Automation System TROVIS 5500
Heating and District Heating Controller
TROVIS 5575
Electronics from SAMSON
Mounting and
Operating Instructions
EB 5575 EN
®
Firmware version 1.6x
Edition January 2007
Page 2
Disclaimer of liability
Disclaimer of liability
We are constantly developing our products and therefore, reserve the right to change the
product or the information contained in this document at any time without notice.
We do not assume any liability for the accuracy or completeness of these mounting and op
erating instructions. Moreover, we do not guarantee that the buyer can use the product for
an intended purpose. SAMSON rejects any liability for claims by the buyer, especially
claims for compensation including lost profits or any other financial loss, except the damage
was caused intentionally or by gross negligence. If an essential term of the contract is
breached by negligence, SAMSON’s liability is limited to the foreseeable damage.
Safety instructions
The device may only be assembled, started up or operated by trained and
4
experienced personnel familiar with the product. Proper shipping and appropriate storage are assumed.
The controller has been designed for use in electrical power systems. For
4
wiring and maintenance, you are required to observe the relevant safety
regulations.
The TROVIS 5575 Heating Controller is available in various versions. The type designation
registered on the nameplate of the controller indicates the controller version:
Type designation (nameplate)Version
TROVIS 5575-000xStandard controller with illuminated display background and with
TROVIS 5575-001x
TROVIS 5575-002xController without illuminated display background and without
device bus
Controller with illuminated display background, with device bus
and with an additional pump output
device bus
These instructions apply to all versions of the TROVIS 5575-00xx Heating Controller.
6 EB 5575 EN
Page 7
Operation
1Operation
The controller is ready for use with the temperatures and operating schedules preset by the
manufacturer.
On start-up, the current time and date need to be set at the controller (–> section 1.5).
1.1Operating elements
The operating controls are located in the front panel of the controller and protected by a
Plexiglas door.
1.1.1 Rotary pushbutton and changeover key
Rotary pushbutton
Turn q:
*
Display, select parameters and function blocks
Press:
Confirm adjusted selection or settings
Changeover key
(use pen or any other pointed item to press)
Press to switch between operating level and configuration/pa-
rameter level
EB 5575 EN 7
Page 8
Operation
1.1.2 Rotary switches
Use the three rotary switches to adjust the desired operating mode (icons on the left) and the
relevant parameters (icons on the right).
The top and middle switches are assigned to the heating circuits (see page 121). The rotary
switch in the middle is not used in systems without a second heating circuit.
The bottom switch is assigned to the DHW circuit.
Rotary switch to adjust the operating modes of the heating circuit
Automatic/time-controlled operation
with switchover between day and night modes
Day mode (rated operation)
Night mode (reduced operation)
Control operation deactivated, frost protection only
Manual operation: correction value adjusted in percent
and activation/deactivation of the pumps
Rotary switch to adjust the parameters of the heating circuit
Day set point (rated room temperature)
Night set point (reduced room temperature)
Times-of-use for heating
Party mode
Controller time: setting current time, date and year
Rotary switch to adjust the operating modes of the DHW circuit
Automatic/time-controlled operation
with switchover between times when DHW heating
is permissible/impermissible
DHW heating deactivated, frost protection only
Manual operation: correction value adjusted in percent
and activation/deactivation of the pumps
8 EB 5575 EN
Page 9
Operation
Rotary switch to adjust the parameters of the DHW circuit
Set point for DHW temperature
Times-of-use for DHW heating
Times-of-use for DHW circulation pump
Party mode
Note!
If several rotary switches are set to “Parameter“ (right side),blinks on the display. The
controller cannot be operated.
1.2Operating modes
Day mode (rated operation)
Regardless of the programmed times-of-use and summer mode, the set points relevant for
rated operation are used by the controller.
Night mode (reduced operation)
Regardless of the programmed times-of-use, the set points relevant for reduced operation are
used by the controller.
Automatic/time-controlled operation
During the programmed times-of-use, the controller works in rated operation. Outside these
times-of-use, the controller is in reduced operation, unless control operation is deactivated
depending on the outdoor temperature. The controller switches automatically between both
operating modes.
Manual operation
Valves and pumps can be controlled manually (–> section 3).
EB 5575 EN 9
Page 10
Operation
1.3Display
During operation, the display indicates the current time as well as information about the op
eration of the controller. The times-of-use are represented by black squares below the row of
numbers at the top of the display. Icons indicate the operating status of the controller.
16 Valve Rk2: OPEN
17 Valve Rk2: CLOSED
18 Time-of-use
19 Control circuit assignment:
20 OT dependent control
deactivated
18
19
20
: Heating circuit 1
: Heating circuit 2
-
* UP1, UP2, SLP, UP5, bA9 indicate possible choices for pump selection in manual operating mode.
Fig. 1 · Icons
The controller status can be displayed in operating level (–> section 1.4).
TROVIS 5575-000x and TROVIS 5575-001x:
An illuminated display indicates that the controller is being operated or a fault exists.
TROVIS 5575-002x:
Version without illuminated display
10 EB 5575 EN
Page 11
1.4Displaying data
Operation
The time, date, public holidays and vacation periods as well as the temperatures of con
nected sensors and their set points can be retrieved and displayed with the help of the rotary
pushbutton.
Note!
Data can also be viewed in manual operating mode.
To do so, select Info, confirm and proceed as described below.
Proceed as follows:
Select value.
q
Depending on the configuration of the controller, the different data points are dis
played:
__:__ Time
Room temperature, heating circuit 1, 2
Outdoor temperature
Temperature at flow sensor VF, heating circuit 1, 2
Temperature at flow sensor VF1, primary heat exchanger circuit
Temperature at flow sensor VF2, DHW circuit
Temperature at solar collector sensor VF3
Temperature at return flow sensor RüF
-
-
Temperature at storage tank sensor SF1
Temperature at storage tank sensor SF2
Temperature at storage tank sensor SF2 of the solar circuit
Temperature at flow sensor VF4
Compare the set point/limit value and the actual value.
Press the rotary pushbutton to display the time and date.
EB 5575 EN 11
Page 12
Operation
1.5Setting the controller time
The current time and date need to be set immediately after start-up and after a power failure
of more than 24 hours has occurred. This is the case when the time blinks on the display.
Proceed as follows:
2423222120191817161514131211109876543210
Turn the top rotary switch to position“Controller
time“ (right side).
Display shows: time
Confirm the adjusted year.
Display shows: date (day.month)
q
Edit the date.
Confirm the adjusted date.
Display shows: time
Return the rotary switch to the desired operating mode
(left side).
12 EB 5575 EN
Page 13
Operation
1.6Setting the times-of-use
Three times-of-use can be set for each day of the week.
If only one time-of-use is required, the start and stop times of the second time-of-use must be
adjusted to identical values. In this case, the third time-of-use is not displayed.
If only two times-of-use are required, the start and stop times of the third time-of-use must be
adjusted to identical values.
The times-of-use for the different control circuits are adjusted at the rotary switches one afterthe other:
Time period/day1–71–7, 1, 2, 3, 4, 5, 6, 7 with 1–7 = daily,
Start first time-of-use06:00 00:00 to 24:00 h; in steps of 15 minutes
Stop first time-of-use22:00 00:00 to 24:00 h; in steps of 15 minutes
Start second time-of-use22:15 00:00 to 24:00 h; in steps of 15 minutes
Stop second time-of-use22:15 00:00 to 24:00 h; in steps of 15 minutes
Start third time-of-use–00:00 to 24:00 h; in steps of 15 minutes
Stop third time-of-use–00:00 to 24:00 h; in steps of 15 minutes
* Default values (WE) valid for heating circuit 1/primary heat exchanger circuit (top rotary switch)
WE*Range of values
1 = Monday, 2 = Tuesday, …, 7 = Sunday
EB 5575 EN 13
Page 14
Operation
Proceed as follows:Turn appropriate rotary switch to position
“Times-of-use”.
1–7
0123456789101112131415161718192021222324
Display shows:
Select period/day for which the times-of-use are to be
Display shows:
Edit start time (steps of 15 minutes).
q
,blinks
Confirm start time.
Display shows:
q
Edit stop time (steps of 15 minutes).
STOP
Confirm stop time.
Display shows:
START
The second time-of-use is set like the first time-of-use.
To set the times-of-use for each day, repeat the instructions in the fields highlighted in gray.
Return the rotary switch to the desired operating mode (left side).
Note!
Do not use the 1–7 menu to check the programmed times-of-use.
If this menu is opened after the times-of-use have been programmed, the schedule program
med for Monday is also adopted for all other days of the week.
-
14 EB 5575 EN
Page 15
Operation
1.7Setting party mode
Using the Party mode function, the controller continues or activates rated operation of the
controller during the time when the party timer is active, regardless of the adjusted
times-of-use. The party timer begins when the rotary switch has been returned to operating
mode“Automatic“. When the party timer has elapsed, the party function is reset to
00:00.
The party modes for the different control circuits are adjusted at the rotary switches one afterthe other:
Edit desired length of the one-off time-of-use.
Return the rotary switch to operating mode“Automatic“ (left side).
or the remaining time of the adjusted party timer
WERange of values
Note!
The time elapsing on the party timer is displayed in steps of 15 minutes.
EB 5575 EN 15
Page 16
Operation
1.8Activating extended operating level
After the key number 1999 has been adjusted, the following information can be viewed and
edited after the data points listed in section 1.4 have been displayed:
Flow rate
4
Heat capacity
4
Public holidays ““ (editable)
4
Vacation periods ““ (editable)
4
Valve positions
4
Switching states of the binary inputs
4
Info 2 · The following data are shown in the same sequence as shown below:
4
Controller ID
Memory capacity of data logging module (section 9.1)
255
Operating hours of solar circuit pump (refer to section 6.4)
Water flowmeter (refer to section 6.3)
Opening the extended operating level:
Switch to configuration and parameter level.
Display shows:
q
Set key number 1999.
Confirm key number.
Display shows: time
0 0 0 0
Note!
The additional information is no longer displayed when the key number 1999 is adjusted
again.
16 EB 5575 EN
Page 17
Operation
1.8.1 Setting public holidays
On public holidays, the times-of-use specified for Sunday apply. A maximum of 20 public
holidays may be entered.
Parameter
Public holidays–Extended operating level / 01.01 (1 Jan) to 31.12 (31 Dec)
To enter additional public holidays, re-select
lighted in gray.
Exit data point “Public holidays“.
WELevel / Range of values
In extended operating mode, select “Public holidays“.
q
Display shows:
Open data point “Public holidays“.
If applicable, select
q
Activate editing mode for public holiday.blinks.
Edit desired public holiday.
q
Confirm public holiday.
– – – –
– – – –
.
and repeat the steps in the fields high-
Note! Public holidays can also be adjusted in parameter level PA5 (–> section 2.3).
Deleting a public holiday:
q
Under data point “Public holidays“, select the holiday you wish to delete.
Confirm selection.
q
Select
– – – –
.
Delete the public holiday.
Note!
Public holidays that are not assigned to a specific date should be deleted by the end of the
year so that they are not carried on into the following year.
EB 5575 EN 17
Page 18
Operation
1.8.2 Setting vacation periods
During vacation periods, the controller constantly remains in reduced operating mode. A
maximum of 10 vacation periods can be entered. Each vacation period can be assigned
separately to the heating circuits Rk1 to Rk2 and/or to the DHW circuit.
Parameter
Vacation period (START, STOP)–Extended operating level / 01.01 to 31.12
To enter additional vacation periods, re-select
highlighted in gray.
WELevel / Range of values
In extended operating level, select “Vacation periods“.
q
Display shows:
Open data point “Vacation periods“.
START
Display shows:
If applicable, select
q
Activate editing mode for start date of vacation period.
blinks.
Edit start date of vacation period.
q
Confirm start date of vacation period.
q
Edit end of vacation period.
Display shows:
Confirm end date of the vacation period.
