Samson TROVIS 5433 Mounting And Operating Instructions

Firmware version 1.2x Edition January 2008
Mounting and Operating Instructions
EB 5433 EN
Automation System TROVIS 5400 Heating and District Heating Controller TROVIS 5433
®
Electronics from SAMSON
Disclaimer of liability
We are constantly developing our products and therefore, reserve the right to change the product or the information contained in this document at any time without notice.
We do not assume any liability for the accuracy or completeness of these mounting and operating instructions. Moreover, we do not guarantee that the buyer can use the product for an intended purpose. SAMSON rejects any liability for claims by the buyer, especially claims for compensation including lost profits or any other financial loss, except the damage was caused intentionally or by gross negligence. If an essential term of the contract is breached by negligence, SAMSON’s liability is limited to the foreseeable damage.
Safety instructions
4
The device may only be assembled, started up or operated by trained and experienced personnel familiar with the product. Proper shipping and appropriate storage are assumed.
4
The controller has been designed for use in electrical power systems. For wiring and maintenance, you are required to observe the relevant safety regulations.
2 EB 5433 EN
Disclaimer of liability
Contents
1 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1 Operating elements. . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1.1 Rotary pushbutton . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1.2 Rotary switches. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.2 Operating modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.3 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.4 Displaying data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.5 Setting the controller time . . . . . . . . . . . . . . . . . . . . . . . 10
1.6 Setting the times-of-use . . . . . . . . . . . . . . . . . . . . . . . . 11
1.6.1 Setting public holidays . . . . . . . . . . . . . . . . . . . . . . . . 13
1.6.2 Setting vacation periods . . . . . . . . . . . . . . . . . . . . . . . . 15
1.7 Presetting temperature set points . . . . . . . . . . . . . . . . . . . . 17
2 Start-up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2.1 Setting the system code number . . . . . . . . . . . . . . . . . . . . 18
2.2 Activating and deactivating functions. . . . . . . . . . . . . . . . . . 19
2.3 Changing parameters . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.4 Calibrating sensors . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.5 Resetting to default values . . . . . . . . . . . . . . . . . . . . . . . 24
3 Manual operation. . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4 Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
5 Functions of the heating circuit . . . . . . . . . . . . . . . . . . . . 36
5.1 Weather-compensated control . . . . . . . . . . . . . . . . . . . . . 36
5.1.1 Gradient characteristic . . . . . . . . . . . . . . . . . . . . . . . . 37
5.1.2 4-point characteristic . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.2 Fixed set point control . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.3 Drying of jointless floors . . . . . . . . . . . . . . . . . . . . . . . . 39
5.4 Outdoor temperature dependent deactivation. . . . . . . . . . . . . . 40
5.4.1 OT deactivation value rated operation . . . . . . . . . . . . . . . . . 40
5.4.2 OT deactivation value reduced operation. . . . . . . . . . . . . . . . 41
5.4.3 OT activation value rated operation . . . . . . . . . . . . . . . . . . 41
5.4.4 Summer mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
5.5 Delayed outdoor temperature adaptation. . . . . . . . . . . . . . . . 42
5.6 Remote operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
5.6.1 Room panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
5.6.2 Floating switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
5.7 Optimization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
5.7.1 Advance heating depending on outdoor temperature . . . . . . . . . . 44
EB 5433 EN 3
Contents
5.7.2 Optimization with room sensor . . . . . . . . . . . . . . . . . . . . 45
5.8 Flash adaptation . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
5.9 Room temperature dependent control . . . . . . . . . . . . . . . . . 46
6 Functions of the DHW circuit. . . . . . . . . . . . . . . . . . . . . . 48
6.1 DHW heating in the storage tank system . . . . . . . . . . . . . . . . 48
