Samson TROVIS 6495 Series, TROVIS 6495-2 Mounting And Operating Instructions

Series 6495 Industrial Controller TROVIS 6495-2
Mounting and Operating Instructions
EB 6495-2 EN
®
Firmware version 1.11 Edition December 2009
Definitions of the signal words used in these instructions
!
DANGER!
DANGER indicates a hazardous situation which, if not avoided, will result in death or
NOTICE
NOTICE indicates a property damage mes sage.
serious injury.
-
2 EB 6495-2 EN
Note: Supplementary explanations, informa tion and tips
-
Contents
Contents Page
1 Important safety instructions . . . . . . . . . . . . . . . . . . . . . . 5
2 Device version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1 Article code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.2 Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.1 Operation structure . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.2 Display and operator controls . . . . . . . . . . . . . . . . . . . . . 13
6 Operating level . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.1 Changing the set point. . . . . . . . . . . . . . . . . . . . . . . . . 16
6.2 Switching over to manual mode and changing the output . . . . . . . . . 16
6.3 Opening/closing cascade . . . . . . . . . . . . . . . . . . . . . . . 17
7 Info menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
8 Operating menu . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
8.1 Entering the operating menu . . . . . . . . . . . . . . . . . . . . . . 23
8.2 Changing the control parameters. . . . . . . . . . . . . . . . . . . . 23
8.3 Switching over internal/external set point. . . . . . . . . . . . . . . . 25
8.4 Switching over between internal set points and changing them . . . . . 25
9 Configuration menu. . . . . . . . . . . . . . . . . . . . . . . . . . 29
9.1 Entering the configuration level . . . . . . . . . . . . . . . . . . . . 29
9.2 Configuring the controller . . . . . . . . . . . . . . . . . . . . . . . 30
9.2.1 Setting configuration items. . . . . . . . . . . . . . . . . . . . . . . 30
9.2.2 Configuration example . . . . . . . . . . . . . . . . . . . . . . . . 31
9.3 Adapting the display . . . . . . . . . . . . . . . . . . . . . . . . . 33
9.3.1 Changing the controller display . . . . . . . . . . . . . . . . . . . . 33
9.3.2 Setting up additional display. . . . . . . . . . . . . . . . . . . . . . 35
9.3.3 Switching Controller [1] and Controller [2] displays . . . . . . . . . . . 38
10 Locking the controller . . . . . . . . . . . . . . . . . . . . . . . . . 41
10.1 Locking the operating level. . . . . . . . . . . . . . . . . . . . . . . 41
10.2 Locking all keys over a digital input . . . . . . . . . . . . . . . . . . 42
10.3 Activating key number operation . . . . . . . . . . . . . . . . . . . 43
11 User calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
11.1 Calibrating analog inputs . . . . . . . . . . . . . . . . . . . . . . . 45
EB 6495-2 EN 3
Contents
11.2 Calibrating analog outputs. . . . . . . . . . . . . . . . . . . . . . . 45
12 Fault alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
13 Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
13.1 Infrared interface . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
13.2 Optional interface boards . . . . . . . . . . . . . . . . . . . . . . . 50
13.2.1 RS-232/USB interface board . . . . . . . . . . . . . . . . . . . . . 50
13.2.2 RS-485/USB interface board . . . . . . . . . . . . . . . . . . . . . 51
13.3 SAMSON memory pen . . . . . . . . . . . . . . . . . . . . . . . . 53
14 Setting and operation with TROVIS-VIEW software . . . . . . . . . . 55
14.1 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
14.1.1 System requirements. . . . . . . . . . . . . . . . . . . . . . . . . . 55
14.2 Installing TROVIS-VIEW software. . . . . . . . . . . . . . . . . . . . 56
14.3 Starting TROVIS-VIEW and performing settings . . . . . . . . . . . . . 57
14.3.1 Configuring the controller . . . . . . . . . . . . . . . . . . . . . . . 60
14.3.2 Reading information. . . . . . . . . . . . . . . . . . . . . . . . . . 62
14.4 Operational data graphs (Trend Viewer) . . . . . . . . . . . . . . . . 64
14.5 Data transmission . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
14.5.1 Setting up communication port . . . . . . . . . . . . . . . . . . . . . 66
14.5.2 Online operation (direct data transmission) . . . . . . . . . . . . . . . 67
14.5.3 Offline operation (indirect data transmission) . . . . . . . . . . . . . . 67
14.5.4 Data transmission between TROVIS-VIEW and memory pen. . . . . . . 68
15 Appendix. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
15.1 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
15.2 Configuration list . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
15.3 Abbreviations used. . . . . . . . . . . . . . . . . . . . . . . . . . 145
15.4 Block diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
4 EB 6495-2 EN
1 Important safety instructions
Important safety instructions
For your own safety, follow these instructions concerning the mounting, start-up and opera tion of the industrial controller:
The industrial controller may only be mounted, started up or operated by trained and
4
experienced personnel familiar with the product. According to these Mounting and Operating Instructions, trained personnel refers to individuals who are able to judge the work they are assigned to and recognize possi ble dangers due to their specialized training, their knowledge and experience as well as their knowledge of the relevant standards.
