Samsung MIM-B18 User Manual

Data Management Server2

MIM-D00A

BACnet Gateway

MIM-B17

LonWorks Gateway

MIM-B18

Air Conditioner

user manual

imagine the possibilities

Thank you for purchasing this Samsung product.

E DB98-32140A(3)

SafetyPrecautions

Before using the DMS2, read carefully these instructions.

After reading the instructions, keep this user's manual in a handy and safe place. If a user is changed, you must hand over the manuals.

Never attempt to install the air conditioning system or to move the DMS2 by yourself.

WARNING

CAUTION

DonotattempttoinstallorrepairthisDMS2byyourself.

ThisDMS2containsnouser-serviceableparts.

Alwaysconsultauthorizedservicepersonnelforrepairs.

Whenmoving,consultauthorizedservicepersonnelfor disconnectionandinstallationoftheDMS2.

Ensurethatthewallisstrongenoughtosupportthe weightoftheDMS2.

MustinstalltheDMS2withratedpowersupply.

Intheeventofamalfunction(burningsmell,etc.), immediatelystopoperation,turnofftheelectrical breaker,andconsultauthorizedservicepersonnel.

DonotuseinflammablegasesneartheDMS2. DonotspillwaterintotheDMS2.

DonotoperatetheDMS2withwethands.

DonotinstalltheDMS2inalocationwhereitwillcome intocontactwiththecombustiblegases,machineoil, sulphidegas,etc.

Donotpressbuttonswithapointedthing. DonotpullorbendtheDMS2cableexcessively. DonotusethisDMS2forotherpurpose.

Donotsprayaninsecticideorothercombustiblethings ontheDMS2.

DonotcleantheDMS2withbenzene,solventsorother chemicals.

DonotgiveashocktotheDMS2ordisassembleitby yourself.

E-2

Contents

 

GENERAL DESCRIPTION ......................................................

4

VIEWING THE PARTS ..........................................................

6

BEFORE USE .....................................................................

8

MAIN FUNCTION .............................................................

10

STARTING DMS2 ...........................................................

14

CONTROL AND MONITORING .............................................

18

ZONE MANAGEMENT .......................................................

45

SCHEDULE .....................................................................

50

EHPPOWER CONSUMPTION INSPECTION ............................

60

CONTROL LOGIC MANAGEMENT ........................................

71

SYSTEM SETTINGS ...........................................................

84

PIMSETTING ...............................................................

131

CHECK BEFORE USING PANEL ..........................................

133

SETTING NETWORK INFORMATION ...................................

134

CHECKING INDOOR/OUTDOOR UNIT INFORMATION ............

136

CHECKING DMS2VERSION ............................................

137

DATA BACKUP SETTING .................................................

140

CHECKING ERROR INFORMATION .....................................

142

RESET PASSWORD .........................................................

143

BUTTON LOCK ..............................................................

144

SAFETY HALT ...............................................................

145

TROUBLESHOOTING .......................................................

146

SPECIFICATIONS ............................................................

148

LICENSE .......................................................................

149

E-3

General Description

IntroductionofDMS2(DataManagementServer2)

The DMS2 is an Internet based device for central management of Samsung system air-conditioners. It supports LAN & WAN and operates 24 hours without a separate PC.

AdvantagesofDMS2System

The DMS2 provides the following advantages:

Everyday Device–The DMS2 is operational all year long 24 hours.

Independent Operation–The DMS2 can operate schedule control, peak power control, and power distribution without a PC.

Note In order to run peak power control and power distribution, relevant controllers need to be installed.

Internet Control

Web – The DMS2 has a built-in web server function and can be accessed from a remote location to operate status

monitoring, control, trouble history, and schedule setting of the system air-conditioners.

Using an Upper Level Controller–When a separate upper level controller (S-NET series) is used, a number of DMS2 can be controlled with one central management system.

Data Storage–The DMS2 has its own database built-in, therefore, trouble history, indoor unit installation information, and power distribution data can be saved and retrieved.

