Keep your fingers and clothing away from any moving
parts.
• Clean up the site after you finish, remembering to check
that no metal scraps or bits of wiring have been left inside
the unit being serviced.
Others
• Ventilate any enclosed areas when installing or testing
the refrigeration system. Escaped refrigerant gas, on
contact with fire or heat, can produce dangerously
toxic gas.
• Confirm upon completing installation that no refrigerant
gas is leaking. If escaped gas comes in contact with a
stove, gas water heater, electric room heater or other heat
source, it can produce dangerously toxic gas.
• Do not install only a single indoor unit.
2
Page 91
CAUTION
1. General
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning.
If the electric wiring diagram does not appear in this manual, please check for the diagram on the indoor unit.
1-1. Tools Required for Installation (not supplied)
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenter’s level
6. Sabre saw or key hole saw
1-2. Accessories Supplied with Unit
Table 1
PartsFigureQ’tyPartsFigureQ’tyPartsFigureQ’ty
Hex wrenchCushion rubber4
Labels for inter-unit
cable and tube
ABCD
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
1
4 each
Reducer
(3/8" 1/2")
CMH1972A
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
16. Vacuum pump (For R410A)
17. Manifold valve
Reducer
(1/2" 3/8")
1
CMH2472A
CMH3172A
Packed in the outdoor unit.
1
2
1-3. Optional Copper Tubing Kit
Copper tubing for connecting the outdoor unit to the
indoor unit is available in kits which contain the narrow
and wide tubing, fittings and insulation. Consult your
nearest sales outlet or air conditioning workshop.
2.Foamed polyethylene insulation for the specified
copper tubes as required to precise length of tubing.
Wall thickness of the insulation should be not less
than 5/16" (8 mm).
3.Use insulated copper wire for field wiring.Wire size
varies with the total length of wiring.
1-4. Type of Copper Tube and Insulation Material
Refer to 5.Wiring Instructions for details.
If you wish to purchase these materials separately from
a local source, you will need:
1.Deoxidized annealed copper tube for refrigerant tubing as detailed in Table 2.
Cut each tube to the appropriate lengths 1' to 1'4"
Check local electrical codes
and regulations before
obtaining wire. Also, check
any specified instructions or
limitations.
(30 cm to 40 cm) to dampen vibration between units.
1-5. Additional Materials Required for Installation
1.Refrigeration (armored) tape
2.Insulated staples or clamps for connecting wire
(See local codes.)
3.Putty
4.Refrigeration lubricant
5.Clamps or saddles to secure refrigerant tubing
3
Page 92
2. Installation Site Selection
Drain hose
Indoor unit
Outside drainage
INDOOR
UNIT (1)
INDOOR
UNIT (4)
INDOOR
UNIT (3)
INDOOR
UNIT (2)
Tubing length (L1)
L2
L3
L4
H2
H3
H4
OUTDOOR
UNIT
Elevation
difference (H1)
WARNING
CAUTION
3.3 ft.
(1m)
(1m)
(1m)
3.3 ft.
(1m)
3.3 ft.
3.3 ft.
3.3 ft.
(1m)
2-1. Indoor Unit
To prevent abnormal heat generation
and the possibility of fire, do not
place obstacles, enclosures and
grilles in front of or surrounding the
air conditioner in a way that may
block air flow.
AVOID:
G direct sunlight.
G nearby heat sources that may affect performance of the
unit.
G areas where leakage of flammable gas may be expected.
Fig. 1
For wall-mounted units
G placing or allowing any obstructions near the air conditioner
inlet or outlet.
G installing in rooms that contain instant-on (rapid-start)
fluorescent lamps.(These may prevent the air conditioner
from receiving signals.)
G places where large amounts of oil mist exist.
G installing in locations where there are devices that
generate high-frequency emissions.
DO:
G select an appropriate position from which every corner of
the room can be uniformly air-conditioned. (High on a wall
is best for wall-mounted types.)
G select a location that will hold the weight of the unit.
G select a location where tubing and drain hose have the
shortest run to the outside. (Fig.1)
G allow room for operation and maintenance as well as
unrestricted air flow around the unit. (Fig. 2a or 2b)
G install the unit within the maximum elevation difference
(H1, H2, H3, H4) above or below the outdoor unit and
within a total tubing length (L1+L2+L3, L1+L2+L3+L4)
from the outdoor unit as detailed in Table 3 and Fig.3a.
Fig. 3a
2" (5 cm)
min.
For ceiling-mounted cassette units
• Air delivery from a ceilingmounted cassette unit will
be degraded if the distance
from the floor to the ceiling
is greater than 10 ft. (3 m).
• For stable operation of the
air conditioner,do not install
wall-mounted units less
than 5' (1.5 m) from floor
level. (Fig. 3b)
4
6" (15 cm)
min.
Front View
Fig. 2a
Fig. 2b
Minimum height
from floor level
Fig. 3b
2" (5 cm)
Indoor unit
5' (1.5 m)
Floor level
min.
