Automation System TROVIS 5500
Room Controller
TROVIS 5572
Electronics from SAMSON
Mounting and
Operating Instructions
EB 5572 EN
®
Firmware version 1.10
Edition February 2007
Page 2
Disclaimer of liability
Disclaimer of liability
We areconstantly developing our products and therefore, reservethe right to change the prod
uct or the information contained in this document at any time without notice.
We donot assume any liability for the accuracy or completenessof these mounting and operat
ing instructions. Moreover, we do not guarantee that the buyer can use the product for an in
tended purpose. SAMSON rejects any liability for claims by the buyer, especially claims for
compensation including lost profits or any other financial loss, except the damage was caused
intentionally or by gross negligence. If an essential term of the contract is breached by negli
gence, SAMSON’s liability is limited to the foreseeable damage.
Safety instructions
The device may only be assembled, started up or operated by trained and
4
experienced personnel familiar with the product.
Proper shipping and appropriate storage are assumed.
The correct time and date needs to be set directly after starting up the controller or after the
power supply has been disconnected for more than 24 hours.
How to proceed:
Open the cover.
Press key briefly (approx 1 s). The time appears on the display.
An arrow on the right of the display at the same level as the changeover key indi
cates that the time can be changed.
Press this key to enter the editing mode.
The time starts to blink.
Enter the correct time.
Confirm the time.
Select date setting.
Press this key to enter the editing mode.
The date starts to blink.
Enter the correct date.
Confirm the date.
Select year setting.
Press this key to enter the editing mode.
The year starts to blink.
Enter the correct year.
Confirm the year.
Exit the parameter level.
-
Note!
If no key is pressed within five minutes, the controller display returns to the set point reading.
EB 5572 EN 7
Page 8
Operation
1.4Programming the time schedule
Three times-of-use can be programmed for each day of the week within which the controller
regulates the room temperature to the
Set point for time-of-use
set the start and stop times of this time-of-use to the identical time.
Parameters
Times-of-use Mon to Fri
Times-of-use Sat and Sun
WERange of values
08:00 to 20:00
00:00 to 00:00
00:00 to 24:00 h in steps of 15 minutes
00:00 to 24:00 h in steps of 15 minutes
How to proceed:
Open cover.
Press key briefly (approx 1 s). The time appears on the display.
An arrow on the right of the display at the same level as the changeover key indi
cates that the time can be changed.
The date appears on the display.
The year appears on the display.
Select time-of-use setting.
The arrow at the top of display points to.
Reading: 1–7 = daily, 1 = Monday, 2 = Tuesday, …, 7 = Sunday
Press this key to enter the editing mode.
The start time of the first time-of-use appears on the display.
Set the start time (in 15-minute steps).
Confirm the start time.
The stop time of the first time-of-use appears on the display.
Set the stop time (in 15-minute steps).
Confirm the stop time.
The start time of the second time-of-use appears on the display.
. If a time-of-use is not required,
-
Repeat the instructions highlighted in gray to set the second and third times-of-use. After all the
times-of-use have been programmed:
Exit the parameter level.
Note!
If no key is pressed within five minutes, the controller display returns to the set point reading.
8 EB 5572 EN
Page 9
Operation
1.5Selecting the operating mode (presence button)
Presskey repeatedly to cycle through the following operating modes:.
Temporary set point settings (see section 1.6) are reset when the operating mode is changed.
Automatic mode
(during time-of-use, no icon appears outside of time-of-use; 6…5…6)
Depending on the programmed time schedule, the controller regulates the room tem
perature to the
for outside of time-of-use
Set point for time-of-use
outside of the time-of-use.
Time-of-use (;55555…)
The controller regulates the room temperature to the
less of the programmed time schedule.
Outside of time-of-use (66666…)
The controller regulates the room temperature to the
time-of-use
regardless of the programmed time schedule.
The duration of the time-of-use and outside of time-of-use operating mode is set in function
block F02:
Function
Resetting operating mode1F02*
* F02 - 0: Operating mode settings for continuous time-of-use/outside of time-of-use
F02 - 1: Operating mode settings for time-of-use/outside of time-of-use that applies until the next
time schedule starts when the operating mode changes back to automatic mode
during the time-of-use and to the
Set point for time-of-use
Set point for outside of
WEConfiguration
Set point
regard
-
-
EB 5572 EN 9
Page 10
Operation
1.6Changing temperature set points temporarily
During the controller operation, the current set point and the actual temperature appear on the
display.
