Samson TROVIS 5572, TROVIS 5500 Mounting And Operating Instructions

Automation System TROVIS 5500 Room Controller TROVIS 5572
Electronics from SAMSON
Mounting and Operating Instructions
EB 5572 EN
®
Disclaimer of liability
Disclaimer of liability
We areconstantly developing our products and therefore, reservethe right to change the prod uct or the information contained in this document at any time without notice.
We donot assume any liability for the accuracy or completenessof these mounting and operat ing instructions. Moreover, we do not guarantee that the buyer can use the product for an in tended purpose. SAMSON rejects any liability for claims by the buyer, especially claims for compensation including lost profits or any other financial loss, except the damage was caused intentionally or by gross negligence. If an essential term of the contract is breached by negli gence, SAMSON’s liability is limited to the foreseeable damage.
Safety instructions
The device may only be assembled, started up or operated by trained and
4
experienced personnel familiar with the product. Proper shipping and appropriate storage are assumed.
4
-
-
-
-
2 EB 5572 EN

Contents

Contents
1 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1 Operating elements. . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3 Setting the controller time . . . . . . . . . . . . . . . . . . . . . . . . 7
1.4 Programming the time schedule . . . . . . . . . . . . . . . . . . . . . 8
1.5 Selecting the operating mode (presence button) . . . . . . . . . . . . . 9
1.6 Changing temperature set points temporarily . . . . . . . . . . . . . . 10
2 Start-up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.1 Activate/deactivate functions . . . . . . . . . . . . . . . . . . . . . 11
2.2 Changing parameters . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.3 Calibrating the room sensor . . . . . . . . . . . . . . . . . . . . . . 13
2.4 Checking inputs and outputs . . . . . . . . . . . . . . . . . . . . . . 14
2.5 Reset to default settings . . . . . . . . . . . . . . . . . . . . . . . . 15
3 Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.1 Heating functions . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.1.1 Window contact . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.1.2 Optimization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.1.3 Vacation period. . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.2 Cooling functions . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.2.1 Window contact . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.2.2 Dew point monitoring . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.3 Operating mode override . . . . . . . . . . . . . . . . . . . . . . . 18
3.4 Summer time/winter time changeover . . . . . . . . . . . . . . . . . 18
3.5 Key lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.6 Switching outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
6 Electrical connection. . . . . . . . . . . . . . . . . . . . . . . . . . 23
7 Appendix. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
7.1 Function block list . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
7.2 Parameter list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
7.3 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
EB 5572 EN 3
Brief description
Changeover key (short = 1 s) (time, date, time schedules)
Changeover key (long = 5 s) (
Set points
parameter level)
Presence button (Operating mode: Automatic – Time-of-use – Outside time-of-use)
Arrow keys (scrolling, changing)
Reset key Default settings
4 EB 5572 EN
Data sheet key (configuration level)
Thermometer key (
Control
parameter level)
Radio tower key (
Communication
Enter key (selecting, confirming)
parameter level, test)
Operation
1 Operation
The room controller is ready for use after performing the connections (section 6) and start-up (section 2).
1.1 Operating elements
Operating elements when cover is closed
Arrow keys (up and down keys)
Used to select displays and parameters
Manual key
Without any function
Additional operating elements accessible with the cover open
Enter key
Used to confirm a selection or setting
Changeover key
Key pressed for approx. 1 sec.: Open controller time and programmed time schedule Key pressed for approx. 5 sec.: Open tering key number)
Presence button
Used to select operating mode (Automatic – Time-of-use – Outside of time-of-use)
Set points
parameter level (only after en-
Note that you require a pointed object such as a ball-point pen in order to press the follow ing recessed keys:
Thermometer key
Used to access
Radio tower key
Used to access
Data sheet key
Used to access configuration level (only after entering key number)
Reset key
Used to reset the room controller to its default settings (delivery state) (only after entering key number)
Control
Communication
parameter level (only after entering key number)
parameter level (only after entering key number)
EB 5572 EN 5
-
Operation
1.2 Display
