Samson TROVIS 5571, TROVIS 5500 Series Mounting And Operating Instructions

Page 1
Automation System TROVIS 5500 Programmable Logic Controller (PLC) TROVIS 5571
Electronics from SAMSON
Mounting and Operating Instructions
EB 5571 EN
®
Page 2
Disclaimer of liability
Disclaimer of liability
We are constantly developing our products and therefore, reserve the right to change the product or the information contained in this document at any time without notice.
We do not assume any liability for the accuracy or completeness of these mounting and operating instructions. Moreover, we do not guaranteethat thebuyer can use the product for an intended purpose. SAMSON rejects any liability for claims by the buyer, especially claims for compensation including lost profits or any other financial loss, except the damage was caused intentionally or by gross negligence. If an essential term of the contract is breached by negligence, SAMSON’s liability is limited to the foreseeable damage.
Safety instructions
The device may only be assembled, started up or operated by trained and
4
experienced personnel familiar with the product. Proper shipping and appropriate storage are assumed.
The device has been designed for use in electrical power systems. For wiring
4
and maintenance, you are required to observe the relevant safety regulations.
Modifications of the PLC firmware compared to the previous version
1.10 (old) 1.11 (new)
New default setting for parameter Expansion of the data logging function (see section 5.5)
1.11 (old) 1.21 and lower (new)
Internal modifications
2 EB 5571 EN
Gateway
= Off
Page 3
Contents

Contents Page

1 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1 Operating elements. . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1.1 Operating keys. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2.1 Adjusting the contrast of the display . . . . . . . . . . . . . . . . . . . 6
1.3 Displaying data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.4 Setting the system time . . . . . . . . . . . . . . . . . . . . . . . . . 8
2 Start-up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.1 Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.2 Changing PLC settings. . . . . . . . . . . . . . . . . . . . . . . . . 11
2.3 Configuring universal inputs . . . . . . . . . . . . . . . . . . . . . . 13
2.4 Resetting to default values . . . . . . . . . . . . . . . . . . . . . . . 15
3 Manual operation. . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4 Operational faults . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
5.1 Modbus slave interface . . . . . . . . . . . . . . . . . . . . . . . . 18
5.2 Modbus master interface . . . . . . . . . . . . . . . . . . . . . . . 20
5.3 Description of communication parameters to be adjusted . . . . . . . . 21
5.4 Meter bus interface . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.4.1 Activating the meter bus . . . . . . . . . . . . . . . . . . . . . . . . 23
5.5 Data logging module . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.5.1 Data logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.5.2 Saving and loading firmware and applications . . . . . . . . . . . . . 26
6 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
7 Electrical connection. . . . . . . . . . . . . . . . . . . . . . . . . . 29
8 Appendix. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
8.1 Settings level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
8.2 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
8.3 Special key codes . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
8.4 Expansion modules . . . . . . . . . . . . . . . . . . . . . . . . . . 35
8.4.1 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
8.4.2 Terminal assignment. . . . . . . . . . . . . . . . . . . . . . . . . . 36
8.4.3 Integrating the expansion modules . . . . . . . . . . . . . . . . . . . 37
8.5 Sensor resistance tables . . . . . . . . . . . . . . . . . . . . . . . . 38
8.6 Customer data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
EB 5571 EN 3
Page 4
Operation
1 Operation
The programmable logic controller (PLC) is freely programmable. The controller is delivered without an executable application in the memory. The application must be developed sepa
®
rately for the desired purpose on a personal computer using ISaGRAF
(programming as in
IEC 61131-1) and then transferred to the controller. On start-up, after transferring the generated application, the current time and date must be set
in the controller (–> section 1.4).
1.1 Operating elements
1.1.1 Operating keys
The keys are located in the front panel of the PLC and protected by a Plexiglas door.
Changeover key
(press with pen or other pointed item) Switch between levels (after entering the key code)
Reset key
(press with pen or other pointed item) Reset freely accessible parameters and function blocks to their default values (factory settings)
-
4 EB 5571 EN
Cursor key(s)
Pressing both keys together:
– Switch to information level
Pressing one of the keys separately: – Navigate in levels (also in the application developed with ISaGRAF – Set data points
Enter key
– Open levels (also in the application developed with ISaGRAF
®
– Activate editing mode for parameters and function blocks – Confirm entered settings
®
)
)
Page 5
Operation
1.2 Display
The programmable logic controller has a plain text display. The display is automatically illuminated when entering or setting the controller.
After connecting the controller to the power supply, “System is being initialized…“ appears briefly on the display. Should the display not be illuminated or the contrast is too strong/weak, you can adapt the dis play illumination. Refer to section 1.2.1.
28.11.2005 10:00:05 V1.1xx
Application: … Version: … Date: … CRC: … Size: … kB Cycle time: … ms
The current status of the three communication interfaces “RS-232/Slave“, “RS-485/Master“ and “RS-232/Prog“ appears at the bottom of the display:
RS-232/Slave (left) RS-485/Master (middle) RS-232/Prog (right)
Interface inactive Interface inactive Interface inactive
If an application is not saved on the PLC, the normal display (left) contains the date, time and current firmware version.
If an application is saved on the PLC, the normal display contains application-related information.
-
blinking
blinking
SMS
Direct connection to control station
active
Modem inactive
Modem initializa
tion active
RING,
calling active
Connection estab
lished/canceled
Connection to con
trol station active
Error
SMS sending
active
Modbus master
active
-
-
-
Connection to
ISaGRAF
®
bench active
Data logging
active
EB 5571 EN 5
Work-
Page 6
Operation
Note!
If no key is pressed for two minutes, the PLC returns to the normal display. The background illumination of the display is switched off automatically. Any settings that have not been confirmed are not saved and must be re-entered.
1.2.1 Adjusting the contrast of the display
Entering the key code
0000
Activate the editing mode. Display: Entering the key code
0000
blinks
Confirm the
0000
reading. Set the contrast. Confirm the changed setting.
Display: Normal display (depending on the application)
6 EB 5571 EN
Page 7
1.3 Displaying data
Operation
The states of the inputs and outputs as well as information on the connected meter bus instru ments can be retrieved in the information level. In addition, the analog and binary outputs can be changed (refer to section 3 on manual operation). The information level is divided into individual menu items:
Analog inputs · Measured data from connected sensors
4
Analog outputs · Output data from four analog outputs *
4
Binary inputs · States of the binary sensors (on/off)
4
Binary outputs · States of the binary outputs (on/off) *
4
Meter bus · Output data of the meters connected over meter bus
4
*)The analog and binary output settings can be changed after entering the key code.
