Samson TROVIS 5400, TROVIS 5482 Mounting And Operating Instructions

Automation System TROVIS 5400 Repeater TROVIS 5482
Mounting and operating instructions
EB 5409-1 EN
Edition December 2000
Application
Contents
Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Principle of operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Opening the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1 Application
The TROVIS 5482 Repeater is used in a RS-485 bus system to increase the line length by 1200 m.
CAUTION!
Assembly, start-up and operation of the device may only be performed by trained and experienced personnel familiar with this product.
It can also be used to convert data for a 4-wire bus system into data for a 2-wire bus system.
2 EB 5409-1 EN
2 Principle of operation
Principle of operation
The device is equipped with two interfaces, X1 and X2, which are electrically isolated from each other as well as from the PE connection. Four LEDs are located on the front side of the device. When they are illuminated or blink, the following conditions are signalled:
Power on X1 sending data X1 receiving data X2 recognizes that transmitter is active
(DCD) There is a series of jumpers on the printed circuit board inside the device which allows the repeater to be adapted to the require­ments of a RS-485 bus system. Fig. 1 illustra­tes the position of the jumpers. The casing can be opened as described in section 3. The following functions can be selected or set (for the exact jumper settings and the default po­sitions refer to Tables 1 to 6):
Selecting a 2-wire or 4-wire system
Depending on the bus system used, a 2-wire or 4-wire system must be selected for each interface (see Table 1).
Controlling the transmitter for interface X2
A signal level detector is located at both in terfaces. It recognizes whenever a bus station sends data (transmitter activated). In the 2-wire system, it controls the switching bet ween sending and receiving data. The signal level detector can be disabled. In that case, sending and receiving are switched over by the data itself (see Table 3). An adjustment of the transmission rate is not necessary.
Blocking duration of the transmitter
In the 2-wire system, one interface is blocked whenever the other interface sends data. Jumpers X16 and X17 allow the duration of the blocking to be changed, should commu­nication problems occur (see Table 4).
Increasing the duration of the transmitters switching signal for X2
In order to prevent reflections in the lines of the 2-wire system, the transmitters switching signal can be lengthened.This is only possi ble for the interface X2 (see Table 5).
-
-
-
Bus termination of interfaces
The bus can be terminated both at interface X1 and at X2 by positioning the jumpers X6, X7 and X11, X12 as shown in Table 2.
Grounding the interfaces
If necessary for older devices, it is possible to ground the interfaces X1 or X2 by changing the position of the jumper X5 as described in Table 6.
EB 5409-1 EN 3
Loading...
+ 5 hidden pages