Samson TROVIS 5500, TROVIS 5576 Mounting And Operating Instructions

TROVIS 5500 Automation System TROVIS 5576 Heating and
District Heating Controller
Mounting and Operating Instructions
EB 5576 EN
Firmware version 2.41 Edition July 2018
®
Electronics from SAMSON
Safety instructions
4
The device may only be assembled, started up or operated by trained and experienced personnel familiar with the product. Proper shipping and ap
-
propriate storage are assumed.
4
The controller has been designed for use in electrical power systems. For wiring and maintenance, you are required to observe the relevant safety regulations.
2 EB 5576 EN
Safety instructions
Revisions to controller firmware in comparison to previous versions
1.70 (previous)
1.71 (new)
Err 2 message (default setting loaded) is not displayed anymore. See section 8.1. Single error messages to be forwarded over the device bus can be selected.
1.71
(previous)
1.82 (new) An interrupted drying of jointless floors can be continued by selecting the restarting stages
START temperature maintaining phase or START temperature reduction phase. See section
5.3. During thermal disinfection, the
Hold time of disinfection temperature can be used to deter­mine how long the disinfection temperature must be maintained within the adjusted time period to rate the process successful. See section 6.11.
Besides the release of single control circuits, the release of the controller is possible over the binary input. See section 7.9.
1.82
(previous)
1.90 (new) The new system code numbers Anl 14.1 to 14.3 increase the total of different hydraulic
schematics to 43. The new systems are all fitted with a buffer tank and a DHW storage tank. System Anl 14.3 additionally contains a solar circuit with reroutable heat flow. See sections 4 and 6.4.
For firmware 1.90 and higher, the maximum flow set point of the controller can be de
-
manded by issuing up to two analog signals for requesting external demand with se
-
quence control. See section 7.14.
1.90 (previous)
1.95 (new)
The priority operation (reverse control and set-back operation) can be set regardless of the time and temperature in the system. Refer to sections 6.9.1 and 6.9.2.
The setting CO1 -> F20 - 1 allows an external demand for heat to be made when insuffi
-
cient heat is supplied. Refer to section 7.17.
EB 5576 EN 3
Revisions to controller firmware in comparison to previous versions
Revisions to controller firmware in comparison to previous versions
1.90 (previous)
1.95 (new)
The priority operation (reverse control and set-back operation) can be set regardless of the time and temperature in the system. Refer to sections 6.9.1 and 6.9.2.
The setting CO1 -> F20 - 1 allows an external demand for heat to be made when insuffi
-
cient heat is supplied. Refer to section 7.17.
1.95 (previous)
2.00 (new)
New system (Anl 10.5) added. Refer to section 4. The limit switch for creep feed rate limitation can also be connected to input RüF1. In pre
­vious versions, it could only be connected to the binary input (terminals 04/12). Refer to section 7.12.3.
A primary controller linked over the device bus can receive and process the demand of downstream controllers (version 2.00 and higher) optionally in control circuit Rk1 and/or Rk2. Refer to section 7.13.1.
The
Boiler pump OFF parameter has been replaced by the Hysteresis parameter. Refer to
section 6.4.
2.00 (previous)
2.12 (new)
New hydraulic schematic (Anl 11.6) added. Refer to page 64. New cooling control function (refer to section 5.13)
The cooling circuit causes a reversal of the operating direction and a minimum limitation of the return flow temperature in Rk1/2.
The demand processing using a 0 to 10 V signal can be applied to the 0 to 130 °C trans
-
mission range. Refer to section 7.11.
2.12 (previous)
2.13 (new)
The priority operation (reverse control and set-back operation) can be activated for system Anl 4.5 either for only one heating circuit (Rk1or Rk2) or for both heating circuits (Rk1and Rk2). Refer to section 6.9.
New function to control the speed of the charging pump based on the charging progress. Refer to section 6.7.
2.13 (previous)
2.14 (new)
The flow rate and capacity limitation over meter bus can be performed in control circuit Rk1 and additionally in Rk2. Refer to section 9.3.2.
2.14 (previous)
2.20 (new)
New hydraulic schematics Anl 16.x (buffer tank system) added. Refer to page 68. The drying of jointless floors cannot be cancelled due to a different flow temperature. Refer
to section 5.3.