6.2 DHW heating in the storage tank charging system . . . . . . . . . . . 50
6.3 DHW heating in the instantaneous water system . . . . . . . . . . . . 53
6.4 Intermediate heating operation . . . . . . . . . . . . . . . . . . . . 54
6.5 Parallel pump operation . . . . . . . . . . . . . . . . . . . . . . . . 54
6.6 Operation of circulation pump during storage tank charging . . . . . . 54
6.7 Priority operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
6.7.1 Reverse control . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
6.7.2 Set-back operation . . . . . . . . . . . . . . . . . . . . . . . . . . 55
6.8 Forced charging of the DHW storage tank . . . . . . . . . . . . . . . 56
6.9 Thermal disinfection of the DHW storage tank . . . . . . . . . . . . . 56
6.10 Vacation periods and public holidays for DHW heating. . . . . . . . . 58
7 System-wide functions . . . . . . . . . . . . . . . . . . . . . . . . 59
7.1 Automatic summer time/winter time changeover . . . . . . . . . . . . 59
7.2 Frost protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
7.3 Forced operation of the pumps. . . . . . . . . . . . . . . . . . . . . 59
7.4 Return flow temperature limitation . . . . . . . . . . . . . . . . . . . 60
7.5 Condensate accumulation control . . . . . . . . . . . . . . . . . . . 61
7.6 Three-step control . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
7.7 On/off control . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
7.8 Requesting/processing external demand . . . . . . . . . . . . . . . . 63
7.9 Locking the manual level. . . . . . . . . . . . . . . . . . . . . . . . 67
7.10 Locking the rotary switches . . . . . . . . . . . . . . . . . . . . . . 67
8 Operational faults . . . . . . . . . . . . . . . . . . . . . . . . . . 68
8.1 Error alarm list . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
8.2 Sensor failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
8.3 Temperature monitoring . . . . . . . . . . . . . . . . . . . . . . . . 69
8.4 Collective alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
9 Memory pen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
10 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
11 Electrical connection. . . . . . . . . . . . . . . . . . . . . . . . . . 73
12 Appendix. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
4 EB 5433 EN
Contents
12.1 Function block lists . . . . . . . . . . . . . . . . . . . . . . . . . . 76
12.2 Parameter lists . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
12.3 Sensor resistance tables . . . . . . . . . . . . . . . . . . . . . . . . 90
12.4 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
12.5 Customer data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Abbreviations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
EB 5433 EN 5
Contents
1 Operation
The controller is ready for use with the temperatures and operating schedules preset by the manufacturer. On start-up, the current time and date need to be adjusted at the controller (–> section 1.5).
1.1 Operating elements
The operating controls are located in the front panel of the controller and protected by a Plexiglas door with an integrated quick guide.
1.1.1 Rotary pushbutton
Rotary pushbutton
Turn q: Display, select parameters and function blocks
Press : Confirm adjusted selection or settings
1.1.2 Rotary switches
Rotary switch for “Configuration and parameterization“
COPA Switch to configuration and parameter level
Times-of-use for DHW circulation pump
DHW temperature set point
Day set point (rated room temperature)
Night set point (reduced room temperature)
Times-of-use for heating
Controller time: setting the current time, date and year
INFO Switch to information level
(view measured values and their set points/limit values)
6 EB 5433 EN
Operation
*
Rotary switch for “Operating modes“
– Manual operation: valve closes 0 Manual operation: valve stationary + Manual operation: valve opens
Control operation deactivated, frost protection only DHW heating active, heating switched off Night mode (reduced operation) Day mode (rated operation) Automatic mode (operation according to time schedule)
1.2 Operating modes
Day mode (rated operation)
Regardless of the programmed times-of-use and summer mode, the controller uses the set points relevant for rated operation.
The
DHW temperature set point
remains constantly active in system Anl 6.
Night mode (reduced operation)
Regardless of the programmed times-of-use, the controller uses the set points relevant for re­duced operation.
The
Sustained DHW temperature
remains constantly active in system Anl 6.