)
)
Proceed as follows:
Information level
Analog inputs
Analog outputs Binary inputs Binary outputs Meter bus System info
Back
Binary outputs
BA07=OFF BA08=OFF BA09=OFF BA10=OFF BA11=OFF BA12=OFF
Back
Information level
Analog inputs Analog outputs Binary inputs Binary outputs Meter bus System info
Back
Switch to the information level. Display: Information level The menu item “Analog inputs“ is highlighted.
Select required menu item, e.g. binary outputs. Activate the menu item. Select required data point.
Returning to the information level
Select
Back
to return to the information level.
Exit the menu item. Display: Information level
Exiting the information level
Select
Back
.
Exit the information level. Display: Normal display (depending on the application)
-
Note!
If no key is pressed for two minutes, the PLC automatically returns to the normal display.
EB 5571 EN 7
Page 8
Operation
1.4 Setting the system time
The current time and date need to be set immediately after start-up and after a power failure lasting more than 24 hours.
Set the system time in the settings level under the menu item “Date / time”. The Automatic sum
mer time function can also be activated or deactivated in this menu item.
System time: Time-dependent functions of the saved application are based on the system
4
time set in the PLC. Automatic summer time: The summer time is automatically set on the last Sunday in
4
March at 02:00 h and the winter time on the last Sunday in October at 03:00 h.
Proceed as follows:
-
Entering the key code
0000
Settings level
Date / time
RS-232/Slave RS-485/Master RS-232/Prog Meter bus Universal input type
Back
Settings level
28.11.2005 10:00
RS-232/Slave RS-485/Master RS-232/Prog Meter bus Universal input type
Back
Activate the editing mode. Display: Entering the key code
0000
blinks
Enter the key code. Confirm the key code entered.
Display: Settings level The “Date / time“ menu item is highlighted.
Activate the menu item “Date / time“. Display: System time (DD.MM.YYYY HH:MM)
Activate the editing mode for the system time.
DD
Display: Date (
) blinks. Enter date. Confirm date entered.
MM
Display: Month (
) blinks.
8 EB 5571 EN
Page 9
Settings level
Automatic summer time? On
RS-232/Slave RS-485/Master RS-232/Prog Meter bus Universal input type
Back
Settings level
28.11.2005 10:00
RS-232/Slave RS-485/Master RS-232/Prog Meter bus Universal input type
Back
Operation
Enter month. Confirm month entered.
YYYY
Display: Year (
) blinks. Enter year. Confirm year entered.
HH
Display: Time (
) blinks. Enter hour. Confirm hour entered.
MM
Display: Minutes (
) blink. Enter minutes. Confirm minutes entered.
Display: “Automatic summer time? __“ blinks If required, change the current setting (on/off) of the
Automatic summer time function. Activate function: Automatic summer time? On Deactivate function: Automatic summer time? Off Exit the menu item “Date / time“.
Display: Settings level
Settings level
Date / time RS-232/Slave RS-485/Master RS-232/Prog Meter bus Universal input type
Back
Exiting the settings level
Select
Back.
Exit the settings level. Display: Normal display (depending on the application)
Note!
If no key is pressed for two minutes, the PLC automatically returns to the normal display.
EB 5571 EN 9
Page 10
Start-up
2 Start-up
2.1 Programming
Programming the PLC requires a PC with ISaGRAF®software.
®
The ISaGRAF needs of your plant (ISaGRAF
software enables you to program a control system that is tailored to the specific
®
development environment 1400-7621). Programming must fol low the structures and rules stipulated in IEC 61131-3. The PLC may be programmed with the languages defined in the standard: Sequential Function Chart (SFC), Instruction List (IL), Flow Chart (FC), Function Block Diagram (FBD), Ladder Diagram (LD), and Structured Text (ST).
®
There are 128 KB of memory available in the PLC for the ISaGRAF
application.
The application is complied to machine code in the PC environment. This code is then trans ferred to the PLC over the front RJ-45 jack (connecting cable 1400-7620).
Programming languages:
Sequential Function Chart (SFC):
Instruction List (IL): Low-level textual language for logic and arithmetic operations Flow Chart (FC): High-level language used to visualize the data flow Function Block Diagram
(FBD): Ladder Diagram (LD): Simple graphics-based language for logical operations (boolean) Structured Text (ST): High level language similar to PASCAL and C especially designed for
Used to describe operations of a sequential process with a simple gra­phic representation
Graphics-based language for building and combining complex functions (logical, arithmetic)
control applications
For operation and application of the ISaGRAF®environment, refer to the documentation in cluded in the software package. To enable simple and clear programming, ready-made func tions and function blocks, e.g. for boiler systems, heat exchanger sequence control, ventilation systems, heating circuits or domestic hot water systems, are available from SAMSON.
-
-
-
-
Parameters* Station address 255 RS-232/Prog / 1 to 247, 255 Baud rate 9600 RS-232/Prog / 9600, 19200
WE Settings level / Range of values
* –> Section 5.3 (Description of communication parameters to be adjusted)
10 EB 5571 EN
Page 11
Start-up
Note!
In ISaGRAF status or value of the internal variable is written to the associated holding or coil register and can be read or written over Modbus.
Important! The PLC application must be reloaded after a cold start.
®
, internal variables can be assigned (integer or bool) network addresses. The
2.2 Changing PLC settings
PLC settings can only be changed after entering the valid key code. The valid key code can be found on page 42. To avoid unauthorized use, remove the page or
make the key code unreadable. Change PLC settings in the settings level, which contains the following menu items:
Date / time, refer to section 1.4
4
RS-232/Slave, refer to section 5.1
4
RS-485/Master, refer to section 5.2
4
RS-232/Prog, refer to section 2.1
4
Meter bus, refer to section 5.4
4
Universal input type, refer to section 2.3
4
Proceed as follows:
Entering the key code
0000
Activate the editing mode. Display: Entering the key code
0000
blinks
Enter the valid key code.
EB 5571 EN 11
Page 12
Start-up
Settings level
Date / time
RS-232/Slave RS-485/Master RS-232/Prog Meter bus Universal input type
Back
RS-232/Slave
Modbus Slave Modem Baud rate
Back
Settings level
Date / time RS-232/Slave RS-485/Master RS-232/Prog Meter bus Universal input type
Back
Confirm the key code. Display: Settings level The menu item “Date / time“ is highlighted.
Select the menu item in which the settings are to be changed, e.g. “RS-232/Slave“.
Activate the selected menu item. Select the data point which you want to change. Activate the editing mode of the data point.
Display: Data point blinks. Set the data point. Confirm the setting.
Returning to the settings level
Back
Select
to return to the settings level.
Exit the menu item. Display: Settings level
Exiting the settings level
Select
Back
to return.