4 EB 5576 EN
Revisions to controller firmware in comparison to previous versions
2.20 (previous)
2.24 (new)
Internal modifications
2.24 (previous)
2.26 (new) Outdoor temperature using 0 to 10 V signal function extended
Outdoor temperatures can be received or sent using a 0 to 10 V signal.
2.26 (previous)
2.28 (new)
New system Anl 11.5
2.28 (previous)
2.41 (new)
New functions and parameters in buffer tank systems (see section 5.5): CO1>F22: SLP depending on return flow temperature CO5´>F01: Y1 reverse CO5´>F02: Y2 reverse CO5´>F07: AE1 zero shift New functions and parameters in buffer tank systems (continued): PA1: Min. set point for buffer tank charging PA1: Stop buffer tank charging PA1: Charging temperature boost PA1: Lag time of charging pump PA4: Maximum buffer tank temperature
New Differential temperature control function (CO1>F23) in systems Anl 1.0 and 16.0. Refer to section 5.14.
TROVIS5570 Control Panel is discontinued. Restrictions when using a mini module (accessories no. 1400-7436). Refer to section 9.4.
Contents
1 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.1 Operating elements . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.1.1 Rotary pushbutton and changeover key . . . . . . . . . . . . . . . . . 9
1.1.2 Rotary switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.2 Operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.3 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.4 Displaying data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
1.5 Setting the controller time . . . . . . . . . . . . . . . . . . . . . . . 17
1.6 Setting the times-of-use . . . . . . . . . . . . . . . . . . . . . . . . 18
1.7 Setting the party mode. . . . . . . . . . . . . . . . . . . . . . . . . 20
1.8 Activating extended operating level . . . . . . . . . . . . . . . . . . 21
1.8.1 Setting public holidays. . . . . . . . . . . . . . . . . . . . . . . . . 22
1.8.2 Setting vacation periods . . . . . . . . . . . . . . . . . . . . . . . . 23
1.9 Setting room and DHW temperature set points . . . . . . . . . . . . . 25
2 Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
2.1 Setting the system code number . . . . . . . . . . . . . . . . . . . . 27
2.2 Activating and deactivating functions. . . . . . . . . . . . . . . . . . 28
2.3 Changing parameters . . . . . . . . . . . . . . . . . . . . . . . . . 29
2.4 Calibrating sensors . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2.5 Resetting to default values . . . . . . . . . . . . . . . . . . . . . . . 35
3 Manual operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
4 Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5 Functions of the heating circuit. . . . . . . . . . . . . . . . . . . . . 74
5.1 Weather-compensated control . . . . . . . . . . . . . . . . . . . . . 74
5.1.1 Gradient characteristic. . . . . . . . . . . . . . . . . . . . . . . . . 75
5.1.2 Four-point characteristic . . . . . . . . . . . . . . . . . . . . . . . . 77
5.2 Fixed set point control . . . . . . . . . . . . . . . . . . . . . . . . . 78
5.3 Underfloor heating/drying of jointless floors . . . . . . . . . . . . . . 79
5.4 Deactivation depending on outdoor temperature . . . . . . . . . . . . 80
5.4.1 OT deactivation value in rated operation . . . . . . . . . . . . . . . . 80
5.4.2 OT deactivation value in reduced operation. . . . . . . . . . . . . . . 80
5.4.3 OT activation value in rated operation . . . . . . . . . . . . . . . . . 81
5.5 Buffer tank systems . . . . . . . . . . . . . . . . . . . . . . . . . . 81
5.6 Summer mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
5.7 Delayed outdoor temperature adaptation. . . . . . . . . . . . . . . . 85
5.8 Remote operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
5.9 Optimization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
5 EB 5576 EN
Contents
5.10 Flash adaptation. . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
5.10.1 Flash adaptation without outdoor sensor (room temperature dependent) . 88
5.11 Adaptation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
5.12 Pump management . . . . . . . . . . . . . . . . . . . . . . . . . . 89
5.13 Cooling control . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
5.14 Differential temperature control. . . . . . . . . . . . . . . . . . . . . 92
6 Functions of the DHW circuit . . . . . . . . . . . . . . . . . . . . . . 93
6.1 DHW heating in the storage tank system . . . . . . . . . . . . . . . . 93
