Samsung MIM-D00A User Manual

Data Management Server2

MIM-D00A

BACnet Gateway

MIM-B17

LonWorks Gateway

MIM-B18

Air Conditioner

user manual

imagine the possibilities

Thank you for purchasing this Samsung product.

E DB98-33388A(1)

Safety Precautions

Before using the DMS2, read carefully these instructions.

After reading the instructions, keep this user's manual in a handy and safe place. If a user is changed, you must hand over the manuals.

Never attempt to install the air conditioning system or to move the DMS2 by yourself.

WARNING

CAUTION

Do not attempt to install or repair this DMS2 by yourself.

This DMS2 contains no user-serviceable parts.

Always consult authorized service personnel for repairs.

When moving, consult authorized service personnel for disconnection and installation of the DMS2.

Ensure that the wall is strong enough to support the weight of the DMS2.

Must install the DMS2 with rated power supply.

In the event of a malfunction (burning smell, etc.), immediately stop operation, turn off the electrical breaker, and consult authorized service personnel.

Do not use inflammable gases near the DMS2.

Do not spill water into the DMS2.

Do not operate the DMS2 with wet hands.

Do not install the DMS2 in a location where it will come into contact with the combustible gases, machine oil, sulphide gas, etc.

Do not press buttons with a pointed thing.

Do not pull or bend the DMS2 cable excessively.

Do not use this DMS2 for other purpose.

Do not spray an insecticide or other combustible things on the DMS2.

Do not clean the DMS2 with benzene, solvents or other chemicals.

Do not give a shock to the DMS2 or disassemble it by yourself.

E-2

Contents

 

General Description ........................................................

4

Viewing the Parts ............................................................

6

Before Use ......................................................................

8

Main Function ..............................................................

10

Starting DMS2 ............................................................

14

Control and Monitoring .............................................

18

Zone Management ........................................................

59

Schedule ......................................................................

64

EHP Power Consumption Inspection ............................

74

Control Logic Management .........................................

85

System Settings ............................................................

98

Check Before using Panel ...........................................

147

Setting Network Information ....................................

148

Checking Indoor/Outdoor Unit Information .............

150

Checking DMS2 Version ............................................

151

Data Backup Setting ..................................................

154

Checking Error Information ......................................

156

Reset Password ..........................................................

157

Button Lock ...............................................................

158

Safety Halt ................................................................

159

Troubleshooting ........................................................

160

Specifications .............................................................

162

License ........................................................................

163

Note The contents and pictures used in this user manual may be changed without advance notice for the functional reinforcement and improvement of a product.

E-3

General Description

Introduction of DMS2 (Data Management Server2)

The DMS2 is an Internet based device for central management of Samsung system air-conditioners. It supports LAN & WAN and operates 24 hours without a separate PC.

Advantages of DMS2 System

The DMS2 provides the following advantages:

Everyday Device–The DMS2 is operational all year long 24 hours.

Independent Operation–The DMS2 can operate schedule control and power distribution without a PC.

Note In order to run power distribution, relevant controllers need to be installed.

Internet Control

Web – The DMS2 has a built-in web server function and can be accessed from a remote location to operate status

monitoring, control, trouble history, and schedule setting of the system air-conditioners.

Using an Upper Level Controller–When a separate upper level controller (S-NET series) is used, a number of DMS2 can be controlled with one central management system.

Data Storage–The DMS2 has its own database built-in, therefore, trouble history, indoor unit installation information, and power distribution data can be saved and retrieved.

Large Scale Management–At most 256 indoor units can be connected to one DMS2 and therefore, only one DMS2 can manage small and medium size buildings.

Automatic ”e-mail” sending–When an error is occurred, inform the error details to an e-mail saved on DMS2.

E-4

Terms

DMS2: The abbreviation of Data Management Server2.

Upper Controller: It means S-NET Series, a local controller of the DVM system.

S-NET 3, S-NET mini and RMS are linked to a DMS2.

Centralized Controller: A device that controls 16 groups of the DVM air conditioner. A central control device of a DVM system which is located between a DMS2 and an outdoor unit interface module.

Interface module: A data interface module of a DVM system which is located between a central controller and an outdoor unit.

AHU(Air Handling Unit): Excutes heat exchange between air and cooling unit using central air conditioning duct method.

