Rudd RGTK-06MAES User Manual

FORM NO. G11-488 REV. 5
Supersedes Form No. G11-488 Rev. 4
GAS FURNACES
RGTK- SERIES
Models with Input Rates from 60,000 to 120,000 BTU/HR [17.58 to 35.17 kW]
(All Models 92% A.F.U.E.† or Above)
90 PLUS®WITH DUAL COMFORT CONTROL
TWO-STAGE DOWNFLOW/HORIZONTAL GAS FURNACES
The Rheem Classic Series®90 Plus with Dual Comfort Control line of
downflow/horizontal gas furnaces are designed for utility rooms, clos-
ets, alcoves, or attics. T
he RGTK is shipped in the downflow configu­ration and is easily converted for horizontal left-hand airflow applications.
The design is certified by CSA.
Features
Two stages of operation to save energy and maintain optimal com-
fort level.
Furnace operates at 70% capacity for low-heat and 100% capacity
for high-heat.
Compatible with single or two-stage thermostat. (For optimal per-
formance two-stage thermostat recommended.)
Heat exchanger tubular construction is stainless steel for maximum
corrosion resistance and thermal fatigue reliability.
Low profile “34 inch” design is lighter and easier to handle and
leaves room for optional accessories.
Top electrical connections, left or right side gas, and condensate
drainage connections on downflow/horizontal models.
Integrated control board manages all operational functions and
provides hookups for humidifier and electronic air cleaner.
An insulated blower compartment, a slow-opening gas valve and a
specially designed inducer system make it one of the quietest fur­naces on the market today.
Pre-paint galvanized steel cabinet.
Molded permanent filters.
Optional indoor or outdoor combustion air.
Transformer and control fuse protection.
Control board diagnostics.
Condensate drain trap for horizontal/downflow application provided
standard. A variety of cooling coils and plenums designed to use with the Rheem Classic Series
®
90 Plus gas furnaces are available as
optional accessories for air conditioning models.
A.F.U.E. (Annual Fuel Utilization Efficiency) calculated in accordance with Department of Energy test
procedures.
2 Rheem Manufacturing Company
STANDARD EQUIPMENT
Completely assembled and wired; heat exchanger; primary: 409 and aluminized 409 stainless steel, secondary: 29-4C stainless steel; induced draft; pressure switches; redundant main gas control manual shut-off; blower compartment door safety switch; solid state time on/off blower control; limit controls; 100% safety lock out; cool fan off delay; field selectable heat fan off delay; one hour automatic retry; power and self-test diagnostics; flame sense current diagnostics; electronic air cleaner connections; twinning (built-in) features; humidifier connections; humidifier on/off delay; low speed continuous fan option; single speed option for heating and cooling applications; pressure regulator for natural and L.P. (propane) gasses; transformer; direct drive, multi-speed blower motor. (Please note: a thermostat is not included as standard equipment.)
OPTIONAL EQUIPMENT
NOTE: Furnace is not listed for use with fuels other than natural or L.P.
(propane) gas.
All models can be converted by a local service dealer to use L.P. (propane) gas without changing burners. Factory approved kits must be used to convert from natural to L.P. (propane) gas and may be ordered as optional accessories from a parts distributor.
For L.P. (propane) operation, refer to Conversion Kit Index Form.
WARNING
THIS FURNACE IS NOT APPROVED
OR RECOMMENDED
FOR USE IN MOBILE HOMES
PRIMARY AND SECONDARY HEAT EXCHANGER
REMOTE SENSOR
IN-SHOT BURNERS
PRESSURE SWITCHES
DRAFT INDUCER
INTEGRATED
FURNACE CONTROL
GAS VALVE AND MANIFOLD
CLASSIC SERIES 90 PLUS HIGH EFFICIENCY DOWNFLOW/HORIZONTAL GAS FURNACE
DIRECT SPARK IGNITION & REMOTE SENSOR
Rheem Manufacturing Company 3
BEFORE PURCHASING THIS APPLIANCE, READ IMPORTANT ENERGY COST AND EFFICIENCY INFORMATION AVAILABLE FROM YOUR RETAILER.
PHYSICAL DATA AND SPECIFICATIONS— DOWNFLOW/HORIZONTAL MODELS
U.S. and Canadian Models
NOTES: All models are 115V, 60HZ, 1ø.Gas connection size for all models is 1/2" [13 mm] N.P.T.
See Index Form for LP Conversion Kits.In accordance with D.O.E. test procedures.