Automatic mode
During the programmed times-of-use, the controller works in rated operation. Outside these times-of-use, the controller is in reduced operation, unless control operation is deactivated depending on the outdoor temperature. The controller switches automatically between both operating modes.
Manual operation – 0 +
Valves and pumps can be controlled manually (–> section 3). The default setting of the circulation pump is permanent operation.
EB 5433 EN 7
Operation
1.3 Display
During operation, the display indicates the current time as well as information about the op
­eration of the controller. The days of the week are represented by black squares below the row of numbers at the top of the display (1 = Monday, 2 = Tuesday, and shown here, 7 = Sunday). Icons indicate the operating status of the controller.
The controller status can be displayed in operating level (–> section 1.4).
8 EB 5433 EN
Operation
102435
M
1 2
3 4
7681091112131514 16 1817 19 20 2221 23 24
M
9
8
7
6
5
4
3
2
1
10 11 12 13 14
Fig. 1 · Icons
1 Automatic mode 2 Public holidays 3 Day mode
(rated operation) 4 Vacation mode 5 Night mode
(reduced operation) 6 Summer mode
7 Frost protection 8 Manual operation 9 Operational fault 10 Heating circuit demand 11 Valve heating circuit
OPEN (left arrow) CLOSED (right arrow)
12 Pump operation
1 Heating circul. pump UP 2 Exchanger charging
pump TLP 3 Storage charg. pump SLP 4 Circulation pump ZP
13 DHW demand 14 Valve DHW circuit
OPEN (left arrow) CLOSED (right arrow)
1.4 Displaying data
The time and temperature values of connected sensors and their set points can be retrieved and displayed in the info level.
Proceed as follows:
Turn rotary switch “Configuration and parameterization“ to INFO. Display shows: time _ _:_ _ The black squares below the row of numbers at the top of the display in this case repre
-
sent the times-of-use.
q
Depending on the configuration of the controller, different data points are displayed in info level.
Room temperature, RS
Outdoor temperature, AS
/ Temperature at flow sensor VS1, heating circuit/primary exchanger circuit
Temperature at return flow sensor RüS
/ Temperature at flow sensor VS2, DHW circuit (Anl 3 to 5)
, Temperature at storage sensor (Anl 2 to 4)
Temperature at return flow sensor RüS_TW (Anl 5)
Compare the set point/limit temperature and the actual temperature.
EB 5433 EN 9
Operation
1.5 Setting the controller time
The current time and date need to be set immediately after start-up or after a power failure lasting more than 24 hours. This is the case when the time blinks on the display.
Proceed as follows:
Turn rotary switch “Configuration and parameterization“ to data point “Controller time“. Display shows: time
Activate editing mode for controller time.
blinks.
q
Edit time.
Confirm time. Display shows: date (day.month) The individual week days which are represented by black squares below the row of numbers can be read off at the top of the display: 1 = Monday, 2 = Tuesday, ..., 5 = Friday (shown here)
Activate editing mode for date.
blinks.
q
Edit date.
Confirm date. Display shows: year
Activate editing mode for year.
blinks.
q
Edit year. Confirm year.
Display shows: time Return rotary switch “Configuration and
parameterization“ to INFO. Display shows: time
10 EB 5433 EN
Operation
1.6 Setting the times-of-use
Three times-of-use can be set for each day of the week. If a time-of-use is not required, its start and stop times must be set to identical times.
The times-of-use for heating and the DHW circulation pump are set using the top rotary switch:
Times-of-use Position Heating
DHW circulation pump
Parameters
WE* Rotary switch / Range of values
Period/day 1 1, 2, 3, 4, 5, 6, 7 with 1-7 = every day,
1 = Monday, 2 = Tuesday, ..., 7 = Sunday Start first time-of-use 7:00 0:00 h to 24:00 h; in steps of 30 minutes Stop first time-of-use 22:00 0:00 h to 24:00 h; in steps of 30 minutes Start second time-of-use 22:00 0:00 h to 24:00 h; in steps of 30 minutes Stop second time-of-use 22:00 0:00 h to 24:00 h; in steps of 30 minutes Start third time-of-use 22:00 0:00 h to 24:00 h; in steps of 30 minutes Stop third time-of-use 22:00 0:00 h to 24:00 h; in steps of 30 minutes
*Default setting (WE) valid for heating (switch position )
Note!