The controller is intended for use in low-voltage installations.
4
For wiring and maintenance, you are required to observe the relevant safety regula tions.
To avoid damage to any equipment, the following also applies:
Proper shipping and appropriate storage are assumed.
4
-
-
-
EB 6495-2 EN 5
Device version
2 Device version
2.1 Article code
Industrial Controller TROVIS 6495-2 x
Supply voltage
85 to 264 V AC 24 V AC/DC
1 2
2.2 Accessories
Accessories Order no.
TROVIS-VIEW Configuration
and Operator Interface.......... 6661-1033
Infrared adapter (RS-232)...... 8864-0900
Bracket for infrared adapter... 1400-9769
USB 1.1 serial adapter........... 8812-2001
RS-232/USB interface board.. 1400-9917 RS-485/USB interface board.. 1400-9918 USB cable (2 m) with type A
and 5-pin mini-B connectors... 8801-7301 Connecting cable
RJ 12/D-sub 9-pin (RS-232)... 1400-7699
Memory pen (RS-232)........... 1400-9753
Modular adapter
RJ 12/D-sub 9-pin................. 1400-7698
6 EB 6495-2 EN
Installation
3 Installation
The TROVIS 6495-2 Industrial Controller is designed for panel mounting. Its front case has the dimensions 96 x 96 mm.
NOTICE
When installing several TROVIS 6495-2 In dustrial Controllers, the minimum distance between each controller as shown in Fig. 1 must be kept!
Mounting
clips
96 (3.78")
96 (3.78")
91.2 (3.59")
1. Prepare a panel cut-out with the dimen sions 92
+0.8
x 92
+0.8
2. Push the industrial controller into the panel cut-out from the front.
3. Insert the two mounting clips in the notches on the top and bottom.
4. Turn the threaded rods in the direction
-
of the control panel using a screw driver, clamping the case against the control panel.
Terminal strips
12 34
150 (5.90")
156 (6.14")
Slot for interface board
-
mm.
-
Panel cut-out and minimum distances when installing several controllers
Fig. 1 · Installation
>30
Panel
cut-out
>15
92
(3.62"
+0.8
+0.3
)
)
+0.3
+0.8
92
(3.62"
EB 6495-2 EN 7
Electrical connection
4 Electrical connection
!
Risk of electric shock!
When installing electric cables, you are re quired to observe the regulations governing electrical power plant installation in the country where the controller is to be in stalled.
Installation notes
Install the power supply lines and the sig
nal lines separately! Do not install them parallel to each other! To improve noise immunity, observe a minimum distance of 10 cm between the power line and the measuring input line. The lines for the dig­ital signals (bus lines) as well as the ana­log signal lines (sensor lines, analog in­puts and outputs) must also be routed using separate cables.
To avoid measurement errors or other dis­turbances, use shielded cables for the an­alog and binary signal lines and bus lines. Ground the shield at one end, either at the controller inlet or at the control cab inet outlet, using the largest possible cross-section. Connect the central ground ing point and the PE grounding conductor with a cable≥10 mm² using the shortest route.
Inductances in the control cabinet, e.g. contactor coils, are to be equipped with suitable interference suppressors (RC ele ments).
