28 EB 5724 EN
Operation
Î Turn counterclockwise to retract the actu-
ator stem (approx. 4 turns for 1mm travel).
Changing the set point W1
The default settings of set point W1 is 60°C
and W2 is 70°C.
These set point can be changed in the TRO-
VIS-VIEW software.
To manually adjust the W1 set point without
TROVIS-VIEW, turn the set point potentiometer (11 in Fig.1) located on the printed cir-
cuit board of the actuator. The adjustable
setting range is between 10 and 100% of
the measuring range (default: lower measur-
ing range value Xmin = 0°C and upper
measuring range value Xmax = 100°C).
In the delivered state, the set point potenti-
ometer is set to 0%, i.e. it does not have any
effect on W1 set point (60°C).
Additional points that apply:
Device with rmware 2.10 or lower:
Î The set point potentiometer only takes ef-
fect when the actual value originates
from a Pt1000 sensor. In the combination with F05 - 1 (Current input active)
and F06 - 1 (Current input function = set
point), the set point potentiometer is not
active.
Device with rmware 2.11 or higher:
The set point can be adjusted even when using the current input.
Î The manually adjusted value at the set
point potentiometer for W1 is only used
for control if function block F12 in
TROVIS-VIEW is set to 1 (Automatic set
point potentiometer: manual setting ef-
fective above 10%. The required setting
F12 - 1 is the default setting.
Î The set point W2 can only be changed
in TROVIS-VIEW.
Risk of damage to the screw heads on the
front cover due to the use of the wrong tool.
To loosen and tighten the screws, only use
TORX
®
T10, TORXPLUS®10IP, or a atblade screwdriver with 0.8mm blade thickness and 4.0mm blade width.
1. Open front cover.
2. Set W1 set point as required at the set
point potentiometer (11 in Fig.1).
0
100
50
Setting range: 0 to
100% of the measuring range (default set-
ting 0 to 100°C)
Do not forget to check the automatic set
point potentiometer function.
3. Close front cover.
Function of automatic set point potentiometer
Î Any setting below 10% at the set point
potentiometer is ignored by the control-
ler. The controller uses the W1 set point
from the parameter list (TROVIS-VIEW
software) for control.
Î Any setting above 10% at the set point
potentiometer is used by the controller
NOTICE
!