Use the arrow keys to temporarily change the current set point.
The new temporary set pointapplies until the next time-of-use starts or until the operating mode
is changed, however, eight hours at the maximum.
The following maximum set point shifts apply:
Set point for time-of-use
4
Set point for outside of time-of-use:
4
Set point for vacation mode
4
How to proceed:
Change the set point temporarily in steps of 0.5 °C.
Note!
The temporary set point can also be overwritten by a building control station (GLT) when the
communication is active (see section 4).
:±3 °C
+8 °C
:+8 °C
10 EB 5572 EN
Page 11
2Start-up
Start-up
The changes described in this section concerning controller configuration can only be per
formed after the valid key number has been entered.
The valid key number is specified on page 27. To prevent unauthorized access to the key num
ber, tear out or blank out the key number.
2.1Activate/deactivate functions
A function is activated and deactivated by selecting the associated function block.
The function blocks are listed in section 7.1.
How to proceed:
Open cover.
Press the data sheet key.
Enter key number.
The configuration level is opened.
Select the function block.
Enter the editing mode.
Fb : _ _ blinks.
Activate the function block.
Reading: Fb : _ _ ON
or
Deactivate the function block.
Reading: Fb : _ _ OFF
Confirm setting.
Repeat the instructions highlighted in gray to set further function blocks.
On completing the controller configuration:
Exit the configuration level (or, alternatively, by pressing).
-
-
Note!
If no key is pressed within five minutes, the controller display returns to the set point reading.
EB 5572 EN 11
Page 12
Start-up
2.2Changing parameters
Depending on the active functions, not all the parameters that are specified in the parameter
lists in the appendix are accessible (–> section 7.2).
The parameters are arranged in topics in various parameter levels (PA):
PA
4
4
4
Set points
PA
Control
PA
Communication
How to proceed:
Open cover.
Select required parameter level:
Enter the key number.
The parameter level is opened.
Select parameter.
Enter the editing mode.
The display starts to blinks.
Set parameter.
Confirm setting.
Repeat the instructions highlighted in gray to set other parameters in the opened parameter
level. On completing all the parameter settings:
Exit the parameter level. Use corresponding key depending on the parameter level:
:Set points for time-of-use, outside of time-of-use, and
If no key is pressed within five minutes, the controller display returns to the set point reading.
12 EB 5572 EN
Page 13
Start-up
2.3Calibrating the room sensor
If the temperature displayed on the room controller (current temperature on the bottom right of
the display) does not match the actual room temperature, the measured temperature of the
room sensor can be changed and reset. On calibration, the currently displayed sensor temper
ature needs to be changed to match the directlymeasured roomtemperature (referencetemper
ature).
Note!
An incorrectly performed calibration leads to the wrong room temperature measurements and
results in incorrect control performance. Use a thermometer with a high degree of accuracy on
measuring the reference temperature.
How to proceed:
Open cover.
Select
Communication
Enter the key number.
The parameter level is opened.
The device address appears on the display.
The Baud rate appears on the display.
The transmit/receive test appears on the display.
Select correction value for room sensor
Reading: Measured temperature (small); correction value (large)
Enter the editing mode.
The correction value starts to blink.
Set the temperature difference found.
Confirm the temperature difference.
Exit the parameter level (or, alternatively, by pressing).
parameter level.
-
-
Note!
If no key is pressed within five minutes, the controller display returns to the set point reading.
EB 5572 EN 13
Page 14
Start-up
2.4Checking inputs and outputs
The current state of the binary inputs, triacs and analog outputs can be displayed in the
munication
How to proceed:
parameter level. The state of triacs andanalog outputscan be changed manually.
Open cover.
Select
Communication
Enter the key number.
The parameter level is opened
Press key 4 times.
The state of the binary input BE1 appears:
E1 0 /E1 1 (BE1 open/closed)
Press the key once to change to the next input or output:
• Analog output AA1 · Reading: AA1 0 to AA1 100 (0 to 10 V voltage)
• Analog output AA2 · Reading: AA2 0 to AA2 100 (0 to 10 V voltage)
Changing triac/analog output state:
The output triac 1 (A1), triac 2 (A2), analog output AA1 or analog output AA2 ap
pear on the controller display.
