Samson TROVIS 5573 Mounting And Operating Instructions

Automation System TROVIS 5500 Heating and District Heating Controller TROVIS 5573
Electronics from SAMSON
Mounting and Operating Instructions
EB 5573 EN
®
Disclaimer of liability/Safety instructions
Disclaimer of liability
We areconstantly developing our products and therefore, reservethe right to change the prod uct or the information contained in this document at any time without notice.
We donot assume any liability for the accuracy or completenessof these mounting and operat ing instructions. Moreover, we do not guarantee that the buyer can use the product for an in tended purpose. SAMSON rejects any liability for claims by the buyer, especially claims for compensation including lost profits or any other financial loss, except the damage was caused intentionally or by gross negligence. If an essential term of the contract is breached by negli gence, SAMSON’s liability is limited to the foreseeable damage.
Important safety instructions
For your own safety, observe the following instructions on the installation, start up and opera tion of the controller:
The device may only be installed, started up or operated by trained and experienced
4
personnel familiar with the product. The controller has been designed for use in electrical power systems. For wiring and
4
maintenance, you are required to observe the relevant safety regulations.
In addition, the following applies to prevent damage to the controller:
Proper shipping and appropriate storage are assumed.
4
Definitions of the signal words used in these instructions
-
-
-
-
-
!
DANGER!
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING!
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
2 EB 5573 EN
NOTICE
NOTICE indicates a property damage message.
Note: Supplementary explanations, information and tips
Contents

ContentsPage

1 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1 Operating controls . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1.1 Rotary pushbutton . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1.2 Rotary switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.2 Operating modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.2.1 Setting the operating modes. . . . . . . . . . . . . . . . . . . . . . . 7
1.3 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.4 Opening the information level . . . . . . . . . . . . . . . . . . . . . 9
1.5 Setting the controller time . . . . . . . . . . . . . . . . . . . . . . . 10
1.6 Setting the times-of-use . . . . . . . . . . . . . . . . . . . . . . . . 11
1.7 Setting the party mode . . . . . . . . . . . . . . . . . . . . . . . . 13
1.8 Activating the extended information level. . . . . . . . . . . . . . . . 14
1.8.1 Setting public holidays . . . . . . . . . . . . . . . . . . . . . . . . 15
1.8.2 Setting vacation periods . . . . . . . . . . . . . . . . . . . . . . . . 16
1.9 Entering day and night set points . . . . . . . . . . . . . . . . . . . 18
2 Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2.1 Setting the system code number . . . . . . . . . . . . . . . . . . . . 20
2.2 Activating and deactivating functions. . . . . . . . . . . . . . . . . . 21
2.3 Changing parameters . . . . . . . . . . . . . . . . . . . . . . . . . 23
2.4 Calibrating sensors . . . . . . . . . . . . . . . . . . . . . . . . . . 24
2.5 Resetting to default values . . . . . . . . . . . . . . . . . . . . . . . 25
3 Manual mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4 Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5 Functions of the heating circuit . . . . . . . . . . . . . . . . . . . . 46
5.1 Weather-compensated control . . . . . . . . . . . . . . . . . . . . . 46
5.1.1 Gradient characteristic . . . . . . . . . . . . . . . . . . . . . . . . 47
5.1.2 4-point characteristic . . . . . . . . . . . . . . . . . . . . . . . . . 49
5.2 Fixed set point control . . . . . . . . . . . . . . . . . . . . . . . . . 50
5.3 Underfloor heating/drying of jointless floors . . . . . . . . . . . . . . 51
5.4 Deactivation depending on outdoor temperature . . . . . . . . . . . . 52
5.4.1 OT deactivation value in rated operation . . . . . . . . . . . . . . . . 52
5.4.2 OT deactivation value in reduced operation . . . . . . . . . . . . . . 52
5.4.3 OT activation value in rated operation . . . . . . . . . . . . . . . . . 53
5.4.4 Summer mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
5.5 Delayed outdoor temperature adaptation. . . . . . . . . . . . . . . . 54
5.6 Remote operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
