Automation System 5400
Boiler Controller
TROVIS 5474
Electronics from SAMSON
Mounting and
Operating Instructions
EB 5474 EN
®
Firmware version 2.0x
Edition July 2004
Page 2
Disclaimer of liability
Disclaimer of liability
We areconstantly developing our products and therefore, reservethe right to change the prod
uct or the information contained in this document at any time without notice.
We do not assume any liability for the accuracy or completeness of these mounting and
operating instructions. Moreover, we do not guaranteethat thebuyer can use the product for an
intended purpose. SAMSON rejects any liability for claims by the buyer, especially claims for
compensation including lost profits or any other financial loss, except the damage was caused
intentionally or by gross negligence. If an essential term of the contract is breached by
negligence, SAMSON’s liability is limited to the foreseeable damage.
Safety instructions
The device may only be assembled, started up or operated by trained and
4
experienced personnel familiar with the product. Proper shipping and
appropriate storage are assumed.
The controller has been designed for use in electrical power systems. For
4
wiring and maintenance, you are required to observe the relevant safety
regulations.
The Safety shutdown function (section 8.10) does not replace the safety tem-
4
perature limiter as the boiler controller is not a safety-relevant component.
The controller is ready for use with the temperatures and time schedules preset by the manufac
turer.
On start-up, the current time and date need to be set at the controller (–> section 1.5).
1.1Operating elements
The operating controls are located in the front panel of the controller and protected by a Plexi
glas door.
1.1.1 Operating keys
Changeover key
(press using a pointed object such as a pen)
Switch from the info level to the parameter and configuration level and back
Reset key
(press using a pointed object such as a pen)
Press to reset accessible parameters to their default settings; the controller
must be in the configuration level
Arrow keys
– To scroll within levels
– To change values
Enter key
– To access levels
– Access parameters and functions to edit them
– Confirm settings
– Display set points in the info level
-
-
6 EB 5474 EN
Page 7
1.1.2 Operating switches
Mode selector switch
Selector switch
2
1
11
22O12
Operation
Automatic mode with switchover between
day mode and night mode
Automatic mode with switchover between
day mode and stand-by mode
Day mode (rated operation)
Night mode (reduced operation)
Manual/maintenance mode
Stand-by mode
Boiler 1 and 2 in operation;
automatic lag/lead sequence change
Boiler 1 in operation,
Boiler 2 switched off
Boiler 2 in operation,
Boiler 1 switched off
Boiler 1 and 2 switched off
Boiler 1 and 2 in operation;
Boiler 2 as lead boiler
Boiler 1 and 2 in operation;
Boiler 1 as lead boiler
EB 5474 EN 7
Page 8
Operation
Correction switch for the flow temperature
Set point set-back by 2.5 °C per notch
No change in set point
Set point raised by 2.5 °C per notch
+
0
1.2Operating modes
Day mode (rated operation)
Regardless ofthe programmed times-of-use and summer mode,the set points relevant for rated
operation are used by the controller.
Night mode (reduced operation)
Regardless of the programmed times-of-use and summer mode, the set points relevant for reduced operation are used by the controller.
Stand-by mode
The controller is switched off. The boilers only work when there is a demand for DHW or a demand for an external set point. The protective functions remain active.
Automatic mode
During the programmed times-of-use, the controller works in rated operation. Outside these
times-of-use, the controller is in reduced operation or stand-by mode, depending on the set
tings. The controller switches automatically between both operating modes.
Maintenance mode
Pumps are controlled manually (–> section 3).
Control is not possible. Use the maintenancemode just for maintenance purposes and for emis
sion measurements.
The default setting of the circulation pumps is set for constant operation.
-
-
8 EB 5474 EN
Page 9
1.3Display
Operation
During operation, the display indicates the current time as well as informationabout the opera
tion of the controller. The times-of-use are represented by black squares below the row of num
bers at the top of the display. Icons indicate the operating status of the controller.
mode
9 Malfunction
10 Boiler and boiler stages
11 Valve in control circuit 1
Open: Left arrow
Closed: Right arrow
12 Boiler pump 1 ON
1211 1314
1617181920
15
1
1112131415
2122
24
23
2
13 Valve in control circuit 2
Open: Left arrow
Closed: Right arrow
14 Boiler pump 2 ON
15 DHW heating
-
-
Fig. 1 · Icons
The controller status can be displayed in the operating level (–> section 1.4).
EB 5474 EN 9
Page 10
Operation
1.4Displaying data
Controller time, measured values, set points and limits, times-of-use, public holidays and vaca
tion periods can be retrieved and displayed in th
131). The various levels are listed in section 13.3.
InF1: Boiler 1
4
InF2: System Anl 1 to 3, Co5 -> Fb13 = ON: Separate heating circuit
4
4
4
4
4
4
Proceed as follows:
System Anl 4 to 7: Boiler 2
InF3: System Anl 1 to 3, Co5 -> Fb13 = ON: Direct heating circuit
InF4: DHW heating
InF5: General information, e.g. times-of-use
InF8: Error initialization
InF9: Modbus and meter bus communication
Select info level.
Open info level.
Scroll to read the various datapoints of the selected info level that appear one after
the other.
Compare the set point/limit with the actual value.
Press both arrows keys simultaneously:
Return to the display with time.
e InF1toInF9
info levels (-> Fig. 10 on page
-
10 EB 5474 EN
Page 11
Operation
1.5Setting the controller time
The current time and date need to be set immediately after start-up and after a power failure
lasting longer than 24 hours. This is indicated by the time blinking on the display.
PA5
The time is set in the
Proceed as follows:
9876543210
parameter level.
242322212019181716151413121110
Switch to the configuration and parameter level.
Display:
PA1
9876543210
1
9876543210
242322212019181716151413121110
242322212019181716151413121110
Select PA5 parameter level.
Open PA5 parameter level.
Display: Time
Activate editing mode for the controller time.
blinks.
Change time.
9876543210
242322212019181716151413121110
Confirm time.
Display: Date (Day-Month)
Activate editing mode for the date.
blinks.
Change date.
EB 5474 EN 11
Page 12
Operation
9876543210
242322212019181716151413121110
Confirm date.
Display: Year
Activate editing mode for the controller time.
blinks.
Change year.
Confirm year.
Exit PA5 parameter level.
Return to the operating level.
Note!
The controller automatically returns to the operating level if the keys are left unpressed for two
minutes.
12 EB 5474 EN
Page 13
Operation
1.6Setting the times-of-use
Two times-of-use can be set for each day of the week. If only one time-of-use is required, the
start and stop times of the second time-of-use must be programmed to identical times.
Parameters
Period/day1–7PA5 / 1–7, 1 to 7
Start first time-of-use7:00 PA5 / 00:00 to 24:00h; in steps of 30 minutes
Stop first time-of-use12:00 PA5 / 00:00 to 24:00h; in steps of 30 minutes
Start second time-of-use12:00 PA5 / 00:00 to 24:00h; in steps of 30 minutes
Stop second time-of-use22:00 PA5 / 00:00 to 24:00h; in steps of 30 minutes
Proceed as follows:
9876543210
242322212019181716151413121110
WEParameter level / Range of values
Switch to the configuration and parameter level.
Display:
PA1
Select PA5 parameter level.
Open PA5 parameter level.
Display: Controller time
9876543210
9876543210
242322212019181716151413121110
242322212019181716151413121110
Select datapoint for times-of-use.
Display:
1
Activate editing mode for times-of-use.
Display: 1–7
Select period/day for which the times-of-use are to be
valid:
1–7 = Monday to Sunday,
1 = Monday, 2 = Tuesday, …, 7 = Sunday
EB 5474 EN 13
Page 14
Operation
9876543210
START
242322212019181716151413121110
Activate editing mode for period/day.
Display: START;blinks.
Edit start time (steps of 30 minutes).
9876543210
STOP
242322212019181716151413121110
Confirm start time.
Display:
STOP
Edit stop time (steps of 30 minutes).
Confirm stop time.
Display:
START
The second time-of-use is set like the first time-of-use.
To set the times-of-use for each day, repeat the instructions in the fields highlighted in gray.
Select
End
on the display.
Exit the datapoint for times-of-use.
Exit the parameter level.
Return to the operating level.
Note!
Do notuse the 1–7 menu to check the programmed times-of-use. On openingthis menu, the ti
mes-of-use are reset to their default settings.
-
Note!
The controller automatically returns to the operating level if the keys are left unpressed for two
minutes.
14 EB 5474 EN
Page 15
Operation
1.6.1 Entering vacation periods
When the switch position Automatic operation with switchover between day mode and night
mode is selected, night set points (reduced set points) are used by the controller. When the
switch position Automatic operation with switchover between day mode and stand-by mode
is selected, the system is switched off. The frost protection function remains active.
A maximum of 10 vacation periods may be entered.
Parameter
Vacation periods–PA5 / 01.01 to 31.12
Proceed as follows:Switch to the parameter and configuration level.
9876543210
242322212019181716151413121110
To enter additional vacations, re-select
in the fields highlighted in gray.
Exit the parameter level.
Return to the operating level.
WEParameter level / Range of value
Display:
PA1
Select PA5 parameter level.
Open PA5 parameter level. Display: Controller time
Select datapoint for vacation period. Display:
Open data point for vacation period. Display:
If applicable, select
– – – –
.
START
Activate editing mode for vacation periods.
blinks.
Set start date of vacation period.
Confirm start date of the vacation period.
Display:
STOP
Set end of vacation period.
Confirm end of the vacation period.
––––
(between 31.12 and 01.01) and repeat the steps
Note!
In systems Anl 1 to 3 with integrated DHW heating (Co5 -> Fb13 = ON), the vacations entered
also apply to the DHW heating with the setting Co4 -> Fb10 = ON.
EB 5474 EN 15
Page 16
Operation
Vacation periods that are not assigned to a specific date should be deleted by the end of the
year so that they are not carried on into the following year.
Deleting vacation periods:
Select the vacation period you wish to delete in the datapoint for vacation periods.
Confirm selection.
Select
– – – –
.
Delete vacation period.
Note!
The controller automatically returns to the operating level if the keys are left unpressed for two
minutes.
1.6.2 Entering public holidays
The times-of-use programmed for Sunday apply on public holidays. A maximum of 20 public
holidays can be entered.
Parameter
Public holidays–PA5 / 01.01 to 31.12
WEParameter level / Range of value
Proceed as follows:Switch to the parameter and configuration level.
Display:
PA1
Select PA5 parameter level.
Open PA5 parameter level. Display: Controller time
8
56
4
0
123
9
1211 1314
10
7
1617181920
15
2122
24
23
Select datapoint for public holidays.
Display:
Open datapoint for public holidays.
Display:
If applicable, select
START
– – – –
.
Activate editing mode for public holiday.
blinks.
Edit public holiday.
Confirm public holiday.
16 EB 5474 EN
Page 17
Operation
To enter additional public holidays, re-select
––––
(between 31.12 and 01.01) and repeat the
steps in the fields highlighted in gray.
Exit the parameter level.
Return to the operating level.
Note!
In systems Anl 1 to 3 with integrated DHW heating (Co5 ->Fb13 =ON), thepublic holidaysen
tered also apply to the DHW heating with the setting Co4 -> Fb10 = ON.
Public holidays that are not assigned to a specific date should be deleted by the end of the year
so that they are not carried on into the following year.
Deleting a public holiday:
Select the holiday you wish to delete in the datapoint for public holidays.
Confirm selection.
– – – –
Select
.
Delete the public holiday.
Note!
The controller automatically returns to the operating level if the keys are left unpressed for two
minutes.
-
EB 5474 EN 17
Page 18
Start-up
2Start-up
2.1Setting the system code number and the boiler rating
7 different hydraulic schematics are available. Each system configuration is represented by a
system code number (Anl). The different schematics are dealt with in section 4. Available con
troller functions are described in sections 5 to 8.
Changing the system code number resets previously adjusted function blocks to their default set
tings (WE). Function block parameters and settingsin theparameter level remain unchanged.
The system code number is set in the parameter and configuration level.
Proceed as follows:
Switch to the parameter and configuration level.
level.
level.
1
Anl 1
PA1
Display shows:
Select
Anl
Open
Anl
Display:
Select system code number (Anl).
-
-
System Anl 1
System Anl 2
System Anl 3
System Anl 4
System Anl 5
System Anl 6
System Anl 7
1
Anl 1
1
Anl 2
2
1
Anl 3
2
1
1
2
Anl 4
1
1
2
1
2
Anl 5
2
1
1
2
2
Anl 6
1
1
2
2
Anl 7
Confirm system code number (Anl).
The burner and stage icons for burner 1 blink.
The boiler rating is shown.
18 EB 5474 EN
Single boiler for one-stage burner
Single boiler for two-stage burner
Single boiler for modulating burner
Double boiler for one-stage condensing boiler and
two-stage low-temperature boiler
Double boiler for 2 two-stage burners
Double boiler for modulating and two-stage burner
Double boiler for two modulating burners
Page 19
Start-up
Set the required rating.
Set first the capacity of the basic stage and then the total capacity of the burner of
two-stage and modulating burners.
Confirm the rating.
Set the capacity of the second burner in systems Anl 4 to 7.
End
Select
Exit the
Display:
on the display.
Anl
level.
Co1
2.2Activating and deactivating functions
A function is activated or deactivated in the associated function block. The numbers 0 to 24 in
the top row of the display represent the respective function block numbers. When a configura
tion level is opened, the activated function blocks are indicated by a black square on the
right-hand side below the function block number. The function blocks are described in section 13.2.