*E = Standard
*N = NO
x
Models
MODEL IDENTIFICATION
R G T K 07E* AM E S
Rheem Gas
Furnace
Downflow/
Horizontal
Condensing
Gas Furnace
Design
Series
Heating Input
Designation
Variations
A = Std. B = Wide
Cabinet
Blower Size
M = 11 x 7
[279 x 178 mm]
R = 11 x 10
[279 x 254 mm]
Z = 12 x 11
[305 x 279 mm]
Y = 12 x 7
[305 x 178 mm]
Heat/Cool
Designation
E = 1100-1300 CFM
[519-613.5 L/s]
G = 1500-1700 CFM
[707.9-802.3 L/s]
J = 1900-2100 CFM
[896.7-991.1 L/s]
Fuel Code S = U.S. and
Canadian Natural Gas
Electric
Ignition
06
*
07
*
09
*
10
*
12
*
Input
BTU/HR
60,000 [17.6 kW] 75,000 [22 kW].6
90,000 [26.4 kW] 105,000 [30.7 kW] 120,000 [35.2 kW]
NOTES: *E = Standard
*N = NO
x
Models
[ ] Designates Metric Conversions
MODEL NUMBERS RGTK-06*MAES RGTK-07*MAES RGTK-07*YBGS RGTK-09*ZAJS RGTK-10*ZAJS
HIGH FIRE INPUT BTU/HR [kW] LOW FIRE INPUT BTU/HR [kW] 42,000 [12.31] 52,500 [15.39] 52,500 [15.39] 63,000 [18.46] 73,500 [21.54] HIGH FIRE HEATING CAPACITY BTU/HR [kW] 56,000 [16.41] 70,000 [20.51] 70,000 [20.51] 84,000 [24.62] 97,000 [28.43] 113,000 [33.12] HIGH FIRE HIGH ALTITUDE INPUT 8000' 40,800 [11.96] 51,000 [14.95] 51,000 [14.95] 61,200 [17.94] 71,400 [20.93] HIGH FIRE HIGH ALTITUDE OUTPUT
AT 8000' (HIGH FIRE) [kW] BLOWER (D x W)
[mm] MOTOR H.P. [W]–SPEEDS–TYPE MOTOR FULL LOAD AMPS 6.8 6.8 9.5 9.5 9.5 HEATING SPEED–HIGH FIRE MED-LO MED-HI MED-LO MED-LO MED-LO HEATING SPEED–LOW FIRE LOW LOW LOW LOW LOW LOW COOLING SPEED HIGH HIGH HIGH HIGH HIGH MINIMUM EXT. STATIC PRESSURE
(IN. W.C.) [kPa] MAXIMUM EXT. STATIC PRESSURE
(IN. W.C.) [kPa] HEATING CFM @ .2" [.049 kPa]
W.C. E.S.P. [L/s] COOLING CFM @ .5" [.124 kPa]
W.C. E.S.P. [L/s] TEMPERATURE RISE-HIGH FIRE
RANGE °F [°C] TEMPERATURE RISE-LOW FIRE
RANGE °F [°C] RETURN AIR CABINETS (OPT.)
RXGR­FILTER SIZE [mm]
STANDARD, HIGH VELOCITY PERMANENT FILTER (IN.)
APPROX. SHIPPING WEIGHT (LBS.) [kg] 117 [53.1] 123 [55.8] 123 [55.8] 148 [67.1] 152 [68.9]
AFUE
60,000 [17.58] 75,000 [21.98] 75,000 [21.98] 90,000 [26.38] 105,000 [30.77]
37,944 [11.12] 47,430 [13.90] 47,430 [13.90] 56,916 [16.69] 66,402 [19.46]
11 x 7
[279 x 178]
1
/2 [373]-4-PSC1/2 [373]-4-PSC3/4 [559]-4-PSC3/4 [559]-4-PSC3/4 [559]-4-PSC
.12 [.029] .12 [.029] .12 [.029] .15 [.037] .20 [.049]
.50 [.124] .50 [.124] .50 [.124] .50 [.124] .50 [.124]
885 [418] 1060 [500] 1375 [649] 1400 [661] 1425 [673]
1180 [557] 1150 [543] 1625 [767] 1850 [873] 1820 [859]
40-70
[22.2-38.9]
30-60
[16.7-33.3]
C17B
(2) 12" x 20"
[305 x 508]
153/4 x 25 x 1 153/4 x 25 x 1 153/4 x 25 x 1 191/4 x 25 x 1 191/4 x 25 x 1 223/4 x 25 x 1
93.8 92.5 93.0 93.2 92.2
11 x 7
[279 x 178]
45-75
[25-41.7]
45-75
[25-41.7]
C17B
(2) 12" x 20"
[305 x 508]
12 x 7
[305 x 178]
35-65
[19.4-36.1]
25-55
[13.9-30.6]
C21B
(2) 12" x 20"
[305 x 508]
12 x 11
[305 x 279]
45-75
[25-41.7]
35-65
[19.4-36.1]
C21B
(2) 20" x 20"
[508 x 508]
12 x 11
[305 x 279]
50-80
[27.8-44.4]
35-65
[19.4-36.1]
C21B
(2) 20" x 20"
[508 x 508]
RGTK-12*RAJS
120,000 [35.17]
84,000 [24.62]
81,600 [23.91]
75,888 [22.24]
11 x 10
[279 x 254]
3
/4 [559]-4-PSC
9.5
MED-HI
HIGH
.20 [.049]
.50 [.124]
1565 [739]
2040 [963]
50-80
[27.8-44.4]
45-75
[25-41.7]
C24B
(2) 24" x 20"
[609 x 508]
160 [72.6]
92.4
Loading...