Samsung MIM-B18 User Manual

Data Management Server2
MIM-D00A
BACnet Gateway
MIM-B17
LonWorks Gateway
MIM-B18
Air Conditioner
user manual
DB98-32140A(3)
imagine the possibilities
Thank you for purchasing this Samsung product.
E-2
Safety Precautions
Before using the DMS2, read carefully these instructions.
After reading the instructions, keep this user's manual in a handy and safe place.
If a user is changed, you must hand over the manuals.
Never attempt to install the air conditioning system or to move the DMS2 by yourself.
WARNING
CAUTION
Do not attempt to install or repair this DMS2 by yourself.
This DMS2 contains no user-serviceable parts. Always consult authorized service personnel for repairs.
When moving, consult authorized service personnel for
disconnection and installation of the DMS2.
Ensure that the wall is strong enough to support the
weight of the DMS2.
Must install the DMS2 with rated power supply.In the event of a malfunction (burning smell, etc.),
immediately stop operation, turn off the electrical breaker, and consult authorized service personnel.

Do not use inflammable gases near the DMS2.

Do not spill water into the DMS2.

Do not operate the DMS2 with wet hands.

Do not install the DMS2 in a location where it will come into contact with the combustible gases, machine oil, sulphide gas, etc.

Do not press buttons with a pointed thing.

Do not pull or bend the DMS2 cable excessively.

Do not use this DMS2 for other purpose.

Do not spray an insecticide or other combustible things on the DMS2.

Do not clean the DMS2 with benzene, solvents or other chemicals.