The functions are arranged in topic groups:
Co1: Boiler 1
4
Co2: Systems Anl 1 to 3, Co5 -> Fb13 = ON: separate heating circuit
4
Systems Anl 4 to 7: Boiler 2
Co3: Systems Anl 1 to 3, Co5 -> Fb13 = ON: direct heating circuit
4
Co4: DHW heating
4
Co5: General functions
4
Co6: Sensor initialization
4
Co8: Error initialization
4
Co9: Modbus and meter bus communication
4
-
Proceed as follows:
Switch to the parameter and configuration level.
Display shows:
Switch to the configuration level (-> Fig. 10, page 131).
Open the configuration level.
PA1
EB 5474 EN 19
Page 20
Start-up
Select function block.
Activate editing mode for function block.
The function block number starts to blink.
0 0 0 0
If
section 2.4).
Activate function block (Fb = ON).
An activated function block is indicated by a black square below (right) the function
block number in the top row of the controller display.
or:
Deactivate function block (Fb = OFF).
Confirm setting.
If the function block is not closed, further function block parameters can be adjusted.
Proceed as follows:
Make the desired changes and confirm.
If applicable, the next function block parameter is displayed.
Confirm all parameters to exit the opened function block.
To adjust additional function blocks within the configuration level, repeat the steps in the fields
highlighted in gray.
Exit the configuration level.
Return to the operating level.
appears on the display, the key number needs to be entered first (refer to
Note!
The controller automatically returns to the operating level if the keys are left unpressed for two
minutes.
20 EB 5474 EN
Page 21
2.3Changing parameters
Start-up
Depending on the activated functions, not all parameters listed in the parameter list in the Ap
pendix (–> section 13.2) might be available.
The parameters are arranged in topic groups:
PA1: Boiler 1
4
PA2: Systems Anl 1 to 3, Co5 -> Fb13 = ON: separate heating circuit
4
4
4
4
4
Proceed as follows:
To adjust additional parameters, repeat the steps in the fields highlighted in gray.
Systems Anl 4 to 7: Boiler 2
PA3: Systems Anl 1 to 3, Co5 -> Fb13 = ON: direct heating circuit
PA4: DHW heating
PA5: General parameters
PA9: Modbus and meter bus communication
Switch to the parameter and configuration level. Display:
Select parameter level (-> Fig. 10, page 131).
Open the parameter level.
Select parameter.
Activate editing mode for parameter.
Change parameter.
Confirm parameter setting.
Exit the parameter level.
Return to the operating level.
PA1
-
Note!
The controller automatically returns to the operating level if the keys are left unpressed for two
minutes.
EB 5474 EN 21
Page 22
Start-up
2.4Enter key number
Some functions are protected against unintentional or unauthorized access. These functions can
only be activated or deactivated after the valid key number has been entered. The valid key
number for initial start-up can be found on page 127. To avoid unauthorized use of the key
number, remove the page or make the key number unreadable.
Proceed as follows:
0 0 0 0
The key number remains active for approx. 10 minutes.
blinks on the display.
Set valid key number.
Confirm key number.
When the correct key number is entered, the function block to be changed blinks on the
display.
When an incorrect key number is entered, the controller returns to the next configuration
level.
2.5Calibrating sensors
The connected sensors are calibrated in the Co6 configuration level. The following applies:
The resistance values of the sensors can be found on page 115.
Each universal input can be configured separately.
The function block parameter includes the following types: Ni 200/1000, PTC, NTC,
Pt 100/1000, (0/4 to 20) mA. The function blocks Co6 -> Fb01 to Fb17 correspond to the bi
nary inputs BE1 to BE17 in the terminal wiring plan (–> page 78 onwards).
Activate the function block for the required sensor and select the function block parameter
which matches the type of the input signal.
Note!
Pt 100 orPt 1000 sensor should be used to measure theflow temperature as only these types of
sensor are able to measure temperatures reaching up to 160 °C (maximum temperature of the
flow temperature set point).
-
22 EB 5474 EN
Page 23
Start-up
If the temperature values displayed at the controller differ from the actual temperatures, the
measured values of all connected sensors can be changed or readjusted. To calibrate a sensor,
the currently displayed sensor value must be changed such that it matches the temperature (ref
erence temperature) measured directly at the point of measurement.
Perform the calibration in function block Fb23 in Co6.
Proceed as follows:
Switch to the parameter and configuration level.
Display:
PA1
Select Co6 configuration level.
Open Co6 configuration level.
Select function block Fb23.
Confirm setting.
Display:
0 0 0 0
Enter currently valid key number.
The function block Fb23 blinks on the display.
Activate function block.
Confirm setting.
Select the function block for the sensor to be calibrated:
The function blocks Co6 -> Fb01 to Fb17 correspond to the binary inputs BE1 to BE17
in the terminal wiring plan (–> page 78 onwards) depending on the selected system
code number (Anl), e.g. Co6 -> Fb03 for sensor VFg (all systems).
Activate editing mode for sensor.
Fb_ blinks on the display.
Display measured temperature.
Activate editing mode for measured temperature.
Measured temperature blinks.
Correct measured temperature.
Read the actual temperature directly from the thermometer at the point of measure
-
ment and enter this value as the reference temperature.
Confirm corrected measured temperature.
Additional sensors are calibrated similarly.
-
EB 5474 EN 23
Page 24
Start-up
Select function block Fb23.
Activate editing mode for function block Fb23.
Deactivate function block Fb23.
Confirm setting.
Select
End
on the display.
Exit the configuration level.
Return to the operating level.
Note!
The adjusted sensor values are not reset by the function for resetting to default values.
2.6Resetting to default values
All parametersand function blocks that can be setwithout entering the key number can bereset
to their default settings (WE).
Proceed as follows:
Reset to default settings.
Function blocks and parameters are reset to their default settings (WE).
Note!
Resetting protected parameters to their default settings is only possible when the key number is
still active.
The controller isready foroperation with its default settings. You just need to set the correctdate
and current time.
24 EB 5474 EN
Page 25
Manual operation
3Manual operation
All the settings of the outputs canbe setin the manual mode, see wiring plan(-> section12).
Proceed as follows:Set mode selector switch to.
After approx. 10 seconds the boilers start operation at
full capacity. Display:
HAnd
9876543210
242322212019181716151413121110
Select
Open the manual level. Display:
Select output:
bA: 1, 2BA1 and BA2
3-Pt: 1, 2BA3 and BA4, BA5 and BA6
1
PU: 1, 2BA7 and BA8
StUF: 1, 2, 3, 4 BA9 to BA12
AnAL: 1, 2AA 1, 2 (RK1, RK2)
Activate editing mode for output.
The display blinks.
Activate output, increase value.
Three-point stepping output: OPEN
or:
Deactivate output, decrease value.
Three-point stepping output: CLOSED
and:
Three-point stepping output: STOP
Confirm setting.
The changed values remain valid as long as the manual
mode is active.
Slide mode switch to.
Exit the manual level.
on the display.
bA1
Note!
In manual mode, frost protection does not function.
EB 5474 EN 25
Page 26
Systems
4Systems
7 hydraulic schematics are available.
System code
number (Anl)
1
2
3
4
5Double boiler for 2 two-stage burnersChange in lag/lead sequence either
6Double boiler for modulating und
7Double boiler for two modulating
System descriptionComments
Single boiler for one-stage burner
Single boiler for two-stage burner
Single boiler for modulating burner
Double boiler for one-stage condensing boiler
and two-stage low-temperature boiler
two-stage burners
burners
Optionally separate heating circuit
and DHW heating can be controlled
Lag sequence without automatic
lag/lead sequence change
depending on operating hours, on
outdoor temperature or boiler
capacity
Lag sequence without automatic
lag/lead sequence change
Change in lag/lead sequence either
depending on operating hours, on
outdoor temperature or boiler
capacity
26 EB 5474 EN
Page 27
System Anl 1 with Co5 -> Fb13 = OFF
RK1
RüFg
Systems
VFg
AF
VL
RL
KF1
RüF1
1
Pu1
System Anl 1 with Co5 -> Fb13 = ON
VF2
Pu2
RK2
VFg
RK1
KF1
RüF1
1
Pu1
RüFg
RüF2
K1 One-stage burner
Pu3
SLP
RF
SF1
SF2
AF
K1 One-stage burner
EB 5474 EN 27
Page 28
Systems
System Anl 2 with Co5 -> Fb13 = OFF
KF1
RüF1
1
2
System Anl 2 with Co5 -> Fb13 = ON
VF2
Pu2
RK2
VFg
Pu1
RK1
RüF2
RüFg
VFg
K1 Two-stage burner
RF
Pu3
AF
VL
RL
AF
28 EB 5474 EN
KF1
RüFg
RK1
Pu1
RüF1
1
2
SLP
SF1
SF2
K1 Two-stage burner
Page 29
System Anl 3 with Co5 -> Fb13 = OFF
Systems
KF1
RüF1
System Anl 3 with Co5 -> Fb13 = ON
VF2
Pu2
RK2
VFg
Pu1
RK1
RüF2
VFg
RüFg
K1 Modulating burner
Pu3
AF
VL
RL
RF
AF
KF1
RüF1
RK1
Pu1
RüFg
SLP
SF1
SF2
K1 Modulating burner
EB 5474 EN 29
Page 30
Systems
System Anl 4
System Anl 5
KF1
VFg
RüFg
RK1RK2
Pu1Pu2
1
RüF1
KF2
1
2
RüF2
K1 One-stage condensing boiler
VL
RL
AF
K2 Two-stage low-temperature boiler
VFg
RüFg
VL
RL
AF
30 EB 5474 EN
KF1
RK1RK2
Pu1Pu2
1
2
RüF1
KF2
1
2
RüF2
K1, K2 Two-stage burner
Page 31
System Anl 6
Systems
KF1
System Anl 7
RK1RK2
Pu1Pu2
RüF1
KF2
1
2
RüF2
RüFg
K1 Modulating burner
K2 Two-stage burner
RüFg
VFg
VFg
VL
RL
VL
RL
AF
AF
KF1
RK1RK2
Pu1Pu2
RüF1
KF2
RüF2
K1, K2 Modulating burner
EB 5474 EN 31
Page 32
Boiler functions
5Boiler functions
5.1Boiler switching behavior
The
Minimum activation and deactivation time
ters described in following.
To be able to keep the cooling off periods between two activation phases, a boiler is first
switched on when the time entered in
Minimum deactivation time
activation.
To ensurethe burning of residues left over during the start-upphase, a boiler is switched off first
after the time entered in
Parameters
Minimum activation time1 minPA1, PA2* / 0 to 90 min
Minimum deactivation time2 minPA1, PA2* / 0 to 90 min
Minimum activation time
On/off boiler
A boiler is activated when the flow temperature falls below the flow temperature set point by
Hysteresis
the
Lockout time
the
(Fig. 3). After the operational feedback message (burner firing –> section 5.10),
must elapse before the boiler is switched to the next stage. If the flow temperature is expected toreach theset pointrange withinthe
to the next stage.
A boiler stage is switched off when the flow temperature exceeds theflow temperature set point
by the
Hysteresis
.
Modulating boiler
A boiler starts to operate with its minimum capacity if the flow temperature falls below the flow
temperature set point by the
firing –>section 5.10), the
Hysteresis
Lockout time
(Fig. 2). After the operational feedback message (burner
troller modulates the boiler capacity to match the actual energy requirement according to the
flow temperature set point.
parameters have priority over allother parame
has passed since the last de
has elapsed.
WEParameter level / Range of values
* Only in systems Anl 4 to 7
Tolerance time
, the boiler doesnot switch
must elapsebefore the modulation is enabled. The con
-
-
-
Parameters
Hysteresis3 °CPA5 / 1 to 20 °C
Tolerance time30 min PA5 / 0 to 99 min
Lockout time2 minPA5 / 0 to 99 min
WEParameter level / Range of values
32 EB 5474 EN
Page 33
Flow temperature set point +
Hysteresis
Boiler functions
t
[°C]
VL
Flow temperature set point
Flow temperature set point –
Hysteresis
Burner start
Activation of
boiler stage
Fig. 3 · Criteria for switching the boiler stages
tVL[°C]
Flow temperature set point +
Hysteresis
Flow temperature set point
Flow temperature set point –
Hysteresis
Lockout time
Operational alarm
f. burner
t [s]
Tolerance time
t [s]
Burner start
Activation of
boiler stage
Lockout time
Operational alarm
f. burner
Fig. 2 · Criteria for switching the modulating boiler
Tolerance time
EB 5474 EN 33
Page 34
Boiler functions
5.2Lag/lead sequence control
The boilers are released depending on the configuration:
Co1, Co2* -> Fb00 = OFF: Boiler released according to the position of the mode selector
4
switch
Co1, Co2* -> Fb00 = ON: Boiler 1 is not released if binary input BE17 is closed, pro
4
vided Boiler 1 is not locked by the mode switch.
Boiler 2* is released if binary input BE16 is closed, provided Boiler 2 is not locked by the
mode switch.
Function
Release of boiler K1, 2OFFCo1, Co2* -> Fb00
WEConfiguration
* Only in systems Anl 4 to 7
5.2.1 Control without sensor VFg
The Burner activation independent from sensor VFg function allows the boiler to be switched
on independently from sensor VFg, i.e. exclusively according to boiler sensors VF1 and VF2.
Other functions which have an effect on the lag and lead sequence control of the boiler in
two-boiler systems do not affect the boiler which works independently any more.
