Samson 5100, 5179 User Manual

Automation System TROVIS 5100 District Heating Controller TROVIS 5179
Electronics from SAMSON
Mounting and Operating Instructions
EB 5179 EN
®
Disclaimer of liability
Disclaimer of liability
We are constantly developing our products and therefore, reserve the right to change the product or the information contained in this document at any time without notice.
We do not assume any liability for the accuracy or completeness of these mounting and operating instructions. Moreover, we do not guaranteethat thebuyer can use the product for an intended purpose. SAMSON rejects any liability for claims by the buyer, especially claims for compensation including lost profits or any other financial loss, except the damage was caused intentionally or by gross negligence. If an essential term of the contract is breached by negligence, SAMSON’s liability is limited to the foreseeable damage.
Safety instructions
The device may only be assembled, started up or operated by trained and
4
experienced personnel familiar with the product. Proper shipping and appropriate storage are assumed.
The controller has been designed for use in electrical power systems. For
4
wiring and maintenance, you are required to observe the relevant safety regulations.
2 EB 5179 EN

Contents

Contents
1 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1 Operating elements. . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1.1 Operating keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1.2 Operating switches . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.2 Operating modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.3 Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.4 Displaying data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.5 Setting the controller time . . . . . . . . . . . . . . . . . . . . . . . 11
1.6 Setting the times-of-use . . . . . . . . . . . . . . . . . . . . . . . . 13
1.6.1 Copying the times-of-use . . . . . . . . . . . . . . . . . . . . . . . 15
1.6.2 Entering public holidays . . . . . . . . . . . . . . . . . . . . . . . . 16
1.6.3 Entering vacation periods . . . . . . . . . . . . . . . . . . . . . . . 18
2 Start-up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2.1 Setting the system code number . . . . . . . . . . . . . . . . . . . . 20
2.2 Activating and deactivating functions. . . . . . . . . . . . . . . . . . 21
2.3 Changing parameters . . . . . . . . . . . . . . . . . . . . . . . . . 23
2.3.1 Enter key number . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
2.4 Configuring universal inputs . . . . . . . . . . . . . . . . . . . . . . 24
2.5 Calibrating sensors . . . . . . . . . . . . . . . . . . . . . . . . . . 24
2.6 Resetting to default values . . . . . . . . . . . . . . . . . . . . . . . 26
3 Manual operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4 Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
5 Functions of the heating circuit . . . . . . . . . . . . . . . . . . . . 38
5.1 Functioning principle . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.2 Weather-compensated control . . . . . . . . . . . . . . . . . . . . . 38
5.2.1 Gradient characteristic . . . . . . . . . . . . . . . . . . . . . . . . 39
5.2.2 4-point characteristic . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.3 Fixed set point control . . . . . . . . . . . . . . . . . . . . . . . . . 41
5.4 Differential temperature control using variable weighting factors. . . . . 41
5.5 Deactivation depending on outdoor temperature . . . . . . . . . . . . 42
5.5.1 OT deactivation value in rated operation . . . . . . . . . . . . . . . . 42
5.5.2 OT deactivation value in reduced operation . . . . . . . . . . . . . . 42
5.5.3 OT activation value in rated operation . . . . . . . . . . . . . . . . . 43
5.5.4 Summer mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
5.6 Delayed outdoor temperature adaptation. . . . . . . . . . . . . . . . 44
5.7 Outdoor temperature-dependent advance heating . . . . . . . . . . . 44
EB 5179 EN 3
Contents
5.8 Remote operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
5.9 Optimization with room sensor. . . . . . . . . . . . . . . . . . . . . 45
5.10 Flash adaptation . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
5.11 Adaptation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
5.12 Room temperature-dependent control . . . . . . . . . . . . . . . . . 48