Do not give a shock to the DMS2 or disassemble it by yourself.
E-3
Contents
GENERAL DESCRIPTION ...................................................... 4
VIEWING THE PARTS .......................................................... 6
BEFORE USE ..................................................................... 8
MAIN FUNCTION ............................................................. 10
STARTING DMS2 ........................................................... 14
CONTROL AND MONITORING ............................................. 18
ZONE MANAGEMENT ....................................................... 45
SCHEDULE ..................................................................... 50
EHP POWER CONSUMPTION INSPECTION ............................ 60
CONTROL LOGIC MANAGEMENT ........................................ 71
SYSTEM SETTINGS ........................................................... 84
PIM SETTING ............................................................... 131
CHECK BEFORE USING PANEL .......................................... 133
SETTING NETWORK INFORMATION ................................... 134
CHECKING INDOOR/OUTDOOR UNIT INFORMATION ............ 136
CHECKING DMS2 VERSION ............................................ 137
DATA BACKUP SETTING ................................................. 140
CHECKING ERROR INFORMATION ..................................... 142
RESET PASSWORD ......................................................... 143
BUTTON LOCK .............................................................. 144
SAFETY HALT ............................................................... 145
TROUBLESHOOTING ....................................................... 146
SPECIFICATIONS ............................................................ 148
LICENSE ....................................................................... 149
E-4
General Description
Introduction of DMS2 (Data Management Server2)
The DMS2 is an Internet based device for central management of Samsung system air-conditioners. It supports LAN & WAN and operates 24 hours without a separate PC.
Advantages of DMS2 System
The DMS2 provides the following advantages:
Everyday Device–The DMS2 is operational all year long 24 hours. Independent Operation–The DMS2 can operate schedule control, peak power control,
and power distribution without a PC.
Note In order to run peak power control and power distribution, relevant controllers
Internet Control
Web – The DMS2 has a built-in web server function and can be accessed from a
Using an Upper Level Controller–When a separate upper level controller (S-NET
Data Storage–The DMS2 has its own database built-in, therefore, trouble history,
Large Scale Management–At most 256 indoor units can be connected to one DMS2
Automatic ”e-mail” sending–When an error is occurred, inform the error details to an
need to be installed.
remote location to operate status monitoring, control, trouble history, and schedule setting of the system air-conditioners.
series) is used, a number of DMS2 can be controlled with one central management system.
indoor unit installation information, and power distribution data can be saved and retrieved.
and therefore, only one DMS2 can manage small and medium size buildings.
e-mail saved on DMS2.
E-5
Terms
DMS2: The abbreviation of Data Management Server2. Upper Controller: It means S-NET Series, a local controller of the DVM system.
Centralized Controller: A device that controls 16 groups of the DVM air conditioner.
Interface module: A data interface module of a DVM system which is located between
AHU(Air Handling Unit): Excutes heat exchange between air and cooling unit using
ERV(Energy Recovery Ventilator): Ventilating system using heat recover y function.
S-NET 3, S-NET mini and RMS are linked to a DMS2.
A central control device of a DVM system which is located between a DMS2 and an outdoor unit interface module.
a central controller and an outdoor unit.
central air conditioning duct method.
E-6
Viewing the Parts
Front View
No. Name Description
LCD Display Display current time/ Check menu
Menu button Access to main menu
/ button
Set button
Bottom cover
Select the function you want and set detailed functions in main menu
Check the function you want from main menu and select it
Unfasten 2 screws on the bottom and separate the bottom cover from DMS2. Then check cable connection part.
Indicator
Name Description
Power Turns blue when the power is supplied.
CPU Alive
Ethernet–Linked Turns green during normal connection.
Ethernet–Active Blinks in orange during normal transmission/reception.
COM1~5 – TX Blinks in green during normal transmission.
COM1~5 – RX Blinks in green during normal reception.
Check Turns green when notice occurs.
Blinks in orange with 1 second intervals during normal operation.
E-7
Bottom View
Separate bottom cover by unfastening 2 screws on the bottom.
DI Terminal2
Connect Digital Input
- Channel 6~Channel10