Black squares under 1 to 4 at the top of the display
indicate the assignment of the vacation periods to the
individual heating circuits.
q
Select the control circuit to which the current vacation
period should apply.
Current vacation period applies to circuit Rk1
Current vacation period applies to circuit Rk2
–
Current vacation period applies to DHW circuit
The vacation period can be assigned to a single control
circuit or any combination of all three control circuits
(Rk1 to Rk2, DHW circuit).
– – – –
, – –.– – (day.month)
– – – –
.
STOP, – –.– –
and repeat the steps in the fields
(day.month)
18 EB 5575 EN
Page 19
Operation
Exit data point “Vacation periods“.
Note! Vacation periods can also be adjusted in parameter level PA5 (–> section 2.3).
Deleting vacation periods:
Under “Vacation periods“, select the start date of the period you wish to delete.
q
Confirm selection.
Select
– – – –
q
Delete vacation period.
Note!
Vacation periods should be deleted by the end of the year so that they are not carried on
into the following year.
.
EB 5575 EN 19
Page 20
Operation
1.9Presetting room and DHW temperature set points
For the heating circuits, the desired room temperatures during the day (
during the night (
In the DHW circuit, the temperature you wish the DHW to be heated to can be adjusted.
The temperature set points for the different control circuits are adjusted at the rotary switches
one after the other:
Desired temperature set pointSwitchPosition
Heating circuit 1*: Day set pointTop
Heating circuit 1*: Night set pointTop
Heating circuit 2*: Day set pointMiddle
Heating circuit 2*: Night set pointMiddle
DHW circuit*: DHW temperature set pointBottom
* Refer to page 121 for assignment
Parameter
Day set point20 °C Top, middle / 0 to 40 °C
Night set point15 °C Top, middle / 0 to 40 °C
DHW temperature set point55 °C Bottom / Min. to max. DHW temperature
Proceed as follows:
Turn appropriate rotary switch to “Set point temperature“.
Display shows: temperature value
q
Change temperature value.
Return the rotary switch to the desired operating mode (left side).
Version without device bus: Settings in CO7 level do not apply.
(refer to section 2 on start-up)
CO1
CO4CO5
CO1CO2
PA2Anl
PA4
PA4
PA5CO7
EB 5575 EN 21
Page 22
Start-up
2Start-up
The modifications of the controller configuration and parameter settings described in this sec
tion can only be performed after the valid key number has been adjusted.
The valid key number for initial start-up can be found on page 134. To avoid unauthorized
use of the key number, remove the page or make the key number unreadable. In addition, it
is possible to adjust a new, customized key number (–> section 7.15).
2.1Setting the system code number
21 different hydraulic schemes are available in the TROVIS 5575-000x standard version
and in the TROVIS 5575-002x version. The TROVIS 5575-001x version has two additional
hydraulic schemes. Each system configuration is represented by a system code number. The
different schematics are dealt with in section 4. Available controller functions are described
in sections 5, 6 and 7.
Changing the system code number resets previously adjusted function blocks to their default
values (WE). Function block parameters and parameter level settings remain unchanged.
The system code number is adjusted in configuration level.
Proceed as follows:
Switch to configuration and parameter level.
Display shows:
q
Set valid key number.
Confirm key number.
Display shows:
q
Select
Anl.
Activate editing mode for the system code number.
q
Edit system code number.
Confirm system code number.
Display shows:
Return to operating level.
0 0 0 0
PA1
End
-
22 EB 5575 EN
Page 23
Start-up
2.2Activating and deactivating functions
A function is activated via the associated function block. The numbers 0 to 24 in the top row
of the display represent the respective function block numbers. When a configuration level is
opened, the activated function blocks are indicated by a black square on the right-hand side
below the function block number. For more details on function blocks, refer to section 12.1.
The functions are grouped by topics:
CO1: Heating circuit Rk1 ()
4
CO2: Heating circuit Rk2 ()
4
CO3: Not used
4
CO4: DHW heating
4
CO5: System-wide functions
4
CO6: Not used
4
CO7: Device bus
4
Proceed as follows:
Switch to configuration and parameter level.
Display shows:
q
Set valid key number.
Confirm key number.
Display shows:
q
Select configuration level (-> Fig. 2).
Open configuration level.
q
Select function block.
Activated function blocks are marked by “- 1“.
Deactivated function blocks are marked by “- 0“.
Activate editing mode for the function block.
F__
blinks.
q
Activate the function block.
Display shows:
An activated function block is indicated by a black square below (right) the function
block number in the top row of the controller display.
Or:
0 0 0 0
PA1
F__ - 1
EB 5575 EN 23
Page 24
Start-up
Deactivate the function block.
q
Display shows:
q
To adjust additional function blocks, repeat the steps in the fields highlighted in gray.
q
q
Confirm settings.
If the function block is not closed, further function block parameters can be adjusted.
Proceed as follows:
Make the desired changes and confirm.
If applicable, the next function block parameter is displayed.
Confirm all parameters to exit the opened function block.
Select
End
Exit configuration level.
Select
End
Return to operating level.
F__ - 0
.
.
24 EB 5575 EN
Page 25
2.3Changing parameters
Start-up
Depending on the adjusted system code number and the activated functions, not all parame
ters listed in the parameter list in the Appendix (–> section 12.2) might be available.
The parameters are grouped by topics:
PA1: Heating circuit Rk1 ()
4
PA2: Heating circuit Rk2 ()
4
PA3: Not used
4
PA4: DHW heating
4
PA5: System-wide functions
4
PA6: Not used
4
PA7: Not used
4
Proceed as follows:
Switch to configuration and parameter level.
Display shows:
Set valid key number.
q
Confirm key number.
Display shows:
q
Select parameter level (-> Fig. 2).
Open parameter level.
q
Select desired parameter.
Activate editing mode for the parameter.
q
Edit the parameter.
Confirm the parameter.
To adjust additional parameters, repeat the steps in the fields highlighted in gray.
q
Select
End
Exit parameter level.
q
Select
End
Return to operating level.
0 0 0 0
PA1
.
.
-
EB 5575 EN 25
Page 26
Start-up
2.4Calibrating the sensors
The connected sensors are calibrated in configuration level CO5.
The following applies:
CO5 -> F01 - 1 and CO5 -> F02 - 1: Ni 1000 (Pt 100) sensors
4
The resistance values of the sensors can be found on page 122.
If the temperature values displayed at the controller differ from the actual temperatures, the
measured values of all connected sensors can be changed or readjusted. To calibrate a sen
sor, the currently displayed sensor value must be changed such that it corresponds with a
temperature value (reference value) measured directly at the point of measurement.
Sensor calibration is to be activated in CO5 via function block F20.
An improper sensor calibration can be deleted by setting F20 - 0.
Proceed as follows:
-
Switch to configuration and parameter level. Display shows:
q
Set valid key number.
Confirm key number. Display shows:
q
Select configuration level CO5.
Open configuration level CO5.
q
Select function block F20.
Activate editing mode for function block F20.
q
Select appropriate sensor icon:
Room sensor RF, heating circuits 1, 2
Outdoor sensor AF1
Flow sensor VF, heating circuits 1, 2
Flow sensor VF1, primary heat exchanger circuit
Flow sensor VF2, DHW circuit
Solar collector sensor VF3
26 EB 5575 EN
PA1
0 0 0 0
Page 27
Return flow sensor RüF
Storage sensor SF1
Storage sensor SF2
Storage sensor SF2 for solar circuit
Flow sensor VF4
Display measured value.
Measured value blinks.
Correct measured value.
q
Read the actual temperature directly from the thermometer at the point of measurement
and enter this value as reference temperature.
Confirm corrected measured value.
Additional sensors are calibrated similarly.
q Select
q
q
End
.
Exit configuration level.
Select
End
.
Return to operating level.
Start-up
2.5Resetting to default values
All parameters in parameter levels PA1, PA2 and PA5 adjusted with the rotary switches, ex
cept for the maximum flow temperature and the return flow limiting temperature in
PA1/PA2, can be reset to their default values (WE).
Proceed as follows:
Switch to configuration and parameter level.
q
Set key number 1991.
Confirm key number.
Note! Resetting the parameters to their default values generates an “Err 2“ alarm, which is
automatically reset shortly after midnight.
EB 5575 EN 27
-
Page 28
Manual operation
3Manual operation
Switch to manual operating mode to configure all outputs (see wiring diagram in sec
tion 11).
Manual operation for the different control circuits is adjusted at the rotary switches:
POS_ : Correction value in percent
UP_: Activation of the circulation pump
SLP: Activation of the storage tank charging pump
Confirm selection.
Display blinks.
q
Edit the correction value or activate/deactivate the circulation pump etc.
Confirm edited settings.
The modified values remain active as long as the controller is in manual mode.
Return the rotary switch to the desired operating mode (left side).
Manual operation of the selected control circuit is deactivated by switching to any other
operating mode.
-
Note!
Simply setting the rotary switch to“Manual operation“ does not have any affect on the
outputs. You have to actually enter a correction value or activate/deactivate the pumps to
configure the outputs.
In manual operating mode, frost protection (–> section 7.2) is not activated.
28 EB 5575 EN
Page 29
Systems
4Systems
21 (23 in TROVIS 5575-001x) different hydraulic schemes are available.
The systems can be designed as primary or secondary systems. The fundamental hydraulic
differences between a primary and a secondary system are illustrated in Fig. 3.
1. A mixing valve replaces the heat exchanger in the heating/DHW circuit
4
2. A storage tank charging pump replaces the primary solenoid/thermoelectric valve
4
The controller settings do not have to be changed.
1.
Primary system
RüF1VF1UP1RK1RK1RF1VF1UP1RüF1 RF1
BE
BA
AE
RK
Secondary system
BE
BA
AE
RK
2.
Primary system
BE
BA
AE
RK
WW
Secondary system
KW
SF1SLP
BE
BA
AE
RK
Fig. 3 · Differences between primary and secondary systems
WW
KW
SF1SLP
EB 5575 EN 29
Page 30
Systems
Boiler systems:
Single-stage boiler systems can be configured to include any system whose heating circuits
and DHW circuit include just one heat exchanger. These systems are Anl 1.0, 1.5, 1.6, 2.x,
3.0, 4.0 and 4.1.
The boiler can be controlled by an on/off output (CO1 -> F12 - 0).
Which controller functions are available depends on the selected system code number (Anl).
5.1Weather-compensated control
When weather-compensated control is used, the flow temperature is adjusted depending on
the outdoor temperature. The heating characteristic in the controller defines the flow temper
ature set point as a function of the outdoor temperature (–> Fig. 5). The outdoor temperature
required for weather-compensated control can either be measured at an outdoor sensor or
transmitted from a connected device bus.
[˚C]
t
VL
130
120
110
100
90
80
70
60
50
40
30
20
Fig. 5 · Gradient characteristics
2.62.93.2
2.4
2.2
2.0
1.8
1.6
1.4
1.2
1.0
0.8
0.6
0.4
0.2
t
A
-20 [
-16-12-8-4048121620
C]
˚
t
VL
t
A
Flow temperature
Outdoor temperature
-
Functions
WEConfiguration
Outdoor sensor AF11CO1 -> F02 - 1
Receive value from AF20CO7 -> F09 - 1; register no.
50 EB 5575 EN
Page 51
Functions of the heating circuit
TROVIS 5575-000x and TROVIS 5575-001x:
The outdoor temperature is alternatively received over the device bus when the following
configurations are made:
CO7 -> F01- 1 and CO7 -> F07 - 1
An outdoor temperature input independent from AF1 can be sent over the device bus for a
second heating circuit following configurations are made:
CO2 -> F02 - 1 and CO7 -> F09 -> 1
A second outdoor sensor cannot be connected.
TROVIS 5575-002x:
Version without device bus: The outdoor temperature can be only be measured directly over
the outdoor sensor AF.
