The purpose of this manual is twofold:
one, to provide the installer with the
basic directions and recommendations
for the proper installation and adjustment
of the water heater; and two, for
the owner–operator, to explain the
features, operation, safety precautions,
maintenance and troubleshooting of the
water heater. This manual also includes a
parts list.
It is very important that all persons who
are expected to install, operate or adjust
this water heater read the instructions
carefully so they may understand how to
perform these operations. If you do not
understand these instructions or any terms
within it, seek professional advice.
Any questions regarding the operation,
maintenance, service or warranty of this
water heater should be directed to the
seller from whom it was purchased. If
additional information is required, refer to
the section on “If you need service.”
Do not destroy this manual. Please read carefully and keep in a safe place for future reference.
Recognize this symbol as an indication of Important Safety Information!
!
California Proposition 65 Warning: This product contains chemicals known to the State of California to cause cancer, birth
!
defects or other reproductive harm.
®
AP14990-2 (08/10)
Page 2
System Model Numbers
Please visit our web site for new product updates, answers to frequently asked questions (faq) and useful
information about solar water heating systems.
2) System Description and
Operational Principle . . . 8
3) Installation Requirements -
General . . . . . . . . . . . . . . 9
4) Installation Requirements -
Specic . . . . . . . . . . . . . 10
5) Start Up Procedures . . . . . 20
6) Three Modes of System
Operation . . . . . . . . . . . 21
7) Isolating the Major
Components and
Shut Down Procedures . 23
8) Summer Vacation
Recommendations . . . . 23
9) Maintenance and
Troubleshooting . . . 24-25
10) Solaray System Component
Parts . . . . . . . . . . . . 26-27
Write the model and serial numbers here:
Model Number of Solar System Tank: ____________________________________
Serial Number of Solar System Tank: _____________________________________
Model Number of Collector Panel #1: ____________________________________
Serial Number of Collector Panel #1: _____________________________________
Model Number of Collector Panel #2: ____________________________________
Serial Number of Collector Panel #2: _____________________________________
Model Number of Solar System Pump: ___________________________________
Serial Number of Solar System Pump: ____________________________________
Model Number of Solar System Control: _________________________________
Serial Number of Solar System Control: _________________________________
You can find them on a label on the appliance.
Staple sales slip or cancelled check here.
Proof of the original purchase date is needed to obtain service
under the warranty.
READ THIS MANUAL
Inside you will find many helpful hints on how to use and
maintain your water heater properly. Just a little preventive
care on your part can save you a great deal of time and money
over the life of your water heater.
You’ll find many answers to common problems in the Before
You Call For Service section. If you review our chart of
Troubleshooting Tips first, you may not need to call for service
at all.
READ THE SAFETY INFORMATION
Your safety and the safety of others are very important. There
are many important safety messages in this manual and on your
appliance. Always read and obey all safety messages.
This is the safety alert symbol. Recognize this symbol
as an indication of Important Safety Information!
!
This symbol alerts you to potential hazards that can
kill or hurt you and others.
Figures. . . . . . . . . . . 28-31
If You Need Service . . . . . . .32
All safety messages will follow the safety alert symbol and
either the word “DANGER”, “WARNING”, “CAUTION” or
“NOTICE”.
These words mean:
!
DANGER
that will result in death or serious
injury.
WARNING
could result in death or serious injury
and/or damage to property.
!
CAUTION
may result in minor or moderate
injury.
NOTICE:
specified procedure or maintain
a specific condition.
An imminently hazardous situation
A potentially hazardous situation that
A potentially hazardous situation that
Attention is called to observe a
3
Page 4
Introduction
!
Thank you for purchasing a solar water heating
system. It is one of the most effective and troublefree systems available today. In addition to reducing
your water-heating bills, it will help preserve precious
natural resources by using free energy from the sun.
As with an electric or gas water heater, your new
solar water heating system operates automatically to
ensure you will always have an ample supply of hot
water. However, there are simple steps you can take to
increase both its efficiency and service life.
This manual provides the manufacturers recommended
procedures for solar water-heating systems. The
procedures are essential for correct installation,
troubleshooting and maintenance.
Read each section of this manual thoroughly before
beginning work on the system.
CAUTION: Changes to the design or intended
use of the Solar Water Heating System will void the
manufacturers warranty. Installation,
troubleshooting, and maintenance must be
performed by a qualified technician.