6.1.1 DHW circuit additionally controlled by a globe valve . . . . . . . . . . 95
6.2 DHW heating in the storage tank charging system . . . . . . . . . . . 96
6.2.1 Cold charging protection. . . . . . . . . . . . . . . . . . . . . . . . 98
6.3 DHW heating in instantaneous heating system . . . . . . . . . . . . . 99
6.4 DHW heating with solar system. . . . . . . . . . . . . . . . . . . . 100
6.5 Intermediate heating operation . . . . . . . . . . . . . . . . . . . . 100
6.6 Parallel pump operation . . . . . . . . . . . . . . . . . . . . . . . 100
6.7 Speed control of the charging pump . . . . . . . . . . . . . . . . . 101
6.8 Circulation pump operation during storage tank charging . . . . . . . 101
6.9 Priority operation. . . . . . . . . . . . . . . . . . . . . . . . . . . 102
6.9.1 Reverse control. . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
6.9.2 Set-back operation . . . . . . . . . . . . . . . . . . . . . . . . . . 103
6.10 Forced charging of the DHW storage tank. . . . . . . . . . . . . . . 103
6.11 Thermal disinfection . . . . . . . . . . . . . . . . . . . . . . . . . 104
7 System-wide functions . . . . . . . . . . . . . . . . . . . . . . . . 106
7.1 Automatic summer/standard time swichover . . . . . . . . . . . . . 106
7.2 Frost protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
7.3 Forced operation of the pumps . . . . . . . . . . . . . . . . . . . . 107
7.4 Return flow temperature limitation. . . . . . . . . . . . . . . . . . . 107
7.5 Condensate accumulation control . . . . . . . . . . . . . . . . . . . 108
7.6 Three-step control . . . . . . . . . . . . . . . . . . . . . . . . . . 109
7.7 On/off control . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
7.8 Continuous control . . . . . . . . . . . . . . . . . . . . . . . . . . 109
7.9 Releasing a control circuit/controller over the binary input . . . . . . . 110
7.10 Speed control of the charging pump . . . . . . . . . . . . . . . . . 111
7.11 Processing an external demand . . . . . . . . . . . . . . . . . . . . 111
7.12 Flow rate/capacity limitation in Rk1. . . . . . . . . . . . . . . . . . 113
7.12.1 Limitation using pulse input . . . . . . . . . . . . . . . . . . . . . . 113
7.12.2 Limitation using 0/4 to 20 mA signal . . . . . . . . . . . . . . . . . 114
7.12.3 Creep feed rate limitation using a binary input . . . . . . . . . . . . 115
EB 5576 EN 6
Contents
7.12.4 Limitation of the calculated capacity. . . . . . . . . . . . . . . . . . 116
7.13 Device bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
7.13.1 Requesting and processing an external demand . . . . . . . . . . . . 117
7.13.2 Sending and receiving outdoor temperatures . . . . . . . . . . . . . 119
7.13.3 Synchronizing the clock . . . . . . . . . . . . . . . . . . . . . . . 119
7.13.4 Priority over all controllers . . . . . . . . . . . . . . . . . . . . . . 120
7.13.5 Connecting a TROVIS 5570 Room Panel . . . . . . . . . . . . . . . 120
7.13.6 Display error messages issued by the device bus. . . . . . . . . . . . 121
7.14 Requesting an external demand by issuing a 0 to 10 V signal . . . . . 122
7.15 Connecting potentiometers for valve position input. . . . . . . . . . . 122
7.16 Feeder pump operation. . . . . . . . . . . . . . . . . . . . . . . . 123
7.17 External demand for heat due to insufficient heat supply . . . . . . . . 123
7.18 Locking manual level . . . . . . . . . . . . . . . . . . . . . . . . . 124
7.19 Locking the rotary switches . . . . . . . . . . . . . . . . . . . . . . 124
7.20 Setting a customized key number . . . . . . . . . . . . . . . . . . . 124
8 Operational faults . . . . . . . . . . . . . . . . . . . . . . . . . . 125
8.1 Error list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
8.2 Sensor failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
8.3 Temperature monitoring . . . . . . . . . . . . . . . . . . . . . . . 126
8.4 Collective error message . . . . . . . . . . . . . . . . . . . . . . . 126
8.5 Error status register. . . . . . . . . . . . . . . . . . . . . . . . . . 127
9 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
9.1 System bus interface in combination with RS-232/RS-485
cable converters (for two-wire or four-wire bus) . . . . . . . . . . . . 128
9.2 Description of communication parameter settings . . . . . . . . . . . 129
9.3 Meter bus interface. . . . . . . . . . . . . . . . . . . . . . . . . . 130
