Samson TROVIS 5432 Mounting And Operating Instructions

Automation System 5400 Heating and District Heating Controller
TROVIS 5432
Electronics from SAMSON
Mounting and Operating Instructions
EB 5432 EN
Firmware version 2.1x Edition July 2004
Disclaimer of liability
Disclaimer of liability
We are constantly developing our products and therefore, reserve the right to change the product or the information contained in this document at any time without notice.
We do not assume any liability for the accuracy or completeness of these mounting and op erating instructions. Moreover, we do not guarantee that the buyer can use the product for an intended purpose. SAMSON rejects any liability for claims by the buyer, especially claims for compensation including lost profits or any other financial loss, except the damage was caused intentionally or by gross negligence. If an essential term of the contract is breached by negligence, SAMSON’s liability is limited to the foreseeable damage.
Safety instructions
The device may only be assembled, started up or operated by trained and
4
experienced personnel familiar with the product. Proper shipping and ap­propriate storage are assumed. The controller has been designed for use in electrical power systems. For
4
wiring and maintenance, you are required to observe the relevant safety regulations.
-
2 EB 5432 EN
Contents

Table of contents

1 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1 Control knob . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Operating modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.4 Displaying data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.5 Setting the system time . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.6 Setting the times-of-use . . . . . . . . . . . . . . . . . . . . . . . . 10
1.7 Stand-by mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.7.1 Vacation mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.7.2 Outdoor temperature dependent deactivation. . . . . . . . . . . . . . 12
1.8 Party mode
1.9 Correcting the set point . . . . . . . . . . . . . . . . . . . . . . . . 14
1.9.1 Correcting the set point temporarily . . . . . . . . . . . . . . . . . . 14
1.9.2 Correcting the set point permanently . . . . . . . . . . . . . . . . . . 14
2 Start-up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.1 Configuration and parameterization . . . . . . . . . . . . . . . . . . 15
3 Manual operation mode . . . . . . . . . . . . . . . . . . . . . . . 16
4 Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
5 Functions of the heating circuit . . . . . . . . . . . . . . . . . . . . 23
5.1 Weather-compensated control . . . . . . . . . . . . . . . . . . . . . 23
5.2 Fixed set point control . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.3 Drying of jointless floors . . . . . . . . . . . . . . . . . . . . . . . . 25
5.4 Automatic deactivation of the heating . . . . . . . . . . . . . . . . . 26
5.5 Outdoor temperature dependent advance heating . . . . . . . . . . . 27
5.6 Delayed adaptation to the outdoor temperature . . . . . . . . . . . . 27
5.7 Remote control . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
5.8 Flash adaptation . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
5.9 Room temperature-based control. . . . . . . . . . . . . . . . . . . . 29
6 Functions of the DHW circuit . . . . . . . . . . . . . . . . . . . . . 30
6.1 DHW priority . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
7 System-wide functions . . . . . . . . . . . . . . . . . . . . . . . . 32
7.1 Automatic summer time/winter time changeover . . . . . . . . . . . . 32
7.2 Frost protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
7.3 Forced operation of the pumps. . . . . . . . . . . . . . . . . . . . . 32
7.4 Limiting the return flow temperature . . . . . . . . . . . . . . . . . . 33
(constant rated operation)
. . . . . . . . . . . . . . . . . 13
EB 5432 EN 3
Contents
7.5 Three-step control . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
7.6 On/off control . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
8 Malfunctions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
9 Infrared interface . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
10 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
11 Electrical connection. . . . . . . . . . . . . . . . . . . . . . . . . . 39
12 Appendix. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
12.1 Function block list . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
12.2 Parameter list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
12.3 Resistance values with Pt 1000 sensor . . . . . . . . . . . . . . . . . 43
12.4 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
12.5 User data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Abbreviations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
4 EB 5432 EN
Operation
1 Operation
The controller is ready for use with the temperatures and operating time schedules preset by the manufacturer. On start-up, the current time and date need to be set at the controller (–> section 1.5).
1.1 Control knob
Turn q:
*
Select parameters, displays and temperature displays
Press :
Confirm adjusted selection or settings
Press for three seconds 3s:
Switch from the operating level to the user level as well as from the user level to the installation level
1.2 Operating modes
Automatic mode
Display: and in the time-of-use periods, and outside of the times-of-use periods The controller works in rated operation within the programmed times-of-uses and in reduced operation outside of the times-of-use, provided that the control operation is not deactivated due to the outdoor temperature. The controller switches automatically between both operat­ing modes.
