Automation System TROVIS 5500
Programmable Logic Controller (PLC)
TROVIS 5571
Electronics from SAMSON
Mounting and
Operating Instructions
EB 5571 EN
®
Firmware version 1.21
Edition March 2009
Disclaimer of liability
Disclaimer of liability
We are constantly developing our products and therefore, reserve the right to change the
product or the information contained in this document at any time without notice.
We do not assume any liability for the accuracy or completeness of these mounting and
operating instructions. Moreover, we do not guaranteethat thebuyer can use the product for an
intended purpose. SAMSON rejects any liability for claims by the buyer, especially claims for
compensation including lost profits or any other financial loss, except the damage was caused
intentionally or by gross negligence. If an essential term of the contract is breached by
negligence, SAMSON’s liability is limited to the foreseeable damage.
Safety instructions
The device may only be assembled, started up or operated by trained and
4
experienced personnel familiar with the product. Proper shipping and
appropriate storage are assumed.
The device has been designed for use in electrical power systems. For wiring
4
and maintenance, you are required to observe the relevant safety
regulations.
Modifications of the PLC firmware compared to the previous version
1.10 (old) 1.11 (new)
New default setting for parameter
Expansion of the data logging function (see section 5.5)
The programmable logic controller (PLC) is freely programmable. The controller is delivered
without an executable application in the memory. The application must be developed sepa
®
rately for the desired purpose on a personal computer using ISaGRAF
(programming as in
IEC 61131-1) and then transferred to the controller.
On start-up, after transferring the generated application, the current time and date must be set
in the controller (–> section 1.4).
1.1Operating elements
1.1.1 Operating keys
The keys are located in the front panel of the PLC and protected by a Plexiglas door.
Changeover key
(press with pen or other pointed item)
Switch between levels (after entering the key code)
Reset key
(press with pen or other pointed item)
Reset freely accessible parameters and function blocks to their default values
(factory settings)
-
4 EB 5571 EN
Cursor key(s)
Pressing both keys together:
– Switch to information level
Pressing one of the keys separately:
– Navigate in levels (also in the application developed with ISaGRAF
– Set data points
Enter key
– Open levels (also in the application developed with ISaGRAF
®
– Activate editing mode for parameters and function blocks
– Confirm entered settings
®
)
)
Operation
1.2Display
The programmable logic controller has a plain text display.
The display is automatically illuminated when entering or setting the controller.
After connecting the controller to the power supply, “System is being initialized…“ appears
briefly on the display.
Should the display not be illuminated or the contrast is too strong/weak, you can adapt the dis
play illumination. Refer to section 1.2.1.
If an application is not saved on the PLC, the normal display
(left) contains the date, time and current firmware version.
If an application is saved on the PLC, the normal display
contains application-related information.
-
blinking
blinking
SMS
Direct connection
to control station
active
Modem inactive
Modem initializa
tion active
RING,
calling active
Connection estab
lished/canceled
Connection to con
trol station active
Error
SMS sending
active
Modbus master
active
-
-
-
Connection to
ISaGRAF
®
bench active
Data logging
active
EB 5571 EN 5
Work-
Operation
Note!
If no key is pressed for two minutes, the PLC returns to the normal display. The background
illumination of the display is switched off automatically.
Any settings that have not been confirmed are not saved and must be re-entered.
1.2.1 Adjusting the contrast of the display
Entering the key code
0000
Activate the editing mode.
Display: Entering the key code
0000
blinks
Confirm the
0000
reading.
Set the contrast.
Confirm the changed setting.
Display: Normal display (depending on the
application)
6 EB 5571 EN
1.3Displaying data
Operation
The states of the inputs and outputs as well as information on the connected meter bus instru
ments can be retrieved in the information level. In addition, the analog and binary outputs can
be changed (refer to section 3 on manual operation).
The information level is divided into individual menu items:
Analog inputs · Measured data from connected sensors
4
Analog outputs · Output data from four analog outputs *
4
Binary inputs · States of the binary sensors (on/off)
4
Binary outputs · States of the binary outputs (on/off) *
4
Meter bus · Output data of the meters connected over meter bus
4
*)The analog and binary output settings can be changed after entering the key code.
)
)
Proceed as follows:
Information level
Analog inputs
Analog outputs
Binary inputs
Binary outputs
Meter bus
System info
Analog inputs
Analog outputs
Binary inputs
Binary outputs
Meter bus
System info
Back
Switch to the information level.