The times-of-use for DHW heating are set in parameter level PA2 similar to the times-of-use for heating and the DHW circulation pump.
EB 5433 EN 11
Operation
Proceed as follows: Turn rotary switch “Configuration and
parameterization“ to “Times-of-use”. Display shows:
1
q
Select period/day for times-of-use: 1 = Monday, 2 = Tuesday , ..., 7 = Sunday, 1-7 = daily
Activate editing mode for period/day. Display shows:
1*, START
* The display 1 (2, 3) indicates the first (second, third)
time-of-use.
Activate editing mode for start time.
and blink.
q
Edit start time (steps of 30 minutes). Confirm start time.
Display shows:
STOP
q
Edit stop time (steps of 30 minutes). Confirm stop time.
Display shows:
2, START
The second and third time-of use are set similar to the first one.
q
Select
End
.
Exit active data point “Period/day“.
To set the times-of-use for additional days, repeat the instructions in the fields highlighted in gray.
Return rotary switch “Configuration and parameterization“ to INFO. Display shows: time
Note!
Do not use the
1–7
menu to check the adjusted times-of-use as only the times-of-use for
Monday are displayed under this data point, which are then adopted for the whole week.
12 EB 5433 EN
Operation
1.6.1 Setting public holidays
On public holidays, the times-of-use specified for Sunday apply. A maximum of 20 public holidays may be entered.
Parameter
WE Level / Range of values Public holidays PA-SYS / 01.01 to 31.12 (1 Jan to 31 Dec) Adopt public holidays and
vacations for DHW
0 CO2 -> F07 - 1
Proceed as follows:
Turn rotary switch “Configuration and parameterization“ to COPA. Display shows:
0,NR
blinks.
q
Set valid key number. Confirm key number.
Display shows:
PA 1
q
Select parameter level PA-SYS. Open parameter level PA-SYS.
q
Select “Public holidays“. Display shows:
Open “Public holidays“.
q
If applicable, select
– –.– –
.
Activate editing mode for public holiday.
blinks.
q
Edit public holiday. Confirm public holiday.
To enter additional public holidays, re-select
– – – –
and repeat the steps in the fields high
-
lighted in gray.
q
Select
End
.
Exit parameter level. Display shows: CO1
Return rotary switch “Configuration and parameterization“ to INFO. Display shows: time
EB 5433 EN 13
Operation
Note!
Public holidays that are not assigned to a specific date should be deleted by the end of the year so that they are not carried on into the following year.
Deleting a public holiday:
q
Under “Public holidays“, select the holiday you wish to delete. Confirm selection.
q
Select
– –.– –
(display – –.– – is adjustable between 31.12 and 01.01).
Delete public holiday.
14 EB 5433 EN
Operation
1.6.2 Setting vacation periods
During vacation periods, the heating constantly remains in reduced operating mode. The DHW heating is monitored for frost protection, if necessary. A maximum of 10 vacation pe
-
riods can be entered.
Parameter
WE Level / Range of values Vacation period (START, STOP) PA-SYS / 01.01 to 31.12 (1 Jan to 31 Dec) Adopt public holidays and
vacations for DHW
0 CO2 -> F07 - 1
Proceed as follows:
Turn rotary switch “Configuration and parameterization“ to COPA. Display shows:
0,NR
blinks.
q
Set valid key number. Confirm key number.
Display shows:
PA 1
q
Select parameter level PA-SYS. Open parameter level PA-SYS.
q
Select “Vacation periods“. Display shows:
Open “Vacation periods“ Display shows:
START
q
If applicable, select
– –.– –
.
Activate editing mode for start date of vacation period.
