Samson TROVIS 5474 Mounting And Operating Instructions

Page 1
Automation System 5400 Boiler Controller TROVIS 5474
Electronics from SAMSON
Mounting and Operating Instructions
EB 5474 EN
®
Page 2
Disclaimer of liability
Disclaimer of liability
We areconstantly developing our products and therefore, reservethe right to change the prod uct or the information contained in this document at any time without notice.
We do not assume any liability for the accuracy or completeness of these mounting and operating instructions. Moreover, we do not guaranteethat thebuyer can use the product for an intended purpose. SAMSON rejects any liability for claims by the buyer, especially claims for compensation including lost profits or any other financial loss, except the damage was caused intentionally or by gross negligence. If an essential term of the contract is breached by negligence, SAMSON’s liability is limited to the foreseeable damage.
Safety instructions
The device may only be assembled, started up or operated by trained and
4
experienced personnel familiar with the product. Proper shipping and appropriate storage are assumed.
The controller has been designed for use in electrical power systems. For
4
wiring and maintenance, you are required to observe the relevant safety regulations. The Safety shutdown function (section 8.10) does not replace the safety tem-
4
perature limiter as the boiler controller is not a safety-relevant component.
-
2 EB 5474 EN
Page 3

Contents

Contents
1 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1 Operating elements. . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1.1 Operating keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1.2 Operating switches . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.2 Operating modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.3 Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.4 Displaying data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.5 Setting the controller time . . . . . . . . . . . . . . . . . . . . . . . 11
1.6 Setting the times-of-use . . . . . . . . . . . . . . . . . . . . . . . . 13
1.6.1 Entering vacation periods . . . . . . . . . . . . . . . . . . . . . . . 15
1.6.2 Entering public holidays . . . . . . . . . . . . . . . . . . . . . . . . 16
2 Start-up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2.1 Setting the system code number and the boiler rating . . . . . . . . . . 18
2.2 Activating and deactivating functions. . . . . . . . . . . . . . . . . . 19
2.3 Changing parameters . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.4 Enter key number . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.5 Calibrating sensors . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.6 Resetting to default values . . . . . . . . . . . . . . . . . . . . . . . 24
3 Manual operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4 Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
5 Boiler functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.1 Boiler switching behavior . . . . . . . . . . . . . . . . . . . . . . . 32
5.2 Lag/lead sequence control. . . . . . . . . . . . . . . . . . . . . . . 34
5.2.1 Control without sensor VFg . . . . . . . . . . . . . . . . . . . . . . 34
5.2.2 Outdoor temperature-dependent sequence . . . . . . . . . . . . . . . 34
5.2.3 Capacity-dependent sequence . . . . . . . . . . . . . . . . . . . . . 35
5.2.4 Sequence lock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
5.2.5 Lag delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
5.3 Change in lag/lead sequence (Anl 4 to 7) . . . . . . . . . . . . . . . 36
5.3.1 Outdoor temperature-dependent change (Anl 5 and 7) . . . . . . . . . 36
5.3.2 Capacity-dependent change (Anl 5 and 7) . . . . . . . . . . . . . . . 36
5.3.3 Operating hours-dependent change (Anl 5 and 7) . . . . . . . . . . . 37
5.3.4 Change with binary input (Anl 4 to 7) . . . . . . . . . . . . . . . . . 37
5.4 Return flow boost . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.4.1 Common return flow boost . . . . . . . . . . . . . . . . . . . . . . 38
5.5 Parallel operation (Anl 7) . . . . . . . . . . . . . . . . . . . . . . . 38
EB 5474 EN 3
Page 4
Contents
5.6 Operating hours counter. . . . . . . . . . . . . . . . . . . . . . . . 38
5.7 Boiler pump control . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.8 Boiler sensor acting as a thermostat . . . . . . . . . . . . . . . . . . 39
5.9 Modulation feedback . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.10 Operational alarm . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.11 Return flow sensor acting as a thermostat. . . . . . . . . . . . . . . . 41
6 Functions of the heating circuit . . . . . . . . . . . . . . . . . . . . 42
6.1 Outdoor temperature-dependent advance heating . . . . . . . . . . . 42
6.2 Optimization using a room sensor . . . . . . . . . . . . . . . . . . . 42
7 Functions of the DHW circuit. . . . . . . . . . . . . . . . . . . . . . 44
7.1 DHW heating in the storage tank system (Anl 1 to 3) . . . . . . . . . . 44
7.1.1 Priority circuit (Anl 1 to 3) . . . . . . . . . . . . . . . . . . . . . . . 45
7.2 Forced charging of the DHW storage tank (Anl 1 to 7) . . . . . . . . . 46
7.3 Thermal disinfection (Anl 1 to 3) . . . . . . . . . . . . . . . . . . . . 47
7.4 External DHW demand (Anl 1 to 7) . . . . . . . . . . . . . . . . . . 48
8 System-wide functions . . . . . . . . . . . . . . . . . . . . . . . . 49
8.1 Weather-compensated control . . . . . . . . . . . . . . . . . . . . . 49
8.1.1 Gradient characteristic . . . . . . . . . . . . . . . . . . . . . . . . 50
8.1.2 4-point characteristic . . . . . . . . . . . . . . . . . . . . . . . . . 51
8.2 Fixed set point control . . . . . . . . . . . . . . . . . . . . . . . . . 52
8.3 Differential temperature control using variable weighting factors. . . . . 53
8.4 Deactivation depending on outdoor temperature . . . . . . . . . . . . 53
8.5 Summer mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
8.6 Delayed outdoor temperature adaptation. . . . . . . . . . . . . . . . 54
8.7 Automatic summer time/winter time changeover . . . . . . . . . . . . 55
8.8 Frost protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
8.9 Forced operation of the pumps. . . . . . . . . . . . . . . . . . . . . 56
8.10 Flow temperature limitation . . . . . . . . . . . . . . . . . . . . . . 56
8.11 Control mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
8.11.1 Three-step control . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
8.11.2 On/off control . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
8.11.3 Continuous control . . . . . . . . . . . . . . . . . . . . . . . . . . 58
8.12 Control signal deactivation. . . . . . . . . . . . . . . . . . . . . . . 59
8.13 Processing of external demand. . . . . . . . . . . . . . . . . . . . . 59
8.14 Feedforwarding the outdoor temperature . . . . . . . . . . . . . . . . 59
8.15 Locking of changed settings . . . . . . . . . . . . . . . . . . . . . . 60
9 Operational faults . . . . . . . . . . . . . . . . . . . . . . . . . . 61
4 EB 5474 EN
Page 5
Contents
9.1 Error list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
9.2 Sensor failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
9.3 Displaying the lead/collective error alarm . . . . . . . . . . . . . . . 62
9.4 Error status register . . . . . . . . . . . . . . . . . . . . . . . . . . 62
9.5 Error alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
9.5.1 Sending text message in case of error . . . . . . . . . . . . . . . . . 64
9.5.2 Sending fax in case of a fault alarm . . . . . . . . . . . . . . . . . . 65
10 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
10.1 Controller with RS-232 port . . . . . . . . . . . . . . . . . . . . . . 67
10.2 System bus interface in conjunction with cable converters
RS-232/RS-485 (for four-wire bus) . . . . . . . . . . . . . . . . . . 68
10.3 Description of communication parameters to be adjusted . . . . . . . . 69
10.4 Meter bus interface . . . . . . . . . . . . . . . . . . . . . . . . . . 71
10.4.1 Activating the meter bus . . . . . . . . . . . . . . . . . . . . . . . . 71
10.5 Memory module. . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
11 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
12 Electrical connection. . . . . . . . . . . . . . . . . . . . . . . . . . 76
13 Appendix. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
13.1 Function block list . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
13.2 Parameter lists . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
13.3 Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
13.4 Sensor resistance tables . . . . . . . . . . . . . . . . . . . . . . . 115
13.5 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
13.6 Customer data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
EB 5474 EN 5
Page 6
Operation
1 Operation
The controller is ready for use with the temperatures and time schedules preset by the manufac turer. On start-up, the current time and date need to be set at the controller (–> section 1.5).
1.1 Operating elements
The operating controls are located in the front panel of the controller and protected by a Plexi glas door.
1.1.1 Operating keys
Changeover key
(press using a pointed object such as a pen) Switch from the info level to the parameter and configuration level and back
Reset key
(press using a pointed object such as a pen) Press to reset accessible parameters to their default settings; the controller must be in the configuration level
Arrow keys
– To scroll within levels – To change values
Enter key
– To access levels – Access parameters and functions to edit them – Confirm settings – Display set points in the info level
-
-
6 EB 5474 EN
Page 7
1.1.2 Operating switches
Mode selector switch
Selector switch
2
1
1 1
22O12
Operation
Automatic mode with switchover between day mode and night mode
Automatic mode with switchover between day mode and stand-by mode
Day mode (rated operation) Night mode (reduced operation)
Manual/maintenance mode Stand-by mode
Boiler 1 and 2 in operation; automatic lag/lead sequence change
Boiler 1 in operation, Boiler 2 switched off
Boiler 2 in operation, Boiler 1 switched off
Boiler 1 and 2 switched off Boiler 1 and 2 in operation;
Boiler 2 as lead boiler Boiler 1 and 2 in operation;
Boiler 1 as lead boiler
EB 5474 EN 7
Page 8
Operation
Correction switch for the flow temperature
Set point set-back by 2.5 °C per notch No change in set point Set point raised by 2.5 °C per notch
+
0
1.2 Operating modes
Day mode (rated operation)
Regardless ofthe programmed times-of-use and summer mode,the set points relevant for rated operation are used by the controller.
Night mode (reduced operation)
Regardless of the programmed times-of-use and summer mode, the set points relevant for re­duced operation are used by the controller.
Stand-by mode
The controller is switched off. The boilers only work when there is a demand for DHW or a de­mand for an external set point. The protective functions remain active.
Automatic mode
During the programmed times-of-use, the controller works in rated operation. Outside these times-of-use, the controller is in reduced operation or stand-by mode, depending on the set tings. The controller switches automatically between both operating modes.
Maintenance mode
Pumps are controlled manually (–> section 3). Control is not possible. Use the maintenancemode just for maintenance purposes and for emis sion measurements. The default setting of the circulation pumps is set for constant operation.
-
-
8 EB 5474 EN
Page 9
1.3 Display
Operation
During operation, the display indicates the current time as well as informationabout the opera tion of the controller. The times-of-use are represented by black squares below the row of num bers at the top of the display. Icons indicate the operating status of the controller.
8
1
2
3
4 5
6
7
8
9
1 Automatic operation 2 Rated operation 3 Vacation mode 4 Reduced operation 5 Public holiday mode 6 Summer mode 7 Frost protection
0
123
1
4
2
10
9
10
7
1 2
1 2
56
8 Manual/maintenance
mode 9 Malfunction 10 Boiler and boiler stages 11 Valve in control circuit 1
Open: Left arrow
Closed: Right arrow 12 Boiler pump 1 ON
1211 1314
1617181920
15
1
11 12 13 14 15
2122
24
23
2
13 Valve in control circuit 2
Open: Left arrow
Closed: Right arrow 14 Boiler pump 2 ON 15 DHW heating
-
-
Fig. 1 · Icons
The controller status can be displayed in the operating level (–> section 1.4).
EB 5474 EN 9
Page 10
Operation
1.4 Displaying data
Controller time, measured values, set points and limits, times-of-use, public holidays and vaca tion periods can be retrieved and displayed in th
131). The various levels are listed in section 13.3.
InF1: Boiler 1
4
InF2: System Anl 1 to 3, Co5 -> Fb13 = ON: Separate heating circuit
4
4 4 4 4 4
Proceed as follows:
System Anl 4 to 7: Boiler 2 InF3: System Anl 1 to 3, Co5 -> Fb13 = ON: Direct heating circuit InF4: DHW heating InF5: General information, e.g. times-of-use InF8: Error initialization InF9: Modbus and meter bus communication
Select info level. Open info level. Scroll to read the various datapoints of the selected info level that appear one after
the other. Compare the set point/limit with the actual value. Press both arrows keys simultaneously:
Return to the display with time.
e InF1toInF9
info levels (-> Fig. 10 on page
-
10 EB 5474 EN
Page 11
Operation
1.5 Setting the controller time
The current time and date need to be set immediately after start-up and after a power failure lasting longer than 24 hours. This is indicated by the time blinking on the display.
PA5
The time is set in the
Proceed as follows:
9876543210
parameter level.
242322212019181716151413121110
Switch to the configuration and parameter level. Display:
PA1
9876543210
1
9876543210
242322212019181716151413121110
242322212019181716151413121110
Select PA5 parameter level.
Open PA5 parameter level. Display: Time
Activate editing mode for the controller time.
blinks.
Change time.
9876543210
242322212019181716151413121110
Confirm time. Display: Date (Day-Month)
Activate editing mode for the date.
blinks.
Change date.
EB 5474 EN 11
Page 12
Operation
9876543210
242322212019181716151413121110
Confirm date. Display: Year
Activate editing mode for the controller time.
blinks. Change year. Confirm year.
Exit PA5 parameter level.
Return to the operating level.
Note!
The controller automatically returns to the operating level if the keys are left unpressed for two minutes.
12 EB 5474 EN
Page 13
Operation
1.6 Setting the times-of-use
Two times-of-use can be set for each day of the week. If only one time-of-use is required, the start and stop times of the second time-of-use must be programmed to identical times.
Parameters
Period/day 1–7 PA5 / 1–7, 1 to 7 Start first time-of-use 7:00 PA5 / 00:00 to 24:00h; in steps of 30 minutes Stop first time-of-use 12:00 PA5 / 00:00 to 24:00h; in steps of 30 minutes Start second time-of-use 12:00 PA5 / 00:00 to 24:00h; in steps of 30 minutes Stop second time-of-use 22:00 PA5 / 00:00 to 24:00h; in steps of 30 minutes
Proceed as follows:
9876543210
242322212019181716151413121110
WE Parameter level / Range of values
Switch to the configuration and parameter level. Display:
PA1
Select PA5 parameter level. Open PA5 parameter level.
Display: Controller time
9876543210
9876543210
242322212019181716151413121110
242322212019181716151413121110
Select datapoint for times-of-use. Display:
1
Activate editing mode for times-of-use. Display: 1–7
Select period/day for which the times-of-use are to be valid: 1–7 = Monday to Sunday, 1 = Monday, 2 = Tuesday, …, 7 = Sunday
EB 5474 EN 13
Page 14
Operation
9876543210
START
242322212019181716151413121110
Activate editing mode for period/day. Display: START; blinks.
Edit start time (steps of 30 minutes).
9876543210
STOP
242322212019181716151413121110
Confirm start time. Display:
STOP
Edit stop time (steps of 30 minutes). Confirm stop time.
Display:
START
The second time-of-use is set like the first time-of-use.
To set the times-of-use for each day, repeat the instructions in the fields highlighted in gray.
Select
End
on the display. Exit the datapoint for times-of-use. Exit the parameter level. Return to the operating level.
Note!
Do notuse the 1–7 menu to check the programmed times-of-use. On openingthis menu, the ti mes-of-use are reset to their default settings.
-
Note!
The controller automatically returns to the operating level if the keys are left unpressed for two minutes.
14 EB 5474 EN
Page 15
Operation
1.6.1 Entering vacation periods
When the switch position Automatic operation with switchover between day mode and night mode is selected, night set points (reduced set points) are used by the controller. When the
switch position Automatic operation with switchover between day mode and stand-by mode is selected, the system is switched off. The frost protection function remains active.
A maximum of 10 vacation periods may be entered.
Parameter
Vacation periods PA5 / 01.01 to 31.12
Proceed as follows: Switch to the parameter and configuration level.
9876543210
242322212019181716151413121110
To enter additional vacations, re-select in the fields highlighted in gray.
Exit the parameter level. Return to the operating level.
WE Parameter level / Range of value
Display:
PA1
Select PA5 parameter level. Open PA5 parameter level. Display: Controller time Select datapoint for vacation period. Display: Open data point for vacation period. Display: If applicable, select
– – – –
.
START
Activate editing mode for vacation periods.
blinks. Set start date of vacation period. Confirm start date of the vacation period.
Display:
STOP
Set end of vacation period. Confirm end of the vacation period.
––––
(between 31.12 and 01.01) and repeat the steps
Note!
In systems Anl 1 to 3 with integrated DHW heating (Co5 -> Fb13 = ON), the vacations entered also apply to the DHW heating with the setting Co4 -> Fb10 = ON.