5.1.1 Gradient characteristic
Basically, the following rule applies: a decrease in the outdoor temperature causes the flow
temperature to increase. By varying the parameters
characteristic to your individual requirements. Increasing
temperature, decreasing
forms a parallel transport of the heating characteristic in upward or downward direction.
Outside the times-of-use, reduced set points are used for control:
The reduced flow set point is calculated as the difference between the adjusted values for
Day set point
The parameters
limits of the flow temperature. A separate gradient characteristic can be selected for the limi
tation of the return flow temperature.
Examples for adjusting the characteristic:
Old building, radiator design 90/70:Gradient approx. 1.8
4
New building, radiator design 70/55:Gradient approx. 1.4
4
New building, radiator design 55/45:Gradient approx. 1.0
4
Underfloor heating depending on arrangement: Gradient smaller 0.5
4
(rated room temperature) and
Max. flow temperature
Gradient
in a lower flow temperature. The parameter
and
Gradient
Night set point (reduced room temperature).
Min. flow temperature
and
Gradient
Level
, you can adapt the
results in a higher flow
Level
per-
mark the upper and lower
-
Note!
Particularly for control operation without room sensor, the adjusted room temperatures for
day (Day set point) and night (Night set point) only become effective satisfactorily when the
heating characteristic has been adapted to the building/heating surface layout.
WERotary switch / Range of values
Day set point20 °CTop, middle / 0 to 40 °C
Night set point15 °CTop, middle / 0 to 40 °C
Parameters
WEParameter level / Range of values
Gradient, flow1,8*PA1, 2 / 0.2 to 3.2
Level, flow0 °CPA1, 2 / –30 to 30 °C
Min. flow temperature20 °CPA1, 2 / 5 to 130 °C
Max. flow temperature90 °C* PA1, 2 / 5 to 130 °C
* With CO1, 2 -> F05 - 1, the following applies: Gradient, flow / 0.2 to 1.0 (1.0)
Max. flow temperature / 5 to 50 °C (50 °C)
5.1.2 4-point characteristic
The 4-point characteristic allows you to define your own heating characteristic.
It is defined by 4 points each for the
and the
flow temperature
Min. flow temperature
t
[˚C]
VL
100
t
VLmax
90
80
70
60
50
40
30
t
VLmin
20
10
Fig. 6 · 4-point characteristic
Return flow temperature
mark the upper and lower limits of the flow temperature.
characteristic has been selected, provided no additional functions (e.g. Optimization, Flash
adaptation) have been selected.
Functions
4-point characteristic0CO1, 2 -> F11 - 1
Parameters
Outdoor
temperature
Flow temperaturePoint 1
Reduced flow
temperature
Return flow
temperature
Min. flow temperature20 °CPA1, 2 / 5 to 130 °C
Max. flow temperature90 °C*PA1, 2 / 5 to 130 °C
* *With CO1, 2 -> F05 - 1, the following applies: Max. flow temperature / 5 to 50 °C (50 °C)
Point 1
Point 2
Point 3
Point 4
Point 2
Point 3
Point 4
Point 1
Point 2
Point 3
Point 4
Point 1 to 4 65 °CPA1, 2 / 5 to 90 °C
WEConfiguration
WEParameter level / Range of values
–15 °C
–5 °C
5°C
15 °C
70 °C
55 °C
40 °C
25 °C
60 °C
40 °C
20 °C
20 °C
PA1, 2 / –40 to 50 °C
PA1, 2 / 5 to 130 °C
PA1, 2 / 5 to 130 °C
Note!
The 4-point characteristic function can only be activated when the Adaptation function is not
active (CO1, 2 -> F08 - 0).
5.2Fixed set point control
During the times-of-use, the flow temperature can be controlled according to a fixed set
point. Outside the times of use, the controller adjusts the reduced flow temperature.
Set the desired rated flow temperature as
Night set point
as
.
Day set point
, and the reduced flow temperature
EB 5575 EN 53
Page 54
Functions of the heating circuit
Functions
Outdoor sensor AF11CO1 -> F02 - 0
Parameter
Day set point50 °CTop, middle / Min. to max. flow temperature
Night set point30 °CTop, middle / Min. to max. flow temperature
Parameters
Min. flow temperature20 °CPA1, 2 / 5 to 130 °C
Max. flow temperature90 °CPA1, 2 / 5 to 130 °C
WEConfiguration
WERotary switch / Range of values
WEParameter level / Range of values
Note!
A fixed set point control in heating circuit 2 with CO2 -> F02 - 0 can only be configured if
CO1 -> F02 - 0 is set as well, because the heating circuit 2 with CO2 -> F02 - 0 only uses
the measured outdoor temperature provided by heating circuit 1.
5.3Underfloor heating/drying of jointless floors
Using function block setting CO1, 2 -> F05 - 1, the respective heating circuit is configured as
an underfloor heating circuit. In doing so, the controller at first only limits the range of values
of the heating characteristic gradient and the maximum flow temperature in parameter levels PA1, 2:
Range of values of the gradient: 0.2 to1.0
4
Range of values of the maximum flow temperature: 5 to 50 °C
4
In addition, it is possible to activate the Drying of jointless floors function. In connection with
this, the function block parameters are listed which appear after activating this function
block. They determine the drying process: the first heating up phase always starts with a flow
temperature of 25 °C. In the course of 24 hours, this temperature is raised by the value en
tered in
within the first 24 hours. If the
number of days entered in
duction
to 0, the temperature maintaining phase moves directly to automatic mode.
Temperature rise
determines the temperature reduction downwards. If the
, i.e. the default setting causes the temperature to rise to 30 °C
Maximum temperature
Maintaining time for maximum temperature
is reached, it is kept constant for the
. The
Temperature re
Temperature reduction
-
-
is set
54 EB 5575 EN
Page 55
Functions of the heating circuit
The drying function is activated by changing the setting
. The course of the drying process can be monitored in the information level over the
duction
STOPtoSTART
after
Temperature re
icon of flow temperature display () of the associated heating circuit:
Temperature build-up phase
Temperature maintaining phase
Temperature reducing phase
The drying process has been successfully completed when the additional icon in the flow
temperature display goes out after the last phase without the operating fault appearing.
STOP
on the display indicates that there has been a deviation of flow temperature of more
than 5 °C for longer than 30 minutes. The function is canceled by the controller in such
cases. While
appears on the display, the controller keeps the flow temperature con
-
STOP
stant at 25 °C.
A power failure while the drying function is active or when
STOP
appears on the display automatically leads to the drying function restarting.
In systems in which the drying function had to be interrupted due to DHW heating (e.g.
Anl 2.1, 4.1), storage tank charging does not occur while the drying function is active, provided it is not used for frost protection of the storage tank.
Note!
The function block parameter can only be accessed when the function has started by deactivating the function block and activating it again.
-
FunctionsWEConfiguration
Underfloor heating
Drying of jointless floors
0
5 °C/24 h
45 °C
4
0 °C/24 h
STOP
CO1, 2 -> F05 - 1
Temperature rise / 1 to 10 °C/24 h
Maximum temperature / 25 to 60 °C
Maintaining time for max. temperature / 1 to 10 days
Temperature reduction / 0 to 10 °C/24 h
START
EB 5575 EN 55
Page 56
Functions of the heating circuit
5.4Deactivation depending on outdoor temperature
5.4.1 OT deactivation value in rated operation
If the outdoor temperature exceeds the limit entered in
, the heating circuit concerned is put out of service immediately. The valve is closed and the
tion
OT deactivation value in rated opera
-
pump is switched off after t = 2 x valve transit time. Heating operation is restarted immediately
when the outdoor temperature falls below this value (less 0.5 °C hysteresis).
With the default settings, this means that, during the warm season, the system is switched off at
an outdoor temperature of 22 °C.
Parameter
OT deactivation value
in rated operation
WEParameter level / Range of values
22 °CPA1, 2 / 0 to 50 °C
5.4.2 OT deactivation value in reduced operation
If the outdoor temperature exceeds the limit value
the heating circuit concerned is put out of service immediately. The valve is closed and the
pump is switched off after t = 2 x valve transit time. Heating operation is restarted immediately
when the outdoor temperature falls below this value (less 0.5 °C hysteresis).
With the default settings, this means that, at night, the system is switched off at an outdoor
temperature of 15 °C to save energy. Nevertheless, remember that the system requires some
time in the morning to heat up the building.
Parameter
OT deactivation value
in reduced operation
WEParameter level / Range of values
15 °CPA1, 2 / –20 to 50 °C
OT deactivation value in reduced operation
5.4.3 OT activation value in rated operation
,
If a heating circuit is in reduced operation (automatic operating mode), the circuit is auto
matically transferred to rated operation when the outdoor temperature falls below the limit
OT activation value in rated operation
value
. When the limit value is exceeded (plus 0.5 °C
hysteresis), reduced operation is restarted.
This function is activated at very low temperatures to avoid that the building cools down ex
cessively outside the times-of-use when low outdoor temperatures occur.
Parameter
OT activation value
in rated operation
WEParameter level / Range of values
–15 °C PA1, 2 / –20 to 5 °C
56 EB 5575 EN
-
-
Page 57
Functions of the heating circuit
5.4.4 Summer mode
Summer mode is activated depending on the mean daytime temperature (measured between
7.00h and 22.00h) during the desired period.
If the mean daytime temperature exceeds the
OT limit value in summer mode
on n successive
days, summer mode is activated on the following day. This means that the valves in all heat
ing circuits are closed and the circulation pumps are switched off after t = 2 x valve transit
time. If the mean daytime temperature remains below the
OT limit value in summer mode
on
m successive days, summer mode is deactivated on the following day.
Functions
Summer mode0
WEConfiguration
CO5 -> F04 - 1
01.06
2
30.09
1
18 °C
Start summer mode/ 01.01 (1 Jan) to 31.12 (31 Dec)
No. of days until activation / 1 to 3
Stop summer mode / 01.01 to 31.12
No. of days until deactivation / 1 to 3
OT limit value in summer mode /0 to 30 °C
Note!
Summer mode only becomes effective when the controller is in automatic mode ().
5.5Delayed outdoor temperature adaptation
-
The calculated outdoor temperature is used to determine the flow temperature set point. The
heat response is delayed when the outdoor temperature either decreases, increases or increases and decreases. If the outdoor temperature varies by, for example, 12 °C within a
very short period of time, the calculated outdoor temperature is adapted to the actual out
Delay
door temperature in small steps. Assuming a
C
°°12
th
==
Ch
3
.
4
/
of 3 °C/h, the adaptation would take
-
Note!
The delayed outdoor temperature adaptation helps avoid unnecessary overloads of central
heating stations in combination with either overheated buildings occurring, for example, due
to warm winds, or temporarily insufficient heating due to the outdoor sensor being exposed
to direct sunshine.
In operating level, the outdoor temperature blinks on the display while delayed outdoor tem
-
perature adaptation is active. The calculated outdoor temperature is displayed.
EB 5575 EN 57
Page 58
Functions of the heating circuit
Functions
Delayed OT adaptation when OT decreases0CO5 -> F05 - 1
Delayed OT adaptation when OT increases0CO5 -> F06 - 1
WEConfiguration
3 °C/h Delay / 1 to 6 °C/h
5.6Remote operation
Apart from measuring the room temperature, the Type 5244 Room Panel (PTC room sensor)
and Type 5257-5 Room Panel (Pt 1000 sensor) provide the following opportunities of influ
encing the control process:
Selection of the operating mode: – Automatic mode
4
Set point correction: during rated operation, the room temperature set point can be in
4
creased or reduced by up to 5 °C using a continuously adjustable rotary knob.
When the room sensor is activated and the remote operation (room panel) is connected and
activated, the measured room temperature is displayed. Nevertheless, it is not used for control unless the Optimization, Adaptation or Flash adaptation functions have been activated.
