Samson foundation 3787 Mounting And Operating Instructions

FOUNDATION
TM
FIELDBUS Positioner
Type 3787
Fig. 1 ⋅Type 378 7
EB 8383-1 EN
Firmware R 1.4x/K 1.4x Edition November 2004
Contents Page 1 Design and principle of operation
. . . . . . . . . . . . . . . . . . . . . . 8
1.1 Optional limit switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.2 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2 Attachment to the control valve
. . . . . . . . . . . . . . . . . . . . . . . 10
2.1 Direct attachment to Type 3277 Actuator . . . . . . . . . . . . . . . . . . . 10
2.2 Attachment acc. to IEC 60534-6 . . . . . . . . . . . . . . . . . . . . . . . 14
2.2.1 Mounting sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.2.2 Presetting the valve travel . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.3 Attachment to rotary actuators . . . . . . . . . . . . . . . . . . . . . . . . 17
2.3.1 Mounting the lever with feeler roll . . . . . . . . . . . . . . . . . . . . . . . 18
2.3.2 Mounting the intermediate piece . . . . . . . . . . . . . . . . . . . . . . . 18
2.3.3 Aligning and mounting the cam disk . . . . . . . . . . . . . . . . . . . . . 20
2.3.4 Reversing amplifier for double-acting actuators . . . . . . . . . . . . . . . . 22
2.4 Fail-safe action of the actuator . . . . . . . . . . . . . . . . . . . . . . . . 22
3 Connections
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.1 Pneumatic connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.1.1 Pressure gauge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.1.2 Supply air pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.2 Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.2.1 Establishing communication . . . . . . . . . . . . . . . . . . . . . . . . . 28
4Operation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.1 LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.2 Write protection and simulation switches . . . . . . . . . . . . . . . . . . . 30
4.3 Activate/deactivate forced venting function . . . . . . . . . . . . . . . . . . 30
4.4 Default setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.4.1 Adjusting mechanical zero . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.4.2 Initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.5 Operation via TROVIS-VIEW . . . . . . . . . . . . . . . . . . . . . . . . . 33
4.5.1 Initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4.5.2 Testing the control valve . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
4.6 Setting the inductive limit switches . . . . . . . . . . . . . . . . . . . . . . 34
Contents
2
EB 8383-1 EN
5 Maintenance
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
6 Servicing explosion-protected versions
. . . . . . . . . . . . . . . . . . . 35
7 Parameter description
. . . . . . . . . . . . . . . . . . . . . . . . . . . 36
7.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
7.2 Device Description (DD) . . . . . . . . . . . . . . . . . . . . . . . . . . 36
7.3 Notes on the parameters . . . . . . . . . . . . . . . . . . . . . . . . . . 36
7.3.1 Legends assigned to the parameters . . . . . . . . . . . . . . . . . . . . . 37
7.3.2 Notes on parameter storage classes S, N and D . . . . . . . . . . . . . . . 37
7.4 Block structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.4.1 Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
7.4.2 Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
7.4.3 Function Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
7.4.3.1 Analog Output Function Block . . . . . . . . . . . . . . . . . . . . . . . 57
Parameters of the Analog Output Function Block . . . . . . . . . . . . . . . 59
7.4.3.2 PID Function Block (PID controller) . . . . . . . . . . . . . . . . . . . . . . 65
Parameters of the PID Function Block . . . . . . . . . . . . . . . . . . . . 67
7.5 Other parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
7.5.1 Stale counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
7.5.2 Link objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
7.5.3 LAS capabilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
8Diagnostic messages
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
8.1 Messages of the XD_ERROR_EXT parameter (Transducer Block) . . . . . . . 79
8.2 Messages of the XD_ERROR parameter (Transducer Block) . . . . . . . . . . 80
8.3 Messages of the SELF_CALIB_STATUS parameter (Transducer Block) . . . . . 81
Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
EC Type Examination Certificate . . . . . . . . . . . . . . . . . . . . . . 83
CSA/FM certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Contents
EB 8383-1 EN
3
Safety instructions
The device may only be assembled, started up, and operated by experienced personnel familiar with this product. In these mounting and operating instructions, the term "experienced person­nel" refers to individuals who are able to evaluate the responsibilities assigned to them as well as recognize potential hazards due to their specialized train­ing, knowledge, and experience as well as their special knowledge of the rele­vant standards.
Explosion-protected versions of this device may only be operated by person­nel who have undergone special training or instructions, or who are auth­orized to work on explosion-protected devices in hazardous areas.
Any hazards which could be caused by the process medium, the operating pressure, the signal pressure and moving parts of the control valve, must be prevented by means of appropriate measures.
Should inadmissible motions or forces be produced in the pneumatic actuator as a result of the level associated with the supply air pressure, these must be restricted by means of a suitable pressure reducing station.
Proper shipping and appropriate storage of the device are assumed.
Note:
Devices with the CE mark meet the requirements specified in the Directive 94/9/EC and the Directive 89/336/EEC. The Declaration of Conformity can be viewed and downloaded from the SAMSON website at www.samson.de.
Modifications of positioner firmware in comparison to previous versions
Previous New
Positioner R 1.41 R 1.42
Correction in the zero calibration activated over software communication
4
EB 8383-1 EN
Firmware modifications
Communication K1.00 K1.20
Version compatible with user interface software version number: Fisher-Rosemount DeltaV in version 5.1 or higher National Instruments Fieldbus Configurator in version 2.3 or higher. All host systems certified by the Fieldbus Foundation Alteration to default values of the following parameters: AO Function Block CHANNEL, PID Function Block GAIN, PID Function Block RESET, PID Function Block BYPASS
Resource Block parameter extended: BLOCK_ERROR, page 40 Transducer Block parameters changed/extended: BLOCK_ERR, page 46.