EB 5474 EN 15
Page 16
Operation
Vacation periods that are not assigned to a specific date should be deleted by the end of the year so that they are not carried on into the following year.
Deleting vacation periods:
Select the vacation period you wish to delete in the datapoint for vacation periods. Confirm selection. Select
– – – –
.
Delete vacation period.
Note!
The controller automatically returns to the operating level if the keys are left unpressed for two minutes.
1.6.2 Entering public holidays
The times-of-use programmed for Sunday apply on public holidays. A maximum of 20 public holidays can be entered.
Parameter
Public holidays PA5 / 01.01 to 31.12
WE Parameter level / Range of value
Proceed as follows: Switch to the parameter and configuration level.
Display:
PA1
Select PA5 parameter level. Open PA5 parameter level. Display: Controller time
8
56
4
0
123
9
1211 1314
10
7
1617181920
15
2122
24
23
Select datapoint for public holidays. Display:
Open datapoint for public holidays. Display:
If applicable, select
START
– – – –
.
Activate editing mode for public holiday.
blinks. Edit public holiday. Confirm public holiday.
16 EB 5474 EN
Page 17
Operation
To enter additional public holidays, re-select
––––
(between 31.12 and 01.01) and repeat the
steps in the fields highlighted in gray.
Exit the parameter level. Return to the operating level.
Note!
In systems Anl 1 to 3 with integrated DHW heating (Co5 ->Fb13 =ON), thepublic holidaysen tered also apply to the DHW heating with the setting Co4 -> Fb10 = ON.
Public holidays that are not assigned to a specific date should be deleted by the end of the year so that they are not carried on into the following year.
Deleting a public holiday:
Select the holiday you wish to delete in the datapoint for public holidays. Confirm selection.
– – – –
Select
.
Delete the public holiday.
Note!
The controller automatically returns to the operating level if the keys are left unpressed for two minutes.
-
EB 5474 EN 17
Page 18
Start-up
2 Start-up
2.1 Setting the system code number and the boiler rating
7 different hydraulic schematics are available. Each system configuration is represented by a system code number (Anl). The different schematics are dealt with in section 4. Available con troller functions are described in sections 5 to 8.
Changing the system code number resets previously adjusted function blocks to their default set tings (WE). Function block parameters and settingsin theparameter level remain unchanged.
The system code number is set in the parameter and configuration level.
Proceed as follows:
Switch to the parameter and configuration level.
level. level.
1
Anl 1
PA1
Display shows: Select
Anl
Open
Anl
Display: Select system code number (Anl).
-
-
System Anl 1 System Anl 2 System Anl 3
System Anl 4
System Anl 5
System Anl 6
System Anl 7
1
Anl 1
1
Anl 2
2
1
Anl 3
2
1
1
2
Anl 4
1
1
2 1
2
Anl 5
2
1
1
2
2
Anl 6
1
1
2
2
Anl 7
Confirm system code number (Anl). The burner and stage icons for burner 1 blink. The boiler rating is shown.
18 EB 5474 EN
Single boiler for one-stage burner Single boiler for two-stage burner Single boiler for modulating burner Double boiler for one-stage condensing boiler and
two-stage low-temperature boiler
Double boiler for 2 two-stage burners
Double boiler for modulating and two-stage burner
Double boiler for two modulating burners
Page 19
Start-up
Set the required rating. Set first the capacity of the basic stage and then the total capacity of the burner of two-stage and modulating burners.
Confirm the rating. Set the capacity of the second burner in systems Anl 4 to 7.
End
Select Exit the
Display:
on the display.
Anl
level.
Co1
2.2 Activating and deactivating functions
A function is activated or deactivated in the associated function block. The numbers 0 to 24 in the top row of the display represent the respective function block numbers. When a configura tion level is opened, the activated function blocks are indicated by a black square on the right-hand side below the function block number. The function blocks are described in sec­tion 13.2.
The functions are arranged in topic groups:
Co1: Boiler 1
4
Co2: Systems Anl 1 to 3, Co5 -> Fb13 = ON: separate heating circuit
4
Systems Anl 4 to 7: Boiler 2
Co3: Systems Anl 1 to 3, Co5 -> Fb13 = ON: direct heating circuit
4
Co4: DHW heating
4
Co5: General functions
4
Co6: Sensor initialization
4
Co8: Error initialization
4
Co9: Modbus and meter bus communication
4
-
Proceed as follows:
Switch to the parameter and configuration level. Display shows:
Switch to the configuration level (-> Fig. 10, page 131). Open the configuration level.
PA1
EB 5474 EN 19
Page 20
Start-up
Select function block. Activate editing mode for function block.
The function block number starts to blink.
0 0 0 0
If section 2.4).
Activate function block (Fb = ON). An activated function block is indicated by a black square below (right) the function block number in the top row of the controller display.
or:
Deactivate function block (Fb = OFF). Confirm setting.
If the function block is not closed, further function block parameters can be adjusted. Proceed as follows: Make the desired changes and confirm. If applicable, the next function block parameter is displayed. Confirm all parameters to exit the opened function block.
To adjust additional function blocks within the configuration level, repeat the steps in the fields highlighted in gray.
Exit the configuration level. Return to the operating level.
appears on the display, the key number needs to be entered first (refer to
Note!
The controller automatically returns to the operating level if the keys are left unpressed for two minutes.
20 EB 5474 EN
Page 21
2.3 Changing parameters
Start-up
Depending on the activated functions, not all parameters listed in the parameter list in the Ap pendix (–> section 13.2) might be available.
The parameters are arranged in topic groups:
PA1: Boiler 1
4
PA2: Systems Anl 1 to 3, Co5 -> Fb13 = ON: separate heating circuit
4
4 4 4 4
Proceed as follows:
To adjust additional parameters, repeat the steps in the fields highlighted in gray.
Systems Anl 4 to 7: Boiler 2 PA3: Systems Anl 1 to 3, Co5 -> Fb13 = ON: direct heating circuit PA4: DHW heating PA5: General parameters PA9: Modbus and meter bus communication
Switch to the parameter and configuration level. Display: Select parameter level (-> Fig. 10, page 131). Open the parameter level. Select parameter. Activate editing mode for parameter. Change parameter. Confirm parameter setting.
Exit the parameter level. Return to the operating level.
PA1
-
Note!
The controller automatically returns to the operating level if the keys are left unpressed for two minutes.
EB 5474 EN 21
Page 22
Start-up
2.4 Enter key number
Some functions are protected against unintentional or unauthorized access. These functions can only be activated or deactivated after the valid key number has been entered. The valid key number for initial start-up can be found on page 127. To avoid unauthorized use of the key number, remove the page or make the key number unreadable.
Proceed as follows:
0 0 0 0
The key number remains active for approx. 10 minutes.
blinks on the display. Set valid key number. Confirm key number.
When the correct key number is entered, the function block to be changed blinks on the display. When an incorrect key number is entered, the controller returns to the next configuration level.
2.5 Calibrating sensors
The connected sensors are calibrated in the Co6 configuration level. The following applies:
Co6 -> Fb00 = ON: Pt 100/Pt 1000 sensors mixed (default setting)
4
Co6 -> Fb00 = OFF: Pt 100/PTC sensors mixed
4
The resistance values of the sensors can be found on page 115. Each universal input can be configured separately.
The function block parameter includes the following types: Ni 200/1000, PTC, NTC, Pt 100/1000, (0/4 to 20) mA. The function blocks Co6 -> Fb01 to Fb17 correspond to the bi nary inputs BE1 to BE17 in the terminal wiring plan (–> page 78 onwards). Activate the function block for the required sensor and select the function block parameter which matches the type of the input signal.
Note!
Pt 100 orPt 1000 sensor should be used to measure theflow temperature as only these types of sensor are able to measure temperatures reaching up to 160 °C (maximum temperature of the flow temperature set point).
-
22 EB 5474 EN
Page 23
Start-up
If the temperature values displayed at the controller differ from the actual temperatures, the measured values of all connected sensors can be changed or readjusted. To calibrate a sensor, the currently displayed sensor value must be changed such that it matches the temperature (ref erence temperature) measured directly at the point of measurement.
Perform the calibration in function block Fb23 in Co6.
Proceed as follows:
Switch to the parameter and configuration level. Display:
PA1
Select Co6 configuration level. Open Co6 configuration level. Select function block Fb23. Confirm setting.
Display:
0 0 0 0
Enter currently valid key number. The function block Fb23 blinks on the display.
Activate function block. Confirm setting. Select the function block for the sensor to be calibrated:
The function blocks Co6 -> Fb01 to Fb17 correspond to the binary inputs BE1 to BE17 in the terminal wiring plan (–> page 78 onwards) depending on the selected system code number (Anl), e.g. Co6 -> Fb03 for sensor VFg (all systems).
Activate editing mode for sensor. Fb_ blinks on the display.
Display measured temperature. Activate editing mode for measured temperature.
Measured temperature blinks. Correct measured temperature.
Read the actual temperature directly from the thermometer at the point of measure
-
ment and enter this value as the reference temperature. Confirm corrected measured temperature.
Additional sensors are calibrated similarly.
-
EB 5474 EN 23
Page 24
Start-up
Select function block Fb23. Activate editing mode for function block Fb23. Deactivate function block Fb23. Confirm setting. Select
End
on the display. Exit the configuration level. Return to the operating level.
Note! The adjusted sensor values are not reset by the function for resetting to default values.
2.6 Resetting to default values
All parametersand function blocks that can be setwithout entering the key number can bereset to their default settings (WE).
Proceed as follows:
Reset to default settings. Function blocks and parameters are reset to their default settings (WE).
Note!
Resetting protected parameters to their default settings is only possible when the key number is still active. The controller isready foroperation with its default settings. You just need to set the correctdate and current time.
24 EB 5474 EN
Page 25
Manual operation
3 Manual operation
All the settings of the outputs canbe setin the manual mode, see wiring plan(-> section12).
Proceed as follows: Set mode selector switch to .
After approx. 10 seconds the boilers start operation at full capacity. Display:
HAnd
9876543210
242322212019181716151413121110
Select Open the manual level. Display: Select output:
bA: 1, 2 BA1 and BA2 3-Pt: 1, 2 BA3 and BA4, BA5 and BA6
1
PU: 1, 2 BA7 and BA8 StUF: 1, 2, 3, 4 BA9 to BA12 AnAL: 1, 2 AA 1, 2 (RK1, RK2)
Activate editing mode for output.
The display blinks.
Activate output, increase value.
Three-point stepping output: OPEN
or:
Deactivate output, decrease value.
Three-point stepping output: CLOSED
and:
Three-point stepping output: STOP
Confirm setting. The changed values remain valid as long as the manual mode is active.
Slide mode switch to .
Exit the manual level.
on the display.
bA1
Note! In manual mode, frost protection does not function.
EB 5474 EN 25
Page 26
Systems
4 Systems
7 hydraulic schematics are available.
System code
number (Anl)
1 2 3
4
5 Double boiler for 2 two-stage burners Change in lag/lead sequence either
6 Double boiler for modulating und
7 Double boiler for two modulating
System description Comments
Single boiler for one-stage burner Single boiler for two-stage burner Single boiler for modulating burner Double boiler for one-stage condensing boiler
and two-stage low-temperature boiler
two-stage burners
burners
Optionally separate heating circuit and DHW heating can be controlled
Lag sequence without automatic lag/lead sequence change
depending on operating hours, on outdoor temperature or boiler capacity
Lag sequence without automatic lag/lead sequence change
Change in lag/lead sequence either depending on operating hours, on outdoor temperature or boiler capacity
26 EB 5474 EN
Page 27
System Anl 1 with Co5 -> Fb13 = OFF
RK1
RüFg
Systems
VFg
AF
VL
RL
KF1
RüF1
1
Pu1
System Anl 1 with Co5 -> Fb13 = ON
VF2
Pu2
RK2
VFg
RK1
KF1
RüF1
1
Pu1
RüFg
RüF2
K1 One-stage burner
Pu3
SLP
RF
SF1 SF2
AF
K1 One-stage burner
EB 5474 EN 27
Page 28
Systems
System Anl 2 with Co5 -> Fb13 = OFF
KF1
RüF1 1 2
System Anl 2 with Co5 -> Fb13 = ON
VF2
Pu2
RK2
VFg
Pu1
RK1
RüF2
RüFg
VFg
K1 Two-stage burner
RF
Pu3
AF
VL
RL
AF
28 EB 5474 EN
KF1
RüFg
RK1
Pu1
RüF1
1 2
SLP
SF1 SF2
K1 Two-stage burner
Page 29
System Anl 3 with Co5 -> Fb13 = OFF
Systems
KF1
RüF1
System Anl 3 with Co5 -> Fb13 = ON
VF2
Pu2
RK2
VFg
Pu1
RK1
RüF2
VFg
RüFg
K1 Modulating burner
Pu3
AF
VL
RL
RF
AF
KF1
RüF1
RK1
Pu1
RüFg
SLP
SF1 SF2
K1 Modulating burner
EB 5474 EN 29
Page 30
Systems
System Anl 4
System Anl 5
KF1
VFg
RüFg
RK1 RK2
Pu1 Pu2
1
RüF1
KF2
1
2
RüF2
K1 One-stage condensing boiler
VL
RL
AF
K2 Two-stage low-temperature boiler
VFg
RüFg
VL
RL
AF
30 EB 5474 EN
KF1
RK1 RK2
Pu1 Pu2
1 2
RüF1
KF2
1
2
RüF2
K1, K2 Two-stage burner
Page 31
System Anl 6
Systems
KF1
System Anl 7
RK1 RK2
Pu1 Pu2
RüF1
KF2
1 2
RüF2
RüFg
K1 Modulating burner K2 Two-stage burner
RüFg
VFg
VFg
VL
RL
VL
RL
AF
AF
KF1
RK1 RK2
Pu1 Pu2
RüF1
KF2
RüF2
K1, K2 Modulating burner
EB 5474 EN 31
Page 32
Boiler functions
5 Boiler functions
5.1 Boiler switching behavior
The
Minimum activation and deactivation time
ters described in following. To be able to keep the cooling off periods between two activation phases, a boiler is first switched on when the time entered in
Minimum deactivation time
activation. To ensurethe burning of residues left over during the start-upphase, a boiler is switched off first after the time entered in
Parameters
Minimum activation time 1 min PA1, PA2* / 0 to 90 min Minimum deactivation time 2 min PA1, PA2* / 0 to 90 min
Minimum activation time
On/off boiler
A boiler is activated when the flow temperature falls below the flow temperature set point by
Hysteresis
the
Lockout time
the
(Fig. 3). After the operational feedback message (burner firing –> section 5.10),
must elapse before the boiler is switched to the next stage. If the flow tempera­ture is expected toreach theset pointrange withinthe to the next stage. A boiler stage is switched off when the flow temperature exceeds theflow temperature set point by the
Hysteresis
.
Modulating boiler
A boiler starts to operate with its minimum capacity if the flow temperature falls below the flow temperature set point by the firing –>section 5.10), the
Hysteresis
Lockout time
(Fig. 2). After the operational feedback message (burner
troller modulates the boiler capacity to match the actual energy requirement according to the flow temperature set point.
parameters have priority over allother parame
has passed since the last de
has elapsed.
WE Parameter level / Range of values
* Only in systems Anl 4 to 7
Tolerance time
, the boiler doesnot switch
must elapsebefore the modulation is enabled. The con
-
-
-
Parameters
Hysteresis 3 °C PA5 / 1 to 20 °C Tolerance time 30 min PA5 / 0 to 99 min Lockout time 2 min PA5 / 0 to 99 min
WE Parameter level / Range of values
32 EB 5474 EN
Page 33
Flow temperature set point + Hysteresis
Boiler functions
t
[°C]
VL
Flow temperature set point
Flow temperature set point – Hysteresis
Burner start
Activation of
boiler stage
Fig. 3 · Criteria for switching the boiler stages
tVL[°C]
Flow temperature set point + Hysteresis
Flow temperature set point
Flow temperature set point – Hysteresis
Lockout time
Operational alarm f. burner
t [s]
Tolerance time
t [s]
Burner start
Activation of
boiler stage
Lockout time
Operational alarm f. burner
Fig. 2 · Criteria for switching the modulating boiler
Tolerance time
EB 5474 EN 33
Page 34
Boiler functions
5.2 Lag/lead sequence control
The boilers are released depending on the configuration:
Co1, Co2* -> Fb00 = OFF: Boiler released according to the position of the mode selector
4
switch Co1, Co2* -> Fb00 = ON: Boiler 1 is not released if binary input BE17 is closed, pro
4
vided Boiler 1 is not locked by the mode switch. Boiler 2* is released if binary input BE16 is closed, provided Boiler 2 is not locked by the mode switch.