ERV(Energy Recovery Ventilator): Ventilating system using heat recovery function.

E-5

Viewing the Parts

Front View

No.

Name

Description

 

 

 

LCD Display

Display current time/ Check menu

 

 

 

 

Menu button

Access to main menu

 

 

 

▼/▲button

Select the function you want and set detailed functions in

main menu

 

Set button

Check the function you want from main menu

 

and select it

 

 

Bottom cover

Unfasten 2 screws on the bottom and separate the bottom

cover from DMS2. Then check cable connection part.

 

 

Indicator

Name

Description

 

 

Power

Turns blue when the power is supplied.

 

 

CPU Alive

Blinks in orange with 1 second intervals during normal

operation.

 

 

 

Ethernet–Linked

Turns green during normal connection.

 

 

Ethernet–Active

Blinks in orange during normal transmission/reception.

 

 

COM1~5 – TX

Blinks in green during normal transmission.

 

 

COM1~5 – RX

Blinks in green during normal reception.

 

 

Check

Turns green when notice occurs.

 

 

E-6

Bottom View

Separate bottom cover by unfastening 2 screws on the bottom.

DI Terminal2

 

 

 

 

 

DO Terminal1

 

 

 

 

 

Connect Digital Input

 

 

 

 

Connect Digital Output

- Channel 6~Channel10

 

 

 

 

- Channel 1~Channel 5

DI Terminal1

 

 

 

 

 

 

DO Terminal 2

 

 

 

 

 

 

Connect Digital Input

 

 

 

 

Connect Digital Output

- Channel 1~Channel 5

 

 

 

 

- Channel 6~Channel 10

 

RS485

 

Communication

Power

terminal

Terminal

Connect for RS485

Connect

communication

DMS2 adapter

with devices such as

 

centralized controller/

Reset Button

interface module

- COM1 ~ COM5

Reset DMS2

Serial Terminal

 

 

 

 

 

 

Cable tie groove

 

 

 

 

 

 

 

 

 

 

 

Arrange cables connected to

 

 

 

Service agent checks error

 

DMS2

status

 

 

LAN Terminal

 

 

SD Card Socket

 

 

 

 

 

Connect LAN cable

 

 

 

 

Socket for sub memory (SD or MMC)

(Sub memory is for DMS2 program update and set information saving)

PurchaseSDcardseparately.

E-7

Before Use

System Configuration

S-NETmini

S-NET3

 

Internet

 

DMS2

 

 

Centralized controller

Interfacemodule

Interfacemodule

 

Interfacemodule

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connecting centralized controller and DMS2 ( type )

You can control up to 16 centralized controllers and 256 indoor units using DMS2.

Connecting interface module and DMS2 ( type)

-You can control up to 80 interface modules and 256 indoor units using DMS2.

16 interface modules can be connected to RS485 communication channel of DMS2. - The more interface modules are connected, the longer time takes for tracking.

E-8

When connecting centralized controller and interface module to the DMS2 of same communication channel, only one of them will communicate according to the communication channel mode setting of [System Settings][Tracking].

Therefore, do not connect the centralized controller and interface module to the same communication channel.

If you set the communication channel mode as interface module, virtual centralized controller address will be assigned. Therefore if you connect centralized controller at the same time and set the address as virtual centralized controller address, it may cause trouble for bringing device information.

Channel 0: Virtual centralized controller 11,

Channel 1: Virtual centralized controller 12,

Channel 2: Virtual centralized controller 13,

Channel 4: Virtual centralized controller 14,

Channel 5: Virtual centralized controller 15

Web Browser Specification

Install Windows XP SP2, Windows 2000 SP4 or later version

Install Internet Explorer 7.0 or later version

You can use Internet Explorer 6.0 but it is not recommended. Install Silverlight 2.0 or later version

Note Visit internet homepage (http://www.microsoft. com/silverlight/) to download Silverlight. Or you can download it through the download link which is noticed automatically when the PC is connected to the Internet and you access to DMS2 for the first time.

Silverlight operates normally with Windows XP SP2 or later version.

It may not operate normally with former version of Windows.

Computer Settings for DMS2 Connection

All settings of DMS2 will be arranged in web page which built in DMS2.

You should access to DMS2 IP to use DMS2 web page. There are 2 ways to access DMS2 IP.