Exit the settings level. Display: Normal display (depending on the application)
Note!
If no key is pressed for two minutes, the PLC automatically returns to the normal display.
12 EB 5571 EN
Page 13
Start-up
2.3 Configuring universal inputs
There are 17 universal inputs, which may be used as binary inputs, analog inputs (0 to 10 V, 0/4 to 20 mA) or as sensor inputs. The hardware must be configured accordingly (sensor ini tialization).
Refer to page 38 for the resistance values of the PTC, Pt 100 and Pt 1000 sensors. You can also configure each universal input separately.
The following configurations are available: Pt 100/500/1000/2000, Ni 200/1000/2000, PTC, NTC, 1–2 kΩ, BE, 0/4 to 20 mA (with 50Ωparallel resistor) and 0 to 10 V.
Proceed as follows:
-
Entering the key code
0000
Settings level
Date / time
RS-232/Slave RS-485/Master RS-232/Prog Meter bus Universal input type
Back
Universal input type
UE01=PT100↔PT1000
UE02=PT100↔PT1000 UE03=PT100↔PT1000 UE04=PT100↔PT1000 UE05=PT100↔PT1000 UE06=PT100↔PT1000
Back
Activate the editing mode. Display: Entering the key code
0000
blinks
Enter the valid key code. Confirm the key code.
Display: Settings level The “Date / time“ menu item is highlighted.
Select the menu item “Universal input type“. Activate this selected menu item.
The first universal input UE01is highlighted. Select the universal input. Activate the universal input.
UE__
Display:
blinks.
EB 5571 EN 13
Page 14
Manual operation
Select the type of universal input. The inputs are available in the following order: PT100↔PT1000, PT100↔PTC, NI2000, PT2000, PT500, 0 – 10V, BE, 1000 – 2000Ω, PT100, PT1000, NTC, PTC, NI1000, NI200, 4 – 20mA, 0 – 20mA
Note!
On selecting the universal input types PT100 PT100
PTC, this configuration applies then to all 17 uni
PT1000 or
­versal inputs. Any inputs that have a different type need to be configured separately afterwards.
Binary inputs with terminal 10 functioning as GND are slow (delay of approx. 3 s). Binary inputs with terminal 9 functioning as GND are fast (ms).
If a resistance input has been selected:
(PT100↔PT1000, PT100↔PTC, NI2000, PT2000, PT500, PT100, PT1000, NTC, PTC, NI1000 or NI200)
Universal input type
Calibrate? No
UE02=PT100↔PT1000 UE03=PT100↔PT1000 UE04=PT100↔PT1000 UE05=PT100↔PT1000 UE06=PT100↔PT1000
Back
14 EB 5571 EN
Confirm the type of universal input. Display: ”Calibrate? No“ blinks.
If the temperature sensor connected at the input is not to be calibrated:
Exit the universal input.
If the temperature sensor connected at the input is to be calibrated:
Set to “Calibrate? Yes“. Confirm calibration.
Display:
Temperature measured
by the sensor blinks.
Compare the temperature measured by the sensor with the temperature measured by a reference ther mometer installed directly at the point of measure
-
-
ment.
Page 15
If both temperatures are not the same:
Correct the sensor temperature. Confirm corrected temperature.
Appendix
Universal input type
UE12=PT100↔PT1000 UE13=PT100↔PT1000 UE14=PT100↔PT1000 UE15=PT100↔PT1000 UE16=PT100↔PT1000 UE17=PT100↔PT1000
Back
If another type of universal input is selected:
Confirm the universal input type.
Returning to the settings level
Select
Back
to return to the settings level.
Exit the menu item. Display: Settings level
Settings level
Date / time RS-232/Slave RS-485/Master RS-232/Prog Meter bus Universal input type
Back
Exiting the settings level
Select
Back
to return.
Exit the settings level. Display: Normal display (depending on the application)
2.4 Resetting to default values
The values in the settings level can be reset to their default values.
Important!
Resetting to default values causes a application saved in the PLC to be deleted.
Proceed as follows:
1. Cut the power supply to the PLC.
2. Restart the PLC, while pressing down the reset key with a pointed object. “System is being initialized… Cold start values loaded!“ appears briefly on the display before the normal display with the current firmware version (displays on page 5) ap pears.
The values of the setting level are the same as the default values (see section 8.1).
EB 5571 EN 15
-
Page 16
Manual operation
3 Manual operation
All outputs configured in manual operating mode. Refer to the wiring plan (–> section 7).
Note!
If the analog and binary output menus are activated without entering the key code before hand, the key icon appears at the top of the display when you press the enter key to con firm the setting. This setting is locked. You can only change this setting after entering the key code first.
Proceed as follows:
Entering the key code
Activate the editing mode. Display: Entering the key code
0000
0000
blinks Enter the valid key code. Confirm the key code.
Display: Settings level The “Date / time“ menu item is highlighted.
Select
Back
to return.
Exit the editing mode. Display: Normal display (depending on application )
Information level
Analog inputs
Analog outputs Binary inputs Binary outputs Meter bus System info
Back
Switch to the information level. Display: Information level “Analog inputs“ menu item is highlighted.
Select required menu item “Analog outputs” or “Binary outputs”.
Activate the menu item. Select the required output. Activate the selected output.
Display:
AA...orBA...
blinks.
-
-
16 EB 5571 EN
Page 17
Operational faults
Analog output setting: 0 to 10 V
Increase the value. Reduce the value.
Setting with binary outputs: on/off
Binary input = on Binary input = off
Exit the output. Display: indicates manual intervention.
Information level
Analog inputs Analog outputs Binary inputs Binary outputs Meter bus System info
Back
Exiting the information level
Select
Back
to return.
Exit the information level. Display: Normal display (depending on application)
4 Operational faults
Displaying errors in the error status register and sending fault alarms to a mobile phone over the SMS function or to a fax machine can be configured in ISaGRAF tion. The corresponding function blocks exist for this purpose.
®
to match the applica
-
EB 5571 EN 17
Page 18
Communication
5 Communication
5.1 Modbus slave interface
The PLC can communicate with a control system using the RS-232 Modbus slave interface. To gether with the suitable process visualization software and communication software, a com plete control system can be implemented. The following interface settings are possible:
Operation with a dial-up modem on the RS-232 Modbus slave interface Basically, communication is only establishedautomatically when the application has been con figured to dial when a fault occurs. The controller works autonomously. Nevertheless, the mo dem can dial up to the controller at any time to read data from it or change settings, if neces sary. The use of the modem connecting cable (1400-7139) is recommended.