On activating the Continuous running of pump function, the boiler pumps react like the pumps
of master controller in normal systems.
Functions
Burner activation not dependent on
sensor VFg
Continuous running of pumpOFFCo5 -> Fb14
WEConfiguration
OFFCo5 -> Fb20 = ON
-
5.2.2 Outdoor temperature-dependent sequence
If the outdoor temperature is above the limit entered in
just the lead boiler always remains in operation. The lag boiler is not even activated when the
maximum capacity of the lead boiler is insufficient to achieve an increased flow temperature.
The lag boiler is first released when the outdoor temperature is lower than the limit entered in
Temperature tAfor releasing sequence
The limit entered in
short-term demand above the limit can be compensated for without any loss in comfort by pro
longing the operating time of the lead boiler. This depends on the performance of the lead
boiler.
34 EB 5474 EN
Temperature tAfor releasing sequence
after t = 2 x
Temperature tAfor releasing sequence,
Lockout time
.
must be selected to ensure that a
-
Page 35
Boiler functions
Function
Releasing sequenceONCo5 -> Fb07 = ON
Parameters
Lockout time2 minPA5 / 0 to 99 min
Temperature tAfor releasing sequence12 °CPA5 / –40 to 50 °C
WEConfiguration
WEParameter level / Range of values
5.2.3 Capacity-dependent sequence
The lead boiler is activated when theflow temperaturefalls belowthe flowtemperature setpoint
Hysteresis
by the
the second stage. The second boiler is also activated if 90 % of its maximum load is not sufficient
over thetime period oft=2x
temperature set point and the set point hysteresis is not reached within the tolerance time.
The lag boiler is switched off when one of the following conditions is fulfilled:
The current load of both boilers is less than 90 %.
4
The actualtemperature is greater than the set point and hysteresis added together as wellas
4
its tendency shows that the temperature willnot fallbelow this total within the tolerance time.
Function
Releasing sequenceONCo5 -> Fb07 = OFF
Parameter
Lockout time2 minPA5 / 0 to 99 min
. In the event of a demand for increased capacity, the lead boiler switches to
Lockout time
to increasethe flow temperature to therequired flow
WEConfiguration
WEParameter level / Range of values
5.2.4 Sequence lock
The binary input BE11 is used to lock the sequence. The input of the outdoor temperature is de
termined by the binary input. The outdoor sensor is not required.
Function
Outdoor sensorONCo5 -> Fb00 = OFF, select: FoAUS
WEConfiguration
5.2.5 Lag delay
The
Lag delay
mands. The second boiler is first switched on when required after the time in
elapsed. The time countdown is shown in the InF5 level.
parameter helps minimize losses during start-up in the event of short-term de
Lag delay
EB 5474 EN 35
has
-
-
Page 36
Boiler functions
Parameter
Lag delay10 min PA5 / 0 to 90 min
WEParameter level / Range of values
5.3Change in lag/lead sequence (Anl 4 to 7)
The lag/lead sequence can be changed depending on the outdoor temperature, operating
hours or capacity. The change in lag/lead sequence is only effective when the mode selector
switch is set toand with the configuration Co5 -> Fb20 = OFF.
Note!
A change in lag/lead always takes place when the controller detects a fault in the lead boiler
regardless of the configuration.
2
1
5.3.1 Outdoor temperature-dependent change (Anl 5 and 7)
The outdoor temperature-dependent change in lag/lead sequence is only appropriate when
boilers with varying capacity are used.
The lead boiler is determined by comparing the mean outdoor temperature overthree dayswith
Reverse sequence limit t
the
Outdoor temperature >
4
boiler is the boiler with the smallest unit capacity
Outdoor temperature <
4
boiler is the boiler with the largest unit capacity
Functions
Automatic change in lag/lead sequenceONCo5 -> Fb09 = ON
Condition for change in lag/lead sequenceONCo5 -> Fb10 = OFF, select: 1
Parameter
Outdoor temperature limit for lag/lead
sequence change
parameter:
A
Outdoor temperature limit for lag/lead sequence change
Outdoor temperature limit for lag/lead sequence change
WEConfiguration
WEParameter level / Range of values
15 °C PA5 / –40 to 50 °C
: Lead
: Lead
5.3.2 Capacity-dependent change (Anl 5 and 7)
The lead boiler is the boiler which had the lowest average capacity over the past three days.
Functions
Automatic change in lag/lead sequenceONCo5 -> Fb09 = ON
36 EB 5474 EN
WEConfiguration
Page 37
Boiler functions
Condition for change in lag/lead sequenceONCo5 -> Fb10 = OFF, select: 2
5.3.3 Operating hours-dependent change (Anl 5 and 7)
After a fixed amount of time haselapsed, countingin hoursfrom the time when the last lag/lead
sequence tookplace (
role as lead boiler.
The elapsed operating hours since the last change in lag/lead sequence are shown in the InF5
level.
Functions
Automatic change in lag/lead sequenceONCo5 -> Fb09 = ON
Condition for change in lag/lead sequenceONCo5 -> Fb10 = ON
Parameter
Time interval for lag/lead sequence change168 hPA5 / 1 to 999 h
Time intervalfor lag/lead sequence change)
WEConfiguration
WEParameter level / Range of values
, theother boiler takes on the
5.3.4 Change with binary input (Anl 4 to 7)
The binary input BE4 can be used for the change in lag/lead sequence when the DHW heating
is not being controlled:
BE4 = OFF: Boiler 1 as lead boiler
4
BE4 = ON: Boiler 2 as lead boiler
4
Functions
DHW demand – activeONCo4 -> Fb00 = OFF
Automatic change in lag/lead sequenceOFFCo5 -> Fb09 = OFF
WEConfiguration
Note!
In system Anl 7 the binary input BE4 can be used either for modulation feedback, for an exter
nal demand for DHW or for an external change in lag/lead sequence.
5.4Return flow boost
On fulfilling the criteria for activation (–> section 5.1) the return flow control circuit is closed at
the valve RK1/RK2. In the released boiler K1/K2 (see above), the first stage of the boiler and
the boiler pump Pu1/Pu2 is switched on. The water is circulated in the boiler circuit.
The return control circuit is released if the temperature at the sensor RüF1/RüF2 exceeds the
limit entered in
Minimum return flow temperature.
The mixing valve opens and release the cor
EB 5474 EN 37
-
-
Page 38
Boiler functions
responding flow rateto theplant untilthe valve is completely opened and the boiler pump deliv
ers the maximum flow rate in the plant.
Parameter
Minimum return flow temperature50 °C PA1, PA2* / 20 to 120 °C
WEParameter level / Range of values
* Only in systems Anl 4 to 7
Depending on the configuration, the return flow boost can be controlled with a continuous
signal, on/off signal or three-point stepping signal (–> section 8.11).
5.4.1 Common return flow boost
In systems with two boilers (systems Anl 4, 5, 6 and 7), a common return flow boost can be im
plemented. This is done by using the return flow control circuit of the first boiler K1, depending
on whether the boiler is in operation.
Function
Common return flow boostOFFCo5 -> Fb12 = ON
WEConfiguration
5.5Parallel operation (Anl 7)
This function leads to both boilers working constantly in parallel (no lag/lead sequence
control).
The boilersstart operatingone after the other, taking into account the programmed times:
and
mum deactivation time for boiler K1, 2
for releasing sequence
ture t
A
Function
Parallel operation of boilersOFFCo5 -> Fb19 = ON
Parameters
Minimum deactivation time f. boiler K1, 20 minPA1, 2 / 0 to 90 min
Lag delay10 min PA5 / 0 to 90 min
Temperature tAfor releasing sequence12 °C PA5 / –40 to 50 °C
Lag delay
WEConfiguration
WEParameter level / Range of values
as well as taking into account
Mini-
Tempera-
-
-
5.6Operating hours counter
This function allows the performed operating hours of boilers K1, 2 to be shown in the Inf1, 2
levels. The control is not affected by the counted operating hours. If the operating hours should
be selected to start at a certain initial value, this can be programmed separately.
38 EB 5474 EN
Page 39
Boiler functions
Function
Operating hours counterOFF
WEConfiguration
Co1, Co2* -> Fb02 = ON
0 h
Initial value / Configurable as required
countCounting the operating hours
rESEtReset operating hours to initial value
* Only in systems Anl 4 to 7
5.7Boiler pump control
The boiler pump control is connected with the boiler control loop.
When a boiler is switched on to the first stage, the associated boiler pump is also switched on.
When the boiler is switched off, the boiler is switched off too either after the
elapsed or when the temperature falls below
Boiler flow limit
.
Pump lag time
In summer mode, the boiler pump is switched off together with the boiler when the deactivation
criteria are fulfilled.
In systems without hydraulic separator, in which the heating water must be circulated through
the boiler, the boiler pump may notbe switchedoff. For this purpose, the Continuous running ofpump function is activated. The boiler pump continues to run when the lead boiler is switched
off and the valve is opened. As a result, the cold system water can reach the boiler return flow
pipe. If the return flow temperature is a factor that needs to be monitored in theboiler, theinstallation of an hydraulic separator is recommended.
Function
Continuous running of pumpOFF
WEConfiguration
Co5 -> Fb14 = ON
5 min
Pump lag time / 0 to 90 min
55 °C
Boiler flow limit / 20 to 120 °C
has
5.8Boiler sensor acting as a thermostat
The boiler sensors KF1 and KF2 control the safety deactivation (–> section 8.10), which is trig
gered whenever the maximum flow temperature is exceeded, as well as the temperature-de
pendent pump lag of the boiler pumps Pu1 and Pu2 (–> section 5.7).
The maximum permissible flow temperature can also be monitored in systems Anl 4, 5 and 6
with thermostats. The inputs of the boiler sensors must be defined as binary inputs for this pur
pose. The thermostats are connected to the same terminals as the boiler sensors.
EB 5474 EN 39
-
-
-
Page 40
Boiler functions
Function
Boiler sensor KF1, 2ONCo1, Co2* -> Fb03 = OFF
WEConfiguration
StEiG: Thermostat closes
FALL: Thermostat opens
*Only in systems Anl 4 to 7
5.9Modulation feedback
The modulation feedback in systems Anl 3, 6 and 7 can be implemented by a potentiometer (1
to 2 kΩ) or by a limit switch for maximum boiler capacity output.
Modulation feedback with potentiometer
The inputsfor the potentiometer are marked in thewiring diagrams (–> section 12) with SG_K1
(potentiometer 1) and with SG_K2 (potentiometer 2).
Function
Modulation feedback K1, 2ONCo1, Co2* -> Fb07 = ON
WEConfiguration
* Only in system Anl 7
Note!
In system Anl 7, the binary input BE4 can be used either for modulation feedback, for external
DHW demand or for external change in lag/lead sequence.
5.10 Operational alarm
The boiler controller waits for an operational alarm before it continues (–> section 5.1). The
operational alarm can optionally be issued over a binary input or after fixed time entered in
Start-up time for boiler
parameter.
40 EB 5474 EN
Page 41
Boiler functions
Operational alarm over a binary input
The inputs for the operational alarm are marked in the wiring diagrams (section 12) with BE2
BM_K1 for Boiler 1 and with BE1 BM_K2 for Boiler 2.
Function
Operational alarm K1, 2ONCo1, Co2* -> Fb01 = ON
WEConfiguration
* Only in systems Anl 4 to 7
Operational alarm after start-up
Function
Operational alarm K1, 2ON
WEConfiguration
Co1, Co2* -> Fb01 = OFF
0 s
Start-up time for boiler / 0 to 5400 s
* Only in systems Anl 4 to 7
5.11 Return flow sensor acting as a thermostat
The return flow sensors can optionally be replaced by thermostats. For this purpose, the inputs
for the return flow sensors are defined as binary inputs. The thermostats are connected to the
same terminals as the return flow sensors.
Function
Return flow sensor RüF1, 2ONCo1, Co2* -> Fb04 = OFF
WEConfiguration
StEiG: Thermostat closes
FALL: Thermostat opens
* Only in systems Anl 4 to 7
EB 5474 EN 41
Page 42
Functions of the heating circuit
6Functions of the heating circuit
6.1Outdoor temperature-dependent advance heating
Only selectable for systems Anl 1 to 3 with Co5 -> Fb13 = ON.
The controller switchesthe heatingon beforethe time-of-use starts in normal operation depend
ing onthe outdoor temperature. The
of –12 °C. The advance heating time is shortened in case of higher outdoor temperatures.
Functions
Heating circuit with DHW heatingOFFCo5 -> Fb13 = ON
OptimizationOFF
Outdoor sensorONCo5 -> Fb00 = ON
Advance heatingtime
WEConfiguration
Co3 -> Fb05 = ON,
120 min
Advance heating time / 0 to 360 min
is basedon an outdoor temperature
select: 1
6.2Optimization using a room sensor
Only selectable for systems Anl 1 to 3 with Co5 -> Fb13 = ON.
Both thefunctions describedshould only be used if the room in which theroom sensor is located
(reference room) has a heating characteristic that is similar to the rest of the building.
No thermostat valves should be mounted on the radiators in the reference room.
There are two types of optimization depending on the activation conditions:
The controller activates the heating depending on the outdoor temperature before the
time-of-use starts in normal operation. The
temperature of –12 °C. The advance heating time is shorter whenthe outdoortemperature is
higher (see section 6.1).