9.3.1 Activating the meter bus . . . . . . . . . . . . . . . . . . . . . . . 130
9.3.2 Flow rate/capacity limitation using meter bus . . . . . . . . . . . . . 131
9.4 Memory module/mini module . . . . . . . . . . . . . . . . . . . . 134
9.5 Data logging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
10 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
11 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . 138
12 Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
12.1 Function block lists . . . . . . . . . . . . . . . . . . . . . . . . . . 142
12.2 Parameter lists . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
12.3 Assignment of the rotary switches . . . . . . . . . . . . . . . . . . . 169
12.4 Sensor resistance tables . . . . . . . . . . . . . . . . . . . . . . . 170
12.5 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
7 EB 5576 EN
Contents
12.6 Customer data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
Frequently used abbreviations . . . . . . . . . . . . . . . . . . . . 190
8 EB 5576 EN
Contents
1 Operation
The controller is ready for use with the default temperatures and operating schedules. On start-up, the current time and date need to be set at the controller (–> section 1.5).
1.1 Operating elements
The operating controls are located in the front panel of the controller and protected by a Plexiglas door.
1.1.1 Rotary pushbutton and changeover key
Rotary pushbutton
Turn q: Display, select parameters and function blocks
Press : Confirm adjusted selection or settings
Changeover key
(use pen or any other pointed item to press) Press to switch between operating level and
configuration/parameter level
EB 5576 EN 9
Operation
*
1.1.2 Rotary switches
Use the three rotary switches to adjust the required operating mode (icons on the left) and the relevant parameters (icons on the right). The top and middle switches are assigned to the heating circuits (see page 169). The rotary switch in the middle is not used in systems without a second heating circuit. The bottom switch is assigned to the DHW circuit.
Rotary switch to set the operating modes of the heating circuit
Automatic/time-controlled operation with switchover between rated and reduced operation
Day mode (rated operation) Night mode (reduced operation) Control operation deactivated, frost protection only
Manual operation: correction value adjusted in percent and activation/deactivation of the pumps
Rotary switch to set the parameters of the heating circuit
Day set point (rated room temperature) Night set point (reduced room temperature) Times-of-use for heating Party mode Controller time: setting current time, date and year
Rotary switch to set the operating modes of the DHW circuit
Automatic/time-controlled operation with switchover between times when DHW heating is permissible/impermissible
DHW heating deactivated, frost protection only Manual operation: correction value adjusted in percent
and activation/deactivation of the pumps
10 EB 5576 EN
Operation
Rotary switch to set the parameters of the DHW circuit
Set point for DHW temperature Times-of-use for DHW heating Times-of-use for DHW circulation pump Party mode
Note: If more than one rotary switch is set to position “Parameter“ (right side) at the same time, blinks on the display. The controller cannot be operated.
1.2 Operating modes
Day mode (rated operation)
Regardless of the programmed times-of-use and summer mode, the set points relevant for rated operation are used by the controller.
Night mode (reduced operation)
Regardless of the programmed times-of-use, the set points relevant for reduced operation are used by the controller.
Automatic mode
During the programmed times-of-use, the controller works in rated operation. Outside these times-of-use, the controller is in reduced operation, unless control operation is deactivated depending on the outdoor temperature. The controller switches automatically between both operating modes.
Manual operation
Valves and pumps can be controlled manually (–> section 3).
EB 5576 EN 11
Operation
1.3 Display
During operation, the display indicates the current time as well as information about the op
­eration of the controller. The times-of-use are represented by black squares below the row of numbers at the top of the display. Icons indicate the operating status of the controller.
The controller status can be displayed in operating level (–> section 1.4).