Operation with a leased line modem on the RS-232 Modbus slave interface Communication is established over a permanent connection between two leased line modems. This setup is applied for long-distance transmissions or when different signal level converters are used. The connection between the controller and the modem can also be established over the modem connecting cable (1400-7139).
Operation on a four-wire bus To link the controller and the bus line, the signal level needs to be converted by an appropriate converter (SAMSON cable converter 1400-7308).
-
-
-
-
-
Fig. 1 · Network structure
18 EB 5571 EN
Page 19
Communication
GND TD DTR RTSRDDCD
Fig. 2 · Pin assignment, RJ-12 system bus interface
Modbus slave interface RS-232
The Modbus connection is located on the rear panel of the controller housing (RJ 12 jack). The controller can be connected either directly to the serial interface of a PC (point-to-point connec­tion) or to a (dial-up) modem. A dial-up modem is required if the controller is to be connected to the telecommunications network. In this case, the controller operates autonomously and issues an alarm to the building control station (GLT) when faults occur. In addition, the building control station can dial up to the controller and read data from it.
Parameters* Station address
16-bit addressing? Control system
monitoring Modem Off RS-232/Slave
Cyclical initialization 30 min RS-232/Slave > Modem = On / 1 to 300 min Automatic disconnection 5 min RS-232/Slave > Modem = On / 1 to 300 min Baud rate 9600 RS-232/Slave / 9600, 19200
* –> Section 5.3 (Description of communication parameters to be adjusted)
WE Settings level / Range of values 255
No 30 min
RS-232/Slave > Modbus Slave / 1 to 247, 255 RS-232/Slave > Modbus Slave > Station address / Yes, No RS-232/Slave > Modbus Slave / 1 to 300 min
Modem = On: PLC connected to telecommunications network Modem = Off: PLC directly connected to a computer
EB 5571 EN 19
Page 20
Communication
Modbus slave interface in combination with RS-232/RS-485 cable converters (for four-wire bus)
Operating the PLC in combination with cable converters requires a permanent bus connec
­tion (data cable). The bus line links the devices/control units in an open ring. At the end of the bus line, the data cable is connected to the control station using an RS-485/RS-232 con verter (e.g. TROVIS 5484). The maximum extension (cable length) of the bus line is 1,200 m. A maximum of 32 devices can be connected to such a segment. If you wish to use more than 32 devices or need to bridge greater distances, make sure repeaters (e.g. TROVIS 5482) are installed to replicate the signal. In all, a maximum of 246 devices can be connected to a bus line.
!
Caution!
Make sure that the relevant standards and regulations concerning lightning and overvoltage protection are observed upon installation.
Parameters* Station address
16-bit addressing? Control system
monitoring Modem Off RS-232/Slave / Modem = Off Baud rate 9600 RS-232/Slave / 9600, 19200
* –> Section 5.3 (Description of communication parameters to be adjusted)
WE Settings level / Range of values 255
No 30 min
RS-232/Slave > Modbus Slave / 1 to 247, 255 RS-232/Slave > Modbus Master > Station address / Yes, No RS-232/Slave > Modbus Slave / 1 to 300 min
5.2 Modbus master interface
Modbus instruments can be connected to the PLC using the RS-485 Modbus master interface. The maximum bus line is 1,200 m. If you need to bridge greater distances, make sure repeaters (e.g. TROVIS 5482) are installed to replicate the signal.
Terminals 1 and 2 are used for connection (see Fig. 4).Up to four expansion modules can also be connected in parallel to these terminals. Refer to section 8.4.3 for more details.
-
!
Caution!
Make sure that the relevant standards and regulations concerning lightning and overvoltage protection are observed upon installation.
20 EB 5571 EN
Page 21
Communication
Parameters* Gateway Off RS-485/Master / On, Off Addressing 8 bit RS-485/Master / 8-bit, 16-bit Baud rate 9600 RS-485/Master / 9600, 19200 Frame Off RS-485/Master / On, Off Bias voltage Off RS-485/Master / On, Off Validity 600 s RS-485/Master / 0 to 600 s Pause 0 ms RS-485/Master / 0 to 100 ms Timeout 100 ms RS-485/Master / 100 to 10000 ms Expansion module Broadcast RS-485/Master > Station address / 0 to 255, broadcast
* –> Section 5.3 (Description of communication parameters to be adjusted)
WE Settings level / Range of values
5.3 Description of communication parameters to be adjusted
Station address
This address is used to identify the PLC in bus or modem operation. In a system, each controller needs to be assigned a unique address.
Addressing/16-bit addressing
Selection between 16-bit addressing or 8-bit addressing Select RS-232/Slave menu item (under
16-bit addressing? Yes – 16-bit addressing
4
16-bit addressing? No – 8-bit addressing
4
Station address
):
Baud rate
The baud rate setting refers to the transfer speed between the Modbus instruments.
Control system monitoring
Any intervention made by the control system on dynamic processes are restricted in time, pro vided that communication between the control system and the controller is not established. The controller resets the time monitoring after every valid retrieval of the station address. After the defined maximum time has elapsed, all even bits are reset to “autonomous“.
EB 5571 EN 21
-
Page 22
Communication
Modem
Modem = On:
4
PLC connected to telecommunications network over a modem (RS-232 Modbus slave in terface) Modem = Off:
4
PLC directly connected to a computer (RS-232 Modbus slave interface) and on operating the PLC in combination with cable converters (RS-232/RS-485)
Cyclical initialization
This parameter defines the period of time for a cyclical issue of the initialization command “ATZ“. The command is not issued during dial-up or when connected.
Automatic disconnection
When the controller connects to the building control station but without addressing a Modbus data point, the PLC closes the connection after the time specified for has elapsed.
Gateway
Gateway = On:
4
Any polling by the building control station to the Modbus instruments connected to the PLC is passed directly on to the slaves. Gateway = Off:
4
Any polling by the building control station to the Modbus instruments connected to the PLC is not passed directly on to the slaves.
Automatic disconnection
-
Frame
Frame = On: Framing function activated
4
Frame = Off: Framing function deactivated
4
Bias voltage
We recommend applying a bias voltage on the bus to keep the signal level stable. This bias volt age is usually applied to the bus by the Modbus master.
Bias voltage = On: Bias voltage on the bus
4
Bias voltage = Off: No bias voltage on the bus
4
22 EB 5571 EN
-
Page 23
Communication
Validity
The values saved in the PLC, which have been sent by the slaves, have a time-dependent
Validity
. If the building control station polls the saved data within the valid period of time, the PLC sends the saved data directly to the building control station. However, if the polling to the PLC is outside of this valid time period, the PLC first polls the slaves and then sends these updated data to the building control station.