Room temperature-dependent advance heating and deactivation
4
The controller calculates the required advance heating time (max. 6 hours) adapted to the
building characteristics, resulting in the
reached in the reference room when the time-of-use starts. The heating is heated with the
maximum flowtemperature duringthe advance heating phase. As soon as the
is reached, outdoor temperature-dependent control starts.
Advance heating time
Day set point
(rated room temperature) being
is based on an outdoor
Day setpoint
-
The controllerdeactivates the heating in both types of optimization dependingon the room sen
sors up to two hours before the time-of-use finishes.
The controller chooses the deactivation time such in a way that the room temperature does not
drop significantly below the desired temperature until the time-of-use ends.
42 EB 5474 EN
-
Page 43
Functions of the heating circuit
Outside the times-of-use, the controller monitors the
Sustained temperature
or the
in the case of room temperature-dependent deactivation. When
Night set point
(reduced room temperature)
the temperature falls below the night set point, the controller heats with the max. flow tempera
ture until the measured room temperature exceeds the adjusted value by 1 °C.
Note!
Direct sunshine can cause theroom temperatureto increaseand thusresult inthe prematurede
activation of the heating system.
A drop in room temperature within a brief period outside of the time-of-use may lead to the ad
vance heating to reach the room temperature being activated too early.
Functions
Heating circuit with DHW heatingOFFCo5 -> Fb13 = ON
Room sensorOFFCo3 -> Fb00 = ON
Room temperature-dependent advance heating and deactivation:
OptimizationOFF
Parameter
Day set point20 °CPA3 / 10 to 40 °C
Night set point17 °CPA3 / 10 to 40 °C
Sustained temperature10 °CPA3 / 10 to 40 °C
WEConfiguration
Co3 -> Fb05 = ON,
120 min
WEParameter level / Range of values
Advance heating time / 0 to 360 min
Co3 -> Fb05 = ON,
select: 2
select: 3
-
-
-
EB 5474 EN 43
Page 44
Functions of the DHW circuit
7Functions of the DHW circuit
Only systems Anl 1 to 3 have their own DHW heating (DHW heating in storage system with
Co5 -> Fb13 = ON).
The systems Anl 4 to 7 do not have their own DHW heating; they are, however, able to process
an external DHW demand (-> section 7.4) and to reduce an excessively high flow temperature
over a DHW forced charging in the external system (-> section 7.2).
7.1DHW heating in the storage tank system (Anl 1 to 3)
WW
SLP
Fig. 4 · DHW heating in a storage tank system
SF1
SF2
ZP
KW
SLPStorage tank charging pump
SF1Storage tank sensor 1
SF2Storage tank sensor 2
ZPCirculation pump
WWHot water
KWCold water
Operation with storage tank sensor SF1
The controller begins charging the storage tank when the water temperature measured at sensor SF1 falls below the set point
DHW demand ON
. The controller stops charging the storage
tank when the water temperature in the storage tank measured at sensor SF1 reaches the value
DHW demand ON+Hysteresis
T =
The set point
Functions
Heating circuit with DHW heatingOFFCo5 -> Fb13 = ON
Storage tank sensor SF1OFFCo4 -> Fb03 = ON
Storage tank sensor SF2OFFCo4 -> Fb04 = OFF
Parameters
Boiler set point for DHW demand65 °CPA4 / 20 to 120 °C
DHW demand ON40 °CPA4 / 20 to 90 °C
Hysteresis5 °CPA4 / 0 to 30 °C
Boiler set point for DHW demand
.
determines the set point at sensor VFg.
WEConfiguration
WEParameter level / Range of values
44 EB 5474 EN
Page 45
Functions of the DHW circuit
Operation with two storage tank sensors SF1 and SF2
The controller begins charging the storage tank when the water temperature measured at sen
sor SF1 falls below the set point
DHW demand ON
. The controller stops charging the storage
tank when the water temperature in the storage tank measured at sensor SF2 reaches the value
DHW demand OFF
The set point
Functions
Heating circuit with DHW heatingOFFCo5 -> Fb13 = ON
Storage tank sensor SF1OFFCo4 -> Fb03 = ON
Storage tank sensor SF2OFFCo4 -> Fb04 = ON
Parameters
Boiler set point for DHW demand65 °CPA4 / 20 to 120 °C
DHW demand ON40 °CPA4 / 20 to 90 °C
DHW demand OFF45 °CPA4 / 20 to 90 °C
.
Boiler set point for DHW demand
WEConfiguration
WEParameter level / Range of values
determines the set point at sensor VFg.
Operation with storage tank thermostat
The storage tank thermostat is connected to SF1 and switches the storage tank charging on and
off. The set point
Functions
Heating circuit with DHW heatingOFFCo4 -> Fb13 = ON
Storage tank sensor SF1OFFCo4 -> Fb03 = OFF
Storage tank sensor SF2OFFCo4 -> Fb04 = OFF
Parameter
Boiler set point for DHW demand65 °CPA4 / 20 to 120 °C
Boiler set point for DHW demand
must still be predetermined.
WEConfiguration
WEParameter level / Range of values
-
7.1.1 Priority circuit (Anl 1 to 3)
The DHW heating can be switched with priority over the separate heating circuit 2 or directly
over the heating circuit (heating circuit 3, Pu3).
Heating circuit 2:
During the storage tank charging, the separateheating circuit2 is placed in reduced operation.
EB 5474 EN 45
Page 46
Functions of the DHW circuit
Functions
Heating circuit with DHW heatingOFFCo5 -> Fb13 = ON
DHW priority over HK2OFFCo4 -> Fb06 = ON
WEConfiguration
Heating circuit 3:
During the storage tank charging, the direct heating circuit is switched off. The separate heating
circuit runs in parallel.
Functions
Heating circuit with DHW heatingOFFCo5 -> Fb13 = ON
DHW priority over HK3OFFCo4 -> Fb07 = ON
WEConfiguration
Note!
When the DHW priority over HK3 function is deactivated, the direct heating circuit also runs in
parallel to the DHW charging. The heating circuit may, however, only be overheated by 10 °C .
In other words, the heating circuit is supplied with not enough heat when the boiler set point for
the heating circuit is greater than
Boiler set point for DHW demand
off during storage tank charging when the
Boiler set point for DHWdemand
. The heating circuit is switched
is 10 °C higher than
the boiler set point.
7.2Forced charging of the DHW storage tank (Anl 1 to 7)
A forced charging of the DHW storage tank can prevent that the safety equipment place the
boiler out of operation in case of excessively high flow temperature.
The forced charging of the DHW storage tank takes place when the
forced charging
is exceeded at the flow sensor together with sensor VFg or at one of the two
boiler sensors KF1 or KF2.
In systems without their own DHW heating (systems Anl 4 to 7) the demand for a forced charg
ing is passed on to the connected controllers atbinary outputBA1. The actual forced charging is
started by the controllers that are responsible for the DHW heating.
Functions
Heating circuit with DHW heatingOFFCo5 -> Fb13 = ON*
Forced charging of DHW storage
tank
WEConfiguration
OFF
Co4 -> Fb02 = ON
80 °C
Maximum limit f. DHW forced charging/20 to 120 °C
* Not in systems Anl 4 to 7
Maximum limit for DHW
-
46 EB 5474 EN
Page 47
Functions of the DHW circuit
7.3Thermal disinfection (Anl 1 to 3)
In all systems with DHW heating, the DHW storage tank is thermally disinfected on the selected
Day of week
The charging temperature is always 5 °C higher than the
Thermal disinfection starts at the adjusted
Disinfection temperature
the
display. The error alarm is automatically reset when the
during the next thermal disinfection.
Thermal disinfection for preventing legionella infection causes
high return flow temperatures during the disinfection cycle (return flow temperature limita
4
tion suspended),
high storage tank temperatures after thermal disinfection has been concluded,
4
lime scale (possibly), which can have a negative effect on heat exchanger performance.
4
Note!
This function is not available when a storage tank thermostat is used.
or daily. The storage tank is heated up to the adjusted
Disinfection temperature
Start time
is not reached at the end of thermal disinfection,blinks on the
and finishes at the
Disinfection temperature
Disinfection temperature
.
Stop time
at the latest. If
is reached
.
-
Functions
Heating circuit with DHW heatingOFFCo5 -> Fb13 = ON
Storage tank sensor SF1OFFCo5 -> Fb03 = ON
Thermal disinfectionOFF
WEConfiguration
Co4 -> Fb08 = ON
Day of week / 0, 1 to 7 (daily, Mon to Sun)
3
Disinfection temperature / 50 to 80 °C
70 °C
Start time / 00:00 to 23:59 h
00:00
Stop time / 00:00 to 23:59 h
04:00
EB 5474 EN 47
Page 48
Functions of the DHW circuit
7.4External DHW demand (Anl 1 to 7)
This function allows the boiler controller to switch over to the
Boiler set point for DHW demand
when the binary input BE4 (WWA) is closed. The thermal disinfection has priority when the ex
ternal DHW demand and thermal disinfection coincide.
Functions
Modulation feedback K2ONCo2 -> Fb07 = OFF
DHW demand – activeONCo4 -> Fb00 = ON
Parameter
Boiler set point for DHW demand65 °CPA4 / 20 to 120 °C
WEConfiguration
WEParameter level / Range of values
Note!
In system Anl 7, the binary input BE4 can be used either for modulation feedback, for external
DHW demand or for external change in lag/lead sequence.
-
48 EB 5474 EN
Page 49
System-wide functions
8System-wide functions
8.1Weather-compensated control
When weather-compensated control is used, the flow temperature is controlled according to the
outdoor temperature. The boiler characteristic in the controller defines the flow temperature set
point as a function of the outdoor temperature (–> Fig. 5). The outdoor temperature required for
weather-compensated control is measured at the outdoor sensor at the input AF or received
over a 0 to 10 V signal at the input AE2.
[
C]t
˚
VL
130
120
110
100
90
80
70
60
50
40
30
20
20 1612840-4-8 -12 -16 -20
Fig. 5 · Gradient characteristic
3.2 2.92.6
2.4
2.2
2.0
1.8
1.6
1.4
1.2
1.0
0.8
0.4
0.2
t
C]
[
˚
tVLFlow temperature
t
A
A
Outdoor temperature
Caution!
Pt 100or Pt1000 sensorshould be used for measuring the flow temperature as only these sensors
guarantee measurements up to 160 °C (max. temperature of the flow temperature set point).
Function
Outdoor sensorON
WEConfiguration
Co5 -> Fb00 = ON
FUEHL: Outdoor temperature sensor AF
0–10: 0 to 10 V signal
3 °C
Frost protection limit / –30 to 20 °C*
* See section 8.8
EB 5474 EN 49
Page 50
System-wide functions
8.1.1 Gradient characteristic
Basically, the following rule applies: a decrease in the outdoor temperature causes the flow tem
perature to increase. By varying the
teristic to your individual requirements. Increasing
ture, decreasing
transport of the heating characteristic in an upward or downward direction.
Outside the times-of-use, reduced set points are used for control:
Reduced flow set point
Max. flowtemperature
The
its of the flow temperature. A separate gradient characteristic can be selected for the limitation
of the return flow temperature.
Examples for adjusting the characteristic:
Old building, radiator design 90/70:Gradient approx. 1.8
4
New building, radiator design 70/55:Gradient approx. 1.4
4
New building, radiator design 55/45:Gradient approx. 1.0
4
Underfloor heating depending on arrangement: Gradient smaller 0.5
4
Functions
Type of characteristicOFFCo5 -> Fb03 = ON, select: 2
Type of characteristic for separate/direct
heating circuit*
Parameters
Gradient, flow1.8PA2*, PA3*, PA5 / 0.4 to 3.2
Level, flow0 °C PA2*, PA3*, PA5 / –30 to 30 °C
Set-back difference15 °C PA2*, PA3*, PA5 / 0 to 30 °C
Max. flow temperature90 °C PA2*, PA3* / 20 to 160 °C
Min. flow temperature20 °C PA2*, PA3* / 20 to 120 °C
Gradient
in alower flowtemperature. The
= Flow set point–Set-back difference
and
Gradient
Min. flowtemperature
and
Level
WEConfiguration
ONCo2, Co3 -> Fb10 = ON, select: 2*
* Only in systems Anl 1 to 3 with Co5 -> Fb13 = ON
WEParameter level / Range of values
* Only in systems Anl 1 to 3 with Co5 -> Fb13 = ON
parameters, you can adapt the charac
Gradient
parameters markthe upperand lowerlim
results in a higher flow tempera
Level
parameter performsa parallel
.
-
-
-
-
50 EB 5474 EN
Page 51
System-wide functions
[˚C]
8.1.2 4-point characteristic
The 4-point characteristic allows you to define your own heating characteristic.
It is defined by 4 points for the
set-back difference
is predetermined for points P1 and P2 and for points P3 andP4 inthe corre
Outdoor temperature
sponding parameter level, resulting in the dashed line in Fig. 6.