12 EB 5576 EN
Operation
STOP
1
18 2 3
6
7
8
9
4 5
10 11 12 13 14 15 16 17
19
20
21
Fig. 1 · Icons
1 Automatic operation 2 Day mode 3 Night mode 4 Vacation mode 5 Public holiday mode 6 Frost protection 7 Operational fault 8 Output bA9 9 Valve Rk1: OPEN 10 Valve Rk1: CLOSED
11 Storage tank charging
pump SLP 12 Output BA9* 13 Circulation pump UP5* 14 DHW demand 15 Circulation pump UP2* 16 Valve Rk2: OPEN,
output bA9: ON 17 Valve Rk2: CLOSED
output bA8: ON
18 Time-of-use 19 Control circuit assignment:
: Heating circuit Rk1 : Heating circuit Rk2
20 Outdoor temperature
dependent control deactivated
21 Demand with sequence control:
1: One output active 2: Two outputs active
* UP1, UP2, SLP, UP5, bA9 indicate possible choices for pump selection in manual mode.
1.4 Displaying data
The time, date, public holidays and vacation periods as well as the temperatures measured by the connected sensors and their set points can be retrieved and displayed with the help of the rotary pushbutton.
Note: Data can also be viewed in the manual mode in the operating level. To do so, select Info, confirm and proceed as described below.
Proceed as follows:
q
Select value. Depending on the configuration of the controller, the different data points are displayed:
Controller time.
Room temperature
: Heating circuit Rk1 : Heating circuit Rk2
Outdoor temperature
: Heating circuit Rk1 : Heating circuit Rk2
EB 5576 EN 13
Operation
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
°C
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
°C
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
°C
Temperature at the flow sensor VF
: Heating circuit Rk1 : Heating circuit Rk2
Temperature at the flow sensor VF1, primary exchanger circuit
Temperature at the flow sensor VF2, DHW circuit
Temperature at the solar collector sensor VF3
Temperature at the return flow sensor RüF
: Heating circuit Rk1 : Heating circuit Rk2
14 EB 5576 EN
Operation
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
˚C
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
˚C
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
˚C
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
˚C
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
°C
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
˚C
Temperature at the return flow sensor RüF, DHW circuit
Temperature at the storage tank sensor SF1 (DHW storage tank)
Temperature at the storage tank sensor SF2 (DHW storage tank)
Temperature at the storage tank sensor SF3 (DHW storage tank)
Temperature at the storage tank sensor SF2, SF3 (buffer tank)
EB 5576 EN 15
Operation
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
˚C
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
°C
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
˚C
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
˚C
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
˚C
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
˚C
Temperature at the storage tank sensor SF4 (buffer tank)
Temperature at the flow sensor VF4
Compare set point/limit and actual value. By pressing the rotary pushbutton when the time is displayed, the date appears on the display.
16 EB 5576 EN
Operation
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
˚C
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
°C
1.5 Setting the controller time
The current time and date need to be set immediately after start-up and after a power failure of more than 24 hours has occurred. This is the case when the time blinks on the display.
Proceed as follows:
Turn the top rotary switch to position “Controller time“ (right side). Display shows: time
q
Edit the controller time.
Confirm the adjusted time. Display shows: year
q
Edit the year.
Confirm the adjusted year. Display shows: date (day.month)
q
Edit the date. Confirm the adjusted date.
Display shows: time Return the rotary switch to the desired operating mode
(left side).
Note: The correct time is guaranteed after a power failure of 24 hours. Normally, the correct time is still retained at least 48 hours after a power failure.
EB 5576 EN 17
Operation
2423222120191817161514131211109876543210
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
242322212019181716151413121110
9876543210
1.6 Setting the times-of-use
Three times-of-use can be set for each day of the week. If only one time-of-use is required, the start and stop times of the second time-of-use must be set to identical times. In this case, the third time-of-use is not displayed. If only two times-of-use are required, the start and stop times of the third time-of-use must be set to identical times.