Function
Release of boiler K1, 2 OFF Co1, Co2* -> Fb00
WE Configuration
* Only in systems Anl 4 to 7
5.2.1 Control without sensor VFg
The Burner activation independent from sensor VFg function allows the boiler to be switched on independently from sensor VFg, i.e. exclusively according to boiler sensors VF1 and VF2. Other functions which have an effect on the lag and lead sequence control of the boiler in two-boiler systems do not affect the boiler which works independently any more. On activating the Continuous running of pump function, the boiler pumps react like the pumps of master controller in normal systems.
Functions
Burner activation not dependent on sensor VFg
Continuous running of pump OFF Co5 -> Fb14
WE Configuration OFF Co5 -> Fb20 = ON
-
5.2.2 Outdoor temperature-dependent sequence
If the outdoor temperature is above the limit entered in just the lead boiler always remains in operation. The lag boiler is not even activated when the maximum capacity of the lead boiler is insufficient to achieve an increased flow temperature. The lag boiler is first released when the outdoor temperature is lower than the limit entered in
Temperature tAfor releasing sequence
The limit entered in short-term demand above the limit can be compensated for without any loss in comfort by pro longing the operating time of the lead boiler. This depends on the performance of the lead boiler.
34 EB 5474 EN
Temperature tAfor releasing sequence
after t = 2 x
Temperature tAfor releasing sequence,
Lockout time
.
must be selected to ensure that a
-
Page 35
Boiler functions
Function
Releasing sequence ON Co5 -> Fb07 = ON
Parameters
Lockout time 2 min PA5 / 0 to 99 min Temperature tAfor releasing sequence 12 °C PA5 / –40 to 50 °C
WE Configuration
WE Parameter level / Range of values
5.2.3 Capacity-dependent sequence
The lead boiler is activated when theflow temperaturefalls belowthe flowtemperature setpoint
Hysteresis
by the the second stage. The second boiler is also activated if 90 % of its maximum load is not sufficient over thetime period oft=2x temperature set point and the set point hysteresis is not reached within the tolerance time. The lag boiler is switched off when one of the following conditions is fulfilled:
The current load of both boilers is less than 90 %.
4
The actualtemperature is greater than the set point and hysteresis added together as wellas
4
its tendency shows that the temperature willnot fallbelow this total within the tolerance time.
Function
Releasing sequence ON Co5 -> Fb07 = OFF
Parameter
Lockout time 2 min PA5 / 0 to 99 min
. In the event of a demand for increased capacity, the lead boiler switches to
Lockout time
to increasethe flow temperature to therequired flow
WE Configuration
WE Parameter level / Range of values
5.2.4 Sequence lock
The binary input BE11 is used to lock the sequence. The input of the outdoor temperature is de termined by the binary input. The outdoor sensor is not required.
Function
Outdoor sensor ON Co5 -> Fb00 = OFF, select: FoAUS
WE Configuration
5.2.5 Lag delay
The
Lag delay
mands. The second boiler is first switched on when required after the time in elapsed. The time countdown is shown in the InF5 level.
parameter helps minimize losses during start-up in the event of short-term de
Lag delay
EB 5474 EN 35
has
-
-
Page 36
Boiler functions
Parameter
Lag delay 10 min PA5 / 0 to 90 min
WE Parameter level / Range of values
5.3 Change in lag/lead sequence (Anl 4 to 7)
The lag/lead sequence can be changed depending on the outdoor temperature, operating hours or capacity. The change in lag/lead sequence is only effective when the mode selector switch is set to and with the configuration Co5 -> Fb20 = OFF.
Note!
A change in lag/lead always takes place when the controller detects a fault in the lead boiler regardless of the configuration.
2
1
5.3.1 Outdoor temperature-dependent change (Anl 5 and 7)
The outdoor temperature-dependent change in lag/lead sequence is only appropriate when boilers with varying capacity are used. The lead boiler is determined by comparing the mean outdoor temperature overthree dayswith
Reverse sequence limit t
the
Outdoor temperature >
4
boiler is the boiler with the smallest unit capacity Outdoor temperature <
4
boiler is the boiler with the largest unit capacity
Functions
Automatic change in lag/lead sequence ON Co5 -> Fb09 = ON Condition for change in lag/lead sequence ON Co5 -> Fb10 = OFF, select: 1
Parameter
Outdoor temperature limit for lag/lead sequence change
parameter:
A
Outdoor temperature limit for lag/lead sequence change
Outdoor temperature limit for lag/lead sequence change
WE Configuration
WE Parameter level / Range of values 15 °C PA5 / –40 to 50 °C
: Lead
: Lead
5.3.2 Capacity-dependent change (Anl 5 and 7)
The lead boiler is the boiler which had the lowest average capacity over the past three days.
Functions
Automatic change in lag/lead sequence ON Co5 -> Fb09 = ON
36 EB 5474 EN
WE Configuration
Page 37
Boiler functions
Condition for change in lag/lead sequence ON Co5 -> Fb10 = OFF, select: 2
5.3.3 Operating hours-dependent change (Anl 5 and 7)
After a fixed amount of time haselapsed, countingin hoursfrom the time when the last lag/lead sequence tookplace ( role as lead boiler. The elapsed operating hours since the last change in lag/lead sequence are shown in the InF5 level.
Functions
Automatic change in lag/lead sequence ON Co5 -> Fb09 = ON Condition for change in lag/lead sequence ON Co5 -> Fb10 = ON
Parameter
Time interval for lag/lead sequence change 168 h PA5 / 1 to 999 h
Time intervalfor lag/lead sequence change)
WE Configuration
WE Parameter level / Range of values
, theother boiler takes on the
5.3.4 Change with binary input (Anl 4 to 7)
The binary input BE4 can be used for the change in lag/lead sequence when the DHW heating is not being controlled:
BE4 = OFF: Boiler 1 as lead boiler
4
BE4 = ON: Boiler 2 as lead boiler
4
Functions
DHW demand – active ON Co4 -> Fb00 = OFF Automatic change in lag/lead sequence OFF Co5 -> Fb09 = OFF
WE Configuration
Note!
In system Anl 7 the binary input BE4 can be used either for modulation feedback, for an exter nal demand for DHW or for an external change in lag/lead sequence.
5.4 Return flow boost
On fulfilling the criteria for activation (–> section 5.1) the return flow control circuit is closed at the valve RK1/RK2. In the released boiler K1/K2 (see above), the first stage of the boiler and the boiler pump Pu1/Pu2 is switched on. The water is circulated in the boiler circuit. The return control circuit is released if the temperature at the sensor RüF1/RüF2 exceeds the limit entered in
Minimum return flow temperature.
The mixing valve opens and release the cor
EB 5474 EN 37
-
-
Page 38
Boiler functions
responding flow rateto theplant untilthe valve is completely opened and the boiler pump deliv ers the maximum flow rate in the plant.
Parameter
Minimum return flow temperature 50 °C PA1, PA2* / 20 to 120 °C
WE Parameter level / Range of values
* Only in systems Anl 4 to 7
Depending on the configuration, the return flow boost can be controlled with a continuous signal, on/off signal or three-point stepping signal (–> section 8.11).
5.4.1 Common return flow boost
In systems with two boilers (systems Anl 4, 5, 6 and 7), a common return flow boost can be im plemented. This is done by using the return flow control circuit of the first boiler K1, depending on whether the boiler is in operation.
Function
Common return flow boost OFF Co5 -> Fb12 = ON
WE Configuration
5.5 Parallel operation (Anl 7)
This function leads to both boilers working constantly in parallel (no lag/lead sequence control). The boilersstart operatingone after the other, taking into account the programmed times:
and
mum deactivation time for boiler K1, 2
for releasing sequence
ture t
A
Function
Parallel operation of boilers OFF Co5 -> Fb19 = ON
Parameters
Minimum deactivation time f. boiler K1, 2 0 min PA1, 2 / 0 to 90 min Lag delay 10 min PA5 / 0 to 90 min Temperature tAfor releasing sequence 12 °C PA5 / –40 to 50 °C
Lag delay
WE Configuration
WE Parameter level / Range of values
as well as taking into account
Mini-
Tempera-
-
-
5.6 Operating hours counter
This function allows the performed operating hours of boilers K1, 2 to be shown in the Inf1, 2 levels. The control is not affected by the counted operating hours. If the operating hours should be selected to start at a certain initial value, this can be programmed separately.
38 EB 5474 EN
Page 39
Boiler functions
Function
Operating hours counter OFF
WE Configuration
Co1, Co2* -> Fb02 = ON
0 h
Initial value / Configurable as required count Counting the operating hours rESEt Reset operating hours to initial value
* Only in systems Anl 4 to 7
5.7 Boiler pump control
The boiler pump control is connected with the boiler control loop. When a boiler is switched on to the first stage, the associated boiler pump is also switched on. When the boiler is switched off, the boiler is switched off too either after the elapsed or when the temperature falls below
Boiler flow limit
.
Pump lag time
In summer mode, the boiler pump is switched off together with the boiler when the deactivation criteria are fulfilled.
In systems without hydraulic separator, in which the heating water must be circulated through the boiler, the boiler pump may notbe switchedoff. For this purpose, the Continuous running of pump function is activated. The boiler pump continues to run when the lead boiler is switched off and the valve is opened. As a result, the cold system water can reach the boiler return flow pipe. If the return flow temperature is a factor that needs to be monitored in theboiler, theinstal­lation of an hydraulic separator is recommended.
Function
Continuous running of pump OFF
WE Configuration
Co5 -> Fb14 = ON
5 min
Pump lag time / 0 to 90 min
55 °C
Boiler flow limit / 20 to 120 °C
has
5.8 Boiler sensor acting as a thermostat
The boiler sensors KF1 and KF2 control the safety deactivation (–> section 8.10), which is trig gered whenever the maximum flow temperature is exceeded, as well as the temperature-de pendent pump lag of the boiler pumps Pu1 and Pu2 (–> section 5.7). The maximum permissible flow temperature can also be monitored in systems Anl 4, 5 and 6 with thermostats. The inputs of the boiler sensors must be defined as binary inputs for this pur pose. The thermostats are connected to the same terminals as the boiler sensors.
EB 5474 EN 39
-
-
-
Page 40
Boiler functions
Function
Boiler sensor KF1, 2 ON Co1, Co2* -> Fb03 = OFF
WE Configuration
StEiG: Thermostat closes FALL: Thermostat opens
*Only in systems Anl 4 to 7
5.9 Modulation feedback
The modulation feedback in systems Anl 3, 6 and 7 can be implemented by a potentiometer (1 to 2 kΩ) or by a limit switch for maximum boiler capacity output.
Modulation feedback with potentiometer
The inputsfor the potentiometer are marked in thewiring diagrams (–> section 12) with SG_K1 (potentiometer 1) and with SG_K2 (potentiometer 2).
Function
Modulation feedback K1, 2 ON Co1, Co2* -> Fb07 = ON
WE Configuration
* Only in system Anl 7
Note!
In system Anl 7, the binary input BE4 can be used either for modulation feedback, for external DHW demand or for external change in lag/lead sequence.
5.10 Operational alarm
The boiler controller waits for an operational alarm before it continues (–> section 5.1). The operational alarm can optionally be issued over a binary input or after fixed time entered in
Start-up time for boiler
parameter.
40 EB 5474 EN
Page 41
Boiler functions
Operational alarm over a binary input
The inputs for the operational alarm are marked in the wiring diagrams (section 12) with BE2 BM_K1 for Boiler 1 and with BE1 BM_K2 for Boiler 2.
Function
Operational alarm K1, 2 ON Co1, Co2* -> Fb01 = ON
WE Configuration
* Only in systems Anl 4 to 7
Operational alarm after start-up
Function
Operational alarm K1, 2 ON
WE Configuration
Co1, Co2* -> Fb01 = OFF
0 s
Start-up time for boiler / 0 to 5400 s
* Only in systems Anl 4 to 7
5.11 Return flow sensor acting as a thermostat
The return flow sensors can optionally be replaced by thermostats. For this purpose, the inputs for the return flow sensors are defined as binary inputs. The thermostats are connected to the same terminals as the return flow sensors.
Function
Return flow sensor RüF1, 2 ON Co1, Co2* -> Fb04 = OFF
WE Configuration
StEiG: Thermostat closes FALL: Thermostat opens
* Only in systems Anl 4 to 7
EB 5474 EN 41
Page 42
Functions of the heating circuit
6 Functions of the heating circuit
6.1 Outdoor temperature-dependent advance heating
Only selectable for systems Anl 1 to 3 with Co5 -> Fb13 = ON. The controller switchesthe heatingon beforethe time-of-use starts in normal operation depend ing onthe outdoor temperature. The of –12 °C. The advance heating time is shortened in case of higher outdoor temperatures.
Functions
Heating circuit with DHW heating OFF Co5 -> Fb13 = ON Optimization OFF
Outdoor sensor ON Co5 -> Fb00 = ON
Advance heatingtime
WE Configuration
Co3 -> Fb05 = ON,
120 min
Advance heating time / 0 to 360 min
is basedon an outdoor temperature
select: 1
6.2 Optimization using a room sensor
Only selectable for systems Anl 1 to 3 with Co5 -> Fb13 = ON. Both thefunctions describedshould only be used if the room in which theroom sensor is located (reference room) has a heating characteristic that is similar to the rest of the building. No thermostat valves should be mounted on the radiators in the reference room.
There are two types of optimization depending on the activation conditions:
Outdoor temperature-dependent advance heating, room temperature-dependent deacti-
4
vation
The controller activates the heating depending on the outdoor temperature before the time-of-use starts in normal operation. The temperature of –12 °C. The advance heating time is shorter whenthe outdoortemperature is higher (see section 6.1).
Room temperature-dependent advance heating and deactivation
4
The controller calculates the required advance heating time (max. 6 hours) adapted to the building characteristics, resulting in the reached in the reference room when the time-of-use starts. The heating is heated with the maximum flowtemperature duringthe advance heating phase. As soon as the is reached, outdoor temperature-dependent control starts.
Advance heating time
Day set point
(rated room temperature) being
is based on an outdoor
Day setpoint
-
The controllerdeactivates the heating in both types of optimization dependingon the room sen sors up to two hours before the time-of-use finishes.
The controller chooses the deactivation time such in a way that the room temperature does not drop significantly below the desired temperature until the time-of-use ends.
42 EB 5474 EN
-
Page 43
Functions of the heating circuit
Outside the times-of-use, the controller monitors the
Sustained temperature
or the
in the case of room temperature-dependent deactivation. When
Night set point
(reduced room temperature)
the temperature falls below the night set point, the controller heats with the max. flow tempera ture until the measured room temperature exceeds the adjusted value by 1 °C.
Note!
Direct sunshine can cause theroom temperatureto increaseand thusresult inthe prematurede activation of the heating system. A drop in room temperature within a brief period outside of the time-of-use may lead to the ad vance heating to reach the room temperature being activated too early.
Functions
Heating circuit with DHW heating OFF Co5 -> Fb13 = ON Room sensor OFF Co3 -> Fb00 = ON
Outdoor temperature-dependent advance heating, room temperature-dependent deactivation:
Optimization OFF
Outdoor sensor AF1 to 3 ON Co5 -> Fb00 = ON
Room temperature-dependent advance heating and deactivation:
Optimization OFF
Parameter
Day set point 20 °C PA3 / 10 to 40 °C Night set point 17 °C PA3 / 10 to 40 °C Sustained temperature 10 °C PA3 / 10 to 40 °C
WE Configuration
Co3 -> Fb05 = ON,
120 min
WE Parameter level / Range of values
Advance heating time / 0 to 360 min
Co3 -> Fb05 = ON,
select: 2
select: 3
-
-
-
EB 5474 EN 43
Page 44
Functions of the DHW circuit
7 Functions of the DHW circuit
Only systems Anl 1 to 3 have their own DHW heating (DHW heating in storage system with Co5 -> Fb13 = ON). The systems Anl 4 to 7 do not have their own DHW heating; they are, however, able to process an external DHW demand (-> section 7.4) and to reduce an excessively high flow temperature over a DHW forced charging in the external system (-> section 7.2).