(For about settings, refer to installation manual.)

Static IP setting

E-9

Dynamic IP(DHCP) setting

Main Function

Interface with Upper Level Controller

The DMS2 receives/manages setting and control data from the upper level controller and sends the received data to the lower level system.

The upper level controllers of the DMS2 are the S-NET series and the connectible S-NET series are S-NET 3, S-NET mini and RMS.

S-NET 3: System air conditioner controlling and monitoring program that is used by installing on a PC.

S-NET mini: System air conditioner controlling and monitoring

device with touchscreen

RMS: A device which supervises operation status and break down status by connecting to DMS2 for system air conditioner remote service. If break down is detected, it notifies service agent and makes fast service possible.

Save Trouble History

The DMS2 saves at most 1024 cases of trouble history.

If the number of errors exceeds 1024, only the latest 1024 cases are stored by deleting the oldest trouble history.

Device name, address, error occurrence time, error solvation time, trouble history will be saved. You can check it in web page or upper controller.

When an error occurs, it sends trouble history to e-mail saved in DMS2.

Device

Type

 

 

 

Indoor unit communication error

Indoor Unit

Indoor unit sensor related error

 

Other errors

 

 

 

Outdoor unit communication error

Outdoor Unit

Pipe inspection error

Outdoor unit sensor related error

 

 

Outdoor unit related other errors

 

 

Communication error

Option device related communication

such as centralized controller

error

 

 

E-10

Set and Run Schedule

The schedule function of the DMS2 can be set through the Web or using the upper level controller. 1day/Everyday/Every week schedules can be set.

Each schedule can be used selectively by using the run schedule/stop schedule order.

At most 256 schedules can be set.

Indoor unit control is possible at least 1 minute of interval by set schedule.

 

 

 

 

 

Item

Content

 

Remark

 

 

 

 

 

 

Schedule Period

Starting and ending date of a schedule

 

 

 

 

 

 

 

 

Exception Day

Set an exception day within a schedule

period to

 

 

Setup

ignore the schedule control

 

 

 

 

 

 

 

 

Devices to

Select devices to receive schedule control

 

 

be applied

 

 

 

 

 

 

 

 

 

 

 

Set indoor unit operation modes

 

 

 

- Device On time

 

 

 

- Device Off time

Weekly Repeat:

 

 

- Desired temperature

 

 

Maximum 10 events

 

 

- Operation mode: Auto/Cool/Dry/Fan/Heat/Off

 

Event

- Remote control usage Enable RC/ Disable RC/

per day

 

 

Cond.RC

Daily Repeat:

 

 

- Fan speed: Auto/Low/Mid/High

Maximum 70 events

 

 

- Air flow: None/Vertical/Horizontal/All

 

 

 

 

 

- ERV operation mode: Auto/HeatEx/ByPass/Sleep

 

 

 

- ERV Fan speed: Low/High/Turbo

 

 

 

 

 

 

 

E-11

Main Function (Continued)

Save Integrated Power Distribution Data

The DMS2 calculates and distributes the power consumed by each indoor unit by receiving the total power usage from the watt-hour meter interface modules (SIM/PIM) and taking into account the operation status of the indoor units.

The DMS2 saves at most 1 year of data. After a year, the oldest data is deleted and the latest data is saved. This data can be checked through the built-in Web page of the DMS2 or by S-NET 3.

System Architecture

S-NET3

Internet

WebClient

 

DMS2

Upto 8units

Centralizedcontroller

SIM/PIM

SIM/PIM

 

Upto

Upto

 

8units

8units

 

Watt-hourmeter

Watt-hourmeter

E-12

Time Segmentation

Time segmentation is used to divide 24 hours into different sections and to distribute power according to each section.

This function is used when the power consumption fee is different according to different time slots or when a building is charged differently depending on the consumption time.

1 section (A) is set as 24hours, and the factory default setting is set as 1 section. The time, 24hours, can also be divided into 2 sections (A,B,A), 3 sections (A,B,C,A) or 4 sections (A,B,C,D,A)

DMS2 shows the result of the power distribution for each section you set.

Inputmanually(Whensetting2sections,3sections,and4sections)

If communication error occurs between DMS and the lower level controllers, actual power consumption and the result of power distribution value may not be same. Make sure to solve communication error status.

