Samson TROVIS 5100, TROVIS 5171 Mounting And Operating Instructions

Automation System TROVIS 5100 Control and Processing Unit TROVIS 5171
Electronics from SAMSON
Mounting and Operating Instructions
EB 5171 EN
®
Disclaimer of liability
Disclaimer of liability
We are constantly developing our products and therefore, reserve the right to change the product or the information contained in this document at any time without notice.
We do not assume any liability for the accuracy or completeness of these mounting and operating instructions. Moreover, we do not guarantee that the buyer can use the product for an intended purpose. SAMSON rejects any liability for claims by the buyer, especially claims for compensation including lost profits or any other financial loss, except the damage was caused intentionally or by gross negligence. If an essential term of the contract is breached by negligence, SAMSON’s liability is limited to the foreseeable damage.
Safety instructions
The device may only be assembled, started up or operated by trained and
4
experienced personnel familiar with the product. Proper shipping and appropriate storage are assumed.
The device has been designed for use in electrical power systems. For wiring
4
and maintenance, you are required to observe the relevant safety regulations.
2 EB 5171 EN

Contents

Contents
1 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1 Operating elements. . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1.1 Operating keys. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3 Displaying data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.4 Setting the controller time . . . . . . . . . . . . . . . . . . . . . . . . 8
1.5 Setting the times-of-use . . . . . . . . . . . . . . . . . . . . . . . . . 9
2 Start-up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.1 Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.2 Activating and deactivating functions. . . . . . . . . . . . . . . . . . 13
2.3 Changing parameters . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.4 Entering the key number. . . . . . . . . . . . . . . . . . . . . . . . 16
2.5 Configuring the universal inputs . . . . . . . . . . . . . . . . . . . . 16
2.6 Resetting to default values . . . . . . . . . . . . . . . . . . . . . . . 18
3 Manual operation. . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4 System-wide functions . . . . . . . . . . . . . . . . . . . . . . . . 20
4.1 Automatic summer time/winter time changeover . . . . . . . . . . . . 20
5 Operational faults . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.1 Error status register . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.2 Fault alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.2.1 Sending SMS text message in case of a fault . . . . . . . . . . . . . . 22
5.2.2 Sending fax in case of a fault alarm . . . . . . . . . . . . . . . . . . 23
6 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
6.1 RS-232-C system bus interface. . . . . . . . . . . . . . . . . . . . . 25
6.2 System bus interface with RS-232/RS-485 cable converters
(for four-wire bus). . . . . . . . . . . . . . . . . . . . . . . . . . . 26
6.3 Description of communication parameters to be adjusted . . . . . . . . 27
6.4 Meter bus interface . . . . . . . . . . . . . . . . . . . . . . . . . . 29
6.4.1 Activating the meter bus . . . . . . . . . . . . . . . . . . . . . . . . 29
7 LON communication . . . . . . . . . . . . . . . . . . . . . . . . . 31
7.1 Sending outdoor temperatures and the controller time. . . . . . . . . . 31
8 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
9 Electrical connection. . . . . . . . . . . . . . . . . . . . . . . . . . 35
10 Appendix. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
10.1 Function block list . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
EB 5171 EN 3
Contents
10.2 Parameter list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
10.3 Sensor resistance tables . . . . . . . . . . . . . . . . . . . . . . . . 44
10.4 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
10.5 Customer data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Frequently used abbreviations. . . . . . . . . . . . . . . . . . . . . 54
4 EB 5171 EN
Operation
1 Operation
The TROVIS 5171 Control and Processing Unit (Programmable Logic Controller = PLC) is freely programmable. The controller is delivered without an executable program in the mem ory. The application must be developed separately for the desired purpose on the PC using
®
ISaGRAF
(programming as in DIN IEC 61131-1) and then transferred to the controller.
On start-up, after transferring the generated application, the current time and date must be set in the controller (–> section 1.4).
1.1 Operating elements
1.1.1 Operating keys
The keys are located in the front panel of the PLC and protected by a Plexiglas door.