Max. flowtemperature
The
and
Min. flowtemperature
its of the flow temperature.
t
[˚C]
VL
100
t
VLmax
90
80
70
60
50
t
VLmin
40
30
20
10
P4
20 15 1050–5 –10 –15 –20
Fig. 6 · 4-point characteristic
P2
P3
P1
and the
Flow temperature
parameters markthe upperand lowerlim
P1 to 4 Points 1 to 4
Flow temperature
t
VL
Outdoor temperature
t
A
..minMin. flow temperature
..max Max. flow temperature
4-point characteristic
-------- Reduced 4-point characteristic
t
A
. The
Boiler
-
-
Functions
WEConfiguration
Type of characteristicOFFCo5 -> Fb03 = ON, select: 1
Type of characteristic for separate/
OFFCo2, Co3 -> Fb10 = ON, select: 1*
direct heating circuit*
* Only in systems Anl 1 to 3 with Co5 -> Fb13 = ON
EB 5474 EN 51
Page 52
System-wide functions
Parameters
Outdoor temperaturePoint 1
Point 2
Point 3
Point 4
Flow temperaturePoint 1
Point 2
Point 3
Point 4
Set-back differencePoints
½
Points
3/4
Max. flow temperature90 °CPA2*, PA3* / 20 to 160 °C
Min. flow temperature20 °CPA2*, PA3* / 20 to 120 °C
WEParameter level / Range of values
–10 °C
– 5 °C
10 °C
90 °C
80 °C
68 °C
50 °C
15 °C
20 °C
* Only in systems Anl 1 to 3 with Co5 -> Fb13 = ON
PA2*, PA3*, PA5 / –20 to 50 °C
5 °C
PA2*, PA3*, PA5 / 20 to 160 °C
PA2*, PA3*, PA5 / 0 to 30 °C
8.2Fixed set point control
During the times-of-use, the flow temperature can be controlled according to a fixed
Outside the times-of-use, this
Set point
is reduced by the
Set-back difference
The fixed set point control is activated when there is no outdoor sensor AF connected to the system or when it has been configured in the function block Type of characteristic. In the case that
the fixed set point control is configured and an outdoor sensor is connected, the outdoor temperature is displayed in the InF5 level. The outdoor temperature does not have any effect on the
control loop.
Functions
Type of characteristicOFFCo5 -> Fb03 = OFF
Type of characteristic for separate/
direct heating circuit*
Parameters
Flow temperature set point70 °C PA2*, PA3*, PA5 / 20 to 160 °C
Set-back difference15 °C PA2*, PA3*, PA5 / 0 to 30 °C
WEConfiguration
OFFCo2, Co3 -> Fb10 = OFF*
* Only in systems Anl 1 to 3 with Co5 -> Fb13 = ON
WEParameter level / Range of values
* Only in systems Anl 1 to 3 with Co5 -> Fb13 = ON
Set point
.
.
52 EB 5474 EN
Page 53
System-wide functions
8.3Differential temperature control using variable weighting factors
This functionallows thereturn flow temperature, total (RüFg) to be taken into account in the con
trol loop, in addition to the flow temperature, total (VFg).
The difference between the flow temperature, total (VFg) and return flow temperature, total
(RüFg) is specified using the
Intended temperature difference
parameter. It is a measure for the
energy consumption in a heating circuit. The greater the temperature difference, the larger the
energy required by a heating circuit. If the actual temperature difference is not the same as the
intended temperature difference, it is evaluated by the
. After initial signs for a deviation occur, the flow temperature is raisedor reducedby this
control
Kp factor for differential temperature
factor.
When the
Kp factor for differential temperature control
is set to 0, the return flow temperature
does not have any effect on the control of the flow temperature.
When the
Kp factor for differential temperature control
is set to 1, a pure return flow tempera
ture limitation takes place.
Function
Return flow sensor, total RüFgOFF
WEConfiguration
Co5 -> Fb02 = ON
10 °C
Intended temperature difference / 0 to 90 °C
0.5
Kp factor for differential temperature control /
0 to 1
8.4Deactivation depending on outdoor temperature
The controller switches to the stand-by mode when
to summer mode in rated operation
during times-of-use or
change to summer mode in reduced operation
Should the temperature fall below the limit, the heating is started again. The function for deacti
vation depending outdoor temperature is set by default.
Parameter
Outdoor temperature limit causing change
to summer mode in rated operation
Outdoor temperature limit causing change
to summer mode in reduced operation
WEParameter level / Range of values
22 °C PA5 / 0 to 50 °C
10 °C PA5 / –10 to 50 °C
Outdoor temperature limit causing change
Outdoor temperature limit causing
outside times of use is exceeded.
-
-
-
EB 5474 EN 53
Page 54
System-wide functions
8.5Summer mode
Summer mode is activated depending on the mean daytime temperature (measured between
7.00h and 22.00h) during the desired period.
If the mean daytime temperature exceeds the
Outdoor temperature limit
on two consecutive
days, summer mode is activated on the following day: the heating is switched off. If the mean
daytime temperature remains below the
Outdoor temperature limit
on the next day, summer
mode is deactivated on the following day.
Function
Summer modeON
WEConfiguration
Co5 -> Fb06 = ON
01.06
Start summer mode / 01.01 to 31.12
30.09
Stop summer mode / 01.01 to 31.12
18 °C
Outdoor temperature limit /0 to 40 °C
8.6Delayed outdoor temperature adaptation
The calculated outdoor temperature is used to determine the flow temperature set point. The
heat response is delayed when the outdoor temperature either decreases, or increases and decreases. If the outdoor temperature varies by, for example, 12 °C within a very short period of
time, the calculated outdoor temperature is adapted to the actual outdoor temperature in small
Delay
steps. Assuming a
of 3 °C/h, the adaptation would take
C
°°12
t
==
Ch
3/
4h
.
Note!
The delayed outdoor temperature adaptation helps avoid unnecessary overloads of central
heating stationsin combination with either overheated buildings occurring, forexample, due to
warm winds, or temporarily insufficient heating due to the outdoor sensor being exposed to di
rect sunshine.
Function
Delayed outdoor temperature adaptation OFF
WEConfiguration
Co5 -> Fb01 = ON
AB Delay on decreasing temperature
ABAUF Delay on decreasing and increasing
Delay / 1 to 6.0 °C/h
3 °C/h
temperature
54 EB 5474 EN
-
Page 55
System-wide functions
8.7Automatic summer time/winter time changeover
The clock is automatically adjusted on the last Sundayin Marchat 2.00h and on the last Sunday
in October at 3.00h.
Function
Summer time/winter time changeoverONCo5 -> Fb05 = ON
WEConfiguration
8.8Frost protection
To protect the system from freezing up, the flow temperature or return flow temperature are
monitored.
Note!
The frost protection function is not activatedwhen manualmode is selected at the mode switch.
Flow temperature monitoring
The flow temperature cannot drop enough to cause the pipes to freeze when the controller is in
rated or reduced operation. In stand-by mode, the flow temperature is not regulated. Therefore,
it ismonitored. Shouldthe flow temperature fall below 3 °C, the flow temperature is restrictedto
the minimum return flow temperature.
Return flow temperature monitoring
The outdoor temperature is monitored at the input AF (outdoor sensor) or at the input AE2 (0 to
10 V signal). In both cases, the
Frost protection limit
(–30 to 30 °C, WE: 3 °C with Co5 -> Fb00
= ON) must be defined to monitor this parameter.
Alternatively, a frost protection thermostat can also be used for monitoring. This requires input
AF to be configured as a binary input (BE11) (Co5 -> Fb00 = OFF, FroSt).
If there is no boiler in operation and the outdoor temperature falls below the frost protection
limit or if the binary input of the frost protection thermostat is active, the pumps are activated
and the valves opened. As a result,the systemor individual parts of the system cannotfreeze.
Function
Outdoor sensor
WEConfiguration
ONCo5 -> Fb00
EB 5474 EN 55
Page 56
System-wide functions
8.9Forced operation of the pumps
When the pumps (Pu1, Pu2 and Pu3) have not been activated for 24 hours, forced operation of
the pumps is started between 12.00h and 12.01h. The forced operation of the storage tank
pump SLP is operated between 12.01h and 12.02h.
8.10 Flow temperature limitation
The boiler temperature is regulated to the limit set in
Maximum flow temperature
and an alarm
is displayed when the flow temperature at the boiler outlet of a modulating burner reaches the
Maximum flow temperature+Temperature rise
limit
The limitation is stopped again when the flow temperature falls below the limit set in
flow temperature
.
.
Maximum
During the active limitation, the boiler temperature blinks in InF1 and InF2 levels. Pressto
read the limit.
Function
Boiler sensor KF1, 2
Parameters
Maximum flow temperature KF1, 290 °C PA1, PA2* / 20 to 160 °C
Temperature rise10 °C PA5 / 0 to 30 °C
WEConfiguration
ONCo1, Co2* -> Fb03 = ON
* Only in systems Anl 4 to 7
WEParameter level / Range of values
* Only in systems Anl 4 to 7
Note! The controller cannot replace a safety temperature limiter.
The flow temperature is monitored by athermostat whenthe functionis deactivated. The input of
the flow sensor is defined as a binary input. The thermostat is connected to terminals 24 (RK1)
or 25 (RK2).
Function
Boiler sensor KF 1, 2ONCo1, Co2* -> Fb03 = OFF
WEConfiguration
StEiG Thermostat closes
FALLThermostat opens
*Only in systems Anl 4 to 6
Note! The sensor inputs VF1 and VF2 cannot be used as thermostat inputs in system Anl 7.
56 EB 5474 EN
Page 57
System-wide functions
8.11 Control mode
The selected control mode (section 8.11.1 to 8.11.3) of the return flow boost affects the control
mode of the modulation and vice versa. The following connection applies:
Return flow boost in continuous control<–>Modulation in three-point
4
Return flow boost in on/off or three-point control <–>Modulation in continuous
4
On using modulating burners (systems Anl 6 and 7), the default setting of the control signal for
the returnflow boost is configured to be continuous (Co1, 2 -> Fb05 = ON)and the modulation
control uses a three-point signal. With Co1, 2 -> Fb05 = OFF, this assignment is reversed,
meaning that the modulating burners can also be controlled with a continuous signal.
Setting for return flow boost: continuous control; Modulation: three-step control
Functions
RüL-RK1, 2
Setting for return flow boost: three-step control; Modulation: continuous control
Functions
RüL-RK1, 2
3-step pulsing/on-off signal RüL-RK1, 2OFFCo1, Co2* -> Fb06 = ON
WEConfiguration
Co1, Co2* -> Fb05 = ON
6
120 s
0 s
WEConfiguration
6
120 s
0 s
120 s
(proportional gain) / 0.1 to 99.9
K
P
T
(reset time) / 0 to 999 s
N
T
(derivative-action time) / 0 to 999 s
V
Co1, Co2* -> Fb05 = OFF
K
(proportional gain) / 0.1 to 99.9
P
T
(reset time) / 0 to 999 s
N
T
(derivative-action time) / 0 to 999 s
V
T
(valve transit time) / 5 to 240 s
Y
Setting for return flow boost: on/off control; Modulation: continuous control
Functions
RüL-RK1, 2
3-step pulsing/on-off signal RüL-RK1, 2OFF
WEConfiguration
Co1, Co2* -> Fb05 = OFF
K
6
120 s
0 s
120 s
5 °C
120 s
120 s
(proportional gain) / 0.1 to 99.9
P
T
(reset time) / 0 to 999 s
N
T
(derivative-action time) / 0 to 999 s
V
T
(valve transit time) / 5 to 240 s
Y
Co1, Co2* -> Fb06 = OFF
Hysteresis / 1 to 30 °C
Min. activation time / 0 to 600 s
Min. deactivation time / 0 to 600 s
EB 5474 EN 57
Page 58
System-wide functions
* Only in systems Anl 4 to 7
Note!
The control mode is configured separately in Co2 -> Fb14 or Fb15 for the separate heating cir
cuit in systems Anl 1 to 3 (Co5 -> Fb13 = ON).
8.11.1 Three-step control
The setpoint can be controlled using a PI algorithm. Thevalve reacts to pulses that the controller
emits whena system deviation occurs. The length ofthe first pulse. in particular, depends onthe
extent of the system deviation and the selected
increases). The pulse and pause lengths change continuously until the system deviation
as K
P
Proportional gain K
has been eliminated. The pauselength betweenthe singlepulses isgreatly influencedby the
set time T
The
(the pause length increases as TNincreases).
N
Transit time T
specifies the time required by the valve to travel through the range of 0 to
Y
(the pulse length increases
P
Re
100 %.
8.11.2 On/off control
The output signal of the controller is switched on or off.
Depending on the controlled variable, the outputsignal is switched on oroff when the temperature fallsbelow orexceeds the required set point by T = 0.5 x
selected, the less the signal is switched on and off. The
esis
mum deactivation time
determine the time interval between changes in the output signal.
Hysteresis
Minimum activation time
. Thegreater the
and
Hyster-
Mini-
-
-
8.11.3 Continuous control
The set point can be controlled using a PID algorithm. The valve receives an analog 0 to 10 V
signal from the controller. The proportional component causes an immediate change in the 0 to
10 Vsignal when a system deviation occurs (the greater the K
tegral-action component only comes into effect when a certain time has passed: T
the time passing until the integral-action component has changed theoutput signal to the extent
that the proportional component directly changed the signal (the greater the T
rate of change). The derivative-action component determines how strongly a change in the sys
tem deviation affects the output signal (the greater the T
58 EB 5474 EN
, thegreater the change). The in
P
, the slower the
N
, the stronger the change).
V
stands for
N
-
-
Page 59
8.12 Control signal deactivation
System-wide functions
This function protects three-point stepping actuators without final position deactivation from over
loading bymonitoring the total of thecontrol signal pulses. No furthercontrol signals are issued if
it exceeds three times the
Valve transit time T
. It is assumed that the control valve is already open
Y
or closed, meaning further control signals do not change the valve position.
Function
Control signal deactivationOFFCo5 -> Fb16 = ON
WEConfiguration
8.13 Processing of external demand
The controller (= primary controller) is able to process analog signals for demand.