START
and blink.
q
Edit start date of vacation period. Confirm start date of vacation period.
Display shows:
STOP, start date of vacation period
q
Edit end of vacation period. Confirm end of vacation period.
To enter additional vacation periods, re-select
– –.– –
and repeat the steps in the fields
highlighted in gray.
EB 5433 EN 15
Operation
q
Select
End
.
Exit parameter level. Display shows: CO1
Return rotary switch “Configuration and parameterization“ to INFO. Display shows: time
Note!
Vacation periods should be deleted by the end of the year so that they are not carried on into the following year.
Deleting vacation periods:
q
Under “Vacation periods“, select the start date of the period you wish to delete. Confirm selection.
q
Select
– –.– –
(display – –.– – is adjustable between 31.12 and 01.01).
Delete vacation period.
16 EB 5433 EN
Operation
1.7 Presetting temperature set points
For the heating circuit, the desired room temperatures during the day (
Day set point
) and
during the night (
Night set point
) can be preset. In the DHW circuit, the temperature you wish the domestic hot water to be heated to can be adjusted.
The temperature set points are adjusted using the top rotary switch:
Desired temperature set point Position Day set point
Night set point
DHW temperature set point
Parameters
WE Rotary switch / Range of values Day set point 20 °C 10 to 40 °C Night set point 15 °C 10 to 40 °C DHW temperature set point 55 °C Min. to max. DHW temperature
Proceed as follows:
Turn rotary switch “Configuration and parameterization“ to “Set point temperature“. Display shows: temperature value
Activate editing mode for set point temperature. Display blinks.
q
Edit set point temperature. Confirm set point temperature. Return rotary switch “Configuration and parameterization“ to INFO.
Display shows: time
EB 5433 EN 17
Operation
2 Start-up
The modifications of the controller configuration and parameter settings described in this sec
-
tion can only be carried out after the valid key number has been entered. The valid key number for initial start-up can be found on page 96. To avoid unauthorized
use of the key number, remove the page or make the key number unreadable.
2.1 Setting the system code number
Six different hydraulic schemes are available. Each system configuration is represented by a system code number. The different schemes are dealt with in section 4. Available controller functions are described in sections 5, 6 and 7.
Changing the system code number resets previously adjusted function blocks to their default values. Function block parameters and parameter level settings remain unchanged. The system code number is set in the configuration level.
Proceed as follows:
Turn rotary switch “Configuration and parameterization“ to COPA. Display shows:
0,NR
blinks.
q
Set valid key number. Confirm key number.
Display shows:
PA 1
q
Select
Anl
.
View current system code number. Activate editing mode for system code number.
Anl
blinks.
q
Set system code number. Confirm system code number.
Display shows:
End
Exit data point “System code number“. Return rotary switch “Configuration and parameterization“ to INFO. Display shows: time
18 EB 5433 EN
Start-up
2.2 Activating and deactivating functions
A function is activated via the associated function block. The numbers 0 to 24 in the top row of the display represent the respective function block numbers. When a configuration level is opened, the activated function blocks are indicated by a black square on the right-hand side below the function block number. For more details on function blocks, refer to section 12.1.
The functions are grouped by topics:
4
CO1: Heating circuit
4
CO2: DHW heating
4
CO-SYS: System-wide
Proceed as follows:
Turn rotary switch “Configuration and parameterization“ to COPA. Display shows:
0,NR
blinks.
q
Set valid key number. Confirm key number.
Display shows:
PA 1
q
Select configuration level. Open configuration level.
q
Select function block. Activated function blocks are marked by “- 1“. Deactivated function blocks are marked by “- 0“.
Activate editing mode for function block.
F__
blinks.
q
Activate function block. Display shows:
F__ - 1
Or:
q
Deactivate function block. Display shows:
F__ - 0
EB 5433 EN 19
Start-up
Confirm settings. If the function block is not closed, further function block parameters can be adjusted. Proceed as follows:
1. Open data point.
2. Make desired changes and confirm.
3. If applicable, the next function block parameter is displayed. When all function block parameters have been adjusted, select
End
and confirm.