This manual will help you get the most out of your
solar water heating system. Please read it carefully
when the installation is complete, and review it from
time to time to refresh your memory about the service
requirements and safety measures.
The Operation section of the manual contains
important information regarding the system procedures
as well as safety measures pertaining to the system. It
is important that you follow these guidelines to ensure
safe, efficient and trouble-free operation.
While the system requires very little maintenance,
there will be a periodic need for some upkeep. The
Maintenance section outlines those requirements for
service, which you may do yourself, as well as those
procedures best performed by a qualified service
technician.
The Troubleshooting section contains steps you can
take if the system is not performing, as it should.
The solar energy system described by this manual,
when properly installed and maintained, meets
the minimum standards established by the Solar
Rating and Certification Corporation (SRCC). This
certification does not imply endorsement or warranty
of this product by the SRCC.
The solar energy system described by this manual,
when properly installed and maintained, meets the
minimum standards established by the Florida Solar
Energy Center, in accordance with Section 377.705,
Florida Statutes. This certification does not imply
endorsement or warranty of this product by the Florida
4
Solar Energy Center or the state of Florida.
The components of the system include a water storage
tank, solar collector panels, expansion tank, pump
valves and fittings.
In locations which are subject to temperatures below
41°F, a mixture of heat transfer fluid and water
circulates through the solar collector panels. This fluid
is heated by the sun, then circulated through a heat
exchange, heating the potable (drinking) water inside
the storage tank. The heat transfer fluid is a non-toxic,
food-grade liquid, which provides freeze protection
for the closed loop heat transfer loop. It is colored to
differentiate the closed system fluid from the potable
water supply.
This circulation of the heat transfer fluid is
accomplished by a pump and sensors. These solar
water heaters are referred to as closed loop systems.
Your hot water is stored in a steel tank lined with
porcelain enamel and thickly insulated to help maintain
the water temperature throughout the day and night.
To ensure your hot water supply is never depleted, the
system is equipped with a backup heating element..
When there may be insufficient solar energy, you are
still assured of all the hot water you will need.
While your system is one of the most efficient
available, there are two simple steps you can take to
increase your water-heating cost savings.
Keep the use of the Backup Heater to a Minimum
You can save the most money on your water-heating
bills by using the backup heating element on your
system as little as possible. If the sun shines brightly
between 10 am and 3 pm, enough heat will normally
be generated to keep the water hot throughout the rest
of the day and night.
However, on days when the sky is cloudy or when
large quantities of hot water are being used, we suggest
that the backup heating element be left “ON” overnight
to ensure adequate hot water the next morning.
Try to use Hot Water during Daylight Hours
When possible, schedule heavy hot water use, such
as dish washing, laundry and showers, in the middle
of the day. If hot water usage occurs while the sun is
up, the fresh (cold) water added to the storage tank is
heated more quickly.
When water is used late in the day or at night, the
fresh water entering the tank will be heated by the
heating element so hot water is available in the
morning.
Page 5
IMPORTANT SAFETY INFORMATION.
!
R
E
S
E
T
R
E
S
E
T
TURN OFF
POWER
BEFORE
SERVICING
90°F150°F
125°F
(66°C)
(52°C)
(32°C)
READ ALL INSTRUCTIONS BEFORE USING.
DANGER!
WATER TEMPERATURE SETTING
Safety and energy conservation are factors to be considered when selecting the water
temperature setting of water heater’s thermostat. Water temperatures above 125°F can
cause severe burns or death from scalding. Be sure to read and follow the warnings
outlined on the label pictured below.
Time/Temperature Relationship in Scalds
!
D A N G E R
HOT
BURN
Water temperature over 125°F can
cause severe burns instantly or
death from scalds.
Children, disabled and elderly are
at highest risk of being scalded.
See instruction manual before
setting temperature at water
heater.
Feel water before bathing or
showering.
Temperature limiting valves are
available, see manual.
!
DANGER: Burns from Hot Water and
Steam - Use extreme care when opening
relief valves, charging closed loop, and
filling storage tank.
The electrical element booster thermostat has
been factory set at 50°C (120°F) to reduce the
risk of scald injury. Adjusting the thermostat to a
higher setting is not recommended. Hotter water
increases the potential for Hot Water Scalds.
Temperature Time To Produce a Serious Burn
120°F More than 5 minutes
125°F 1½ to 2 minutes
130°F About 30 seconds
135°F About 10 seconds
140°F Less than 5 seconds
145°F Less than 3 seconds
150°F About 1½ seconds
155°F About 1 second
Table courtesy of Shriners Burn Institute
The chart shown above may be used as a guide
in determining the proper water temperature for your
home.