5.13 Pump management . . . . . . . . . . . . . . . . . . . . . . . . . . 49
5.14 Releasing the heating circuit . . . . . . . . . . . . . . . . . . . . . . 50
5.15 Position feedback in pre-control circuit . . . . . . . . . . . . . . . . . 50
6 Functions of the DHW circuit. . . . . . . . . . . . . . . . . . . . . . 51
6.1 DHW heating in the storage tank charging system . . . . . . . . . . . 51
6.2 DHW heating in the storage tank system . . . . . . . . . . . . . . . . 53
6.3 Priority operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
6.3.1 Reverse control . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
6.3.2 Set-back operation . . . . . . . . . . . . . . . . . . . . . . . . . . 56
6.4 Forced charging of the DHW storage tank . . . . . . . . . . . . . . . 56
6.5 Thermal disinfection of the DHW storage tank . . . . . . . . . . . . . 56
7 System-wide functions . . . . . . . . . . . . . . . . . . . . . . . . 58
7.1 Automatic summer time/winter time changeover . . . . . . . . . . . . 58
7.2 Frost protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
7.3 Forced operation of the pumps. . . . . . . . . . . . . . . . . . . . . 58
7.4 Return flow temperature limitation . . . . . . . . . . . . . . . . . . . 58
7.5 Condensate accumulation control . . . . . . . . . . . . . . . . . . . 60
7.6 Compensating for time delays . . . . . . . . . . . . . . . . . . . . . 60
7.7 Three-step control . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
7.8 On/off control . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
7.9 Continuous-action control . . . . . . . . . . . . . . . . . . . . . . . 62
7.10 Forwarding the outdoor temperature . . . . . . . . . . . . . . . . . . 63
7.11 Flow rate/capacity limitation over a pulse input. . . . . . . . . . . . . 63
7.12 Locking manual level . . . . . . . . . . . . . . . . . . . . . . . . . 65
8 Operational faults . . . . . . . . . . . . . . . . . . . . . . . . . . 66
8.1 Error list/sensor failure . . . . . . . . . . . . . . . . . . . . . . . . 66
8.2 Collective error alarm . . . . . . . . . . . . . . . . . . . . . . . . . 67
8.3 Temperature monitoring . . . . . . . . . . . . . . . . . . . . . . . . 69
8.4 Monitoring the input terminals for limit violations . . . . . . . . . . . . 70
8.5 Error status register . . . . . . . . . . . . . . . . . . . . . . . . . . 71
4 EB 5179 EN
Contents
8.6 Error alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
8.6.1 Sending text message in case of a fault alarm . . . . . . . . . . . . . 73
8.6.2 Sending fax in case of a fault alarm . . . . . . . . . . . . . . . . . . 73
9 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
9.1 RS-232-C system bus interface . . . . . . . . . . . . . . . . . . . . 76
9.2 RS-232/RS-485 system bus interface (for four-wire bus) in combination with
cable converters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
9.3 Description of communication parameters to be adjusted . . . . . . . . 78
9.4 Meter bus interface . . . . . . . . . . . . . . . . . . . . . . . . . . 80
9.4.1 Activating the meter bus . . . . . . . . . . . . . . . . . . . . . . . . 80
9.4.2 Flow rate/capacity limitation using meter bus. . . . . . . . . . . . . . 81
9.5 LON communication. . . . . . . . . . . . . . . . . . . . . . . . . . 83
9.6 Requesting/processing an external demand . . . . . . . . . . . . . . 84
9.7 Sending outdoor temperatures and controller time . . . . . . . . . . . 85
10 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
11 Electrical connection. . . . . . . . . . . . . . . . . . . . . . . . . . 89
12 Appendix. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
12.1 Function block lists. . . . . . . . . . . . . . . . . . . . . . . . . . . 96
12.2 Parameter list . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
12.3 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
12.4 Sensor resistance tables . . . . . . . . . . . . . . . . . . . . . . . 128
12.5 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
12.6 Customer data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
EB 5179 EN 5
Operation
1 Operation
The controller is ready for use with the temperatures and operating schedules preset by the manufacturer. On start-up, the current time and date need to be set at the controller (–> section 1.5).
1.1 Operating elements
The operating controls are located in the front panel of the controller and protected by a Plexi glas door.
