The contents and pictures used in this user manual
may be changed without advance notice for the
functional reinforcement and improvement of a
product.
E-3
General Description
Introduction of DMS2 (Data Management Server2)
The DMS2 is an Internet based device for central management of Samsung system
air-conditioners. It supports LAN & WAN and operates 24 hours without a separate PC.
Advantages of DMS2 System
The DMS2 provides the following advantages:
Everyday Device–The DMS2 is operational all year long 24 hours.
Independent Operation–The DMS2 can operate schedule control and power distribution
without a PC.
Note In order to run power distribution, relevant controllers need to be installed.
Internet Control
Web – The DMS2 has a built-in web server function and can be accessed from a
remote location to operate status
monitoring, control, trouble history, and schedule setting of the system
air-conditioners.
Using an Upper Level Controller–When a separate upper level controller (S-NET
series) is used, a number of DMS2 can be controlled with one central management
system.
Data Storage–The DMS2 has its own database built-in, therefore, trouble history,
indoor unit installation information, and power distribution data can be saved and
retrieved.
Large Scale Management–At most 256 indoor units can be connected to one DMS2
and therefore, only one DMS2 can manage small and medium size buildings.
Automatic ”e-mail” sending–When an error is occurred, inform the error details to an
e-mail saved on DMS2.
E-4
Terms
DMS2: The abbreviation of Data Management Server2.
Upper Controller: It means S-NET Series, a local controller of the DVM system.
S-NET 3, S-NET mini and RMS are linked to a DMS2.
Centralized Controller: A device that controls 16 groups of the DVM air conditioner.
A central control device of a DVM system which is located
between a DMS2 and an outdoor unit interface module.
Interface module: A data interface module of a DVM system which is located between
a central controller and an outdoor unit.
AHU(Air Handling Unit): Excutes heat exchange between air and cooling unit using
central air conditioning duct method.
ERV(Energy Recovery Ventilator): Ventilating system using heat recovery function.
E-5
Viewing the Parts
Front View
No.Name Description
LCD DisplayDisplay current time/ Check menu
Menu buttonAccess to main menu
▼/▲ button
Set button
Bottom cover
Select the function you want and set detailed functions in
main menu
Check the function you want from main menu
and select it
Unfasten 2 screws on the bottom and separate the bottom
cover from DMS2. Then check cable connection part.
E-6
Indicator
NameDescription
PowerTurns blue when the power is supplied.
CPU Alive
Ethernet–LinkedTurns green during normal connection.
Ethernet–ActiveBlinks in orange during normal transmission/reception.
COM1~5 – TXBlinks in green during normal transmission.
COM1~5 – RXBlinks in green during normal reception.
CheckTurns green when notice occurs.
Blinks in orange with 1 second intervals during normal
operation.
Bottom View
Separate bottom cover by unfastening 2 screws on the bottom.
DI Terminal2
Connect Digital Input
- Channel 6~Channel10
DI Terminal1
Connect Digital Input
- Channel 1~Channel 5
Power
Terminal
Connect
DMS2 adapter
Reset Button
Reset DMS2
Serial Terminal
Service agent checks error
status
SD Card Socket
Socket for sub memory (SD or MMC)
( Sub memory is for DMS2 program update and set
information saving)
※ Purchase SD card separately.
DO Terminal1
Connect Digital Output
- Channel 1~Channel 5
DO Terminal 2
Connect Digital Output
- Channel 6~Channel 10
RS485
Communication
terminal
Connect for RS485
communication
with devices such as
centralized controller/
interface module
- COM1 ~ COM5
Cable tie groove
Arrange cables connected to
DMS2
LAN Terminal
Connect LAN cable
E-7
Before Use
System Configuration
S-NET mini
Centralized
controller
Interface module
S-NET 3
Internet
DMS2
ⓐⓑ
Interface module
Interface module
Connecting centralized controller and DMS2 (ⓐ type )
You can control up to 16 centralized controllers and 256 indoor units using DMS2.
Connecting interface module and DMS2 (ⓑ type)
- You can control up to 80 interface modules and 256 indoor units using DMS2.
※ 16 interface modules can be connected to RS485 communication channel of DMS2.
- The more interface modules are connected, the longer time takes for tracking.
E-8
When connecting centralized controller and interface module to the DMS2 of same
communication channel, only one of them will communicate according to the
communication channel mode setting of [System Settings][Tracking].
Therefore, do not connect the centralized controller and interface module to the same
communication channel.
If you set the communication channel mode as interface module, virtual centralized
controller address will be assigned. Therefore if you connect centralized controller
at the same time and set the address as virtual centralized controller address, it may
Install Windows XP SP2, Windows 2000 SP4 or later version
Install Internet Explorer 7.0 or later version
※ You can use Internet Explorer 6.0 but it is not recommended.
Install Silverlight 2.0 or later version
Note
Visit internet homepage (http://www.microsoft.
com/silverlight/) to download Silverlight. Or you can
download it through the download link which is noticed
automatically when the PC is connected to the Internet
and you access to DMS2 for the first time.
Silverlight operates normally with Windows XP SP2 or
later version.
It may not operate normally with former version of
Windows.
Computer Settings for DMS2 Connection
All settings of DMS2 will be arranged in web page which built in
DMS2.
You should access to DMS2 IP to use DMS2 web page.
There are 2 ways to access DMS2 IP.
(For about settings, refer to installation manual.)
Static IP setting
Dynamic IP(DHCP) setting
E-9
Main Function
Interface with Upper Level Controller
The DMS2 receives/manages setting and control data from the
upper level controller and sends the received data to the lower
level system.
The upper level controllers of the DMS2 are the S-NET series
and the connectible S-NET series are S-NET 3, S-NET mini and
RMS.
S-NET 3: System air conditioner controlling and monitoring
program that is used by installing on a PC.
S-NET mini: System air conditioner controlling and monitoring
device with touchscreen
RMS: A device which supervises operation status and break
down status by connecting to DMS2 for system air
conditioner remote service. If break down is detected,
it notifies service agent and makes fast service possible.
Save Trouble History
The DMS2 saves at most 1024 cases of trouble history.
If the number of errors exceeds 1024, only the latest 1024 cases
are stored by deleting the oldest trouble history.
Device name, address, error occurrence time, error solvation
time, trouble history will be saved. You can check it in web
page or upper controller.
When an error occurs, it sends trouble history to e-mail saved
in DMS2.
E-10
DeviceType
Indoor Unit
Outdoor Unit
Communication error
such as centralized controller
Indoor unit communication error
Indoor unit sensor related error
Other errors
Outdoor unit communication error
Pipe inspection error
Outdoor unit sensor related error
Outdoor unit related other errors
Option device related communication
error
Set and Run Schedule
The schedule function of the DMS2 can be set through the Web
or using the upper level controller. 1day/Everyday/Every week
schedules can be set.
Each schedule can be used selectively by using the run
schedule/stop schedule order.
At most 256 schedules can be set.
Indoor unit control is possible at least 1 minute of interval by
set schedule.
ItemContentRemark
Schedule PeriodStarting and ending date of a schedule
Exception Day
Setup
Devices to
be applied
Event
Set an exception day within a schedule period to
ignore the schedule control
Select devices to receive schedule control
Set indoor unit operation modes
- Device On time
- Device O time
- Desired temperature
- Operation mode: Auto/Cool/Dry/Fan/Heat/O
- Remote control usage Enable RC/ Disable RC/
Cond.RC
- Fan speed: Auto/Low/Mid/High
- Air ow: None/Vertical/Horizontal/All
- ERV operation mode: Auto/HeatEx/ByPass/Sleep
- ERV Fan speed: Low/High/Turbo
Weekly Repeat:
Maximum 10 events
per day
Daily Repeat:
Maximum 70 events
E-11
Main Function (Continued)
Save Integrated Power Distribution Data
The DMS2 calculates and distributes the power consumed by each indoor unit by
receiving the total power usage from the watt-hour meter interface modules (SIM/PIM)
and taking into account the operation status of the indoor units.
The DMS2 saves at most 1 year of data. After a year, the oldest data is deleted and
the latest data is saved. This data can be checked through the built-in Web page of
the DMS2 or by S-NET 3.
System Architecture
S-NET 3
Centralized controller
Watt-hour meter
DMS2
Up to
8 units
Internet
Web Client
Up to
8 units
SIM /PIM
Up to
8 units
Watt-hour meter
SIM /PIM
E-12
Time Segmentation
Time segmentation is used to divide 24 hours into different sections and to distribute
power according to each section.