!
DANGER: Households with small children,
disabled, or elderly persons may require a 120°F
or lower thermostat setting to prevent contact
with “HOT” water.
NOTICE: Mixing valves should be installed to reduce
the point of use water temperature by mixing hot and
cold water in branch water lines. Contact a licensed
installer or the local plumbing authority for further
information.
The temperature of the water in the water heater can be
regulated by setting the temperature dial of the adjustable
surface mounted thermostat located behind the jacket access panel.
This thermostat controls the
Reset button
Thermostat
dial pointer
Thermostat
protective
cover
water heater’s heating element only. (A separate thermostat should be utilized in
monitoring the temperature
from the collector).
To comply with safety regulatio ns the thermostat is
factory set at 120° F or less
where local codes require.
!
DANGER: Hotter
water increases the
potential for Hot
Water SCALDS.
5
Page 6
IMPORTANT SAFETY INFORMATION.
READ ALL INSTRUCTIONS BEFORE USING.
WARNING!
For your safety, the information in this manual must be followed to minimize the risk of fire or
explosion, electric shock, or to prevent property damage, personal injury, or loss of life.
Be sure to read and understand the entire Use and Care Manual before attempting to install or
operate this water heater. It may save you time and cost. Pay particular attention to the Safety
Instructions. Failure to follow these warnings could result in serious bodily injury or death.
Should you have problems understanding the instructions in this manual, or have any questions,
STOP, and get help from a qualified service technician, or the local utility.
FOR INSTALLATIONS IN THE STATE OF CALIFORNIA
California Law requires that residential water heaters must be braced, anchored or strapped
to resist falling or horizontal displacement due to earthquake motions. For residential water
heaters up to 52 gallon capacity, a brochure with generic earthquake bracing instructions can be
obtained from: Office of the State Architect, 1102 Q Street, Suite 5100, Sacramento, CA 95814
or you may call 916-445-8100 or ask a water heater dealer.
However, applicable local codes shall govern installation. For residential water heaters
of a capacity greater than 52 gallons, consult the local building jurisdiction for acceptable
bracing procedures.
SAFETY PRECAUTIONS
Have the installer show you the location of the circuit breaker and how to shut it off if
necessary. Turn off the circuit breaker if the water heater has been subjected to overheating,
fire, flood, physical damage or if the ECO fails to shut off.
● Read this manual entirely before installing
or operating the water heater.
● Use this appliance only for its intended
purpose as described in this Use and Care
Manual.
● Be sure your appliance is properly installed
in accordance with local codes and the
provided installation instructions.
● Do not attempt to repair or replace any part
of your water heater unless it is specifically
recommended in this manual. All other
servicing should be referred to a qualified
technician.
READ AND FOLLOW THIS SAFETY INFORMATION
CAREFULLY.
SAVE THESE INSTRUCTIONS
6
Page 7
PREFACE
Let us rst offer two words of grateful appreciation.
Thank You! We sincerely appreciate your business.
We also wish to say thank you for "going solar". Solar
water heating systems help to reduce our nation’s
dependence on polluting fossil fuels, minimize
the greenhouse gas emissions associated with
conventional water heating and, very importantly,
lower your monthly utility costs.
Section 1: Introduction
Solar water heating systems are climate and site
specic appliances. Different types of solar systems
are installed around the world in accordance with
regional weather and water quality conditions. System
performance varies as a function of the household
hot water load, including daily showers, laundry and
kitchen uses, average ground water and ambient air
temperatures, the home’s roof pitch and orientation,
and, of course, the seasonal intensity of solar
radiation. These variables, some of which change
from home to home on the same neighborhood street,
will determine how much energy and money your
system will save on an annual basis.
Your solar system is known as a "forced circulation"
system because it utilizes a mechanical pump to
efciently circulate the Dow Chemical Dowfrost HD
propylene glycol heat transfer uid (HTF) throughout
the system. The HTF protects the collector piping
from freezing and inhibits scaling deposits that can
reduce performance in "open-loop" systems utilizing
potable water as the HTF. Proper application and
maintenance of the HTF can protect your solar water
heating system to minus 60° Fahrenheit.