DI Terminal1
Connect Digital Input
- Channel 1~Channel 5
Power Terminal
Connect DMS2 adapter
Reset Button
Reset DMS2
Serial Terminal
Service agent checks error status
SD Card Socket
Socket for sub memory (SD or MMC) ( Sub memory is for DMS2 program update and set
information saving)
Purchase SD card separately.
DO Terminal1
Connect Digital Output
- Channel 1~Channel 5
DO Terminal 2
Connect Digital Output
- Channel 6~Channel 10
RS485 Communication terminal
Connect for RS485 communication with devices such as centralized controller/ interface module
- COM1 ~ COM5
Cable tie groove
Arrange cables connected to DMS2
LAN Terminal
Connect LAN cable
E-8
Before Use
System Configuration
S-NET mini
Centralized controller
Interface module
S-NET 3
DMS2
Interface module
Internet
Interface module
Connecting centralized controller and DMS2 ( type )
You can control up to 16 centralized controllers and 256 indoor units using DMS2.
Connecting interface module and DMS2 ( type)
- You can control up to 80 interface modules and 256 indoor units using DMS2. 16 interface modules can be connected to RS485 communication channel of DMS2.
- The more interface modules are connected, the longer time takes for tracking.
E-9
When connecting centralized controller and interface module to the DMS2 of same
communication channel, only one of them will communicate according to the communication channel mode setting of [System Settings]
[Tracking].
Therefore, do not connect the centralized controller and interface module to the same communication channel.
If you set the communication channel mode as interface module, virtual centralized
controller address will be assigned. Therefore if you connect centralized controller at the same time and set the address as virtual centralized controller address, it may
cause trouble for bringing device information. Channel 0: Virtual centralized controller 11, Channel 1: Virtual centralized controller 12, Channel 2: Virtual centralized controller 13, Channel 4: Virtual centralized controller 14, Channel 5: Virtual centralized controller 15
Web Browser Specification
Install Windows XP SP2, Windows 2000 SP4 or later version Install Internet Explorer 7.0 or later version
You can use Internet Explorer 6.0 but it is not recommended.
Install Silverlight 2.0 or later version
Note
Visit internet homepage (http://www.microsoft.
com/silverlight/) to download Silverlight. Or you can download it through the download link which is noticed automatically when the PC is connected to the Internet and you access to DMS2 for the first time.
Silverlight operates normally with Windows XP SP2 or
later version. It may not operate normally with former version of Windows.
Computer Settings for DMS2 Connection
All settings of DMS2 will be arranged in web page which built in DMS2. You should access to DMS2 IP to use DMS2 web page. There are 2 ways to access DMS2 IP. (For about settings, refer to installation manual.)
Static IP settingDynamic IP(DHCP) setting
E-10
Main Function
Interface with Upper Level Controller
The DMS2 receives/manages setting and control data from the upper level controller and sends the received data to the lower level system.
The upper level controllers of the DMS2 are the S-NET series
and the connectible S-NET series are S-NET 3, S-NET mini and RMS.
S-NET 3: System air conditioner controlling and monitoring
program that is used by installing on a PC.
S-NET mini: System air conditioner controlling and monitoring
device with touchscreen
RMS: A device which supervises operation status and break
down status by connecting to DMS2 for system air conditioner remote service. If break down is detected, it notifies service agent and makes fast service possible.
Save Trouble History
The DMS2 saves at most 1024 cases of trouble history. If the number of errors exceeds 1024, only the latest 1024 cases are stored by deleting the oldest trouble history.
Device name, address, error occurrence time, error solvation
time, trouble history will be saved. You can check it in web page or upper controller.
When an error occurs, it sends trouble history to e-mail saved
in DMS2.
Device Type
Indoor Unit
Outdoor Unit
Communication error such as centralized controller
Indoor unit communication error Indoor unit sensor related error Other errors
Outdoor unit communication error Pipe inspection error Outdoor unit sensor related error Outdoor unit related other errors
Option device related communication error
E-11
Set and Run Schedule
The schedule function of the DMS2 can be set through the Web or using the upper level controller. 1day/Everyday/Every week schedules can be set.
Each schedule can be used selectively by using the run
schedule/stop schedule order.
At most 256 schedules can be set. Indoor unit control is possible at least 1 minute of interval by
set schedule.
Item Content Remark
Schedule Period Starting and ending date of a schedule
Exception Day
Setup
Indoor unit to