This function is used when the power consumption fee is different according to
different time slots or when a building is charged differently depending on the
consumption time.
1 section (A) is set as 24hours, and the factory default setting is set as 1 section.
The time, 24hours, can also be divided into 2 sections (A,B,A), 3 sections (A,B,C,A) or
4 sections (A,B,C,D,A)
DMS2 shows the result of the power distribution for each section you set.
Input manually (When setting 2 sections, 3sections, and 4sections)
If communication error occurs between DMS and the lower level controllers,
actual power consumption and the result of power distribution value may not be
same. Make sure to solve communication error status.
- Communication error example : Between DMS2 and SIM/PIM
Between SIM/PIM and Watt-hour meter
Between DMS2 and Centralized controller
Between Centralized controller and interface
module
Between Interface module and indoor/outdoor
units Between DMS2 and interface module
E-13
Starting DMS2
Starting DMS2
Current time setting
Set the current time of DMS2 system.
“2009/01/01 01:01:01” is factory setting. Set the current time as DMS2 system time.
You can set DMS2 time in [System Settings] [System environment setting]
(Refer to page 118~119)
If DMS2 time does not set as the current time, DMS2 may cause malfunction when
using Schedule or control logic management.
(1) Make sure that centralized controller communication cables(C1, C2) or interface module
communication cables(R1, R2) are connected.
For communication between DMS2 and centralized controller/interface module,
centralized controller communication cable(C1, C2) or interface module
communication cable(R1, R2) should be connected.
(2) Execute tracking.
DMS2 communicates with centralized controller and interface module and
brings information about installed indoor unit and outdoor unit.
After tracking, you can use indoor unit control and other menu.
For tracking, refer to [System Settings] [Tracking] (Refer to page 134~144)
E-14
Access to DMS2 & Login
Address bar
Run internet explorer on your computer.
1
Enter IP address (http://192.168.0.100) on the address bar,
2
and then press [ENTER].
If it is the first access to DMS2, “Install Microsoft Silverlight”
message will be displayed.
- The message will not appear if Microsoft Silverlight have
already installed.
If the message window and login screen does not
appear, check PC setting status.
3
Click [Run] and continue installation.
3
Access to DMS2 again after installation.
E-15
Starting DMS2 (Continued)
4
E-16
Enter ID and password when DMS2 main web page appears.
4
Then click [LOGIN].
The default DMS2 user ID is 'admin' and password is '1234'.
Depending on authorization settings which set by the
administrator, access to some functions may be restricted.
To edit user authorization, refer to [System Settings]
[User authorization management]. (Refer to page 101)
Note
Only authorized users can access to web page.
Fewer than 5 concurrent users are recommended
DMS2 manager should change ID and password for
Logout: To log out, click [LOGOUT] on the top of the
because connection speed may slow down.
security and management. (Refer to page 99)
menu.
Silverlight will run normally with Windows XP SP2 or later
version. With former version of Windows, DMS2 may not
operate normally.
Logged-in User with No Authorization
When the screen above appears, ask for manager.
1
Depending on control authorization setting, there can be
a user who does not have control authorization.
Above screen will appear when the logged-in user does
not have control authorization.
E-17
Control and Monitoring
Devices controlled and monitored by DMS2
TypeDisplay
Indoor unit
display icon
ERV
display icon
AHU
display icon
ERV PLUS
display icon
Remote controller
(Controlling range)
TypeDisplay
Fresh duct
display icon
Global 4 way
display icon
DI
(Digital Input)
display icon
DO
(Digital Output)
display icon
Remote controller
(Controlling range)
DMS2 can control and monitor the devices in the above table.
When users select multiple devices, 'Basic Control' will be displayed on the screen.
(This is when different types of multiple devices are selected.)
E-18
Monitoring Indoor Unit Operation Status
1
2
Click [Control and Monitoring] when DMS2 web page menu screen appears.
1
[Control and Monitoring] screen will appear when you log-in to DMS2 web page.
Check the current status of all devices.
2
You can check the current controlling status of all installed indoor units, ERV, AHU,
ERV PLUS, Fresh duct, Global 4 Way, and other devices.
Note
When the advanced functions (such as Sleep mode, Energy saving function) are
selected through wired/wireless remote controllers or indoor unit panel,
set operation mode on the remote controllers and DMS2 may be displayed
differently. Also, when controlling by DMS2, additional functions will be canceled.
Depending on the model of indoor unit, Horizontal/All air flow direction control
AHU, ERV, ERV PLUS, Global 4 Way, Fresh duct, Lighting, and other devices will be
may not be possible. In this case, vertical or fixed flow will be displayed depending
on indoor unit’s basic operation specification.
displayed only when the corresponding devices are installed.
Some functions available on DMS2 webpage may not be functional at BACnet
Gateway and LonWorks Gateway. For detailed function, refer to the installation
manual or contact Samsung Electronics.
E-19
Control and Monitoring (Continued)
Controlling an Indoor Unit
1
Status display window
2
Click [Control and Monitoring] when DMS2 web page menu
1
screen appears.
[Control and Monitoring] screen will appear when you
log-in to DMS2 web page.
Select an indoor unit to control.
2
Check the indoor unit status through status display window.
When the selected indoor unit is switched on, the remote
controller panel will be automatically activated.
3
E-20
3
Turn the indoor unit on by clicking [].
Remote controller panel will be activated.
5
4
6
Select the operation mode.
4
You can select Auto, Cool, Dry, Fan and Heat operation mode.
Click [][] to set the desired temperature.
5
Each time you click the buttons, the temperature will be adjusted by 1℃(1°F).
If Auto/Cool/Dry mode is in operation, you can adjust the desired temperature in
the range of 18℃(65°F)~30℃(86°F).
If Heat mode is in operation, you can adjust the desired temperature in the range of
16℃(61°F)~30℃(86°F).
You cannot adjust the desired temperature in Fan mode.
When the operation mode of an indoor unit is Cool or Dry mode, you cannot set the
desired temperature lower than lower limit temperature if lower limit is enabled.
When the operation mode of indoor unit is Heat mode, you cannot set the desired
temperature higher than upper limit temperature if upper limit is enabled.
Select the fan speed.
6
You can select Auto, Low, Mid and High.
If Auto/Dry mode is in operation, fan speed will be set as Auto fan speed.
If Fan mode is in operation, you cannot select Auto fan speed.
E-21
Control and Monitoring (Continued)
8
7
Select the air flow.
7
You can select Vertical, Horizontal, All and None air flow direction.
Set remote controller settings.
8
You can select Enable RC, Disable RC, and Cond. RC.
When selecting [Disable RC], indoor unit control by wired/wireless remote controller
and indoor unit panel is not possible. Indoor unit control is only available in
DMS2 web page.
Click [] when you want to use wired remote controller in each room.
Note
When filter warning sign is displayed on indoor unit status window
Select the indoor unit and click [Reset filter].
Filter warning will be released.
Make sure that each indoor unit must be turned on to control. Selecting remote controller, reset filter, operation mode limits, setting lower/upper
Some air flow direction option may be restricted depending on the indoor unit
E-22
temperature limit are possible even if the power of indoor unit is off.
model.
Indoor Unit Operation Mode Limit
1
Status display window
2
You can monitor the operation status of all indoor units or
have individual or whole control of the indoor units.
Click [Control and Monitoring] when DMS2 web page menu
1
screen appears.
[Control and Monitoring] screen will appear when you
log-in to DMS2 web page.
Select an indoor unit to control.
2
Check the indoor unit status through status display
window.
When the selected indoor unit is switched on, the remote
controller panel will be automatically activated.
E-23
Control and Monitoring (Continued)
3
Set operation mode limit.
3
You can select 'Cool only(Fan, Cool)’, ‘Heat only(Fan, Heat)’ and ‘No limits’.
- Cool only (Fan, Cool) : If cool only indoor unit operates in Heat mode,
reset the indoor unit as set operation mode.
- Heat only (Fan, Heat) : If heat only indoor unit operates in cool mode,
reset the indoor unit as set operation mode.
- No limits : You can use cool only and heat only with no limits.
- e.g : If the 'cool only fan' indoor unit operates in heating mode, DMS2 will detect it
and reset the indoor unit in Fan mode.
Note
Operation mode limits setting is not available in ERV. ERV Plus doesn’t operate Fan mode, it only operates cool mode in ‘cool only’. Mixed operation can occur regardless of operation mode limits setting.
E-24
ERV Plus doesn’t operate Fan mode, it only operates heat mode in ‘heat only’.