5.7 Optimization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
EB 5573 EN 3
Contents
5.8 Flash adaptation . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
5.8.1 Flash adaptation without outdoor sensor (room temperature dependent) . 57
5.9 Adaptation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
6 Functions of the DHW circuit . . . . . . . . . . . . . . . . . . . . . 59
6.1 DHW heating in the storage tank system . . . . . . . . . . . . . . . . 59
6.1.1 DHW circuit additionally controlled by a globe valve . . . . . . . . . . 61
6.2 DHW heating in the storage tank charging system . . . . . . . . . . . 62
6.3 DHW heating in instantaneous heating system . . . . . . . . . . . . . 64
6.4 DHW heating with solar system . . . . . . . . . . . . . . . . . . . . 65
6.5 Intermediate heating operation . . . . . . . . . . . . . . . . . . . . 65
6.6 Parallel pump operation . . . . . . . . . . . . . . . . . . . . . . . . 65
6.7 Circulation pump operation during storage tank charging. . . . . . . . 66
6.8 Priority operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
6.8.1 Reverse control . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
6.8.2 Set-back operation . . . . . . . . . . . . . . . . . . . . . . . . . . 67
6.9 Forced charging of the DHW storage tank . . . . . . . . . . . . . . . 67
6.10 Thermal disinfection of the DHW storage tank . . . . . . . . . . . . . 68
7 System-wide functions . . . . . . . . . . . . . . . . . . . . . . . . 70
7.1 Automatic summer time/winter time changeover . . . . . . . . . . . . 70
7.2 Frost protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
7.3 Forced operation of the pumps. . . . . . . . . . . . . . . . . . . . . 71
7.4 Return flow temperature limitation . . . . . . . . . . . . . . . . . . . 71
7.5 Condensate accumulation control . . . . . . . . . . . . . . . . . . . 72
7.6 Three-step control . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
7.7 On/off control . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
7.8 Continuous control in control circuit Rk1 . . . . . . . . . . . . . . . . 73
7.9 Releasing a control circuit/controller over the binary input . . . . . . . 74
7.10 Processing of external demand in control circuit Rk1 . . . . . . . . . . 75
7.11 Creep feed rate limitation using a binary input . . . . . . . . . . . . . 76
7.12 Locking manual level . . . . . . . . . . . . . . . . . . . . . . . . . 76
7.13 Locking the rotary switch . . . . . . . . . . . . . . . . . . . . . . . 77
7.14 Feeder pump operation . . . . . . . . . . . . . . . . . . . . . . . . 77
7.15 Setting a customized key number . . . . . . . . . . . . . . . . . . . 77
8 Operational faults . . . . . . . . . . . . . . . . . . . . . . . . . . 78
8.1 Error list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
8.2 Sensor failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
8.3 Temperature monitoring . . . . . . . . . . . . . . . . . . . . . . . . 79
4 EB 5573 EN
Contents
8.4 Error status register . . . . . . . . . . . . . . . . . . . . . . . . . . 79
8.5 Sending text messages in case of error . . . . . . . . . . . . . . . . . 80
9 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
9.1 RS-232/modem communications module . . . . . . . . . . . . . . . 83
9.2 RS-485 communications module . . . . . . . . . . . . . . . . . . . . 84
9.3 Description of communication parameter settings . . . . . . . . . . . . 85
9.4 Memory module . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
9.5 Data logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
10 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
11 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . 90
12 Appendix. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
12.1 Function block lists . . . . . . . . . . . . . . . . . . . . . . . . . . 93
12.2 Parameter lists . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
12.3 Sensor resistance tables . . . . . . . . . . . . . . . . . . . . . . . 112
12.4 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
12.5 Customer data. . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Key abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Modifications to controller firmware in comparison to previous version
1.80 (previous)
1.82 (new)
Internal modifications
EB 5573 EN 5
Operation
1 Operation
The controller is ready for use with the default temperatures and operating schedules. On start-up, the current time and date need to be set at the controller (–> section 1.5).
1.1 Operating controls
The operating controls are located in the front panel of the controller.