Display: Information level
The menu item “Analog inputs“ is highlighted.
Select required menu item, e.g. binary outputs.
Activate the menu item.
Select required data point.
Returning to the information level
Select
Back
to return to the information level.
Exit the menu item.
Display: Information level
Exiting the information level
Select
Back
.
Exit the information level.
Display: Normal display (depending on the
application)
-
Note!
If no key is pressed for two minutes, the PLC automatically returns to the normal display.
EB 5571 EN 7
Operation
1.4Setting the system time
The current time and date need to be set immediately after start-up and after a power failure
lasting more than 24 hours.
Set the system time in the settings level under the menu item “Date / time”. The Automatic sum
mer time function can also be activated or deactivated in this menu item.
System time: Time-dependent functions of the saved application are based on the system
4
time set in the PLC.
Automatic summer time: The summer time is automatically set on the last Sunday in
4
March at 02:00 h and the winter time on the last Sunday in October at 03:00 h.
Proceed as follows:
-
Entering the key code
0000
Settings level
Date / time
RS-232/Slave
RS-485/Master
RS-232/Prog
Meter bus
Universal input type
Back
Settings level
28.11.2005 10:00
RS-232/Slave
RS-485/Master
RS-232/Prog
Meter bus
Universal input type
Back
Activate the editing mode.
Display: Entering the key code
0000
blinks
Enter the key code.
Confirm the key code entered.
Display: Settings level
The “Date / time“ menu item is highlighted.
Activate the menu item “Date / time“.
Display: System time (DD.MM.YYYY HH:MM)
Activate the editing mode for the system time.
DD
Display: Date (
) blinks.
Enter date.
Confirm date entered.
MM
Display: Month (
) blinks.
8 EB 5571 EN
Settings level
Automatic summer time? On
RS-232/Slave
RS-485/Master
RS-232/Prog
Meter bus
Universal input type
Back
Settings level
28.11.2005 10:00
RS-232/Slave
RS-485/Master
RS-232/Prog
Meter bus
Universal input type
Back
Operation
Enter month.
Confirm month entered.
YYYY
Display: Year (
) blinks.
Enter year.
Confirm year entered.
HH
Display: Time (
) blinks.
Enter hour.
Confirm hour entered.
MM
Display: Minutes (
) blink.
Enter minutes.
Confirm minutes entered.
Display: “Automatic summer time? __“ blinks
If required, change the current setting (on/off) of the
Automatic summer time function.
Activate function: Automatic summer time? On
Deactivate function: Automatic summer time? Off
Exit the menu item “Date / time“.
Display: Settings level
Settings level
Date / time
RS-232/Slave
RS-485/Master
RS-232/Prog
Meter bus
Universal input type
Back
Exiting the settings level
Select
Back.
Exit the settings level.
Display: Normal display (depending on the
application)
Note!
If no key is pressed for two minutes, the PLC automatically returns to the normal display.
EB 5571 EN 9
Start-up
2Start-up
2.1Programming
Programming the PLC requires a PC with ISaGRAF®software.
®
The ISaGRAF
needs of your plant (ISaGRAF
software enables you to program a control system that is tailored to the specific
®
development environment 1400-7621). Programming must fol
low the structures and rules stipulated in IEC 61131-3. The PLC may be programmed with the
languages defined in the standard: Sequential Function Chart (SFC), Instruction List (IL), Flow
Chart (FC), Function Block Diagram (FBD), Ladder Diagram (LD), and Structured Text (ST).
®
There are 128 KB of memory available in the PLC for the ISaGRAF
application.
The application is complied to machine code in the PC environment. This code is then trans
ferred to the PLC over the front RJ-45 jack (connecting cable 1400-7620).
Programming languages:
Sequential Function Chart
(SFC):
Instruction List (IL):Low-level textual language for logic and arithmetic operations
Flow Chart (FC):High-level language used to visualize the data flow
Function Block Diagram
(FBD):
Ladder Diagram (LD):Simple graphics-based language for logical operations (boolean)
Structured Text (ST):High level language similar to PASCAL and C especially designed for
Used to describe operations of a sequential process with a simple graphic representation
Graphics-based language for building and combining complex functions
(logical, arithmetic)
control applications
For operation and application of the ISaGRAF®environment, refer to the documentation in
cluded in the software package. To enable simple and clear programming, ready-made func
tions and function blocks, e.g. for boiler systems, heat exchanger sequence control, ventilation
systems, heating circuits or domestic hot water systems, are available from SAMSON.