Fig. 7 · Wiring plan for Type 5244/5257-5 Room Panels to TROVIS 5575 for Rk1 or Rk2
Function
Rooms sensors RF1/20CO1, 2 -> F01 - 1
WEConfiguration
58 EB 5575 EN
Page 59
Functions of the heating circuit
TROVIS 5575-000x and TROVIS 5575-001x:
Alternatively, the TROVIS 5570 Room Panel can be connected when the following configu
rations are made:
CO7 -> F01 -1 and CO7 -> F03 - 1 and CO7 -> F04 - 1 (see section 7.11.5)
Day set point
The
formed at the room panel. Only the calculated flow temperature set point or the room tem
perature set point (for flash adaptation and adaptation) are changed accordingly.
The evaluation of a room temperature sensor connected to the terminals RF is not possible
for this control circuit when a TROVIS 5570 Room Panel is configured.
TROVIS 5575-002x:
Version without device bus: The TROVIS 5570 Room Panel cannot be connected.
set by the rotary switch remains unaffected by set point corrections per
-
-
-
5.7Optimization
This function requires the use of a room sensor. Depending on the building characteristics,
the controller determines and adapts the required preheating time (maximum 8 hours) to ensure that the desired
ence room when the time-of-use starts. During the preheating period, the controller heats
with the max. flow temperature. This temperature is built up in steps of 10 °C. As soon as the
Day set point
Depending on the room sensors, the controller switches off the heating system up to one hour
before the time-of-use ends. The controller chooses the deactivation time such that the room
temperature does not drop significantly below the desired value until the time-of-use ends.
During the preheating period and the premature deactivation of the heating system, the
iconsorblink on the display. Outside the times-of-use, the controller monitors the
Night set point
point, the controller heats with the max. flow temperature until the measured room tempera
ture exceeds the adjusted value by 1 °C.
Day set point
has been reached, weather-compensated control is activated.
(reduced room temperature). When the temperature falls below the night set
(rated room temperature) has been reached in the refer-
-
Note!
Direct sunshine can cause the room temperature to increase and thus result in the premature
deactivation of the heating system.
When the room temperature decreases while the heating system is temporarily outside its
times-of-use, this can prematurely cause the controller to heat up to the adjusted
Day set point20 °CTop, middle/0to40°C
Night set point15 °CTop, middle/0to40°C
WEConfiguration
WERotary switch / Range of values
5.8Flash adaptation
To achieve that the controller reacts immediately to room temperature deviations during
rated or reduced operation, adjust the function block setting CO1, 2 -> F09 - 1.
and
Day set
Gain K
The heating is then always switched off as soon as the room temperature exceeds the
or
point
Night set point
by 2 °C.
Heating first starts again when the room has cooled off and the room temperature is 1 °C
above the
Set point
are set to a value other than 0. The
perature set point is corrected by 1 °C. A
. The flow temperature set point is corrected if the
Cycle time
determines the intervals at which the flow tem-
Gain K
set to a value other than 0 causes a direct
p
Cycle time
increase/decrease in flow temperature set point when a sudden deviation in room temperature arises. A
Gain K
setting of 10.0 is recommended.
p
Note!
Cooling loads, such as drafts or open windows, affect the control process!
Rooms may be temporarily overheated when the cooling load has been eliminated!
Day set point20 °CTop, middle, bottom/0to40°C
Night set point15 °CTop, middle, bottom/0to40°C
Parameters
Flow day set point50 °CPA1, 2 / 5 to 130 °C
Flow night set point30 °CPA1,2/5to130°C
WEConfiguration
CO1, 2 -> F09 - 1
20 min
0
WERotary switch / Range of values
WEParameter level / Range of values
Cycle time / 1 to 100 min
K
(gain) / 0 to 25
p
-
.
EB 5575 EN 61
Page 62
Functions of the heating circuit
5.9Adaptation
The controller is capable of automatically adapting the heating characteristic to the building
characteristics, provided a gradient characteristic has been set (CO1, 2 -> F11 - 0). The ref
erence room, where the room sensor is located, represents the entire building and is moni
tored to ensure that the room set point (
Day set point)
is maintained. When to mean mea
sured room temperature in rated operation deviates from the adjusted set point, the heating
characteristic is modified accordingly for the following time-of-use. The corrected value is
displayed in parameter levels PA1, 2 under
Day set point20 °CTop, middle/0to40°C
Night set point15 °CTop, middle / 0 to 40 °C
WEConfiguration
WERotary switch / Range of values
Gradient, flow
.
Note!
If the Flash adaptation function is already configured with a small cycle time, the Adaptation
function should not be configured as well.
-
-
-
62 EB 5575 EN
Page 63
Functions of the DHW circuit
6Functions of the DHW circuit
6.1DHW heating in the storage tank system
Start storage tank charging
WW
SLP
Fig. 8 · Schematics of a storage tank system
SF1
ZP
KW
The controller begins charging the storage tank when the water temperature measured at
sensor SF1 falls below the
DHW temperature set point
the system exceeds the desired charging temperature, the controller tries to reduce the flow
temperature in the heating circuit for up to 3 minutes before the storage tank charging pump
is activated. When there is no heating operation or when the flow temperature in the system
is lower, the storage tank charging pump is switched on immediately.
If the function CO4 -> F15 - 1 (SLP ON depending on return flow temperature) is activated,
the primary valve is opened without simultaneously operating the storage tank charging
pump. The storage tank charging pump is not switched on before the primary return flow
temperature has reached the temperature currently measured at storage sensor SF1.
This function enables storage tank charging when the heating system is switched off, e.g. in
summer mode, without cooling down the storage tank first by filling it with cold flow water.
The storage tank charging pump does not start operation before a sufficiently high tempera
ture has been reached at the heat exchanger.
SLPStorage tank charging
pump
SF1Storage sensor 1
ZPCirculation pump
WWHot water
KWCold water
by 0.1 °C. If the flow temperature in
-
Note!
Instead of the parameter
DHW temperature
, the
Charging temperature
solute value at the rotary switch if a storage tank thermostat is used.
can be set as the ab
EB 5575 EN 63
-
Page 64
Functions of the DHW circuit
Time-controlled switchover of storage tank sensors
By configuring a second storage tank sensor SF2 over the function block CO4 -> F19 -1, it is
possible to determine that the storage tank sensor SF1 is used for day mode in the DHW cir
cuit and that the storage tank sensor SF2 is used for night mode. As a result, different stor
age tank volumes can be kept at a constant temperature according to a time schedule, and
also at different temperatures if the
DHW set point
and
Sustained DHW temperature
differ
from one another.
Stop storage tank charging
The controller stops charging the storage tank when the water temperature measured at sen
sor SF1 has reached the temperature T =
DHW temperature+hysteresis
heating operation or when the flow temperature demand in the system is lower, the corre
. When there is no
sponding valve is closed.
The storage tank charging pump is switched off after t =
x
pump
valve transit time
.
lag time of storage tank charging
With the default settings, the temperature in the storage tank is increased by 5 °C to reach
50 °C when the storage tank temperature falls below 45 °C. The charging temperature is
calculated from the DHW temperature (45 °C) plus the charging temperature boost (10 °C),
which equals 55 °C. When the storage tank has been charged, the heating valve is closed
and the charging pump continues operation for the time t (lag). Outside the times-of-use, the
storage tank is only charged when the temperature falls below 40 °C (
perature
). In this case, the tank is charged with a charging temperature of 50 °C until 45 °C
Sustained DHW tem-
is reached in the tank.
Functions
Storage sensor SF11CO4 -> F01 - 1
Storage sensor SF2CO4 -> F02 (- 1 when CO4 -> F19 - 1)
SLP ON depending on return flow temperature0CO4 -> F15
Time-controlled switchover of storage sensors0CO4 -> F19 (- 1 only when CO4 -> F02 - 1)
Parameter
DHW temperature set point or charging
temperature set point with CO4 -> F01 - 0
Parameters
Min. DHW temperature*40 °CPA4 / 5 to 90 °C
Max. DHW temperature*60 °CPA4 / 5 to 90 °C
Hysteresis**5 °CPA4 / 0 to 30 °C
Charging temperature boost***10 °CPA4 / 0 to 50 °C
WEConfiguration
WERotary switch / Range of values
55 °CBottom / Min. to max. DHW temperature
WEParameter level / Range of values
-
-
64 EB 5575 EN
Page 65
Functions of the DHW circuit
Parameters
Lag of storage tank charging pump0.5PA4 / 0 to 10.0
Sustained DHW temperature40 °CPA4 / 20 to 90 °C
*Parameters serve as limitation of the adjustment range for the DHW temperature to be set
at the rotary switch
** Deactivation value T =
*** Charging temperature T =
DHW temperature+hysteresis
DHW temperature+charging temperature boost
WEParameter level / Range of values
6.1.1 DHW circuit additionally controlled by a globe valve
In system Anl 11.1, the following version with globe valve can be configured instead of the
three-way valve control in the DHW circuit:
Rk2/Y2Control circuit/valve 2
SLPStorage tank charging
SF1Storage sensor 1
VF2Flow sensor 2
ZPCirculation pump
WWHot water
KWCold water
Fig. 9 · Schematics of a storage tank system with a globe valve for return flow temperature limitation
Globe valve and temperature sensor VF2 are used exclusively for return flow temperature
limitation in the schematics shown above. The pre-control circuit provides at least the same
flow temperature as in the standard schematic version which is calculated from
+
perature set point
Charging temperature boost+Primary exchanger control boost set
point.
The functions and parameters of the DHW heating in the storage tank system are upgraded
by the following settings:
FunctionWEConfiguration
DHW circuit additionally controlled by a
globe valve
ParameterWEParameter level / Range of values
Maximum return flow temperature65 °C PA4 / 20 to 90 °C
0CO4 -> F20 - 1
pump
DHW tem
-
EB 5575 EN 65
Page 66
Functions of the DHW circuit
6.2DHW heating in the storage tank charging system
Start storage tank charging
TLPExchanger charging pump
SLP
TLP
Fig. 10 · Schematics of a storage tank charging system
VF
WW
SF1
SF2
ZP
KW
The controller begins charging the storage tank when the water temperature measured at
sensor SF1 falls below the
DHW temperature set point
the system exceeds the desired charging temperature, the controller tries to reduce the flow
temperature in the heating circuit for up to 3 minutes before the exchanger charging pump is
activated together with the storage tank charging pump.
When there is no heating operation or when the flow temperature in the system is lower, the
exchanger charging pump is switched on immediately. If the temperature currently measured
at sensor SF1 is reached at sensor VF, the storage tank charging pump is switched on.
If a storage tank thermostat is used, the storage tank charging pump is switched on when the
temperature T =
charging temperature
– 5 °C is reached at sensor VF.
VFFlow sensor
SLPStorage tank charging pump
SF1Storage sensor 1
SF2Storage sensor 2
ZPCirculation pump
WWHot water
KWCold water
by 0.1 °C. If the flow temperature in
Note!
Instead of the
DHW temperature
parameter, the
Charging temperature
can be adjusted as
absolute value at the rotary switch if a storage tank thermostat is used.
When the flow sensor VF4 is activated, the set point in the heat exchanger circuit is influ
enced by the system deviation in the storage tank charging circuit upon activation of the stor
age tank charging pump: if the temperature measured at flow sensor VF4 is lower than the
desired charging temperature, the set point in the heat exchanger circuit is increased in steps
of 1 °C.
When the set point in the heat exchanger charging circuit reaches the
perature
value, the set point is no longer increased. “Err 4“ alarm is generated.
Max. charging tem
-
66 EB 5575 EN
-
Page 67
Functions of the DHW circuit
Note!
The set point in the heat exchanger circuit which is valid at the end of the charging cycle will
be used again at the beginning of the next cycle.
If times-of-times have been set for DHW heating, the
the rotary switch is applied during these times-of-use. Outside the times-of-use, the
DHW temperature
is used. This does not apply when a storage tank thermostat is used.