If indoor unit with operation mode limit is in mixed operation, DMS2 solves mixed
operation status automatically by controlling the indoor unit in set operation mode.
In the following circumstances, all indoor units under the
same outdoor unit should be set to the same operation
mode limits. Mixed operation can occur continuously
when you set some of indoor unit to cool only and the
other to heat only.
- If the centralized controller is MCM-A202 and is in
group mode
- If the centralized controller is in group mode and the
interface module is MIM-B13 or MIM-B04A
Except above circumstances, DMS2 changes the
operation mode limit of all indoor units under the same
outdoor unit to same operation mode limit.
- If the centralized controller is in group mode and is
above MCM-A202A and all the interface modules under
the centralized controller are above MIM-B13A
- If the centralized controller is in individual mode
If you set the cooling only indoor unit’s operation mode
limit to heating only, DMS2 may display Heating
Cooling alternately.
E-25
Control and Monitoring (Continued)
Setting Lower/Upper Temperature Limit of an Indoor Unit
1
Status display window
2
E-26
You can monitor the operation status of all indoor units, and
control the indoor units as a whole, or as individual units.
Click [Control and Monitoring] when DMS2 web page menu
1
screen appears.
[Control and Monitoring] screen will appear when you
log-in to DMS2 web page.
Select an indoor unit to control.
2
Check the indoor unit status through status display window.
When the selected indoor unit is switched on, the remote
controller panel will be automatically activated.
3
4
Set upper temperature limit by pressing [] and [].
3
Click 'Heat upper limit' to apply the upper temperature limit setting.
When indoor unit is operating in heat mode, DMS2 controls indoor unit as upper
temperature limit if the desired temperature is higher than upper temperature limit.
Upper temperature limit can be set in the range of 16°C(61°F)~30°C(86°F).
When an indoor unit is operating in Heat mode and the upper temperature limit is
applied, you cannot set the desired temperature higher than the upper temperature
limit.
Set lower temperature limit by pressing [] and [].
4
You can set lower temperature limit by clicking 'Cool lower limit'.
When indoor unit is operating in cool mode, DMS2 controls indoor unit as lower
temperature limit if the desired temperature is lower than lower temperature limit.
Lower temperature limit can be set in the range of 18°C(65°F)~30°C(86°F).
When indoor unit is operating in Cool or Dry mode and the low temperature limit is
applied, you cannot set the desired temperature lower than the lower temperature
limit.
Note
You cannot set the lower and upper temperature limit of ERV, ERV PLUS,
and Fresh duct.
E-27
Control and Monitoring (Continued)
Monitoring the operation status of Global 4 Way
1
Status display window
2
E-28
You can monitor the operation status of Global 4 Way, and
control Global 4 Way as a whole, or as individual units.
Click [Control and Monitoring] when DMS2 web page menu
1
screen appears.
[Control and Monitoring] screen will appear when you
log-in to DMS2 web page.
Check the current status of Global 4 Way.
2
Check the status of Global 4 Way through the status
display window.
When the selected Global 4 way is switched on,
the remote controller panel will be automatically
activated.
Controlling Global 4Way
1
2
Click [Control and Monitoring] when DMS2 web page menu
1
screen appears.
[Control and Monitoring] screen will appear when you
log-in to DMS2 web page.
3
Check the current status of Global 4 Way.
2
Check the status of Global 4 Way through the
status display window.
When the selected Global 4 way is switched on,
the remote controller panel will be automatically
activated.
3
Turn the Global 4way on by clicking [].
Remote controller panel will be activated.
E-29
Control and Monitoring (Continued)
4
6
Select SPI setting.
4
You can set SPI through button activation / non activation.
5
Select Human Sensor setting .
5
You can set Human Sensor through button activation / non activation.
Select Auto Clean setting.
6
You can set Auto cleaning through button activation / non activation.
Note
SPI, Human Sensor, and Auto Clean will work only when the corresponding
options are installed and their normal operation is guaranteed when the
centralized controller is above MCM-A202D and Interface module is
MIM-B13D.
Refer to the ‘Controlling an indoor unit’ for Global 4 Way control. (Page 20~22) Refer to the ‘Indoor unit operation mode limit’ for Global 4 Way operation
Refer to the ‘Setting lower/upper temperature Limit of an Indoor Unit’ for
E-30
mode limit. (Page 23~25)
setting lower or upper temperature limit of Global 4 Way. (Page 26~27)
Monitoring AHU Operation Status
1
Status display window
2
You can monitor the operation status of AHU, and control AHU as a whole,
or as individual units.
Click [Control and Monitoring] when DMS2 web page menu screen appears.
1
[Control and Monitoring] screen will appear when you log-in to DMS2 web page.
Check current status of AHU.
2
Check AHU status through status display window.
When the selected AHU is switched on, the remote controller panel will be
automatically activated.
Note
To control AHU, refer to the ‘Controlling an indoor unit’ steps.
AHU’s fan speed is fixed as high. (Refer to the page 20~22)
You cannot set air flow direction of AHU.
To set the operation mode limit of AHU, refer to the ‘Indoor unit operation mode
To set the lower/upper temperature limit of AHU, refer to the ‘Setting lower/upper
limit’ steps. (Refer to the page 23~25)
temperature limit of indoor unit’ steps. (Refer to the page 26~27)
E-31
Control and Monitoring (Continued)
Monitoring Fresh duct operation status
1
Status display window
2
You can monitor the operation status of Fresh duct, and control the Fresh duct
as a whole, or as individual units.
Click [Control and Monitoring] when DMS2 web page menu screen appear.
1
[Control and Monitoring] screen will appear when you log-in to DMS2 web page.
Check the current status of a Fresh duct.
2
Check the status of a Fresh duct through the status display window.
When the selected Fresh duct is switched on, the remote controller panel will be
automatically activated.
E-32
Controlling a Fresh duct
1
3
2
Click [Control and Monitoring] when DMS2 web page menu screen appear.
1
[Control and Monitoring] screen will appear when you log-in to DMS web page.
Check the current status of a Fresh duct.
2
Check the status of a Fresh duct through the status display window.
When the selected Fresh duct is switched on, the remote controller panel will be
automatically activated.
3
Turn the Fresh duct on by clicking [].
Remote controller panel will be activated.
E-33
Control and Monitoring (Continued)
4
Set cooling/heating discharge temperature by clicking []and[]
4
When the Fresh duct is in Cool mode, the Fresh duct can be set as cooling discharge
temperature and when the Fresh duct is in Heat mode, the Fresh duct can be set as
heating discharge temperature.
When the Fresh duct is in Auto or Fan mode, the discharge temperature cannot be
adjusted.
Cooling discharge temperature can be set in the range of 15°C(59°F)~25°C(77°F).
Heating discharge temperature can be set in the range of 18°C(65°F)~30°C(86°F).
Note
The normal Fresh duct operation is guaranteed when the centralized controller
is above MCM-A202D and the interface module is MIM-B13D.
Controlling or monitoring cooling/heating discharge temperature setting is
Refer to the ‘Controlling an indoor unit’ for Fresh duct control. ( Page 20~22) The fan speed of a Fresh duct is fixed as ‘High’. Setting air flow direction of a Fresh duct is not available. Refer to the ‘Indoor unit operation mode limit’ for Fresh duct operation mode
available only when the DMS2 is directly connected to the Interface module
MIM-B13D. However, when the DMS2 is connected to a centralized controller,
controlling or monitoring cooling/heating discharge temperature setting is
not available.
limit. (Page 23~25)
E-34
Monitoring ERV Operation Status
1
Status display window
2
You can monitor the operation status of ERV, and control the
ERV as a whole, or as individual units.
Click [Control and Monitoring] when DMS2 web page menu
1
screen appears.
[Control and Monitoring] screen will appear when you
log-in to DMS2 web page.
Check current status of ERV.
2
Check the status of ERV through the status display window.
When the selected ERV is switched on, the remote controller
panel will be automatically activated.
E-35
Control and Monitoring (Continued)
Controlling ERV
1
2
3
E-36
You can monitor the operation status of ERV, and control the
ERV as a whole, or as individual units.
Click [Control and Monitoring] when DMS2 web page menu
1
screen appears.
[Control and Monitoring] screen will appear when you
log-in to DMS2 web page.
Select an ERV to control.
2
When the selected ERV is switched on, the remote controller
panel will be automatically activated.
3
Turn ERV on by pressing [].
The remote controller panel will be activated.
6
4
5
Select the operation mode.
4
You can select Auto, HeatEx, By pass and Sleep.
Select the fan speed.