Communication K 1.00 K1.31
The output parameters of the function blocks can be interconnected within a device and with blocks in other devices at the same time. In the previous version, it was only possible to either interconnect function blocks within a device or with blocks in other devices. An Output Failure in BLOCK_ERR of the AO Function Block generates a Block Alarm. The automatic resetting control loop monitor (previously not automatic resetting) is evaluated for the control loop error indication via LED or the message "Calibration Error". This means this alarm or message is automatically reset as soon as the control loop monitor cannot find an error anymore.
Communication K 1.31 K1.40
The default value for RESET in the PID Block has been changed from 0 to 3402823466 x 10
38
(maximum possible value). The integral-action component of the PID is ineffective at this value as well as at 0. On switching over the operating mode from MAN to AUTO, a smooth switchover is achieved.
EB 8383-1 EN
5
Technical data
Positioner
Travel Direct attachment to Type 3277 Attachment acc. to IEC 60534-6
Adjustable 5 to 30 mm 5 to 255 mm or 30 to 120° for rotary actuators
Bus connection Fieldbus interface as per IEC 61158-2, bus-powered
Physical Layer Class: 113 (not explosion-protected version) and 111 (Ex-version) Field device according to FM 3610 entity and FISCO.
Per m issib le o perati ng v oltage 9 to 32 V DC; The speci f icatio ns i n the EC Type E xamina tion Certif i cate addit ionally
apply for explosion-protected devices. Power supply over bus cable
Max. operating current 13 mA
Additional current in case of fault 0 mA
Supply air Supply air from 1.4 to 6 bar (20 to 90 psi);
Air quality as per ISO 8573-1: Max. particle size and density: Class 4; Oil co nt ents: C la ss 3; Pr es sure de w p oint: C la ss 3
Signal pressure (output) 0 bar up to the pressure of the supply air
Characteristic, adjustable
Deviation
Globe valve: linear, equal percentage, reverse equal percentage, SAMSON butterfly valve: linear, equal percentage VETEC plug rotary valve: linear, equal percentage ≤1 %
Dead band (based on rated travel/angle
Adjustable from 0.1 to 10.0 % , default 0.5 %
Resolution (internal measurement) < 0.05 %
Tran sit time re quired For v al ve tra ns it time up to 75 s
Set point ramp for exhaust and supply air separately adjustable
Operating direction Reversible, setting by software
Air consumption Independent of supply air <90l
n
/h
Air s upply A ctuat or f illed: wh en Δp = 6 bar 9.3 m
n
3
/h, when Δp = 1.4 bar 3.5 m
n
3
/h
Actu at or vented : w hen Δp = 6 bar 15.5 m
n
3
/h, when Δp = 1.4 bar 5.8 m
n
3
/h
Permissible ambient temperature 40 to 80 °C
The specifi cation s in t h e EC Typ e Examin ation Certif icate addi tionally app ly f o r explosion-protected devices
Effects Temperature: ≤0.15 %/10 K, supply air: none,
Vibrations: none up to 250 Hz and 4 g
Deg re e o f prote ct io n IP 65 us ing fil te r check va lve inc luded
Electromagnetic compatibility Requirements acc. to EN 61000-6-2, EN 61000-6-3 and
NAMUR Recommendations NE 21 are met
Bin ar y in pu t Inte rn al powe r s upply 5 V DC , R
i
= 100 kΩ for a la rm func ti on
Forced venting (activated over an internal switch)
Input 6 to 24 V DC, R
i
approx. 6 kΩ at 24 V D C ( depend in g on volt age) Switching point for "1" signal ≥ 3 V, switc hi ng poin t f or "0" sign al only at 0 V, K
V
0.17
6
EB 8383-1 EN
Versions
Accessories
Inductive limit switches Two Type SJ 2 SN Proximity Switches for connection to a switching amplifier acc. to
EN 60947-5-6
Communication
Data transmission In accordance with FOUNDATION
TM
Fieldbus specification
Communication Profile Class: 31 PS, 32: Interoperability Test System (I TS) Revision 4.0
Materials
Case Die -c as t alumi num, chr om ized an d p lastic -c oated
External parts Stainless steel 1.4571 and 1.4301
Weigh t Appr ox 1. 3 kg
Versions of the positioner
Model
3787 -
XXX
0
X3X
Explosion protection Without
II 2 G EEx ia IIC T6/ II 2 D IP 65 T 80 °C acc. to ATEX Ex ia FM/CSA
II 3 G EEx ia IIC T6/ II 3 D IP 54 T 80 °C acc. to ATEX
0
1 3
8
Accessories Limit switches Without
2 inductive
0 22
Forced venting Without (deactivated)
With (activated)
0 12
Pneumatic connections
NPT 1/4- 18 ISO 228/1-G 1/4
1 2
Electric connections Cable gland M20 x 1.5
Nickel-plated brass
Quantity: 1 2
1 2
EB 8383-1 EN
7
1 Design and principle of operation
The digital positioner compares the refer­ence variable, which is cyclically trans­mitted over the FOUNDATION
TM
Fieldbus, with the travel or opening angle of the con­trol valve. It then delivers a corresponding signal pressure. It is suitable for attachment to linear and rotary actuators.