Large Scale Management–At most 256 indoor units can be connected to one DMS2 and therefore, only one DMS2 can manage small and medium size buildings.

Automatic ”e-mail” sending–When an error is occurred, inform the error details to an e-mail saved on DMS2.

E-4

Terms

DMS2: The abbreviation of Data Management Server2.

Upper Controller: It means S-NET Series, a local controller of the DVM system.

S-NET 3, S-NET mini and RMS are linked to a DMS2.

Centralized Controller: A device that controls 16 groups of the DVM air conditioner. A central control device of a DVM system which is located between a DMS2 and an outdoor unit interface module.

Interface module: A data interface module of a DVM system which is located between a central controller and an outdoor unit.

AHU(Air Handling Unit): Excutes heat exchange between air and cooling unit using central air conditioning duct method.

ERV(Energy Recovery Ventilator): Ventilating system using heat recovery function.

E-5

ViewingtheParts

FrontView

No.

Name

Description

 

 

 

LCDDisplay

Displaycurrenttime/Checkmenu

 

 

 

 

Menubutton

Accesstomainmenu

 

 

 

▼/▲button

Selectthefunctionyouwantandsetdetailedfunctionsin

 

mainmenu

 

Setbutton

Checkthefunctionyouwantfrommainmenu

 

andselectit

 

 

 

 

 

Bottomcover

Unfasten2screwsonthebottomandseparatethebottom

 

 

coverfromDMS2.Thencheckcableconnectionpart.

Indicator

Name

Description

 

 

Power

Turnsbluewhenthepowerissupplied.

 

 

CPUAlive

Blinksinorangewith1secondintervalsduringnormal

operation.

 

Ethernet–Linked

Turnsgreenduringnormalconnection.

 

 

Ethernet–Active

Blinksinorangeduringnormaltransmission/reception.

 

 

COM1~5–TX

Blinksingreenduringnormaltransmission.

 

 

COM1~5–RX

Blinksingreenduringnormalreception.

 

 

Check

Turnsgreenwhennoticeoccurs.

 

 

E-6

BottomView

Separate bottom cover by unfastening 2 screws on the bottom.

DITerminal2

DOTerminal1

Connect Digital Input

Connect Digital Output

- Channel 6~Channel10

- Channel 1~Channel 5

DITerminal1

DOTerminal 2

Connect Digital Input

Connect Digital Output

- Channel 1~Channel 5

- Channel 6~Channel 10

 

RS485

 

Communication

Power

terminal

Terminal

Connect for RS485

Connect

communication

DMS2 adapter

with devices such as

 

centralized controller/

Reset Button

interface module

- COM1 ~ COM5

Reset DMS2

 

SerialTerminal

Cable tie groove

Arrange cables connected to

Service agent checks error

DMS2

status

LANTerminal

SD Card Socket

Connect LAN cable

 

Socket for sub memory (SD or MMC)

 

(Sub memory is for DMS2 program update and set

 

information saving)

 

PurchaseSDcardseparately.

 

E-7

BeforeUse

SystemConfiguration

S-NETmini S-NET3

 

Internet

 

DMS2

 

 

Centralized controller

Interfacemodule

Interfacemodule

 

Interfacemodule

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ConnectingcentralizedcontrollerandDMS2( type)

Youcancontrolupto16centralizedcontrollersand256indoorunitsusingDMS2.

ConnectinginterfacemoduleandDMS2( type)

-Youcancontrolupto80interfacemodulesand256indoorunitsusingDMS2.

16interfacemodulescanbeconnectedtoRS485communicationchannelofDMS2. -Themoreinterfacemodulesareconnected,thelongertimetakesfortracking.

E-8

When connecting centralized controller and interface module to the DMS2 of same communication channel, only one of them will communicate according to the communication channel mode setting of [System Settings][Tracking].

Therefore, do not connect the centralized controller and interface module to the same communication channel.