Control cabinet elements with high field strength, e.g. transformers or frequency converters, are to be shielded with sepa
-
rators providing a good ground connec tion.
The controller has screw terminals for
1.5 mm² wires (0.5 to 1.5 mm² wire
-
cross-section). The lines are connected to the terminal strips
1 to 4 as shown in the following connection diagrams 2a to 2c.
Transmitter supply
The controller has a supply output to power
­a maximum of four two-wire transmitters
(21 V DC, 90 mA).
Resistance thermometer
The analog inputs AI1 to AI4 are designed for the connection of resistance thermome­ters Pt 100 and Pt 1000 in a three-wire cir­cuit. The resistance of each connection lead must be the same and not exceed 15Ω. Lead calibration is not necessary.
Resistance thermometers can also be con­nected in two-wire circuits. In this case, connect a jumper between the controller ter
-
minals. Take into account that the lead resis tance may reach several ohms over long
-
distances, causing the measured value to be considerably distorted. This measured value can be balanced out using a correction value (configuration item
I.1.4/I.2.4/I.3.4/I.4.4 Input signal increase/decrease, see section 15.2).
-
-
-
-
-
8 EB 6495-2 EN
Electrical connection
Potentiometer
The analog input AI2 is designed for the connection of a potentiometer. Potentiome ters between 50 and 1200Ωcan be connected.
A potentiometer is used, for example for po sition feedback of an electrical actuator or for input of an external set point.
Terminal strip 1
DIP switches:
( 
)
* & 
 
'&
&

 

"
% 
$
&
 


 
"

Generally, we recommend performing a user calibration. To perform a calibration, use the configuration items A.20.2.13
-
(zero) and A.20.2.14 (end), see section
11.
-
 
 
ϑ
ϑ
ϑ
ϑ
!
 ##
Fig. 2a · Electrical connection
EB 6495-2 EN 9
Electrical connection
T
C
Terminal strip 2
Supply output
21 V DC
max. 90 mA
Digital input DI1
GND8382
Digital input DI2
Digital input DI3
GND
Digital input DI4
89 90
+ –
31 32Analog output AO1 33 81
35 36Analog output AO2 37 97 98Analog output AO3 99 85 86 87
Current
0/4 to 20 mA
+ –
+ –
+
+ –
+ –
+ – +
Voltage
0/2 to 10 V
– +
– +
– +
Digital input with internal supply
Digital input with external supply
24 V DC
+
24 V DC
+
RS-485/USB interface (option, see section 13.2.2)
4-wire
AR
RX
BR BTR
TX RX/TX
ATR
Fig. 2b · Electrical connection
10 EB 6495-2 EN
2-wire
2-Leiter4-Leiter
RS-232 interface (option, see section 13.2.1)
ND
R
16
D
V
Terminal strip 3
Digital output DO5
Digital output DO6
Digital output DO7
Terminal strip 4
Supply 3 to 42 V DC, max. 30 mA
+
61 62 63 64 65
+
+
66
Electrical connection
Supply voltage
Switch output SO1 (+) Digital output DO1
Switch output SO1 (–) Digital output DO2
Switch output SO2 (+) Digital output DO3
Switch output SO2 (–) Digital output DO4
Fig. 2c · Electrical connection
L
L
85 to 264 V AC 24 V AC/DC (20 to 30 V)
N
N
Three-step output
for motor-driven actuator 42 43
52 53
45 46
55 56
+
L1
+
L1 L1
On/off output with pulse-pause modulation
N
N
L+ L–
Digital output:
limit values, alarms, on/off output + L1
+
EB 6495-2 EN 11
Operation
5 Operation
5.1 Operation structure
The controller has the following operation levels:
Operating level (Fig. 3): The controller is in this level while the con troller is in operation. Key information on the control process are displayed in this level.
Info menu:
The info menu consists of several menu items containing information on the running process and the firmware version.
Controlled variable Error
Reference variable Controller
Manipulated variable (output)
Infrared interface
Fig. 3 · Display and operating controls
-
Operating menu:
The operating menu allows the control pa
­rameter and set points to be changed. These are located in two different menu items.