The Type 3787 Positioner communicates as per FOUNDATION
TM
Fieldbus specification with field devices, programmable logic con­trollers and process management systems. An integrated PID Function Block allows the control of required process variables di­rectly in the field.
The travel of the control valve is picked up by the inductive displacement sensor (1) and supplied to the microcontroller (2) via a converter. The microcontroller compares the travel with the reference variable and controls the two pneumatic 2/2-way on-off valves (3, 4) when a system deviation occurs. The on-off valves fill (3) or vent (4) the pneumatic actu­ator via corresponding amplifiers corre­sponding to the system deviation. Two LEDs on the inside of the cover indicate the operating status of the positioner. The positioner is equipped with a standard binary input over which any process infor­mation can be signaled via the FOUNDA­TION
TM
Fieldbus. The write protection switch (6) located on the inside of the cover prevents stored con­figuration data from being overwritten.
Forced venting:
The positioner is controlled over a 6 to 24 V signal which causes the corresponding sig­nal pressure to be applied to the actuator. If the voltage signal drops, the signal pressure is shut off and the actuator is vented. The control valve moves to its fail-safe position regardless of the output variable issued by the microcontroller.
1.1 Optional limit switches
Limit switches can be retrofitted to the stand­ard positioner.
Two proximity switches can be used for fail­safe circuits to indicate the valves end posi­tions.
1.2 Communication
The positioner is completely controlled via digital signal transmission according to the FOUNDATION
TM
Fieldbus specification based on the E EN 50170/A1 draft. Data is transmitted as bit synchronous current modulation at a transmission rate of
31.25 kbit/s over twisted pairs according to IEC 61158-2.
Configuration with TROVIS-VIEW
The positioner can be configured using the SAMSON Configuration and Operator In­terface, TROVIS-VIEW. To configure the positioner, connect its addi­tional
SERIAL INTERFACE
to the RS-232 in­terface of a PC using an adapter cable. After adapting the positioner to the process requirements, TROVIS-VIEW enables the process to be controlled online.
8
EB 8383-1 EN
Design and principle of operation
Configuration with NI-FBUSTM Configurator
The positioner can also be configured using the NI-FBUS
TM
Configurator from National Instruments. An interface card installed in a PC is re­quired to connect it to FOUNDATION
TM
Fieldbus.
The NI-FBUS
TM
Configurator can be used to
configure the whole FOUNDATION
TM
Fieldbus network.
Fig. 2 ⋅Functional diagram
e
p
3
4
2
9
7
8
6
1
G
μC
&
IEC 61158-2
e
p
G
Fieldbus
Foundation
8
TROVIS
VIEW
11
10
1
12
u
13
Forced venting
Binary input
Supply air
Exhaust air
Serial Interface
1 Inductive displacement sensor 2 Microcontroller 3 On-off valve for supply air 4 On-off valve for exhaust air 5 Microcontroller 6 Switches for write protection and
simulation mode 7 Binary input 8 Forced venting 9 IEC 61158-2 interface module 10 Actuator stem 11 Lever 12 Clamp 13 Configuration interface
EB 8383-1 EN
9
Design and principle of operation
2 Attachment to the control valve
The positioner can be attached either di­rectly to a SAMSON Type 3277 Actuator or to control valves with cast yokes or rod­type yokes according to IEC 60534-6 (NAMUR). In connection with an intermediate piece, the positioner can also be attached to rot­ary actuators.
Since the standard positioner is delivered without accessories, please refer to the tables for required mounting parts and their order numbers.
Note!
For fast control valves with small travel vol­umes (transit time < 0.6 sec.), replace the fil­ter in the signal pressure output with a screw-in throttle, if necessary, to improve the control properties. See also sections
2.1, 2.2 and 2.3.
Important!
The positioner does not have its own vent­ing plug, instead vented air has to escape through venting plugs located on the mount­ing parts (see Figs. 3, 5 and 7). A filter check valve for the vented air is in­cluded in every positioner delivery (under the transparent protective cap on the back of the positioner). Replace the standard vent­ing plug included in the accessories with this filter check valve. This is the only way to achieve the degree of protection IP 65 by preventing dirt and moisture from entering the device.
2.1 Direct attachment to Type 3277 Actuator
The necessary accessories are listed in the Tables 1, 2 and 3 on page 13
.
When looking at the signal pressure connec­tion or the switchover plate (actuator 120 cm
2
), the positioner must be attached to the left side of the actuator. The
arrow
on the black cover of the case
(Fig. 11) should point
towards the dia-
phragm chamber
.
Exception:
Control valves in which the plug closes the seat area when the actuator stem retracts. In this case, the positioner has to be attached to the right side of the actuator and the arrow points away from the dia­phragm chamber.
1. Screw the clamp (1.2) to the actuator
stem, ensuring that the fastening screw is located in the groove of the actuator stem.
2. Screw the assigned pick-up lever D1 or
D2 to the transmission lever of the posi­tioner.
3. Fasten the distance plate (15) with seal
pointing towards the actuator yoke.
4. Place the positioner on the plate so that
the lever D1 or D2 slides centrally over the pin of the clamp (1.2). Then screw tight to the distance plate (15).