Set point DHW temperature
adjusted at
Sustained
Time-controlled switchover of storage tank sensors
By configuring a second storage tank sensor SF2 over the function block CO4 -> F19 -1, it is
possible to determine that the storage tank sensor SF1 is used for day mode in the DHW cir
cuit and that the storage tank sensor SF2 is used for night mode. As a result, different stor
age tank volumes can be kept at a constant temperature according to a time schedule, and
also to different temperatures if the
DHW set point
and
Sustained DHW temperature
differ
from one another.
Stop storage tank charging
The controller stops charging the storage tank when the water temperature measured at sensor SF2 has reached the temperature T =
DHW temperature+hysteresis
. To do so, the
exchanger charging pump is switched off first.
When there is no heating operation or when the flow temperature demand in the system is
lower, the corresponding valve is closed. The storage tank charging pump is switched off af-
lag of storage tank charging pumpxvalve transit time
ter t =
Functions
Storage tank sensor SF11CO4 -> F01 - 1
Storage tank sensor SF21CO4 -> F02 - 1
Flow sensor VF40CO4 -> F05
Time-controlled switchover of storage
sensors
Parameter
DHW temperature set point or charging tem
perature set point with CO4 -> F01 - 0
Parameters
Min. DHW temperature*40 °CPA4 / 5 to 90 °C
Max. DHW temperature*60 °CPA4 / 5 to 90 °C
WEConfiguration
0CO4 -> F19
WERotary switch / Range of values
-
55 °CBottom /Min. to max. DHW
WEParameter level / Range of values
temperature
.
-
EB 5575 EN 67
Page 68
System-wide functions
Parameters
Hysteresis**5 °CPA4 / 0 to 30 °C
Charging temperature boost***10 °CPA4 / 0 to 50 °C
Max. charging temperature80 °CPA4 / 20 to 130 °C (only with VF4)
Lag of storage tank charging pump0.5PA4 / 0 to 10.0
Sustained DHW temperature40 °CPA4 / 20 to 90 °C
*Parameters serve as limitation of the adjustment range for the DHW temperature to be set
at the rotary switch
** Deactivation value T =
*** Charging temperature T =
DHW temperature+hysteresis
DHW temperature+charging temperature boost
WEParameter level / Range of values
6.3DHW heating in instantaneous heating system
VFFlow sensor
ZPCirculation pump
WWHot water
KWCold water
Water flowmeter
Fig. 11 · Schematics of an instantaneous heating system with water flowmeter
(CO4 -> F04 - 1, select: AnA)
Without a flowmeter or flow switch, the required
DHW temperature
at sensor VF is only reg
ulated during the times-of-use of the circulation pump ZP. The flowmeter or flow switch allow
the controller to recognize exactly when DHW is being tapped. By deleting all the
time-of-uses for the circulation pump, it is possible to regulate the required DHW tempera
-
ture just while the DHW is being tapping.
FunctionsWEConfiguration
Water flowmeter0
ParametersWERotary switch / Range of values
DHW temperature set point55 °CBottom /Min. to max. DHW temperature
Sustained DHW temperature40 °C Bottom /Min. to max. DHW temperature
CO4 -> F04 - 1
AnA
AnA (water flowmeter), bin (flow switch)
68 EB 5575 EN
-
Page 69
Appendix
ParametersWEParameter level / Range of values
Min. DHW temperature40 °CPA4 / 5 to 90 °C
Max. DHW temperature60 °CPA4 / 5 to 90 °C
6.4DHW heating with solar system
The systems Anl 1.3 and 2.3 include a solar system for DHW heating. In these systems, the
difference between the temperatures measured at storage sensor SF2 and the sensor at the
solar collector VF3 is determined. The
Solar pump ON
temperature difference between sensors VF3 and SF2 required to activate the solar pump. If
the temperature difference falls below the value of
switched off. Basically, the solar pump is also switched off when the water temperature mea
sured at sensor SF2 has reached the
Max. storage tank temperature
Note!
The times-of-use of the DHW circuit do not affect the operation of the solar system.
After the key number 1999 has been entered, the operating hours of the solar pump are displayed in extended operating level.
Parameters
Solar pump ON10 °CPA4 / 1 to 30 °C
Solar pump OFF3 °CPA4 / 0 to 30 °C
Max. storage tank temperature80 °CPA4 / 20 to 90 °C
WEParameter level/Range of values
parameter determines the minimum
Solar pump OFF,
the solar pump is
.
-
6.5Intermediate heating operation
This function is only available in systems Anl 2.x, 4.1 and 4.5. With the setting
CO4 -> F07 - 1, heating operation of the UP1 heating circuit is reactivated for a period of
10 minutes after 20 minutes of priority (heating deactivated during DHW heating). By setting
CO4 -> F07 - 0, storage tank charging is given unlimited priority over the heating operation
in the UP1 heating circuit.
Function
Intermediate heating1CO4 -> F07 - 1
WEConfiguration
EB 5575 EN 69
Page 70
Appendix
6.6Parallel pump operation
This function is only available in systems Anl 2.1 to 2.3, 4.1 and 4.5. With the setting
CO4 -> F06 - 1, the circulation pump UP1 remains switched on during DHW heating unless
certain operating situations occur. These situations include, for example, those when the cur
rent flow temperature demand of the pump circuit is lower than the adjusted
perature for parallel pump operation
. In this case, the controller applies priority operation, if
necessary with intermediate heating. Once a parallel pump operation cycle has been acti
vated and the time for
Stop parallel operation in case of deviation
has elapsed, system devi
Flow limit tem
-
ations greater than 5 °C cause the controller to suspend parallel operation for 10 minutes
and to apply priority operation. Setting the
Stop parallel operation in case of deviation
to 0
minutes leads to a parallel operation once initiated remaining regardless of a deviation.
Function
Parallel pump operation0
WEConfiguration
CO4 -> F06 - 1
10 min
40 °C
Stop parallel operation in case of deviation / 0 to 10 min
Flow limit temperature for parallel pump operation /
20 to 90 °C
6.7Circulation pump operation during storage tank charging
With the setting CO4 -> F11 - 1, the circulation pump continues operation according to the
set schedule even during storage tank charging.
With the setting CO4 -> F11 - 0, the circulation pump is switched off as soon as the storage
tank charging pump is activated. The circulation pump returns to operate according to
schedule when the storage tank charging pump has been switched off again.
Function
Circulation pump operation
during storage tank charging
WEConfiguration
0CO4 -> F11
-
-
-
6.8Priority operation
In many district heating systems with primary DHW heating, the allotted amount of water is
only intended to supply the heating system. As a result, the capacity required for DHW heat
ing needs to be taken from the heating system when great heating loads occur; and this, until
DHW heating has been concluded.
Nevertheless, heating operation is not to be interrupted simply. Only the amount of energy
required for DHW heating is to be deducted. This can be achieved by using the priority func
tions Reverse control and Set-back operation.
70 EB 5575 EN
-
-
Page 71
Appendix
6.8.1 Reverse control
In all systems with DHW heating and at least one heating circuit with control valve, DHW
heating can be given priority by applying reverse control. With the setting CO4 -> F08 - 1,
the temperature at the sensor VFx in the DHW circuit can be monitored.
In systems without the sensor VFx in the DHW circuit (e.g. Anl 4.5, 11.0), the temperature
directly at the storage sensor SF1 is monitored. If system deviations occur after the time for
Activate priority in case of deviation
has elapsed, the set point of the heating circuit with
control valve is gradually reduced each minute until the flow temperature set point has
reached 5 °C at the minimum. How strongly the controller responds is determined by the
Correction factor
Functions
Priority through reverse control0
Priority through set-back
operation
.
WEConfiguration
CO4 -> F08 - 1
2 min
1.0
0CO4 -> F09 - 0
Activate priority in case of deviation / 2 to 10 min
Correction factor / 0.1 to 10.0
6.8.2 Set-back operation
In all systems with DHW heating and at least one heating circuit with control valve, DHW
heating can be given priority by applying set-back operation. With the setting
CO4 -> F09 - 1, the temperature at the sensor VFx in the DHW circuit can be monitored.
In systems without the sensor VFx in the DHW circuit (e.g. Anl 4.5, 11.0), the temperature
directly at the storage sensor SF1 is monitored. If system deviations occur after the time for
Activate priority in case of deviation
point of the heating circuit with control valve.
Functions
Priority through reverse control0CO4 -> F08 - 0
Priority through set-back
operation
has elapsed, reduced operation is activated for the set
WEConfiguration
0
2 min
CO4 -> F09 - 1
Activate priority in case of deviation / 2 to 10 min
6.9Forced charging of the DHW storage tank
To provide the full room heating performance when the time-of-use of the heating circuits be
gins, existing storage tanks are charged one hour before the time-of-use of the heating cir
cuits starts. For the individual controller, this means that storage tank charging is activated
when the water temperature in the storage tank falls below the adjusted deactivation value of
EB 5575 EN 71
-
-
Page 72
Appendix
T =
DHW temperature+hysteresis
place when the DHW circuit is not used at the beginning of the time-of-use set for the heating
circuit(s).
Note!
This function is not available when a storage tank thermostat is used.
. The forced charging of the storage tank does not take
6.10 Thermal disinfection of the DHW storage tank
In all systems with DHW heating, the DHW storage tank is thermally disinfected on a se
Day of the week
lected
In systems with DHW storage tank, it is heated up, taking into account the
4
perature boost
Disinfection temperature
ends at the specified
In systems with DHW heating in instantaneous heating system, the function remains active
4
taking into account the
SF1, has reached the adjusted
been terminated because the
Start time
If the
ing to the programmed time schedule depending on the switching state of a binary input (terminal 03/12, only possible without SF2/RF2). A break contact (bE = 0) or optionally also a
make contact (bE = 1) of the binary input starts the thermal disinfection. It stops at the latest
when the switching state of the binary input next changes.
When the
fection cycle, “Err 3“ alarm is generated. The alarm is automatically reset when the
tion temperature
Thermal disinfection for preventing legionella infection causes
4
4
4
Disinfection temperature
excessively high return flow temperatures during the disinfection cycle (return flow tempe
rature limitation suspended),
excessively high DHW temperatures after thermal disinfection has been concluded,
lime scale (possibly), which can have a negative effect on heat exchanger performance.
or every day.
Charging tem
parameter (or
Stop time
and
Stop time
is properly reached during the following thermal disinfection cycle.
Set point boost
. Disinfection begins at the adjusted
.
Set point boost
Disinfection temperature,
Stop time
are set to the identical time, the process is controlled accord-
has not been reached before the end of the thermal disin
, depending on the system) to the adjusted
Start time
parameter until the circulation pipe, measured at
provided disinfection has not
has been reached.
and, at the latest,
-
Disinfec
-
-
-
-
72 EB 5575 EN
Page 73
Appendix
Note!
This function is not available when a storage tank thermostat is used.
Controllers that are linked over a device bus are subjected to return flow temperature limita
tion in the primary control circuit even during the thermal disinfection in a secondary control
ler.
1bE = 1, 0 (start of disinfection with BE (term. 03/12 =
Day of the week / 1–7, 1, 2, ..., 7 with
1–7 = every day, 1 = Monday, ..., 7 = Sunday
Start time / 0:00h to 23:45h; in steps of 15 minutes
Stop time / 0:00h to 23:45h; in steps of 15 minutes
Disinfection temperature / 60 to 90 °C
Set point boost / 0 to 50 °C
ON, OFF; only applies when Start time = Stop time)
EB 5575 EN 73
Page 74
System-wide functions
7System-wide functions
7.1Automatic summer time/winter time changeover
The clock is automatically adjusted on the last Sunday in March at 2.00h and on the last
Sunday in October at 3.00h.
Function
Summer time/winter time changeover 1CO5 -> F08 - 1
WEConfiguration
7.2Frost protection
Frost protection measures become effective whenever the outdoor temperature falls below the
Frost protection limit.