Wall
Page 93
G install the indoor unit more than 3.3' (1 m) aw a y from an y
antenna or power lines or connecting wires used for television, radio, telephone, security system, or intercom.
Electrical noise from any of these sources may affect
operation.
G install in a sturdy manner to avoid increased operating
noise.
Table 3
Max.Max. Allowable Total Limit of Limit of ElevationRequired Amount
* If total tubing length becomes 150 to 200 ft. (Max.) or 150 to 230 ft. (Max.), charge additional refrigerant (R410A) by 0.22 oz./ft.
No additional charge of compressor oil is necessary.For more detailed charging information, refer to the Technical & Service Manual.
AllowableTubing Length Total Tubing LengthDifference of Additional
per unit(L1+L2+L3) or (L1+L2+L3+L4)(ft.)(oz./ft.)*
(ft.)(L1+L2+L3+L4)(ft.)
(ft.)
5
Page 94
Union 1/2"(12.70mm)
1/2"(12.70
mm
)
Flare 3/8"(9.52
mm
)
A joint for connecting tubes of
different sizes
(3/8"(9.52mm) 1/2"(12.70mm)) Supplied Reducer
1/4"(6.35mm)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
C
B
A
Outdoor unitIndoor unit
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
(KMHS1872)
(XHS1872)
3/8"(9.52mm)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
C
B
A
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
D
Outdoor unitIndoor unit
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
Union 3/8"(9.52mm)Flare 1/2"(12.70mm)
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
1/2"(12.70mm)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
(1/2"(12.70
mm
) 3/8"(9.52mm)) Supplied Reducer
3/8"(9.52mm)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52mm)
3/8"(9.52
mm
)
C
B
A
Outdoor unitIndoor unit
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
2-2. Connecting Indoor Units
Figures (4a) – (4k) show the different types of indoor unit connections, including the use of a reducer.
To select the required indoor unit to be connected, refer to the Combination Table that was included in the
outdoor unit package.
(1) Connecting indoor unit for CMH1972A
(A)
Fig. 4a
(B)
(2) Connecting indoor unit for CMH2472A
(A)
Fig. 4b
Fig. 4c
6
Page 95
(B)
C
B
A
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
D
Outdoor unitIndoor unit
(KMHS1872)
(XHS1872)
1/2"(12.70mm)
1/2"(12.70
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
Locally purchased
C
B
(KMHS1872)
(XHS1872)
D
Outdoor unitIndoor unit
Union 1/2"(12.70
mm
)Flare 3/8"(9.52mm)
(3/8"(9.52
mm
) 1/2"(12.70mm))
1/2"(12.70mm)
3/8"(9.52
mm
)
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
A
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
(KMHS1872)
(XHS1872)
1/2"(12.70
mm
)
1/2"(12.70
mm
)
1/4"(6.35
mm
)
Union 5/8"(15.88mm)Flare 1/2"(12.70mm)
(1/2"(12.70
mm
) 5/8"(15.88mm)) Locally purchased
C
B
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
D
Outdoor unitIndoor unit
(KMHS2472)
1/2"(12.70mm)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
5/8"(15.88
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
A
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
(C)
Fig. 4d
(D)
Fig. 4e
Fig. 4f
7
Page 96
Union 3/8"(9.52mm)Flare 1/2"(12.70mm)
(1/2"(12.70
mm
) 3/8"(9.52mm)) Supplied Reducer
D
C
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
Outdoor unitIndoor unit
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
1/2"(12.70mm)
1/2"(12.70
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
A
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
B
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
(3) Connecting indoor unit for CMH3172A
Union 3/8"(9.52mm)Flare 1/2"(12.70mm)
(1/2"(12.70
mm
3/8"(9.52mm)) Supplied Reducer
A
Outdoor unitIndoor unit
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
3/8"(9.52mm)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
B
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
C
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
1/2"(12.70
mm
)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
D
(KMHS1872)
(XHS1872)
1/2"(12.70
mm
)
1/2"(12.70
mm
)
1/4"(6.35
mm
)
A
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
B
Outdoor unitIndoor unit
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
D
C
(KMHS1872)
(XHS1872)
(KMHS1872)
(XHS1872)
1/2"(12.70
mm
)
1/2"(12.70
mm
)
1/2"(12.70
mm
)
1/2"(12.70
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
(A)
(B)
Fig. 4g
(C)
Fig. 4h
Fig. 4i
8
Page 97
(D)
Union 5/8"(15.88mm)Flare 1/2"(12.70mm)
(1/2"(12.70
mm
) 5/8"(15.88mm))Locally purchased
C
D
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
Outdoor unitIndoor unit
(KMHS2472)
Union 3/8"(9.52mm)Flare 1/2"(12.70mm)
(1/2"(12.70
mm
) 3/8"(9.52mm))Supplied Reducer
1/2"(12.70mm)
1/2"(12.70
mm
)
5/8"(15.88
mm
)
3/8"(9.52
mm
)
A
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
B
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
Union 5/8"(15.88mm)Flare 1/2"(12.70mm)
(1/2"(12.70
mm
) 5/8"(15.88mm)) Locally purchased
B
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
A
Outdoor unitIndoor unit
(KMHS0772,KMHS0972,KMHS1272)
(XMHS0972,XMHS1272)
3/8"(9.52mm)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
C
(KMHS1872)
(XHS1872)
1/2"(12.70
mm
)
1/2"(12.70
mm
)
1/4"(6.35
mm
)
D
(KMHS2472)
1/2"(12.70
mm
)
5/8"(15.88
mm
)
1/4"(6.35
mm
)
(E)
Fig. 4j
Fig. 4k
9
Page 98
2-3. Outdoor Unit
NOTE
Outdoor unit
Hot air
Heat source
Exhaust fan
NO
Min.