5
You can select Low, High and Turbo.
Fan speed is set to Low in Sleep mode.
Set remote controller settings.
6
You can select Enable RC, Disable RC, and Cond. RC.
When selecting [Enable RC], indoor unit control by wired/
wireless remote controller is not possible. Indoor unit
control is only available in DMS2 web page.
Click [ ] when you want to use wired remote controller in
each room.
Note
When filter warning sign is displayed on ERV status
window
Select the ERV and click [Reset filter]. Filter warning will be
released.
Make sure that ERV must be turned on to control. Selecting remote controller and filter reset are possible
even if the power of indoor unit is off.
E-37
Control and Monitoring (Continued)
Monitoring ERV PLUS operation status
1
Status display window
2
E-38
You can monitor the operation status of ERV PLUS,
and control the ERV PLUS as a whole, or as individual units.
Click [Control and Monitoring] when DMS2 web page menu
1
screen appears.
[Control and Monitoring] screen will appear when you
log-in to DMS2 web page.
Check the current status of ERV PLUS.
2
Check the status of ERV PLUS through the status display
window.
When the selected ERV PLUS is switched on, the remote
controller panel will be automatically activated.
Controlling ERV PLUS
1
2
Click [Control and Monitoring] when DMS2 web page menu
1
screen appear.
[Control and Monitoring] screen will appear when you
log-in to DMS2 web page.
3
Select ERV PLUS to control.
2
Check the status of ERV PLUS through the status display
window.
When the selected ERV PLUS is switched on, the remote
controller panel will be automatically activated.
3
Turn the ERV PLUS on by clicking [ ].
Remote controller panel will be activated.
E-39
Control and Monitoring (Continued)
4
Select the operation mode
4
You can select Auto, Cool, Off and Heat mode.
Note
The normal ERV PLUS control or monitoring is guaranteed when the
centralized controller is above MCM-A202D and the interface module is
MIM-B13D.
Refer to the ‘Controlling ERV’ for ERV PLUS control. (Page 36 ~ 37) Refer to the ‘Indoor unit operation mode limit’ for ERV PLUS operation
ERV PLUS doesn’t operate Fan mode, so it only operates cool mode in
ERV PLUS doesn’t operate Fan mode, so it only operates heat mode in
mode limit. (Page 23 ~ 25)
‘cool only’.
‘heat only’.
E-40
Monitoring DMS DI/DO Operation Status
1
Click [Control and Monitoring] when DMS2 web page menu
1
screen appears.
[Control and Monitoring] screen will appear when you
log-in to DMS2 web page.
3
2
Check the current status of DI and DO device.
2
Monitor the device through the control panel.
3
Note
Entering ON/OFF becomes impossible for DI device.
Entering ON/OFF becomes possible for DO device. Entering control value becomes impossible for DI/DO
You can control and monitor DI/DO which built-in
device.
DMS2. However, DI 1, 2 and DO 1, 2, 9, 10 are excluded
from controlling and monitoring because they are
used for the internal function of DMS.
E-41
Control and Monitoring (Continued)
Controlling DMS DO
1
2
E-42
Click [Control and Monitoring] when DMS2 web page menu screen appears.
1
[Control and Monitoring] screen will appear when you log-in to DMS2 web page.
Select DO device to control when control and monitoring screen appears.
2
Check the status of DI or DO device.
3
Turn DO device on by clicking [ON]/[OFF] button on the control panel.
3
Note
Remote controller setting is not possible for DI/DO device.
Monitoring the selected multiple devices operation status
1
Status display window
2
You can monitor the operation status of other type devices,
and control other type devices as a whole, or as individual units.
Click [Control and Monitoring] when DMS2 web page menu screen appears.
1
[Control and Monitoring] screen will appear when you log-in to DMS2 web page.
Check the status of the selected multiple devices.
2
Check the status of an indoor unit through status display window.
When the selected devices are switched on, the remote controller panel will be
automatically activated.
Note
When users select multiple devices, 'Basic Control' will be displayed
The current status of last selected indoor unit type devices (Indoor unit, AHU,
The status of last selected ERV type devices (ERV, ERV PLUS) will be displayed
The list of the selected multiple devices will be displayed on the ‘Selected Device’.
on the screen. (This is when different types of multiple devices are selected.)
Fresh duct, Global 4 way) will be displayed on the 'Indoor control'.
on the 'Ventilation Control'.
E-43
Control and Monitoring (Continued)
Controlling the selected multiple devices
1
3
2
E-44
Click [Control and Monitoring] when DMS2 web page menu
1
screen appears.
[Control and Monitoring] screen will appear when you
log-in to DMS2 web page.
Check the status of the selected devices.
2
Check the status of an indoor unit through status display
window.
When the selected devices are switched on, the remote
controller panel will be automatically activated.
3
Turn the selected devices on by clicking [ ].
Remote controller panel will be activated.
4
5
6
7
8
9
Select the desired temperature by clicking [][].
4
Each time you click the button, the temperature will be adjusted by 1°C(1°F).
If Auto/Cool/Dry mode is in operation, you can adjust the desired temperature in the
range of 18°C(65°F)~30°C(86°F).
If Heat mode is in operation, you can adjust the desired temperature in the range of
16°C(61°F)~30°C(86°F).
You cannot adjust the desired temperature in Fan mode.
When the operation mode of an indoor unit is in Cool or Dry mode, you cannot set
the desired temperature lower than lower limit temperature if lower limit is enabled.
When the operation mode of an indoor unit is in Heat mode, you cannot set the
desired temperature higher than upper limit temperature if upper limit is enabled.
Select the operation mode.
5
You can select Auto, Cool, Dry, Fan and Heat mode.
Select the fan speed.
6
You can select Auto, Low, Mid and High.
If Auto/Dry mode is in operation, fan speed will be set as Auto fan speed.
If Fan mode is in operation, you cannot select Auto fan speed.
E-45
Control and Monitoring (Continued)
Select the ERV operation mode.
7
You can select Auto, Heat Ex, By pass and Sleep mode.
Select the fan speed.
8
You can select Low, high and Turbo.
If Sleep mode is in operation, the fan speed will be set as
Low fan speed.
When controlling certain types of devices in detail, select
9
the device you want to control on the list of the ‘Selected
Device’.
Note
If the ERV type devices are not on the list of the
‘Selected Device’, ventilation control will not be
activated.
If the indoor unit type devices are not on the list of the
When controlling an indoor unit, ERV devices
When controlling ERV devices, Indoor unit (Indoor unit,
You can select power on/off, Disable RC, Reset filter,
Power on/off, Disable RC and Reset filter are controlled
When selecting multiple devices, the list of the selected
‘Selected Device’, Indoor control will not be activated.
(ERV, ERV PLUS) cannot be controlled.
AHU, Fresh duct, Global 4 Way) cannot be controlled.
Indoor Control (Desired temp, operation mode, fan
speed) and ERV Control in the ‘Basic control’.j
to all the devices.
devices will be displayed at the bottom of the remote
controller. When selecting the device you want to
control, the remote control panel of the selected device
will be activated and you can control the selected
device in detail. However, the rest of the devices cannot
be controlled other than the selected device.
E-46
Checking the Installation Information
1
2
3
You can check the installation status of currently connected
device.
Click [Control and Monitoring] when DMS2 web page menu
1
screen appears.
[Control and Monitoring] screen will appear when you
log-in to DMS2 web page.
Click ‘Install.Info’. tab at the bottom left of the screen.
2
Check installation status of currently connected device in the
3
installation information tab.
You can check installation information by pressing
[∧] and [∨] buttons.
E-47
Control and Monitoring (Continued)
View the Control History & Power Consumption
1
2
E-48
3
You can select a device and view control history and power
consumption information.
Click [Control and Monitoring] when DMS2 web page menu
1
screen appears.
[Control and Monitoring] screen will appear when you
log-in to DMS2 web page.
Select a device you want to view control history and power
2
consumption.
Click [View control history & power consumption]tab and
3
wait for a while.
Control history and power consumption information are
received from DMS2.
‘Data receiving’ message will appear on the bottom right
of the tab.
When data reception is completed from DMS2, check control
4
history and power consumption of selected device.
Note
In ‘Control history’, you can check power control and
remote controller usage status.
Operation mode, desired temperature, air flow and fan
speed control shows you the controlled time and type
of control only.
If SIM is not installed, power consumption information
may not be correct.
Power consumption information is displayed only
when SIM is installed.
If SIM is removed, value measured with SIM will be
displayed.