1.1.1 Operating keys
Changeover key
Press to switch between operating level and configuration/parameter level
Reset key
Press to reset accessible parameters to their default settings; the controller must be in the parameter level
Arrow keys
– To scroll within levels – To change values
Enter key
– To access levels – Access parameters and functions to edit them – Confirm settings – Display set points in info level
-
6 EB 5179 EN
Operation
1.1.2 Operating switches
Heating circuit mode selector switch
Automatic mode with switchover between rated operation and reduced operation
Rated operation Reduced operation Manual operation: Control valve opens - stationary - closes
(for on/off control: + ON, 0 OFF)
DHW circuit mode selector switch
The operating mode icon stickers are included in the scope of delivery and can be stuck on the front above the mode selector switch for control circuit 2 (middle), if required.
Automatic mode Rated operation DHW heating OFF Manual operation: Control valve opens - stationary - closes
(for on/off control: + ON, 0 OFF)
Note! In manual mode, frost protection is not guaranteed.
EB 5179 EN 7
Operation
The assignment of the control circuits to the mode selector switches depends on the system code number (Anl):
System
(Anl)
Top Middle Bottom 1 Heating circuit 1 Heating circuit 2 Pre-control circuit 2 Heating circuit 1 DHW heating Heating circuit 2 3 Heating circuit 1 Heating circuit 2 Heating circuit 3/Pre-control
4 Heating circuit 1 DHW heating Pre-control circuit 5 Heating circuit 1 DHW heating Heating circuit 2/Pre-control
6 Heating circuit 1 Heating circuit 2 Heating circuit 3 7 Heating circuit 1 DHW heating Pre-control circuit 8 Heating circuit 1 DHW heating Heating circuit 2/Pre-control
9 Heating circuit 1 DHW heating Heating circuit 2
10 Heating circuit 1 DHW heating Heating circuit 2
Mode selector switch
circuit
circuit
circuit
1.2 Operating modes
Day mode (rated operation)
Regardless ofthe programmed times-of-use and summer mode,the set points relevant for rated operation are used by the controller.
Night mode (reduced operation)
Regardless of the programmed times-of-use, the set points relevant for reduced operation are used by the controller.
Automatic mode
During the programmed times-of-use, the controller works in rated operation. Outside these times-of-use, the controller is in reduced operation, unless control operation is deactivated de pending on the outdoor temperature. The controller switches automatically between both oper ating modes.
Manual operation+ 0 –
Valves and pumps can be controlled manually.
8 EB 5179 EN
-
-
1.3 Display
Operation
During operation, the display indicates the current time as well as informationabout the opera tion of the controller. The times-of-use are represented by black squares below the row of num bers at the top of the display. Icons indicate the operating status of the controller.
The controller status can be displayed in the operating level (InF level) (–> section 1.4).
1 2
3 4
5 6
7
8
1 Automatic operation 2 Day mode
(rated operation)
3 Night mode
(reduced operation) 4 Vacation mode 5 Public holiday mode 6 Frost protection 7 Malfunction
1
1
9
10 11 12 1413 15
8 Circulation pump RK1–3 9 Valve RK1–3 or
Primary valve: OPEN or DHW: OPEN
10 Valve RK1–3 or
Primary valve: CLOSED or DHW: CLOSED
11 Storage tank charging
pump SLP
10 11 12 13 14 15 16 17 18 19123456789 0212223240
452
16
12 DHW storage tank 13 Circulation pump ZP 14 DHW demand 15 Exchanger charging pump
TLP
16 Time-of-use
-
-
Fig. 1 · Icons
EB 5179 EN 9
Operation
1.4 Displaying data
Measured values, set points, times-of-use, public holidays and vacation periods can be re trieved and displayed in the section 11.4.
InF1: Heating circuit 1
4
InF2: Heating circuit 2
4
InF3: Heating circuit 3
4
InF4: DHW heating
4
InF5: Primary control circuit
4
InF6: Does not exist
4
InF7: LON communication
4
InF8: Error status register/sensor failure
4
InF9: Communication
4
PU: Pumps, manual level
4
bIn-E: Binary inputs and outputs
4
Error: Alarms
4
Proceed as follows:
Select information level (–> Fig. 10 on page 141). Confirm information level. Select value you want to change. Compare the set point/limit value and the actual value. Press keys simultaneously:
to switch to the operating level.