Day mode (constant rated operation)
Display: Regardless of the programmed times-of-use, the set points relevant for rated operation are used constantly by the controller.
Stand-by mode (vacation mode)
Display: In stand-by mode, the heating is switched off regardless of the programmed times-of-use. The frost protection mode is still active.
Night mode (reduced operation; can only be set over the room panel)
Display: Regardless of the programmed times-of-use, the set points relevant for reduced operation are used constantly by the controller.
PArTY
HoLidAY
or
or – – –
EB 5432 EN 5
Operation
1.3 Display
The current set point appears on the display during operation. Which set point is displayed depends on:
The configured type of control
4
The programmed times-of-use
4
Weather-compensated control, room set point mode (F1 - 1 and F9 - 1)
Day set point (time-of-use period)* or night set point (outside of time-of-use period)
Weather-compensated control (F1 - 1 and F9 - 0), fixed set point control (F1 - 0 and F7 - 0)
Flow temperature (times-of-use period)* or reduced flow temperature (outside of time-of-use period)
The set point (left) and the measured value (right) are displayed in this example.
* Appears on the depicted display
Note!
The icon appears additionally on the display for a control functioning with the room panel unit (F7- 1). A temporarily active set point (corrected once) is indicated on the display by the icon together with the icon (refer to section 1.9.1). An active function for drying of jointless floors is indicated on the display by the icon together with the icon (refer to section 5.3).
6 EB 5432 EN
Operation
1 Days of week
1 2
3
4 5 6 7 8 9 10
Fig. 1 · Icons
Mon (1) to Sun (7)
2 Times-of-use
periods 3 Malfunction 4 Manual mode 5 Automatic mode 6 Day operation
(rated operation) 7 Night operation
(reduced operation) 8 Outdoor sensor 9 Room sensor 10 Hot water demand
1.4 Displaying data
The times-of-use periods, measured values as well as set points or limit values can be re­trieved and displayed in the user level (–> Fig. 10 on page 49). The controller configuration determines which measured values as well as which set points or limit values appear on the display.
Proceed as follows:
3s Switch to user level.
Display: Time
q
Select value. The different data points appear on the display in sequence:
Display Meaning
Current time-of-use
,
Open data point
q
Display daily times-of-use. Confirm
Times-of-use
Times-of-use
appears on the display.
.
by pressing the knob when
End
EB 5432 EN 7
Operation
Display Meaning
* Day set point
* Night set point
or flow temperature set point (F1 - 0 and F7 - 0)
or reduced flow temperature set point (F1 - 0 and F7 - 0) OT deactivating value in rated operation (F1 - 1 and F9 - 0) OT deactivating value in reduced operation (F1 - 1 and F9 - 0)
t1
t2
,
t2
,
t3
t4
t4
,
t5
, Measured value: Storage tank temperature (F7 - 0)
q
Select
End
Switch to operating level.
Measured value: Flow temperature
Flow temperature set point
Measured value: Outdoor temperature
Delayed outdoor temperature (F3 - 1)
Measured value: Storage tank temperature (F1 - 0 and F7 - 1)
Activating/deactivating value for DHW system (DHW set point + on/off differential)
Measured value: Return air temperature
Maximum return air temperature
Measured value: DHW temperature monitoring
Monitoring value
Measured value: Room temperature (F7 - 1)
Day set point or night set point (influenced by a room panel, if applicable)
Activating/deactivating value for DHW system (DHW set point + on/off differential)
on the display.
* Note!
The icon appears additionally on the display for a control functioning with the room panel unit (F7- 1).
8 EB 5432 EN
Operation
1.5 Setting the system time
The current time and date need to be set immediately after start-up and after a power failure lasting more than 72 hours has occurred. This is indicated by the time blinking on the dis play. The time is already in the edit mode and can be changed directly. The first two instruc tions steps are then omitted.
Proceed as follows:
3s Switch to user level.
Display: Time. Open time data point.
blinks.
Change time.
q
Confirm time setting. Display: Year.
Change year.
q
Confirm year. Display: Date (day.month) as well as day of the week ( = Mon, = Tue, …, = Sun)
q
Change date. Confirm date.
Display: Time
q
Select
End
on the display.
Switch to operating level.