Pause
Pause
The time entered in responded to the last polling by the PLC.
Timeout
is the time that elapses before the PLC polls a slave after it has
If the slave does not respond to a PLC polling after the time in generated.
Expansion module (1400-9386)
Expansion modules are connected by specifying their station address. This station address can be entered in default state (reset over the jumpers) using the last two figures of the serial num­bers.
Example:
The serial number 600116 means that the station address is 16. This can only be dialed by the broadcast function when one expansion module is connected.
Timeout
has elapsed, an alarm is
5.4 Meter bus interface
Thanks to the meter bus interface, the PLC can communicate with up to 3 heat and water meters according to EN 1434-3. Details onthe useof the different heat and water meters can be found in the technicaldocumen tation TV-SK 6311.
5.4.1 Activating the meter bus
To successfully transfer data from the heat meter (WMZ) to the PLC, the heat meter must use a standardized protocol in accordance with EN 1434-3. It is impossible to make a general state ment about which specific data can be accessed in each meter.For detailson thedifferent meter makes, refer to the technical documentation TV-SK 6311.
-
-
EB 5571 EN 23
Page 24
Communication
Meter bus
WMZ#1: EN1434/Cont. 250
WMZ#2: None WMZ#3: None
Back
Model code [None, P15, PS2, EN1434, CAL3, APAto, SLS]
4
The model code, which needs to be set for the respective heat meter, can be found in TV-SK 6311. In general, the default setting of 1434 can be used for most devices. Reading mode [Coil, Cont, 24h]
4
The meters can be read either automatically approx. every 24 hours (24h), continuously (con) or when the coils (= Modbus data points) assigned to the heat meters WMZ1 to WMZ3 are overwritten with the value 1 over the system bus interface (Coil).
All settings that are made for communication with heat or water meters are stored in Settings level > Meter bus > WMZ#_. Set the parameters in the following sequence: – Model code – Reading mode – Meter bus address
Note!
With reading mode “24h“, the displayed values are not updated by reading the status information again; the values read during the last cycle remain unchanged. With reading mode “con“, the values in the levels are not continuously updated. Reopen the specific level to get current values.
Meter bus address (Addr?) [0 to 255]
4
A meter bus address must be unique and correspond with the address preset in the WMZ. If the preset meter bus address is unknown, a single heat meter connected to the controller can be assigned meter bus address 254. Address 255 deactivates communica tion with the respective heat meter.
-
Parameters
Model code None Meter bus > WMZ#_ /
Reading mode Meter bus > WMZ#_ / Coil, Cont, 24h Meter bus address Meter bus > WMZ#_ / 0 to 255
In theinformation level,“EN1434“ is displayed when the meter bus is activated. Press the enter key toget to the display referring to themeter bus. The following information is displayed about the selected heat meter:
24 EB 5571 EN
WE Settings level / Range of values
None, P15, PS2, EN1434, CAL3, APAto, SLS
Page 25
Communication
WMZ#1 (EN1434)
ID no.: FFFFFFFF
Flow rate: _.___ l/h Total capacity: –.––– m3 Capacity: –.––– kW Energy: –.––– Mwh Flow pipe: – °C
Back
Note!
A blinking icon at the end of the header “WMZ#_ (EN1434)“ indicates an operational fault. Check the heat/water meter connection to the meter bus interface and check the parameters set in the Settings level > Meter bus > WMZ#_.
ID no.
4
Flow rate [l/h]
4
Total capacity [m3]
4
Capacity [kW]
4
Energy [Mwh]
4
Flow pipe [°C]
4
Return flow pipe [°C]
4
Meter bus address
4
Status
4
5.5 Data logging module
Data logging module inserted
L: Data logging
A: wtf_a02 (V90) A: kesf_a01 (V20) F: Firmware (V1.11) F: Firmware (V1.12)
Back
A data logging module (order no. 1400-9378) allows the firmware versions and applications to be saved and loaded in addition to data logging.
The data loggingmodule isconnected to the RJ-45 jack at the front of the controller. The menu shown here *) appears on the display as soon as the data logging module is inserted.
*) The menu items A: … (application) and F: … (firmware) depend on the current firmware and
application of the PLC as well as on the firmware and application saved in the data logging module.
5.5.1 Data logging
The data logging module allows controller data to be saved. Without any additional program ming, the controllersaves thephysical inputs 1 to 7 every minute. When the memory of the data logging module is full, the controller starts to write over the oldest data.
After connecting the data logging module, the “Data logging” menu item must be selected for this function.
EB 5571 EN 25
-
Page 26
Communication
Note!
The Data logging function causes all the data previously saved in the module to be deleted.
The data logging viewer software allows the data to be viewed in graph format. The USB-Con verter 3 (order no. 1400-9377) is required to connect the data logging module to a computer. The data logging viewer software is supplied with the USB-Converter 3.
5.5.2 Saving and loading firmware and applications
On loading (represented by ) a firmware or application, dataare downloadedfrom thedata logging module onto the PLC.
Note!
An application or firmware can only be loaded after the key code has been entered.
4
4
4 4
A: … Downloading an application onto the PLC.
The application in the PLC is overwritten.
F: … Downloading a firmware onto the PLC.
The firmware in the PLC is overwritten.
On saving (represented by ) afirmware or application, data are uploaded from the PLC onto the data logging module.
A: … Uploading a current application onto the data logging module. F: … Uploading the firmware onto the data logging module.
-
26 EB 5571 EN
Page 27
Installation
6 Installation
The controller consists of the housing with the electronics and the back panel with the terminals. It is suitable for panel, wall, and top hat rail mounting (Fig. 3).
Panel mounting
1. Remove both screws (1).
2. Pull apart the controller housing and back panel.
3. Make a cut-out of 138 x 92 mm (width x height) in the control panel.
4. Insert the controller housing through the panel cut-out.
5. Insert one mounting clamp (2) each at the top and bottom or at the sides. Screw the
threaded rod towards the panel with a screwdriver such that the housing is clamped against the control panel.
6. Install the electrical connections at the back of the housing as described in section 7.
7. Fit the controller housing.
8. Fasten both screws (1).
Wall mounting
1. Remove both screws (1).
2. Pull apart the controller housing and back panel.
3. If necessary, bore holes with the specified dimensions in the appropriate places. Fasten
the back panel with four screws.