InF1toInF9
information levels. The various displays are listed in
-
10 EB 5179 EN
Operation
1.5 Setting the controller time
The current time and date need to be set immediately after start-up and after a power failure lasting longer than 24 hours.
Proceed as follows:
9876543210
242322212019181716151413121110
Switch to configuration and parameter level. Display:
PA1
9876543210
9876543210
242322212019181716151413121110
242322212019181716151413121110
Select PA5 parameter level.
Open PA5 parameter level. Display: Controller time
Activate editing mode for the controller time
blinks.
Change controller time.
9876543210
242322212019181716151413121110
Confirm controller time. Display: Date (day.month)
Activate editing mode for the controller date. Change date setting.
EB 5179 EN 11
Operation
9876543210
242322212019181716151413121110
Confirm date. Display: Year.
Activate editing mode for the controller year. Change year setting. Confirm year. Exit PA5 parameter level. Return to the operating level.
Note!
The controller automatically returns to the operating level if the keys are left unpressed for two minutes.
12 EB 5179 EN
Operation
1.6 Setting the times-of-use
Two times-of-use can be set for each day of the week. If just one time-of-use is required, the start and stop times of the second time-of-use must be programmed to identical times. The time schedules for the three heating circuits, DHW heating and the circulation pump can be read over Modbus. Pump circuits are treated as mixer circuits.
Time schedule Parameter level Icon Heating circuit 1 to 3 PA1 to PA3 DHW heating PA4 Circulation pump PA4
Parameters
Period/day 1–7 1–7, 1, 2, 3, 4, 5, 6, 7 with 1–7 = every day,
Start first time-of-use 07:00 0:00 to 24:00h; in steps of 30 minutes Stop first time-of-use 12:00 0:00 to 24:00h; in steps of 30 minutes Start second time-of-use 12:00 0:00 to 24:00h; in steps of 30 minutes Stop second time-of-use 22:00 0:00 to 24:00h; in steps of 30 minutes * Default settings (WE) valid for heating circuits 1 to 3
WE* Range of values
1 = Monday, 2 = Tuesday, ..., 7 = Sunday
Proceed as follows:
9876543210
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
242322212019181716151413121110
Switch to configuration and parameter level. Display:
PA1
Select parameter level. Open parameter level.
Select datapoint for times-of-use.
EB 5179 EN 13
Operation
9876543210
242322212019181716151413121110
Activate editing mode for times-of-use. Display:
1–7
Select period/day for which the times-of-use are to be valid: 1–7 = every day, 1 = Monday, 2 = Tuesday, ..., 7 = Sunday
9876543210
242322212019181716151413121110
Activate editing mode for period/day.
START
Display shows:
; blinks
Edit start time (steps of 30 minutes).
9876543210
242322212019181716151413121110
Confirm start time. Display shows:
STOP
Edit stop time (steps of 30 minutes).
STOP
Confirm stop time. Display shows:
START
The second time-of-use is set like the first time-of-use.
To set the times-of-use for each day, repeat the instructions in the fields highlighted in gray.
End
Select
on the display. Exit the datapoint for times-of-use. Exit the parameter level. Return to the operating level.
Note!
Do not use the 1–7 datapoints to check the programmed times-of-use. Otherwise, the times-of-use are reset to their default settings.
Note!
The controller automatically returns to the operating level if the keys are left unpressed for two minutes.
14 EB 5179 EN
Operation
1.6.1 Copying the times-of-use
The times-of-use of heating circuit 1 (2) can be copied and used for heating circuit 2 (3).
Copy function Parameter level Icon HK1 –> HK2 PA1
HK2 –> HK3 PA2
Proceed as follows:
Switch to configuration and parameter level. Display:
Select parameter level. Open parameter level. Select “COPY_“ data point. Open copy program.
The display blinks. Copy the times-of-use. Select Exit the parameter level. Return to the operating level.
PA1
End
on the display.