Enter the editing mode.
Close triac (A_ 1) or raise voltage at the analog output.
or
Open TRIAC (A_ 0) or reduce voltage at the analog output.
parameter level.
Com
-
-
Exit the parameter level (or, alternatively, by pressing).
Note!
If no key is pressed within five minutes, the controller display returns to the set point reading.
14 EB 5572 EN
Page 15
2.5Reset to default settings
All parameters and functions can be reset to their default settings.
How to proceed:
Open cover.
Select default setting menu.
Enter the key number.
The default setting menu is opened.
Enter the editing mode.
Press key.
Confirm the reset.
Exit the default setting menu.
Start-up
EB 5572 EN 15
Page 16
Functions
3Functions
3.1Heating functions
3.1.1 Window contact
The window contact function depends on the state of binary input BE1:
BE1 = 0:The heating valve is closed.
4
BE1 = 1:Control according to the current operating mode.
4
The heating valve is opened for five minutes every 20 minutes
3.1.2 Optimization
The controller determines the
building characteristics.
Advance heating time
The
time-of-use
when the time-of-use starts, but at an earlier point in time instead.
The
side of time-of-use
finish when the outside of time-of-use starts, but at an earlier point in time instead.
Note!
Advance heating time
time
Function
Optimization0F03 - 1
Parameters
Maximum advance heating time360 minPA
Maximum cooling down time120 minPA
already when the time-of-use starts. In optimization mode, heating does not start
Cooling down time
already when the time-of-use ends. In optimization mode, heating does not
and
Maximum cooling down time
Advance heating time
is the time required to achieve the room temperature
is the time required to achieve the room temperature
and
Cooling down time
parameters respectively.
WEConfiguration
WEParameter level / Range of values
and
Cooling down time
are restricted by the
Set points
Set points
Maximum advance heating
/ 0 to 360 min
/ 0 to 120 min
depending on the
Set point for out-
Set point for
16 EB 5572 EN
Page 17
3.1.3 Vacation period
Functions
During the programmed
perature to the
The Presence alert function (section 3.3) isnot activeduring the programmed vacation period.
Parameters
Set point for vacation mode15 °CPA
Vacation schedule–PA
Set point for vacation mode
Vacation period
WEParameter level / Range of values
(start and stop), the controller regulates the room tem
.appears on the display.
Set points
Set points
/ 5 to 30 °C
/ –
3.2Cooling functions
The cooling valve regulates the temperature to the current set point during the time-of-use.
The following applies for outside of time-of-use:
When F04 - 0: No cooling
When F04 - 1: The temperature is regulated to a raised set point. The setback calculated
from the set point for outside of time-of-use during heating is interpreted
as an increase.
Function
Cooling0F04*
* F04 - 0: No cooling outside of time-of-use
F04 - 1: Cooling also outside of time-of-use
WEConfiguration
3.2.1 Window contact
The Window contact function depends on the state of binary input BE1:
BE1 = 0:The cooling valve is closed.
4
BE1 = 1:Control according to the current operating mode.
4
-
3.2.2 Dew point monitoring
The dew point monitoring uses the binary input BE2:
BE2 = 0:Temperature regulated to
4
BE2 = 1:Cooling is interrupted.
4
Function
Function BE20F01 - 1
Set point for outside of time-of-use
WEConfiguration
.
EB 5572 EN 17
Page 18
Functions
3.3Operating mode override
The adjusted operating mode override is processed by binary input BE2:
BE2 = 0:Control according to the current operating mode.
4
BE2 = 1:The temperature is regulated to
4
Note!
If the vacation mode is set, the setting F01 - 1 has no function; the controller continues to regu
late the temperature to
programmed time schedule or operating mode.
Set point for vacation mode.
Set point for time-of-use
regardless of the
-
Function
Function BE20F01 - 0
WEConfiguration
3.4Summer time/winter time changeover
The time changeover is performed automatically on the last Sunday in March at 02:00 h and on
the last Sunday in October at 03:00 h.
Function
Summer time/winter time changeover1F06 - 1
WEConfiguration
3.5Key lock
When this function is active,,,,andkeys do not have any function.