4. Install the electrical connections at the back of the housing as described in section 7.
5. Fit the controller housing.
6. Fasten both screws (1).
Top hat rail mounting
1. Remove both screws (1).
2. Pull apart the controller housing and the back panel.
3. Fasten the spring-loaded hook (4) at the bottom of the top hat rail (3).
4. Slightly push the controller upwards and pull the upper hook (5) over the top hat rail.
5. Install the electrical connections at the base as described in section 7.
6. Remount the controller housing.
7. Fasten both screws (1).
EB 5571 EN 27
Page 28
Installation
Wall mounting
Panel mounting
57
42
2
Back panel of the controller
1
2
Controller housing
Top hat rail mounting
62
15
5
Dimensions in mm
WxHxD=144x96x111
Fig. 3 · Installation
28 EB 5571 EN
5
4
3
Page 29
Electrical connection
7 Electrical connection
Caution!
For electrical connection of the PLC, you are required to observe the relevant electrotechnical regulations of the country of use as well as the regulations of the local power supplier. Make sure all electrical connections are installed by trained and qualified personnel!
Notes on installing the electrical connections
Install the 230 V power supply lines and the signal lines separately! To increase noise im
4
munity, observe a minimum distance of 10 cm between the lines. Make sure the minimum distance is also observed when the lines are installed in a cabinet. The lines for digital signals (bus lines) and analog signals (sensor lines, analog outputs)
4
must also be installed separately. In plants with a high electromagnetic noise level, we recommend to use shielded cables
4
for the analog signal lines. Ground the shield at one side, either at the control cabinet in­let or outlet, using the largest possible cross-section. Connect the central grounding point and the PE grounding conductor with a cable≥10 mm² using the shortest route. Inductances in the control cabinet, e.g. contactor coils, are to be equipped with suitable
4
interference suppressors (RC elements). Control cabinet elements with high field strength, e.g. transformers or frequency conver-
4
ters, should be shielded with separators providing a good ground connection.
Overvoltage protection
If signal lines are installed outside buildings or over large distances, make sure appro
4
priate surge or overvoltage protection measures are taken. Such measures are indispen sable for bus lines! The shield of signal lines installed outside buildings must have current conducting
4
capacity and be grounded on both sides. Surge diverters must be installed at the control cabinet inlet.
4
Noise suppression
The TROVIS 5571 Controller with SAMSON actuator is interference suppressed according to VDE 0875. If different actuator makes are used, or moreover, further actuators with interfer ence sourcesare usedin a plant, the operator/supplier of a custom-made plant must makesure that the entire plant complies with VDE0875 regulations due to thelegal obligation of ensuring interference suppression.
-
-
-
-
EB 5571 EN 29
Page 30
Electrical connection
Legend
AA Analog output
AE Analog input
BA Binary output
BE Binary input
GND Ground
30 EB 5571 EN
Note!
If the universal inputs are used as
current or voltage inputs, terminal
13 instead of terminal 10 must be
used as ground.
Do not connect terminals 9, 10
and 13!
Meter bus
Supply + 15 V
Fig. 4 · Wiring plan of TROVIS 5571
Page 31
Electrical connection
Connecting the PLC
Open the housing to connect the cables. Make holes in the marked locations at the top, bottom or back of the housing’s back panel and fit suitable grommets or screw joints. Observe the diagram (Fig. 4) for connection. The connection diagram contains all possible in puts and outputs. The assignment of the corresponding inputs and outputs is determined by the respective application.
Inputs
When wiring the universal inputs (BE1/AE1 to BE17/AE17), make sure to use terminal 13 as ground in case of active inputs (current and voltage inputs). If the universal inputs are used as passive inputs (sensors or binary inputs), terminal 10 must be used as ground. Binary inputs with terminal 10 functioning as ground (GND) are slow (a delay of approx. 3 sec onds). Binary inputs with terminal 9 functioning as ground (GND) are fast (ms).
Outputs
The binary low-voltage outputs (BA1 and BA2) are used for signaling. As a result, only a mini­mal load can be applied to these outputs (50 V DC, max. 100 mA ohmic load). If greater loads are to be applied, it is recommended to control relays over theoutputs whichthen switchthe ele­vated load. The 10 binary outputs (BA3 to BA12) can be loaded with max. 250 V AC, 2 A.
Modbus
The control station is connected over a serial RS-232 interface at the back of the controller. Further Modbus instruments (slaves) are connected to the PLC over the RS-485 interface
(terminals 1 and 2).
-
-
Connecting the sensors
Cables with a minimum cross-section of 2 x 0.5 mm² can be connected to the terminals at the back panel of the housing.
EB 5571 EN 31
Page 32
Appendix
8 Appendix
8.1 Settings level
Menu item Functions/parameters Setting range WE
section
Date/time System time (date and time) freely configurable
Automatic summer time On / Off On
See
RS-232/Slave
Modbus slave 5.1
Station address 16-bit addressing
Control system
1 to 247, 255 Yes / No
255
No
1 to 300 min 30 min
monitoring
)
Only with
*
modem = On
Modem Cyclical initialization * Auto. disconnection *
On / Off
)
1 to 300 min
)
1 to 300 min
Off
30 min
5 min
Baud rate 9600, 19200 9600
RS-485/Master Gateway On / Off Off 5.2
Addressing 8 bit, 16 bit 8 bit Baud rate 9600, 19200 9600 Frame On / Off Off Bias voltage On / Off Off Validity 0 to 600 s 0 s Pause 0 to 100 ms 0 ms Timeout 100 to 10000 ms 100 ms Expansion module
Station address 0 to 255 0
RS-232/Prog Station address 1 to 247, 255 255 2.1
Baud rate 9600, 19200 9600
32 EB 5571 EN
Page 33
Appendix
Menu item Functions/parameters Setting range WE
Meter bus WMZ#1 to WMZ#3
Model code
None, P15, PS2, EN1434,
None
CAL3, APAto, SLS
Reading mode Meter bus address
Universal input type UE01 to UE17 PT100↔PT1000
Coil, Cont, 24h 0 to 255
1) 2)
, PT100↔PTC PT2000 0–10V, BE, 1000–2000Ω, PT100 NI1000
1) 2)
, NI20002),
2)
, PT5002),
2)
, NTC2), PTC2),
2)
, NI2002),
PT100 PT1000
4–20mA, 0–20mA
1)
Settling valid for all UE
2)
Calibration? Yes / No
See
section
5.4
2.3
EB 5571 EN 33
Page 34
Appendix
8.2 Technical data
TROVIS 5571 Programmable Logic Controller (PLC)
Universal inputs 17 universal inputs, separately configurable as:
Outputs 10 binary relay outputs,
Interfaces
Modbus slave interface
Optional: Modbus master interface RS-485 for communication with other Modbus instruments (connected
Meter bus Connected over terminals 48/49/50 Programming interface For installing an application created in IsaGraf®(front RJ-45 jack)
Voltage supply 230 V AC, 48 to 62 Hz Power consumption Approx. 8 VA Ambient temperature 0 to 40 °C Storage temperature –20 to 60 °C Degree of protection IP 40 Class of protection II Degree of contamination 2 Overvoltage category II Humidity rating F Noise emission According to EN 61000-6-3 Noise immunity According to EN 61000-6-1 Noise suppression According to DIN VDE 0875 Weight Approx. 0.6 kg
– Resistance input
Pt 100/500/1000, Ni 200/1000/2000, PTC/NTC, 1–2 k
– Current input
0/4 to 20 mA (50Ωparallel resistor) – Voltage input 0–10 V – Binary input, floating
non-floating in pairs, 2 A/250 V AC 2 low-voltage binary outputs, 100 mA/50 V AC 4 analog outputs (0 to 10 V),
non-floating in pairs (max. load > 4.7 kΩ)
RS-232 for modem or point-to-point communication with PC (RJ-12 jack at the back)
Modbus interface RS-485 over cable converter 1400-7308
over terminals 1/2)
and data logging
Ω
34 EB 5571 EN
Page 35
8.3 Special key codes
Description Key codes
Task info 21 Delete PLC application 17 Interface protocols 20 Restart controller 15 Error memory 23
8.4 Expansion modules
8.4.1 Technical data
Extension of the inputs and outputs at the programmable logic controller (PLC)
Inputs
Binary inputs 6 · Optionally can be used as:
Outputs
Binary outputs 4 · 230 V/2 A (relay)
Interfaces Modbus RS-485 Operating voltage 24 V AC Dimensions [mm]
Width 140 Height 93 Depth 30
1)
Note!