Changeover key
(press with pen or other pointed item) Switch between levels (–> inside of back cover)
Reset key
(press with pen or other pointed item) Reset freely accessible parameters and function blocks to their default values (factory settings)
-
Cursor key(s)
– Navigate in levels (also in application developed with ISaGRAF – Change values
Enter key
®
– Open levels (also in application developed with ISaGRAF
) – Activate editing mode for parameters and function blocks – Confirm entered settings
®
)
EB 5171 EN 5
Operation
1.2 Display
After switching on and during operation, the PLC is in the operating level. When the applica tion is active, either the name of the application or a customer-specific menu is displayed.
®
This menu can be customized to meet your specific needs in the ISaGRAF
STOP
If no application has been loaded or activated,
is displayed.
application.
If an active connection between the PC and PLC exists, the icon is displayed. In the info level, the current controller time and operating data are displayed. The binary in
puts and outputs are represented by black squares below the row of numbers. Icons indicate the operating status of the PLC.
Time-controlled
operation
Status binary input
Status binary output
Fault alarm
Manual operation
Connection PC – PLC
The icons can also be displayed with the application created in ISaGRAF®.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
BO BI START STOP
Binary inputs/outputs Application active
No application loaded in PLC/ application stopped
Vacation periods Public holidays
-
-
Fig. 1 · Icons
6 EB 5171 EN
Operation
1.3 Displaying data
The states of the inputs and outputs, the available memory as well as information on fault alarms and communication can be retrieved in the info level.
The following levels provide information on the device status:
FREI _ _ _ KB: Free memory; for programming with ISaGRAF
4
INF1 AI: Measured value of connected analog inputs (AE1 to AE17);
4
BI: Status of the binary inputs (ON/OFF) AO: Output value of the two analog outputs [V] BO: Status of the binary outputs (ON/OFF)
INF2…6 Do not exist
4
INF7 LON communication
4
INF8 FSR: Error status register
4
INF9 Modbus/meter bus communication
4
Proceed as follows:
3s Switch to configuration and parameter level.
Display shows: Select Switch to info level.
Display shows: controller time Select info level (–> Fig. 6 on page 53). Open info level. Select data point.
Exit info level:
Select Return to operating level.
Display shows: name of the application or customer-specific menu
(in devices with LON interface and CO7 -> FB00 = ON)
BRUCH: Sensor failure information
END
END
Bar graph indicates the cycle time: Block 1 = 1 ms, Block 2 = 2 ms, Block 3 = 4 ms, Block 4 = 8 ms, ...
depending on configuration of universal inputs in CO6 [mA, °C, V]
PA5
.
.
®
EB 5171 EN 7
Operation
1.4 Setting the controller time
The current time and date need to be set immediately after start-up and after a power failure lasting more than 24 hours.
PA5
The time is set in
Proceed as follows:
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
parameter level.
3s Switch to configuration and parameter level.
Display shows:
PA5
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Open PA5 parameter level. Display shows: controller time
Activate editing mode for controller time. Change controller time.
Confirm changed time. Display shows: date (day.month)
Activate editing mode for date. Change date.
Confirm date. Display shows: year
Activate editing mode for year. Change year. Confirm year.
Display shows:
Zeit 1
8 EB 5171 EN
Operation
Select
END
. Exit PA5 parameter level. Select
END
. Exit configuration and parameter level.
Display shows: controller time
END
Select
. Switch to operating level.
Display shows: name of the application or customer-specific menu
Note!
If no key is pressed for two minutes, the PLC returns to operating level.
1.5 Setting the times-of-use
The controller provides 12 times-of-use that can be utilized separately. Within a specified time-of-use (ZEIT 1 to ZEIT 12), two usage periods can be programmed for each day of the week. If you do not require all usage periods, the start and stop times of the idle periods must be set to identical times.
Note!
The behavior of the PLC during and outside the times-of-use is to be determined in the ISaGRAF
Parameters
Period, day Mo -- So PA5 / Mo -- So, Monday to Sunday Start time-of-use 1 7:00h PA5 / 0:00h to 24:00h; in steps of 30 minutes Stop time-of-use 1 12:00h PA5 / 0:00h to 24:00h; in steps of 30 minutes Start time-of-use 2 12:00h PA5 / 0:00h to 24:00h; in steps of 30 minutes Stop time-of-use 2 22:00h PA5 / 0:00h to 24:00h; in steps of 30 minutes
®
application.
Default Parameter level/Range of values
EB 5171 EN 9
Operation
Proceed as follows: 3s Switch to configuration and parameter level.