4
E-49
Control and Monitoring (Continued)
Cycle Monitoring
1
2
3
You can select an indoor unit and check cycle information.
E-50
Click [Control and Monitoring] [Cycle Monitoring] when DMS2 web page menu
1
screen appears.
Click [Select].
2
DMS2 installation information will be displayed.
Select a device to check cycle information.
3
If you select centralized controller, its subordinate outdoor unit which has the
earliest address will be selected.
If you select interface module, its subordinate outdoor unit will be selected.
If you select indoor unit, upper outdoor unit will be selected.
Cycle information of selected outdoor unit and subordinate indoor units.
4
If the status of outdoor unit and indoor unit is changed, status value turns into blue.
Note
You can check all the cycle information on DVM Plus 2 or DVM Plus 3 with the
centralized controller MCM-A202B and interface module MIM-B13B (or higher
version of those devices) only. However, some cycle information may not be
displayed on any other models of outdoor unit.
Indoor Unit Usage Restriction_Operation Limit
1
3
You can set the operation of indoor unit as cooling only and
heating only.
Click [Control and Monitoring] [Indoor unit usage
1
restriction] when DMS2 web page menu screen appears.
Press [Edit] button.
2
Set the limit mode.
3
You can select 'Cool-only’, ‘Heat-only’ or ‘None’.
- For cooling only indoor unit, you can select cool, dry and
fan modes only.
- For heating only indoor unit, you can select heat and fan
modes only.
2
E-51
Control and Monitoring (Continued)
4
Set the control mode.
4
If you set the control mode, indoor unit operating in limited operation mode will
be automatically set to operate in pre-set control mode. You can set the different
control mode to each of the indoor units.
- Cooling only indoor unit: You can select fan or cool mode.
- Heating only indoor unit: You can select fan or heat mode.
(Ex: When the indoor unit with fan mode is changed to heat mode, DMS2 will
perceive it and control the indoor unit in fan mode.)
ERV PLUS doesn’t operate Fan mode, so it operates only Cool or Heat mode in the
'cool only' or 'heat only' limit mode.
Note
Mixed operation can occur even if you set limit mode.
If the indoor unit with operation mode limit is in mixed operation, DMS2 will
solve the problem automatically by controlling it in control mode.
In the following circumstances, all indoor units under the same outdoor unit
should be set to the same limit mode. Mixed operation can occur continuously
when you set some of indoor unit to cool only and the other to heat only.
- If the centralized controller is MCM-A202 and is in group mode
- If the centralized controller is in group mode and the interface module is
MIM-B13 or MIM-B04A
Except above circumstances, DMS2 changes the limit mode of all indoor units
under the same outdoor unit to same limit mode.
- If the centralized controller is in group mode and is above MCM-A202A and all
the interface modules under the centralized controller are above MIM-B13A
- If the centralized controller is in individual mode
If you set the cooling only indoor unit’s limit mode to heating only, DMS2 may
display Heating Cooling alternately.
E-52
Indoor Unit Usage Restriction_Temperature Limit in Cool/Heat mode
1
2
You can set temperature lower/upper temperature limit in
cool/heat mode.
Click [Control and Monitoring] [Indoor unit usage
1
restriction] when DMS2 web page menu screen appears.
Press [Edit] button.
2
E-53
Control and Monitoring (Continued)
3
Set the lower/upper temperature limit.
3
You can set lower/upper temperature limit by selecting
'Enable'/'Disable'.
If desired temperature is lower than lower limit
temperature when the indoor unit is operating in cool
mode, DMS2 controls indoor unit to lower temperature
limit.
If desired temperature is higher than upper limit
temperature when the indoor unit is operating in heat
mode, DMS2 controls indoor unit to upper temperature
limit.
Lower temperature limit range: 18℃(65°F)~30℃(86°F)
Upper temperature limit range: 16℃(61°F)~30℃(86°F)
If the indoor unit is in Auto(Cool)/Auto(Heat) mode, lower/
upper temperature limit will be applied when the indoor
unit is operating in Auto mode.
However, if the upper temperature limit is set to
16°C(61°F)~17°C(64°F), the upper temperature limit in
Auto(Heat) mode is 18°C(65°F).
ERV plus and Fresh duct cannot set the lower temperature
limit in Cool mode or upper temperature limit in Heat mode.
4
E-54
Click [Save].
4
Indoor unit usage restriction setting will be saved.
Checking the Trouble History
1
Click [Control and Monitoring] [Trouble history]
1
when DMS2 web page menu screen appears.
Check all the trouble history.
2
You can check address, device type, occurrence time,
resolution time, code number and status.
3
You can check detailed information on trouble history by
3
selecting the item in the list.
Note
DMS2 saves maximum 1024 trouble histories.
If the number of history exceeds 1024, DMS2 will delete
the oldest history first.
If the same code trouble is detected repeatedly in the
same device on the same day, trouble history will be
shown as 1 case. If it occurs more than 2 times,
‘Resolution time’ may change every time you check.
And the number of repetition will be displayed in
‘Status’ field.
E-55
Control and Monitoring (Continued)
Checking the Trouble History by Date
1
3
DMS2 saves maximum 1024 trouble histories. If the number
of history exceeds 1024, DMS2 will delete the oldest history
first.
Click [Control and Monitoring] [Trouble history]
1
when DMS2 web page menu screen appears.
Enter the time period you want to check.
2
Enter year/month/day in order.
Click [Search].
3
You can check address, device type, occurrence time,
resolution time, code number and status in the entered
period.
2
4
E-56
You can check detailed information on trouble history by
4
selecting the item in the list.
Deleting the Trouble History
1
2
Click [Control and Monitoring] [Trouble history]
1
when DMS2 web page menu screen appears.
Select trouble history you want to delete.
2
Click [Delete].
3
Click [OK] from the confirm window. Selected trouble
history will be deleted.
3
E-57
Control and Monitoring (Continued)
Checking the Operation Status
1
3
You can check operation status of indoor unit which is
controlled by DMS2.
4
E-58
Click [Control and Monitoring] [Checking operation status]
1
when DMS2 web page menu screen appears.
Check the operation history.
2
You can check the device type, occurrence time, control
unit, control type, and controlled device address of
indoor unit which is controlled by DMS2 and subordinate
controller.
You can check operation status by entering date.
3
Enter year/month/day then click [Search]. You can check
control history that occurred on the entered date.
You can check detailed control history which is controlled by
4
the command by pressing control history in the list.
Note
DMS2 saves the information of operation history for 180 days.
However, it varies depending on saving space of DMS2.
Zone Management
Zone Setting & Edit – Individual/Group Initialization
1
3
2
Click [Zone management] [Zone Setting & Edit] when DMS2 web page menu screen
1
appears.
Same screen will be displayed even if you click [Zone management] only.
Initialize the indoor unit organization as individual by clicking [Individual].
2
Individual initialization reorganizes connected indoor unit based on installation address.
Initialize the indoor unit organization as group by clicking [Group].
3
Group initialization reorganizes connected indoor unit based on RMC address.
After group initialization, indoor units are displayed as one device when
upper zone is selected in the [Control and Monitoring] screen.
When editing zone after group initialization, moving in group is only allowed.
After group initialization, subordinate devices cannot be moved individually to
the other zone.
Note
Only the user who has authorization to edit all zones can use zone initialization.
- To the user who has no authorization to use zone initialization and manage
structure, button will not be displayed.
If the user does not have authorization to edit zone, [Inidividual], [Group] and
[Zone edit] will not be displayed.
E-59
Zone Management (Continued)
Zone Setting & Edit – Setting the User Authorization
1
2
Click [Zone management] [Zone Setting & Edit] when DMS2 web page menu
1
screen appears.
Same screen will be displayed even if you press [Zone management] only.
3
Set user authorization for each zone.
2
If the user has no authorization for the zone, controlling and monitoring of the
zone is restricted.
The user who is allowed to control and monitor zone has ‘’ sign.
Click [Save] to save.
3
The user of currently selected zone is selected in the screen.
You should set the authorization for controlling and monitoring the zone when the
user is added.
If you do not set the authorization for zone after adding a user, the zone will not be
displayed even if the user logged in.
Setting the user authorization is valid only for the zone displayed on the screen. If you
select the other zone setting without clicking save button after changing the setting,
user authorization for previously selected zone will be gone.
When initializing zone, all rights are given to all users.
E-60
Zone Setting & Edit – Zone Edit
1
2
Click [Zone management] [Zone Setting & Edit] when
1
DMS2 web page menu screen appears.
Same screen will be displayed even if you press
[Zone management] only.