be applied
Event
Set an exception day within a schedule period to ignore the schedule control
Select indoor units to receive schedule control
Set indoor unit operation modes
- Indoor unit On time
- Indoor unit Off time
- Set temperature
- Operation mode: Auto/Cool/Dry/Fan/Heat
- Remote control usage ON/OFF/Level1
- Fan speed: Auto/Low/Mid/High
- Air flow: None/Vertical/Horizontal/All
- ERV operation mode: Auto/HeatEx/ByPass/Sleep
- ERV Fan speed: Low/High/Turbo
Weekly Repeat: Maximum 10 events per day Daily Repeat: Maximum 70 events
E-12
Main Function (Continued)
Save Integrated Power Distribution Data
The DMS2 calculates and distributes the power consumed by each indoor unit by receiving the total power usage from the watt-hour meter interface modules (SIM/PIM) and taking into account the operation status of the indoor units. The DMS2 saves at most 1 year of data. After a year, the oldest data is deleted and the latest data is saved. This data can be checked through the built-in Web page of the DMS2 or by S-NET 3.
System Architecture
S-NET 3
Centralized controller
Watt-hour meter
DMS2
Up to
8 units
Internet
Web Client
Up to
8 units
SIM /PIM
Up to
8 units
Watt-hour meter
SIM /PIM
E-13
Time Segmentation
Time segmentation is used to divide 24 hours into different sections and to distribute
power according to each section.
This function is used when the power consumption fee is different according to
different time slots or when a building is charged differently depending on the consumption time.
Time can be divided into 1 section (A), 2 sections (A,B,A), and 3 sections (A,B,C,B,A). When the time is divided into 2 or 3 sections, you should install S-NET 3 to calculate or
check the distributed power on each section.
DMS2 will always show the result of the power distribution on section 1, regardless of
section 2 or 3.
Input manually (When setting 2 sections and 3 sections)
If communication error occurs between DMS and the lower level controllers, actual power consumption and the result of power distribution value may not be same. Make sure to solve communication error status.
- Communication error example : Between DMS2 and SIM/PIM
Between SIM/PIM and Watt-hour meter Between DMS2 and Centralized controller Between Centralized controller and interface module Between Interface module and indoor/outdoor units Between DMS2 and interface module
E-14
Starting DMS2
Starting DMS2
Current time setting
Set the current time of DMS2 system. “2009/01/01 01:01:01” is factory setting. Set the current time as DMS2 system time.
You can set DMS2 time in [System Settings] (Refer to page 104~105)
If DMS2 time does not set as the current time, DMS2 may cause malfunction when using Schedule or control logic management.
Connecting centralized controller & interface module
(1) Make sure that centralized controller communication cables(C1, C2) or interface module
communication cables(R1, R2) are connected.
For communication between DMS2 and centralized controller/interface module,
centralized controller communication cable(C1, C2) or interface module communication cable(R1, R2) should be connected.
(2) Execute tracking.
DMS2 communicates with centralized controller and interface module and brings
information about installed indoor unit and outdoor unit.
After tracking, you can use indoor unit control and other menu. For tracking, refer to [System Settings] [Tracking] (Refer to page 120~130)
[System environment setting]
E-15
Access to DMS2 & Login
Address bar
Run internet explorer on your computer.
1
Enter IP address (http://192.168.0.100) on the address bar,
2
and then press [ENTER].
If it is the first access to DMS2, “Install Microsoft Silverlight” message will be displayed.
- The message will not appear if Microsoft Silverlight have already installed. If the message window and login screen does not appear, check PC setting status.
3
Click [Run] and continue installation.
3
Access to DMS2 again after installation.
E-16
Starting DMS2 (Continued)
4
Enter ID and password when DMS2 main web page appears.
4
Then click [LOGIN].
The default DMS2 user ID is 'admin' and password is '1234'.Click [Connect] to log in as a regular user.Depending on authorization settings which set by the
administrator, access to some functions may be restricted.
To edit user authorization, refer to [System Settings]
[User authorization management]. (Refer to page 87)
Note
Only authorized users can access to web page.
Fewer than 5 concurrent users are recommended
DMS2 manager should change ID and password for
Logout: To log out, click [LOGOUT] on the top of the
because connection speed may slow down.
security and management. (Refer to page 85)
menu.
Silverlight will run normally with Windows XP SP2 or later version. With former version of Windows, DMS2 may not operate normally.
E-17
Logged-in User with No Authorization
When the screen above appears, ask for manager.
1
Depending on control authorization setting, there can be