Display shows:
PA5
Open PA5 parameter level.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Display shows: controller time Select desired times-of-use (ZEIT 1 to ZEIT 12), e.g.
ZEIT 1. Display shows:
ZEIT _
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Activate editing mode for selected time-of-use. Display shows:
Mo -- So
(Monday to Sunday)
Select period/day for time-of-use.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
START
Activate editing mode for selected time-of-use.
START
Display shows:
; blinks.
Edit start time (steps of 30 minutes).
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
STOP
Confirm start time. Display shows:
STOP
Edit stop time (steps of 30 minutes). Confirm stop time.
Display shows:
START
The second time-of-use is set similarly to the first.
To set times-of-use for each day, repeat the instructions in the fields highlighted in gray.
10 EB 5171 EN
Operation
Note!
Do not use the Mo -- So menu to check the programmed times-of-use. If this menu is opened after the times-of-use have been set, the usage times programmed for each day of the week are reset to their default settings.
Select
END
. Exit parameter level. Select
END
. Exit configuration and parameter level.
Display shows: controller time
END
Select
. Switch to operating level.
Display shows: name of the application or customer-specific menu
Note!
If no key is pressed for two minutes, the PLC returns to the operating level.
EB 5171 EN 11
Start-up
2 Start-up
2.1 Programming
Programming the PLC requires a PC with ISaGRAF®software.
®
The ISaGRAF cific needs of your plant (ISaGRAF must follow the structures and rules stipulated in DIN IEC 61131-3. The PLC may be pro grammed with the languages defined in the standard: Sequential Function Chart (SFC), In
software enables you to program a control system that is tailored to the spe
®
development environment 1400-7621). Programming
-
­struction List (IL), Flow Chart (FC), Function Block Diagram (FBD), Ladder Diagram (LD), and Structured Text (ST).
There are 128 KB of memory available in the PLC for the ISaGRAF
®
application.
The programmed application is complied to machine code in the PC environment. This code is then transferred to the PLC over the front RJ-45 jack (connecting cable 1400-7308).
Programming languages:
Sequential Function Chart (SFC):
Instruction List (IL): Low-level textual language for logic and arithmetic operations Flow Chart (FC): High-level language used to visualize the data flow Function Block Diagram
(FBD): Ladder Diagram (LD): Simple graphics-based language for logical operations (boolean) Structured Text (ST): High level language similar to PASCAL and C especially designed for
Used to describe operations of a sequential process with a simple graphic representation
Graphics-based language for building and combining complex functions (logical, arithmetic)
control applications
For operation and application of the ISaGRAF®environment, refer to the documentation in cluded in the software package. To enable simple and clear programming, ready-made functions and function blocks are available from SAMSON.
-
-
Note! In ISaGRAF®, internal variables can be assigned (hexadecimal) network addresses. The status or value of the internal variable is written to the associated holding register and can be read over Modbus. The PLC holding registers 42001 to 46999 are reserved for this purpose.
Important! The PLC application must be reloaded after a cold start.
12 EB 5171 EN
Start-up
2.2 Activating and deactivating functions
A function is activated over the associated function block. The numbers 0 to 24 in the top row of the display represent the respective function block numbers. When a configuration level is opened, the activated function blocks are indicated by a black square on the right-hand side below the function block number. For more details on function blocks, refer to section 10.1.
The functions are grouped by topics:
CO1…4 Do not exist
4
CO5 Higher level functions
4
CO6 Configuration of universal inputs
4
CO7 LON communication
4
CO8 Fault initialization
4
CO9 Modbus/meter bus communication
4
Proceed as follows:
3s Switch to configuration and parameter level.
Display shows: Select configuration level (–> Fig. 6 on page 53). Open configuration level. Select function block. Activate editing mode for selected function block.
Function block number blinks. When the display shows tion 2.4.
Activate function block (FB = ON). An activated function block is indicated by a black square on the right-hand side be low the function block number.
Or:
Deactivate function block (FB = OFF). Confirm changed settings.
If the function block is not closed, further function blocks can be edited.
(in devices with LON interface and CO7 -> FB00 = ON)
PA5
0 0 0 0
, the valid key number must be entered, see sec
-
-
EB 5171 EN 13
Start-up
Proceed as follows: Change settings and confirm changes. If applicable, the following function block parameter is displayed. Once all parameters have been confirmed, the opened function block is closed.