The external flow temperature set point of the preceding controller is received over the analog
input AE1. 0 to 10 V corresponds to 0 to 120 °C. Demands under a signal of 1 V are sup
pressed. The received flow temperature set point is compared to the controller’s own flow tem-
Boost
perature set point. The higher of both flow temperature set points plus the
parameter is
used for the control.
Boost
The
parameter improves the control characteristic of the downstream control valves in the
heating circuit and compensates for any pipeline losses.
Function
External demandOFFCo5 -> Fb15 = ON
WEConfiguration
0 °CBoost / 0 to 30 °C
8.14 Feedforwarding the outdoor temperature
The outdoortemperature can be passed on to anothercontroller over the analog output AA2 (0
to 10 V) by setting Co2 -> Fb05 = ON, provided this output isnot usedfor acontrol signalor for
the modulation control.
Systems Anl 1 to 3:
The outdoor temperature is constantly applied to AA2. No special settings are necessary. 0 to
10 V corresponds to –40 to 50 °C.
Systems Anl 4 to 6:
Function
Continuous RüL-RK2OFFCo2 -> Fb05 = OFF
WEConfiguration
-
-
EB 5474 EN 59
Page 60
System-wide functions
System Anl 7:
The outdoor temperature cannot be passed on as the output AA2 is constantly used for a control
signal or for the modulation control.
8.15 Locking of changed settings
An active locking of all manual levels means that no settings (configuration and
parameterization) can be performed at the controller.
Function
Configuration and parameterization
protection
WEConfiguration
OFFCo5 -> Fb04 = ON
60 EB 5474 EN
Page 61
Operational faults
9Operational faults
Operational faults are indicated by theicon blinking on the display.
“Error“ immediately appears on the display. Pressto access the error level. Use the arrow
keys toscroll thedifferent error alarms, if need be. The error level remains inthe displayloop as
long as an acute operational fault exist even if it has not be opened by pressing.
9.1Error list
Err 1 Sensor failure in RK1 (in combination with sensor icons)
4
Err 2 Sensor failure in RK2 (in combination with sensor icons)
4
Err 3 Sensor failure in heating circuit (in combination with sensor icon)
4
Err 4 Sensor failure in DHW circuit (in combination with sensor icons)
4
Err 5 Failure of sensor VFg, RüFg or AF (in combination with sensor icons)
4
Err b1 Fault in Boiler K1
4
Err b2 Fault in Boiler K2
4
Err P1 Fault in Pump Pu1
4
Err P2 Fault in Pump Pu2
4
Err-1 Default values read (default settings)
4
Err-2 Final temperature of thermal disinfection not achieved
4
Err-3 Mode selector switch 1 defective
4
Err-4 Selector switch defective
4
Err-5 Correction switch for the flow temperature defective
4
9.2Sensor failure
The errorlist explains how the “Err-1”to “Err-5” on the display inthe error level indicate sensor
failures. After exiting the error level, detailed information can be found within the operating
level by reading each temperature: A sensor icon in combination with three dashes instead of
the measured temperature on the display indicates that this sensor is defective.
Sensor icons
Outdoor sensor AF
Flow sensor VF2, VFg,
Boiler sensor KF1, KF2
Return flow sensor RüF1, RüF2, RüFg
Room sensor RF
Storage tank sensor SF1
Storage tank sensor SF2
EB 5474 EN 61
Page 62
Operational faults
The following list shows how the controller reacts depending on which sensor fails:
Outdoor sensor AF: When the outdoor sensor fails, the controller uses a flow temperature
4
set point of 70 °C. The boiler pumps are switched on and the control valves of the return flow
boost are opened to ensure frost protection.
Flow sensor VFg: Both boilers are switched off immediately.
4
Flow sensor VF1, VF2: The affected boiler is switched off. The other boiler takes over.
4
Return flow sensor RüFg: The controller continues to functionwithout thedifferential temper
4
ature control using variable weighting factors.
Boiler return flow sensor RüF: The controller continues to function without the return temper
4
ature limitation. If the affected boiler is switched on, the boiler pump is switched on and the
control valve receives a constant signal.
Storage tank sensor SF1/SF 2: When one of the sensors fail, storage tank charging no lon
4
ger takes place.
Boiler K1, K2 (binary inputs SM_K): The affected boiler and the associated pump are
4
stopped.
Pumps (binary inputs SM_P): The affected boiler and the associated pump are stopped.
4
9.3Displaying the lead/collective error alarm
The lead is indicated over BA2 when the function block is active:
Lead 1: BA2 = OFF
4
Lead 2: BA2 = ON
4
The binary output BA2 is set in the event of an error when the function block is not active. Errors
are still displayed by “Err” in the info level.
Function
Displaying lead/collective alarmOFFCo5 -> Fb11
WEConfiguration
-
-
-
9.4Error status register
The error status register is used to indicate controller or system errors. In modem operation with
Dial-up also upon corrected fault
the building control station to be dialed.
The error status registers are displayed in InF8 level. By default the error status register FSR1
(holding register 60) is displayed. Keeppressed to display FSR2 (holding register 61). In
both displays, function blocks Fb20 to Fb23 are set when a bit is set in the error status register
not being displayed.
62 EB 5474 EN
function, any change in state of the error status register causes
Page 63
Operational faults
Holding register 60 (HR60)
Number = Bit no. in HR0 1234567891011
A set bit is indicated byon the right of
number
Bit value2
Sensor breakageD0
Default values readD1
–D2
Mode switch faultyD3
Boiler switch faultyD4
Correction switch for flow temp. faultyD5
Unauthorized accessD6
Error alarm of a binary input
Error alarm WMZ M-BusD8
Data error alarm from WMZD9
–D10
Fault alarm binary input changedD11
0212223242526272829210211
D7
Holding register 61 (HR61)
Number = Bit no. in HR0 1 2 3
A set bit is indicated byon the right of number
Bit value2
Error thermal disinfectionD0
–D1
–D2
Error Boiler 1, 2 or Pump Pu1,2, or
Temperature exceeded limit
0212223
D3
Example of a transfer to the control system:
The error statusregister istransferred asa word<w> in a holding register (HR) whose content is
represented by the total of the value <z> of the active data bit:
<w> = ([D0] x <1> + [D1] x <2>) + … + ([D11] x <2048>)
EB 5474 EN 63
Page 64
Operational faults
9.5Error alarms
Error alarms can be sent over amodem either directly to thecontrol station or over the SMStext
message functionto a mobile phone or to a fax. Just onefunction (Modbus, SMS function or fax
function) can be selected at one time since the functions use the same interface.
The error alarms to a mobile phone and to a fax contain the number of the affected error status
register (FSR1/FSR2), the fault as per error status register (BitNo), the controller ID and the bit
number (Bit xx).
9.5.1 Sending text message in case of error
Currently, text messages can only be sent to the German D1 network. The corresponding access
numbers into the D1 network as well as the mobile phone number of the recipient must be set in
the PA9 level:
D1 access number: 0171 252 10 02
4
(add 0 in front when dialing from a private branch exchange)
Digits 0 to 9, P = pause, - = end, max. 22 characters
The access number is assigned by Deutsche Telekom and may alter.
Mobile phone number: 49 xxx yyyyyyy , where xxx stands for 160, 171 or any other valid
4
D1 dialing code and yyyyyy represents the specific phone number of the mobile phone you
wish the alarm to be sent to.
Digits 0 to 9, P = pause, - = end, max. 14 characters
Note!
Currently, text messages can only be sent to the German D1 network.
Functions
ModbusONCo9 -> Fb00 = OFF
Modem functionOFFCo9 -> Fb01 = OFF
Text message alarm to a mobile
phone
SMS dialing procedureOFFCo9 -> Fb07
Alarm sent per faxOFFCo9 -> Fb10 = OFF
64 EB 5474 EN
WEConfiguration
OFFCo9 -> Fb06 = ON
Page 65
Operational faults
Parameters
Access number–PA9 / configurable as required*
Phone number–PA9 / configurable as required**
* Digits 0 to 9, P = pause, - = end, max. 14 characters
** Digits 0 to 9, P = pause, - = end, max. 22 characters
WEParameter level / Range of values
9.5.2 Sending fax in case of a fault alarm
The controller type is forwarded in addition to a detailed error description. The recipient’s fax
number must be programmed in the PA9 level. Optionally, also the sender’s station ID can be
programmed; this number will then be forwarded as well. If no station ID is specified, the string
“nicht verfügbar“ (not available) is inserted.
Fax number:
4
Digits 0 to 9, P = Pause, - = End, max. 14 characters
(place an additional 0 in front when dialing from a private branch exchange)
Phone number of sending fax:
4
Digits 0 to 9, P = Pause, - = End, max. 14 characters
Functions
ModbusONCo9 -> Fb00 = OFF
Modem functionOFFCo9 -> Fb01 = OFF
Text message alarm to a mobile phoneOFFCo9 -> Fb06 = OFF
Alarm sent per faxOFFCo9 -> Fb10 = ON
Fax dialing procedureOFFCo9 -> Fb11
Parameters
Fax number–PA9 / configurable as required*
Phone number of sending controller–PA9 / configurable as required*
* Digits 0 to 9, P = pause, - = end, max. 14 characters
WEConfiguration
WEParameter level / Range of values
EB 5474 EN 65
Page 66
Communication
10Communication
Using the serial system bus interface RS-232-C, the TROVIS 5474 Boiler Controller can commu
nicate with a building control system. In combination with a suitable software for process visual
ization and communication, a complete control system can be implemented.
The following communication settings are possible:
– Operation with a dial-up modem at the RS-232-C system bus interface
Basically, communication is only established automatically when errors occur. The controller
works autonomously. Nevertheless, the modem can dial up to the controller at any time to read
data from it or otherwise influence it, if necessary. We recommend to use the modem connect
ing cable (1400-7139).
– Operation with a leased line modem at the RS-232-C system bus interface
Communication is established via a permanent connection between two leased line modems.
This setup is applied for long-distance transmissions or when different signal level converters
are used. The connection between controller and modem can also be established via the modem connecting cable (1400-7139).
– Operation at a four-wire or two-wire bus
To establish the link between controller and bus line, thesignal level needs to be converted by a
converter (SAMSON’s cable converter 1400-7308).
GLT
RS 232CRS 232C
TROVIS 5474
TROVIS 5474
RS232
RS485
RS 485
RS232
RS485
RS232
RS485
-
-
-
Fig. 7 · Network structure
66 EB 5474 EN
Page 67
Communication
10.1 Controller with RS-232 port
The system bus connection is located at the back of the controller housing (RJ-12 jack).
In this case, the controller can be connected either directly to the serial interface of a PC
(point-to-point connection)or to a (dial-up) modem. A dial-upmodem is required if the control
ler is to be connected to the telecommunications network. In this case, the controller works au
tonomously and can issue an alarm call to the building control station when errors occur. Addi
tionally, the building control station can dial up the controller, read data from it, and send new
data once the valid key number has been written to the holding register no. 40070.
On recognizing the key code from the controller as valid, the register value “1” confirms writing
permission. In any other case, the register value remains at “0”. Any further establishment of
communications requires the writing permission to beacquired byresending the key number.
Note!
If a wrong key number has been written to holding register no. 40070 for the third consecutive
time, the controller immediately interrupts themodem connectionand setsthe D6bit ofthe error
status register (Unauthorized access). As a result, the call to the configured control system is
triggered and a text message/fax sent. Bit D6 is deleted as soon as the error status register has
been read by the control system and the connection has been terminated.
In special cases, the Lock dial-up function can be selected to stop dial-up in case an error occurs. Using the Dial-up also upon corrected error function, the controller additionally informs
the building control station when a previously signaled error no longer persists.
Functions
ModbusONCo9 -> Fb00 = ON
Modem functionOFFCo9 -> Fb01 = ON
Modem dialing procedureOFFCo9 -> Fb02
Lock dial-upOFFCo9 -> Fb03
Modbus 16-bit addressingOFFCo9 -> Fb04
Dial-up also upon corrected faultOFFCo9 -> Fb00
Parameters*
Station address (ST.-NR)255PA9 / 1 to 247 (with Fb04 = ON: 1 to 999)
Baud rate (BAUD)9600PA9 / 300 to 19200
Cyclic initialization (I)30 min PA9 / 0 to 255 min
Modem dial interval between calls (P)5 minPA9 / 1 to 255 min
WEConfiguration
WEParameter level / Range of values
-
-
-
EB 5474 EN 67
Page 68
Communication
Parameters*
Modem timeout (t)5 minPA9 / 1 to 255 min
Number of redial attempts (C)5PA9 / 0 to 99
Phone number of building control station
(tELno)
Phone number of alternative recipient
(rESno)
** Digits 0 to 9, P = Pause, - = End, max. 23 characters
WEParameter level / Range of values
–PA9 / Set as required**
–PA9 / Set as required**
* –> Section 10.3 (“Description of communication parameters to be adjusted“)
10.2 System bus interface in conjunction with cable converters
RS-232/RS-485 (for four-wire bus)
A constant bus connection is required (data cable) for the operation of the controller with serial
RS-485 interface. The bus line links the control units/devices in an open ring. At the end of the
bus line, the data cable is connected to the control station using an RS-485/RS-232 converter
(e.g. TROVIS 5484).
The maximum range of the bus connection (cable length) is 1,200 meters. A maximum of
32 devices can be connected to such a segment.