1.1.1 Rotary pushbutton
Rotary pushbutton
*
+
Turn [q]: Display, select parameters and function blocks
Press [ ]: Confirm adjusted selection or settings
1.1.2 Rotary switch
The rotary switchis usedto setthe operatingmode andthe relevantparameters foreach control circuit.
Information level, rotary switch in normal position Operating modes Manual level
6 EB 5573 EN
Day set point (rated room temperature) Night set point (reduced room temperature) Times-of-use for heating/DHW Party mode Controller time Configuration and parameter level
Operation
1.2 Operating modes
Day mode (rated operation) : Regardless of the programmed times-of-use and summer
mode, the set points relevant for rated operation are used by the controller. Night mode(reduced operation) : Regardlessof the programmed times-of-use, the set points
relevant for reduced operation are used by the controller. Stand-by mode : Regardless of the programmed times-of-use, control operation is deacti
vated. Only the frost protection is activated, if need be. Automatic mode : During the programmed times-of-use, the controllerworks in rated opera
tion. Outside these times-of-use, the controller is in reduced operation, unless control operation is deactivateddepending on the outdoor temperature. The controller switches automatically be tween both operating modes.
Manual mode : Valves and pumps can be controlled manually (–> section 3).
1.2.1 Setting the operating modes
1. Turn the rotary switch to (operating modes). blinks on the display.
For systems with just one control circuit (e.g. Anl 1.0), steps 2 and 3 can be skipped
4
(selecting the control circuit).
2. Select the control circuit whose operating mode is to be set [q]:
Heating circuit 1 Heating circuit 2 DHW circuit/circulation pump (DHW)
Only those control circuits are available for selection which can be controlled by the
4
system schematics (Anl) selected.
3. Confirm the control circuit [ ].
4. Select the operating mode [q]: , , or
5. Confirm the operating mode [ ].
6. Return the rotary switch to normal switch position (information level).
-
-
-
Note: Inautomatic mode, the momentary stage of the operating schedule( for day mode or
for night mode) is displayed in the information level together with the icon .
EB 5573 EN 7
Operation
1.3 Display
The display indicates the time as well as information about the operation of the controller when the rotary switch is at the normal position (information level). The times-of-use together with temperatures of the various control circuits can be viewed on the display by turning the rotary pushbutton. Thetimes-of-use are represented by black squares below the rowof numbers at the top of the display. Icons indicate the operating status of the controller.
Public holiday mode
Vacation mode Operational fault Frost protection
Heating circuit 1 Heating circuit 2 DHW circuit
Automatic mode Automatic mode Automatic mode Night mode Night mode Night mode Day mode Day mode Day mode Manual mode Manual mode Manual mode Stand-by mode Stand-by mode Stand-by mode Circulation pump UP1* Circulation pump UP2* Valve Rk1 OPEN Valve Rk2 OPEN
Pump output TLP/CP*
Valve Rk1 CLOSED Valve Rk2 CLOSED
* UP1, UP2, TLP, CP, SLP and ZP indicate possible choices for pump selection in manual mode.
Fig. 1 · Icons
Storage tank charging
pump SLP*
Circulation pump ZP*
The controller status can be displayed in the information level (–> section 1.4).
8 EB 5573 EN
1.4 Opening the information level
Operation
At the normal switch position (information level), the time, date, public holidays and vaca tion periods as well as the temperaturesmeasured by the connected sensorsand their set points can be retrieved and displayed.
Note: Data can also be viewed in the operating level (manual mode). To do so, select Info, confirm and proceed as described below.
Proceed as follows:
1. Select value [q].
Depending on the configuration of the controller, the current values of the following data points are displayed one after the other:
__:__ Time
Room temperature, heating circuits 1, 2
Outdoor temperature
Temperature at flow sensor VF, heating circuits 1, 2
Temperature at flow sensor VF1, primary heat exchanger circuit
Temperature at flow sensor VF2, VF4, DHW circuit
Temperature at solar collector sensor VF3
-
Temperature at return flow sensor RüF
Temperature at storage tank sensor SF1
Temperature at storage tank sensor SF2
Temperature at storage tank sensor of the solar circuit
2. By confirming a data point [ ] its set point/limit is displayed. When the time is indicated
on the display, the date appears on pressing the rotary pushbutton.