7.1 DHW heating in the storage tank system (Anl 1 to 3)
WW
SLP
Fig. 4 · DHW heating in a storage tank system
SF1
SF2
ZP
KW
SLP Storage tank charging pump SF1 Storage tank sensor 1 SF2 Storage tank sensor 2 ZP Circulation pump WW Hot water KW Cold water
Operation with storage tank sensor SF1
The controller begins charging the storage tank when the water temperature measured at sen­sor SF1 falls below the set point
DHW demand ON
. The controller stops charging the storage
tank when the water temperature in the storage tank measured at sensor SF1 reaches the value
DHW demand ON+Hysteresis
T = The set point
Functions
Heating circuit with DHW heating OFF Co5 -> Fb13 = ON Storage tank sensor SF1 OFF Co4 -> Fb03 = ON Storage tank sensor SF2 OFF Co4 -> Fb04 = OFF
Parameters
Boiler set point for DHW demand 65 °C PA4 / 20 to 120 °C DHW demand ON 40 °C PA4 / 20 to 90 °C Hysteresis 5 °C PA4 / 0 to 30 °C
Boiler set point for DHW demand
.
determines the set point at sensor VFg.
WE Configuration
WE Parameter level / Range of values
44 EB 5474 EN
Page 45
Functions of the DHW circuit
Operation with two storage tank sensors SF1 and SF2
The controller begins charging the storage tank when the water temperature measured at sen sor SF1 falls below the set point
DHW demand ON
. The controller stops charging the storage
tank when the water temperature in the storage tank measured at sensor SF2 reaches the value
DHW demand OFF
The set point
Functions
Heating circuit with DHW heating OFF Co5 -> Fb13 = ON Storage tank sensor SF1 OFF Co4 -> Fb03 = ON Storage tank sensor SF2 OFF Co4 -> Fb04 = ON
Parameters
Boiler set point for DHW demand 65 °C PA4 / 20 to 120 °C DHW demand ON 40 °C PA4 / 20 to 90 °C DHW demand OFF 45 °C PA4 / 20 to 90 °C
.
Boiler set point for DHW demand
WE Configuration
WE Parameter level / Range of values
determines the set point at sensor VFg.
Operation with storage tank thermostat
The storage tank thermostat is connected to SF1 and switches the storage tank charging on and off. The set point
Functions
Heating circuit with DHW heating OFF Co4 -> Fb13 = ON Storage tank sensor SF1 OFF Co4 -> Fb03 = OFF Storage tank sensor SF2 OFF Co4 -> Fb04 = OFF
Parameter
Boiler set point for DHW demand 65 °C PA4 / 20 to 120 °C
Boiler set point for DHW demand
must still be predetermined.
WE Configuration
WE Parameter level / Range of values
-
7.1.1 Priority circuit (Anl 1 to 3)
The DHW heating can be switched with priority over the separate heating circuit 2 or directly over the heating circuit (heating circuit 3, Pu3).
Heating circuit 2: During the storage tank charging, the separateheating circuit2 is placed in reduced operation.
EB 5474 EN 45
Page 46
Functions of the DHW circuit
Functions
Heating circuit with DHW heating OFF Co5 -> Fb13 = ON DHW priority over HK2 OFF Co4 -> Fb06 = ON
WE Configuration
Heating circuit 3:
During the storage tank charging, the direct heating circuit is switched off. The separate heating circuit runs in parallel.
Functions
Heating circuit with DHW heating OFF Co5 -> Fb13 = ON DHW priority over HK3 OFF Co4 -> Fb07 = ON
WE Configuration
Note!
When the DHW priority over HK3 function is deactivated, the direct heating circuit also runs in parallel to the DHW charging. The heating circuit may, however, only be overheated by 10 °C . In other words, the heating circuit is supplied with not enough heat when the boiler set point for the heating circuit is greater than
Boiler set point for DHW demand
off during storage tank charging when the
Boiler set point for DHWdemand
. The heating circuit is switched
is 10 °C higher than
the boiler set point.
7.2 Forced charging of the DHW storage tank (Anl 1 to 7)
A forced charging of the DHW storage tank can prevent that the safety equipment place the boiler out of operation in case of excessively high flow temperature. The forced charging of the DHW storage tank takes place when the
forced charging
is exceeded at the flow sensor together with sensor VFg or at one of the two boiler sensors KF1 or KF2. In systems without their own DHW heating (systems Anl 4 to 7) the demand for a forced charg ing is passed on to the connected controllers atbinary outputBA1. The actual forced charging is started by the controllers that are responsible for the DHW heating.
Functions
Heating circuit with DHW heating OFF Co5 -> Fb13 = ON* Forced charging of DHW storage
tank
WE Configuration
OFF
Co4 -> Fb02 = ON
80 °C
Maximum limit f. DHW forced charging/20 to 120 °C
* Not in systems Anl 4 to 7
Maximum limit for DHW
-
46 EB 5474 EN
Page 47
Functions of the DHW circuit
7.3 Thermal disinfection (Anl 1 to 3)
In all systems with DHW heating, the DHW storage tank is thermally disinfected on the selected
Day of week
The charging temperature is always 5 °C higher than the Thermal disinfection starts at the adjusted
Disinfection temperature
the display. The error alarm is automatically reset when the during the next thermal disinfection.
Thermal disinfection for preventing legionella infection causes
high return flow temperatures during the disinfection cycle (return flow temperature limita
4
tion suspended), high storage tank temperatures after thermal disinfection has been concluded,
4
lime scale (possibly), which can have a negative effect on heat exchanger performance.
4
Note!
This function is not available when a storage tank thermostat is used.
or daily. The storage tank is heated up to the adjusted
Disinfection temperature
Start time
is not reached at the end of thermal disinfection, blinks on the
and finishes at the
Disinfection temperature
Disinfection temperature
.
Stop time
at the latest. If
is reached
.
-
Functions
Heating circuit with DHW heating OFF Co5 -> Fb13 = ON Storage tank sensor SF1 OFF Co5 -> Fb03 = ON Thermal disinfection OFF
WE Configuration
Co4 -> Fb08 = ON Day of week / 0, 1 to 7 (daily, Mon to Sun)
3
Disinfection temperature / 50 to 80 °C
70 °C
Start time / 00:00 to 23:59 h
00:00
Stop time / 00:00 to 23:59 h
04:00
EB 5474 EN 47
Page 48
Functions of the DHW circuit
7.4 External DHW demand (Anl 1 to 7)
This function allows the boiler controller to switch over to the
Boiler set point for DHW demand
when the binary input BE4 (WWA) is closed. The thermal disinfection has priority when the ex ternal DHW demand and thermal disinfection coincide.
Functions
Modulation feedback K2 ON Co2 -> Fb07 = OFF DHW demand – active ON Co4 -> Fb00 = ON
Parameter
Boiler set point for DHW demand 65 °C PA4 / 20 to 120 °C
WE Configuration
WE Parameter level / Range of values
Note!
In system Anl 7, the binary input BE4 can be used either for modulation feedback, for external DHW demand or for external change in lag/lead sequence.
-
48 EB 5474 EN
Page 49
System-wide functions
8 System-wide functions
8.1 Weather-compensated control
When weather-compensated control is used, the flow temperature is controlled according to the outdoor temperature. The boiler characteristic in the controller defines the flow temperature set point as a function of the outdoor temperature (–> Fig. 5). The outdoor temperature required for weather-compensated control is measured at the outdoor sensor at the input AF or received over a 0 to 10 V signal at the input AE2.
[
C] t
˚
VL
130
120
110
100
90
80
70
60
50
40
30
20
20 16 12 8 4 0 -4 -8 -12 -16 -20
Fig. 5 · Gradient characteristic
3.2 2.9 2.6
2.4
2.2
2.0
1.8
1.6
1.4
1.2
1.0
0.8
0.4
0.2 t
C]
[
˚
tVLFlow temperature t
A
A
Outdoor temperature
Caution!
Pt 100or Pt1000 sensorshould be used for measuring the flow temperature as only these sensors guarantee measurements up to 160 °C (max. temperature of the flow temperature set point).
Function
Outdoor sensor ON
WE Configuration
Co5 -> Fb00 = ON FUEHL: Outdoor temperature sensor AF
0–10: 0 to 10 V signal
3 °C
Frost protection limit / –30 to 20 °C*
* See section 8.8
EB 5474 EN 49
Page 50
System-wide functions
8.1.1 Gradient characteristic
Basically, the following rule applies: a decrease in the outdoor temperature causes the flow tem perature to increase. By varying the teristic to your individual requirements. Increasing ture, decreasing transport of the heating characteristic in an upward or downward direction.
Outside the times-of-use, reduced set points are used for control: Reduced flow set point
Max. flowtemperature
The its of the flow temperature. A separate gradient characteristic can be selected for the limitation of the return flow temperature.
Examples for adjusting the characteristic:
Old building, radiator design 90/70: Gradient approx. 1.8
4
New building, radiator design 70/55: Gradient approx. 1.4
4
New building, radiator design 55/45: Gradient approx. 1.0
4
Underfloor heating depending on arrangement: Gradient smaller 0.5
4
Functions
Type of characteristic OFF Co5 -> Fb03 = ON, select: 2 Type of characteristic for separate/direct
heating circuit*
Parameters
Gradient, flow 1.8 PA2*, PA3*, PA5 / 0.4 to 3.2 Level, flow 0 °C PA2*, PA3*, PA5 / –30 to 30 °C Set-back difference 15 °C PA2*, PA3*, PA5 / 0 to 30 °C Max. flow temperature 90 °C PA2*, PA3* / 20 to 160 °C Min. flow temperature 20 °C PA2*, PA3* / 20 to 120 °C
Gradient
in alower flowtemperature. The
= Flow set point–Set-back difference
and
Gradient
Min. flowtemperature
and
Level
WE Configuration
ON Co2, Co3 -> Fb10 = ON, select: 2*
* Only in systems Anl 1 to 3 with Co5 -> Fb13 = ON WE Parameter level / Range of values
* Only in systems Anl 1 to 3 with Co5 -> Fb13 = ON
parameters, you can adapt the charac
Gradient
parameters markthe upperand lowerlim
results in a higher flow tempera
Level
parameter performsa parallel
.
-
-
-
-
50 EB 5474 EN
Page 51
System-wide functions
[˚C]
8.1.2 4-point characteristic
The 4-point characteristic allows you to define your own heating characteristic. It is defined by 4 points for the
set-back difference
is predetermined for points P1 and P2 and for points P3 andP4 inthe corre
Outdoor temperature
sponding parameter level, resulting in the dashed line in Fig. 6.
Max. flowtemperature
The
and
Min. flowtemperature
its of the flow temperature.
t
[˚C]
VL
100
t
VLmax
90 80 70 60 50
t
VLmin
40 30 20 10
P4
20 15 10 5 0 –5 –10 –15 –20
Fig. 6 · 4-point characteristic
P2
P3
P1
and the
Flow temperature
parameters markthe upperand lowerlim
P1 to 4 Points 1 to 4
Flow temperature
t
VL
Outdoor temperature
t
A
..min Min. flow temperature ..max Max. flow temperature
4-point characteristic
-------- Reduced 4-point characteristic
t
A
. The
Boiler
-
-
Functions
WE Configuration
Type of characteristic OFF Co5 -> Fb03 = ON, select: 1 Type of characteristic for separate/
OFF Co2, Co3 -> Fb10 = ON, select: 1*
direct heating circuit*
* Only in systems Anl 1 to 3 with Co5 -> Fb13 = ON
EB 5474 EN 51
Page 52
System-wide functions
Parameters
Outdoor temperature Point 1
Point 2 Point 3 Point 4
Flow temperature Point 1
Point 2 Point 3 Point 4
Set-back difference Points
½ Points
3/4 Max. flow temperature 90 °C PA2*, PA3* / 20 to 160 °C Min. flow temperature 20 °C PA2*, PA3* / 20 to 120 °C
WE Parameter level / Range of values –10 °C
– 5 °C
10 °C 90 °C
80 °C 68 °C 50 °C
15 °C 20 °C
* Only in systems Anl 1 to 3 with Co5 -> Fb13 = ON
PA2*, PA3*, PA5 / –20 to 50 °C
5 °C
PA2*, PA3*, PA5 / 20 to 160 °C
PA2*, PA3*, PA5 / 0 to 30 °C
8.2 Fixed set point control
During the times-of-use, the flow temperature can be controlled according to a fixed Outside the times-of-use, this
Set point
is reduced by the
Set-back difference
The fixed set point control is activated when there is no outdoor sensor AF connected to the sys­tem or when it has been configured in the function block Type of characteristic. In the case that the fixed set point control is configured and an outdoor sensor is connected, the outdoor tem­perature is displayed in the InF5 level. The outdoor temperature does not have any effect on the control loop.
Functions
Type of characteristic OFF Co5 -> Fb03 = OFF Type of characteristic for separate/
direct heating circuit*
Parameters
Flow temperature set point 70 °C PA2*, PA3*, PA5 / 20 to 160 °C Set-back difference 15 °C PA2*, PA3*, PA5 / 0 to 30 °C
WE Configuration
OFF Co2, Co3 -> Fb10 = OFF*
* Only in systems Anl 1 to 3 with Co5 -> Fb13 = ON WE Parameter level / Range of values
* Only in systems Anl 1 to 3 with Co5 -> Fb13 = ON
Set point
.
.
52 EB 5474 EN
Page 53
System-wide functions
8.3 Differential temperature control using variable weighting factors
This functionallows thereturn flow temperature, total (RüFg) to be taken into account in the con trol loop, in addition to the flow temperature, total (VFg). The difference between the flow temperature, total (VFg) and return flow temperature, total (RüFg) is specified using the
Intended temperature difference
parameter. It is a measure for the energy consumption in a heating circuit. The greater the temperature difference, the larger the energy required by a heating circuit. If the actual temperature difference is not the same as the intended temperature difference, it is evaluated by the
. After initial signs for a deviation occur, the flow temperature is raisedor reducedby this
control
Kp factor for differential temperature
factor. When the
Kp factor for differential temperature control
is set to 0, the return flow temperature does not have any effect on the control of the flow temperature. When the
Kp factor for differential temperature control
is set to 1, a pure return flow tempera ture limitation takes place.
Function
Return flow sensor, total RüFg OFF
WE Configuration
Co5 -> Fb02 = ON
10 °C
Intended temperature difference / 0 to 90 °C
0.5
Kp factor for differential temperature control / 0 to 1
8.4 Deactivation depending on outdoor temperature
The controller switches to the stand-by mode when
to summer mode in rated operation
during times-of-use or
change to summer mode in reduced operation
Should the temperature fall below the limit, the heating is started again. The function for deacti vation depending outdoor temperature is set by default.
Parameter
Outdoor temperature limit causing change to summer mode in rated operation
Outdoor temperature limit causing change to summer mode in reduced operation
WE Parameter level / Range of values 22 °C PA5 / 0 to 50 °C
10 °C PA5 / –10 to 50 °C
Outdoor temperature limit causing change
Outdoor temperature limit causing
outside times of use is exceeded.
-
-
-
EB 5474 EN 53
Page 54
System-wide functions
8.5 Summer mode
Summer mode is activated depending on the mean daytime temperature (measured between
7.00h and 22.00h) during the desired period. If the mean daytime temperature exceeds the
Outdoor temperature limit
on two consecutive days, summer mode is activated on the following day: the heating is switched off. If the mean daytime temperature remains below the
Outdoor temperature limit
on the next day, summer
mode is deactivated on the following day.
Function
Summer mode ON
WE Configuration
Co5 -> Fb06 = ON
01.06
Start summer mode / 01.01 to 31.12
30.09
Stop summer mode / 01.01 to 31.12
18 °C
Outdoor temperature limit /0 to 40 °C
8.6 Delayed outdoor temperature adaptation
The calculated outdoor temperature is used to determine the flow temperature set point. The heat response is delayed when the outdoor temperature either decreases, or increases and de­creases. If the outdoor temperature varies by, for example, 12 °C within a very short period of time, the calculated outdoor temperature is adapted to the actual outdoor temperature in small
Delay
steps. Assuming a
of 3 °C/h, the adaptation would take
C
°°12
t
==
Ch
3/
4h
.
Note!
The delayed outdoor temperature adaptation helps avoid unnecessary overloads of central heating stationsin combination with either overheated buildings occurring, forexample, due to warm winds, or temporarily insufficient heating due to the outdoor sensor being exposed to di rect sunshine.
Function
Delayed outdoor temperature adaptation OFF
WE Configuration
Co5 -> Fb01 = ON AB Delay on decreasing temperature
ABAUF Delay on decreasing and increasing
Delay / 1 to 6.0 °C/h
3 °C/h
temperature
54 EB 5474 EN
-
Page 55
System-wide functions
8.7 Automatic summer time/winter time changeover
The clock is automatically adjusted on the last Sundayin Marchat 2.00h and on the last Sunday in October at 3.00h.