-
-
-
-
Parameters*
Station address255RS-232/Prog / 1 to 247, 255
Baud rate9600RS-232/Prog / 9600, 19200
WESettings level / Range of values
* –> Section 5.3 (Description of communication parameters to be adjusted)
10 EB 5571 EN
Start-up
Note!
In ISaGRAF
status or value of the internal variable is written to the associated holding or coil register and
can be read or written over Modbus.
Important! The PLC application must be reloaded after a cold start.
®
, internal variables can be assigned (integer or bool) network addresses. The
2.2Changing PLC settings
PLC settings can only be changed after entering the valid key code.
The valid key code can be found on page 42. To avoid unauthorized use, remove the page or
make the key code unreadable.
Change PLC settings in the settings level, which contains the following menu items:
Date / time, refer to section 1.4
4
RS-232/Slave, refer to section 5.1
4
RS-485/Master, refer to section 5.2
4
RS-232/Prog, refer to section 2.1
4
Meter bus, refer to section 5.4
4
Universal input type, refer to section 2.3
4
Proceed as follows:
Entering the key code
0000
Activate the editing mode.
Display: Entering the key code
0000
blinks
Enter the valid key code.
EB 5571 EN 11
Start-up
Settings level
Date / time
RS-232/Slave
RS-485/Master
RS-232/Prog
Meter bus
Universal input type
Back
RS-232/Slave
Modbus Slave
Modem
Baud rate
Back
Settings level
Date / time
RS-232/Slave
RS-485/Master
RS-232/Prog
Meter bus
Universal input type
Back
Confirm the key code.
Display: Settings level
The menu item “Date / time“ is highlighted.
Select the menu item in which the settings are to be
changed, e.g. “RS-232/Slave“.
Activate the selected menu item.
Select the data point which you want to change.
Activate the editing mode of the data point.
Display: Data point blinks.
Set the data point.
Confirm the setting.
Returning to the settings level
Back
Select
to return to the settings level.
Exit the menu item.
Display: Settings level
Exiting the settings level
Select
Back
to return.
Exit the settings level.
Display: Normal display (depending on the
application)
Note!
If no key is pressed for two minutes, the PLC automatically returns to the normal display.
12 EB 5571 EN
Start-up
2.3Configuring universal inputs
There are 17 universal inputs, which may be used as binary inputs, analog inputs (0 to 10 V,
0/4 to 20 mA) or as sensor inputs. The hardware must be configured accordingly (sensor ini
tialization).
Refer to page 38 for the resistance values of the PTC, Pt 100 and Pt 1000 sensors.
You can also configure each universal input separately.
The following configurations are available: Pt 100/500/1000/2000, Ni 200/1000/2000,
PTC, NTC, 1–2 kΩ, BE, 0/4 to 20 mA (with 50Ωparallel resistor) and 0 to 10 V.
Proceed as follows:
-
Entering the key code
0000
Settings level
Date / time
RS-232/Slave
RS-485/Master
RS-232/Prog
Meter bus
Universal input type
Activate the editing mode.
Display: Entering the key code
0000
blinks
Enter the valid key code.
Confirm the key code.
Display: Settings level
The “Date / time“ menu item is highlighted.
Select the menu item “Universal input type“.
Activate this selected menu item.
The first universal input UE01is highlighted.
Select the universal input.
Activate the universal input.
UE__
Display:
blinks.
EB 5571 EN 13
Manual operation
Select the type of universal input.
The inputs are available in the following order:
PT100↔PT1000, PT100↔PTC, NI2000, PT2000,
PT500, 0 – 10V, BE, 1000 – 2000Ω, PT100,
PT1000, NTC, PTC, NI1000, NI200, 4 – 20mA,
0 – 20mA
Note!
On selecting the universal input types PT100
PT100
PTC, this configuration applies then to all 17 uni
↔
PT1000 or
↔
versal inputs. Any inputs that have a different type need to
be configured separately afterwards.
Binary inputs with terminal 10 functioning as GND are slow
(delay of approx. 3 s).
Binary inputs with terminal 9 functioning as GND are fast
(ms).