Configuration menu:
The controller is adapted to its control task by changing configuration items and pa
­rameters. The configuration level is divided into menus and submenus. The submenus contain the individual configuration items and parame ters.
Display
Key panel with operator keys
DIP switch
(at the side of the
housing)
mA / V AI1
Pt 100 Pt 1000
mA / V AI2
Pt 100 Pt 1000 Potentiometer
Pt 100 Pt 1000
Pt 100 Pt 1000
mA / V
AI3
mA / V
AI4
-
12 EB 6495-2 EN
Operation
5.2 Display and operator controls
Display
The controller is in the operating level while the controller is in operation. The display is divided into two sections. Each section is assigned to one controller. The default assignment is as follows:
Left display: Controller [1]
4
Right display: Controller [2]
4
The controlled variable (actual value), error, set point and manipulated variable (output) are displayed for each controller in the de­fault setting.
Status messages concerning the digital in­puts and outputs can be displayed depend­ing on the configuration. For control modes with just one controller, further signals can be displayed in five rows in the additional display.
Infrared interface
Data are transmitted between the controller and TROVIS-VIEW installed on the computer over the infrared interface of the controller and the infrared adapter (order no. 8864-0900) connected to the computer.
To make the initial setting effective, both DIP switches of an analog input must have the same position. If just one DIP switch is switched, the last valid configuration of the input remains effective. An error message is generated and the digital output for error messages DO7 is activated. The fault alarm icon is displayed in the operating level (see section 12).
Two DIP switches are assigned to each ana log input AI1 to AI4.
Both DIP switches on the right:
4
Current signal (mA or V) Both DIP switches on the left:
4
Resistance signal (Pt 100 or Pt 1000) or potentiometer (only with analog input AI2)
Key panel with operator keys
Left and right row:
4
Manual/automatic key Cursor key Cursor key
Middle row:
4
Info key Enter key Escape key
-
DIP switches
Before an analog input can be configured, the DIP switches must be set correspond ingly. These switches are used to initially se lect whether an input is to accept a cur rent/voltage signal (mA, V) or a resistance signal (Pt 100, Pt 1000, potentiometer).
-
-
-
EB 6495-2 EN 13
Operation
Note: A difference is only made between the keys on the left and right in the operat ing level. In this case, the keys on the left are used to operate the controller on the left dis
The function of the keys varies depending on the level/menu which is active. See the table
-
below.
­play and the keys on the right are used to operate the controller on the right display.
Operator
keys Operating level Info menu Operating menu Configuration level
Manual/
automatic
key
Cursor
keys
Switch between
manual and automatic control mode
Cascade control:
Open/close con­troller cascade
Automatic mode:
Change set point
Manual mode:
Change output value
No function –
– Browse through
menu and information
No function –
– Browse through a
menu
– Change set point
and control parameters
Edit individual
items of parame ters
– Browse through
menu, submenu, configuration items and param­eters
Set configuration items and param eters
-
-
Enter
key
Info key
Escape
key
14 EB 6495-2 EN
Enter main menu (operating menu and configuration level)
Enter info menu
Confirm restart after supply voltage failure
Enter menu items–Confirm settings
Switch over set point
No function –
Return to the ope rating level stepwise
No function –
-
Return to the oper ating level step wise
-
-
Enter menu, submenu, configu ration items and parameters
Confirm settings
No function –
Return to the oper ating level step wise
-
-
-
Operating level
6 Operating level
The display in the operating level is ar
ranged depending on the control mode se The operating level is active while the con troller is in operation. Key information on the control process is displayed in this level.
Default reading on display:
Row 1 Actual value PV0 at comparator Row 2 Error signal +/–e Row 3 Set point SP1 ... SP4, SPE, SPC Row 4 Output according to priority
Overview: Default reading on display in the operating level for various control modes
Control mode Operating level (default reading)
M.1-1
1x Fixed set point/follow-up control
M.1-2
Ratio control
Controller [1]
Controller [1]
lected. For control modes with two control
­lers, the default display has two sections: Controller [1] on the left display section and Controller [2] on the right display section. See overview below.
Note: The default reading can be adapted as required. See section 9.3.