-
-
Note! On initial start-up and after a power failure lasting more than 72 hours, the controller switches automatically to the operating level after the date has been set and confirmed. The last two steps are omitted.
Note! The controller automatically switches to the operating level if the control knob is left untouched for five minutes.
EB 5432 EN 9
Operation
1.6 Setting the times-of-use
Three time-of-use periods can be set for each day of the week. If not all the time-of-use periods are required, the start and stop times of the third time-of-use period (for just two periods) must be set to identical times or, alternatively, the start and stop times of the second time-of-use (for just one period). The controller then automatically sets the start and stop times to the stop time of the previous time-of-use period. The times-of-use are displayed in the user level (–> Fig. 10 on page 49).
Note!
You can set the times-of-use for each day or for an entire week. If you want to set the times-of-use for certain days to be different than the rest of the week, we recommend you set the times-of-use for the entire week first (display: ) and then al ter the times-of-use for each day which require different times-of-use. The week setting of the times-of-use writes over any already programmed times-of-use.
-
Parameter
Time period/day 1–7 = daily,
Start time of first time-of-use 07:00 00:00 to 24:00 h; in steps of 30 minutes Stop time of first time-of-use 22:00 00:00 to 24:00 h; in steps of 30 minutes Start time of second time-of-use 22:00 00:00 to 24:00 h; in steps of 30 minutes Stop time of second time-of-use 22:00 00:00 to 24:00 h; in steps of 30 minutes Start time of third time-of-use 22:00 00:00 to 24:00 h; in steps of 30 minutes Stop time of third time-of-use 22:00 00:00 to 24:00 h; in steps of 30 minutes
WE Range of values
= Monday, = Tuesday, …, = Sunday
Note!
The controller includes an optimized activation function which makes sure the controller auto matically changes to the valid set point ( blinks), six hours at the earliest before the pro
-
grammed time-of-use starts, to compensate for low outdoor temperatures.
10 EB 5432 EN
-
Proceed as follows: 3s Switch to the user level.
Display: Time Select
q
q
q
q
To set other times-of-use, repeat the instructions in the fields highlighted in gray.
q
Select
End
on the display.
Exit
Times-of-use
q
Select
End
Switch to operating level.
.
on the display.
Times-of-use
Open data point
Select time period/day and times-of-use:
= Monday, = Tuesday, …, = Sunday and
with
Open time period/day. Display: Start time of first time-of-use period
and blink.
Change start time (in steps of 30 minutes).
Confirm start time. Display: Stop time of first time-of-use period
and blink. Change stop time. Confirm stop time.
Display: Set time-of-use period
.
Times-of-use
blinks.
= first time-of-use period, = second time-of-use period, = third time-of-use period.
blinks.
.
= daily
Operation
Note!
The controller automatically switches to the operating level if the control knob is left un touched for five minutes.
EB 5432 EN 11
-
Operation
1.7 Stand-by mode
1.7.1 Vacation mode
Function independent of controller setting. The vacation mode function places the heating circuit into the stand-by mode: the heating is
deactivated, however, frost protection is guaranteed. The functions of an existing DHW cir cuit remain unchanged.
The vacation mode function is set in the operating level (set point display).
Proceed as follows:
Select menu
q
will go). The display blinks.
Confirm vacation mode. Alternatively: Wait 3 minutes until the display stops blinking. The vacation mode is activated.
Note!
The controller is in vacation mode when HoLidAY appears on the display. The controller exits the vacation mode when the current set point is reset (–> section 1.9).
HoLidAY
(turn knob to the left as far as it
-
1.7.2 Outdoor temperature dependent deactivation
Controller setting F1 - 1 and F9 - 1 The outdoor temperature dependent deactivation function places the heating circuit into the
stand-by mode dependent on the outdoor temperature. The heating is deactivated when the outdoor temperature exceeds the active limit value (plus 1 °C on/off differential), however, frost protection is still guaranteed. – – – appears on the display as the flow temperature set point while the outdoor temperature dependent deactivation function is active. The functions of an existing DHW circuit remain unchanged.
OT deactivating value in rated operation
The
value in reduced operation
12 EB 5432 EN
outside of the times-of-use apply and are set in the user level.
within the times-of-use and
OT deactivating
Proceed as follows: Vorgehen: 3s Switch to user level.
Display: Time. Select
OT deactivating value in rated operation
OT deactivating value in reduced operation
Open data point. Change data point. Confirm data point. Select
End
on the display.