Function
Summer time/winter time changeover ON Co5 -> Fb05 = ON
WE Configuration
8.8 Frost protection
To protect the system from freezing up, the flow temperature or return flow temperature are monitored.
Note!
The frost protection function is not activatedwhen manualmode is selected at the mode switch.
Flow temperature monitoring
The flow temperature cannot drop enough to cause the pipes to freeze when the controller is in rated or reduced operation. In stand-by mode, the flow temperature is not regulated. Therefore, it ismonitored. Shouldthe flow temperature fall below 3 °C, the flow temperature is restrictedto the minimum return flow temperature.
Return flow temperature monitoring
The outdoor temperature is monitored at the input AF (outdoor sensor) or at the input AE2 (0 to 10 V signal). In both cases, the
Frost protection limit
(–30 to 30 °C, WE: 3 °C with Co5 -> Fb00 = ON) must be defined to monitor this parameter. Alternatively, a frost protection thermostat can also be used for monitoring. This requires input AF to be configured as a binary input (BE11) (Co5 -> Fb00 = OFF, FroSt). If there is no boiler in operation and the outdoor temperature falls below the frost protection limit or if the binary input of the frost protection thermostat is active, the pumps are activated and the valves opened. As a result,the systemor individual parts of the system cannotfreeze.
Function
Outdoor sensor
WE Configuration ON Co5 -> Fb00
EB 5474 EN 55
Page 56
System-wide functions
8.9 Forced operation of the pumps
When the pumps (Pu1, Pu2 and Pu3) have not been activated for 24 hours, forced operation of the pumps is started between 12.00h and 12.01h. The forced operation of the storage tank pump SLP is operated between 12.01h and 12.02h.
8.10 Flow temperature limitation
The boiler temperature is regulated to the limit set in
Maximum flow temperature
and an alarm
is displayed when the flow temperature at the boiler outlet of a modulating burner reaches the
Maximum flow temperature+Temperature rise
limit The limitation is stopped again when the flow temperature falls below the limit set in
flow temperature
.
.
Maximum
During the active limitation, the boiler temperature blinks in InF1 and InF2 levels. Press to read the limit.
Function
Boiler sensor KF1, 2
Parameters
Maximum flow temperature KF1, 2 90 °C PA1, PA2* / 20 to 160 °C Temperature rise 10 °C PA5 / 0 to 30 °C
WE Configuration ON Co1, Co2* -> Fb03 = ON * Only in systems Anl 4 to 7
WE Parameter level / Range of values
* Only in systems Anl 4 to 7
Note! The controller cannot replace a safety temperature limiter.
The flow temperature is monitored by athermostat whenthe functionis deactivated. The input of the flow sensor is defined as a binary input. The thermostat is connected to terminals 24 (RK1) or 25 (RK2).
Function
Boiler sensor KF 1, 2 ON Co1, Co2* -> Fb03 = OFF
WE Configuration
StEiG Thermostat closes FALL Thermostat opens
*Only in systems Anl 4 to 6
Note! The sensor inputs VF1 and VF2 cannot be used as thermostat inputs in system Anl 7.
56 EB 5474 EN
Page 57
System-wide functions
8.11 Control mode
The selected control mode (section 8.11.1 to 8.11.3) of the return flow boost affects the control mode of the modulation and vice versa. The following connection applies:
Return flow boost in continuous control <–> Modulation in three-point
4
Return flow boost in on/off or three-point control <–> Modulation in continuous
4
On using modulating burners (systems Anl 6 and 7), the default setting of the control signal for the returnflow boost is configured to be continuous (Co1, 2 -> Fb05 = ON)and the modulation control uses a three-point signal. With Co1, 2 -> Fb05 = OFF, this assignment is reversed, meaning that the modulating burners can also be controlled with a continuous signal.
Setting for return flow boost: continuous control; Modulation: three-step control
Functions
RüL-RK1, 2
Setting for return flow boost: three-step control; Modulation: continuous control
Functions
RüL-RK1, 2
3-step pulsing/on-off signal RüL-RK1, 2 OFF Co1, Co2* -> Fb06 = ON
WE Configuration
Co1, Co2* -> Fb05 = ON
6 120 s 0 s
WE Configuration
6 120 s 0 s 120 s
(proportional gain) / 0.1 to 99.9
K
P
T
(reset time) / 0 to 999 s
N
T
(derivative-action time) / 0 to 999 s
V
Co1, Co2* -> Fb05 = OFF K
(proportional gain) / 0.1 to 99.9
P
T
(reset time) / 0 to 999 s
N
T
(derivative-action time) / 0 to 999 s
V
T
(valve transit time) / 5 to 240 s
Y
Setting for return flow boost: on/off control; Modulation: continuous control
Functions
RüL-RK1, 2
3-step pulsing/on-off signal RüL-RK1, 2 OFF
WE Configuration
Co1, Co2* -> Fb05 = OFF K
6 120 s 0 s 120 s
5 °C 120 s 120 s
(proportional gain) / 0.1 to 99.9
P
T
(reset time) / 0 to 999 s
N
T
(derivative-action time) / 0 to 999 s
V
T
(valve transit time) / 5 to 240 s
Y
Co1, Co2* -> Fb06 = OFF Hysteresis / 1 to 30 °C
Min. activation time / 0 to 600 s Min. deactivation time / 0 to 600 s
EB 5474 EN 57
Page 58
System-wide functions
* Only in systems Anl 4 to 7
Note!
The control mode is configured separately in Co2 -> Fb14 or Fb15 for the separate heating cir cuit in systems Anl 1 to 3 (Co5 -> Fb13 = ON).
8.11.1 Three-step control
The setpoint can be controlled using a PI algorithm. Thevalve reacts to pulses that the controller emits whena system deviation occurs. The length ofthe first pulse. in particular, depends onthe extent of the system deviation and the selected
increases). The pulse and pause lengths change continuously until the system deviation
as K
P
Proportional gain K
has been eliminated. The pauselength betweenthe singlepulses isgreatly influencedby the
set time T
The
(the pause length increases as TNincreases).
N
Transit time T
specifies the time required by the valve to travel through the range of 0 to
Y
(the pulse length increases
P
Re
100 %.
8.11.2 On/off control
The output signal of the controller is switched on or off. Depending on the controlled variable, the outputsignal is switched on oroff when the tempera­ture fallsbelow orexceeds the required set point by T = 0.5 x
selected, the less the signal is switched on and off. The
esis mum deactivation time
determine the time interval between changes in the output signal.
Hysteresis
Minimum activation time
. Thegreater the
and
Hyster-
Mini-
-
-
8.11.3 Continuous control
The set point can be controlled using a PID algorithm. The valve receives an analog 0 to 10 V signal from the controller. The proportional component causes an immediate change in the 0 to 10 Vsignal when a system deviation occurs (the greater the K tegral-action component only comes into effect when a certain time has passed: T the time passing until the integral-action component has changed theoutput signal to the extent that the proportional component directly changed the signal (the greater the T rate of change). The derivative-action component determines how strongly a change in the sys tem deviation affects the output signal (the greater the T
58 EB 5474 EN
, thegreater the change). The in
P
, the slower the
N
, the stronger the change).
V
stands for
N
-
-
Page 59
8.12 Control signal deactivation
System-wide functions
This function protects three-point stepping actuators without final position deactivation from over loading bymonitoring the total of thecontrol signal pulses. No furthercontrol signals are issued if it exceeds three times the
Valve transit time T
. It is assumed that the control valve is already open
Y
or closed, meaning further control signals do not change the valve position.
Function
Control signal deactivation OFF Co5 -> Fb16 = ON
WE Configuration
8.13 Processing of external demand
The controller (= primary controller) is able to process analog signals for demand. The external flow temperature set point of the preceding controller is received over the analog input AE1. 0 to 10 V corresponds to 0 to 120 °C. Demands under a signal of 1 V are sup pressed. The received flow temperature set point is compared to the controller’s own flow tem-
Boost
perature set point. The higher of both flow temperature set points plus the
parameter is
used for the control.
Boost
The
parameter improves the control characteristic of the downstream control valves in the
heating circuit and compensates for any pipeline losses.
Function
External demand OFF Co5 -> Fb15 = ON
WE Configuration
0 °C Boost / 0 to 30 °C
8.14 Feedforwarding the outdoor temperature
The outdoortemperature can be passed on to anothercontroller over the analog output AA2 (0 to 10 V) by setting Co2 -> Fb05 = ON, provided this output isnot usedfor acontrol signalor for the modulation control.
Systems Anl 1 to 3:
The outdoor temperature is constantly applied to AA2. No special settings are necessary. 0 to 10 V corresponds to –40 to 50 °C.
Systems Anl 4 to 6:
Function
Continuous RüL-RK2 OFF Co2 -> Fb05 = OFF
WE Configuration
-
-
EB 5474 EN 59
Page 60
System-wide functions
System Anl 7:
The outdoor temperature cannot be passed on as the output AA2 is constantly used for a control signal or for the modulation control.
8.15 Locking of changed settings
An active locking of all manual levels means that no settings (configuration and parameterization) can be performed at the controller.
Function
Configuration and parameterization protection
WE Configuration OFF Co5 -> Fb04 = ON
60 EB 5474 EN
Page 61
Operational faults
9 Operational faults
Operational faults are indicated by the icon blinking on the display. “Error“ immediately appears on the display. Press to access the error level. Use the arrow
keys toscroll thedifferent error alarms, if need be. The error level remains inthe displayloop as long as an acute operational fault exist even if it has not be opened by pressing .
9.1 Error list
Err 1 Sensor failure in RK1 (in combination with sensor icons)
4
Err 2 Sensor failure in RK2 (in combination with sensor icons)
4
Err 3 Sensor failure in heating circuit (in combination with sensor icon)
4
Err 4 Sensor failure in DHW circuit (in combination with sensor icons)
4
Err 5 Failure of sensor VFg, RüFg or AF (in combination with sensor icons)
4
Err b1 Fault in Boiler K1
4
Err b2 Fault in Boiler K2
4
Err P1 Fault in Pump Pu1
4
Err P2 Fault in Pump Pu2
4
Err-1 Default values read (default settings)
4
Err-2 Final temperature of thermal disinfection not achieved
4
Err-3 Mode selector switch 1 defective
4
Err-4 Selector switch defective
4
Err-5 Correction switch for the flow temperature defective
4
9.2 Sensor failure
The errorlist explains how the “Err-1”to “Err-5” on the display inthe error level indicate sensor failures. After exiting the error level, detailed information can be found within the operating level by reading each temperature: A sensor icon in combination with three dashes instead of the measured temperature on the display indicates that this sensor is defective.
Sensor icons
Outdoor sensor AF Flow sensor VF2, VFg,
Boiler sensor KF1, KF2
Return flow sensor RüF1, RüF2, RüFg
Room sensor RF Storage tank sensor SF1 Storage tank sensor SF2
EB 5474 EN 61
Page 62
Operational faults
The following list shows how the controller reacts depending on which sensor fails:
Outdoor sensor AF: When the outdoor sensor fails, the controller uses a flow temperature
4
set point of 70 °C. The boiler pumps are switched on and the control valves of the return flow boost are opened to ensure frost protection. Flow sensor VFg: Both boilers are switched off immediately.
4
Flow sensor VF1, VF2: The affected boiler is switched off. The other boiler takes over.
4
Return flow sensor RüFg: The controller continues to functionwithout thedifferential temper
4
ature control using variable weighting factors. Boiler return flow sensor RüF: The controller continues to function without the return temper
4
ature limitation. If the affected boiler is switched on, the boiler pump is switched on and the control valve receives a constant signal. Storage tank sensor SF1/SF 2: When one of the sensors fail, storage tank charging no lon
4
ger takes place. Boiler K1, K2 (binary inputs SM_K): The affected boiler and the associated pump are
4
stopped. Pumps (binary inputs SM_P): The affected boiler and the associated pump are stopped.
4
9.3 Displaying the lead/collective error alarm
The lead is indicated over BA2 when the function block is active:
Lead 1: BA2 = OFF
4
Lead 2: BA2 = ON
4
The binary output BA2 is set in the event of an error when the function block is not active. Errors are still displayed by “Err” in the info level.
Function
Displaying lead/collective alarm OFF Co5 -> Fb11
WE Configuration
-
-
-
9.4 Error status register
The error status register is used to indicate controller or system errors. In modem operation with
Dial-up also upon corrected fault
the building control station to be dialed. The error status registers are displayed in InF8 level. By default the error status register FSR1
(holding register 60) is displayed. Keep pressed to display FSR2 (holding register 61). In both displays, function blocks Fb20 to Fb23 are set when a bit is set in the error status register not being displayed.
62 EB 5474 EN
function, any change in state of the error status register causes
Page 63
Operational faults
Holding register 60 (HR60)
Number = Bit no. in HR 0 1234567891011 A set bit is indicated by on the right of
number
Bit value 2 Sensor breakage D0 Default values read D1 –D2 Mode switch faulty D3 Boiler switch faulty D4 Correction switch for flow temp. faulty D5 Unauthorized access D6 Error alarm of a binary input Error alarm WMZ M-Bus D8 Data error alarm from WMZ D9 – D10 Fault alarm binary input changed D11
0212223242526272829210211
D7
Holding register 61 (HR61)
Number = Bit no. in HR 0 1 2 3 A set bit is indicated by on the right of number
Bit value 2 Error thermal disinfection D0 –D1 –D2 Error Boiler 1, 2 or Pump Pu1,2, or
Temperature exceeded limit
0212223
D3
Example of a transfer to the control system:
The error statusregister istransferred asa word<w> in a holding register (HR) whose content is represented by the total of the value <z> of the active data bit:
<w> = ([D0] x <1> + [D1] x <2>) + … + ([D11] x <2048>)
EB 5474 EN 63
Page 64
Operational faults
9.5 Error alarms
Error alarms can be sent over amodem either directly to thecontrol station or over the SMStext message functionto a mobile phone or to a fax. Just onefunction (Modbus, SMS function or fax function) can be selected at one time since the functions use the same interface. The error alarms to a mobile phone and to a fax contain the number of the affected error status register (FSR1/FSR2), the fault as per error status register (BitNo), the controller ID and the bit number (Bit xx).
9.5.1 Sending text message in case of error
Currently, text messages can only be sent to the German D1 network. The corresponding access numbers into the D1 network as well as the mobile phone number of the recipient must be set in the PA9 level:
D1 access number: 0171 252 10 02
4
(add 0 in front when dialing from a private branch exchange) Digits 0 to 9, P = pause, - = end, max. 22 characters The access number is assigned by Deutsche Telekom and may alter. Mobile phone number: 49 xxx yyyyyyy , where xxx stands for 160, 171 or any other valid
4
D1 dialing code and yyyyyy represents the specific phone number of the mobile phone you wish the alarm to be sent to. Digits 0 to 9, P = pause, - = end, max. 14 characters
Note!
Currently, text messages can only be sent to the German D1 network.
Functions
Modbus ON Co9 -> Fb00 = OFF Modem function OFF Co9 -> Fb01 = OFF Text message alarm to a mobile
phone SMS dialing procedure OFF Co9 -> Fb07 Alarm sent per fax OFF Co9 -> Fb10 = OFF
64 EB 5474 EN
WE Configuration
OFF Co9 -> Fb06 = ON
Page 65
Operational faults
Parameters
Access number PA9 / configurable as required* Phone number PA9 / configurable as required** * Digits 0 to 9, P = pause, - = end, max. 14 characters ** Digits 0 to 9, P = pause, - = end, max. 22 characters
WE Parameter level / Range of values
9.5.2 Sending fax in case of a fault alarm
The controller type is forwarded in addition to a detailed error description. The recipient’s fax number must be programmed in the PA9 level. Optionally, also the sender’s station ID can be programmed; this number will then be forwarded as well. If no station ID is specified, the string “nicht verfügbar“ (not available) is inserted.
Fax number:
4
Digits 0 to 9, P = Pause, - = End, max. 14 characters (place an additional 0 in front when dialing from a private branch exchange)
Phone number of sending fax:
4
Digits 0 to 9, P = Pause, - = End, max. 14 characters
Functions
Modbus ON Co9 -> Fb00 = OFF Modem function OFF Co9 -> Fb01 = OFF Text message alarm to a mobile phone OFF Co9 -> Fb06 = OFF Alarm sent per fax OFF Co9 -> Fb10 = ON Fax dialing procedure OFF Co9 -> Fb11
Parameters
Fax number PA9 / configurable as required* Phone number of sending controller PA9 / configurable as required* * Digits 0 to 9, P = pause, - = end, max. 14 characters
WE Configuration
WE Parameter level / Range of values
EB 5474 EN 65
Page 66
Communication
10 Communication
Using the serial system bus interface RS-232-C, the TROVIS 5474 Boiler Controller can commu nicate with a building control system. In combination with a suitable software for process visual ization and communication, a complete control system can be implemented.