If you wish to use more than 32 devices in line or need to bridge greater distances, make sure
repeaters (e.g. TROVIS 5482) are installed to replicate the signal. With 8-bit addressing, a
maximum of 246 devices can be addressed and connected to a bus.
!
Warning!
You are required to follow the relevant standards and regulations concerning lightning and
overvoltage protection on installation.
Functions
ModbusONCo9 -> Fb00 = ON
Modem functionOFFCo9 -> Fb01 = OFF
Modbus 16-bit addressingOFFCo9 -> Fb04
Parameters*
Station address (ST.-NR)255PA9 / 1 to 247 (with Fb04 = ON: 1 to 999)
Baud rate9600PA9 / 300 to 19200
* –> Section 10.3 (”Description of communication parameters to be adjusted“)
WEConfiguration
WEParameter level / Range of values
68 EB 5474 EN
Page 69
Communication
10.3 Description of communication parameters to be adjusted
Station address (ST.-NR)
This address is used to identify the controller in bus or modem mode. In a system, each control
ler needs to be assigned a unique address.
Baud rate (BAUD)
In a bus system, baud rate refers to the transfer speed between control system and controller. In
modem mode, baud rate refers to the transfer speed between controller and modem.
The baud rate adjusted at the controller must correspond with the baud rate of the control sys
tem, otherwise no communication can be established.
Cyclical initialization (I)
This parameter defines the period of time for a cyclical issue of the initialization command
“ATZ“. The command is not issued during dial-up or when connected. “ATZ“ causes the pro
file 0 to be copied to the active profile, provided the modem parameters have been set and
saved in profile 0 using a suitable terminal program.
Typical initialization of a modem with a terminal program:
AT & F (restores modem to its factory settings)
OK(response of the modem)
ATEOSO = 1(command input, EO: echo off;
SO = 1: answer on first ring)
-
-
-
Dialing pause (P)
It is recommendable to pause for approx. 3 to 5 minutes between dialing up to the control system to avoid a permanent overloading of the telecommunications network. The
defines the interval between 2 dialing attempts.
Modem time-out (t)
When the controller connects to the control station but without addressing a Modbus data point,
the connection is closed after the time specified for
tus register has not been read during the control station connection, the controller dials up to the
control station again after the
Number of redialing attempts (C)
The controller tries to dial up to the control system again, observing the
the control stationis busyor thefunction thattriggered the call has not been reset by the control
ler. Afterthe specified number of redialingattempts have failed, the controller dialsthe alterna
tive recipient.
Reset the function that triggered the call = Polling the error status register (HR 40060)
Dialing pause
Modem time-out
(P) has elapsed.
has elapsed. If the error sta
Dialing pause
Dialing pause
, in case
EB 5474 EN 69
-
-
-
Page 70
Communication
Phone number of control station (tElno)
Enter the phone number of the control system modem including the dialing code, if necessary.
Short pauses between the numbers can be entered using P (= 1 second); the end of the string is
to be marked by “–“. The phone number may include a maximum of 22 characters.
Example: “069, 2sec. pause, 4009, 1 sec. pause, 0“:069PP4009P0–(=11characters)
Phone number of alternative recipient (rESno)
Enter thephone number of an alternative recipient, ifrequired including the dialing code. Short
pauses between the numbers can be entered using P (= 1 second); “–“ indicates the end of the
string. The phone number can include max. 22 characters.
Example: “069, 1 sec. pause, 654321“: 0 6 9 P 6 5 4 3 2 1 – (= 10 characters)
Common modem settings are:
EO- Echo off
4
QO- Enable result codes
4
X3- Dial without checking for dial tone
4
% CO- Data compression off
4
\ N1- Buffer off, fault correction off
4
V1- Result codes in text format
4
% B 9600 - Baud rate 9600
4
\ VO- Standard connect result code
4
Resetting to default settings
A modem can be reset to its default settings directly at the controller after entering the key number.
The initialization settings described here are indispensable for operation on a dial-up modem.
Nevertheless, it cannot be guaranteed that data are transferred after the initialization settings
have been adjusted. Due to the broad range of modems available on the market and the diffe
rent commands, refer to the operating manual of the modem for further details.
GND TD DTRRTSRDDCD
Fig. 8 · Pin assignment of RJ-12 jack
10.4 Meter bus interface
The TROVIS 5474 Controller can communicate with up to 3 heat and water meters according to
EN 1434-3.
Details on the useof thedifferent heator watermeters canbe found in the technical documentation TV-SK 6311.
-
10.4.1 Activating the meter bus
To successfully transfer data from the heat meter (WMZ) to the controller, the heat meter must
use a standardized protocol in accordance with EN 1434-3. It is impossible to make a general
statement about which specific data can be accessed in each meter. For details on the different
meter makes, refer to the technical documentation TV-SK 6311.
All necessary function block parameters to set up communication with heat or water meters are
available in Co9 -> Fb21 to Fb23. The meter bus address, the model code, and the reading
mode must be specified. A meter bus address must be unique and correspond with the address
preset in the heat meter.
If the preset meter bus address is unknown, a single heat meter connected to the controller can
be assigned meter bus address 254. Address 255 deactivates communication with the respec
tive heat meter. The model code, which needs to be set for the respective heat meter, can be
found in TV-SK 6311.
In general, the default setting of 1434 can be used for most devices.
EB 5474 EN 71
-
Page 72
Communication
The meters can be read either automatically approx. every 24 hours (24h), continuously (con) or
when the coils (= Modbus data points) assigned to the heat meters WMZ1 to WMZ3 are written
with the value 1 over the system bus interface (CoiL).
In InF9info level, “1434“ is displayed when the meter bus isactivated. Press the enter key to get
to the display referring to the meter bus. For each of the three heat meters whose address is
not 255, “buSi“ (with i = 1, 2, 3) appears. Press the enter key again to display the following in
formation about the associated heat meter:
Flow rate (d, cm/h)
4
Volume (U, cm³)
4
Output capacity (P, kW)
4
Energy (A, Mwh, GJ)
4
Flow temperature (b, °C)
4
Return flow temperature (b, °C)
4
Meter ID number (L without enter key, H with enter key)
4
Meter bus address (sent by WMZ) (A, –)
4
Blinking values in combination with black squares in the top row of the display (fault status of
the associated meter –> TV-SK 6311) indicate different faults.
Note!
With reading mode “24h“,the displayedvalues arenot updatedby readingthe status information again; the values read during the last cycle remain unchanged.
With reading mode“con, thevalues in the levels are not continuously updated. Reopen the specific level to get current values.
-
Function
Meter busOFF
72 EB 5474 EN
WEConfiguration
255
1434
con
Co9 -> Fb21 = ON, Fb22 = ON, Fb23 = ON
Meter bus address for WMZ 1 to 3 / 0 to 255
Model code WMZ 1 to 3 / P15, PS2, 1434, CAL3, APAtO, SLS
Reading mode WMZ 1 to 3 / 24h, con, CoiL
Page 73
Communication
10.5 Memory module
The use of a memory module (accessory no. 1400-7142) is particularly useful to transfer all
data fromone TROVIS 5474 Controller to several other TROVIS 5474 Controllers. The memory
module is plugged into the RJ-12 jack integrated into the front panel. Once the module has
been connected, “74 SP“ is displayed. If the memory module already contains data from a dif
ferent TROVIS 5474 Controller, press the enter key until “SP 74" is displayed.
Pressing the enter key to confirm “74 SP“ causes the controller settings to be transferred to
4
the memory module.
Pressing the enter key to confirm “SP 74“ causes the saved controller settings to be trans
4
ferred from the memory module to the controller.
During the data transfer, the bars on the display indicate the progress. After the display stops,
remove the memory module from the controller.
-
-
EB 5474 EN 73
Page 74
Installation
11Installation
The controller consists of the housing with the electronics and the back panel with the terminals.
It is suitable for panel, wall, and top hat rail mounting (Fig. 9).
Panel mounting
1. Remove both screws (1).
2. Pull apart the controller housing and back panel.
3. Make a cut-out of 138 x 91 mm (width x height) in the control panel.
4. Insert the controller housing through the panel cut-out.
5. Insert one mounting clamp (2) each at the top and bottom or at the sides. Screw the
threaded rod towards the panel with a screwdriver such that the housing is clamped
against the control panel.
6. Install the electrical connections at the back of the housing as described in section 11.
7. Fit the controller housing.
8. Fasten both screws (1).
Wall mounting
1. Remove both screws (1).
2. Pull apart the controller housing and back panel.
3. If necessary, bore holes with the specified dimensions in the appropriate places. Fasten
the back panel with four screws.
4. Install the electrical connections at the back of the housing as described in section 11.
5. Fit the controller housing.
6. Fasten both screws (1).
Top hat rail mounting
1. Fasten the spring-loaded hook (4) at the bottom of the top hat rail (3).
2. Slightly push the controller upwards and pull the upper hooks (5) over the top hat rail.
74 EB 5474 EN
Page 75
Panel mounting
Installation
2
Back panel of the
controller
1
Wall mounting
Dimensions in mm:
W x H x D = 144 x 96 x 125
Fig. 9 · Installation
57
42
2
Top hat rail mounting
62
15
Controller housing
5
4
5
3
EB 5474 EN 75
Page 76
Electrical connection
12Electrical connection
!
Caution!
For electrical installation, you are required to observe the relevant electrotechnical regulations
of the country of use as well as the regulations of thelocal powersuppliers. Makesure all electri
cal work is performed by trained and experienced personnel!
nity, observe a minimum distance of 10 cm between the lines. Make sure the minimum dis
tance is also observed when the lines are installed in a cabinet.
The lines for digitalsignals (buslines) andanalog signals(sensor lines,analog outputs) must
4
also be installed separately!
In plants with a high electromagnetic noise level, we recommend to use shielded cables for
4
the analog signal lines. Ground the shield at one side, either at the control cabinet inlet or
outlet, using the largest possible cross-section. Connect the central grounding point and the
PE grounding conductor with a cable≥10 mm² using the shortest route.
Inductances in the control cabinet, e.g. contactor coils, are to be equipped with suitable in-
4
terference suppressors (RC elements).
Control cabinet elements with highfield strength, e.g. transformers or frequency converters,
4
should be shielded with separators providing a good ground connection.
Overvoltage protection
If signal lines are installed outside buildings or over large distances, make sure appropriate
4
surge or overvoltage protection measures are taken. Such measures are indispensable for
bus lines!
The shield of signal lines installed outside buildings must have current conducting capacity
4
and must be grounded on both sides.
Surge diverters must be installed at the control cabinet inlet.
4
Connecting the controller
The controller is connected as illustrated in the following wiring diagrams.
If individual inputs for other functions, e.g. for binary input, are to be used, it must be config
ured in the configuration levels (Co1 to Co6).
Open the housing to connect the cables. To connect the feeding cables, make holes in the
marked locationsat the top, bottom or back of therear part of the housing and fit suitable cable
glands.
-
-
-
76 EB 5474 EN
Page 77
Electrical connection
Connecting the sensors
Cables with a minimum cross-section of 2 x 0.5 mm² can be connected to the terminals at the
back panel of the housing.
Connecting the actuators
Connect cables with at least 1.5 mm² suitable for damplocations to the terminals of the control
ler output. The direction of travel needs to be checked at start-up.
Set slide switch to (+). Valves must open.
4
Set slide switch to (–). Valves must close.
4
Connecting the pumps
Connect allcables withat least 1.5 mm² to the terminals of the controller asillustrated inthe corre
sponding wiring diagram.
Legend for wiring plans:
AAAnalog outputRLReturn flow
AA_GNDCommon analog groundingRüFReturn flow sensor
AEAnalog input (general)RüFgReturn flow sensor, total
AFOutdoor temperature sensorSFStorage tank sensor
BABinary outputSG_KPotentiometer
BEBinary inputSLPStorage tank charging pump
BM_KBoiler operational faultSM_KBoiler fault alarm
FGPotentiometer (valve)SM_PuPump fault alarm
Frg_KRelease boilerSM_SCollective fault alarm
HKHeating circuitStStep of total capacity
KBoilerVFFlow sensor
KFBoiler sensorVFgFlow sensor, total
MBUSMeter busWWADHW demand
PuPumpWWZDHW forced charging
RFRoom sensor
RKControl circuit
OFF 4 to 7 Co5 -> Fb12 = ON: RK1 as return flow boost for lead boiler
OFF 1 to 3
ON 1 to 7 Co5 -> Fb14 = ON: Continuous running of lead boiler pump
Function block parameters:
Pump lag time / 0 to 90 min (5 min)
Boiler flow limit / 20 to 120 °C (55 °C)
OFF 1 to 7 Co5 -> Fb15 = ON: Function block parameter:
Boost / 0 to 30 °C (0 °C)
OFF 1 to 7 Co5 -> Fb16 = ON: Control signal deactivation after 3 x T
setting in Co5 -> Fb10
event of a malfunction
operating hours
Y
19 Parallel operation
of boilers
20 Burner activation
not dependent on
sensor VFg
Fb = Function block, WE = Default setting
OFF7Co5 -> Fb19 = ON: Both boilers operate in parallel regardless
OFF 4 to 7 Co5 -> Fb20 = ON: Boilers are controlled exclusively ac
90 EB 5474 EN
of the system load. The boilers are started up one after the
other taking into account the delay and lockout times.
cording to the boiler sensors VF1 and VF2. VFg has no affect
on the control loop.