EB 5573 EN 9
Operation
1.5 Setting the controller time
The current time and date need to be set immediately after start-up and after a power failure of more than 24 hours has occurred. This is the case when the time blinks on the display.
Proceed as follows:
1. Turn the rotary switch to (controller time). Display: time, and blink.
2. Edit the controller time [q].
3. Confirm the adjusted time [ ]. Display: year
4. Edit the year [q].
10 EB 5573 EN
5. Confirm the adjusted year [ ]. Display: date (day.month)
6. Edit the date [q].
7. Confirm the adjusted date [ ]. Display: time
8. Return the rotary switch to normal switch position (information level).
1.6 Setting the times-of-use
Three times-of-use can be set for each day of the week.
Parameters
Period/day 1–7 1–7, 1, 2, 3, 4, 5, 6, 7 with 1–7 = every day,
Start first time-of-use 6:00 0:00 to 24:00h; in steps of 15 minutes Stop first time-of-use 22:00 0:00 to 24:00h; in steps of 15 minutes Start second time-of-use 22:15 0:00 to 24:00h; in steps of 15 minutes Stop second time-of-use 22:15 0:00 to 24:00h; in steps of 15 minutes Start third time-of-use 0:00 to 24:00h; in steps of 15 minutes Stop third time-of-use 0:00 to 24:00h; in steps of 15 minutes * Default values (WE) valid for heating circuits
Proceed as follows:
1. Turn the rotary switch to (times-of-use). blinks.
For systems with just one control circuit (e.g. Anl 1.0), steps 2 to 5 can be skipped
4
(selecting the control circuit and specifying the DHW circuit). Only the DHW circuit is controlled in systems Anl 1.5 and 1.9. Therefore the instruc-
4
tions steps 2 and 3 (selecting the control circuit) do not apply and can be skipped.
2. Select the control circuit, for which the times-of-use are to be entered [q]:
Heating circuit 1 Heating circuit 2 DHW circuit/circulation pump (DHW)
Only those control circuits are available for selection which can be controlled by the
4
system (Anl) selected.
3. Confirm the control circuit [ ]. If control circuit 1 or 2 has been selected, skip steps 4 and 5.
4
4. Specify DHW circuit [q]:
WE* Range of values
1 = Monday, 2 = Tuesday, ..., 7 = Sunday
Operation
DHW heating / Circulation pump (DHW)
5. Confirm [ ].
EB 5573 EN 11
Operation
6. Select period/day for which the times-of-use are to be valid [q]: 1–7 = every day, 1 = Monday, 2 = Tuesday, ..., 7 = Sunday
7. Activate editing mode for period/day [ ].
START
Display:
8. Edit start time [q]. (in steps of 15 minutes)
9. Confirm start time [ ]. Display:
10. Edit stop time [q]. (in steps of 15 minutes)
11. Confirm stop time [ ]. Display: The indicated time corresponds to the stop time for the first time-of-use plus 15 minutes.
To set the second and third times-of-use, repeat steps 8 to 11. If no further times-of-use for the selected period/day are to be programmed, confirm the displayed start time twice (2x [ ]).
For daily setting, repeat steps 6 to 11 in the same sequence.
, and blink.
STOP
START
Note: Do not use the 1–7 menu to check the programmed times-of-use.
If this menu is opened after the times-of-use have been set, the schedule programmed for Mon day is also adopted for all other days of the week.
12. After setting all times-of-use: Return the rotary switch to normal switch position (information level).
12 EB 5573 EN
-
Operation
1.7 Setting the party mode
Using the Party mode function, the controller continues or activates the day mode during the time when theparty timeris active,regardless ofthe programmedtimes-of-use. When the party timer has elapsed, the party mode timer is reset to 00:00.
Parameter
Continue/activate rated operation 0 h 0 to 48 hours
Proceed as follows:
1. Turn the rotary switch to (party mode). blinks.
In systems Anl 1.0, 1.9 and 3.5, the display reads 00:00 or indicates the remaining
4
time of party timer. Steps 2 and 3 can be skipped (selecting the control circuit).