-
-
-
M.1-3
Cascade control
M.1-4
Override control
Slave controller [1]
Main controller [1]
Master controller [2]
Override controller [2]
EB 6495-2 EN 15
Operating level
Overview: Default reading on display in the operating level for various control modes
Control mode Operating level (default reading)
M.1-5
Fixed set point/follow-up control
Controller [1]
Controller [2]
M.1-6
Ratio controller and controller
To operate the controller, use the cursor keys ( , ) and the manual/automatic key ( ) in the operating level. These keys are located on the left and right of the key panel. Use the keys on the left to operate the controller shown in the left display section and use the keys on the right to operate the controller shown in the right display section.
The following actions can be performed in the operating level:
Change the set point→section 6.1
4
Switch over to manual mode and
4
change the output→section 6.2 Open/close cascade (only with cas
4
cade control (setting M.1-3)) section 6.3
Ratio controller [1]
-
Controller [2]
6.1 Changing the set point
Change the set point in automatic mode us­ing the cursor keys:
Increase the set point. Decrease the set point.
Note: The last digit is changed by one value every time the key is pressed. Hold the key down to change the value at a faster rate.
6.2 Switching over to manual mode and changing the output
Note: The left display for Controller [1] is
shown in the following examples. Conse quently, the keys on the left are used for op eration.
-
-
16 EB 6495-2 EN
1x Switch to manual mode.
The hand icon appears above the controller designation [1]/[2]. The currently active manipulated variable (output) is highlighted:
AO1 = 46.5 % … Increase the manipulated variable or … Reduce the manipulated variable.
Note: The last digit is changed by one value every time the key is pressed. Hold the key down to change the value at a faster rate.
Operating level
Note: In the following example, the master controller [2] is shown on the right display (default). As a result, the manual/automatic key on the right is used to open/close the cascade.
1x Close the cascade.
The cascade icon is no longer displayed when the cascade is closed. The output value YM of the master controller [2] specifies the set point SPM of the slave controller [1]: SPM = YM
1x Open the cascade.
Return to automatic mode
1x Return to automatic mode.
The hand icon is no longer dis
played.
-
6.3 Opening/closing cascade
The opening/closing cascade function is only possible for cascade control (setting M.1-3).
The cascade is opened and closed by press ing the manual/automatic key of the master controller [2].
The cascade icon appears when the cascade is opened. The set point of the slave controller [1] can be changed using the cursor keys ( , ).
The cascade can also be opened/closed over a digital input. See configuration item C.2.2.3 in section 15.2 and section
-
C.2.2.3 in the Configuration Manual KH 6495-2 EN.
EB 6495-2 EN 17
Info menu
←←
---------------------- ----------------------------
→→
Operating level Info menu Controller [1] * Set point
Input variable PV, … **
Output **
* If an error message exists, a
submenu is added to the info menu. This submenu Error message is displayed directly after entering the info level (on top of the submenu Controller[1]).
** Only assigned input and
output variables are displayed.
Controller [2] See controller [1]
Inputs/outputs Analog inputs AI1 … 4
Analog inputs [%] AI1 … 4
Analog outputs AO1 … 3
Switch outputs SO1 … 2
Digital inputs DI1 … 4
Digital outputs DO1 … 4
Digital outputs DO5 … DO7
Last events Event 1/x
Event x/x
Diagnosis Diagnosis - 1 (operating time)
Diagnosis - 2 (device temperature)
Diagnosis - 3 (cycle times)
18 EB 6495-2 EN
Diagnosis - 4 (system-internal events)
Diagnosis - 5 (system-internal events)
Diagnosis - 6 (telegram counter)
Versions Firmware
Info menu
7 Info menu
Information on the running process and the controller can be viewed in the info menu. Usually, there are the following menu items
Controller [1], possibly Controller [2], Inputs/outputs, Last events, Diagno sis and Versions. If an error message ex
ists, the menu item Error message is added to the info menu.
Enter the info menu by pressing the info key
. Use the cursor keys ( , ) to browse
through the menu. Press the enter key to select a menu item. Press the escape key to return.
Note: Both the keys on the left and right in the key panel can be used for the info menu.
Example: A control mode with one control­ler is configured. An error message does not exist in the controller.