7' (2 m)
Min.
7' (2 m)
Ground
Obstacle
Obstacle above
Air discharge
Min. 8" (20 cm)
Air intake
CAUTION
AVOID:
G heat sources, exhaust fans, etc.(Fig. 5a)
G damp, humid or uneven locations.
DO:
G choose a place as cool as possible.
G choose a place that is well ventilated.
G install in a location where at least two sides are unob-
structed, so that the flow of air at the intake port or
exhaust port is not blocked, and so that sufficient
space is ensured for maintenance to be carried out
without trouble.In general the top also must be unobstructed. (Fig. 5b)
G provide a solid base (level concrete pad, concrete block,
6" × 1'4" (15 × 40 cm) beams or equal), a minimum of 6"
(15 cm) above ground level to reduce humidity and
protect the unit against possible water damage and
decreased service life.(Figs. 5c and 5d)
Fig. 5a
Air intakeMin. 8" (20 cm)
Min.
4" (10 cm)
Air discharge
Valve
side
Min. 10"
(25 cm)
Min.
1’8" (50 cm)
Fig. 5b
Drain holes
A solid base must not cover
the hole of the bottom plate.
G install cushion rubber under unit’s feet to reduce vibration
and noise.(Fig. 5e)
G use lug bolts or equal to bolt down unit, reducing vibration
and noise.
G install in a location where no antenna of a television or
radio exists within 10' (3 m).
2-4. Baffle Plate for the Outdoor Unit
It is recommended to use baffle plates.
When the outdoor unit is installed in a position exposed to
strong wind (such as seasonal winds with low air temperature in winter), baffle plates must be installed on the outdoor
unit. (Fig. 5f)
This unit is designed so that the fan of the outdoor unit runs
at low speed when the air conditioner is operated at low
outdoor air temperatures.When the outdoor unit is exposed
to strong wind, the system pressure drops because of the
freeze protector.
Install a pair of windbaffle plates at the front and back of the
outdoor unit if it will be subject to strong wind during the
winter.(Figs. 5f, 5g, 5h, 5i, and 5j)
2. Remove the panel side L, and drill 3 holes of ø1/4 inch
(6.5 mm) at the prescribed position.
3. Install the windbaffle on the unit using field supply bolts
and nuts.
4. Recommended bolts to be used are 15/64" (M6 ISO
standard), and the recommended length of the bolts is
between 19/32 – 25/32 inch (15 – 20 mm).
5. Use washers and spring washers to tightly fasten the
windbaffle to the unit.
(2) Right side
1. Remove the top panel from the unit.
2. Use 2 preholes on the panel side R to install the baffle
plate.
3. Remove the panel side R from the unit by removing the
screws.These screws are used in step 4 below.
4. Put (sandwich) the windbaffle between the unit and the
panel side R, then install the windbaffle on the unit using
the above screws. Be careful not to damage the screw
holes.
2. Air Discharge Baffle
1. Remove the panels front, top, side L and R from the
unit and drill 4 holes of ø1/4 inch (6.5 mm) at the
prescribed positions.
2. Install the windbaffle on the unit using field supply
bolts and nuts.
3. Recommended bolts to be used are 15/64" (M6 ISO
standard), and the recommended length of the bolts
is between 13/32 – 19/32 inch (10 – 15 mm).
4. Use washers and spring washers to tightly fasten the
windbaffle to the unit.
Fig. 5iFig. 5j
NOTE
G In order to prevent contact of the bolts and heat exchanger and other parts inside the unit, install the windbaffle using
bolts from inside the unit and fasten the bolts with nuts from outside the unit.
G When the windbaffle is installed on the unit, the unit has higher wind resistance. In order to prevent the unit from
falling over, anchor the legs of the unit using anchor bolts (or similar method).
(4) Precautions for installation
1. Be sure not to damage painted surfaces.
2. Finish the edges of the windbaffle to avoid cuts or injury.
3. Drilling of holes must be carefully done so that no damage is caused to external or internal parts of the unit.
Particular care must be taken that drill chips do not drop into the unit.
12
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.