COPY2 COPY3
EB 5179 EN 15
Operation
1.6.2 Entering public holidays
On public holidays, the times-of-use specified for Sunday apply. A maximum of 20 public holi days may be entered.
Parameters
Public holidays f. heating circuit 1 PA1 / 01.01 to 31.12 Public holidays f. heating circuit 2 PA2 / 01.01 to 31.12 Public holidays f. heating circuit 3 PA3 / 01.01 to 31.12
WE Level / Range of values
Note!
The programmed public holidays and vacations of any heating circuit (HK1, HK2 or HK3) ap ply with the setting Co4 -> Fb12 = ON , select 1, 2 or 3 also for the DHW heating.
Proceed as follows: Switch to configuration and parameter level.
Display:
PA1
Select parameter level. Open parameter level.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Select datapoint for public holidays. Display shows:
Open data point for public holidays.
– – – –
If applicable, select
.
Activate editing mode for public holiday.
blinks. Edit public holiday Confirm public holiday.
––––
To enter additional public holidays, re-select
(between 31.12 and 01.01) and repeat the
steps in the fields highlighted in gray.
Exit the parameter level. Return to the operating level.
-
-
16 EB 5179 EN
Operation
Note!
Public holidays that are not assigned to a specific date should be deleted by the end of the year so that they are not carried on into the following year.
Deleting a public holiday:
Select the holiday you wish to delete in the datapoint for public holidays. Confirm selection. Select
– – – –
.
Delete the public holiday.
Note!
The controller automatically returns to the operating level if the keys are left unpressed for two minutes.
EB 5179 EN 17
Operation
1.6.3 Entering vacation periods
During vacation periods, the controller constantly remains in the reduced operating mode. The system is monitored for frost. A maximum of 10 vacation periods can be entered.
Parameters
Vacation period for heating circuit 1 PA1 / 01.01 to 31.12 Vacation period for heating circuit 2 PA2 / 01.01 to 31.12 Vacation period for heating circuit 3 PA3 / 01.01 to 31.12
Note!
The programmed public holidays and vacations of any heating circuit (HK1, HK2 or HK3) ap ply with the setting Co4 -> Fb12 = ON , select 1, 2 or 3 also for the DHW heating.
Proceed as follows: Switch to configuration and parameter level.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
To enter additional vacation periods, re-select the steps in the fields highlighted in gray.
Exit the parameter level.
WE Level / Range of values
Display:
PA1
Select parameter level. Open parameter level. Select datapoint for vacation periods.
Display shows: Open datapoint for vacation periods.
Display shows If applicable, select
: START
– – – –
.
Activate editing mode for vacation periods.
blinks. Set start date of vacation period. Confirm start date of the vacation period.
Display shows:
STOP
Set end of vacation period. Confirm end of the vacation period.
––––
(between 31.12 and 01.01) and repeat
-
18 EB 5179 EN
Operation
Return to the operating level.
Note!
Vacation periods that are not assigned to a specific date should be deleted by the end of the year so that they are not carried on into the following year.
Deleting vacation periods:
Select the vacation period you wish to delete in the datapoint for vacation periods. Confirm selection. Select
– – – –
.
Delete vacation period.
Note!
The controller automatically returns to the operating level if the keys are left unpressed for two minutes.
EB 5179 EN 19
Start-up
2 Start-up
2.1 Setting the system code number
10 different hydraulic schematics are available. Each system configuration is represented by a system code number. The different schematics are dealt with in section 4. Available controller functions are described in sections 5, 6 and 7.
Changing the system code number resets previously adjusted function blocks to their default set tings (WE).
The system code number is set in the configuration level.
Proceed as follows:
Switch to configuration and parameter level. Display shows:
Select
Anl
Activate editing mode for the system code number.
Anl
blinks on the display. Edit system code number. Confirm system code number.
Display shows: Return to the operating level.
PA1
_ on the display.
Co1
-
Note!
The controller automatically returns to the operating level if the keys are left unpressed for two minutes.