a user who does not have control authorization.
Above screen will appear when the logged-in user does
not have control authorization.
E-18
Control and Monitoring
DMS2 Controllable Devices
Type Display Remote controller (Controlling range)
Indoor unit display icon
ERV display icon
AHU display icon
DI(Digital Input) display icon
DO(Digital Output) display icon
If the user select several devices, the remote controller of last selected device will be displayed on the screen.
E-19
Monitoring Indoor Unit Operation Status
1
Click [Control and Monitoring] when DMS2 web page menu
1
screen appears.
[Control and Monitoring] screen will appear when you
log-in to DMS2 web page.
2
Check the current status of all devices.
2
You can check current status of all installed indoor units,
ERV, AHU, DI and DO.
Note
 When the advanced functions (such as Sleep mode,
Energy saving function) are selected through wired/ wireless remote controllers or indoor unit panel, set operation mode on the remote controllers and DMS2 may be displayed differently. Also, when controlling by DMS2, additional functions will be canceled.
 Depending on the model of indoor unit, horizontal/
all air flow control may not be possible. In this case, vertical or fixed flow will be displayed depending on indoor unit’s basic operation specification.
 Devices such as AHU and ERV will be displayed only
when they are installed.
E-20
Control and Monitoring (Continued)
Controlling Indoor Unit
1
Status display window
2
Click [Control and Monitoring] when DMS2 web page menu
1
screen appears.
[Control and Monitoring] screen will appear when you
log-in to DMS2 web page.
Select indoor unit to control.
2
Check the indoor unit status through status display
window.
3
4
Turn the indoor unit on by clicking [ON].
3
Click [Detail].
4
E-21
5
7
Select the operation mode.
5
You can select Auto, Cool, Dry, Fan or Heat operation
mode.
Click [][] to set the desired temperature.
6
Each time you click the buttons, the temperature will be
adjusted by 1℃(
1°F).
If Auto/Cool/Dry mode is in operation, you can adjust the
desired temperature in the range of 18℃(65°F)
~
30℃(86°F).
If Heat mode is in operation, you can adjust the desired
temperature in the range of 16℃(61°F)~30℃(86°F)
You cannot adjust the desired temperature in Fan mode.When the operation mode of indoor unit is Cool or Dry
mode, you cannot set the desired temperature lower than lower limit temperature if lower limit is enabled.
When the operation mode of indoor unit is Heat mode,
you cannot set the desired temperature higher than upper limit temperature if upper limit is enabled.
6
.
Select the fan speed.
7
You can select Auto, Low, Mid or High.If Auto/Dry mode is in operation, fan speed will be set as
Auto fan speed.
If Fan mode is in operation, you cannot select Auto fan
speed.
E-22
Control and Monitoring (Continued)
8
9
Select the air flow.
8
You can select Vertical, Horizontal, All and None air flow.
Set remote controller settings.
9
You can select ON, OFF and Level1.When selecting [OFF], indoor unit control by wired/
wireless remote controller and indoor unit panel is not possible. Indoor unit control is only available in DMS2 web page.
Click [ON] when you want to use wired remote controller
in each room.
Note
When filter warning sign is displayed on indoor unit
status window
Select the indoor unit and click [Reset filter]. Filter warning will be released.
 Make sure that each indoor unit must be turned on to
control.
 Selecting remote controller, reset filter, operation
mode limits, setting lower/upper temperature limit are possible even if the power of indoor unit is off.
 Some air flow option may be restricted depending on
the indoor unit model.
E-23
Indoor Unit Operation Mode Limit
1
Status display window
2
Click [Control and Monitoring] when DMS2 web page menu
1
screen appears.
[Control and Monitoring] screen will appear when you
log-in to DMS2 web page.
Select indoor unit to control.
2
Check the indoor unit status through status display
window.
3
Click [Detail].
3
You can check and set operation mode, fan speed, air flow
and desired temperature of selected indoor unit.
E-24
Control and Monitoring (Continued)
4
Set operation mode limit.
4
You can select 'Cool only(Fan, Cool)’, ‘Heat only(Fan, Heat)’ and ‘No limits’.
- Cool only (Fan, Cool): If cooling only indoor unit operates in heat mode, indoor
- Heat only (Fan, Heat): If heating only indoor unit operates in cool mode, reset the
- No limits: You can use cooling only and heating only with no limits.
- Ex: If the cooling only indoor unit (with Fan mode set as alternative operation mode) operates in heating mode, DMS2 will detect it and reset the indoor unit in Fan mode.
Note
Operation mode limits setting is not available in ERV. Mixed operation can occur regardless of operation mode limits setting. If indoor unit with operation mode limit is in mixed operation, DMS2 solves