If you set the communication channel mode as interface module, virtual centralized controller address will be assigned. Therefore if you connect centralized controller at the same time and set the address as virtual centralized controller address, it may cause trouble for bringing device information.

Channel 0: Virtual centralized controller 11,

Channel 1: Virtual centralized controller 12,

Channel 2: Virtual centralized controller 13,

Channel 4: Virtual centralized controller 14,

Channel 5: Virtual centralized controller 15

WebBrowserSpecification

Install Windows XP SP2, Windows 2000 SP4 or later version

InstallInternet Explorer 7.0 or later version

You can use Internet Explorer 6.0 but it is not recommended. Install Silverlight 2.0 or later version

Note Visitinternethomepage(http://www.microsoft. com/silverlight/)todownloadSilverlight.Oryoucan downloaditthroughthedownloadlinkwhichisnoticed automaticallywhenthePCisconnectedtotheInternet andyouaccesstoDMS2forthefirsttime.

SilverlightoperatesnormallywithWindowsXPSP2or laterversion.

Itmaynotoperatenormallywithformerversionof Windows.

ComputerSettingsforDMS2Connection

All settings of DMS2 will be arranged in web page which built in DMS2.

You should access to DMS2 IP to use DMS2 web page. There are 2 ways to access DMS2 IP.

(For about settings, refer to installation manual.)

Static IP setting

E-9

Dynamic IP(DHCP) setting

MainFunction

InterfacewithUpperLevelController

TheDMS2receives/managessettingandcontroldatafromthe upperlevelcontrollerandsendsthereceiveddatatothelower levelsystem.

TheupperlevelcontrollersoftheDMS2aretheS-NETseries andtheconnectibleS-NETseriesareS-NET3,S-NETminiand RMS.

S-NET3: Systemairconditionercontrollingandmonitoring programthatisusedbyinstallingonaPC.

S-NETmini:Systemairconditionercontrollingandmonitoring devicewithtouchscreen

RMS:Adevicewhichsupervisesoperationstatusandbreak downstatusbyconnectingtoDMS2forsystemair conditionerremoteservice.Ifbreakdownisdetected, itnotifiesserviceagentandmakesfastservicepossible.

SaveTroubleHistory

The DMS2 saves at most 1024 cases of trouble history.

If the number of errors exceeds 1024, only the latest 1024 cases are stored by deleting the oldest trouble history.

Device name, address, error occurrence time, error solvation time, trouble history will be saved. You can check it in web page or upper controller.

When an error occurs, it sends trouble history to e-mail saved in DMS2.

Device

Type

 

 

 

Indoorunitcommunicationerror

IndoorUnit

Indoorunitsensorrelatederror

 

Othererrors

 

 

 

Outdoorunitcommunicationerror

OutdoorUnit

Pipeinspectionerror

Outdoorunitsensorrelatederror

 

 

Outdoorunitrelatedothererrors

 

 

Communicationerror

Optiondevicerelatedcommunication

suchascentralizedcontroller

error

 

 

E-10

SetandRunSchedule

The schedule function of the DMS2 can be set through the Web or using the upper level controller. 1day/Everyday/Every week schedules can be set.

Each schedule can be used selectively by using the run schedule/stop schedule order.

At most 256 schedules can be set.

Indoor unit control is possible at least 1 minute of interval by set schedule.

Item

Content

Remark

 

 

 

SchedulePeriod

Startingandendingdateofaschedule

 

 

 

 

ExceptionDay

Setanexceptiondaywithinascheduleperiodto

 

Setup

ignoretheschedulecontrol

 

 

 

 

Indoorunitto

Selectindoorunitstoreceiveschedulecontrol

 

beapplied

 

 

 

 

 

 

 

Setindoorunitoperationmodes

 

 

-IndoorunitOntime

 

 

-IndoorunitO time

WeeklyRepeat:

 

-Settemperature

Maximum10events

 

-Operationmode:Auto/Cool/Dry/Fan/Heat

Event

perday

-RemotecontrolusageON/OFF/Level1

 

DailyRepeat:

 

-Fanspeed:Auto/Low/Mid/High

 

Maximum70events

 

-Airflow:None/Vertical/Horizontal/All

 

-ERVoperationmode:Auto/HeatEx/ByPass/Sleep

 

 

-ERVFanspeed:Low/High/Turbo

 

 

 

 

E-11

MainFunction(Continued)

SaveIntegratedPowerDistributionData

TheDMS2calculatesanddistributesthepowerconsumedbyeachindoorunitby receivingthetotalpowerusagefromthewatt-hourmeterinterfacemodules(SIM/PIM) andtakingintoaccounttheoperationstatusoftheindoorunits.

TheDMS2savesatmost1yearofdata.Afterayear,theoldestdataisdeletedand thelatestdataissaved.Thisdatacanbecheckedthroughthebuilt-inWebpageof theDMS2orbyS-NET3.

System Architecture

S-NET3

Internet

WebClient

 

 

DMS2

Upto 8units

Centralizedcontroller

SIM/PIM

SIM/PIM

 

Upto

Upto

 

8units

8units

 

Watt-hourmeter

Watt-hourmeter

E-12

Time Segmentation

Timesegmentationisusedtodivide24hoursintodifferentsectionsandtodistribute poweraccordingtoeachsection.

Thisfunctionisusedwhenthepowerconsumptionfeeisdifferentaccordingto differenttimeslotsorwhenabuildingischargeddifferentlydependingonthe consumptiontime.

Timecanbedividedinto1section(A),2sections(A,B,A),and3sections(A,B,C,B,A).

Whenthetimeisdividedinto2or3sections,youshouldinstallS-NET3tocalculateor checkthedistributedpoweroneachsection.

DMS2willalwaysshowtheresultofthepowerdistributiononsection1,regardlessof section2or3.

Inputmanually(Whensetting2sectionsand3sections)

If communication error occurs between DMS and the lower level controllers, actual power consumption and the result of power distribution value may not be same. Make sure to solve communication error status.

- Communication error example : Between DMS2 and SIM/PIM

Between SIM/PIM and Watt-hour meter

Between DMS2 and Centralized controller

Between Centralized controller and interface module

Between Interface module and indoor/outdoor units Between DMS2 and interface module

E-13

StartingDMS2

StartingDMS2

Current time setting

SetthecurrenttimeofDMS2system.

“2009/01/0101:01:01”isfactorysetting.SetthecurrenttimeasDMS2systemtime. YoucansetDMS2timein[SystemSettings][Systemenvironmentsetting] (Refertopage104~105)

If DMS2 time does not set as the current time, DMS2 may cause malfunction when using Schedule or control logic management.

Connecting centralized controller & interface module

(1)Makesurethatcentralizedcontrollercommunicationcables(C1,C2)orinterfacemodule communicationcables(R1,R2)areconnected.

ForcommunicationbetweenDMS2andcentralizedcontroller/interfacemodule, centralizedcontrollercommunicationcable(C1,C2)orinterfacemodule communicationcable(R1,R2)shouldbeconnected.

(2)Executetracking.

DMS2communicateswithcentralizedcontrollerandinterfacemoduleandbrings informationaboutinstalledindoorunitandoutdoorunit.

Aftertracking,youcanuseindoorunitcontrolandothermenu.

Fortracking,referto[SystemSettings][Tracking](Refertopage120~130)

E-14

AccesstoDMS2&Login

Address bar

3

1Run internet explorer on your computer.

2Enter IP address (http://192.168.0.100) on the address bar, and then press [ENTER].

If it is the first access to DMS2, “Install Microsoft Silverlight” message will be displayed.

-The message will not appear if Microsoft Silverlight have already installed.

If the message window and login screen does not appear, check PC setting status.

3Click [Run] and continue installation.

Access to DMS2 again after installation.

E-15

StartingDMS2(Continued)

4

4EnterIDandpasswordwhenDMS2mainwebpageappears. Thenclick[LOGIN].