- Communication error example : Between DMS2 and SIM/PIM

Between SIM/PIM and Watt-hour meter Between DMS2 and Centralized controller Between Centralized controller and interface module

Between Interface module and indoor/outdoor units Between DMS2 and interface module

E-13

Starting DMS2

Starting DMS2

Current time setting

Set the current time of DMS2 system.

“2009/01/01 01:01:01” is factory setting. Set the current time as DMS2 system time. You can set DMS2 time in [System Settings] [System environment setting] (Refer to page 118~119)

If DMS2 time does not set as the current time, DMS2 may cause malfunction when using Schedule or control logic management.

Connecting centralized controller & interface module

(1)Make sure that centralized controller communication cables(C1, C2) or interface module communication cables(R1, R2) are connected.

For communication between DMS2 and centralized controller/interface module, centralized controller communication cable(C1, C2) or interface module communication cable(R1, R2) should be connected.

(2)Execute tracking.

DMS2 communicates with centralized controller and interface module and brings information about installed indoor unit and outdoor unit.

After tracking, you can use indoor unit control and other menu.

For tracking, refer to [System Settings] [Tracking] (Refer to page 134~144)

E-14

Access to DMS2 & Login

Address bar

3

1Run internet explorer on your computer.

2Enter IP address (http://192.168.0.100) on the address bar, and then press [ENTER].

If it is the first access to DMS2, “Install Microsoft Silverlight” message will be displayed.

-The message will not appear if Microsoft Silverlight have already installed.

If the message window and login screen does not appear, check PC setting status.

3Click [Run] and continue installation.

Access to DMS2 again after installation.

E-15

Starting DMS2 (Continued)

4

4Enter ID and password when DMS2 main web page appears. Then click [LOGIN].

The default DMS2 user ID is 'admin' and password is '1234'.

Depending on authorization settings which set by the administrator, access to some functions may be restricted.

To edit user authorization, refer to [System Settings][User authorization management]. (Refer to page 101)

Note Only authorized users can access to web page.

Fewer than 5 concurrent users are recommended because connection speed may slow down.

DMS2 manager should change ID and password for security and management. (Refer to page 99)

Logout: To log out, click [LOGOUT] on the top of the menu.

Silverlight will run normally with Windows XP SP2 or later version. With former version of Windows, DMS2 may not operate normally.

E-16

Logged-in User with No Authorization

1When the screen above appears, ask for manager.

Depending on control authorization setting, there can be a user who does not have control authorization.

Above screen will appear when the logged-in user does not have control authorization.

E-17

Control and Monitoring

Devices controlled and monitored by DMS2

Type

Display

Remotecontroller

Type

Display

Remotecontroller

(Controllingrange)

(Controllingrange)

 

 

 

 

 

 

 

 

 

 

 

 

 

Fresh duct

 

 

Indoor unit

 

 

display icon

 

 

 

 

 

 

 

display icon

 

 

 

 

 

 

 

 

Global 4 way

 

 

 

 

 

 

 

ERV

 

 

display icon

 

 

 

 

 

 

 

display icon

 

 

 

 

 

 

 

 

 

 

 

AHU

 

 

DI

 

 

 

 

(Digital Input)

 

 

display icon

 

 

 

 

 

 

display icon

 

 

 

 

 

 

 

 

 

 

 

 

 

ERV PLUS

 

 

DO

 

 

 

 

(Digital Output)

 

 

display icon

 

 

 

 

 

 

display icon

 

 

 

 

 

 

 

 

 

 

 

 

 

DMS2 can control and monitor the devices in the above table.

When users select multiple devices, 'Basic Control' will be displayed on the screen. (This is when different types of multiple devices are selected.)

E-18

Samsung MIM-D00A User Manual

Monitoring Indoor Unit Operation Status

1

2

1Click [Control and Monitoring] when DMS2 web page menu screen appears.

[Control and Monitoring] screen will appear when you log-in to DMS2 web page.

2Check the current status of all devices.

You can check the current controlling status of all installed indoor units, ERV, AHU, ERV PLUS, Fresh duct, Global 4 Way, and other devices.

Note When the advanced functions (such as Sleep mode, Energy saving function) are selected through wired/wireless remote controllers or indoor unit panel,

set operation mode on the remote controllers and DMS2 may be displayed differently. Also, when controlling by DMS2, additional functions will be canceled.