To set further function blocks, repeat the instructions in the fields highlighted in gray.
END.
Select Exit configuration level. Select
END
.
Exit configuration and parameter level. Display shows: controller time
END
Select Switch to operating level.
Display shows: name of the application or customer-specific menu
.
Note!
If no key is pressed for two minutes, the PLC returns to the operating level.
14 EB 5171 EN
2.3 Changing parameters
Start-up
Depending on the activated functions, not all parameters listed in the Appendix (–> sec tion 10.2) might be available.
The parameters are grouped by topics:
PA1…4 Do not exist
4
PA5 Controller time, times-of-use
4
PA6 Does not exist
4
PA7 LON communication
4
PA8 Does not exist
4
PA9 Modbus/meter bus communication
4
Proceed as follows:
3s Switch to configuration and parameter level. Display shows:
Select parameter level (–> Fig. 6 on page 53). Open parameter level. Select parameter. Activate editing mode for selected parameter. Change parameter. Confirm parameter.
To set further parameters, repeat the instructions in the fields highlighted in gray.
Select Exit parameter level. Select Exit configuration and parameter level.
Display shows: controller time Select Switch to operating level.
Display shows: name of the application or customer-specific menu
(in devices with LON interface and CO7 -> FB00 = ON)
END
.
END
.
END
.
PA5
-
Note!
If no key is pressed for two minutes, the PLC returns to operating level.
EB 5171 EN 15
Start-up
2.4 Entering the key number
Some functions are protected against unintentional and unauthorized access by a key num ber. The key number, which is required to activate and deactivate protected functions, can be found on page 49. To avoid unauthorized use, remove the page or make the key number unreadable.
Proceed as follows:
On the display,
Enter key number. Confirm key number.
When the correct number has been entered, the function block you wish to change blinks on the display. When an invalid key number is entered, the PLC switches to the next configuration level.
The key number remains active for approximately 5 minutes.
0 0 0 0
blinks.
2.5 Configuring the universal inputs
Note!
Connect a 50 When the inputs (0 to 10 V or 0(4) to 20 mA) are active, use terminal 13 for GND instead of terminal 10.
17 universal inputs are available. The inputs can be configured to serve as a binary, analog (0 to 10 V, 0(4) to 20 mA) or sensor input. The hardware must be configured accordingly (sensor initialization).
The sensor resistance values can be found on page 44. The following applies:
CO6 -> Fb00 = ON: Pt 100 and Pt 1000 mixed (default)
4
CO6 -> Fb00 = OFF: Pt 100 and PTC mixed
4
Each universal input can also be configured separately. The following function block parameters are available: Pt 100/500/1000/2000, Ni 200/1000/2000, PTC, NTC, OHM (1-2 kΩ), BE, 0(4) to 20 mA, and 0 to 10 V (model no. 5171-0003 and higher). The function blocks FB01 to FB17 correspond to the binary inputs BE1 to BE17 in the wiring
resistor in parallel on using the 0(4) to 20 mA input.
Ω
-
16 EB 5171 EN
Start-up
diagram (–> page 37). The function block for the selected sensor is activated and the func
-
tion block parameter associated with the type of input signal is selected. If the temperature values displayed by the PLC deviate from the actual temperatures, the
measured values of the connected sensors can be changed or reset. When calibrating a sensor, the currently displayed sensor value must be changed such that it corresponds to the temperature value (reference value) measured directly at the point of measurement. Sensor calibration must be activated in CO6 using FB23. An improper calibration can be deleted by setting FB23 = OFF.
Note!
The tolerance by which a sensor value can be corrected is ±12 °C.
Proceed as follows:
3s Switch to configuration and parameter level.
Display shows:
PA5
Select CO6 configuration level. Open CO6 configuration level. Select function block FB23. Open function block FB23. Select sensor input you wish to calibrate. Display measured value. Measured value blinks. Correct measured value.
Use the actual temperature from a thermometer installed directly at the point of mea
-
surement as reference value. Confirm corrected measured value.
Further sensors are calibrated similarly.
Select
END
. Exit configuration level. Select
END
. Exit configuration and parameter level. Display shows: controller time Select
END
.
EB 5171 EN 17
Loading...
+ 39 hidden pages