The times-of-use for the different control circuits are set at the rotary switches one after the other:
Times-of-use Rotary switch Position Heating circuit 1* Top Heating circuit 2* Middle DHW heating* Bottom Circulation pump Bottom
* Refer to page 169 for assignment
Parameters
WE* Range of values
Period/day 1–7 1–7, 1, 2, 3, 4, 5, 6, 7 with 1–7 = every day,
1 = Monday, 2 = Tuesday, ..., 7 = Sunday Start first time-of-use 6:00 0:00 to 24:00h; in steps of 15 minutes Stop first time-of-use 22:00 0:00 to 24:00h; in steps of 15 minutes Start second time-of-use 22:15 0:00 to 24:00h; in steps of 15 minutes Stop second time-of-use 22:15 0:00 to 24:00h; in steps of 15 minutes Start third time-of-use 0:00 to 24:00h; in steps of 15 minutes Stop third time-of-use 0:00 to 24:00h; in steps of 15 minutes * Default values (WE) valid for heating circuit 1/primary heat exchanger circuit (top rotary switch)
18 EB 5576 EN
Operation
Proceed as follows: Turn appropriate rotary switch to position
“Times-of-use”. Display shows: 1–7
q
Select period/day for which the times-of-use are to be valid: 1–7 = every day, 1 = Monday, 2 = Tuesday, ..., 7 = Sunday
Activate editing mode for period/day. Display shows: START, blinks
q
Edit start time (steps of 15 minutes).
Confirm start time. Display shows: STOP
q Edit stop time (steps of 15 minutes).
Confirm stop time. Display shows:
START
The second time-of-use is set like the first time-of-use. To set the times-of-use for each day, repeat the instructions in the fields highlighted in gray. Return the rotary switch to the desired operating mode (left side).
Note: Do not use the 1–7 menu to check the programmed times-of-use. If this menu is opened after the times-of-use have been set, the schedule programmed for Monday is also adopted for all other days of the week.
EB 5576 EN 19
Operation
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
ST OP
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
ST A RT
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1.7 Setting the party mode
Using the Party mode function, the controller continues or activates the rated operation of the controller during the time when the party timer is active, regardless of the programmed times-of-use. The party timer begins when the rotary switch has been returned to operating mode “Automatic“. When the party timer has elapsed, the party timer is reset to 00:00.
The party modes for the different control circuits are set at the rotary switches one after the other:
Party timer Rotary switch Position Heating circuit 1* Top Heating circuit 2* Middle DHW circuit* Bottom
* Refer to page 169 for assignment
Parameter
WE Range of values
Continue/activate rated operation 0 h 0 to 48 hours
Proceed as follows:
Turn appropriate rotary switch to “Party mode“. Display shows: 00:00 or the remaining time of the party timer
q
Edit desired length of the one-off time-of-use. Return the rotary switch to operating mode “Automatic“ (left side).
Note: The party timer counts down in steps of 15 minutes.
20 EB 5576 EN
Operation
1.8 Activating extended operating level
After the key number 1999 has been entered, the following information can be viewed and edited after the data points listed in section 1.4 have been displayed:
4
Heat capacity
4
Flow rate
4
Public holidays (can be changed)
4
Vacation periods (can be changed)
4
Valve positions
4
Modem status information
4
Meter bus status information
4
Switching states of the binary inputs
4
Info 2 · The following data are shown in the same sequence as shown below:
Controller ID (refer to section 8.6) Memory capacity of data logging module (section 9.5) Modbus station address (refer to section 9.2) Operating hours of solar circuit pump (refer to section 6.4) Water flow sensor (refer to section 6.3)
Opening the extended operating level:
Switch to configuration and parameter level. Display shows:
0 0 0 0
q
Set key number 1999. Confirm key number.
Display shows: time
Note:
The additional information is hidden when the key number 1999 is entered again.
The key number 1999 cannot be used to change the controller configuration and parameterization. A separate key number exists for configuration and parameterization. Refer to section 2.
EB 5576 EN 21
Operation
1.8.1 Setting public holidays
On public holidays, the times-of-use specified for Sunday apply. A maximum of 20 public holidays may be entered.
Parameter
WE Level / Range of values
Public holidays Extended operating level / 01.01 (1 Jan) to 31.12 (31 Dec)
Proceed as follows:
q
In extended operating level, select “Public holidays“. Display shows:
Open data point for public holidays.
q
If applicable, select – – – –. Activate editing mode for public holiday. blinks.
q
Edit desired public holiday. Confirm public holiday.
To enter additional public holidays, re-select – – – – and repeat the steps in the fields high­lighted in gray.
Exit data point for public holidays.
Note: Public holidays can also be entered in parameter level PA5 (–> section 2.3).
Deleting a public holiday:
q
Under data point for public holidays, select the holiday you wish to delete. Confirm selection.
q
Select – – – – . Delete the public holiday.