5. Mount cover (16).
Actuators with 240, 350 and 700 cm
2
6. Check whether the tongue of the seal
(17) is properly aligned at the side of the connection block (Fig. 3, center)
10
EB 8383-1 EN
Attachment to the control valve
Actuator stem retracts
Side view of connection block
with seal
(ne w
) with switch plate (old)
Fig. 3 ⋅Attachment and signal pressure connection for Type 3277 Actuators (top) and 3277-5 with 120 cm (bottom)
SUPPLY
1817 19
1.2 D2
D1
17
16
15
1.2
16
17
15
Actuator stem retracts
Internal signal pressure connection
Signal pressure tube
1.2 Clamp D1 Lever D2 Lever 15 Distance plate 16 Cover 17 Seal 18 Cover plate 19 Switch plate
Signal pressure bore
Connection block
Marking
Marking
Symbol "actuator stem extends"
"Actuator stem retracts"
Switchover plate
Switchover plate
Signal pressure input
Signal pressure input with brass throttle, if required
Actuator stem extends
Ventin g
Actuator stem extends
EB 8383-1 EN
11
Attachment to the control valve
with the actuator symbol "actuator stem extends" or "actuator stem retracts" to match the actuator version used. If not, remove the three fastening screws and the cover plate (18), turn the seal (17) by 180° and reinsert it. When the
old
connection block is used, turn the switch plate (19) to align the ac­tuator symbol with the arrow.
7. Place the connection block with its seal rings on the positioner and actuator yoke and screw it tight using the fasten­ing screw.
For actuators with "actuator stem re­tracts", additionally attach the ready­made signal pressure line.
Actuator with 120 cm
2
For the Type 3277-5 Actuator with 120 cm
2
effective diaphragm area, the signal press­ure is transmitted to the diaphragm cham­ber via the switchover plate (Fig. 3 bottom).
For a rated travel of 7.5 mm, a brass throttle (see Accessories table on page 13) must be pressed into the seal located in the signal pressure input on the actuator yoke. For a rated travel of 15 mm, this is only re­quired when the supply pressure exceeds 4 bar.
6. Remove the screw plug on the rear of the positioner case and seal the signal pressure output (Output 38) with the plug from the accessories.
7. Mount the positioner so that the bore in the distance plate (15) is aligned with the seal located in the bore of the actua­tor yoke.
8. Align the switchover plate with the corresponding symbol for left attach­ment and screw the plate to the actua­tor yoke.
Important!
If, in addition to the positioner, a solenoid valve or a similar device is attached to the 120 cm
2
actuator, the rear M3 screw must not be removed. In this case, the signal pressure has to be fed from the signal press­ure output to the actuator via the required connecting plate (see Table 2). The swit­chover plate is no longer required.
Note!
For faster control valves with a transit time less than 0.6 seconds, replace the filter in the signal pressure output (output 38) with a screw-in throttle (see Accessories table), if necessary.
Filling the diaphragm chamber with air
If the Type 3277 Actuators diaphragm chamber must be filled with air exhausted from the positioner, the diaphragm cham­ber (for version with "actuator stem ex­tends") can be connected to the connection block using a tube (see Table 3). To do this, first remove the screw plug from the connection block.
For the Type 3277-5 Actuator with "actua­tor stem retracts", the air exhausted from the positioner is constantly supplied to the diaphragm chamber through an internal bore.
12
EB 8383-1 EN
Attachment to the control valve
1402-0938 1402-0939
1)
Order with every pressure gauge kit: 2 restrictions (1790-6121)
1)
2.2 Attachment acc. to IEC 60534-6
The positioner is attached according to NAMUR as shown in Fig. 4 using an adapt­er housing. The valve travel is transmitted via the lever (18) and the shaft (25) to the bracket (28) in the adapter housing and then to the coupling pin (27) located on the lever of the positioner. To attach the positioner, you will require the mounting parts listed in Table 4. Which lever should be used depends on the rated valve travel. The positioner must be attached to the adapter housing with the
arrow
on the
black case cover pointing
away from the
diaphragm actuator
towards the valve. Exception: Control valves in which the plug closes the seat area when the actuator stem retracts. In this case, the arrow must point towards the diaphragm actuator.
If the adapter housing cannot be mounted
between
the actuator and valve (e.g. be­cause the actuator is from another manufac­turer), the
arrow
on the case cover must
point towards the valve!
Note!
For faster control valves with a transit time less than 0.6 seconds, replace the filter in the signal pressure output (output 38) with a screw-in throttle (see Accessories table).
2.2.1 Mounting sequence
Refer to Tables 4 and 5 on page 16 for re­quired mounting parts.
Note!
Prior to mounting the parts, apply signal pressure to the actuator so that the valve is set to 50 % of its travel. This is the only way to make sure that the lever (18) and bracket (28) are exactly aligned.
Control valve with cast yoke
1. Use countersunk screws to fix the plate (20) to the coupling which connects the plug stem and actuator stem. With actu­ators 2100 and 2800 cm
2
, use addi-
tional mounting bracket (32).
2. Remove rubber plug from the adapter housing and fasten the housing to the NAMUR rib with hexagon head screw.
Control valve with rod-type yoke
1. Screw plate (20) to the follower clamp of the plug stem.
2. Screw the studs (29) into the adapter housing.
3. Place the housing with the plate (30) on either the right or left side of the valve stem and fasten tight using the nuts (31). On doing so, make sure the hous­ing is aligned at a height which will still allow the lever (18) to be attached horizontally.