mixed operation status automatically by controlling the indoor unit in set operation mode.
unit operation will be reset to the alternative operation mode.
indoor unit as set operation mode.
In the following circumstances, all indoor units under the same outdoor unit
should be set to the same operation mode limits. Mixed operation can occur continuously when you set some of indoor unit to cool only and the other to heat only.
- If the centralized controller is MCM-A202 and is in group mode
- If the centralized controller is in group mode and the interface module is MIM-B13 or MIM-B04A
Except above  circumstances, DMS2 changes the operation mode limit of all
indoor units under the same outdoor unit to same operation mode limit.
- If the centralized controller is in group mode and is above MCM-A202A and all the interface modules under the centralized controller are above MIM-B13A
- If the centralized controller is in individual mode
If you set the cooling only indoor unit’s operation mode limit to heating only,
DMS2 may display Heating
Cooling alternately.
E-25
Setting Lower/Upper Temperature Limit of Indoor Unit
1
Status display window
2
Click [Control and Monitoring] when DMS2 web page menu
1
screen appears.
[Control and Monitoring] screen will appear when you
log-in to DMS2 web page.
Select indoor unit to control.
2
Check the indoor unit status through status display
window.
3
Click [Detail].
3
E-26
Control and Monitoring (Continued)
Set lower temperature limit by pressing [] and [].
4
You can set lower temperature limit by checking 'Apply'.When indoor unit is operating in cool mode, DMS2
controls indoor unit as lower temperature limit if the desired temperature is lower than lower temperature limit.
Lower temperature limit can be set in the range of
18℃(65°F)~30℃(86°F)
Check 'Apply' to apply the Lower temperature limit setting. When indoor unit is operating in Cool or Dry mode and
the low temperature limit is applied, you cannot set the desired temperature lower than the lower temperature limit.
4
5
.
Set upper temperature limit by pressing [] and [].
5
Check 'Apply' to apply the upper temperature limit setting. When indoor unit is operating in heat mode, DMS2
controls indoor unit as upper temperature limit if the desired temperature is higher than upper temperature limit.
Upper temperature limit can be set in the range of
16℃(61°F)~30℃(86°F)
Check 'Apply' to apply the lower temperature limit setting. When indoor unit is operating in Heat mode and the
upper temperature limit is applied, you cannot set the desired temperature higher than the upper temperature limit.
Note
Temperature limit in Cool/Heat mode setting is not
available in ERV.
If the indoor unit is in Auto(Cool)/Auto(Heat) mode,
lower/upper temperature limit will be applied when the indoor unit is operating in Auto mode. However, if the upper temperature limit is set to 16°C(61°F)~17°C(64°F), the upper temperature limit in Auto(Heat) mode is 18°C(65°F).
.
E-27
Monitoring AHU Operation Status
1
2
Click [Control and Monitoring] when DMS2 web page menu
1
screen appears.
[Control and Monitoring] screen will appear when you
log-in to DMS2 web page.
Check current status of AHU.
2
Note
To control AHU, refer to ‘Controlling indoor unit’ steps.
- AHU’s fan speed is fixed as high. (Refer to page 20~22)
- You cannot set air flow of AHU. To set the operation mode limit of AHU, refer to ‘Indoor
To set the lower/upper temperature limit of AHU,
unit operation mode limit’ steps. (Refer to page 23~24)
refer to ‘Setting lower/upper temperature limit of indoor unit’ steps. (Refer to page 25~26)
E-28
Control and Monitoring (Continued)
Monitoring ERV Operation Status
1
2
Click [Control and Monitoring] when DMS2 web page menu
1
screen appears.
[Control and Monitoring] screen will appear when you
log-in to DMS2 web page.
Check current status of ERV.
2
E-29
Controlling ERV
1
2
Click [Control and Monitoring] when DMS2 web page menu
1
screen appears.
[Control and Monitoring] screen will appear when you
log-in to DMS2 web page.
Select an ERV to control.
2
Check ERV status through status display window.
3
4
Turn ERV on by pressing [ON].
3
Click [Detail].
4
E-30
Control and Monitoring (Continued)
5
7
Select the operation mode.
5
You can select Auto, HeatEx, By pass and Sleep.
Select the fan speed.
6
You can select Low, High and Turbo.Fan speed is set to Low in sleep mode.
Set remote controller settings.
7
You can ON, OFF, Level1.When selecting [OFF], ERV control by wired/wireless
remote controller is not possible. ERV control is only available in DMS2 web page.
Click [ON] when you want to use wired remote controller in
each room.
Note
 When filter warning sign is displayed on ERV status
window
Select the ERV and click [Reset filter]. Filter warning will be released.
6
Make sure that ERV must be turned on to control. Selecting remote controller and filter reset are possible
even if the power of indoor unit is off.
Loading...
+ 158 hidden pages