ThedefaultDMS2userIDis'admin'andpasswordis'1234'.

Click[Connect]tologinasaregularuser.

Dependingonauthorizationsettingswhichsetbythe administrator,accesstosomefunctionsmayberestricted.

Toedituserauthorization,referto [SystemSettings][Userauthorizationmanagement].(Refertopage87)

Note Onlyauthorizeduserscanaccesstowebpage.

Fewerthan5concurrentusersarerecommended becauseconnectionspeedmayslowdown.

DMS2managershouldchangeIDandpasswordfor securityandmanagement.(Refertopage85)

Logout:Tologout,click[LOGOUT]onthetopofthe menu.

Silverlight will run normally with Windows XP SP2 or later version. With former version of Windows, DMS2 may not operate normally.

E-16

Logged-inUserwithNoAuthorization

1When the screen above appears, ask for manager. Dependingon control authorization setting, there can be

a user who does not have control authorization. Abovescreenwillappearwhenthelogged-inuserdoes

nothavecontrolauthorization.

E-17

ControlandMonitoring

DMS2ControllableDevices

Type

Display

Remotecontroller(Controllingrange)

Indoor unit display icon

ERV display icon

AHU display icon

DI(Digital Input) display icon

DO(Digital Output) display icon

If the user select several devices, the remote controller of last selected device will be displayed on the screen.

E-18

MonitoringIndoorUnitOperationStatus

1

2

1Click[ControlandMonitoring]whenDMS2webpagemenu screenappears.

[ControlandMonitoring]screenwillappearwhenyou log-intoDMS2webpage.

2Checkthecurrentstatusofalldevices.

Youcancheckcurrentstatusofallinstalledindoorunits, ERV,AHU,DIandDO.

Note Whentheadvancedfunctions(suchasSleepmode, Energysavingfunction)areselectedthroughwired/ wirelessremotecontrollersorindoorunitpanel, setoperationmodeontheremotecontrollersand DMS2maybedisplayeddifferently.Also,when controllingbyDMS2,additionalfunctionswillbe canceled.

Dependingonthemodelofindoorunit,horizontal/ allairflowcontrolmaynotbepossible.Inthiscase, verticalorfixedflowwillbedisplayeddependingon indoorunit’sbasicoperationspecification.

DevicessuchasAHUandERVwillbedisplayedonly

whentheyareinstalled.

E-19

Samsung MIM-B18 User Manual

ControlandMonitoring(Continued)

ControllingIndoorUnit

1

Statusdisplaywindow

2

34

1Click[ControlandMonitoring]whenDMS2webpagemenu screenappears.

[ControlandMonitoring]screenwillappearwhenyou log-intoDMS2webpage.

2Selectindoorunittocontrol.

Checktheindoorunitstatusthroughstatusdisplay window.

3Turntheindoorunitonbyclicking[ON].

4Click[Detail].

E-20

5

7

6

5Selecttheoperationmode.

YoucanselectAuto,Cool,Dry,FanorHeatoperation mode.

6Click[ ][ ]tosetthedesiredtemperature.

Eachtimeyouclickthebuttons,thetemperaturewillbe adjustedby1 (1°F).

IfAuto/Cool/Drymodeisinoperation,youcanadjustthe

desiredtemperatureintherangeof18 (65°F)~ 30 (86°F).

IfHeatmodeisinoperation,youcanadjustthedesired temperatureintherangeof16 (61°F)~30 (86°F).

YoucannotadjustthedesiredtemperatureinFanmode.

WhentheoperationmodeofindoorunitisCoolorDry mode,youcannotsetthedesiredtemperaturelowerthan lowerlimittemperatureiflowerlimitisenabled.

WhentheoperationmodeofindoorunitisHeatmode, youcannotsetthedesiredtemperaturehigherthanupper limittemperatureifupperlimitisenabled.

7Selectthefanspeed.

YoucanselectAuto,Low,MidorHigh.

IfAuto/Drymodeisinoperation,fanspeedwillbesetas Autofanspeed.