4. Screw the pin (19) into the center row of holes in the plate (20) and lock into place so that it is located approximately above the correct lever marking (1 to 2)
14
EB 8383-1 EN
Attachment to the control valve
Fig. 4 ⋅Attachment according to IEC 60534-6 (NAMUR)
2
1,5
1
2826
AB
24 25 22
32
31
20 19
19 21 2023 18
27b
27a
29 30
Attachment to NAMUR rib
Mounting position
Attachment to rod
18 Lever N1, N2 19 Pin 20 Plate 21 Clamp 22 Clamping plate 23 Screw 24 Pointer 25 Shaft 26 Lever of positioner 27a Transmission pin 27b Lock nut 28 Bracket 29 Studs 30 Plate 31 Nuts 32 Mounting bracket
EB 8383-1 EN
15
Attachment to the control valve
for the assigned travel, see Table 5. Intermediate values must be calculated. Move the clamp (21) beforehand to clasp the pin.
5. Measure the distance from the middle of the shaft (25) to the middle of the pin (19). This value must be entered later when the positioner is being con­figured.
2.2.2 Presetting the valve travel
1. Adjust the shaft (25) in the adapter housing so that the black pointer (24) is aligned with the casted marking on the adapter housing.
2. Screw the clamping plate (22) tight in this position using the screw (23).
3. Screw the coupling pin (27) into the po­sitioner lever (26) on the side with the
Table 4
Attach. acc. to IEC 60534-6 Control valve Travel in mm With lever Order no.
NAMUR mounting kit
See Fig. 4 for parts
Valve w it h cast yoke
7.5 to 60 N1 (125 mm) 1400-6787
30 to 120 N2 (212 mm) 1400-6789
Valve with
rod-type
yoke with
rod diameter
in mm
20 to 25 N1 1400-6436
20 to 25 N2 1400-6437
25 to 30 N1 1400-6438
25 to 30 N2 1400-6439
30 to 35 N1 1400-6440
30 to 35 N2 1400-6441
Attachment to Fisher and Masoneilan linear actuators (one ea ch of bo th mo un ting ki ts is need ed per one ac tuator )
1400-6771
and
1400-6787
Accessories
Press. gauge mounting block G 1/4: 1400-7458 1/4 NPT: 1400-7459
Pressure gauge set St. st./brass: 1400-6957 St. st./St. st.: 1400-6958
Signal pressure throttles (screw-in type and brass throttle) 1400-6964
Filter check valve, replaces vent plug and increases the degree of protection to IP 65 (one included with the delivered positioner)
1790-7408
Table 5
Attachment according to IEC 60534-6
Travel mm *) 7.51515303060306060120
Pin on mark *) 1 12121212
Corresp. distance: pin/lever pivot 42 42 84 42 84 84 168 84 168
With lever N1 (125 mm in length) N2 (212 mm in length)
Tran sm is sion pi n ( 27 ) a t posit io n A A B A B
*) Deviating travels (intermediate values) must be calculated accordingly
16
EB 8383-1 EN
Attachment to the control valve
insert nuts and secure the pin on the other side with a hex nut. Observe the mounting position A or B explained in Table 5 and Fig. 4.
4. Place the positioner onto the adapter housing, making sure the coupling pin (27) is positioned within the arms of the bracket (28). To do so, insert a 2.5 mm Allen key or a screwdriver from the front into the bore located below the oblong hole on the cover plate, and push the positioner lever into the required position.
5. Screw positioner to the adapter housing.
6. Relieve signal pressure from the actuator.
2.3 Attachment to rotary actuators
The positioner can also be attached to rot­ary actuators in accordance with VDI/VDE 3845 by using the mounting parts and ac­cessories listed in Table 6. In this arrange­ment, the actuators rotary motion is con­verted via the cam disk of the actuator stem and the feeler roll of the positioner lever into a linear motion which is required for the inductive displacement sensor. Each cam disk has two curves for the ranges of rotational angle from 0 to 90° (recommended for all angles of rotation smaller than 90°) and 0 to 120° (recom­mended for all angles of rotation larger than 90°).
Ta bl e 6
Rotary actuators (Complete mounting parts, but without cam disks)
Attachment acc. to
VDI/VDE 3845, level
1
SAMS ON Type Actu at or Atta ch me nt to Mas on eilan ac tu ator
Actuator
160 cm
2
Actuator 320 cm
2
Camflex I
DN 25 ...100
Camflex I
DN 125...250
Camflex II
Order no.
1400-8815 1400-7103 1400-7104 1400-7118 1400-7119 1400-7120
Pip ing k it 8 x 1 stainle ss st eel
G: 1400-6670 NPT: 1400-6672
G: 1400-6669 NPT: 1400-6671
Accessories
Order no.
Reversing amplifier for double-acting actuators without springs G: 1079-1118 NPT: 1079-1119
Cam disk (0050-0089) with accessories, angle of rotation 0 to 90° and 0 to 120° 1400-6959
Cam disk (0050-0089) specially for VETEC, adjustable per software from 0 to 75° 1400-6960
Cam disk (0050-0090) specially for Camflex, adjustable per software from 0 to 50° 1400-6961
Pressure gauge mounting block G 1/4: 1400-7458; 1/4 NPT: 1400-7459
Pressure gauge set St. steel/Brass:
1400-6957
St. steel/St. steel:
1400-6958
Signal pressure throttles (screw-in type and brass throttle) 1400-6964
Filter check valve, replaces vent plug and increases the degree of protec­tion to IP 65 (o ne inc lu ded wit h t he deliv er ed posi ti on er)
1790-7408
EB 8383-1 EN
17
Attachment to the control valve
For double-acting, springless rotary actua­tors, a reversing amplifier must be attached to the positioner housing on the side where it is connected to the actuator (see section
2.3.4). If the positioner is attached to a SAMSON
Type 3278 Rotary Actuator, the air ex­hausted from the positioner is admitted to the inside of the actuator without any addi­tional tubing. If the positioner is attached to actuators from other manufacturers (NAMUR), the air is applied to the diaphragm chamber through a tube with a tee connecting the ac­tuator and the exhaust connection of the in­termediate piece.