The following communication settings are possible:
– Operation with a dial-up modem at the RS-232-C system bus interface
Basically, communication is only established automatically when errors occur. The controller works autonomously. Nevertheless, the modem can dial up to the controller at any time to read data from it or otherwise influence it, if necessary. We recommend to use the modem connect ing cable (1400-7139).
Operation with a leased line modem at the RS-232-C system bus interface Communication is established via a permanent connection between two leased line modems. This setup is applied for long-distance transmissions or when different signal level converters are used. The connection between controller and modem can also be established via the mo­dem connecting cable (1400-7139). – Operation at a four-wire or two-wire bus To establish the link between controller and bus line, thesignal level needs to be converted by a converter (SAMSON’s cable converter 1400-7308).
GLT
RS 232C RS 232C
TROVIS 5474
TROVIS 5474
RS232
RS485
RS 485
RS232
RS485
RS232
RS485
-
-
-
Fig. 7 · Network structure
66 EB 5474 EN
Page 67
Communication
10.1 Controller with RS-232 port
The system bus connection is located at the back of the controller housing (RJ-12 jack). In this case, the controller can be connected either directly to the serial interface of a PC (point-to-point connection)or to a (dial-up) modem. A dial-upmodem is required if the control ler is to be connected to the telecommunications network. In this case, the controller works au tonomously and can issue an alarm call to the building control station when errors occur. Addi tionally, the building control station can dial up the controller, read data from it, and send new data once the valid key number has been written to the holding register no. 40070. On recognizing the key code from the controller as valid, the register value “1” confirms writing permission. In any other case, the register value remains at “0”. Any further establishment of communications requires the writing permission to beacquired byresending the key number.
Note!
If a wrong key number has been written to holding register no. 40070 for the third consecutive time, the controller immediately interrupts themodem connectionand setsthe D6bit ofthe error status register (Unauthorized access). As a result, the call to the configured control system is triggered and a text message/fax sent. Bit D6 is deleted as soon as the error status register has been read by the control system and the connection has been terminated.
In special cases, the Lock dial-up function can be selected to stop dial-up in case an error oc­curs. Using the Dial-up also upon corrected error function, the controller additionally informs the building control station when a previously signaled error no longer persists.
Functions
Modbus ON Co9 -> Fb00 = ON Modem function OFF Co9 -> Fb01 = ON Modem dialing procedure OFF Co9 -> Fb02 Lock dial-up OFF Co9 -> Fb03 Modbus 16-bit addressing OFF Co9 -> Fb04 Dial-up also upon corrected fault OFF Co9 -> Fb00
Parameters* Station address (ST.-NR) 255 PA9 / 1 to 247 (with Fb04 = ON: 1 to 999) Baud rate (BAUD) 9600 PA9 / 300 to 19200 Cyclic initialization (I) 30 min PA9 / 0 to 255 min Modem dial interval between calls (P) 5 min PA9 / 1 to 255 min
WE Configuration
WE Parameter level / Range of values
-
-
-
EB 5474 EN 67
Page 68
Communication
Parameters* Modem timeout (t) 5 min PA9 / 1 to 255 min Number of redial attempts (C) 5 PA9 / 0 to 99 Phone number of building control station
(tELno) Phone number of alternative recipient
(rESno)
** Digits 0 to 9, P = Pause, - = End, max. 23 characters
WE Parameter level / Range of values
PA9 / Set as required**
PA9 / Set as required**
* –> Section 10.3 (“Description of communication parameters to be adjusted“)
10.2 System bus interface in conjunction with cable converters RS-232/RS-485 (for four-wire bus)
A constant bus connection is required (data cable) for the operation of the controller with serial RS-485 interface. The bus line links the control units/devices in an open ring. At the end of the bus line, the data cable is connected to the control station using an RS-485/RS-232 converter (e.g. TROVIS 5484). The maximum range of the bus connection (cable length) is 1,200 meters. A maximum of 32 devices can be connected to such a segment.
If you wish to use more than 32 devices in line or need to bridge greater distances, make sure repeaters (e.g. TROVIS 5482) are installed to replicate the signal. With 8-bit addressing, a maximum of 246 devices can be addressed and connected to a bus.
!
Warning!
You are required to follow the relevant standards and regulations concerning lightning and overvoltage protection on installation.
Functions
Modbus ON Co9 -> Fb00 = ON Modem function OFF Co9 -> Fb01 = OFF Modbus 16-bit addressing OFF Co9 -> Fb04
Parameters* Station address (ST.-NR) 255 PA9 / 1 to 247 (with Fb04 = ON: 1 to 999) Baud rate 9600 PA9 / 300 to 19200
* –> Section 10.3 (”Description of communication parameters to be adjusted“)
WE Configuration
WE Parameter level / Range of values
68 EB 5474 EN
Page 69
Communication
10.3 Description of communication parameters to be adjusted
Station address (ST.-NR)
This address is used to identify the controller in bus or modem mode. In a system, each control ler needs to be assigned a unique address.
Baud rate (BAUD)
In a bus system, baud rate refers to the transfer speed between control system and controller. In modem mode, baud rate refers to the transfer speed between controller and modem. The baud rate adjusted at the controller must correspond with the baud rate of the control sys tem, otherwise no communication can be established.
Cyclical initialization (I)
This parameter defines the period of time for a cyclical issue of the initialization command “ATZ“. The command is not issued during dial-up or when connected. “ATZ“ causes the pro file 0 to be copied to the active profile, provided the modem parameters have been set and saved in profile 0 using a suitable terminal program.
Typical initialization of a modem with a terminal program:
AT & F (restores modem to its factory settings) OK (response of the modem) ATEOSO = 1(command input, EO: echo off;
SO = 1: answer on first ring)
-
-
-
Dialing pause (P)
It is recommendable to pause for approx. 3 to 5 minutes between dialing up to the control sys­tem to avoid a permanent overloading of the telecommunications network. The defines the interval between 2 dialing attempts.
Modem time-out (t)
When the controller connects to the control station but without addressing a Modbus data point, the connection is closed after the time specified for tus register has not been read during the control station connection, the controller dials up to the control station again after the
Number of redialing attempts (C)
The controller tries to dial up to the control system again, observing the the control stationis busyor thefunction thattriggered the call has not been reset by the control ler. Afterthe specified number of redialingattempts have failed, the controller dialsthe alterna tive recipient.
Reset the function that triggered the call = Polling the error status register (HR 40060)
Dialing pause
Modem time-out
(P) has elapsed.
has elapsed. If the error sta
Dialing pause
Dialing pause
, in case
EB 5474 EN 69
-
-
-
Page 70
Communication
Phone number of control station (tElno)
Enter the phone number of the control system modem including the dialing code, if necessary. Short pauses between the numbers can be entered using P (= 1 second); the end of the string is to be marked by “–“. The phone number may include a maximum of 22 characters. Example: “069, 2sec. pause, 4009, 1 sec. pause, 0“:069PP4009P0–(=11characters)
Phone number of alternative recipient (rESno)
Enter thephone number of an alternative recipient, ifrequired including the dialing code. Short pauses between the numbers can be entered using P (= 1 second); “–“ indicates the end of the string. The phone number can include max. 22 characters. Example: “069, 1 sec. pause, 654321“: 0 6 9 P 6 5 4 3 2 1 – (= 10 characters)
Common modem settings are:
EO - Echo off
4
QO - Enable result codes
4
X3 - Dial without checking for dial tone
4
% CO - Data compression off
4
\ N1 - Buffer off, fault correction off
4
V1 - Result codes in text format
4
% B 9600 - Baud rate 9600
4
\ VO - Standard connect result code
4
Resetting to default settings
A modem can be reset to its default settings directly at the controller after entering the key num­ber.
Key number Command 44 AT&F&W <CR> <LF>
45 AT&F&W ATX3 <CR> <LF> (for branch exchange systems)
70 EB 5474 EN
Page 71
Communication
Note!
The initialization settings described here are indispensable for operation on a dial-up modem. Nevertheless, it cannot be guaranteed that data are transferred after the initialization settings have been adjusted. Due to the broad range of modems available on the market and the diffe rent commands, refer to the operating manual of the modem for further details.
GND TD DTR RTSRDDCD
Fig. 8 · Pin assignment of RJ-12 jack
10.4 Meter bus interface
The TROVIS 5474 Controller can communicate with up to 3 heat and water meters according to EN 1434-3. Details on the useof thedifferent heator watermeters canbe found in the technical documenta­tion TV-SK 6311.
-
10.4.1 Activating the meter bus
To successfully transfer data from the heat meter (WMZ) to the controller, the heat meter must use a standardized protocol in accordance with EN 1434-3. It is impossible to make a general statement about which specific data can be accessed in each meter. For details on the different meter makes, refer to the technical documentation TV-SK 6311.
All necessary function block parameters to set up communication with heat or water meters are available in Co9 -> Fb21 to Fb23. The meter bus address, the model code, and the reading mode must be specified. A meter bus address must be unique and correspond with the address preset in the heat meter.
If the preset meter bus address is unknown, a single heat meter connected to the controller can be assigned meter bus address 254. Address 255 deactivates communication with the respec tive heat meter. The model code, which needs to be set for the respective heat meter, can be found in TV-SK 6311.
In general, the default setting of 1434 can be used for most devices.
EB 5474 EN 71
-
Page 72
Communication
The meters can be read either automatically approx. every 24 hours (24h), continuously (con) or when the coils (= Modbus data points) assigned to the heat meters WMZ1 to WMZ3 are written with the value 1 over the system bus interface (CoiL).
In InF9info level, “1434“ is displayed when the meter bus isactivated. Press the enter key to get to the display referring to the meter bus. For each of the three heat meters whose address is not 255, “buSi“ (with i = 1, 2, 3) appears. Press the enter key again to display the following in formation about the associated heat meter:
Flow rate (d, cm/h)
4
Volume (U, cm³)
4
Output capacity (P, kW)
4
Energy (A, Mwh, GJ)
4
Flow temperature (b, °C)
4
Return flow temperature (b, °C)
4
Meter ID number (L without enter key, H with enter key)
4
Meter bus address (sent by WMZ) (A, –)
4
Blinking values in combination with black squares in the top row of the display (fault status of the associated meter –> TV-SK 6311) indicate different faults.
Note!
With reading mode “24h“,the displayedvalues arenot updatedby readingthe status informa­tion again; the values read during the last cycle remain unchanged. With reading mode“con, thevalues in the levels are not continuously updated. Reopen the spe­cific level to get current values.
-
Function
Meter bus OFF
72 EB 5474 EN
WE Configuration
255 1434 con
Co9 -> Fb21 = ON, Fb22 = ON, Fb23 = ON Meter bus address for WMZ 1 to 3 / 0 to 255
Model code WMZ 1 to 3 / P15, PS2, 1434, CAL3, APAtO, SLS Reading mode WMZ 1 to 3 / 24h, con, CoiL
Page 73
Communication
10.5 Memory module
The use of a memory module (accessory no. 1400-7142) is particularly useful to transfer all data fromone TROVIS 5474 Controller to several other TROVIS 5474 Controllers. The memory module is plugged into the RJ-12 jack integrated into the front panel. Once the module has been connected, “74 SP“ is displayed. If the memory module already contains data from a dif ferent TROVIS 5474 Controller, press the enter key until “SP 74" is displayed.
Pressing the enter key to confirm “74 SP“ causes the controller settings to be transferred to
4
the memory module. Pressing the enter key to confirm “SP 74“ causes the saved controller settings to be trans
4
ferred from the memory module to the controller.
During the data transfer, the bars on the display indicate the progress. After the display stops, remove the memory module from the controller.
-
-
EB 5474 EN 73
Page 74
Installation
11 Installation
The controller consists of the housing with the electronics and the back panel with the terminals. It is suitable for panel, wall, and top hat rail mounting (Fig. 9).
Panel mounting
1. Remove both screws (1).
2. Pull apart the controller housing and back panel.
3. Make a cut-out of 138 x 91 mm (width x height) in the control panel.
4. Insert the controller housing through the panel cut-out.
5. Insert one mounting clamp (2) each at the top and bottom or at the sides. Screw the
threaded rod towards the panel with a screwdriver such that the housing is clamped against the control panel.
6. Install the electrical connections at the back of the housing as described in section 11.
7. Fit the controller housing.
8. Fasten both screws (1).
Wall mounting
1. Remove both screws (1).
2. Pull apart the controller housing and back panel.
3. If necessary, bore holes with the specified dimensions in the appropriate places. Fasten
the back panel with four screws.
4. Install the electrical connections at the back of the housing as described in section 11.
5. Fit the controller housing.
6. Fasten both screws (1).
Top hat rail mounting
1. Fasten the spring-loaded hook (4) at the bottom of the top hat rail (3).
2. Slightly push the controller upwards and pull the upper hooks (5) over the top hat rail.
74 EB 5474 EN
Page 75
Panel mounting
Installation
2
Back panel of the
controller
1
Wall mounting
Dimensions in mm:
W x H x D = 144 x 96 x 125
Fig. 9 · Installation
57
42
2
Top hat rail mounting
62
15
Controller housing
5
4
5
3
EB 5474 EN 75
Page 76
Electrical connection
12 Electrical connection
!
Caution!
For electrical installation, you are required to observe the relevant electrotechnical regulations of the country of use as well as the regulations of thelocal powersuppliers. Makesure all electri cal work is performed by trained and experienced personnel!
Notes on installing the electrical connections
-
Install the 230 Vpower supplylines andthe signallines separately!To increase noise immu
4
nity, observe a minimum distance of 10 cm between the lines. Make sure the minimum dis tance is also observed when the lines are installed in a cabinet. The lines for digitalsignals (buslines) andanalog signals(sensor lines,analog outputs) must
4
also be installed separately! In plants with a high electromagnetic noise level, we recommend to use shielded cables for
4
the analog signal lines. Ground the shield at one side, either at the control cabinet inlet or outlet, using the largest possible cross-section. Connect the central grounding point and the PE grounding conductor with a cable≥10 mm² using the shortest route. Inductances in the control cabinet, e.g. contactor coils, are to be equipped with suitable in-
4
terference suppressors (RC elements). Control cabinet elements with highfield strength, e.g. transformers or frequency converters,
4
should be shielded with separators providing a good ground connection.
Overvoltage protection
If signal lines are installed outside buildings or over large distances, make sure appropriate
4
surge or overvoltage protection measures are taken. Such measures are indispensable for bus lines! The shield of signal lines installed outside buildings must have current conducting capacity
4
and must be grounded on both sides. Surge diverters must be installed at the control cabinet inlet.
4
Connecting the controller
The controller is connected as illustrated in the following wiring diagrams. If individual inputs for other functions, e.g. for binary input, are to be used, it must be config ured in the configuration levels (Co1 to Co6). Open the housing to connect the cables. To connect the feeding cables, make holes in the marked locationsat the top, bottom or back of therear part of the housing and fit suitable cable glands.
-
-
-
76 EB 5474 EN
Page 77
Electrical connection
Connecting the sensors
Cables with a minimum cross-section of 2 x 0.5 mm² can be connected to the terminals at the back panel of the housing.
Connecting the actuators
Connect cables with at least 1.5 mm² suitable for damplocations to the terminals of the control ler output. The direction of travel needs to be checked at start-up.
Set slide switch to (+). Valves must open.
4
Set slide switch to (–). Valves must close.
4
Connecting the pumps
Connect allcables withat least 1.5 mm² to the terminals of the controller asillustrated inthe corre sponding wiring diagram.