Click [Zone Edit].
2
Zone edit screen will be displayed.
E-61
Zone Management (Continued)
3
6
7
4
5
8
E-62
Click [▼] to set viewing option of zone edit list.
3
You can select from viewing by 'Name’, ‘Address’ and ‘Address & Name'.
Edit item you want.
4
Create in the
above
Create in the
below
Create the sub
zone
Remove
Move upMove up the selected zone or indoor unit.
Move downMove down the selected zone or indoor unit.
Move to upper
level
Rename
CutCut to move the selected zone or indoor unit,
PasteMove the cut zone or indoor unit to the selected zone.
Create a new zone on top of the selected zone.
Create a new zone under the selected zone.
Create a zone one step lower than the user selected.
You cannot create a zone under 5 steps in zone edit.
Remove selected zone. If the selected zone includes device,
the device will move to the top step.
Move the selected zone or indoor unit to the upper level.
Rename the selected zone or indoor unit.
You can use maximum 16 letters.
Click [Remove disappeared] to remove all disappeared devices which were found
5
after tracking.
Change zone properties.
6
You can select “General”, “AHU”, and “Group”.
Mode Property nameDescriptionRemarks
Virtual group which is managed by
▪
installation address, not by RMC
address
The user can create and delete zone.
▪
Not applicable.
( Only supported in group initialization
mode.)
Virtual group which manages AHU kit
▪
in general zone.
The user can create and delete.
▪
Virtual group which is set and
▪
managed by the user.
The user can create and delete.
▪
Virtual group which is managed by
▪
installation address, not by RMC
address.
The user cannot create and delete.
▪
DMS2 creates it automatically.
Virtual group which manages AHU kit
▪
in general zone.
The user can create and delete.
▪
-
Not applicable.
( Only supported in group initialization
mode.)
It will be displayed as single device in
▪
the control and monitoring screen, and
it can be controlled as single device.
You cannot move subordinate device
▪
to the other zone.
-
It is displayed like as one device in the
▪
control and monitoring screen and can
be controlled.
You cannot move subordinate device
▪
to the other zone.
It is displayed like as one device in the
▪
control and monitoring screen and can
be controlled.
You cannot move subordinate device
▪
to the other zone.
Individual
initialization
mode
Group
initialization
mode
General
Group
AHU
General
Group
AHU
Click [Apply].
7
Edited zone structure will be applied.
To cancel the setting, click [Cancel].
8
E-63
Schedule
Creating New schedule
1
2
You can set, edit, delete and use the schedules for air
conditioner control.
Click [Schedule] [Schedule setting] when DMS2 web page
1
menu screen appears.
Click [Register] in the schedule setting screen.
2
Note
It is not available to provide the schedule information to
BMS system.
E-64
3
4
5
Enter the schedule name when the schedule setting screen
3
appears.
Select schedule period you want by clicking calendar.
4
If you select 'No limit' when setting end date, it means
there is no period and it displays Dec 31st, 9999.
To set the end date, remove the check of ‘No limit’ or select
calendar icon which is on the right side of date.
To set an exception date in the schedule period, click
5
[Add exception] and select date(month/day) you want.
Select an exception date on the calendar window.
E-65
Schedule (Continued)
6
E-66
To cancel the added exception date, select the exception
6
date it() and click [Delete].
Maximum 365 exception dates can be saved.
7
8
Click [Add device] to select a device to apply.
7
The list of all the connected devices will be displayed.
You can register a schedule for DMS DO as well.
8
To cancel the selected device, select () the device again
and click [Delete].
E-67
Schedule (Continued)
9
10
Click [∨] to select repeat schedule you want and set an event.
9
You can select 'Weekly', 'Everyday' and '1day'.
However, the starting and end date should be same when you select '1day'.
Enter 4 digits for ON/OFF time setting.
Ex) 8:00 0800, 9:30 0930
Remote controller setting is as follows.
●
Enable RC: Controlling indoor unit using wired/wireless remote controller or
●
Disable RC: Controlling indoor unit using wired/wireless remote controller or
●
Cond. RC
- ON by centralized controller, DMS2: Controlling indoor unit using wired/wireless
- OFF by centralized controller, DMS2: Controlling indoor unit using wired/wireless
Click [Add] to add event.
To delete event, select an event() and click [Delete].
Maximum 70 events can be set per 1 schedule. In case of week schedule, 10 events per
1 day can be set.
If starting and end time of schedule event are repeated, only the schedule event
which is made earlier will be executed.
indoor unit panel in each room is possible.
indoor unit panel in each room is not possible.
remote controller or indoor unit panel in each
room is possible.
remote controller or indoor unit panel in each
room is not possible.
E-68
Click [Save].
10
Set schedule information is saved in DMS2.
Click [Cancel] to cancel schedule setting.
Note
If you select dry mode among basic modes, auto fan
speed is only available.
When the operation mode is ‘Auto’, fan speed is always
set to ‘Auto’.
When the operation mode is ‘Fan’, you cannot control
fan speed as ‘Auto’.
When the operation mode is ‘Dry’, fan speed is always
set to ‘Auto’.
When you select sleep mode among ERV modes, ‘Mid’
fan speed is only available.
The desired temperature range is as below.
- Celsius: 16°C~30°C in heating mode, 18°C~30°C in
cooling mode
- Fahrenheit: 61°F~86°F in heating mode, 65°F~86°F in
cooling mode
If the tracking is not completed, schedule setting is not
possible. To use proper schedule function, make sure to
complete tracking with installation engineer.
‘Off’ operation works only with ERV PLUS.
E-69
Schedule (Continued)
Editing Schedule
2
1
2
1
3
Click [Schedule] [Schedule setting] when DMS2 web page
menu screen appears.
Select the schedule to edit.
For the currently operating schedule, you can only
check it.
E-70
Click [Edit].
3
Edit schedule when the schedule edit screen appears.
Editing schedule method is same as “Creating New
Schedule”. (Refer to page 64~69)
Deleting Schedule
1
2
3
Click [Schedule] [Schedule setting] when DMS2 web page
1
menu screen appears.
Select the schedule to delete.
2
Click [Delete].
3
Click [OK] in confirm window and selected schedule will
be deleted.
Deleting schedule is possible only when the schedule is in
stop status.
If you want to delete schedule which is currently applied,
stop applying the schedule first.
E-71
Schedule (Continued)
Applying schedule
2
3
1
2
3
1
Click [Schedule] [Schedule setting] when DMS2 web page
menu screen appears.
Select the schedule you want to use.
Use schedule functions by clicking [Run] and [Stop].
To apply the selected schedule, click [Run].
To stop the selected schedule, click [Stop].
E-72
Note
To stop all schedules, click [Stop all].
- Currently applied schedule will be stopped.
Checking Schedule Control History
1
2
3
Click [Schedule] [Checking schedule control history] when
1
DMS2 web page menu screen appears.
Select a date to check and then click [Search].
2
Only executed schedules can be searched.
You can check detailed setting by clicking the schedule
3
name.
Note
DMS2 saves the information or schedule control history
for 180 days.
However, it varies depending on saving space of DMS2.
E-73
EHP Power Consumption Inspection
Checking Inspection Result (with SIM/PIM)
1
2
You can check the operation history and power consumption saved in DMS for each
indoor unit.
Click [EHP Power Consumption Inspection] [Check inspection result] when DMS2 web
1
page menu screen appears.
Set date and search condition (power consumption/proportion/individual indoor unit by
2
date) when inspection result screen appears.
Select year/month/day in order.
Based on DMS2 time, you can check up to 365 days of watt-hour meter value.
Click [Search].
3
Inspection result will be displayed depending on set period and searching condition.
You can check power consumption only when watt-hour meter is connected.
If watt-hour meter is not connected, you can check operating proportion by indoor
unit only .
3
4
Click [Save as Excel].
4
Searched inspection result will be saved as MS Excel file.
Note
For data management, it is recommended to save indoor unit inspection result
periodically.
Power consumption inspection result is for reference only and should not be used
E-74
for official financial transactions.
Checking Inspection Result (without SIM/PIM)
1
2
3
Click [EHP Power Consumption Inspection] [Check
1
inspection result] when DMS2 web page menu screen
appears.
Channel setting by indoor unit must be done in advance.
Set date when inspection result screen appears.
2
Select year/month/day in order.
Based on DMS2 time, You can check up to 365 days of
inspection results.
4
Enter power consumption value during the period.
3
Virtual channel is value which is set in channel setting by
indoor unit.
Click [Calculate].