IfFanmodeisinoperation,youcannotselectAutofan speed.

E-21

ControlandMonitoring(Continued)

8

9

8Selecttheairflow.

YoucanselectVertical,Horizontal,AllandNoneairflow.

9Setremotecontrollersettings.

YoucanselectON,OFFandLevel1.

Whenselecting[OFF],indoorunitcontrolbywired/ wirelessremotecontrollerandindoorunitpanelisnot possible.IndoorunitcontrolisonlyavailableinDMS2web page.

Click[ON]whenyouwanttousewiredremotecontroller ineachroom.

Note Whenfilterwarningsignisdisplayedonindoorunit statuswindow

Selecttheindoorunitandclick[Resetfilter]. Filterwarningwillbereleased.

Makesurethateachindoorunitmustbeturnedonto control.

Selectingremotecontroller,resetfilter,operation modelimits,settinglower/uppertemperaturelimitare possibleevenifthepowerofindoorunitisoff.

Someairflowoptionmayberestricteddependingon theindoorunitmodel.

E-22

IndoorUnitOperationModeLimit

1

Statusdisplaywindow

2

1Click[ControlandMonitoring]whenDMS2webpagemenu screenappears.

[ControlandMonitoring]screenwillappearwhenyou log-intoDMS2webpage.

2Selectindoorunittocontrol.

Checktheindoorunitstatusthroughstatusdisplay window.

3 Click[Detail].

Youcancheckandsetoperationmode,fanspeed,airflow anddesiredtemperatureofselectedindoorunit.

3

E-23

ControlandMonitoring(Continued)

4

4Setoperationmodelimit.

Youcanselect'Coolonly(Fan,Cool)’,‘Heatonly(Fan,Heat)’and‘Nolimits’.

-Coolonly(Fan,Cool):Ifcoolingonlyindoorunitoperatesinheatmode,indoor unitoperationwillberesettothealternativeoperation mode.

-Heatonly(Fan,Heat):Ifheatingonlyindoorunitoperatesincoolmode,resetthe indoorunitassetoperationmode.

-Nolimits:Youcanusecoolingonlyandheatingonlywithnolimits.

-Ex:Ifthecoolingonlyindoorunit(withFanmodesetasalternativeoperation mode)operatesinheatingmode,DMS2willdetectitandresettheindoorunit inFanmode.

Note OperationmodelimitssettingisnotavailableinERV.

Mixedoperationcanoccurregardlessofoperationmodelimitssetting.

Ifindoorunitwithoperationmodelimitisinmixedoperation,DMS2solves mixedoperationstatusautomaticallybycontrollingtheindoorunitinset operationmode.

In the following circumstances, all indoor units under the same outdoor unit should be set to the same operation mode limits. Mixed operation can occur continuously when you set some of indoor unit to cool only and the other to heat only.

-If the centralized controller is MCM-A202 and is in group mode

-If the centralized controller is in group mode and the interface module is MIM-B13 or MIM-B04A

Except above circumstances, DMS2 changes the operation mode limit of all indoor units under the same outdoor unit to same operation mode limit.

-If the centralized controller is in group mode and is above MCM-A202A and all the interface modules under the centralized controller are above MIM-B13A

-If the centralized controller is in individual mode

If you set the cooling only indoor unit’s operation mode limit to heating only, DMS2 may display Heating Cooling alternately.

E-24

SettingLower/UpperTemperatureLimitofIndoorUnit

1

Statusdisplaywindow

2

1Click[ControlandMonitoring]whenDMS2webpagemenu screenappears.

[ControlandMonitoring]screenwillappearwhenyou log-intoDMS2webpage.

2Selectindoorunittocontrol.

Checktheindoorunitstatusthroughstatusdisplay window.

3Click[Detail].

3

E-25

ControlandMonitoring(Continued)

4 5

4Setlowertemperaturelimitbypressing[ ]and[ ].

Youcansetlowertemperaturelimitbychecking'Apply'.