Note: Public holidays that are not assigned to a specific date should be deleted by the end of the year so that they are not carried on into the following year.
22 EB 5576 EN
Operation
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1.8.2 Setting vacation periods
During vacation periods, the controller constantly remains in reduced operating mode. A maximum of 10 vacation periods can be entered. Each vacation period can be separately assigned to the heating circuits Rk1 and Rk2 and/or the DHW circuit.
Parameters
WE Level / Range of values
Vacation period (START, STOP) Extended operating level / 01.01 to 31.12
Proceed as follows:
q
In extended operating level, select “Vacation periods“.
Display shows:
Open data point for vacation periods.
Display shows:
START, – –.– – (day.month)
q
If applicable, select – – – – .
Activate editing mode for start date of vacation period.
blinks.
q Edit start date of vacation period.
Confirm start date of the vacation period.
Display shows: STOP, – –.– – (day.month)
q
Edit end of vacation period.
Confirm end of vacation period.
Black squares under 1 to 4 at the top of the display
indicate the assignment of the vacation periods to the
individual control circuits.
q
Select the control circuit to which the current vacation
period should apply.
Current vacation period applies to circuit Rk1 Current vacation period applies to circuit Rk2
Current vacation period applies to DHW circuit The vacation period can be assigned to a single control circuit or any combination of all three control circuits (Rk1 and Rk2, DHW circuit).
To enter additional vacation periods, re-select
– – – – and repeat the steps in the fields
highlighted in gray.
EB 5576 EN 23
Operation
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Exit data point for vacation periods.
Note: Vacation periods can also be entered in parameter level PA5 (–> section 2.3).
Deleting vacation periods:
q
Under data point for vacation periods, select the start date of the period you wish to de
-
lete. Confirm selection.
q
Select – – – – . Delete vacation period.
Note: Vacation periods should be deleted by the end of the year so that they are not carried on into the following year.
24 EB 5576 EN
Operation
1.9 Setting room and DHW temperature set points
For the heating circuits, the desired room temperatures during the day (Day set point) and during the night (Night set point) can be entered into the controller. In the DHW circuit, the temperature you wish the DHW to be heated to can be set.
The temperature set points for the different control circuits are set at the rotary switches one after the other:
Desired temperature set point Switch Position Heating circuit 1*: Day set point Top Heating circuit 1*: Night set point Top Heating circuit 2*: Day set point Middle Heating circuit 2*: Night set point Middle DHW circuit*: DHW temperature set point Bottom
* Refer to page 169 for assignment
Parameters
WE Rotary switch / Range of values Day set point 20 °C Top, middle / –5 to 150 °C Night set point 15 °C Top, middle / –5 to 150 °C DHW temperature set point 60 °C Bottom / Min. to max. DHW temperature
Proceed as follows:
Turn appropriate rotary switch to “Set point temperature“. Display shows: temperature
q
Set temperature value. Return the rotary switch to the desired operating mode (left side).
EB 5576 EN 25
Operation
26 EB 5576 EN
Operation
Fig. 2 · Level structure of TROVIS 5576
q
Configuration and
parameter level
(start-up, see section 2)
PA4
PA5
PA6
CO7
CO6
CO1
PA2
Anl
CO2CO4CO5
End PA1
CO8
q
Operating level
(display of time and
operation, see section 1)
& key number
PA1/CO1: Heating circuit Rk1 ( ) PA2/CO2: Heating circuit Rk2 ( ) PA4/CO4: DHW heating PA5/CO5: System-wide parameters PA6/CO6: Communication parameters/
Modbus/meter bus communication
CO7: Device bus CO8: Initialization of free
inputs
Anl: System code number
2 Start-up
The modifications of the controller configuration and parameter settings described in this sec
-
tion can only be performed after the valid key number has been entered. The valid key number for initial start-up can be found on page 191. To avoid unauthorized
use of the key number, remove the page or make the key number unreadable. In addition, it is possible to enter a new, customized key number (–> section 7.20).
2.1 Setting the system code number
Various hydraulic schematics are available. Each system configuration is represented by a system code number. The different schematics are dealt with in section 4. Available controller functions are described in sections 5, 6 and 7.
Changing the system code number resets previously adjusted function blocks to their default settings (WE). Function block parameters and parameter level settings remain unchanged. The system code number is set in the configuration level.