Information on the current operation appears on the display of the controller during use:
Set point Large reading
Actual temperature Small reading on the bottom right of the display
The actual temperature reading changes in steps of 0.5 °C.
Operating mode No icon outside of time-of-use
during time-of-use in vacation mode
Presence Arrow points to indicating that the automatic operating mode has
been interrupted (refer to section 1.5)
Time schedule 5, 6 changes in automatic operating mode depending on the
programmed time schedule: 5 Time-of-use · 6 Outside of time-of-use
555 Continuous time-of-use (automatic operating mode interrupted) 666 Continuously outside of time-of-use (automatic operatingmode
interrupted)
Communication failure
Control station intervention
Frost protection Actual temperature (small) blinks on the display when
6 EB 5572 EN
blinks on the display
(only when communication is configured, refer to section 4)
RC appears on the display (only when communication is configured, refer to section 4)
– Actual room temperature < 5 °C – Dew-point monitor alarm – Window contact
Snow flake icon (blinking) – Actual room temperature < 5 °C
Snow flake icon (constant) – Dew-point monitor alarm
Operation
1.3 Setting the controller time
The correct time and date needs to be set directly after starting up the controller or after the power supply has been disconnected for more than 24 hours.
How to proceed:
Open the cover. Press key briefly (approx 1 s). The time appears on the display.
An arrow on the right of the display at the same level as the changeover key indi cates that the time can be changed.
Press this key to enter the editing mode. The time starts to blink.
Enter the correct time. Confirm the time. Select date setting. Press this key to enter the editing mode.
The date starts to blink. Enter the correct date. Confirm the date. Select year setting. Press this key to enter the editing mode.
The year starts to blink. Enter the correct year. Confirm the year. Exit the parameter level.
-
Note!
If no key is pressed within five minutes, the controller display returns to the set point reading.
EB 5572 EN 7
Operation
1.4 Programming the time schedule
Three times-of-use can be programmed for each day of the week within which the controller regulates the room temperature to the
Set point for time-of-use
set the start and stop times of this time-of-use to the identical time.
Parameters
Times-of-use Mon to Fri Times-of-use Sat and Sun
WE Range of values 08:00 to 20:00
00:00 to 00:00
00:00 to 24:00 h in steps of 15 minutes 00:00 to 24:00 h in steps of 15 minutes
How to proceed:
Open cover. Press key briefly (approx 1 s). The time appears on the display.
An arrow on the right of the display at the same level as the changeover key indi cates that the time can be changed.
The date appears on the display. The year appears on the display. Select time-of-use setting.
The arrow at the top of display points to . Reading: 1–7 = daily, 1 = Monday, 2 = Tuesday, …, 7 = Sunday
Press this key to enter the editing mode. The start time of the first time-of-use appears on the display.
Set the start time (in 15-minute steps). Confirm the start time.
The stop time of the first time-of-use appears on the display. Set the stop time (in 15-minute steps). Confirm the stop time.
The start time of the second time-of-use appears on the display.
. If a time-of-use is not required,
-
Repeat the instructions highlighted in gray to set the second and third times-of-use. After all the times-of-use have been programmed:
Exit the parameter level.
Note!
If no key is pressed within five minutes, the controller display returns to the set point reading.
8 EB 5572 EN
Operation
1.5 Selecting the operating mode (presence button)
Press key repeatedly to cycle through the following operating modes:. Temporary set point settings (see section 1.6) are reset when the operating mode is changed.
Automatic mode
( during time-of-use, no icon appears outside of time-of-use; 656) Depending on the programmed time schedule, the controller regulates the room tem perature to the
for outside of time-of-use
Set point for time-of-use
outside of the time-of-use.
Time-of-use (;55555…) The controller regulates the room temperature to the less of the programmed time schedule.
Outside of time-of-use (66666…) The controller regulates the room temperature to the
time-of-use
regardless of the programmed time schedule.
The duration of the time-of-use and outside of time-of-use operating mode is set in function block F02:
Function
Resetting operating mode 1 F02* * F02 - 0: Operating mode settings for continuous time-of-use/outside of time-of-use
F02 - 1: Operating mode settings for time-of-use/outside of time-of-use that applies until the next
time schedule starts when the operating mode changes back to automatic mode
during the time-of-use and to the
Set point for time-of-use
Set point for outside of
WE Configuration
Set point
regard
-
-
EB 5572 EN 9
Loading...
+ 19 hidden pages