The objective of the example is to find out the current values of analog inputs AI1 and AI2.
The controller is currently in the operating level:
-
-
Enter the info menu
1x Change to the info menu.
The menu item Controller [1] is highlighted on the display.
Activate analog input readings
1x Select menu item Inputs/outputs.
1x Activate menu item Inputs/out-
puts.
The analog inputs are displayed with their current values.
Return to the operating level
2x Return to the operating level.
EB 6495-2 EN 19
Info menu
Notes concerning the readings in the info menu
Menu item Inputs/outputs
Directly after the digital inputs and outputs, the state of the input/output is indicated: (0) or (1) In the case of a reversed digital input or output, the state of the input/output in reversed form is additionally indicated: inv.(1) or inv.(0)
Menu item Last events
The controller assigned to the input/output is indi cated on the right of the display ([1] or [2]) in the reading of analog inputs, digital inputs, analog outputs, switch outputs and digital outputs. If the input/output is assigned to both controllers, both controller numbers ([1; 2]) are indicated.
Additional readings apply to the digital inputs (separate or combined with the controller number):
[O] indicates that the digital input is assigned
4
to an output. [X] indicates that the digital input activates the
4
key locking.
Additional readings apply to the digital outputs (separate or combined with the controller number):
[I] indicates that the digital output is activated
4
by a digital input. [O] indicates that another digital output has
4
been assigned as the source to the digital out put.
Any events that occur are logged and time-stamped. The last event is always listed first.
-
-
20 EB 6495-2 EN
Menu item Diagnosis - 1
Menu item Diagnosis - 2
Menu item Diagnosis - 3
Info menu
Operating time indicates the time the controller has been operating since the last start-up of the controller in days.hours:Minutes:Seconds.
The total operating time refers to how long the controller has been supplied with voltage (Days.Hours:Minutes:Seconds).
When installing the controller, it is important to make sure that the permissible ambient tempera
­ture (0 to 50 °C) is kept. The device inside temperature is monitored to pro tect the controller. If this temperature falls below 0 °C or rises above 60 °C, a message is generated in Last events and Error messages. If the temperature inside the controller falls below –5 °C or rises above 65 °C, a further message is gener­ated and the fault alarm icon blinks in both con­troller displays.
Reading of current scanning time The scanning time (min) can be reset by pressing the left manual/automatic key and the scan
­ning time (max) can be reset by pressing the right manual/automatic key .
-
EB 6495-2 EN 21
Operating menu
←← ←
------------------- --------------------- ----------------------------------
→→ → → ↵
Operating level Op. menu
Controller [1]
Op. menu
Controller [2]
Control
parameters
KP (proportional-action
coefficient)
TN (reset time)
TV (derivative-action time)
Y0 (operating point)
Change control
parameters
See section 8.2
(derivative-action gain TV.K1)
TV.K
1.P+
(PWM duty cycle SO1.P+)
1.P–
(PWM duty cycle SO1-P–)
2.P+
(PWM duty cycle SO2.P+)
2.P–
(PWM duty cycle SO2.P–)
Set point SP (active set point)
SPI
(current internal set point)
SP1
SP2
SP3
SP4
Switch over
internal/
external set
point
Section 8.3 Switch over
and change
internal set
points
See section 8.4
22 EB 6495-2 EN
Operating menu
8 Operating menu
The operating menu consists of the menu items Control parameters and Set point. The following actions can be per formed:
Change control parameters
4
Section 8.2 Switch over internal/external set point
4
4
Section 8.3
Switch over and change internal set points→Section 8.4
Press the enter key to enter the operating menu. Use the cursor keys ( , ) to browse through the menu. Press the enter key to select a menu item.
Note: Both the keys on the left and right of the key panel can be used for the operating menu.
8.1 Entering the operating menu
The controller is currently in the operating level:
Enter the operating menu of Controller [1]
1x Switch to the main menu.
-
Operating menu contr. [1] is highlighted.
1x Enter Operating menu
contr. [1].
The submenu Control parameters is highlighted.
Note: Enter the operating menu for Control­ler [2] in the same way after selecting it () .