Proceed as follows:
Switch to configuration and parameter level. Display shows: 0 0 0 0
q
Set valid key number. Confirm key number.
Display shows: PA1
q
Select Anl (-> Fig. 2). Activate editing mode for the system code number.
q
Edit system code number. Confirm system code number.
Display shows: End Return to operating level.
EB 5576 EN 27
Start-up
2.2 Activating and deactivating functions
A function is activated or deactivated in the associated function block. The numbers 0 to 24 in the top row of the display represent the respective function block numbers. When a config
­uration level is opened, the activated function blocks are indicated by a black square on the right-hand side below the function block number. For more details on function blocks, refer to section 12.1.
The functions are grouped by topics:
4
CO1: Heating circuit Rk1 ( )
4
CO2: Heating circuit Rk2 ( )
4
CO3: Not used
4
CO4: DHW heating
4
CO5: System-wide functions
4
CO6: Modbus and meter bus communication
4
CO7: Device bus
4
CO8: Initialization of free inputs
Proceed as follows:
Switch to configuration and parameter level. Display shows: 0 0 0 0
q
Set valid key number. Confirm key number.
Display shows: PA1
q
Select configuration level (-> Fig. 2). Open configuration level.
q
Select function block. Activated function blocks are marked by “- 1“. Deactivated function blocks are marked by “- 0“.
Activate editing mode for the function block. F__ blinks.
q
Activate the function block. Display shows:
F__ - 1
An activated function block is indicated by a black square below (right) the function block number in the top row of the controller display.
Or:
28 EB 5576 EN
Start-up
q
Deactivate the function block. Display shows: F__ - 0
Confirm settings. If the function block is not closed, further function block parameters can be adjusted. Proceed as follows: Make the desired changes and confirm. If applicable, the next function block parameter is displayed. Confirm all parameters to exit the opened function block.
To adjust additional function blocks, repeat the steps in the fields highlighted in gray.
q
Select End. Exit configuration level.
q
Select End. Return to operating level.
Note: All function block settings are saved in the non-volatile memory of the controller.
2.3 Changing parameters
Depending on the set system code number and the activated functions, not all parameters listed in the parameter list in the Appendix (–> section 12.2) might be available. The parameters are grouped by topics:
4
PA1: Heating circuit Rk1 ( )
4
PA2: Heating circuit Rk2 ( )
4
PA3: Not used
4
PA4: DHW heating
4
PA5: Parameters for various systems
4
PA6: Communication parameters
4
PA7: Not used
4
PA8: Not used
EB 5576 EN 29
Start-up
Proceed as follows:
Switch to configuration and parameter level.
Display shows: 0 0 0 0
q
Set valid key number.
Confirm key number.
Display shows: PA1
q
Select parameter level (-> Fig. 2). Open parameter level.
q
Select desired parameter. Activate editing mode for the parameter.
q
Edit the parameter. Confirm the parameter.
To adjust additional parameters, repeat the steps in the fields highlighted in gray.
q Select End.
Exit parameter level.
q Select End.
Return to the operating level.
Note: All function block settings are saved in the non-volatile memory of the controller.
2.4 Calibrating sensors
The connected sensors are calibrated in configuration level CO5. The following applies:
4
CO5 -> F01 - 1, CO5 -> F02 - 0, CO5 -> F03 - 0: Pt 1000 (Pt 100) sensors (default)
4
CO5 -> F01 - 0, CO5 -> F02 - 0, CO5 -> F03 - 0: PTC (Pt 100) sensors
4
CO5 -> F01 - 0, CO5 -> F02 - 1, CO5 -> F03 - 0: NTC (Pt 100) sensors
4
CO5 -> F01 - 1, CO5 -> F02 - 1, CO5 -> F03 - 0: Ni 1000 (Pt 100) sensors
4
CO5 -> F01 - 0, CO5 -> F02 - 0, CO5 -> F03 - 1: Pt 500 (Pt 100) sensors The resistance values of the sensors can be found on page 170. If the temperature values displayed at the controller differ from the actual temperatures, the
measured values of all connected sensors can be changed or readjusted. To calibrate a sen
-
30 EB 5576 EN
Start-up
Loading...
+ 164 hidden pages