Legend for wiring plans:
AA Analog output RL Return flow AA_GND Common analog grounding RüF Return flow sensor AE Analog input (general) RüFg Return flow sensor, total AF Outdoor temperature sensor SF Storage tank sensor BA Binary output SG_K Potentiometer BE Binary input SLP Storage tank charging pump BM_K Boiler operational fault SM_K Boiler fault alarm FG Potentiometer (valve) SM_Pu Pump fault alarm Frg_K Release boiler SM_S Collective fault alarm HK Heating circuit St Step of total capacity K Boiler VF Flow sensor KF Boiler sensor VFg Flow sensor, total MBUS Meter bus WWA DHW demand Pu Pump WWZ DHW forced charging RF Room sensor RK Control circuit
-
-
EB 5474 EN 77
Page 78
Electrical connection
System Anl 1
BE1 BE2 BE3 BE4 BE5 BE6 BE7 BE8 BE9 BE10 BE11 BE12 BE13 BE14 BE15 BE16 BE17
0...10V
0...10V BA1
BA2
System Anl 2
BE1 BE2 BE3
BE4 BE5 BE6 BE7 BE8 BE9 BE10 BE11 BE12 BE13 BE14 BE15 BE16 BE17
0...10V
0...10V BA1(2)
BA2(2)
RK1(RL)
RK2(HK)
Pu1(K1) Pu2(HK)
K1.1(ST.1)
SLP
RK1(RL)
RK2(HK)
Pu1(K1) Pu2(HK)
K1.1(ST.1)
K1.2(ST.2)
SLP
L
N
N
PU3
31 32 33
BA3
_
34
+
35
BA4
36
BA5
_
37
+
38
BA6
39
40
BA7
41
BA8
42 43
BA9
44
BA10
45 46
BA11
47
L
31 32 33
BA3
_
34
+
35
BA4
36
BA5
_
37
+
38
BA6
39 40
BA7
41
BA8
42 43
BA9
44
BA10
45
46
BA11
47
BA12
FG
30
BM_K1
29
VFg
28
WWA
27
AE (BE)
26
VF2
25
KF1
24
RüF2
23
RüF1
22
RüFg
21
AF
20
RF
19
SM_Pu1
18
SF1
17
SM_K1
16
SF2
15
Frg_K1
14
AE_GND
13
RK1(AE 0...10V)
12
RK2(AE 0...10V)
11
GND
10
AA_GND
9
AA1(RK1)
8
AA2(RK2)
7
6
WWZ
5
WWZ
4
SM_S
3
SM_S
2
1
FG
30
BM_K1
29
VFg
28
WWA
27
AE (BE)
26
VF2
25
KF1
24
RüF2
23
RüF1
22
RüFg
21
AF
20
RF
19
SM_Pu1
18
SF1
17
SM_K1
16
SF2
15
Frg_K1
14
AE_GND
13
RK1(AE 0...10V)
12
RK2(AE 0...10V)
11
GND
10
AA_GND
9
AA1(RK1)
8
AA2(RK2)
7
WWZ
6
WWZ
5
SM_S
4
SM_S
3
2
1
MODBUS
49
50
MODBUS
50
49
48
MBUS
48
MBUS
+15V
+15V
N +
N
+
78 EB 5474 EN
Page 79
System Anl 3
System Anl 4
Electrical connection
EB 5474 EN 79
Page 80
Electrical connection
System Anl 5
System Anl 6
80 EB 5474 EN
Page 81
Electrical connection
System Anl 7
Note!
If the terminalsBE1 toBE17 areconfigured as 0 to 20 mA or 4 to 20 mA inputs, use terminal 13 (AE_GND) instead of terminal 10 as GND.
EB 5474 EN 81
Page 82
Appendix
13 Appendix
13.1 Function block list
Co1: Boiler K1
Fb Function WE Anl Function block parameter / Range of values (default setting)
00 Release of boiler K1 OFF 1 to 7 Co1 -> Fb00 = ON: Release K1 depending on position of
01 Operational alarmK1ON 1 to 7 Co1 -> Fb01 = ON: Operational alarm over BE2 BM_K1
02 Operating hours
counter K1
03 Boiler sensor KF1 ON 1 to 6 Co1 -> Fb03 = ON: Monitoring with sensor
04 Return flow sensor
RüF1
05 RüL-RK1 ON
OFF 1 to 7 Co1 -> Fb02 = ON: Operating hours counter active
ON 1 to 7 Co1 -> Fb04 = ON: Monitoring with sensor
OFF
mode selector switch and state of BE17 (Frg_K1) Co1 -> Fb00 = OFF: Release K1 only depending on position
of mode selector switch
Co1 -> Fb01 = OFF: Operational alarm after start-up
Function block parameter:
Start-up time for boiler K1 / 0 to 5400 s (0 s)
Function block parameter: Initial value / 0 to 99999 (0 h) Option: count: Counting the operating hours
rESEt: Reset operating hours to initial value
Note: Can only be changed after entering the key number.
Co1 -> Fb03 = OFF: Monitoring with thermostat (BE7), Option: StEiG: Thermostat closes
FALL: Thermostat opens
Note: Cannot be deactivated in system Anl 7.
Co1 -> Fb04 = OFF: Monitoring with thermostat (BE9), Option: StEiG: Thermostat closes
FALL: Thermostat opens
3, 6, 7
Co1 -> Fb05 = ON: Return flow boost continuous control,
1, 2,
Co1 -> Fb05 = OFF: Return flow boost three-step control
4, 5
Function block parameters: K
(proportional gain) / 0.1 to 99.9 (6)
P
T
(reset time) / 0 to 999 s (120 s)
N
T
(derivative-action time) / 0 to 999 s (0 s)
V
With Co1 -> Fb05 = OFF additionally: T
(valve transit time) / 5 to 240 s (120 s)
Y
Modulation three-step control
Modulation continuous control, systems Anl 3, 6 and 7 only
82 EB 5474 EN
Page 83
Appendix
Fb Function WE Anl Function block parameter / Range of values (default setting) 06 Three-step pulsing/
on-off signal RüL-RK1
07 Modulation feedbackK1ON 3, 6, 7 Co1 -> Fb07 = ON: External feedback; the actually measured
Fb = Function block, WE = Default setting
ON 1 to 7 Co1 -> Fb06 = ON, only with Co1 -> Fb05 = OFF:
Three-step signal Co1 -> Fb06 = OFF: On-off signal
Function block parameters
Hysteresis / 1 to 30 °C (5°C) Min. activation time / 0 to 600 s (120 s) Min. deactivation time / 0 to 600 s (120 s)
resistance data are given
Function block parameters
Lower value (Start)=0%Modulation (0=1kΩ) Upper value (Stop) = 100 % Modulation (1000=2kΩ)
Co1 -> Fb07 = OFF: Internal feedback
Function block parameters:
K
(proportional gain) / 0.1 to 99.9 (2)
P
T
(reset time) / 0 to 999 s (30 s)
N
T
(derivative-action time) / 0 to 999 s (0 s)
V
T
(Modulation transit time) / 5 to 240 s (30 s)*
Y
* Only when Co1 -> Fb05 = ON is also configured
EB 5474 EN 83
Page 84
Appendix
Co2: Boiler K2 (systems Anl 4 to 7)
Fb Function WE Anl Function block parameter / Range of values (default setting)
00 Release of boiler K2 OFF 4 to 7 Co2 -> Fb00 = ON: Release K2 depending on position of
01 Operational alarmK2ON 4 to 7 Co2 -> Fb01 = ON: Operational alarm over BE1 BM_K2
02 Operating hours
OFF 4 to 7 Co2 -> Fb02 = ON: Operating hours counter active
counter K2
03 Boiler sensor KF2 ON 4 to 6 Co2 -> Fb03 = ON: Monitoring with sensor
04 Return flow sensor
ON 4 to 7 Co2 -> Fb04 = ON: Monitoring with sensor
RüF2
05 RüL-RK2 OFF 4 to 7 Co2 -> Fb05 = ON: Return flow boost continuous control,
mode selector switch and state of BE16 (Frg_K2) Co2 -> Fb00 = OFF: Release K2 only depending on position
of mode selector switch
Co2 -> Fb01 = OFF: Operational alarm after start-up
Function block parameter:
Start-up time for boiler K2 / 0 to 5400 s (0 s)
Function block parameter: Initial value / 0 to 99999 (0 h) Option: count: Counting the operating hours
rESEt: Reset operating hours to initial value
Note: Can only be changed after entering the key number.
Co2 -> Fb03 = OFF: Monitoring with thermostat (BE6), Option: StEiG: Thermostat closes
FALL: Thermostat opens
Co2 -> Fb04 = OFF: Monitoring with thermostat (BE8), Option: StEiG: Thermostat closes
FALL: Thermostat opens
Modulation three-step control
Co2 -> Fb05 = OFF: Return flow boost three-step control
Modulation continuous control, systems Anl 3, 6 and 7 only
Function block parameters: K
(proportional gain) / 0.1 to 99.9 (6)
P
T
(reset time) / 0 to 999 s (120 s)
N
T
(derivative-action time) / 0 to 999 s (0 s)
V
With Co2 -> Fb05 = OFF additionally: T
(valve transit time) / 5 to 240 s (120 s)
Y
84 EB 5474 EN
Page 85
Appendix
Fb Function WE Anl Function block parameter / Range of values (default setting) 06 Three-step pulsing/
on-off signal RüL-RK2
07 Modulation feedbackK2ON 7 Co2 -> Fb07 = ON: External feedback; the actually measured
Fb = Function block, WE = Default setting
ON 4 to 7 Co2 -> Fb06 = ON, only with Co2 -> Fb05 = OFF:
Three-step signal Co2 -> Fb06 = OFF: On-off signal
Function block parameters
Hysteresis / 1 to 30 °C (5°C) Min. activation time / 0 to 600 s (120 s) Min. deactivation time / 0 to 600 s (120 s)
resistance data are given
Function block parameters
Lower value (Start)=0%Modulation (0=1kΩ) Upper value (Stop) = 100 % Modulation (1000=2kΩ)
Co1 -> Fb07 = OFF: Internal feedback
Function block parameters:
K
(proportional gain) / 0.1 to 99.9 (2)
P
T
(reset time) / 0 to 999 s (30 s)
N
T
(derivative-action time) / 0 to 999 s (0 s)
V
T
(Modulation transit time) / 5 to 240 s (30 s)*
Y
* Only when Co2 -> Fb05 = ON is also configured
EB 5474 EN 85
Page 86
Appendix
Co2: Separate heating circuit (systems Anl 1 to 3)
Note! The configuration table “Co2: Separate heating circuit” is only available in conjunction with configuration Co5 -> Fb13 = ON.
Fb Function WE Anl Function block parameter / Range of values (default setting) 00 Reserved 01 Return flow sensor
RüF2
OFF 1 to 3 Co2 -> Fb01 = ON: Return flow sensor active
09 Control circuit HK2
OFF 1 to 3 Co2 -> Fb09 = ON: HK2 = OFF
deactivated
10 Type of characteristic ON 1 to 3 Co2 -> Fb10 = ON: Weather-compensated control,
option: 1 4-point characteristic
2 Gradient characteristic
Co2 -> Fb10 = OFF: Fixed set point control
11 Summer mode ON 1 to 3 Co2 -> Fb11 = ON: Summer mode active
Function block parameters:
START summer mode/ 01.01 to 31.12 (01.06) STOP summer mode/ 01.01 to 31.12 (30.09) Outdoor temperature limit / 0 to 40 °C (18 °C)
14 Continuous control
RK2
15 Three-step pulsing/
on/off RK2
OFF 1 to 3 Co2 -> Fb14 = ON: Continuous control
Function block parameters:
K
(proportional gain) / 0.1 to 99.9 (6)
P
T
(reset time) / 0 to 999 s (120 s)
N
T
(derivative-action time) / 0 to 999 s (0 s)
V
ON 1 to 3 Co2 -> Fb15 = ON: Three-step pulsing
Function block parameters:
K
(proportional gain) / 0.1 to 99.9 (6)
P
T
(reset time) / 0 to 999 s (120 s)
N
T
(derivative-action time) / 0 to 999 s (0 s)
V
T
(valve transit time) / 5 to 240 s (120 s)
Y
Co2 -> Fb15 = OFF: On/off switching
Fb = Function block, WE = Default setting
86 EB 5474 EN
Page 87
Appendix
Co2: Direct heating circuit)
Note! The configuration table “Co3: Direct heating circuit” is only available in conjunctionwith confi guration Co5 -> Fb13 = ON.
Fb Function WE Anl Function block parameter / Range of values (default setting) 00 Room sensor OFF 1 to 3 Co3 -> Fb00 = ON: Room sensor active
-
05 Optimization OFF 1 to 3 Co3 -> Fb05 = ON: option:
09 Control circuit HK3
OFF
10 Type of characteristic ON 1 to 3 Co3 -> Fb10 = ON: Weather-compensated control,
11 Summer mode ON 1 to 3 Co3 -> Fb11 = ON: Summer mode active
12 Potentiometer input OFF 1 to 3 Co3 -> Fb12 = ON: Connection to room panel
Fb = Function block, WE = Default setting
OFF 1 to 3 Co3 -> Fb09 = ON: HK2 = OFF
1 Activation acc. to outdoor temperature, deactivation
acc. to time schedule*
2 Activation acc. to outdoor temperature, deactivation
acc. to room sensor*
3 Activation and deactivation acc. to room sensor *Function block parameter:
Advance time / 0 to 360 min (120 min)
option: 1 4-point characteristic
2 Gradient characteristic
Co3 -> Fb10 = OFF: Fixed set point control
Function block parameters:
START summer mode/ 01.01 to 31.12 (01.06) STOP summer mode/ 01.01 to 31.12 (30.09) Outdoor temperature limit / 0 to 40 °C (18 °C)
EB 5474 EN 87
Page 88
Appendix
Co4: DHW heating
Fb Function WE Anl Function block parameter / Range of values (default setting)
00 DHW demand active ON 1 to 7 Co4 -> Fb00 = ON: DHW set point during DHW demand
Co4 -> Fb00 = OFF, only with Co5 -> Fb09 = OFF: External
change in lag/lead sequence 01 Reserved 02 DHW forced
charging
03 Storage tank sensor
SF1
04 Storage tank sensor
SF2
05 Reserved 06 DHW priority HK2 OFF 1 to 3*Co4 -> Fb06 = ON: HK2 in reduced operation during
07 DHW priority HK3 OFF 1 to 3*Co4 -> Fb07 = ON: Pump Pu3 switched off during storage
08 Thermal disinfection OFF 1 to 3*Co4 -> Fb08 = ON: Only if Co3 -> Fb03 = ON or
09 Reserved 10 Adopt vacations and
public holidays for DHW heating
Fb = Function block, WE = Default setting
OFF 1 to 7 Co4 -> Fb02 = ON: Monitoring VFg, KF1, KF2 for maximum
limit f. DHW forced charging
Function block parameter:
Maximum limit f. DHW forced charging / 20 to 120 °C (80 °C)
OFF 1 to 3*Co4 -> Fb03 = ON: Storage tank sensor SF1
Co4 -> Fb03 = OFF, only with CO4 -> Fb04 = OFF: Storage
tank thermostat
OFF 1 to 3*Co4 -> Fb04 = ON, only with Co4 -> Fb03 = OFF: Storage
tank sensor SF2
Co4 -> Fb04 = OFF: Only storage tank sensor SF1
storage tank charging
tank charging
Co4 -> Fb03 = ON and Co4 -> Fb04 = ON
Function block parameters:
Day of week / 0 = daily, 1 = Mon, 2 = Tue, …, 7 = Sun (3)
Disinfection temperature / 50 to 80 °C (70 °C)
Start time / 0:00 to 23:59 h (0:00 h)
Stop time / 0:00 to 23:59 h (4:00 h)
OFF 1 to 3*Co4 -> Fb10 = ON: Adopt vacations and public holidays
from Co2
88 EB 5474 EN
Page 89
Appendix
Co5: General functions
Fb Function WE Anl Function block parameter / Range of values (default setting)
00 Outdoor sensor ON 1 to 7 Co5 -> Fb00 = ON:
01 Delayed
outdoor tempera ture adaptation
02 Return flow sensor
total RüFg
03 Type of character-
istic
04 Configuration and
parameterization protection
05 Automatic summer
time/winter time changeover
06 Summer mode ON 1 to 7 Co5 -> Fb06 = ON: Summer mode active
07 Releasing sequence ON 4 to 7 Co5 -> Fb07 = ON: Temperature tAfor releasing sequence
08 – For internal purposes only!