8.2 Changing the control parameters
After activating the operating menu (see section 8.1), the control parameters are changed in the menu item Control pa rameters. Depending on the control behavior, the proportional-action coefficient KP, reset time TN, derivative-action time TV, derivative-action gain TV.K and operating point Y0 can be changed:
EB 6495-2 EN 23
-
Operating menu
Assignment between control parameters and control behavior
C.3.1.1
KP TN •––•• TV Y0 TV.K
PI
-1P-2PD-3
•••••
––••–
••••• ––••–
PID
-4I-5
Note: If on-off/three-step outputs are con figured with pulse width modulation (PWM), the corresponding duty cycles (
SO1.P–, SO2.P+, SO2.P–
SO1.P+,
) can be
changed.
Example: The reset time TN for Controller [1] is to be changed to 100 s.
Enter the operating menu (see section
4
8.1).
Change the reset time TN
1x Activate the menu item Control pa
rameters.
to 100 % range of the measuring range is plotted on the right. The current value of the propor tional-action coefficient KP is indi
-
-
cated below.
1x Select reset time TN.
-
1x Activate reset time TN.
The current value of the reset time is highlighted: 120 s
… Keep pressed and change the reset
time TN to 100 s.
-
1x Confirm the reset time.
The actual value at the comparator PV0 ( ), the set point at the com parator SP0 ( ) and the manipu lated variable Y ( ) are indicated on the left. For ratio control: Actual ratio PVR, ratio set point SPR and manipulated variable Y). Their course within the last minute in the 0
24 EB 6495-2 EN
Return to the operating level
3x Return to the operating level.
-
-
Operating menu
8.3 Switching over internal/external set point
If the external set point SPE (C.2.1.2-1) is configured, the set point SP is equal to SPE. The switchover to an internal set point SPI is performed in the operating menu.
The controller is in the operating level:
Enter the operating menu (see section
4
8.1).
Switchover to the internal set point SPI
1x Select the menu item Set point.
1x Activate the menu item Set point.
The current set point is high lighted: SPE
1x Select internal set point SPI.
1x Confirm the setting
SPI is now the active set point.
Note: Determining and changing the inter­nal set point is described in Section 8.4.
Cascade control
For cascade control (M.1-3) the cascade can also be opened and closed by switching over the set point. The cascade is opened if the following ap­plies in the slave controller [2]: SP = SPI The cascade is closed if the following ap plies in the slave controller [2]: SP = SPM
-
-
The current set point is displayed: SP = SPE
1x Activate the set point SP.
8.4 Switching over between internal set points and changing them
In the operating menu, one of the set points SP1, SP2, SP3 or SP4 can be assigned to the internal set points SPI, depending on the configuration.
EB 6495-2 EN 25
Operating menu
Required configuration for determining the set point
SP1 SP2 SP3 SP4
C.2.1.1-1/-2/-3/-4
C.2.1.1-2/-3/-4
C.2.1.1-3/-4
C.2.1.1-4
Example: The controller [1] has two internal set points SP1 and SP2 (configured with 1C.2.1.1-2).
The set point SP1 is to be switched over to
set point SP2. The set point SP1 is to be kept at 70 while
the set point SP2 is to be changed to 100.
The controller is currently in the operating level:
Enter the operating menu (see section
4
8.1).
1x Activate the menu item Set point
The actual value at the comparator PV0 ( ), the set point at the com parator SP0 ( ) and the manipu lated variable Y ( ) are indicated on the left. For ratio control: Actual ratio PVR, ratio set point SPR and manipulated variable Y). Their course within the last minute in the 0 to 100 % range of the measuring range is plotted on the right. The assignment of the internal set point (in this case: SPI = SP1) is indi­cated below.
1x Activate the internal set point.
The current internal set point is high­lighted: SP1
1x Set the internal set point SPI = SP2.
-
-
Switchover between internal set points
1x Select the menu item Set point.
26 EB 6495-2 EN
1x Confirm the setting
SP2 is now the active set point.
Change set points SP1 and SP2
1x Select the set point SP1.
The set point SP1 has the required value of 70.0 and therefore does not need to be changed.
1x Select the set point SP2.
1x Activate the set point setting SP2.