2. Select the control circuit in which the day mode is to continue or be activated [q]:
Heating circuit 1 Heating circuit 2 DHW circuit
Only those control circuits are available for selection which can be controlled by the
4
system (Anl) selected.
3. Confirm the control circuit [ ].
00:00
Display:
4. Select how long the day mode is to continue running [q].
This setting is made in steps of 15 minutes.
5. Return the rotary switch to normal switch position (information level).
Note: The party timer counts down in steps of 15 minutes.
or indicates the remaining time of party timer.
WE Range of values
EB 5573 EN 13
Operation
1.8 Activating the extended information level
If the extended information level is activated, further information can be viewed after the listed data points:
Public holidays (can be changed, see section 1.8.1)
4
Vacation periods (can be changed, see section 1.8.2)
4
Valve positions
4
Switching states of the binary inputs
4
InFo 2: After confirming the level [ ] the following data appear in the sequence shown be
4
low:
Controller ID Memory capacity of data logging module (section 9.5) 255 Operating hours of solar circuit pump (referto section6.4)
Opening the extended information level:
1. Turn the rotary switch to (parameter and configuration level).
0 0 0 0
Display:
2. Set key number 1999 [q].
3. Confirm key number [ ]. Display:
4. Return the rotary switch to normal switch position (information level).
, blinks.
0 0 0 0
-
Note: The extended information level is deactivated when the key number 1999 is re-entered.
14 EB 5573 EN
1.8.1 Setting public holidays
On public holidays, the times-of-use specified for Sunday apply. A maximum of 20 public holidays may be entered.
Parameter WE Level / Range of values Public holidays Extended information level/ 01.01 to 31.12
Proceed as follows:
1. In the extended information level (normal switch position ) select data point for public holidays [q]. Display:
2. Open data point for public holidays.
– – – –
3. If applicable, select
4. Activate editing mode for public holiday [ ].
and blink.
5. Select public holiday [q].
6. Confirm public holiday [ ].
To enter additional public holidays, re-select – – . – – and repeat the steps 4 to 6.
.
Operation
Note: Public holidays can also be set in PA5 parameter level (–> section 2.3).
Deleting a public holiday:
1. Under data point for public holidays, select the holiday you wish to delete [q].
2. Confirm selection [ ].
3. Select – –.– – [q].
4. Confirm selection [ ]. The public holiday is deleted.
Note: Public holidays that are not assigned to a specific date should be deleted by the end of the year so that they are not carried on into the following year.
EB 5573 EN 15
Operation
1.8.2 Setting vacation periods
During vacation periods, the controller constantly remainsin reducedoperation. Amaximum of 10 vacation periods can be entered. Each vacation period can be separately assigned to the heating circuits Rk1, Rk2 and/or the DHW circuit.
Parameter WE Level / Range of values Vacation period (START, STOP) Extended information level / 01.01 to 31.12
Proceed as follows:
1. In the extended information level (normal switch position ) select data point for vacation periods [q]. Display:
2. Open data point for vacation periods [ ]. Display:
3. If applicable, select
4. Activate editing mode for start date of vacation period [].
5. Edit start date of vacation period [q].
6. Confirm start date of the vacation period. Display:
7. Edit end of vacation period [q].
8. Confirm end of vacation period [ ]. The black square at the top of the display indicate the assignment of the vacation periods to the individual control circuits.
9. Select the control circuit to which the current vacation period should apply [q].
The vacation period can be assigned to a single con trol circuit or any combination of all three circuits (Rk1, Rk2, DHW circuit).
To enter additional vacation periods, re-select
START
– – – –
and blink.
[q].
STOP, – –.– –
Current vacation period applies to heating circuit 1 Current vacation period applies to heating circuit 2 – Current vacation period applies to DHW circuit
– –.– –
and repeat the steps 4 to 9.
-
16 EB 5573 EN
Note: Vacation periods can also be set in PA5 parameter level (–> section 2.3).
Deleting vacation periods:
Operation
1. Under data point for vacation periods, select the start date of the period you wish to de lete [q].
2. Confirm selection [ ].
3. Select
– –.– –
[q].