Frost protection program I (restricted frost protection): frost protection measures are taken
4
only when all heating circuits in the system are in stand-by mode. The circulation pumps
are forcedly switched on and their flow temperature set points are adjusted to 10 °C. The
circulation pump in the DHW circuit is switched on automatically only when stand-by
mode has been adjusted at the mode selector switch in all heating circuits. Nevertheless,
the storage tank is always recharged to 10 °C if the storage tank temperature falls below
5 °C.
Frost protection program II: the heating circuit circulation pumps are always switched on
4
forcedly. The flow temperature set points of all heating circuits currently in stand-by mode
are set to +10 °C. In the DHW circuit, the circulation pump is always activated. If the
storage tank temperature falls below +5 °C, the storage tank is recharged to +10 °C.
Functions
Frost protection program ICO5 -> F09 - 0
Frost protection program IICO5 -> F09 - 1
The hysteresis to cancel the frost protection measures is always 1 °C.
WEConfiguration
3 °CFrost protection limit / –15 to 3 °C
3 °CFrost protection limit / –15 to 3 °C
Note!
Frost protection operation of a pump, a heating circuit or the DHW circuit is active only
when the frost protection iconis indicated on the display.
Fixed set point control without outdoor temperature sensor does not include frost protection
in stand-by mode.
74 EB 5575 EN
Page 75
System-wide functions
7.3Forced operation of the pumps
When the heating circuit pumps have not been activated for 24 hours, forced operation of
the pumps is started between 12.02h and 12.03h. This is done to avoid that the pumps get
stuck when they are not operated for a longer period of time. In the DHW circuit, the circula
tion pump is operated between 12.04h and 12.05h, the other pumps between 12.05h and
12.06h.
7.4Return flow temperature limitation
The temperature difference between the flow and return flow indicates how well the energy is
used: the greater the difference, the higher the efficiency. A return flow sensor is sufficient to
evaluate the temperature difference when the network flow temperatures are determined. The
return flow temperature can be limited either to a value depending on the outdoor tempera
ture (variable) or to a fixed value. When the temperature measured at return flow sensor RüF
exceeds the limit value, the set point of the flow temperature (flow temperature of the heating, charging temperature) is reduced. As a result, the primary flow rate is reduced and the
return flow temperature falls. In systems Anl 2.x and 4.1, the
parameter (PA4 level) is used for limitation in the primary circuit during DHW heating if it is
greater than the parameter valid for the primary circuit. The
strongly the controller responds when the limit values are exceeded in either direction (PI algorithm).
If just P-action is to be implemented, set CO5 -> F16 - 1. This allows the I-action in the return
flow temperature limitation algorithm of all control circuits of the controller to be deactivated.
The set point reading (flow temperature of the heating, charging temperature) blinks to indicate that a return flow limitation is active in the control circuit concerned.
Max. return flow temperature
Limiting factor
determines how
-
-
Note!
Using weather-compensated control with gradient characteristic, the return flow temperature
is limited to a fixed value by equating the parameters
return flow temperature
(PA1, 2).
Return flow temperature foot
and
Max.
Note!
If CO5 -> F00 - 1 is indicated, access to the return flow, flow rate and heat capacity settings
are locked.
EB 5575 EN 75
Page 76
System-wide functions
Function
Return flow sensors RüF1/21
Return flow temperature
limitation with P algorithm
Parameters
Gradient, return flow1,2PA1, 2 / 0.2 to 3.2
Level, return flow0.0 °CPA1, 2 / –30 to 30 °C
Return flow temperature foot65 °CPA1, 2 / 5 to 90 °C
Max. return flow temperature65 °CPA1, 2, 4 / 5 to 90 °C
WEConfiguration
CO1, 2, 4 -> F03 - 1
1.0
0CO5 -> F16
WEParameter level/Range of values
Limiting factor/ 0.1 to 10.0
or
Parameter
Return flow temp. points 1 to 465 °CPA1, 2 / 5 to 90 °C
WEParameter level/Range of values
Note!
To ensure that the preset return flow temperature limiting value can be met, make sure that
– the heating characteristic is not adjusted to ascent too steeply,
– the circulation pumps are not adjusted to run too rapidly,
– the heating systems have been calibrated.
7.5Condensate accumulation control
Activate the Limit deviation for OPEN signal function to start up condensate accumulation
plants, in particular to avoid problematic excess temperatures. The controller response to set
point deviations which cause the primary valve to open is attenuated. The controller response
to set point deviations which cause the control valve to close remains unaffected.
Function
Limit deviation for OPEN signal0
WEConfiguration
CO1, 2, 4 -> F13 - 1
2 °C
Max. system deviation / 2 to 10 °C
Note!
The condensate accumulation control function can only be activated when no on/off control
has been configured, i.e. when CO1, 2, 4 -> F12 - 1 applies.
76 EB 5575 EN
Page 77
System-wide functions
7.6Three-step control
The flow temperature can be controlled using a PI algorithm. The valve reacts to pulses that
the controller emits upon an existing system deviation. The length of the first pulse, in particu
lar, depends on the extent of the system deviation and the selected
pulse length increases as K
increases). The pulse and pause lengths change continuously un
P
Proportional gain K
(the
P
til the system deviation has been eliminated. The pause length between the single pulses is
greatly influenced by the
Valve transit time T
The
Reset time T
specifies the time required by the valve to travel through the range
Y
(the pause length increases as TNincreases).
N
of 0 to 100 %.
Functions
Control type
three-step
WEConfiguration
1
2.0
120 s
45 s
CO1, 2, 4 -> F12 - 1, Rk_
(proportional gain) / 0.1 to 50.0
K
P
T
(reset time) / 1 to 999 sec
N
T
(valve transit time) / 5, 10,15, …, 240 sec
Y
7.7On/off control
The flow temperature can be controlled, for example, by activating and deactivating a
boiler. The controller switches on the boiler when the flow temperature falls below the set
point by T = 0.5 x
hysteresis
boiler is switched off again. The greater the value you choose for
be the activation/deactivation frequency. By setting the
boiler remains switched on during this period regardless of the flow temperature fluctuations.
Similarly, a deactivated boiler will remain switched off regardless of the flow temperature
fluctuations if the
Functions
Control type
on/off
Min. OFF time
. When the set point is exceeded by T = 0.5 x
Hysteresis
Minimum ON time
has been specified.
WEConfiguration
1
5 °C
2 min
2 min
CO1, 2, 4 -> F12 - 0
Hysteresis / 1 to 30 °C
Min. ON time / 0 to 10 min
Min. OFF time / 0 to 10 min
hysteresis
, the
, the lower will
, an activated
-
-
7.8Releasing a control circuit over the binary input
The release of a control circuit using the binary output only becomes effective when the re
spective control circuit is in automatic operating mode (icon). The released control circuit
always works in automatic mode; the deactivated control circuit behaves as if it were trans
ferred to stand-by mode.
EB 5575 EN 77
-
-
Page 78
System-wide functions
It remains active, however, in any case for processing of external demand. The control circuit
can be released via the binary input when the binary input is either open (bE = 0) or closed
(bE = 1).
Note!
In systems with supplementary heating circuit without a valve (Anl 2.x, 4.x), BE1 only influen
ces the operation of this heating circuit. In system Anl 3.0, BE1 influences the operation of
the entire controller (except for processing of an external demand).
-
Functions
Release Rk 1 at BE10
Release Rk 2 at BE20
WEConfiguration
CO1 -> F14 - 1
1
1
bE = 1, 0
CO2 -> F14 - 1
bE = 1, 0
7.9Processing of external demand in Rk1
The controller can process binary or analog requests for an externally required signal by a
more complex secondary system, provided the following requirements are met: the system is
configured without storage tank sensor SF2 or room sensor RF2 and an analog request can
be matched to “0 to 10 V corresponds with 0 to 120 °C flow temperature“. In other words:
flow temperature demand 12 °C/V. Analog requests below 10 °C (< 0.8 V input signal) are
not processed; overvoltage generates a maximum flow set point of 130 °C. An additional
processing of requests for an externally required signal over the device bus can be config
ured.
Note!
Overheating may occur in the heating circuits of the primary controller without control valve.
Excessive charging temperatures in DHW circuits without control valve controlled by the pri
mary controller are excluded when the default settings of the controller are used: while stor
age tank charging is active, no flow temperature higher than the charging temperature is ad
justed by the primary controller. Nevertheless, if the Priority for external demand function is
activated, the external demand is also processed during storage tank charging.
Function
Priority for external demand0CO4 -> F16 - 1
WEConfiguration
-
-
-
-
78 EB 5575 EN
Page 79
System-wide functions
Processing of external demand, binary
Regardless of the operating mode set for control circuit Rk1 – except manual mode –, the
flow temperature specified as
Set point for binary demand processing
is adjusted in control
circuit Rk1 when the binary input (terminals 03/12) is either open (bE = 0) or closed
(bE = 1).
Functions
Processing of external demand in Rk10CO1 -> F15 - 1
Processing of external demand, 0 to 10 V0CO1 -> F16 - 0
Processing of external demand, binary0
Parameter
Set point for binary demand processing40 °CPA1 / 5 to 130 °C
WEConfiguration
CO1 -> F17 - 1
1
WEParameter level/Range of values
bE= 1, 0
Processing of external demand, 0 to 10 V
Regardless of the operating mode set for control circuit Rk1– except manual mode –, the
controller regulates at least the flow temperature corresponding with the 0 to 10 V signal at
terminals 03/13.
Functions
Processing of external demand in Rk10CO1 -> F15 - 1
Processing of external demand, 0 to 10 V0CO1 -> F16 - 1
Processing of external demand, binary0CO1 -> F17 - 0
Parameter
Set point boost of primary exchanger control5 °CPA1 / 5 to 130 °C
WEConfiguration
WEParameter level/Range of values
EB 5575 EN 79
Page 80
System-wide functions
7.10 Flow rate/heat capacity limitation in Rk1
Flow rate/heat capacity limitation can be implemented based on a pulse or standardized
signal of 0/4 to 20 mA provided by the heat meter. This only applies in plants without SF2,
RF2 and without processing of an external demand 0 to 10 V. Particularly when a standard
ized signal is applied, a heat meter (flow meter) with high measuring accuracy is required.
Make sure that the controller is supplied with updated measured values in intervals of max.
5 seconds. In both cases (pulse or standardized signal), there are three different operating
situations:
A system with simultaneous room heating and DHW heating requires maximum energy.
4
A system with a fully charged storage tank which performs only room heating requires
4
less energy.
A system which suspends room heating during DHW heating requires less energy.
4
4
As a result, three different maximum limit values can be specified:
Max. limit value
4
Max. limit value heating
4
Max. limit value DHW
4
In all systems without DHW heating or without heating circuit, only the
the flow rate or capacity can be set.
Note!
The limiting function is not available in systems Anl 10.
to determine the absolute upper limit
for exclusive operation of the room heating
for exclusive operation of the DHW heating
Max. limit value
-
for
7.10.1 Limitation using pulse input
Depending on the operating situation, a heat meter with pulse output connected to input
WMZ/Bed (terminals 03/13) can be used to limit either the flow rate or the capacity in the
system. All limit values are given in the unit “pulses per hour“ [pulse/h]. As a result, the con
troller does not distinguish between a flow rate pulse signal or a capacity pulse signal. As
the displayed current pulse rate P [pulse/h] (–> Extended operating level, key number 1999)
is calculated depending on the interval between the received pulses, it is natural that the con
troller cannot react immediately to all rapid flow rate or capacity changes which occur in the
system.
When the pulse rate reaches the current
circuit Rk1 is reduced. How strongly the controller responds is determined by the
.
factor
80 EB 5575 EN
Max. limit value
, the flow set point of control
Limiting
-
-
Page 81
System-wide functions
Example to determine the limit value:
If a capacity of 30 kW is to be limited, the following limit value must be set for a heat meter
with an output of one pulse per kilowatt-hour:
30 kW
P
==
1kWh/pulse
30 pulse / h
Note!