Depending on the model of indoor unit, Horizontal/All air flow direction control may not be possible. In this case, vertical or fixed flow will be displayed depending on indoor unit’s basic operation specification.

AHU, ERV, ERV PLUS, Global 4 Way, Fresh duct, Lighting, and other devices will be displayed only when the corresponding devices are installed.

Some functions available on DMS2 webpage may not be functional at BACnet Gateway and LonWorks Gateway. For detailed function, refer to the installation manual or contact Samsung Electronics.

E-19

Control and Monitoring (Continued)

Controlling an Indoor Unit

1

Statusdisplaywindow

2

3

1Click [Control and Monitoring] when DMS2 web page menu screen appears.

[Control and Monitoring] screen will appear when you log-in to DMS2 web page.

2Select an indoor unit to control.

Check the indoor unit status through status display window.

When the selected indoor unit is switched on, the remote controller panel will be automatically activated.

3Turn the indoor unit on by clicking [].

Remote controller panel will be activated.

E-20

5 4 6

4Select the operation mode.

You can select Auto, Cool, Dry, Fan and Heat operation mode.

5Click [][] to set the desired temperature.

Each time you click the buttons, the temperature will be adjusted by 1 (1°F).

If Auto/Cool/Dry mode is in operation, you can adjust the desired temperature in the range of 18 (65°F)~30 (86°F).

If Heat mode is in operation, you can adjust the desired temperature in the range of 16 (61°F)~30 (86°F).

You cannot adjust the desired temperature in Fan mode.

When the operation mode of an indoor unit is Cool or Dry mode, you cannot set the desired temperature lower than lower limit temperature if lower limit is enabled.

When the operation mode of indoor unit is Heat mode, you cannot set the desired temperature higher than upper limit temperature if upper limit is enabled.

6Select the fan speed.

You can select Auto, Low, Mid and High.

If Auto/Dry mode is in operation, fan speed will be set as Auto fan speed.

If Fan mode is in operation, you cannot select Auto fan speed.

E-21

Control and Monitoring (Continued)

8

7

7Select the air flow.

You can select Vertical, Horizontal, All and None air flow direction.

8Set remote controller settings.

You can select Enable RC, Disable RC, and Cond. RC.

When selecting [Disable RC], indoor unit control by wired/wireless remote controller and indoor unit panel is not possible. Indoor unit control is only available in

DMS2 web page.

Click [] when you want to use wired remote controller in each room.

Note When filter warning sign is displayed on indoor unit status window

Select the indoor unit and click [Reset filter]. Filter warning will be released.

Make sure that each indoor unit must be turned on to control.

Selecting remote controller, reset filter, operation mode limits, setting lower/upper temperature limit are possible even if the power of indoor unit is off.

Some air flow direction option may be restricted depending on the indoor unit model.

E-22

Indoor Unit Operation Mode Limit

1

Statusdisplaywindow

2

You can monitor the operation status of all indoor units or have individual or whole control of the indoor units.

1 Click [Control and Monitoring] when DMS2 web page menu screen appears.

[Control and Monitoring] screen will appear when you log-in to DMS2 web page.

2 Select an indoor unit to control.

Check the indoor unit status through status display window.

When the selected indoor unit is switched on, the remote controller panel will be automatically activated.

E-23

Control and Monitoring (Continued)

3

3Set operation mode limit.

You can select 'Cool only(Fan, Cool)’, ‘Heat only(Fan, Heat)’ and ‘No limits’.

- Cool only (Fan, Cool) : If cool only indoor unit operates in Heat mode, reset the indoor unit as set operation mode.

- Heat only (Fan, Heat) : If heat only indoor unit operates in cool mode, reset the indoor unit as set operation mode.

-No limits : You can use cool only and heat only with no limits.

-e.g : If the 'cool only fan' indoor unit operates in heating mode, DMS2 will detect it and reset the indoor unit in Fan mode.

Note Operation mode limits setting is not available in ERV.

ERV Plus doesn’t operate Fan mode, it only operates cool mode in ‘cool only’.

ERV Plus doesn’t operate Fan mode, it only operates heat mode in ‘heat only’.

Mixed operation can occur regardless of operation mode limits setting.

If indoor unit with operation mode limit is in mixed operation, DMS2 solves mixed operation status automatically by controlling the indoor unit in set operation mode.