The active function block is closed.
An active function block is represented by a black square on the right-hand side below the function block number.
To adjust additional function blocks, repeat the steps in the fields highlighted in gray.
q
Select
End
. Exit configuration level. Return rotary switch “Configuration and parameterization“ to INFO. Display shows: time
20 EB 5433 EN
Start-up
2.3 Changing parameters
Depending on the adjusted system code number and the activated functions, not all parame
­ters listed in the parameter list in the Appendix (–> section 12.2) might be available. The parameters are grouped by topics:
4
PA1: Heating circuit
4
PA2: DHW heating
4
PA-SYS: Public holidays and vacation periods
Proceed as follows:
Turn rotary switch “Configuration and parameterization“ to COPA. Display shows:
0,NR
blinks.
q
Set valid key number. Confirm key number.
Display shows:
PA 1
q
Select parameter level. Open parameter level.
q
Select parameter. Activate editing mode for parameter.
q
Set parameter. Confirm parameter.
To adjust additional parameters, repeat the steps in the fields highlighted in gray.
q
Select
End
. Exit parameter level. Return rotary switch “Configuration and parameterization“ to INFO. Display shows: time
EB 5433 EN 21
Start-up
2.4 Calibrating sensors
The connected sensors are calibrated in configuration level CO-SYS. The following applies:
4
CO-SYS -> F02 - 1: Pt 1000 sensors (default)
4
CO-SYS -> F02 - 0: PTC sensors The resistance values of the sensors can be found on page 91. If the temperature values displayed on the controller differ from the actual temperatures, the
measured values of all connected sensors can be changed or readjusted. To calibrate a sen
­sor, the currently displayed sensor value must be changed to match a temperature (reference value) measured directly at the point of measurement. Activate the sensor calibration in CO-SYS over function block F08. An incorrect sensor calibration can be deleted by setting F08 - 0.
Proceed as follows:
Turn rotary switch “Configuration and parameterization“ to COPA. Display shows:
0,NR
blinks.
q Set valid key number.
Confirm key number. Display shows:
PA 1
q
Select configuration level CO-SYS. Open configuration level CO-SYS.
q
Select function block F08. Activate editing mode for function block F08.
q
Activate function block F08 (F08 - 1). Confirm function block settings.
q
Select sensor icon:
Room sensor RS
Outdoor sensor AS
22 EB 5433 EN
Start-up
Flow sensor VS1
Return flow sensor RüF
/ Flow sensor VS2/VS1 (system Anl 6)
Storage sensor SS1
Storage sensor SS2
Return flow sensor RüS_TW
Activate editing mode for measured value.
q
Correct measured value. Read the actual temperature directly from the thermometer at the point of measurement and enter this value as the reference temperature.
Confirm corrected measured value.
Additional sensors are calibrated similarly.
q
Select
End
.
Exit function block F08.
q
Select
End
. Exit configuration level CO-SYS. Return rotary switch “Configuration and parameterization“ to INFO. Display shows: time
EB 5433 EN 23
Start-up
2.5 Resetting to default values
All parameters as well as the function block parameters can be reset to their default settings (WE).
Proceed as follows:
Turn rotary switch “Configuration and parameterization“ to COPA. Display shows:
0,NR
blinks.
q
Set valid key number. Confirm key number.
q
Select configuration level CO-SYS. Open configuration level CO-SYS.
q
Select function block F09. Activate editing mode for function block F09.
q
Set F09 - 1. Reset parameters to their default values.
q
Select
End
. Exit configuration level CO-SYS. Return rotary switch “Configuration and parameterization“ to INFO. Display shows: time
24 EB 5433 EN
Start-up
3 Manual operation
Switch to manual operating mode to access all outputs (see wiring diagram in section 11). When manual operation is activated using the rotary switch for “Operating modes“, the ro
­tary switch “Configuration and parameterization“ should be in position INFO, otherwise the pump level cannot be accessed over the rotary pushbutton.