The expansion module 1400-9386 (power supply 24 V AC) can be used in conjunction with TROVIS 5571 PLC (power supply 230 V AC) or with TROVIS 5572 Room Controllers (power supply 24 V AC).
A 230 V AC/24 V AC transformer is required for the expansion module when it is used in conjunction with the TROVIS 5571 Programmable Logic Controller!
– 0 to 10 V input (inputs 1, 2, 5, 6) – Pt 1000 input (inputs 3, 4) – 0 to 1000Ωinput (inputs 3, 4) – Counter inputs, max. 1 kHz (inputs 1, 2) – 0 to 10 V outputs (inputs 5, 6)
1)
Appendix
EB 5571 EN 35
Page 36
Appendix
8.4.2 Terminal assignment
1 BA1 Binary output 1 230 V/2 A 2 BA2 Binary output2 230 V/2 A 3 COM1/2 COM binary output 1/2 4 BA3 Binary output 3 230 V/2 A 5 BA4 Binary output 4 230 V/2 A 6 COM3/4 COM binary output 3/4 7 AC1 24V 8 AC2 24V AC 2 has GND reference
Power supply 24 V AC
9 BE1 Binary input 1 or
0 to 10 V input
10 BE2 Binary input 2 or
0 to 10 V input 11 ( GND input 1/2 12 BE3 Binary input 3 or
Pt 1000 or 0 to 1000
Ω
13 BE4 Binary input 4 or
Pt 1000 or 0 to 1000
Ω
14 ( GND input 3/4 15 BE5 Binary input 5 or
0 to 10 V input 16 BE6 Binary input 6 or
0 to 10 V input 17 ( GND input/output 5/6 18 A1 19 B1
RS-485/MODBUS (slave) Connection to TROVIS 5571/5572
20 A2 21 B2
1)
Only with smart expansion module, functioning similar to a basis device
RS-485/MODBUS (master) Connection to expansion module(s)
AC 1
Or counter input
Or counter input
Or 0 to 10 V output
Or 0 to 10 V output
1)
36 EB 5571 EN
Page 37
8.4.3 Integrating the expansion modules
Appendix
A maximum of four expansion modules (1400-9386) can be integrated over the Modbus mas ter interface (Fig. 5)
TROVIS
5571
PLC
Terminals
21
RS-485
RS-232
TROVIS
5576
Module 1
1
RS-485
AB
Module 2
RS-485
1
AB
Module 3
RS-485
1
AB
Module 4
RS-485
1
AB
RS-485
2
AB
Fig. 5 · Integration of expansion modules (1400-9386)
The expansion modules are integrated in the Settings level under the menu item RS-485/Master
-> Expansion module. The following menu appears when an expansion module has been found:
Expansion module
Serial no.: 116 Station address: – –– – E1 = BE E2 = BE E3 = BE E4 = BE
Back
The station address can be assigned (to match the ISaGRAF project) in this menu and the inputs or outputs (0 to 10 V) E1 to E6 of the expansion modules can be configured.
-
®
EB 5571 EN 37
Page 38
Appendix
8.5 Sensor resistance tables
Resistance values with PTC resistors
Type 5224 Outdoor Temperature Sensors, Types 5264 and 5265 Flow and Return Flow Tem perature Sensors, Type 5264 Storage Tank Temperature Sensors
°C –20 –10 0 10 20 25 30 40 50 60 70 80 90 100 110 120
694 757 825 896 971 1010 1050 1132 1219 1309 1402 1500 1601 1706 1815 1925
Ω
Resistance values with Pt 1000 resistors
Type 5227-2 Outdoor Temperature Sensors, Type 5277-2 (thermowell required) and Type 5267-2 (contact sensor) Flow, Return Flow and Storage Tank Temperature Sensors. Type 5257-1, Type 5257-5 (room panel) Room Temperature Sensors.
–35 –30 –25 –20 –15 –10 –5 0 5 10
°C
862.5 882.2 901.9 921.6 941.2 960.9 980.4 1000.0 1019.5 1039.0
Ω
15 20 25 30 35 40 45 50 55 60
°C
1058.5 1077.9 1097.3 1116.7 1136.1 1155.4 1174.7 1194.0 1213.2 1232.4
Ω
65 70 75 80 85 90 95 100 105 110
°C
1251.6 1270.7 1289.8 1308.9 1328.0 1347.0 1366.0 1385.0 1403.9 1422.9
Ω
115 120 125 130 135 140 145 150
°C
1441.7 1460.6 1479.4 1498.2 1517.0 1535.8 1554.5 1573.1
Ω
Resistance values with Pt 100 resistors
-
Refer to the table for Pt 1000 resistors and divide the specified values by 10. Type 5225 Outdoor Temperature Sensors, Types 5204, 5205-46 to -48 Flow and Return Flow
Temperature Sensors, Types 5205-46 to -48 Storage Tank Temperature Sensors, Type 5255 Room Temperature Sensors.