4. Confirm selection [ ]. The vacation period is deleted.
Note: Vacation periods should be deleted by the end of the year so that they are not carried on into the following year.
-
EB 5573 EN 17
Operation
1.9 Entering day and night set points
The desired room temperature for the day ( the night ( In the DHW circuit, the temperature you wish the DHW to be heated to can be set.
Switch position Parameters WE Range of values
Day set point Rk1, Rk2 20 °C 0 to 40 °C DHW temperature set point 55 °C Min. to max. DHW temperature
Switch position Parameters WE Range of values
Night set point Rk1, Rk2 20 °C 0 to 40 °C DHW sustained temperature 40 °C Min. to max. DHW temperature
Proceed as follows:
1. Turn the rotary switch to the required data point:
2. Select the control circuit for which the set point is to be entered [q]:
3. Confirm the control circuit [ ].
4. Adjust set point [q].
5. Return the rotary switch to normal switch position (information level).
Night set point
for Day set point or DHW temperature set point for Night set point or DHW sustained temperature
blinks.
In systems Anl 1.0, 1.9 and 3.5, the current set point is directly indicated. Skip the
4
following steps 2 and 3 (selecting the control circuit).
Heating circuit 1 Heating circuit 2 DHW circuit
Only those control circuits are available for selection which can be controlled by the
4
system (Anl) selected.
Display: current set point
) can be entered in the controller for the heating circuits.
Day set point
) and a reduced room temperature for
18 EB 5573 EN
q
Information level
Operation
& key number
End PA1
Configuration and
parameter level
(start-up, see section 2)
CO4CO5
PA1/CO1: Rk1 (heating circuit 1) PA2/CO2: Rk2 (heating circuit 2) PA4/CO4: DHW circuit PA5/CO5: System-wide parameters PA6/CO6 Modbus communication
Anl: System code number
q
PA2Anl
PA4
PA5
PA6CO6
CO1CO2
Fig. 2 · Level structure of TROVIS 5573
EB 5573 EN 19
Start-up
2 Start-up
The modifications of the controller configuration and parameter settings described in this sec tion can only be performed after the valid key number has been entered.
The valid key number for initial start-up can be found on page 123. To avoid unauthorized use of the key number, remove the page ormake the key number unreadable. In addition, it is pos sible to enter a new, customized key number (–> section 7.15).
2.1 Setting the system code number
21 different hydraulic schematics are available. Each system configuration is represented by a system code number. The different schematics are dealt with in section 4. Available controller functions are described in sections 5, 6 and 7.
Changing the system code number resets previously adjusted function blocks to their default set tings (WE). Function block parameters and parameter level settings remain unchanged. The system code number is set in the configuration and parameter level.
Proceed as follows:
1. Turn the rotary switch to (configuration and parameter level).
Anl
blinks.
0 0 0 0
PA_
.
End
Display:
2. Set valid key number [q].
3. Confirm key number [ ]. Display:
4. Select
5. Activate editing mode for the system code number [ ].
6. Edit system code number [q].
7. Confirm system code number [ ]. Display:
8. Return the rotary switch to normal switch position (information level).
-
-
-
20 EB 5573 EN
Start-up
2.2 Activating and deactivating functions
A function is activated or deactivated in the associated function block. The numbers 0 to 24 in the top row of the display represent the respective function block numbers. When a configura tion level is opened, the activated function blocks are indicated by a black square on the right-hand side below the function block number. For more details on function blocks, refer to section 12.1.
The functions are grouped by topics:
CO1: Rk1 (Heating circuit 1)
4
CO2: Rk2 (Heating circuit 2)
4
CO3: Not applicable
4
CO4: DHW circuit
4
CO5: System-wide functions
4
CO6: Modbus communication
4
1. Turn the rotary switch to (configuration and parameter level). Display:
2. Set valid key number [q].
3. Confirm key number [ ]. Display:
4. Select configuration level [q].
5. Open configuration level [ ].
6. Select function block [q]. Activated function blocks are marked by “- 1“. Deactivated function blocks are marked by “- 0“.