4
Power consumption by indoor unit during the period will
be displayed.
E-75
EHP Power Consumption Inspection (Continued)
E-76
Check the power consumption result of the selected period.
5
Due to rounding the actual values, actual input value and
result value may different to each other.
If you want to save the consumption result for selected
period as MS Excel file, click [Save as Excel].
Click [Calculate] to go back to inspection result screen.
Note
For data management, it is recommended to save
indoor unit inspection result periodically.
Power consumption inspection result is for reference
only and should not be used for official financial
transactions.
Setting the Inspection Section
3
Click [EHP Power Consumption Inspection] [Setting the
1
inspection section] when DMS2 web page menu screen
appears.
Click [Edit] when inspection result screen appears.
2
1 section is set as default.
Select a section and enter time by section.
3
You should enter time of section B when selecting 2
sections and enter time of section B and section C when
selecting 3 sections and enter time of section B, section C,
and section D when selecting 4 sections.
Correct format of time is HH:MM.
Ex) 4:30 in the af ternoon 16:30
1
4
2
Click [Save].
4
Set power section will be saved in DMS2.
If you do not click [Save], changed setting will not be
saved.
Note
Ex) When selecting 2 sections(A, B, C)
If the border time between A and B is 08:00, section A is
00:00 ~ 08:00,
section B is 08:01 ~ 18:00, and section A again is
18:01 ~ 24:00.
E-77
EHP Power Consumption Inspection (Continued)
Setting and Checking Watt-Hour Meter
1
3
4
2
Click [EHP Power Consumption Inspection] [Setting and checking watt-hour
1
meter] when DMS2 web page menu screen appears.
Setting watt-hour meter is possible only when SIM/PIM is installed.
Click [Edit] when the setting and checking watt-hour meter screen appears.
2
CT proportion ‘1’ is set as default.
Set name and CT proportion of watt-hour meter.
3
You can use maximum 16 letters.
The range of CT proportion value is positive number from 1 to 5000.
Click [Save].
4
Set watt-hour meter information will be saved in DMS2.
If you do not click [Save], changed setting will not be saved.
Watt-hour meter value shows actual value of currently connected watt-hour meter.
Watt-hour meter value will be updated automatically.
When using CT watt-hour meter, be careful that there can be difference with actual
power consumption as much as CT ratio error.
E-78
Checking Kilowatthour History
1
2
3
Click [EHP Power Consumption Inspection] [Setting and Checking watt-hour
1
meter] when DMS2 web page menu screen appears.
Click [Kilowatthour history] when the setting and checking
2
watt-hour meter screen appears.
Select SIM/PIM address and date you want when the kilowatthour history screen
3
appears.
Enter year/month/day in order.
Based on DMS2 time, you can check up to 365 days of kilowatthour history.
Click [Check].
4
Kilowatthour history of set period will be displayed.
4
E-79
EHP Power Consumption Inspection (Continued)
Setting and Checking Virtual Channel
1
3
E-80
2
4
Click [EHP Power Consumption Inspection] [Setting and
1
checking virtual channel] when DMS2 web page menu screen
appears.
Maximum 128 virtual channels can be set.
Virtual channel is written in (24 ~ 31).(1 ~ 16) format
address.
Ex) 24.1, 25.2, 31.8
Click [Edit] when the setting and checking virtual channel
2
screen appears.
Set the name of virtual channel.
3
You can use maximum 16 letters.
Click [Save].
4
Set virtual channel name will be saved in DMS2.
If you do not click [Save], changed setting will not be
saved.
Channel Setting by Indoor Unit
Click [EHP Power Consumption Inspection] [Channel
1
setting by indoor unit] when DMS2 web page menu screen
appears.
Click [Edit] when the setting channel by indoor unit screen
2
appears.
1
2
Some functions available on DMS2 webpage may not be
functional at BACnet Gateway and LonWorks Gateway.
For detailed function, refer to the installation manual or
contact Samsung Electronics.
E-81
EHP Power Consumption Inspection (Continued)
7
Check the address and channel information of SIM/PIM which is connected to watt-
3
hour meter.
If 0~7 SIM/PIM units execute tracking, it will be displayed as 16~23 in DMS2.
Below table shows the channel information of the terminal which SIM and watt-
hour meter is connected.
(Terminal block 1 is on the very left side in SIM.)
Location
Terminal block
Top part1234
Bottom part5678
PIM: Channel 1 is on the most left side and 8 channels are arranged in a line.
Check the information of indoor/outdoor unit which is connected to
4
watt-hour meter.
Check the SIM/PIM channel(watt-hour meter) information of indoor/outdoor unit.
5
You can set the channel when SIM/PIM is installed in DMS2.
When bringing indoor unit’s power from outdoor unit, set the ‘Outdoor unit SIM
channel’ information only.
( ‘Outdoor unit SIM channel’ is referring to watt-hour meter which is connected to
outdoor unit.)
When bringing indoor unit’s power from the other device, not from outdoor unit,
set the ‘Outdoor unit SIM channel’ and ‘Indoor unit SIM channel’ information.
(‘Indoor unit SIM channel’ is referring to watt-hour meter which is connected to
indoor unit.)
Power distribution will be executed automatically. The user does not need to check
the value of watt-hour meter.
The maximum number of SIM channels for an outdoor unit is 4.
Check the virtual channel information of indoor/outdoor unit.
6
To execute power distribution without SIM/PIM, you should set virtual channel.
When bringing indoor unit’s power from outdoor unit, set the ‘Outdoor unit virtual
channel’ information only.
( ‘Outdoor unit virtual channel’ is referring to watt-hour meter which is connected
to outdoor unit.)
When bringing indoor unit’s power from the other device, not from outdoor unit,
set the ‘Outdoor unit virtual channel’ and ‘Indoor unit virtual channel’ information.
(‘Indoor unit virtual channel’ is referring to watt-hour meter which is connected to
indoor unit.)
The number of virtual channel varies depending on the number of interface
module.
To execute power distribution, you need to check watt-hour meter value manually.
Power distribution using SIM/PIM is more accurate than using indoor/outdoor unit
virtual channel. Therefore, it is recommended to execute power distribution using
SIM/PIM.
Set indoor unit to execute power distribution.
7
If you do not set the watt-hour meter information, the power distribution result of
the indoor unit will be displayed as ‘0’.
Click [Save].
8
Set channel information will be saved in DMS2.
If you do not click [Save], changed setting will not be saved.
Information of watt-hour meter connected to indoor/outdoor unit should be accurate.
If the watt-hour meter information is not accurate when you set channel information
of indoor unit, error may occur in the power distribution result.
You should set SIM/PIM channel information in the indoor unit if you want to execute
power distribution using SIM/PIM. If not, it means that you do not execute power
distribution. In this case, the power distribution result of the indoor unit will be ‘0’.
If the information of watt-hour meter connected to indoor/outdoor unit is changed,
consult with installation engineer.
DMS2 executes power distribution based on set information.
Virtual channel is not available when you use BACnet or LonWorks Gateway function.
E-83
EHP Power Consumption Inspection (Continued)
Checking Indoor Unit Operation Time
1
2
3
4
E-84
Click [EHP Power Consumption Inspection] [Checking
1
indoor unit operation time] when DMS2 web page menu
screen appears.
Select search condition (All indoor units by period/
2
Individual indoor unit by date) when Checking indoor unit
operating time screen appears.
Select year/month/day in order.
Based on DMS2 time, you can check up to 365 days of
operation time.
Click [Search].
3
Operation time will be displayed depending on set period
and condition.
Click [Save as Excel].
4
Searched operation time result will be saved as MS Excel
file.
Note
For data management, it is recommended to save indoor
unit operation time result periodically.
Control Logic Management
Setting Control Logic
■
Control logic is used in the following situations.
Ex) The current temperature of the lab is higher than 29℃ and you want cooling operation,
The current temperature of the office is lower than 10℃ and you want heating operation
■
Period, day and time are included in specific conditions.
1
2
You can set, edit, delete and use control logic for controlling device which is
connected to DMS2.
Click [Control logic management] [Setting control logic] when DMS2 web page
1
menu screen appears.
Apply: Indicates control logic usage status.
Run: Indicates If the control logic is applied and whether the operation conditions
are met.
Ex) If there is logic which says ‘If the current temperature of indoor unit is higher
than 29℃, control indoor unit as cool mode.’, 'Yes' will be displayed when the
indoor unit's current temperature is higher than 29℃. 'No' will be displayed
when the indoor unit's current temperature is lower than 29℃.
Click [Register] when setting control logic screen appears.