OFF 1 to 7 Co5 -> Fb01 = ON: Delay active; option:
-
ON 1 to 7 Co5 -> Fb02 = ON: Differential temperature control using
ON 1 to 7 Co5 -> Fb03 = ON: Weather-compensated control;
OFF 1 to 7 Co5 -> Fb04 = ON: Locking the configuration and
ON 1 to 7 Co5 -> Fb05 = ON: Automatic summer time/winter time
option: FUEHL: Sensor at input AF
0-10: 0 to 10 V outdoor temperature at input AE2
Function block parameter:
Frost protection limit / –30 to 20 °C (3 °C) Co5 -> Fb00 = OFF: Input as BE;
option: Lead OFF (FoAUS)
Frost protection BE (FroSt)
Ab: Delay on decreasing temperature AUFAB: Delay on decreasing and rising temperature
Function block parameter:
Delay / 1 to 6 °C/h (3 °C/h)
variable weighting factors;
Function block parameters:
Intended temperature difference / 0 to 90 °C (10 °C) Kp factor for differential temperature control / 0 to 1 (0.5)
option: 1: 4-point characteristic
2: Gradient characteristic
Co5 -> Fb03 = OFF: Fixed set point control
parameterization levels, except for Co5 -> Fb 04
Note: Can only be changed after entering the key number.
changeover
Function block parameters:
START summer mode / 01.01 to 31.12 (01.06) STOP summer mode / 01.01 to 31.12 (30.09) Outdoor temperature limit / 0 to 40 °C (18 °C)
Co5 -> Fb07 = OFF: Unrestricted sequence
EB 5474 EN 89
Page 90
Appendix
Fb Function WE Anl Function block parameter / Range of values (default setting) 09 Automatic change
in lag/lead se quence
10 Condition for
change in lag/lead sequence
11 Displaying
lead/collective alarm
12 Common return
flow boost
13 Heating circuit with
DHW heating
14 Continuous running
of pumps
15 External
demand (AE1)
16 Control signal
deactivation
ON 5, 7 Co5 -> Fb09 = ON: Change in lag/lead sequence as per
­Co5 -> Fb09 = OFF: Change in lag/lead sequence only in the
ON 5, 7 Co5 -> Fb10 = ON: Change in lag/lead sequence acc. to
Co5 -> Fb10 = OFF: option: 1: Change in lag/lead sequence acc. to outdoor temperature 2: Change in lag/lead sequence acc. to capacity
OFF 5, 7 Co5 -> Fb11 = ON: Displaying lead
BA2 = 0 (Füh1), BA2 = 1 (Füh2) Co5 -> Fb11 = OFF: Displaying collective alarm with BA2
OFF 4 to 7 Co5 -> Fb12 = ON: RK1 as return flow boost for lead boiler
OFF 1 to 3
ON 1 to 7 Co5 -> Fb14 = ON: Continuous running of lead boiler pump
Function block parameters:
Pump lag time / 0 to 90 min (5 min) Boiler flow limit / 20 to 120 °C (55 °C)
OFF 1 to 7 Co5 -> Fb15 = ON: Function block parameter:
Boost / 0 to 30 °C (0 °C)
OFF 1 to 7 Co5 -> Fb16 = ON: Control signal deactivation after 3 x T
setting in Co5 -> Fb10
event of a malfunction
operating hours
Y
19 Parallel operation
of boilers
20 Burner activation
not dependent on sensor VFg
Fb = Function block, WE = Default setting
OFF 7 Co5 -> Fb19 = ON: Both boilers operate in parallel regardless
OFF 4 to 7 Co5 -> Fb20 = ON: Boilers are controlled exclusively ac
90 EB 5474 EN
of the system load. The boilers are started up one after the other taking into account the delay and lockout times.
­cording to the boiler sensors VF1 and VF2. VFg has no affect on the control loop.
Page 91
Co6: Sensor initialization
Fb Function WE Anl Comments
00 Global selection of
sensors Sensor input 1
01
to
to
Sensor input 17
17
ON Co6 -> Fb00 = ON: Pt 100, Pt 1000
Co6 -> Fb00 = OFF: Pt 100, PTC
OFF Co6 -> Fb01 to Fb17 = ON: Select sensor: 0–20 (mA),
4–20 (mA), Pt100, Pt1000, PtC, ntC, ni200, n1000 Co6 -> Fb01 to Fb17 = OFF: Same sensor selection as in
FB00
Appendix
23 Sensor calibration OFF Co6 -> Fb23 = ON: Sensor calibration of universal inputs
Fb = Function block, WE = Default setting
possible Co6 -> Fb23 = OFF: No sensor calibration
Co7: Error initialization
Fb Function SZ WE Comments
00 Reserved
BE1
01
to
to
BE17
17
in error status register
22 Limit monitoring OFF Can be configured over Modbus 23 Fault alarm binary
input changed
Fb = Function block, WE = Default setting, SZ = Key number
X OFF Co8 -> Fb01 = ON: Error alarm in error status register
to Co8 -> Fb17 = ON: Error alarm in error status register option: STEIG: Error alarm at BE1 to BE17 = CLOSED
FALL: Error alarm at BE1 to BE17 = OPEN
OFF Co8 -> Fb23 = ON: Subsequent errors are also added to the
error status register HR 60 (Bit D11)
EB 5474 EN 91
Page 92
Appendix
Co9: Modbus/meter bus
Fb Function SZ WE Function block parameter / Range of values (default setting)
00 Modbus ON Co9 -> Fb00 = ON: Modbus active
01 Modem function OFF Co9 -> Fb01 = ON: Modem function active 02 Modem dialing
procedure
03 Lock dial-up OFF Co9 -> Fb03 = ON: No dial-up in case an error
04 Modbus
16-bit addressing
05 Reserved 06 Text message alarm
to a mobile phone
07 SMS dialing
procedure
08 Reserved 09 Reserved 10 Alarm sent per fax OFF Co9 -> Fb10 = ON: Alarm sent per fax
11 Fax dialing
procedure
only with Co9 -> Fb06 = OFF and Co9 -> Fb10 = OFF
OFF Co9 -> Fb02 = ON: Pulse
Co9 -> Fb02 = OFF: Tone
Co9 -> Fb03 = OFF: Dial-up in case an error
OFF Co9 -> Fb04 = ON: 16-bit addressing
Co9 -> Fb04 = OFF: 8-bit addressing
OFF Co9 -> Fb06 = ON: Text message alarm to a mobile phone
only with Co9 -> Fb00 = OFF and Co9 -> Fb10 = OFF
OFF Co9 -> Fb07 = ON: Pulse
Co9 -> Fb07 = OFF: Tone
only with Co9 -> Fb00 = OFF and Co9 -> Fb06 = OFF
OFF Co9 -> Fb11 = ON: Pulse
Co9 -> Fb11 = OFF: Tone
Meter 1
21
to
to
Meter 3
23
Fb = Function block, WE = Default setting, SZ = Key number
OFF Co9 -> Fb21 = ON: Meter 1 is being processed
to Co9 -> Fb23 = ON: Meter 3 is being processed
Function block parameters:
Meter bus address for WMZ / 0 to 255 (255) Model code WMZ / P15, PS2,1434, CAL3, APAtO, SLS (1434) Reading mode WMZ / 24h, con, CoiL (con)
92 EB 5474 EN
Page 93
13.2 Parameter lists
PA1: Boiler 1 (systems Anl 1 to 7) PA2: Boiler 2 (systems Anl 4 to 7)
In the PA2 parameter level, “2” appears instead of “1” on the left of the display.
Appendix
Display Parameter designation
Range of values (default setting)
8
56
4
0
123
9
1211 1314
10
7
1617181920
15
2122
24
23
Maximum flow temperature KF1, 2
˚C
20 to 160 °C (90 °C)
1
8
56
4
0
123
9
1211 1314
10
7
1617181920
15
2122
24
23
Minimum return flow temperature RüF1, 2
˚C
20 to 120 °C
1
8
56
4
0
123
START
9
1211 1314
10
7
1
1617181920
15
2122
24
23
Minimum activation time for boiler K1, 2
0 to 90 min
min
This time must have elapsed before the boiler switched off.
8
56
4
0
123
9
1211 1314
10
7
1617181920
15
2122
24
23
Minimum deactivation time for boiler K1, 2
STOP
0 to 90 min
min
1
This time must have elapsed before the boiler switched on.
EB 5474 EN 93
Page 94
Appendix
PA2: Separate heating circuit (only in systems Anl 1 to 3 with Co5 -> Fb13 = ON) PA3: Direct heating circuit (only in systems Anl 1 to 3 with Co5 -> Fb13 = ON)
In the PA3 parameter level, “3” appears instead of “2” on the left of the display.
Display
0
123
0
123
0
123
0
123
Parameter designation
Range of values (default setting)
8
56
4
9
1211 13 14
10
7
1617181920
15
2122
24
23
4-point characteristic
Press to set parameters outdoor temperature (points 1 to 4) flow temperature (points 1 to 4) and set-back difference (points 2 to 3).
In PA2 (PA3) only with Co2 (Co3) -> Fb10 = ON, option: 1
8
56
4
9
1211 13 14
10
7
1617181920
15
2122
24
23
4-point characteristic, point 1: Outdoor temperature
˚C
Outdoor temperatures of the points 2, 3, 4 are marked by squares below the numbers 2, 3, 4.
–20 to 50 °C (Point 1: –10 °C, point 2: –5 °C, point 3: 5 °C, point 4: 10 °C)
In PA2 (PA3) only with Co2 (Co3) -> Fb10 = ON, option: 1
8
56
4
9
1211 13 14
10
7
1617181920
15
2122
24
23
4-point characteristic, point 1: Flow temperature
˚C
Flow temperatures of the points 2, 3, 4 are marked by squares below the numbers 2, 3, 4.
20 to 160 °C (Point 1: 90 °C, point 2: 80 °C, point 3: 68 °C, point 4: 50 °C)
In PA2 (PA3) only with Co2 (Co3) -> Fb10 = ON, option: 1
8
56
4
9
1211 13 14
10
7
1617181920
15
2122
24
23
4-point characteristic: Set-back difference, point 2
˚C
Set-back difference of the point 3 is marked by square below the number 3.
0 to 30 °C (Point 2: 15 °C, point 3: 20 °C)
In PA2 (PA3) only with Co2 (Co3) -> Fb10 = ON, option: 1
94 EB 5474 EN
Page 95
Appendix
Display
0
123
0
123
0
123
0
123
Parameter designation
Range of values (default setting)
8
56
4
9
1211 13 14
10
7
1617181920
15
2122
23
24
Gradient, flow
0.4 to 3.2 (1.8)
In PA2 (PA3) only with Co2 (Co3) -> Fb10 = ON, select: 2.
8
56
4
9
1211 13 14
10
7
1617181920
15
2122
24
23
Level (parallel shift), flow
˚C
–30 to 30 °C (0 °C)
In PA2 (PA3) only with Co2 (Co3) -> Fb10 = ON, select: 2.
8
56
4
9
1211 13 14
10
7
1617181920
15
2122
24
23
˚C
Set-back difference
0 to 30 °C (15 °C)
In PA2 (PA3) only with Co2 (Co3) -> Fb10 = ON, select: 2.
8
56
4
9
1211 13 14
10
7
1617181920
15
2122
24
23
Fixed set point control, flow temperature set point
˚C
20 to 160 °C (70 °C)
In PA2 (PA3) only with Co2 (Co3) -> Fb10 = OFF
8
56
4
0
123
9
1211 13 14
10
7
1617181920
15
2122
24
23
Fixed set point control, set-back difference
˚C
0 to 30 °C (15 °C)
In PA2 (PA3) only with Co2 (Co3) -> Fb10 = OFF
EB 5474 EN 95
Page 96
Appendix
Display
0
123
0
123
0
123
0
123
Parameter designation
Range of values (default setting)
8
56
4
9
1211 13 14
10
7
1617181920
15
2122
24
23
Maximum flow temperature
˚C
20 to 160 °C (90 °C)
8
56
4
9
1211 13 14
10
7
1617181920
15
2122
24
23
Minimum flow temperature
˚C
20 to 120 °C (20 °C)
8
56
4
9
1211 13 14
10
7
1617181920
15
2122
24
23
Day set point (room set point)
˚C
10 to 40 °C (20 °C)
Only in PA3 with Co3 -> Fb00 = ON and Co3 -> Fb05 = ON
8
56
4
9
1211 13 14
10
7
1617181920
15
2122
24
23
Night set point (reduced room set point)
˚C
10 to 40 °C (17 °C)
56
4
0
123
7
96 EB 5474 EN
Only in PA3
8
9
1211 13 14
10
1617181920
15
2122
24
23
Sustained temperature
˚C
10 to 40 °C (10 °C)
Only in PA3
Page 97
Appendix
Display
0
123
START
0
123
STOP
0
123
0
123
4
4
4
456
56
56
56
Parameter designation
Range of values (default setting)
8
9
1211 13 14
10
7
1617181920
15
2122
24
23
Outdoor temperature deactivation value in reduced operation
˚C
–10 to 50 °C (10 °C)
8
9
1211 13 14
10
7
1617181920
15
2122
24
23
Outdoor temperature deactivation value in rated operation
˚C
0 to 50 °C (22 °C)
8
9
1211 1314
10
7
1617181920
15
2122
24
23
Times-of-use
1–7: daily 1, 2, …, 7: Monday, Tuesday, …, Sunday
8
9
1211 1314
10
7
1617181920
15
2122
24
23
Vacations
Max. 10 vacation periods
8
56
4
0
123
9
1211 1314
10
7
1
1
2
1
2
2
1617181920
15
2122
24
23
Public holidays
Max. 20 public holidays
min
EB 5474 EN 97
Page 98
Appendix
Display
0
123
0
123
0
123
0
123
Parameter designation
Range of values (default setting)
8
56
4
9
1211 1314
10
7
1617181920
15
2122
24
23
Boiler set point for DHW demand
˚C
20 to 120 °C (65 °C)
8
56
4
9
1211 1314
10
7
1617181920
15
2122
24
23
DHW demand ON (SF1)
˚C
20 to 90 °C (40 °C)
8
56
4
9
1211 1314
10
7
1617181920
15
2122
24
23
DHW demand OFF
˚C
20 to 90 °C (45 °C)
Only with Co4 -> Fb03 = ON and Co4 -> Fb04 = ON
8
56
4
9
1211 1314
10
7
1617181920
15
2122
24
23
Hysteresis (only if SF1 is selected)
˚C
0 to 30 °C (5 °C)
56
4
0
123
7
98 EB 5474 EN
Only with Co4 -> Fb03 = ON and Co4 -> Fb04 = OFF
8
9
1211 1314
10
1617181920
15
2122
24
23
Times-of-use for DHW 1–7: daily
1, 2, …, 7: Monday, Tuesday, …, Sunday
Page 99
PA5: General parameters
Appendix
Display Parameter designation
Range of values (default setting)
9876543210
9876543210
9876543210
8
56
4
0
123
9
1211 13 14
10
1617181920
7
15
242322212019181716151413121110
Time
242322212019181716151413121110
Date (Day – Month)
242322212019181716151413121110
Date (Year)
2122
24
23
4-point characteristic
Press to set parameters
outdoor temperature (points 1 to 4) flow temperature (points 1 to 4) and set-back difference (points 2 to 3).
Only with Co5 -> Fb03 = ON, option: 1
EB 5474 EN 99
Page 100
Appendix
Display Parameter designation
Range of values (default setting)
8
56
4
0
123
9
1211 13 14
10
7
1617181920
15
2122
24
23
4-point characteristic, point 1: Outdoor temperature
˚C
Outdoor temperatures of the points 2, 3, 4 are marked by squares below the numbers 2, 3, 4.
–20 to 50 °C (Point 1: –10 °C, point 2: –5 °C, point 3: 5 °C, point 4: 10 °C)
Only with Co5 -> Fb03 = ON, option: 1
8
56
4
0
123
9
1211 13 14
10
7
1617181920
15
2122
24
23
4-point characteristic, point 1: Flow temperature
˚C
Flow temperatures of the points 2, 3, 4 are marked by squares below the numbers 2, 3, 4.
20 to 160 °C (Point 1: 90 °C, point 2: 80 °C, point 3: 68 °C, point 4: 50 °C)
Only with Co5 -> Fb03 = ON, option: 1
8
56
4
0
123
9
1211 13 14
10
7
1617181920
15
2122
24
23
4-point characteristic: Set-back difference, point 2
˚C
Set-back difference of the point 3 is marked by square below the number 3.
0 to 30 °C (Point 2: 15 °C, point 3: 20 °C)
Only with Co5 -> Fb03 = ON, option: 1
8
56
4
0
123
9
1211 13 14
10
7
1617181920
15
2122
24
23
Gradient, flow
56
4
0
123
100 EB 5474 EN
0.4 to 3.2 (1.8)
Only with Co5 -> Fb03 = ON, option: 2
8
9
1211 13 14
10
7
1617181920
15
2122
24
23
Level (parallel shift), flow
˚C
–30 to 30 °C (0 °C)
Only with Co5 -> Fb03 = ON, option: 2
Loading...