Note!
For faster control valves with a transit time less than 0.6 seconds, replace the filter in the signal pressure output (output 38) with a screw-in throttle (see Accessories Table 6).
2.3.1 Mounting the lever with feeler roll
1. Place lever with attached feeler roll (35) on the transmission lever (37) and secure it with the supplied screws (38) and washers.
2.3.2 Mounting the intermediate
piece
SAMSON Type 3278 Actuator:
1. Screw adapter (36) to the free end of the rotary actuator shaft, using two screws.
2. Position intermediate piece (34) on the actuator housing and secure it with two screws. Align the intermediate piece so that the air connections of the posi­tioner face the side of the diaphragm case.
Actuators according to VDI/VDE 3845
1. Place the whole intermediate piece (34, 42, 44 and 45) onto the bracket in­cluded in the delivery scope of the actu­ator (fixing level 1 VDI/VDE 3845) and secure with screws.
2. Align the cam disk (40) and scale (39) as described in section 2.3.3 and screw tight.
With springless actuators, the reversing am­plifier must be screwed to the side of the po­sitioner case. See section 2.3.4.
18
EB 8383-1 EN
Attachment to the control valve
Vent p lu g o r filter check valve
Fig. 5 ⋅Attachment to rotary actuators
33
3835
39
39 40
34
36
40
34
44
45
42 43
37
Attachment to SAMSON Type 3278
Attachment acc. to VDI/VDE 3845
33 Positioner 34 Intermediate piece 35 L ev er with ca m f ollowe r r oll 36 Adapter 37 Transmission lever 38 Screws 39 Scale 40 Cam disk 41 Actuator shaft 42 Plate 43 Bracket 44 Coupling 45 Seal
EB 8383-1 EN
19
Attachment to the control valve
2.3.3 Aligning and mounting the cam disk
In rotary actuators with spring-return mech­anism, the actuator springs determine the fail-safe position and the direction of rota­tion of the control valve. With double-acting, springless rotary actua­tors, the direction of rotation depends on both the actuator and valve version used. The initial position is always based on a closed valve!
Whether the control valve should open or close when the reference variable increases must be set in the software (direction of ac­tion increasing/increasing or increasing/de­creasing).
1. Place the cam disk with scale on the adapter (36) or coupling (34), and fasten the screws loosely at first.
The cam disk has two cam sections. The starting point of each section is marked by a small hole.
Note!
When the valve is closed, the starting point (hole) of the disk must be aligned so that the pivot of the cam disk, the 0° position of the scale and the arrow mark on the viewing window are in one line. The starting point for the closed valve posi­tion should never be below the 0° position!
In actuators with fail-safe position "valve OPEN", the maximum signal pressure must be applied to the actuator prior to aligning the cam disk. In springless actuators, the supply air must be connected.
2. On aligning the cam disk, clip on the double-sided scale disk so that the scale matches the direction of rotation of the control valve. Only then secure the cam disk with the fastening screws.
Securing the aligned cam disk
If you want to additionally secure the cam disk to prevent it from being turned, pro­ceed as follows:
There are four holes arranged around the center hole on the cam disk. Select a suit­able hole from the four holes to secure the cam disk. Drill a hole in the adapter (36) or coupling (44) through the hole chosen and insert a 2 mm dowel pin.
3. Attach the positioner to the intermediate piece (34) so that the lever (35) touches the cam disk with its feeler roll. To do so, insert a 2.5 mm Allen key or screwdriver from the front into the bore hole located below an oblong hole in the cover plate and bring the positioner lever in the required position.
4. Screw positioner to the intermediate piece.
20
EB 8383-1 EN
Attachment to the control valve
Fig. 6 ⋅Aligning the cam disk
Control valve opens
counterclockwise
Control valve opens
clockwise
Feeler roll
Starting point
Holes to secure the cam disk
View onto the actuator shaft from the positioner
Insert clip and then
press tongues outwards
EB 8383-1 EN
21
Attachment to the control valve
2.3.4 Reversing amplifier for double-acting actuators
For the use with double-acting actuators, the positioner must be fitted with a revers­ing amplifier. The reversing amplifier is listed as an acces­sory in the Table 6 on page 17.
The output signal pressure of the positioner is supplied at the output A
1
of the reversing amplifier. An opposing pressure, which equals the required supply pressure when added to the pressure at A
1,
is applied at
output A
2
. The rule A1 + A2 = Z applies.
Mounting
Note!
Prior to mounting the reversing amplifier, remove the sealing plug (1.5). The rubber seal (1.4) must be remain attached.
1. Thread the special nuts (1.3) from the
accessories of the reversing amplifier into the threaded ports of the positioner.
2. Insert the gasket (1.2) into the recess of
the reversing amplifier and push both the hollowed special screws (1.1) into the connecting ports A1 and Z.
3. Place the reversing amplifier onto the
positioner and screw tight using both the special screws (1.1).