2
Setting screen is composed of 4 categories.
- Name & time: Set the name and time(period, days, time) to apply of control logic.
- Factor edit: You can edit factor selection which is components of input/output.
- Input: Set the condition which makes control logic perform.
- Output: Set items to be controlled when the conditions of input are met.
Note
If different value is set for same control item of same address’ device, the indoor
unit follows the first control logic set among running control logics.
It is not available to provide the control logic management information to BMS
system.
E-85
Control Logic Management (Continued)
3
4
E-86
Enter control logic name in the name field when the new
3
control logic setting screen appears.
You can use maximum 16 letters.
Set period, day and time in control logic screen.
4
Select year/month/day in order.
Select a day to run during the control period.
Control logic will be applied only when period, day and
time are united.
If you select ‘Daily’ in day selection, control logic will run
regardless of day.
6
5
Select a factor in the input list.
5
Factor means the target to be controlled or standard item of logic decision.
Select the type of factor.
6
Single: It means 1 device.
Ex) Desired temperature of indoor unit
Arithmetic: It means 2 devices are connected by arithmetic operator.
Ex) Desired temperature of indoor unit 1 – Desired temperature of indoor unit 2
Function: It means several devices are using as value of function.
Ex) Average(Current temperature of Indoor unit 1, Current temperature of
Indoor unit 2, Current temperature of Indoor unit 3)
E-87
Control Logic Management (Continued)
7
Click ‘Select’.
7
List of device which you can select will be displayed.
Select the device to use as factor.
8
Control and monitoring items will be displayed depending on selected device.
Comparison operator compares factor to standard factor.
10
E-89
Control Logic Management (Continued)
12
Select standard value.
12
Select detailed item value of selected factor or factor.
The item varies depending on the left factor when selecting detailed item value
from standard value.
Ex1) Factor : Current temperature of indoor unit 1,
Value of standard value : Enter 29
Ex2) Factor :
When selecting factor from standard value, it must be same with control item of
left factor.
Ex1) Factor : Power of indoor unit 1,
Factor of standard value : Power of indoor unit 2
Ex2) Factor : Current temperature of indoor unit 1,
Factor of standard value : Average current temperature of indoor unit 1 and 2
Select duration time usage.
13
Duration time means the time which the comparing conditions satisf y ‘True’.
The duration time can be set from 1 to 60.
If you select duration time apply, the comparing condition will be 'True'.
To execute, maintain 'True' for duration time.
Note
Only 1 duration time can be set per control logic.
Remote controller usage of indoor unit 1,
Value of standard value : Select one among Enable RC, Disable RC and Cond. RC.
13
The tolerance range of duration time is maximum 1 minute. If you set the
duration time as 2 minutes, operation will be started between 2 and 3 minutes.
E-90
14
15
Select compound factor setting usage.
14
You can use compound factor setting when you give conditions to 2 and 3 input
items.
You can select 1 compound factor from 'AND' and 'OR'.
Select 'AND' if all the input items each should be ‘True'.
Select 'OR' if just 1 input item needs to be 'True'.
Compound factor has priorities in order.
For example, if you set 'OR', 'AND' in order, it means ‘(input item 1 OR input item 2)
AND input item 3’.
Select ‘Select a factor’ in the Output list.
15
E-91
Control Logic Management (Continued)
16
Select type of factor.
16
Single factor can be set for the left factor of output.
- Single factor: It means 1 device.
Ex) Desired temperature of indoor unit
Click 'Select'.
17
List of device which can be selected will be displayed.
17
18
E-92
Select the device to use as factor.
18
19
21
Select detailed item of factor.
19
Detailed item may be different depending on the type of selected device.
Click [Apply].
20
If you do not click [Apply], changed setting will not be saved.
Select command value.
21
The value may vary depending on the detailed item of selected factor.
You can select value of selected item or new factor.
You can set single factor, arithmetic factor and function factor.
20
E-93
Control Logic Management (Continued)
To add output, click [Add].
22
If you want to delete output which you don't use anymore, select it and then click
[Delete].
22
23
Click [Save].
23
Set control logic will be saved in DMS2.
If you do not click [Save], changed setting will not be saved.
Note
Control logic input items consist of factor, comparison operator, standard value
You can enter up to 3 input items of control logic, and the items can be connected
Output item of control logic consists of factor and command value. You can enter up to 20 output items of control logic. You can create up to 256 control logics.
E-94
and duration time.
with compound factor.
Editing/Deleting/Copying Control Logic
2
Click [Control logic management] [Setting control logic]
1
when DMS2 web page menu screen appears.
Select control logic when control logic screen appears.
2
Click [Edit]/[Delete]/[Copy].
3
To edit control logic, refer to 'Setting control logic' steps.
(Refer to page 85~94)
Click [Delete] to delete the selected control logic.
Click [Copy] to copy the selected control logic.
1
3
E-95
Control Logic Management (Continued)
Enable/Disable Control Logic
2
Click [Control logic management] [Setting control logic]
1
when DMS2 web page menu screen appears.
Select control logic when control logic screen appears.
2
Click [Apply]/[Not apply].
3
The selected control logic will be applied by clicking
[Apply].
The selected control logic will not be applied by clicking
[Not apply].
1
3
E-96
Checking Control History
1
2
Click [Control logic management] [Checking control
1
history] when DMS2 web page menu screen appears.
Select the date you want when the control logic screen
2
appears.
Select Year/Month/Day in order.
Based on DMS2 time, you can check of maximum 180 days
of previous control history.
Click [Search].
3
You can check only in daily unit.
Select each items to check detailed contents of control
4
history.
Note
DMS2 saves the information of control logic
management control history for 180 days. However, it
varies depending on saving space of DMS2.
3
4
E-97
System Settings
Adding a User
1
3
4
2
You can add, edit and delete the user of DMS2.
Click [System Settings] [User management] when DMS2 web page menu screen appears.
1
Click [Add user] when user management screen appears.
2
User information input window will be appeared when pressing [Add user].
Enter ID, password, name and description for new user and then select authority.
3
The user ID should be between 4~12 letters and English lower case letters and
numbers only can be used. (English capital letter and special symbols including
space cannot be used for user ID.)
The password should be between 6~12 letters and English capital/lower case
letters, and numbers only can be used, without any spaces. In addition,
the password should contain both English letters and numbers.
Name should be within 20 letters, and description should be in 50 letters.
Registration date will be input automatically as system date.
Select authorization for the user from 'Admin', 'Manager' and 'Regular user'.
Admin has all authorization and 'Manager'/'Regular user' has limited authorization.
Click [Save].
4
There is no limit to the number of user.
User information will be saved in DMS2.
Note
For security and maintenance, you should change the password of the admin
account that is issued by the factory for shipping purposes.
Administrator(Admin) can change all setting of indoor/outdoor unit. Administrator(Admin) can check all indoor/outdoor units connected to DMS2. Administrator(Admin) can edit zone information and assign the zone
information to manager.
A manager can check and control indoor/outdoor units which belong to
assigned zones only.
E-98
Editing a User
2
3
4
Click [System Settings] [User management] when DMS2 web page menu screen
1
appears.
Click the user name to edit when user management screen appears.
2
User information window will be displayed.
Edit user information when the user information window appears.
3
You cannot change user ID.
The password should be between 6~12 letters and English capital/lower case
letters, and numbers only can be used, without any spaces. In addition, the
password should contain both English letters and numbers.
Name should be within 20 letters, and description should be in 50 letters.
Registration date is input automatically as system date. Therefore you cannot edit
registration date.
Select authorization for the user from 'Admin', 'Manager' and 'Regular user'. Admin
has all rights and 'Manager'/'Regular user' has some rights.
1
Click [Save].
4
Modified user information will be saved in DMS2.
Note
User information can be changed only with the admin account. Authorization of admin account cannot be modified. Administrator(Admin) can change all setting of indoor/outdoor unit. Administrator(Admin) can check all indoor/outdoor units connected to DMS2. Administrator(Admin) can edit zone information and assign the zone
information to manager.
A manager can check and control indoor/outdoor units which belong to
assigned zones only.
E-99
System Settings (Continued)
Deleting a User
2
Click [System Settings] [User management] when DMS2
1
web page menu screen appears.
Click the user name to delete when user management
2
screen appears.
User information window will be displayed.
1
4
3
E-100
Click [Delete] when the user delete window appears.
3
Confirm window will pop up saying, “Do you want to
delete the user?"
Click [OK].
4
Selected user information will be deleted in DMS2.
Note
Admin account cannot be deleted.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.