Page 91
Co6: Sensor initialization
Fb FunctionWEAnl Comments
00 Global selection of
sensors
Sensor input 1
01
to
to
Sensor input 17
17
ONCo6 -> Fb00 = ON: Pt 100, Pt 1000
Co6 -> Fb00 = OFF: Pt 100, PTC
OFFCo6 -> Fb01 to Fb17 = ON: Select sensor: 0–20 (mA),
4–20 (mA), Pt100, Pt1000, PtC, ntC, ni200, n1000
Co6 -> Fb01 to Fb17 = OFF: Same sensor selection as in
FB00
Appendix
23 Sensor calibrationOFFCo6 -> Fb23 = ON: Sensor calibration of universal inputs
Fb = Function block, WE = Default setting
possible
Co6 -> Fb23 = OFF: No sensor calibration
Co7: Error initialization
Fb FunctionSZ WE Comments
00 Reserved
BE1
01
to
to
BE17
17
in error status
register
22 Limit monitoringOFF Can be configured over Modbus
23 Fault alarm binary
input changed
Fb = Function block, WE = Default setting, SZ = Key number
X OFF Co8 -> Fb01 = ON: Error alarm in error status register
to
Co8 -> Fb17 = ON: Error alarm in error status register
option: STEIG: Error alarm at BE1 to BE17 = CLOSED
FALL: Error alarm at BE1 to BE17 = OPEN
OFF Co8 -> Fb23 = ON: Subsequent errors are also added to the
error status register HR 60 (Bit D11)
EB 5474 EN 91
Page 92
Appendix
Co9: Modbus/meter bus
Fb FunctionSZ WE Function block parameter / Range of values (default setting)
00 ModbusON Co9 -> Fb00 = ON: Modbus active
01 Modem functionOFF Co9 -> Fb01 = ON: Modem function active
02 Modem dialing
procedure
03 Lock dial-upOFF Co9 -> Fb03 = ON: No dial-up in case an error
04 Modbus
16-bit addressing
05 Reserved
06 Text message alarm
to a mobile phone
07 SMS dialing
procedure
08 Reserved
09 Reserved
10 Alarm sent per faxOFF Co9 -> Fb10 = ON: Alarm sent per fax
11 Fax dialing
procedure
only with Co9 -> Fb06 = OFF and Co9 -> Fb10 = OFF
OFF Co9 -> Fb02 = ON: Pulse
Co9 -> Fb02 = OFF: Tone
Co9 -> Fb03 = OFF: Dial-up in case an error
OFF Co9 -> Fb04 = ON: 16-bit addressing
Co9 -> Fb04 = OFF: 8-bit addressing
OFF Co9 -> Fb06 = ON: Text message alarm to a mobile phone
only with Co9 -> Fb00 = OFF and Co9 -> Fb10 = OFF
OFF Co9 -> Fb07 = ON: Pulse
Co9 -> Fb07 = OFF: Tone
only with Co9 -> Fb00 = OFF and Co9 -> Fb06 = OFF
OFF Co9 -> Fb11 = ON: Pulse
Co9 -> Fb11 = OFF: Tone
Meter 1
21
to
to
Meter 3
23
Fb = Function block, WE = Default setting, SZ = Key number
OFF Co9 -> Fb21 = ON: Meter 1 is being processed
to
Co9 -> Fb23 = ON: Meter 3 is being processed
Function block parameters:
Meter bus address for WMZ / 0 to 255 (255)
Model code WMZ / P15, PS2,1434, CAL3, APAtO, SLS (1434)
Reading mode WMZ / 24h, con, CoiL (con)
92 EB 5474 EN
Page 93
13.2 Parameter lists
PA1: Boiler 1 (systems Anl 1 to 7)
PA2: Boiler 2 (systems Anl 4 to 7)
In the PA2 parameter level, “2” appears instead of “1” on the left of the display.
Appendix
DisplayParameter designation
Range of values (default setting)
8
56
4
0
123
9
1211 1314
10
7
1617181920
15
2122
24
23
Maximum flow temperature KF1, 2
˚C
20 to 160 °C (90 °C)
1
8
56
4
0
123
9
1211 1314
10
7
1617181920
15
2122
24
23
Minimum return flow temperature RüF1, 2
˚C
20 to 120 °C
1
8
56
4
0
123
START
9
1211 1314
10
7
1
1617181920
15
2122
24
23
Minimum activation time for boiler K1, 2
0 to 90 min
min
This time must have elapsed before the boiler switched off.
8
56
4
0
123
9
1211 1314
10
7
1617181920
15
2122
24
23
Minimum deactivation time for boiler K1, 2
STOP
0 to 90 min
min
1
This time must have elapsed before the boiler switched on.
EB 5474 EN 93
Page 94
Appendix
PA2: Separate heating circuit (only in systems Anl 1 to 3 with Co5 -> Fb13 = ON)
PA3: Direct heating circuit (only in systems Anl 1 to 3 with Co5 -> Fb13 = ON)
In the PA3 parameter level, “3” appears instead of “2” on the left of the display.
Display
0
123
0
123
0
123
0
123
Parameter designation
Range of values (default setting)
8
56
4
9
1211 13 14
10
7
1617181920
15
2122
24
23
4-point characteristic
Press to set parameters
outdoor temperature (points 1 to 4)
flow temperature (points 1 to 4) and
set-back difference (points 2 to 3).
In PA2 (PA3) only with Co2 (Co3) -> Fb10 = ON, option: 1
8
56
4
9
1211 13 14
10
7
1617181920
15
2122
24
23
4-point characteristic, point 1: Outdoor temperature
˚C
Outdoor temperatures of the points 2, 3, 4 are marked by squares
below the numbers 2, 3, 4.
–20 to 50 °C
(Point 1: –10 °C, point 2: –5 °C, point 3: 5 °C, point 4: 10 °C)
In PA2 (PA3) only with Co2 (Co3) -> Fb10 = ON, option: 1
8
56
4
9
1211 13 14
10
7
1617181920
15
2122
24
23
4-point characteristic, point 1: Flow temperature
˚C
Flow temperatures of the points 2, 3, 4 are marked by squares
below the numbers 2, 3, 4.
20 to 160 °C
(Point 1: 90 °C, point 2: 80 °C, point 3: 68 °C, point 4: 50 °C)
In PA2 (PA3) only with Co2 (Co3) -> Fb10 = ON, option: 1
8
56
4
9
1211 13 14
10
7
1617181920
15
2122
24
23
4-point characteristic: Set-back difference, point 2
˚C
Set-back difference of the point 3 is marked by square below the
number 3.
0 to 30 °C
(Point 2: 15 °C, point 3: 20 °C)
In PA2 (PA3) only with Co2 (Co3) -> Fb10 = ON, option: 1
94 EB 5474 EN
Page 95
Appendix
Display
0
123
0
123
0
123
0
123
Parameter designation
Range of values (default setting)
8
56
4
9
1211 13 14
10
7
1617181920
15
2122
23
24
Gradient, flow
0.4 to 3.2 (1.8)
In PA2 (PA3) only with Co2 (Co3) -> Fb10 = ON, select: 2.
8
56
4
9
1211 13 14
10
7
1617181920
15
2122
24
23
Level (parallel shift), flow
˚C
–30 to 30 °C (0 °C)
In PA2 (PA3) only with Co2 (Co3) -> Fb10 = ON, select: 2.
8
56
4
9
1211 13 14
10
7
1617181920
15
2122
24
23
˚C
Set-back difference
0 to 30 °C (15 °C)
In PA2 (PA3) only with Co2 (Co3) -> Fb10 = ON, select: 2.
8
56
4
9
1211 13 14
10
7
1617181920
15
2122
24
23
Fixed set point control, flow temperature set point
˚C
20 to 160 °C (70 °C)
In PA2 (PA3) only with Co2 (Co3) -> Fb10 = OFF
8
56
4
0
123
9
1211 13 14
10
7
1617181920
15
2122
24
23
Fixed set point control, set-back difference
˚C
0 to 30 °C (15 °C)
In PA2 (PA3) only with Co2 (Co3) -> Fb10 = OFF
EB 5474 EN 95
Page 96
Appendix
Display
0
123
0
123
0
123
0
123
Parameter designation
Range of values (default setting)
8
56
4
9
1211 13 14
10
7
1617181920
15
2122
24
23
Maximum flow temperature
˚C
20 to 160 °C (90 °C)
8
56
4
9
1211 13 14
10
7
1617181920
15
2122
24
23
Minimum flow temperature
˚C
20 to 120 °C (20 °C)
8
56
4
9
1211 13 14
10
7
1617181920
15
2122
24
23
Day set point (room set point)
˚C
10 to 40 °C (20 °C)
Only in PA3 with Co3 -> Fb00 = ON and Co3 -> Fb05 = ON
8
56
4
9
1211 13 14
10
7
1617181920
15
2122
24
23
Night set point (reduced room set point)
˚C
10 to 40 °C (17 °C)
56
4
0
123
7
96 EB 5474 EN
Only in PA3
8
9
1211 13 14
10
1617181920
15
2122
24
23
Sustained temperature
˚C
10 to 40 °C (10 °C)
Only in PA3
Page 97
Appendix
Display
0
123
START
0
123
STOP
0
123
0
123
4
4
4
456
56
56
56
Parameter designation
Range of values (default setting)
8
9
1211 13 14
10
7
1617181920
15
2122
24
23
Outdoor temperature deactivation value in reduced operation
˚C
–10 to 50 °C (10 °C)
8
9
1211 13 14
10
7
1617181920
15
2122
24
23
Outdoor temperature deactivation value in rated operation
˚C
0 to 50 °C (22 °C)
8
9
1211 1314
10
7
1617181920
15
2122
24
23
Times-of-use
1–7: daily
1, 2, …, 7: Monday, Tuesday, …, Sunday
8
9
1211 1314
10
7
1617181920
15
2122
24
23
Vacations
Max. 10 vacation periods
8
56
4
0
123
9
1211 1314
10
7
1
1
2
1
2
2
1617181920
15
2122
24
23
Public holidays
Max. 20 public holidays
min
EB 5474 EN 97
Page 98
Appendix
Display
0
123
0
123
0
123
0
123
Parameter designation
Range of values (default setting)
8
56
4
9
1211 1314
10
7
1617181920
15
2122
24
23
Boiler set point for DHW demand
˚C
20 to 120 °C (65 °C)
8
56
4
9
1211 1314
10
7
1617181920
15
2122
24
23
DHW demand ON (SF1)
˚C
20 to 90 °C (40 °C)
8
56
4
9
1211 1314
10
7
1617181920
15
2122
24
23
DHW demand OFF
˚C
20 to 90 °C (45 °C)
Only with Co4 -> Fb03 = ON and Co4 -> Fb04 = ON
8
56
4
9
1211 1314
10
7
1617181920
15
2122
24
23
Hysteresis (only if SF1 is selected)
˚C
0 to 30 °C (5 °C)
56
4
0
123
7
98 EB 5474 EN
Only with Co4 -> Fb03 = ON and Co4 -> Fb04 = OFF
8
9
1211 1314
10
1617181920
15
2122
24
23
Times-of-use for DHW
1–7: daily
1, 2, …, 7: Monday, Tuesday, …, Sunday
Page 99
PA5: General parameters
Appendix
DisplayParameter designation
Range of values (default setting)
9876543210
9876543210
9876543210
8
56
4
0
123
9
1211 13 14
10
1617181920
7
15
242322212019181716151413121110
Time
242322212019181716151413121110
Date (Day – Month)
242322212019181716151413121110
Date (Year)
2122
24
23
4-point characteristic
Press to set parameters
outdoor temperature (points 1 to 4)
flow temperature (points 1 to 4) and
set-back difference (points 2 to 3).
Only with Co5 -> Fb03 = ON, option: 1
EB 5474 EN 99
Page 100
Appendix
DisplayParameter designation
Range of values (default setting)
8
56
4
0
123
9
1211 13 14
10
7
1617181920
15
2122
24
23
4-point characteristic, point 1: Outdoor temperature
˚C
Outdoor temperatures of the points 2, 3, 4 are marked by squares
below the numbers 2, 3, 4.
–20 to 50 °C
(Point 1: –10 °C, point 2: –5 °C, point 3: 5 °C, point 4: 10 °C)
Only with Co5 -> Fb03 = ON, option: 1
8
56
4
0
123
9
1211 13 14
10
7
1617181920
15
2122
24
23
4-point characteristic, point 1: Flow temperature
˚C
Flow temperatures of the points 2, 3, 4 are marked by squares
below the numbers 2, 3, 4.
20 to 160 °C
(Point 1: 90 °C, point 2: 80 °C, point 3: 68 °C, point 4: 50 °C)
Only with Co5 -> Fb03 = ON, option: 1
8
56
4
0
123
9
1211 13 14
10
7
1617181920
15
2122
24
23
4-point characteristic: Set-back difference, point 2
˚C
Set-back difference of the point 3 is marked by square below the
number 3.
0 to 30 °C
(Point 2: 15 °C, point 3: 20 °C)
Only with Co5 -> Fb03 = ON, option: 1
8
56
4
0
123
9
1211 13 14
10
7
1617181920
15
2122
24
23
Gradient, flow
56
4
0
123
100 EB 5474 EN
0.4 to 3.2 (1.8)
Only with Co5 -> Fb03 = ON, option: 2
8
9
1211 13 14
10
7
1617181920
15
2122
24
23
Level (parallel shift), flow
˚C
–30 to 30 °C (0 °C)
Only with Co5 -> Fb03 = ON, option: 2
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.