4. Screw the supplied filter (1.6) using a
screwdriver (8 mm wide) into the con­necting bore holes A1 and Z.
Signal pressure connections
A
1
: Output A1 leading to the signal press­ure connection at the actuator which opens the valve when the pressure increases
A
2
: Output A2 leading to the signal press­ure connection at the actuator which closes the valve when the pressure increases
Enter the actuator as "Double-acting without spring-return mechanism" in the user interface software under Start-up
Type of actuator.
2.4 Fail-safe action of the actuator
Note!
If the fail-safe action of the actuator is changed subsequently by converting the ac­tuator springs from "actuator stem extends" to "actuator stem retracts", the mechanical zero must be recalibrated and the posi­tioner reinitialized.
22
EB 8383-1 EN
Reversing amplifier for double-acting actuators
Fig. 7 ⋅Mounting a reversing amplifier
1.3 1.2 1.1 1
Output 38 Supply 9
A
1
1.5 1.6
Z
A
2
1.4
A
1
A
2
Output 38 Supply 9
1.3 1.21.1
1.6
Z
A
1
From the positioner
To the actuator
1 Reversing amplifier
1.1 Special screws
1.2 Gasket
1.3 Special nuts
1.4 Rubber seal
1.5 Plug
1.6 Filter
EB 8383-1 EN
23
Reversing amplifier for double-acting actuators
3 Connections
3.1 Pneumatic connections
The air connections are either 1/4 NPT or G 1/4 tapped holes. Customary fittings for metal and copper pipes or plastic tubes can be used.
Note!
The supply air must be dry and free from oil and dust. Observe the maintenance instruc­tions for upstream pressure reducing station­s. Carefully purge all tubes before connect­ing them.
If the positoner is attached directly to Type 3277 Actuator, the connection for the sig­nal pressure is fixed. For NAMUR attach­ment, the signal pressure can be applied to either the top or bottom diaphragm cham­ber depending on the fail-safe position "ac­tuator stem extends or retracts".
Exhaust air: The exhaust air connection of the positioner is included in the mounting parts. For direct attachment of the posi­tioner, there is a vent plug on the plastic cover of the actuator. For NAMUR attach­ment, this plug is on the adapter housing and for attachment to rotary valves, it is on the intermediate piece or reversing ampli­fier.
3.1.1 Pressure gauge
We recommend mounting pressure gauges for supply air and signal pressure to moni­tor the positioner. The parts are listed as ac­cessories in Tables 3, 4 and 6.
Fig. 8 ⋅Mounting the pressure gauge
2...3mm
Nut Throttle with filter
Order no. 0250-1090 1790-6121
24
EB 8383-1 EN
Connections
3.1.2 Supply air pressure
The required supply air pressure depends on the bench range and the operating direc­tion (fail-safe position) of the actuator. The bench range is mentioned on the name­plate as spring range or signal pressure range.
Actuator stem extends:
Required supply air pressure = Upper bench range value + 0.2 bar, min. 1.4 bar.
Actuator stem retracts:
The required supply air pressure for tight­closing valves is calculated from the maxi­mum signal pressure pst
max
pst
max
= F +
d
2
⋅ π ⋅ Δp
4 ⋅ A
[bar]
d = Seat diameter [cm]
Δ
p = Differential pressure across the valve [bar]
A = Actuator area [cm
2
]
F = Upper bench range value of the actuator [bar]
If there are no specifications, calculate as follows:
Required supply air pressure = Upper bench range value + 1 bar
3.2 Electrical connections
For electrical installation, you are re­quired to observe the relevant elec­trotechnical regulations and the acci­dent prevention regulations that apply in the country of use. In Ger­many, these are the VDE regulations and the accident prevention regula­tions of the employers liability insur­ance association. The following standards apply for in­stallation in hazardous areas: EN 60079-14: 2003 (VDE 0165 Part 1)
"Electrical apparatus for ex-
plosive gas atmospheres"
and EN 50281-1-2: 1999 (VDE 0165 Part 2)
"Electrical apparatus for use in the presence of combustible dust"
. For the interconnection of intrinsi­cally safe electrical equipment, the permissible maximum values speci­fied in the EC type examination certi­ficate apply (U
i
or U0; Ii or I0; Pi or
P
0
; Ci or C0, and Li or L0). For EEx nA equipment (non-spark­ing apparatus), the standard EN 50021: 1999 specifies that con­necting, interrupting, or switching circuits while energized is only allowed during installation, mainten­ance or repair work. For EEx nL equipment (energy­limited apparatus), the standard EN 50021: 1999 allows this type of equipment to be switched under nor­mal operating conditions.
EB 8383-1 EN
25
Connections
Caution!
The terminal assignment specified in the certificate must be adhered to. Reversing the assignment of the elec­trical terminals may cause the explo­sion protection to become ineffective! Do not tamper with enameled screws inside or on the housing.
Note on the selection of cables and wires:
To install intrinsically safe circuits, observe section 12 of the standard EN 60079-14: 2003 (VDE 0165 Part 1). To run multi-core cables or lines with more than one intrinsically safe circuit, section 12.2.2.7 of this standard applies. An additional cable gland can be installed when connecting the de­vice over two separate cables. Cable entries left unused must be sealed with blanking plugs. Devices used at ambient tempera­tures down to 40 °C must have metal cable entries.
The terminal assignment can be found in Fig. 9 as well as on the labels on the cover plate of the positioner case.