Whenindoorunitisoperatingincoolmode,DMS2 controlsindoorunitaslowertemperaturelimitifthe desiredtemperatureislowerthanlowertemperaturelimit.

Lowertemperaturelimitcanbesetintherangeof 18 (65°F)~30 (86°F).

Check'Apply'toapplytheLowertemperaturelimitsetting.

WhenindoorunitisoperatinginCoolorDrymodeand thelowtemperaturelimitisapplied,youcannotsetthe desiredtemperaturelowerthanthelowertemperature limit.

5Setuppertemperaturelimitbypressing[ ]and[ ].

Check'Apply'toapplytheuppertemperaturelimitsetting.

Whenindoorunitisoperatinginheatmode,DMS2 controlsindoorunitasuppertemperaturelimitifthe desiredtemperatureishigherthanuppertemperature limit.

Uppertemperaturelimitcanbesetintherangeof 16 (61°F)~30 (86°F).

Check'Apply'toapplythelowertemperaturelimitsetting.

WhenindoorunitisoperatinginHeatmodeandthe uppertemperaturelimitisapplied,youcannotsetthe desiredtemperaturehigherthantheuppertemperature limit.

Note TemperaturelimitinCool/Heatmodesettingisnot availableinERV.

IftheindoorunitisinAuto(Cool)/Auto(Heat)mode, lower/uppertemperaturelimitwillbeappliedwhen

 

theindoorunitisoperatinginAutomode.

 

However,iftheuppertemperaturelimitissetto

E-26

16°C(61°F)~17°C(64°F),theuppertemperaturelimitin

Auto(Heat)modeis18°C(65°F).

 

MonitoringAHUOperationStatus

1

2

1Click[ControlandMonitoring]whenDMS2webpagemenu screenappears.

[ControlandMonitoring]screenwillappearwhenyou log-intoDMS2webpage.

2CheckcurrentstatusofAHU.

Note TocontrolAHU,referto‘Controllingindoorunit’steps. -AHU’sfanspeedisfixedashigh.(Refertopage20~22) -YoucannotsetairflowofAHU.

TosettheoperationmodelimitofAHU,referto‘Indoor unitoperationmodelimit’steps.(Refertopage23~24)

Tosetthelower/uppertemperaturelimitofAHU, referto‘Settinglower/uppertemperaturelimitof indoorunit’steps.(Refertopage25~26)

E-27

ControlandMonitoring(Continued)

MonitoringERVOperationStatus

1

2

1Click[ControlandMonitoring]whenDMS2webpagemenu screenappears.

[ControlandMonitoring]screenwillappearwhenyou log-intoDMS2webpage.

2CheckcurrentstatusofERV.

E-28

ControllingERV

1

3

4

2

1Click[ControlandMonitoring]whenDMS2webpagemenu screenappears.

[ControlandMonitoring]screenwillappearwhenyou log-intoDMS2webpage.

2SelectanERVtocontrol.

CheckERVstatusthroughstatusdisplaywindow.

3TurnERVonbypressing[ON].

4Click[Detail].

E-29

ControlandMonitoring(Continued)

56

7

5Selecttheoperationmode.

YoucanselectAuto,HeatEx,BypassandSleep.

6Selectthefanspeed.

YoucanselectLow,HighandTurbo.

FanspeedissettoLowinsleepmode.

7Setremotecontrollersettings.

YoucanON,OFF,Level1.

Whenselecting[OFF],ERVcontrolbywired/wireless remotecontrollerisnotpossible.ERVcontrolisonly availableinDMS2webpage.

Click[ON]whenyouwanttousewiredremotecontrollerin eachroom.

Note WhenfilterwarningsignisdisplayedonERVstatus window

SelecttheERVandclick[Resetfilter].Filterwarningwillbe released.

MakesurethatERVmustbeturnedontocontrol.

Selectingremotecontrollerandfilterresetarepossible evenifthepowerofindoorunitisoff.

E-30

Loading...
+ 158 hidden pages