Just theset point and actual temperature appear on thecontroller display. Changes to the oper
ating mode and time schedule and temporary set point changes cannot be made.
Function
Key lock0F05 - 1
WEConfiguration
-
18 EB 5572 EN
Page 19
3.6Switching outputs
Functions
The operating mode of the switching outputs can be selected in the
Control
parameter level.
Note!
Changes to the control signal that are smaller than the value set in
parameter
Parameter
Min. control signal5 %PA
are not processed.
WEParameter level / Range of values
Control
/ 1 to 100 %
Min. control signal
Three-point stepping output (heating only)
The control loop functions with a PI control algorithm. The heating valve reacts to pulses which
the controllerissues when a system deviation exists. Inparticular, the length of the first pulsedepends on the size of the system deviation and the selected
rises). Pulse length and interval time change continuously until the system deviation is
as K
P
Gain K
eliminated. The interval between pulses is influenced considerably by the
terval increases as T
rises). The
N
Valve transit time T
indicates how long the valve needs to
Y
(the pulse length increases
P
Reset time T
(the in-
N
move through the range from 0 to 100 %.
Parameters
Switching outputs function1
Gain K
P
Reset time T
Valve transit time T
N
Y1
WEParameter level / Range of values
PA
Control
/ Select: 1
1.0PA
180 sPA
45 sPA
Control
Control
Control
/ 0.1 to 100
/ 0 to 1000 s
/ 0 to 1000 s
2 x On/off PPM (heating and cooling)
The control signals applied at the 0to 10 Voutput that exceedthe value enteredin the
control signal
1/T
Y1
Parameters
Switching outputs function1
Valve transit time T
Valve transit time T
parameter, are issued as a pulse width modulated signal with the basic frequency
(heating) or 1/TY2(cooling).
WEParameter level / Range of values
PA
Control
/ Select: 2
Y1
Y2
45 sPA
45 sPA
Control
Control
/ 0 to 1000 s
/ 0 to 1000 s
EB 5572 EN 19
Minimum
Page 20
Functions
2 x On-off thermostat (heating and cooling)
The output signal (AA1 heating, AA2 cooling) of the controller is switched on or off.
A control signal is issued when the temperature exceeds or falls below the set point, depending
on the controlled variable. If the control signal exceeds the
Min. Control signal
, the on-off ther
mostat is switched on or off.
Parameter
Switching outputs function1
WEParameter level / Range of values
PA
Control
/ Select: 3
Triac 1 and triac 2 switched according to the time schedule
Both triacs are switched on together depending on the time schedule or the adjusted operating
mode. Both triacs are closed outside of time-of-use.
Parameter
Switching outputs function1
WEParameter level / Range of values
PA
Control
/ Select: 4
Triac 1 switched according to the time schedule, triac 2 switched according the state of
AA2
Triac 1 switches according to the time schedule or adjusted operating mode.
Triac 2 switches on when the control signal for cooling = 100 % and when a system deviation
(cooling demand) continues to exist. Triac 2 functions in sequence to the control signal for cooling, for example, to connect additional cooling equipment. When the temperature reaches the
set point, triac 2 switches off again.
Parameter
Switching outputs function1
WEParameter level / Range of values
PA
Control
/ Select: 5
-
20 EB 5572 EN
Page 21
4Communication
Communication
The serialsystem bus interface RS-485 enables the TROVIS 5572 Room Controller tocommuni
cate with a control system (GLT). A complete control system can be implemented using a suit
able software to visualize the process and to enable communication.
The operation of the controller requires a constant bus link (data cable).The bus line is designed
in an open ring structure to connect individual control equipment. The data cable is connected
at the end of the bus lineto thecontrol station over a RS-485/RS-232 converter (e.g.CoRe 01).
The bus connection range (cable length) is maximum 1200 m. A maximum of 128 devices can
be connected in such a segment. Repeaters must be used (for example, CoRe 01) to regenerate
the signal level over long distances or when more than 32 devices are connected to one bus
line. A maximum of 246 devices can be addressed and connected to a bus with 8-bit
addressing.
Caution!
You are required to follow the relevant standards and regulations applicable to lightning and overvoltage protection on installing the controller.