Cable entries
The cable entry with M20x1.5 cable gland, 7 to 12 mm clamping range. There is a second M20x1.5 cable gland in the housing that can be used for additional connection, if required. The screw terminals are designed for wire cross-sections of 0.2 to 2.5 mm
2
. Tighten
by at least 0.5 Nm.
Bus line
The shielding of the Fieldbus connecting cable is connected to the equipotential bonding system on the process control sys­tem side. At the positioner side, the shielded cable must be routed over the EMI-proof brass cable gland (standard) of the posi­tioner to the terminals. The shield which is placed over the clamping insert is con­nected over a large area to the gland and housing.
To connect the bus line, loosen the coup­ling nut and the clamping insert from the positioner and remove the dust cap.
Slide the coupling nut and clamping in­sert over the connecting cable.
Insulate the end of the bus line to the re­quired connecting length and cut the wire shield off up to a length of approx. 13 mm. If necessary, cut off any cable core filling as well.
Disentangle the braided shield and pull it over the clamping insert.
Press the clamping insert into the con­necting screw gland and screw tight the coupling nut until the connecting cable is clamped tight.
Route the two-wire bus line to the screw terminals marked "IEC 1158-2", whereby no polarity has to be observed.
In exceptional cases, when the plant may not allow such a connection, feed the cable shield through the cable gland and connect it to be capacitive over the terminal "S". However, make sure that a conducting con­nection cannot occur from the shield to the cable gland or housing.
If the shielding is not placed on both sides, we recommend installing an additional sup-
26
EB 8383-1 EN
Connections
pressor kit (order no. 1400-9324). Separ­ate installation instructions are included.
Note!
The connection of limit switches, binary input and forced venting function requires an additional cable gland that must replace the cap fitted on the housing.
Accessories:
Cable gland M20 x 1.5, nickel-
plated brass, order no. 8808-0143
Limit switches
For operation of the limit switches, switch­ing amplifiers have to be connected in the output circuit. Their function is to control the limit values of the control circuit according to NAMUR, thus ensuring operational relia­bility of the positioner. If the positioner is installed in hazardous areas, the relevant regulations must be ob­served.
Binary input
A passive floating contact can be used at the binary input. The positioner signals the status over the bus protocol.
Fig. 9 ⋅Bus line connection and terminal assignment (terminal markings according to DIN 45140)
Brass screw fitting Shield Clamping insert Coupling nut
GW2 GW1
PE
S
NC
-52
+51
-42
+41 -86
+85
-82 +81
IEC 1158-2
FOUNDATION
TM
Fieldbus
Bus cable
Switching amplifier
acc. to EN 60 947-5-6
6 to 24 VDC
Limit switches Binary input Forced venting
EB 8383-1 EN
27
Connections
Forced venting
For the positioners with forced venting func­tion, a voltage between 6 and 24 V DC must be connected to the terminals 81 and
82.
Note!
If there is no voltage connected or the volt­age drops, the positioner vents the actuator and does not respond to the reference vari­able.
28
EB 8383-1 EN
Connections
3.2.1 Establishing communication
Communication between positioner, pro­grammable logic controller or automation system or between PC and workstation and positioner(s) is established in accordance with IEC 61158-2.
If positioners are used in hazardous areas, ex-barriers must be used.
A maximum of 32 control valves can be operated in one segment. The number of po­sitioners that can be connected is reduced when they are used in hazardous areas.
Fig. 10 ⋅ FOUNDATIONTM Fieldbus connection, for non-hazardous areas (top) and for hazardous areas (bottom)
3787
3787
3787
3787
FOUNDATION
TM
Fieldbus IEC 61158-2
FOUNDATION
TM
Fieldbus IEC 61158-2
3787-1
3787-1
3787-1
3787-1
FOUNDATION
TM
Fieldbus IEC 61158-2
FOUNDATION
TM
Fieldbus
IEC 61158-2
Process management system
Process management system
Te rm in at i o n
Ex-fieldbus barriers
Termination
Hazardous area
Supply unit
Non-hazardous area
Supply unit
Termination
EB 8383-1 EN
29
Connections
4Operation
Warning!
Before you take the control valve into operation, carefully move the control valve to its end position by covering the hole (manual oper­ation) on the cover plate (Fig. 11). On doing so, check whether the lever mechanism works properly. If the maximum angle of rotation is exceeded because the wrong lever mechanism has been selected or in­correctly sized, the positioner may be ruined.
4.1 LEDs
There are two LEDs located inside the cover used to monitor the positioner during start­up, operation and to indicate possible faults.
General meaning of LEDs:
Red
Device start-up or error, no control operation possible
Green
No error detected, control operation or fail-safe position (e.g. if not initialized)
Red and green
Error detected, control operation possible
See table below for detailed description.
Description LED
Device start-up:
Red on
No error detected:
Device connected to bus, cold start completed, initialization required Initialization or zero calibration running Device is initialized, no valid set point Device is initialized, valid set point, control operation
Green, generally Green blinks slowly
Green blinks quickly Green blinks 3x quickly + long interval Green on
Error in the control loop:
Zero point error Control loop fault
Red and green Red and green blink slowly Red and green blink quickly
Error leading to first initialization being cancelled
(Device does not go to standard operation) Zero point error Mechanics/pneumatics failure Control loop fault
Red, generally
Red blinks slowly Red on Red blinks quickly
Device errors causing the control operation to be left
Device has detected an internal fault Red blinks 3x quickly + long interval
30
EB 8383-1 EN
Operation
Loading...
+ 68 hidden pages