If CO5 -> F00 - 1 is indicated, access to the return flow, flow rate and heat capacity settings
are locked.
Functions
Flow rate limitation (capacity limi
tation) in Rk1 with pulses at input
WMZ
Flow rate limitation in Rk1 with
WEConfiguration
0
15
15
15
1.0
CO5 -> F10 - 1
pulse
Max. limit value/ 3 to 500
h
pulse
Max. limit value heating* / 3 to 500
h
pulse
Max. limit value DHW* / 3 to 500
h
Limiting factor / 0.1 to 10.0
0CO5 -> F11 - 0
pulse
h
pulse
h
pulse
h
0/4 to 20 mA at input WMZ
* Not in Anl 1.0, 1.5, 1.6, 3.0, 3.5, 4.0 and 11.x
7.10.2 Limitation using 0/4 to 20 mA signal
Depending on the operating situation, a heat meter at input WMZ/Bed (terminals 03/13)
with a 0/4 to 20 mA output (connected in parallel to input WMZ/Bed using 50 Ω) can be
used to limit the flow rate in the system. All limit values are given in the unit “cubic meters
per hour“ [m
per measuring range value
is displayed in the extended operating level (–> key number 1999).
When the flow rate reaches the current
Rk1 is reduced. How strongly the controller responds is determined by the
Note!
If CO5 -> F00 - 1 is indicated, access to the return flow, flow rate and heat capacity settings
are locked.
3
/h]. As a result, both a
must be adjusted in unit [m3/h]. The current flow rate in [m3/h]
Lower measuring range value
Max. limit value
, the flow set point of control circuit
0 or 4 mA and an
Limiting factor
Up
-
.
EB 5575 EN 81
Page 82
System-wide functions
Functions
Flow rate limitation (capacity limi
WEConfiguration
0CO5 -> F10 - 0
tation) in Rk1 with pulses at input
WMZ
Flow rate limitation in Rk1 using
0/4 to 20 mA at input WMZ
0
0
1.5
1.5
1.5
1.5
1.0
CO5 -> F11 - 1
Lower measuring range value / 0, 4 mA
3
m
Upper meas. range value 20 mA / 0.01 to 650
h
3
m
Max. limit value / 0.01 to 650
h
3
m
Max. limit value heating* / 0.01 to 650
h
3
m
Max. limit value DHW* / 0.01 to 650
h
Limiting factor / 0.1 to 10.0
3
m
3
m
h
3
m
3
m
h
h
h
* Not in Anl 1.0, 1.5, 1.6, 3.0, 3.5, 4.0 and 11.x
7.10.3 Creep feed rate limitation over binary input
It is possible to report to the controller when the creep feed rate has fallen below a certain
level by using a limit switch of the primary valve connected to the terminals 04/12. Either the
break contact (bE = 0) of the binary input or the make contact (bE=1) of the binary input can
be assigned to inform about the creep feed rate status. Shortly after the alert, the controller
closes the valve Rk1. As soon as the flow temperature falls below the set point by more than
5 °C after the valve has been closed, control operation is started again.
Function
Creep feed rate limitation0
WEParameter level/Range of values
CO5 -> F12 - 1
1
bE = 0, 1
7.10.4 Limitation of the calculated capacity
The controller is able to calculate the heat capacity used in the system and to limit it depend
ing on the operational circumstances. To achieve this, it uses a connected 0/4 to 20 mA sig
nal for the flow rate, a primary return flow sensor and a primary flow sensor. All limits are
given in the unit kilowatt [kW]. The primary flow sensor is connected at input FG2.
The measured temperature of the primary flow sensor [°C] and the current capacity [kW] are
displayed in the extended operating level (-> key number 1999).
-
The flow set point of control circuit Rk1 is reduced if the capacity reaches the current
mum limit
. How strongly the controller responds is determined by the
Limiting factor
82 EB 5575 EN
Maxi
.
-
-
Page 83
System-wide functions
Note!
If CO5 -> F00 - 1 is indicated, access to the return flow, flow rate and heat capacity settings
are locked.
FunctionsWEConfiguration
Return flow sensor RüF11
Flow rate limitation in Rk1 using 0/4
to 20 mA at input WMZ
Capacity limitation based on a
connected flow rate signal in Rk1
1.0
0
0 mA
1.5
1.5
1.5
1.0
0
1.5 kW
1.5 kW
1.5 kW
1.0
CO1 -> F03 - 1
Limiting factor / 0.1 to 10.0
CO5 -> F11 - 1
Lower measuring range value / 0, 4 mA
3
m
h
Upper meas. range value 20 mA / 0.01 to 650
3
m
h
Max. limit value heating*/ 0.01 to 650
3
m
h
Max. limit value DHW*/ 0.01 to 650
m
Limiting factor / 0.1 to 10.0
CO5 -> F13 - 1
Maximum limit / 0.1 to 6500 kW
Max. limit value heating*/ 0.1 to 6500 kW
Max. limit value DHW*/ 0.1 to 6500 kW
Limiting factor / 0.1 to 10.0
* Not in Anl 1.0, 1.5, 1.6, 3.0, 3.5, 4.0 and 11.x
3
m
3
m
3
h
h
h
7.11 Device bus
TROVIS 5575-002x:
Version without device bus: The description of the device bus (section 7.11) and its func
tions (section 7.11.1 to 7.11.6) are not relevant for this version.
Using the device bus, it is possible to connect up to 32 device (from Series 55xx). For con
nection, the TROVIS 5575 Controller is, above all, equipped with the terminals 14/15.
No attention must be paid to the polarity of the device bus wiring.
Activate the device bus and specify the device bus address for each device. Note that the de
vice bus address 1 is to be set for just one controller in the system, and that all device bus
addresses must be unique. The controller with device bus address 1 implements the required
bus bias voltage for the system.
Once the controllers have been connected and preset, additional functions can be config
ured. These partly application-specific functions include:
-
-
-
EB 5575 EN 83
-
Page 84
System-wide functions
Requesting and processing an external demand (–> page 84)
4
Sending and receiving outdoor temperatures (–> page 85)
4
Synchronizing the clock (–> page 86)
4
Priority over all controllers (–> page 86)
4
Connecting a TROVIS 5570 Room Panel (–> page 87)
4
Display error alarms issued by the device bus (–> page 87)
4
7.11.1 Requesting and processing an external demand
In general, the controller which controls the primary valve or boiler (= primary controller) in
a system of coupled controllers will process the demand of all subsequent controllers (= sec
ondary controllers). As a result, the primary controller must be configured to receive this de
mand. Usually, the secondary controllers are configured such that they send their maximum
flow set point to the primary controller. In special cases, however, it might happen that only
the set point of a control circuit is to be sent. The appropriate function blocks to do so are
also available. After the desired function blocks have been activated, you must specify a register number.
The following applies: in a system of coupled controllers which are hydraulically supplied by
a primary controller all controllers (primary and secondary controllers) must be adjusted to
the same
a demand in register no. 5 will not process a demand sent to register no. 6. The primary
controller compares the received requested demands and its own requested demands and
supplies the system with the required flow temperature – if necessary increased by the value
of the parameter
Register no.
for the “demand registers“. A controller which is configured to receive
Set point boost for primary exchanger control
.
-
-
Note!
Overheating may occur in the heating circuits of the primary controller without control valve.
Primary controller:
Functions
Device bus0
Receive external demand0
Parameter
Set point boost for primary exchanger control5 °CPA1 / 0 to 50 °C
84 EB 5575 EN
WEConfiguration
CO7 -> F01 - 1
32
5
WEParameter level/Range of values
Device bus address
CO7 -> F15 - 1
Register no. / 5 to 64
Page 85
Secondary controller:
System-wide functions
Functions
Device bus0
Send flow set point Rk10CO7 -> F10 - 1*
Send flow set point Rk20CO7 -> F11 - 1*
Send flow set point DHW0CO7 -> F13 - 1*
Send max. flow set point0CO7 -> F14 - 1*
WEConfiguration
CO7 -> F01 - 1
32
5*Register no. / 5 to 64
Device bus address
Note!
The register number specifies the location where the flow set points are saved in the primary
controller. As a result, the register no. set in the secondary controller for CO7 -> F10 to F14
must be the same as the register no. adjusted under CO7 -> F15 in the primary controller.
Excessive charging temperatures in DHW circuits without control valve controlled by the primary controller are excluded when the default settings of the controller are used: while storage tank charging is active, no flow temperature higher than the charging temperature is adjusted by the primary controller.
Nevertheless, if the Priority for external demand function is activated, the external demand
is also processed during storage tank charging.
Function
Priority for external demand0CO4 -> F16 - 1
WEConfiguration
7.11.2 Sending and receiving outdoor temperatures
Controllers equipped with an outdoor sensor can be configured to supply other controllers
with the measured outdoor temperature via the device bus. This enables weather-compen
sated control even in systems which do not have their own outdoor sensor.
Functions
Device bus0
Send value AF10
WEConfiguration
CO7 -> F01 - 1
32
1
Device bus address
CO7 -> F06 - 1
Register no. / 1 to 4
EB 5575 EN 85
-
Page 86
System-wide functions
Functions
Receive value AF10
Receive value AF2 (receive an outdoor temp.
independent of Rk1)
WEConfiguration
CO7 -> F07 - 1
1
0
2
Register no. / 1 to 4
CO7 -> F09 - 1
Register no. / 2 to 4
Note!
The register no. for the outdoor temperature AF1 or AF2 must be the same for the sending
and the receiving controller.
7.11.3 Synchronizing the clock
One controller in a system of coupled controllers should perform the Clock synchronization
function. This controller sends its system time once every 24 hours to all other controllers via
the device bus.
Regardless of this function, the system time of all controllers is adapted immediately when the
time setting of one controller is changed.
Functions
Device bus0
Clock synchronization0CO7 -> F02 - 1
WEConfiguration
CO7 -> F01 - 1
32
Device bus address
7.11.4 Priority over all controllers
It is possible to put the heating circuits of other controllers out of operation while the DHW
heating is active when the controllers are linked to one another over a device bus. Control
lers which should operate a DHW heating with priority need to issue
DHW heating active
-
alert. Controllers that have heating circuits which should be deactivated during this active
DHW heating need to have the configuration Receive release of Rk_ for the heating circuits
concerned. If the circuit is just a DHW circuit which should influence one or more heating cir
cuits, they need to be assigned with the identical register number. In the case that there are
several DHW circuits in the system, selected heating circuits can only react to one or other
active DHW circuits by assigning different register numbers.
If a secondary heating circuit with a valve should be put out of operation, the heating circuit
valve concerned is closed; the heating circuit circulation pump remains in operation.
86 EB 5575 EN
-
Page 87
System-wide functions
If a secondary heating circuit without a valve should be put out of operation, for example, in
system Anl 2.x, just its heating circuit circulation pump and not the primary circuit Rk1 is put
out of operation by using the configuration Receive release of Rk1.
A TROVIS 5570 Room Panel (accessory) can be connected to the TROVIS 5575 Controller to
measure the room temperature and for remote operation of a heating circuit. The room
panel enables direct access to the operating mode and controller time settings as well as to
all relevant parameters of a heating circuit. Additionally, the room temperature, the outdoor
temperature and, if applicable, other data points can be viewed.
The terminals 5 and 6 of the room panel are connected to terminals 14 and 15 of the controller. The room panel is supplied with operating voltage (terminals 1 and 2 of the room
panel (12 to 26.5 V AC/15 to 36 V DC) at the point of installation.