Switch to operating level.
OT deactivating value in rated operation
OT deactivating value in reduced operation
q
q
q
Operation
or
.
1.8 Party mode
Function independent of controller setting. The party mode function sets the controller in rated operation mode: regardless of the pro-
grammed times-of-use, the by the controller.
The party mode function is set in the operating level (set point display).
Proceed as follows:
Note!
The controller is in constant rated operation when PArtY appears on the display. The controller exits the constant rated operation mode when the current set point is reset (–> section 1.9).
(constant rated operation)
Set point dayorFlow temperature set point
q
Select menu will go). The display blinks.
Confirm party mode. Alternatively: Wait 3 minutes until the display stops blinking. The party mode is activated.
PArtY
(turn knob to the right as far as it
are constantly used
EB 5432 EN 13
Operation
1.9 Correcting the set point
The current set point is displayed in the operating level. In rated operation, the or the
Flow temperature set point
tion, the
Night set point
or the
appears on the display (–> section 1.3). In reduced opera
Reduced flow temperature set point
appears on the display.
Day set point
1.9.1 Correcting the set point temporarily
The current set point which appears on the display can be changed for just as long as the rated operation mode (programmed time-of-use period) is running or the reduced operation mode (outside of the time-of-use period) is running. This temporary correction of the set point is made in the operating level (set point display).
Proceed as follows:
Turn the control knob one position.
q
The icon display blinks. Change the parameter.
q
Confirm the new parameter setting. Alternatively: Wait until the display stops blinking. The new parameter setting has been saved. The temporarily active set point (corrected once) is indicated on the display by the icon together with the icon.
1.9.2 Correcting the set point permanently
The permanent change of well as the made in the user level.
Night set pointorReduced flow temperature set point
Day set pointorFlow temperature set point
in reduced operation is
in rated operation as
-
Proceed as follows:
3s Switch to user level. Display: Time
q
Select menu Open the set point.
q
Change the set point. Confirm the set point.
q
Select Switch to operating level.
14 EB 5432 EN
Set point
End
on the display.
(–> page 6).
Start-up
2 Start-up
2.1 Configuration and parameterization
The controller is configured and parameterized in the configuration and parameterization level (–> Fig. 10 on page 49). After accessing the configuration and parameterization level (CoPa level), the function blocks F1 to F9 appear at first, followed by the parameters P1 to P18. The individual functions and parameters are listed in the Appendix (–> page 41). The configuration and parameterization level is locked to prevent unintentional and unautho rized access. This level can only be opened when the key number is known. The key number can be found on page 48. To avoid unauthorized use of the key number, remove the page or make the key number unreadable.
Proceed as follows:
3s Switch to user level. Display: Time
Select
End
q
3s Switch to the configuration and parameterization level (CoPa level).
Display: 0,
on the display.
nr
blinks.
q Set key number.
Confirm key number. Display: F1
q
Select function block* or parameter. Open selected data point.
q
Change data point. Confirm setting of the data point.
To set further function blocks and parameters, repeat the instructions in the fields highlighted in gray.
q
Select
End
on the display.
Return to operating level. Display: Current set point
-
* Note!
A function block is activated when F_ 1 appears on the display; it is deactivated when F_ 0 appears on the display.
EB 5432 EN 15
Manual operation mode
3 Manual operation mode
In manual operation mode, the circulation pump UP is always switched on. The output SLP is usually switched off. Initially, no control signal is issued for the heating circuit.
Activate the manual operation mode in the configuration and parameterization level (CoPa level) over function block F2.
Functions
Manual operation of an actuator 0 F2 - 1
Proceed as follows:
3s Switch to user level.
Display: Time Select
End
q
3s Switch to the configuration and parameterization level (CoPa level).
Display: 0, Set key number.
q
Confirm key number. Display: F1
q
Select function block F2. Open function block F2.
q
Activate function block F2. Display: F2 - 1.
Activate manual operation mode. Display: and
q
Move the actuator manually: oPEn: OPEN (3-step signal); activate output (on/off signal) StoP: Last position (3-step signal); deactivate output (on/off signal) cLoSE: CLOSED (3-step signal)
on the display.
nr
blinks.
StoP
WE Configuration
Note!
The frost protection function is not active in manual operation mode.
16 EB 5432 EN
Loading...
+ 36 hidden pages