E-24

In the following circumstances, all indoor units under the same outdoor unit should be set to the same operation mode limits. Mixed operation can occur continuously when you set some of indoor unit to cool only and the other to heat only.

-If the centralized controller is MCM-A202 and is in group mode

-If the centralized controller is in group mode and the interface module is MIM-B13 or MIM-B04A

Except above circumstances, DMS2 changes the operation mode limit of all indoor units under the same outdoor unit to same operation mode limit.

-If the centralized controller is in group mode and is above MCM-A202A and all the interface modules under the centralized controller are above MIM-B13A

-If the centralized controller is in individual mode

If you set the cooling only indoor unit’s operation mode limit to heating only, DMS2 may display Heating Cooling alternately.

E-25

Control and Monitoring (Continued)

Setting Lower/Upper Temperature Limit of an Indoor Unit

1

Statusdisplaywindow

2

You can monitor the operation status of all indoor units, and control the indoor units as a whole, or as individual units.

1Click [Control and Monitoring] when DMS2 web page menu screen appears.

[Control and Monitoring] screen will appear when you log-in to DMS2 web page.

2Select an indoor unit to control.

Check the indoor unit status through status display window.

When the selected indoor unit is switched on, the remote controller panel will be automatically activated.

E-26

3

4

3Set upper temperature limit by pressing [] and [].

Click 'Heat upper limit' to apply the upper temperature limit setting.

When indoor unit is operating in heat mode, DMS2 controls indoor unit as upper temperature limit if the desired temperature is higher than upper temperature limit.

Upper temperature limit can be set in the range of 16°C(61°F)~30°C(86°F).

When an indoor unit is operating in Heat mode and the upper temperature limit is applied, you cannot set the desired temperature higher than the upper temperature limit.

4Set lower temperature limit by pressing [] and [].

You can set lower temperature limit by clicking 'Cool lower limit'.

When indoor unit is operating in cool mode, DMS2 controls indoor unit as lower temperature limit if the desired temperature is lower than lower temperature limit.

Lower temperature limit can be set in the range of 18°C(65°F)~30°C(86°F).

When indoor unit is operating in Cool or Dry mode and the low temperature limit is applied, you cannot set the desired temperature lower than the lower temperature limit.

Note You cannot set the lower and upper temperature limit of ERV, ERV PLUS, and Fresh duct.

E-27

Control and Monitoring (Continued)

Monitoring the operation status of Global 4 Way

1

Statusdisplaywindow

2

You can monitor the operation status of Global 4 Way, and control Global 4 Way as a whole, or as individual units.

1Click [Control and Monitoring] when DMS2 web page menu screen appears.

[Control and Monitoring] screen will appear when you log-in to DMS2 web page.

2Check the current status of Global 4 Way.

Check the status of Global 4 Way through the status display window.

When the selected Global 4 way is switched on,

the remote controller panel will be automatically activated.

E-28

Controlling Global 4Way

1

3 2

1Click [Control and Monitoring] when DMS2 web page menu screen appears.

[Control and Monitoring] screen will appear when you log-in to DMS2 web page.

2Check the current status of Global 4 Way.

Check the status of Global 4 Way through the status display window.

When the selected Global 4 way is switched on, the remote controller panel will be automatically activated.

3 Turn the Global 4way on by clicking [].

Remote controller panel will be activated.

E-29

Control and Monitoring (Continued)

 

4

6

5

4Select SPI setting.

You can set SPI through button activation / non activation.

5Select Human Sensor setting .

You can set Human Sensor through button activation / non activation.

6Select Auto Clean setting.

You can set Auto cleaning through button activation / non activation.

Note SPI, Human Sensor, and Auto Clean will work only when the corresponding options are installed and their normal operation is guaranteed when the centralized controller is above MCM-A202D and Interface module is MIM-B13D.

Refer to the ‘Controlling an indoor unit’ for Global 4 Way control. (Page 20~22)

Refer to the ‘Indoor unit operation mode limit’ for Global 4 Way operation mode limit. (Page 23~25)

Refer to the ‘Setting lower/upper temperature Limit of an Indoor Unit’ for setting lower or upper temperature limit of Global 4 Way. (Page 26~27)

E-30

Loading...
+ 170 hidden pages