7. Activate editing mode for the function block [ ].
8. Activate the function block [q]. Display: An activated function block is indicated by a black square below (right) the function block number in the top row of the controller display.
or:
Deactivate the function block [q]. Display:
0 0 0 0
PA_
blinks.
F__ - 1
F__ - 0
-
EB 5573 EN 21
Start-up
10. Confirm settings [ ]. If the function block is not closed, further function block parameters can be adjusted.
Proceed as follows: a) Select function block parameter [q]. b) Confirm function block parameter [ ].
If applicable, the next function block parameter is displayed. Confirm all parameters to exit the opened function block.
To adjust additional function blocks in the open configuration level, repeat the steps 6 to 10.
End
11. Select
12. Exit configuration level [ ]. To adjust additional function blocks in the other configuration levels, repeat 4 to 10.
13. Return the rotary switch to normal switch position (information level).
[q].
22 EB 5573 EN
Start-up
2.3 Changing parameters
Depending on the set system code number and the activated functions, not allparameters listed in the parameter list in the Appendix (–> section 12.2) might be available. The parameters are grouped by topics:
PA1: Rk1 (Heating circuit 1)
4
PA2: Rk2 (Heating circuit 2)
4
PA3: Not applicable
4
PA4: DHW heating
4
PA5: System-wide parameters
4
PA6: Communication parameters
4
1. Turn the rotary switch to (configuration and parameter level).
blinks.
End
0 0 0 0
PA_
[q].
Display:
2. Set valid key number [q].
3. Confirm key number [ ]. Display:
4. Select parameter level [q].
5. Open parameter level [ ].
6. Select parameter [q].
7. Activate editing mode for the parameter [ ].
8. Edit the parameter [q].
9. Confirm the parameter [ ]. To adjust additional parameters in the open parameter level, repeat steps 6 to 9.
10. Select
11. Exit parameter level [ ]. To adjust additional parameters in another parameter level, repeat steps 4 to 9.
12. Return the rotary switch to normal switch position (information level).
EB 5573 EN 23
Start-up
2.4 Calibrating sensors
The controller is designed for the connection of Pt 1000 sensors. The resistance values of the Pt 1000 sensors can be found on page 112.
If the temperature values displayed at the controller differ from the actual temperatures, the measured values of all connectedsensors canbe readjusted.To calibratea sensor,the currently displayed sensor value must be changed such that it matches the temperature (reference tem perature) measured directly at the point of measurement. Sensor calibration is to be activated in CO5 via function block F20. An incorrect sensor calibration can be deleted by setting F20 - 0.
Proceed as follows:
1. Turn the rotary switch to (configuration and parameter level). Display:
2. Set valid key number [q].
3. Confirm valid key number [ ]. Display:
4. Select CO5 configuration level [q].
5. Open CO5 configuration level [ ].
6. Select function block F20 [q].
7. Activate editing mode for function block F20 [ ].
8. Select appropriate sensor icon [q]:
0 0 0 0
PA_
-
24 EB 5573 EN
Room sensor RF, heating circuits 1 and 2
Outdoor sensor AF1
Flow sensor VF, heating circuits 1 and 2
Flow sensor VF1, primary heat exchanger circuit
Flow sensors VF2 and VF4, DHW circuit
Solar collector sensor VF3
Return flow sensor RüF
Start-up
Storage tank sensor SF1
Storage tank sensor SF2
Storage tank sensor of the solar circuit SF2
9. Display measured value [ ]. “°C” blinks.
10. Correct measured value [q]. Read the actual temperature directly from the thermometer at the point of measurement and enter this value as the reference temperature.
11. Confirm corrected measured value [ ]. Additional sensors are calibrated similarly.
End
12. Select
13. Return the rotary switch to normal switch position (information level).
[q].
2.5 Resetting to default values
All parameters set over the rotary switchas wellas parametersin PA1, PA2 and PA5 parameter levels can be reset to their default settings (WE), except for the maximum flow temperature and the return flow temperature limits in PA1 and PA2.