Functions
Device bus0CO7 -> F01 - 1; Device bus address
TROVIS 5570 Room Panel in Rk10CO7 -> F03 - 1; Device bus address
TROVIS 5570 Room Panel in Rk20CO7 -> F04 - 1; Device bus address
WEConfiguration
7.11.6 Display error alarms issued by the device bus
Error alarms over device bus do cause controllers with an active modem function already in
the default setting to dial the control station. However, the error alarms issued by the device
bus are not displayed by controllers configured in this way. The setting CO7 -> F16 - 1
causes these controllers to react to the error alarms from the device bus by generating the
Err 5 alarm as long as the faults of the other device bus participants exist. The black squares
under the corresponding numbers at the top of the display indicate which device bus address
is defective for the first 23 device bus participants.
Function
Display error alarms issued by the device bus0CO7 -> F16 - 1
WEConfiguration
EB 5575 EN 87
Page 88
System-wide functions
7.12 Feeder pump operation
In system Anl 3.0, the feeder pump UP1 only starts to operate in the default setting when a
flow temperature demand of a secondary controller exists.
If CO7 -> F14 - 1 is configured in the primary controller in addition to CO7 -> F15 - 1, the
function is also active when the controller’s own secondary circuit requires heat.
Function
Send maximum flow set point0CO7 -> F14 - 1
WEConfiguration
5Register no. / 5 to 64
7.13 Locking manual level
To protect the heating system, this function can be used to lock manual level. When this func
tion has been activated, automatic mode is started when the rotary switch is set to.
Function
Locking manual levels0CO5 -> F21 - 1
WEConfiguration
7.14 Locking the rotary switches
When this function has been activated, the controller remains in automatic mode regardless
of the rotary switch positions. The rotary switches can no longer be used to adjust the controller settings.
Function
Locking the rotary switches0CO5 -> F22 - 1
WEConfiguration
-
88 EB 5575 EN
Page 89
System-wide functions
7.15 Setting a customized key number
To avoid that unauthorized personnel modify functions and parameters of the controller, the
default key number can be replaced with an individual key number.
Choose your custom key number between 0100 and 1900.
Proceed as follows:
Switch to configuration and parameter level. Display shows:
Set key number 1995.
q
Confirm key number.
Set valid key number.
q
Confirm key number. Key number blinks.
Set desired custom key number.
q
Confirm custom key number.
This new key number is now valid.
0 0 0 0
EB 5575 EN 89
Page 90
Operational faults
8Operational faults
Malfunctions or faults are indicated by the blinkingicon on the display. The “Error“ alarm
is displayed immediately. Press the rotary pushbutton to open the error level. It may be possi
ble to view several error alarms by turning the rotary pushbutton. As long as an error is
present, error level is displayed, even though it has not been opened by pressing the rotary
pushbutton. In addition, the display is illuminated for 1 second in intervals of 10 seconds
when a fault persists.
TROVIS 5575-000x and TROVIS 5575-001x:
The display is illuminated approximately every 10 seconds for one second when opera
tional faults occur.
TROVIS 5575-002x:
Version without illuminated display.
In the error level, the error is displayed as specified in the list below.
Note!
After the system code number has been changed, any error alarms are suppressed for
approx. 3 minutes.
-
-
8.1Error list
Err 1 = Sensor failure (–> section 8.2)
4
Err 2 = Reset to default setting (–> section 2.5)
4
Err 3 = Disinfection temperature not reached (–> section 6.9)
4
Err 4 = Max. charging temperature reached (–> section 6.2)
4
Err 5 = Error alarms issued by the device bus displayed (–> section 7.11.6)
4
Err 6 = Temperature monitoring alarm (–> section 8.3)
4
8.2Sensor failure
According to the error list, sensor failures are indicated by displaying “Err 1“ in error level.
For detailed information, exit error level and view the different temperature values in operat
ing level: each sensor icon displayed together with 3 horizontal lines instead of the measured
value indicates a defective sensor. The following list explains how the controller responds to
the failure of the different sensors.
90 EB 5575 EN
-
Page 91
Operational faults
Outdoor sensors AF1: When the outdoor sensor fails, the controller adjusts a flow tem
4
perature set point of 50 °C or the
(adjusted under PA1, 2) is smaller than 50 °C.
ture
Flow sensor(s) heating circuit(s): When the flow sensors in the heating circuits are defec
4
tive, the associated valve moves to 30 % travel. DHW heating using such a sensor to
measure the charging temperature is suspended.
Flow sensors in the DHW circuit with control valve: When the flow sensor VF4 fails, the
4
controller behaves as if VF4 had not been configured. As soon as the control of the
charging temperature becomes impossible (VF2 defective), the associated valve is closed.
Return flow sensors RüF1/2: When the return flow sensor fails, the controller continues
4
operation without return flow temperature limitation.
Room sensors RF1/2: When the room sensor fails, the controller uses the settings for op
4
eration without room sensor. The controller, for example, switches from optimizing mode
to reduced operation; adaptation mode is canceled. The last determined heating charac
teristic remains unchanged.
Storage sensors SF1/2: When one of the two sensors fails, the storage tank is no longer
4
charged (exception: solar system).
Solar sensors SF 3, VF 3: When one of the two sensors fails, the storage tank in the solar
4
circuit is no longer charged.
Max. flow temperature
when the
Max. flow tempera
8.3Temperature monitoring
When a system deviation greater than 10 °C persists in a control circuit for 30 minutes, an
error alarm “Err 6“ (temperature monitoring alarm) is generated.
Function
Temperature monitoring0CO5 -> F19 - 1
WEConfiguration
-
-
-
-
-
EB 5575 EN 91
Page 92
Memory module
9Memory module
The use of a memory module (accessory no. 1400-7142) is particularly useful to transfer all
data from one TROVIS 5575 Controller to several other TROVIS 5575 Controllers. The mem
ory module is plugged into the RJ45 connector integrated into the front panel. Once the
module has been connected, “75 SP“ is displayed. If the memory module already contains
data from a different TROVIS 5575 Controller, turn the rotary pushbutton until “SP 75" is
displayed
Pressing the rotary pushbutton to confirm “75 SP“ causes the controller settings to be
4
transferred to the memory module.
Pressing the rotary pushbutton to confirm “SP 75“ causes the saved controller settings to
4
be transferred from the memory module to the controller.
During the data transfer, the bars on the display indicate the progress. When the transfer
was successful, “I.O.“ is displayed. After that, the connection between controller and mem
ory module can be separated.
Using TROVIS-VIEW software (order no. 6661-1011), all of the controller settings can be
configured and archived on a computer.
9.1Data logging
A data logging module (order no. 1400-9378) saves the following controller data every two
minutes:
Temperatures measured by the sensors
4
Control signals [%]
4
Switching states of the pump outputs
4
Access to the controller settings
4
The data logging module is connected to the RJ-45 jack at the front of the controller. Thanks
to the compact design of the data logging module, the front cover of the controller can be
kept closed even when the module is connected.
The controller starts to write over the oldest data as soon the memory of the data logging
module is full after approximately eight days. The current memory capacity of the data log
Info 2
ging module can be read in the extended operating level under
(range of values: 0 to 6035). Directly after inserting the data logging module, data can be
first read after the first scanning cycle has been performed.
The data logging viewer software allows the data to be viewed in graph format. The
USB-Converter 3 (order no. 1400-9377) is required to connect the data logging module to a
computer. The data logging viewer software is supplied with the USB-Converter 3.
as a second value
-
-
-
92 EB 5575 EN
Page 93
10Installation
Dimensions in mm (W x H x D)
TROVIS 5575-000x and TROVIS 5575-001x
Controller with standard housing base: 144 x 98 x 60
TROVIS 5575-002x
The controller can be fitted with a standard housing base or a high base.
Controller with standard housing base: 144 x 98 x 60
Controller with high base:144 x 98 x 81
Installation
The controller consists of the housing with the electronics and the housing base with the ter
minals. It is suitable for panel, wall and top hat rail mounting (Fig. 12).
Panel mounting
1. Remove both screws (1).
2. Pull apart the controller housing and the base.
3. Make a cut-out of 138 x 92 mm (W x H) in the control panel.
4. Insert the controller housing through the panel cut-out.
5. Insert one mounting clamp (2) each at the top and bottom or at the side. Screw the
threaded rod towards the panel with a screwdriver so that the housing is clamped
against the control panel.
6. Install the electrical connections at the back of the base as described in section 11.
7. Fit the controller housing.
8. Fasten both screws (1).
Wall mounting
1. Remove both screws (1).
2. Pull apart the controller housing and the base.
3. If necessary, bore holes with the specified dimensions in the appropriate places.
Fasten the base with four screws.
4. Install the electrical connections at the base as described in section 11.
5. Remount the controller housing.
6. Fasten both screws (1).
-
EB 5575 EN 93
Page 94
Installation
Top hat rail mounting
1. Fasten the spring-loaded hook (4) at the bottom of the top hat rail (3).
2. Slightly push the controller upwards and pull the upper hook (5) over the top hat rail.
3. Remove both screws (1).
4. Pull apart the controller housing and the base.
5. Install the electrical connections at the base as described in section 11.
6. Remount the controller housing.
7. Fasten both screws (1).
94 EB 5575 EN
Page 95
Installation
Panel mounting
Wall mounting
57
2
Housing base
1
Controller housing
2
62
Top hat rail mounting
15
41
5
Fig. 12 · Installation
5
4
3
EB 5575 EN 95
Page 96
Electrical connection
11Electrical connection
!
Caution!
For electrical installation, you are required to observe the relevant electrotechnical regula
tions of the country of use as well as the regulations of the local power suppliers. Make sure
all electrical connections are installed by trained and experienced personnel!
Notes on installing the electrical connections
Install the 230 V power supply lines and the signal lines separately! To increase noise im
4
munity, observe a minimum distance of 10 cm between the lines. Make sure the minimum
distance is also observed when the lines are installed in a cabinet.
The lines for digital signals (bus lines) and analog signals (sensor lines, analog outputs)
4
must also be installed separately!
In plants with a high electromagnetic noise level, we recommend to use shielded cables
4
for the analog signal lines. Ground the shield at one side, either at the control cabinet inlet or outlet, using the largest possible cross-section. Connect the central grounding point
and the PE grounding conductor with a cable≥10 mm² using the shortest route.
Inductances in the control cabinet, e.g. contactor coils, are to be equipped with suitable
4
interference suppressors (RC elements).
Control cabinet elements with high field strength, e.g. transformers or frequency convert-
4
ers, should be shielded with separators providing a good ground connection.
-
-
Overvoltage protection
If signal lines are installed outside buildings or over large distances, make sure appropri-
4
ate surge or overvoltage protection measures are taken. Such measures are indispens
able for bus lines!
The shield of signal lines installed outside buildings must have current conducting capac
4
ity and must be grounded on both sides.
Surge diverters must be installed at the control cabinet inlet.
4
Connecting the controller
The controller is connected as illustrated in the diagram on the page 101.
Open the housing to connect the cables. To connect the feeding cables, make holes in the
marked locations at the top, bottom or back of the rear part of the housing and fit suitable
grommets or cable glands.
Connecting the sensors
Cables with a minimum cross-section of 2 x 0.5 mm² can be connected to the terminals at
the back panel of the housing.
96 EB 5575 EN
-
-
Page 97
Electrical connection
Connecting the water flowmeter (order no. 1400-9246)
A power supply unit and a 4.7 kΩresistor are required for the water flowmeter to function.
TROVIS 5575Water FlowmeterPower supply unit
brown/
greenwhite
black
13
03
4.7 kΩ
4.5 ... 24 V DC
_
+
Connecting the actuators
Three-step or on/off outputs:
4
Connect cables with at least 1.5 mm² suitable for damp locations to the terminals of the
controller output. The direction of travel needs to be checked at start-up.
Note!
Electric actuators are not automatically supplied with a voltage by the controller. They can be
connected to an external voltage source over the terminals 25 or 28.
If this is not required, place a jumper from terminal 18 to terminal 25 and 28.
Connecting the pumps
Connect all cables with at least 1.5 mm
2
to the terminals of the controller as illustrated in the