The current set point is highlighted:
90.0
… Keep pressed and change the set
point to 100.0.
1x Confirm the set point.
The set point is adopted.
Operating menu
Return to the operating level
3x Return to the operating level.
EB 6495-2 EN 27
Configuration level
←←
------------------- -------------------------------------
Operating level Op. menu
Controller [1]
Configuring the controller,
see section 9.2
2x 2x
Configuration M Control mode
→→
I Input This menu contains the configura
1C Controller [1] These menus contain the configura
2C Controller [2]
O Output This menu contains the configura-
D Communication This menu contains the configura
A General settings This menu contains the configura
Setting the control mode
tion of analog inputs AI1 to AI4 and digital inputs DI1 to DI4. See sec. 15.2 for details.
tion of the controller settings for Controller [1] and Controller [2] as
well as input variables, set points, control functions, restart condition, controller display and key locking. See section 15.2 for details.
tion of analog outputs AO1 to AO3 and digital inputs DO1 to DO6. See section 15.2 for details.
tion of interfaces. See section 15.2 for details.
tion of languages, operation dis play, operator keys and network frequency. In addition, the key number can be entered, a user cali bration of the analog inputs and outputs can be performed and the controller can be reset to the de fault settings. See section 15.2 for more details.
-
-
-
-
-
-
-
28 EB 6495-2 EN
Configuration menu
9 Configuration menu
In the configuration menu, the controller is adapted to its control task by changing indi vidual configuration items and parameters. The configuration menu is subdivided into various menus and submenus. The submenus contain the individual configura tion items and parameters. Section 15.2 in cludes an overview of all possible settings that can be made.
The Configuration Manual KH 6495-2 EN contains detailed descriptions on individual configuration items as well as other helpful information.
Operation within the configuration level is performed using the cursor keys, ( , ), enter key ( ) and escape key ( ).
Note: Both the keys on the left and right of the key panel can be used in the configura­tion level.
If the controller is to be newly configured, we recommend keeping the following con figuration sequence:
1. Set the control mode, e.g. M.1-1
2. Set the input, e.g. I.1.1-6
3. Assign input to controlled variable, e.g.
C.1.1.1-1
4. Change the set point, e.g. C.2.1.1
5. Determine the control algorithm, e.g.
C.3.1.1
6. Assign the output, e.g. O.1.1-1
7. Set the output signal, e.g. O.1.2-1
-
8. Set the operating direction, e.g.
O.1.3-1
9. Set the restart condition, e.g. C.4.1-0
­Configuration Manual KH 6495-2 EN con
tains further information.
9.1 Entering the configuration
-
-
The controller is currently in the operating level:
Enter the configuration level
level
1x Change to the main menu.
The Operating menu Contr. [1] is highlighted.
1x Select Configuration menu.
1x Enter Configuration menu.
-
EB 6495-2 EN 29
Configuration menu
The menu M Control mode is highlighted.
9.2 Configuring the controller
The controller is configured by setting the configuration items and associated parame ters. Each configuration item has its own code, which gives information on its position in the configuration level.
Example: The configuration item Input signal has the code I.1.1.
I
Menu I Input
4
­configuration item C.1.1.1 Input vari able PV:
Note: Some configuration items as well as the parameters can only be set if certain set tings have already been made in the con troller configuration. The required settings for the controller configuration are de scribed in the configuration list (section
15.2) and in the Configuration Manual KH 6495-2 EN.
-
-
-
-
I.1→Submenu 1 Analog
4
input AI1
I.1.1
4
Input signal with the setting -6 Pt 100
For control modes with two controllers, the controller number 1C…“ (Controller [1]) and “2C…“ (Controller [2]) is added to dis tinguish between the controllers, e.g. for
30 EB 6495-2 EN
Configuration item 1
9.2.1 Setting configuration items
1. Read the code of the configuration item
that you want to change from the con­figuration list (section 15.2).
2. Find the position in the configuration
level. See the example in section 9.2.2.
Select and set the configuration item
… If the configuration item that you
want to set is not in the menu M Control mode, select the menu required:
I Input C Controller [1]/[2] O Output D Communication A General settings
-
Loading...
+ 126 hidden pages