Samson 5024-1 Series, 5024-1002, 5024-1001, 5024-1003 Mounting And Operating Instructions

Page 1
Power Supply and Indicator Unit Type 5024-1
Fig. 1 ⋅Type 5024-1
Mounting and Operating Instructions
EB 9539 EN
Edition October 2003
Page 2
Application
1 Application
In addition to displaying current data on the
LC display, two floating contacts indicate The Type 5024-1 Power Supply and Indica­tor Unit is used to supply power to two-wire transmitters (4 to 20 mA) such as Media 6 devices (Type 5006), Type 6051 Electrical Transmitters for Pressure or CTMd pressure sensors from the AB company and other de­vices.
when adjustable minimum and maximum
values are reached.
The direction of action of the alarm contacts
over relays that open or close when the
minimum or maximum value is reached
together with the corresponding illumination
of an LED is selectable over switches.
Technical data
Power Supply and Indicator Unit
Power supply 230 V, 45 to 60 Hz 115 V, 45 to 60 Hz 24 V, 45 to 60 Hz
Power consumption Approx. 1.8 VA
Measuring circuit 4 to 20 mA
Transmitter power supply 24 V at 20 mA
Output 2 floating contact alarms, max. 250 V AC/3 A
Contact rating
Perm. ambient temperature 0 to 50 °C
Degree of protection IP 54
The device may only be mounted, started up or serviced by fully trained and
qualified personnel, observing the accepted industry codes and practices. In these mounting and operating instructions, the term experienced personnel refers to individuals who are able to evaluate the responsibilities assigned to them as well as recognize potential hazards due to their specialized training, knowledge, and experience as well as their special knowledge of the relevant standards.
Proper shipping and appropriate storage are assumed.
Type 5024-1001 5024-1002 5024-1003
$
10
with AC voltage and max. 300 Ω re si sti ve lo ad
2
EB 9539
Note:
The device with a CE marking fulfills the requirements of the European Press­ure Equipment Directive 97/23/EC as well as the Directive 89/336/EEC. The declaration of conformity can be viewed and downloaded on the Internet at http://www.samson.de.
Page 3
Installation
2Installation
Mount the device directly in the control room or to a wall using the supplied mount­ing clips, nuts and bolts. Refer to the dimensional diagram on page 5 for the distances between holes.
2.1 Electrical connections
For electrical installation, you are re­quired to observe the relevant elec­trotechnical regulations and the acci­dent prevention regulations that apply in the country of use. In Germany, these are the VDE regu­lations and the accident prevention regulations of the employers lia­bility insurance.
Connect wires to terminals over the cable glands as illustrated in Fig. 2.
2.1.1 Determining the direction of action for the contact alarms
When connecting the relay contacts c, and no for A1 and A2 (see Fig. 2 for switch­ing function), the direction of action must be set at the selector switches A1 and A2 (lo­cated at the top right-hand corner of the lower board) as follows:
Point on switch is visible:
minimum alarm
When
is reached, the relay
is energized and the LED is illuminated.
Point on switch is not visible:
When the
maximum alarm
is reached, the relay is energized and the LED is illumi­nated.
nc
_
+
Transmitter supply
LNPE
c nc no c nc no
A1 A2
Network
Fig. 2 ⋅Terminal assignment and switching function
Relay contacts
Switching function:
no
c
nc
c common connection
nc normally closed Contact opens when the relay is energized
no normally open Contact closes when the relay is energized
EB 9539
3
Page 4
Operation
3Operation
3.1 Positioning the decimal point and selecting label with enginee­ring units
A jumper located on the top right-hand cor­ner of the display board can be installed at four different positions, depending on where the decimal point should be posi­tioned. Refer to Fig. 3 for the setting.
Select the required multiplication factor and the appropriate engineering units from the supplied adhesive label and stick them on the front cover below the display.
Decimal point
4...20mA
Test
Δ
( )p
3.2 Setting the display
The display can be set in combination with a rheostat of R = 10 kΩ and an ammeter or, alternatively, a pressure transmitter or differential pressure transmitter that has al­ready been adjusted. An ammeter can be connected to the TEST terminals for the transmitters.
3.2.1 Adjusting zero
Required for this adjustment: 2-wire signal from, for example, the trans­mitter must be 4 mA
Turn potentiometer N on the display
board until the required initial value ap­pears on the LC display.
I . X . X . X
Without decimal point
Direction of action Relay
A2
A1 A2
A1
LED
mA
mA
Fig. 3 ⋅Display board
4
EB 9539
R = 10 kΩ
_
A1 A2
+
Switches and potentiome­ter for switching point of max./min. alarm
NSP
Zero
Initial Fine
Span
Page 5
Operation
3.2.2 Adjusting span:
Required for this adjustment: 2-wire signal from, for example, the trans­mitter must be 20 mA
First adjust the rotary switch SP (initial
adjuster), then the potentiometer SP (fine adjuster) until the required final value ap­pears on the LC display.
Dimensions in mm
122.5 110
3.3 Setting the contact alarms
Set the contact alarms A1 and A2 over the selector switch and potentiometer located at the bottom of the display board (Fig. 3). To set the required switching point, adjust the corresponding selector switch for A1 or
point not visible
A2 to justed limit value then appears on the LC dis­play. Set the associated potentiometer until the re­quired limit value appears on the display. Reset the selector switch to display value supplied by the transmitter.
. The currently ad-
point visible
to
70
90
M20x1.5
128
22
56
120.5
EB 9539
5
Page 6
SAMSON AG ⋅ MESS- UND REGELTECHNIK Wei smül lers tra ße 3 ⋅ 60314 Frankfurt am Main ⋅ Germany Phone: +49 69 4009-0 ⋅ Fax: +49 69 4009-1507 Internet: http://www.samson.de
EB 9539 EN
S/Z 2007-08
Loading...