A transmitting and/or receiving test can be initiated in the
RC blinking :Receiving data telegrams from control station (GLT),
4
on the displayeven when they are intended for other controllers
:Controller transmitting to control station (GLT)
4
Description of the parameters that need to be set:
Device address
The
within a system.
Baud rate
The
is used to identify the controller. An address may only be assigned once
indicates the transfer rate between control systemand controllerin a bus system.
The room controller must be mounted at a height of 1.50 m.
Make sure that the operation of the room controller is not affected by heat sources (radiators,
lights, electrical appliances) or by drafts close to doors or windows.
The room controller should not be covered by curtains or any pieces of furniture.
To mount and wire the room controller, remove the housing from the base.
How to proceed:
1. Press down the tongue on the bottom of the controller and tip the housing section forward to remove it from the base.
2. Screw the base to the wall.
3. Connect the wiring as described in section 6.
4. Push the top of the housing section onto the base and push it down.
22 EB 5572 EN
Page 23
6Electrical connection
Important!
The room controller is operated with a 24 V AC power supply.
Terminal assignment
Electrical connection
1
2
30…10 V output 1
40…10 V output 2
5GND for 0…10 V outputs
6Binary input BE1
7Binary input BE2
8GND for binary inputs
9
10AC 2 has GND reference
11
12
13
14
15
16
Modbus RS-485 (slave)
Power supply 24 V AC
Triac output 124 V AC, 1 A
Triac output 224 V AC, 1 A
RS-485; Modbus (master)Connection to expansion module(s)
Connection to the control station (GLT) or
to a Modbus master interface
AC 1
EB 5572 EN 23
Page 24
Appendix
7Appendix
7.1Function block list
FFunction blockWEDescription
01 Function BE20F01 - 0:Operating mode override by BE2
F01 - 1:Dew point monitoring
02 Resetting the operating
mode
03 Optimization0F03 - 0:Function is not active
04 Cooling0F04 - 0:Cooling not active outside of time-of-use
05 Key lock0F05 - 0:Function is not active
06 Summer time/winter
time changeover
07 16-bit addressing0F07 - 0:8-bit addressing
1F02 - 0:Time-of-use/outside of time-of-use operating
mode setting continuous
F02 -1 :Time-of-use/outside of time-of-use operating
mode setting that applies until the next time
schedule starts when the operating mode changes
back to automatic mode
F03 - 1:Optimization; calculation of advance heating time
or cooling down time in heating mode
F04 - 1:Cooling also active outside of time-of-use
F05 - 1:Keys (except for recessed keys) are locked
1F06 - 0:Function is not active
F06 - 1:Automatic time changeover
F07 - 1:16-bit addressing
24 EB 5572 EN
Page 25
7.2Parameter list
Appendix
Set points
parameter level
ParameterWEDescription
01 Set point for time-of-use21 °CAdjustment range: 5 to 30 °C
02 Set point for outside of
17 °CAdjustment range: 5 to 30 °C
time-of-use
03 Set point for vacation
15 °CAdjustment range: 5 to 30 °C
mode
04 Maximum advance
heating time
360 min Start value for the calculation: 120 min
Can only selected when the optimization function is active
(F03 - 1).
05 Maximum cooling
down time
120 min Start value for the calculation: 60 min
Can only selected when the optimization function is active
(F03 - 1).
06 Vacation schedule–
Control
parameter level
ParameterWEDescription
01 Switching outputs
function
1
Option:
1: Three-point stepping output
2: 2 x On/off PPM
3: 2 x On/off thermostat
4: Triac 1 and triac 2 switched according to the time schedule
5: Triac 1 switched according to the time schedule;
Triac 2 switched acc. to the state of triac 1 and AA2
02 Gain K
03 Reset time T
P
N
04 Derivative-action time T
05 Valve transit time T
06 Valve transit time T
Y1
Y2
1.0Adjustment range: 0.1 to 100
180 sAdjustment range: 0 to 1000 s
0 sAdjustment range: 0 to 1000 s
V
45 sAdjustment range: 0 to 1000 s
45 sAdjustment range: 0 to 1000 s
07 Min. control signal5.0 %Adjustment range: 1.0 to 100 %
EB 5572 EN 25
Page 26
Appendix
Communication
ParameterWEDescription
01 Device address0Adjustment range: 0 to 255 (8 bit) 0 to 999 (16 bit)