38 EB 5571 EN
Page 39
8.6 Customer data
Station Operator Relevant SAMSON office
Settings
Functions/parameters Setting range Setting Date/time
System time (date and time) freely configurable Automatic summer time On/Off
RS-232/slave
Station address 1 to 247, 255 16-bit addressing Yes/No Control system
monitoring Modem On/Off Cyclical initialization 1 to 300 min Auto. disconnection 1 to 300 min Baud rate 9600, 19200
RS-485/master
Gateway On/Off Addressing 8 bit, 16 bit Baud rate 9600, 19200 Frame On/Off Bias voltage On/Off Validity 0 to 600 s Pause 0 to 100 ms Timeout 100 to 10000 ms Expansion module
Station address 0 to 255, broadcast
1 to 300 min
Appendix
EB 5571 EN 39
Page 40
Appendix
Meter bus WMZ#1 WMZ#2 WMZ#3
Model code None, P15, PS2, EN1434,
Reading mode Coil, cont, 24h Meter bus address 0 to 255
Universal input UE 1234567891011121314151617
PT100↔PT1000 PT100↔PTC NI2000 PT2000 PT500 0–10V BE 1000–2000 PT100 NTC PTC NI1000 NI200 4–20mA 0–20mA
Ω
CAL3, APAto, SLS
40 EB 5571 EN
Page 41

Index

16-bit addressing. . . . . . . . . . . . . . . . . . 22
8-bit addressing. . . . . . . . . . . . . . . . . . . 22
A
Addressing . . . . . . . . . . . . . . . . . . . . . . 22
Application
saving/loading. . . . . . . . . . . . . . . . . 27
Automatic disconnection. . . . . . . . . . . . . 23
B
Baud rate . . . . . . . . . . . . . . . . . . . . . . . 22
Bias voltage. . . . . . . . . . . . . . . . . . . . . . 23
C
Changeover key. . . . . . . . . . . . . . . . . . . . 4
Communication parameters . . . . . . . . . . 22
Configuring inputs . . . . . . . . . . . . . . . . . 13
Connection
PLC . . . . . . . . . . . . . . . . . . . . . . . . . 32
Sensors . . . . . . . . . . . . . . . . . . . . . . 32
Slaves . . . . . . . . . . . . . . . . . . . . . . . 32
Contrast (display). . . . . . . . . . . . . . . . . . . 6
Control system monitoring. . . . . . . . . . . . 22
Controller time . . . . . . . . . . . . . . . . . . . . . 8
Cursor key(s) . . . . . . . . . . . . . . . . . . . . . . 4
Customer data . . . . . . . . . . . . . . . . . . . . 40
Cyclical initialization . . . . . . . . . . . . . . . 23
D
Data logging module . . . . . . . . . . . . . . . 26
data logging . . . . . . . . . . . . . . . . . . 26
saving/loading applications . . . . . . . 27
saving/loading firmware versions . . . 27
Display . . . . . . . . . . . . . . . . . . . . . . . . . . 5
E
Enter key . . . . . . . . . . . . . . . . . . . . . . . . . 4
Expansion module . . . . . . . . . . . . . . . . . 24
integrating . . . . . . . . . . . . . . . . . 21, 38
technical data. . . . . . . . . . . . . . . . . . 36
terminal assignment . . . . . . . . . . . . . 37
Index
F
Firmware version . . . . . . . . . . . . . . . . . . . 5
saving/loading. . . . . . . . . . . . . . . . . 27
Flow Chart. . . . . . . . . . . . . . . . . . . . . . . 10
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Function Block Diagram . . . . . . . . . . . . . 10
G
Gateway . . . . . . . . . . . . . . . . . . . . . . . . 23
I
Information level . . . . . . . . . . . . . . . . . . . 7
Installation
Panel mounting. . . . . . . . . . . . . . . . . 28
Top hat rail mounting . . . . . . . . . . . . 28
Wall mounting . . . . . . . . . . . . . . . . . 28
Instruction List . . . . . . . . . . . . . . . . . . . . 10
Interface
RS-232 (Modbus slave) . . . . . . . 19 - 20
RS-232/RS-485 (Modbus slave) . . . . 21
RS-485 (Modbus master). . . . . . . . . . 21
Internal variable. . . . . . . . . . . . . . . . . . . 11
ISaGRAF . . . . . . . . . . . . . . . . . . . . . . . . 10
L
Ladder Diagram. . . . . . . . . . . . . . . . . . . 10
M
Manual operation . . . . . . . . . . . . . . 16 - 17
Meter bus . . . . . . . . . . . . . . . . . . . . . . . 24
Modbus master interface. . . . . . . . . . . . . 21
Modbus slave interface. . . . . . . . . . . . . . 19
Modem
Dial-up modem . . . . . . . . . . . . . . . . 19
Leased line. . . . . . . . . . . . . . . . . . . . 19
Modem on/off. . . . . . . . . . . . . . . . . . . . 23
N
Noise suppression . . . . . . . . . . . . . . . . . 30
EB 5571 EN 41
Page 42
Index
O
Operating elements . . . . . . . . . . . . . . . . . 4
Operational faults . . . . . . . . . . . . . . . . . 18
Overvoltage protection . . . . . . . . . . . . . . 30
P
Pause . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Plain text display . . . . . . . . . . . . . . . . . . . 5
Programming. . . . . . . . . . . . . . . . . . . . . 10
R
Reset key. . . . . . . . . . . . . . . . . . . . . . . . . 4
Resistance input
Calibration. . . . . . . . . . . . . . . . . . . . 14
S
Sensor resistance values . . . . . . . . . . . . . 39
Sequential Function Chart . . . . . . . . . . . . 10
Station address . . . . . . . . . . . . . . . . . . . 22
Structured Text. . . . . . . . . . . . . . . . . . . . 10
T
Technical data . . . . . . . . . . . . . . . . . . . . 35
Timeout . . . . . . . . . . . . . . . . . . . . . . . . . 24
V
Validity . . . . . . . . . . . . . . . . . . . . . . . . . 24
W
Wiring plan. . . . . . . . . . . . . . . . . . . . . . 31
42 EB 5571 EN
Key code 1732
Page 43
EB 5571 EN 43
Page 44
Operating level
(created application)
Entering the key code
Information level
Analog inputs
Analog outputs Binary inputs Binary outputs Meter bus System info
Back
0000
XXXX
Settings level
Date / time
RS-232/Slave RS-485/Master RS-232/Prog Meter bus Universal input type
Back
0000
Contrast
Back
BackBack
Back
Normal display
(depending on application)
SAMSON AG · MESS- UND REGELTECHNIK Weismüllerstraße 3 · 60314 Frankfurt am Main Telefon: 069 4009-0 · Telefax: 069 4009-1507 Internet: http://www.samson.de
EB 5571 EN
2009-03