20 EB 5179 EN
Start-up
2.2 Activating and deactivating functions
A function is activated or deactivated in the associated function block. The numbers 0 to 24 in the top row of the display represent the respective function block numbers. When a configura tion level is opened, the activated function blocks are indicated by a black square on the right-hand side below the function block number. For more details on function blocks, refer to section 12.1.
The functions are grouped by topics:
Co1: Heating circuit 1
4
Co2: Heating circuit 2
4
Co3: Heating circuit 3
4
Co4: DHW heating
4
Co5: System-wide functions
4
Co6: Sensor initialization
4
Co7: LON communication
4
Co8: Error initialization
4
Co9: Communication
4
Proceed as follows:
Switch to configuration and parameter level. Display shows:
Select configuration level. Open configuration level. Select function block. Activate editing mode for the function block.
Fb_ blinks on the display.
0 0 0 0
If section 2.3.1
Activate the function block (Fb = ON). An activated function block is indicated by a black square below (right) the function block number in the top row of the controller display.
or:
Deactivate the function block (Fb = OFF).
PA1
appears on the display, the key number needs to be entered first. Refer to
-
EB 5179 EN 21
Start-up
Confirm settings. If the function block is not closed, further function block parameters can be adjusted. Proceed as follows: Make the desired changes and confirm. If applicable, the next function block parameter is displayed. Confirm all parameters to exit the opened function block.
To adjust additional function blocks, repeat the steps in the fields highlighted in gray.
Exit configuration level. Return to the operating level.
Note!
The controller automatically returns to the operating level if the keys are left unpressed for two minutes.
22 EB 5179 EN
Start-up
2.3 Changing parameters
Depending on the set system code number and the activated functions, not all parameters listed in the parameter list in the Appendix (–> section 12.2) might be available.
The parameters are grouped by topics:
PA1: Heating circuit 1
4
PA2: Heating circuit 2
4
PA3: Heating circuit 3
4
PA4: DHW heating
4
PA5: System-wide parameters
4
PA6: Does not exist
4
PA7: LON communication
4
PA8: Does not exist
4
PA9: Communication
4
Proceed as follows:
Switch to configuration and parameter level. Display shows:
Select parameter level. Open parameter level. Select parameter. Activate editing mode for the parameter. Edit the parameter. Confirm the parameter setting.
To adjust additional parameters, repeat the steps in the fields highlighted in gray.
Exit parameter level. Return to the operating level.
PA1
Note!
The controller automatically returns to the operating level if the keys are left unpressed for two minutes.
EB 5179 EN 23
Start-up
2.3.1 Enter key number
Some functions are protected against unintentional or unauthorized access. These functions can only be activated or deactivated after the valid key number has been entered. The valid key number for initial start-up can be found on page 137. To avoid unauthorized use of the key number, remove the page or make the key number unreadable.
Proceed as follows:
0 0 0 0
The key number remains active for approx. 10 minutes.
blinks on the display. Set valid key number. Confirm key number.
When the correct key number is entered, the function block that is to be changed blinks on the display. On entering an incorrect key number, the controllers switches to the next configuration level.
2.4 Configuring universal inputs
The connected sensors are calibrated in Co6 configuration level. The following applies:
Co6 -> Fb00 = ON: Pt 100/Pt 1000 sensors (default setting)
4
Co6 -> Fb00 = OFF: Pt 100/PTC sensors
4
The resistance values of the sensors can be found on page 128. Each universal input can be configured separately. The following inputs Ni 200/1000, PTC, NTC, Pt 100/1000, (0/4...20) mA, (0–10 V) can be configured as function block parameters. The function blocks 01 to 17 correspond to the binary inputs BE1 to BE17 in the terminal wiring plan (page 92 onwards). The function block for the required sensor is activated and the function block parameter selected which corresponds to the type of input signal.
2.5 Calibrating sensors
If the temperature values displayed at the controller differ from the actual temperatures, the measured values of all connected sensors can be changed or readjusted. To calibrate a sensor, the currently displayed sensor value must be changed such that it matches the temperature (ref
24 EB 5179 EN
-
Start-up
erence temperature) measured directly at the point of measurement. Sensor calibration is to be activated in Co6 via function block Fb23.