Proceed as follows:
Turn rotary switch “Configuration and parameterization“ to INFO. Turn “Operating modes“ switch to +, 0 or –.
Display shows:
q
Select pump level PU. Open pump level PU.
Display shows: PU 1 - 0 / PU 1 - 1: heating circulation pump switched off/on
q
Select pump: PU 1: Heating circulation pump UP PU 2: Exchanger charging pump TLP (ZP / Anl 5) PU 3: Storage tank charging pump SLP (DHW valve opens / Anl 5) PU 4: Circulation pump ZP (DHW valve closes / Anl 5) PU 5: Binary output BA (TLP / Anl 5)
Confirm selection. PU blinks.
q
Activate/ deactivate output: PU _ - 0: deactivate pump/binary output PU _ - 1: activate pump/binary output
Confirm edited settings. The modified values remain active as long as the controller is in the manual mode.
q
Select
End
. Exit pump level PU. Turn bottom rotary switch to the desired operating mode.
Note!
Setting the rotary switch to position “Manual operation“ (+ 0 –) also sets PU1 - 1 (not in sys
-
tem Anl 6). All other outputs are deactivated.
EB 5433 EN 25
Manual operation
BE BA AE RK
RüS VS1UPHK RS
BE BA AE RK
VS1UP RüSHK RS
4 Systems
Six different hydraulic schemes are available. The systems can be configured both as pri
­mary and secondary systems. The fundamental hydraulic difference between a primary and a secondary system (heat exchanger in the heating/DHW circuit replaced by a mixing valve) is illustrated in Fig. 2. The controller settings do not have to be changed.
26 EB 5433 EN
Systems
Primary system, indirect Primary system, direct
BE BA AE RK
RüSVS1UP HK RS
Fig. 2 · Converting a primary system into a secondary system
Secondary system
Boiler systems:
Based on the systems Anl 1 to Anl 3, one-stage boiler systems can be set up. The boiler can be controlled by an on/off output (CO-SYS -> F05 - 0).
EB 5433 EN 27
Systems
BE BA AE RK
RüS VS1UPHK RS
BE BA AE RK
UPHK_2-Pkt RSVS1
Fig. 3 · Schematics of a boiler system
Boiler
1-stage
HK Heating circuit RüS Return flow sensor UP Circulation pump VS Flow sensor RS Room sensor
BE Binary input BA Binary output AE Analog input RK Control loop
System Anl 1
Default values
CO1 -> F01 - 0 (without RS) CO1 -> F07 - 1 (with AS) CO-SYS -> F01 - 1 (with RüS)
28 EB 5433 EN
Systems
BE BA AE RK
ASRüS VS1UPHK RS
System Anl 2
Default values
CO1 -> F01 - 0 (without RS) CO1 -> F07 - 1 (with AS) CO2 -> F01 - 1 (with SS1) CO2 -> F02 - 0 (without SS2) CO-SYS -> F01 - 1 (with RüS)
EB 5433 EN 29
Systems
HK Heating circuit RüS Return flow sensor UP Circulation pump VS Flow sensor RS Room sensor SLP Storage tank charging pump WW Hot water KW Cold water ZP Circulation pump SS Storage tank sensor AS Outdoor sensor
BE Binary input BA Binary output AE Analog input RK Control loop
BE BA AE RK
WW
KW
ASZP
RüS VS1
UP
SS1
HK
RS
SLP
System Anl 2, settings deviating from default settings
Settings deviating from default values
CO2 -> F10 - 0 (priority for DHW heating) CO2 -> F06 - 1, option 2 (control of changeover valve and UP)
30 EB 5433 EN
Systems
BE BA AE RK
WW
KW
ASZP
RüS VS1 SS1
HK
RS
UP SLP
Loading...
+ 74 hidden pages