1. Turn the rotary switch to (configuration and parameter level). Display:
2. Set key number 1991 [q].
3. Confirm key number [ ]. The controller is reset to its default settings. Display:
0 0 0 0
0 0 0 0
EB 5573 EN 25
Manual mode
3 Manual mode
Switch to manual mode to configure all outputs, refer to wiring diagram (-> section 11).
NOTICE
The frost protection does not function when the controller is in manual mode.
Proceed as follows:
1. Turn the rotary switch to (manual level).
2. Select output depending on the control circuit (q): POS_ Positioning value in percent
UP_ Activation/deactivation of the circulation pump (heating) SLP Activation/deactivation of the storage tank charging pump TLP Activation/deactivation of the heat exchanger charging pump CP Activation/deactivation of the solar circuit pump ZP Activation/deactivation of the circulation pump (DHW)
3. Confirm the output [ ]. The display blinks.
4. Change positioning value/switching state [q].
5. Confirm setting [ ]. The modified values remain active as long as the controller is in manual mode.
6. Return the rotary switch to normal switch position (information level). The manual mode is deactivated.
Note: The outputs of the controller are not affected by simply turning the rotary switch to (manual level). You have to actually enter a positioning value or activate/deactivate the pumps to configure the outputs.
26 EB 5573 EN
Systems
4 Systems
21 different hydraulic schematics are available. The systems can be configured both as primary and secondary systems. The fundamental hy draulic differences between a primary and a secondary system are illustrated in Fig. 3.
1. mixing valve replaces the heat exchanger in the heating/DHW circuit.
4
2. A storage tank charging pump replaces the primary solenoid/thermoelectric valve.
4
The controller settings do not have to be changed.
1.
Primary system
RüF1 VF1UP1RK1 RK1RF1 VF1UP1 RüF1 RF1
BE BA AE RK
Secondary system
BE BA AE RK
-
2.
Primary system Secondary system
BE BA AE RK
Fig. 3 · Differences between primary and secondary systems
WW
KW
SF1SLP
BE BA AE RK
WW
KW
SF1SLP
EB 5573 EN 27
Systems
Boiler systems:
Single-stage boiler systems can be configured toinclude any system whose heatingcircuits and DHW circuit include just one heat exchanger. These systems are Anl 1.0, 1.5, 1.6, 2.x, 3.0,
3.5, 4.0 and 4.1.
The boiler can be controlled by an on/off output (CO1 -> F12 - 0).
Boiler
single-stage
RK1 RüF1 VF1 UP1 RF1
BE BA
AE RK
Fig. 4 · Configuration of a boiler system
RK1_2 Pkt VF1 UP1 RF1
BE BA
AE RK
28 EB 5573 EN
System Anl 1.0
Systems
UP1RK1
RüF1 VF1
BE BA AE RK
RF1
Default settings
CO1 -> F01 - 0 (without RF1) CO1 -> F02 - 1 (with AF1) CO1 -> F03 - 1 (with RüF1)
AF1
EB 5573 EN 29
Systems
Systems Anl 1.1 to 1.3
DHW
heating
Unfold back cover!
UP1 XX
BE BA AE RK
1)
AF1 RK1 VF1 RüF1 RF1
System Anl 1.1 Anl 1.2 Anl 1.3
Type of DHW heating Type 1 Type 2 Type 3
1)
XX = SLP TLP SLP Integration of flow sensor VF4 Possible Possible – ZP integration with
CO4 -> F10 - 1 (broken line) Note
Not possible
Secondary system only
Default settings
CO1 -> F01 - 0 (without RF1) - 0 (without RF1) - 0 (without RF1) CO1 -> F02 - 1 (with AF1) - 1 (with AF1) - 1 (with AF1) CO1 -> F03 - 1 (with RüF1) - 0 (without RüF1) - 1 (with RüF1) CO4 -> F01 - 1 (with SF1) - 1 (with SF1) - 1 (with SF1) CO4 -> F02 - 0 (without SF2) - 1 (with SF2) - 0 (without SF2) CO4 -> F05 - 0 (without VF4) - 0 (without VF4) - 0 (without VF4)
30 EB 5573 EN
Loading...
+ 96 hidden pages