Proceed as follows:
Switch to configuration and parameter level. Display shows:
PA1
Select Co6 level. Open Co6 level. Display shows:
Fb00
Select function block Fb23. Confirm selection. Display shows:
0 0 0 0
Enter and confirm key number. Fb23 blinks on the display.
Activate editing mode for function block. Activate function block. Start sensor calibration. Select the function block for the sensor that you want to calibrate:
The function blocks Fb01 to Fb17 correspond to the inputs in the terminal wiring plan (page 92 onwards) e.g. Fb02 = BE2
Activate editing mode for function block. Fb_ blinks on the display.
Display measured value. Activate editing mode for measured value.
Measured value blinks on the display. Correct measured temperature. Read the actual temperature directly from the ther
mometer at the point of measurement and enter this value as the reference tempera
-
-
ture. Confirm corrected measured temperature.
Additional sensors are calibrated similarly.
End
Select
. Exit configuration level. Return to the operating level.
EB 5179 EN 25
Start-up
Note! The sensor values adjusted are not reset by the Loading default settings function.
2.6 Resetting to default values
All parameters and function blocks from any parameter level can be reset to their default set tings (WE).
Proceed as follows:
Reset to default settings. Function blocks and parameters are reset to their default settings (WE).
Note!
When the key number is active, thefunction blocksprotected bythe key number are also reset to their default settings. The controller isready foroperation with its default settings. You just need to set the correctdate and current time.
-
26 EB 5179 EN
Manual operation
3 Manual operation
Switch to manual mode to configure all outputs (see wiring diagram in section 11).
Proceed as follows:
Position all selector mode switches to +, 0 or –. Select
PU
pump manual level. Open pump manual level. Select pump PU1 to PU5:
PU1: BA11 PU2: BA12 PU3: BA13 PU4: BA14 PU5: BA15
Confirm pump selection. The display blinks.
Activate output: Deactivate output:
Confirm setting. The modified values remain active as long as the controller is in manual mode.
Move slide switch from 0, + or –. Exit manual level.
Note! In manual mode, frost protection is not guaranteed.
EB 5179 EN 27
Systems
4 Systems
There are 10 hydraulic schematics.
System code number (Anl) Heating Outdoor temperature compensated flow temperature
Number of heating circuits 2231231222 No. of heating circuits w. mixing valve 2221131122
DHW heating •• ••••
From the primary circuit ••• From the secondary circuit ••
12345678910
control with variable return flow temperature limitation
28 EB 5179 EN
System Anl 1
Systems
BE BA AE RK
RK
prim
VF
sek
HK1
UP1 UP2
RK
FW
RüF
RüF1 RK
RF1VF1
HK2
VF2
RüF2
RF2
Default setting
Co1 -> Fb00 = OFF (without RF1) Co1 -> Fb01 = OFF (without RüF1) Co1 -> Fb02 = ON (with AF1) Co2 -> Fb00 = OFF (without RF2) Co2 -> Fb01 = OFF (without RüF2) Co2 -> Fb02 = OFF (without AF2) Co5 -> Fb00 = ON (with VFsek) Co5 -> Fb01 = ON (with RüFprim)
AF2AF1
EB 5179 EN 29
Systems
System Anl 2
BE BA AE RK
RK
FW
RüF
prim
RK
VF
sek
HK1
UP1 UP2
RüF1 RK
RF1VF1
HK2
VF2
RüF2
RF2
Default setting
Co1 -> Fb00 = OFF (without RF1) Co1 -> Fb01 = OFF (without RüF1) Co1 -> Fb02 = ON (with AF1) Co2 -> Fb00 = OFF (without RF2) Co2 -> Fb01 = OFF (without RüF2) Co2 -> Fb02 = OFF (without AF2) Co4 -> Fb00 = ON (with SF1) Co4 -> Fb01 = ON (with SF2) Co4 -> Fb03 = ON (with VFS, with VFT) Co5 -> Fb00 = ON (with VFsek) Co5 -> Fb01 = ON (with RüFprim)
AF2AF1
30 EB 5179 EN
Loading...
+ 112 hidden pages