Your solar water heating system has been designed
to meet exacting SRCC OG-300 certication
requirements. The components found in your system
have been selected for their proven reliability,
longevity and performance in your specic region of
the country.
This manual is intended as a basic solar water heating
primer. Our goal is to familiarize you with the proper
installation, operation, and maintenance of your
solar system. This system is required to be installed
by properly licensed solar or plumbing contractors
in accordance with SRCC Standard OG-300 and all
applicable national, state and local codes, ordinances
and regulations governing solar water heating
installations, as well as good trade practices. Failure
to follow the procedures and practices described in
this manual can void the manufacturer's warranty for
specic component parts.
This manual covers installations utilizing two solar
collectors with a single solar storage tank and also
two tank systems that include a solar storage tank
and a conventional water heater. For simplicity, the
singular form will be used throughout this manual
when referring to all of these components and system
permutations. Frequent reference is made throughout
this manual to specic component parts. The
placement of each component can be seen in system
schematic gures 16, 17 18 & 19. A description of
each component and its function is found in Section
10.
7
Page 8
Section 2: System Decription and Operational Principle
The key components in the solar water heating system
include the solar collector, solar storage tank with
integral heat exchanger, circulation pump, differential
thermostat, expansion tank, pressure gauge, mixing
valve and the non-toxic propylene glycol heat transfer
uid (HTF).
The solar collector is the heart of the system. Simply
stated, when the sun is shinning, heat energy is
absorbed by the solar collector’s all copper absorber
plate and tranferred to the HTF circulating through
the solar collector. The system pump efciently
circulates this heated uid through the collector
piping and integral tank heat exchanger. As the
HTF passes through the heat exchanger the heat in
the uid is transferred by conduction to the potable
water in your solar storage tank. As this process is
continuously repeated during the average sunny day
the temperature in your solar storage tank rises.
When the solar collector absorber plate is
approximately sixteen degrees hotter than the
temperature in the bottom of your solar storage tank,
the controller will turn the circulating pump on. When
the temperature difference has been reduced to eight
degrees, the controller automatically turns the pump
off.
Both single and double tank systems are designed to
provide three separate modes of system operation.
The system will, (1) accommodate 100% solar
operation, (2) serve as a preheater to your solar
storage tank or back-up water heater, or (3) bypass the
solar collector and run 100% on utility power. Section
Six provides instructions for setting the system for
automatic operation in each of these three modes.
The Dowfrost HD HTF protects your solar system
against freezing. Dowfrost HD can provide reliable
freeze protection at temperatures as low as minus
60° Fahrenheit if properly applied and maintained.
Use of uninhibited propylene glycol, plain water or
a concentration of these two uids as the HTF in this
system is strictly prohibited.
Propylene glycol can degrade over time. The process
of degradation is accelerated in presence of oxygen
and/or heat. We strongly encourage you to establish
a preventative maintenance schedule with your
installation contractor. The HTF pH level must be
maintained between 8 and 10 in order to prevent
glycol oxidation and corrosion of the collector
excludes freeze damage for any reason and absorber
plate damage resulting from the oxidation of the
propylene glycol HTF.
In order to completely protect the integrity of the
solar collector and piping, the system is designed to
be drained manually if subject to extended periods
of disuse or persistent hard freeze conditions below
minus 60° Fahrenheit. (See Sections 8.1 and 8.2).
8
Page 9
Section 3: Installation Requirements- General
3.2 The solar collector must be located in a
3. The contractor shall obtain all required permits and
approvals.
3.1 The installation shall conform to all federal, state
and local regulations, codes, ordinances and
standards governing solar water heating system
installations, and the contractor shall adhere to
sound building safety and trade practices. Special
consideration must be given to building code
requirements for the penetration of structural
members and re rated assemblies.
structurally sound area of the roof that will be
unshaded for the majority of the day all year
round. Adjacent buildings and trees should
be checked for possible winter shading. An
instrument such as the Pathnder can be used for
solar site analysis.
3.3 Before the installation the contractor shall
inspect the condition of the roof and notify the
homeowner of any existing roof damage or
necessary repairs.
3.4 The homeowner and contractor shall conrm
the location of all roof and ground mounted
components in advance of the installation.
9
Page 10
Section 4: Installation Requirements- Specific
4. Collector Orientation
The performance of solar water heating systems in
the Northern Hemisphere is optimized when the
collector is mounted facing True South. Performance,
however, suffers very little when the collector is
oriented no more than 45° East or West of True South.
The collector should be unshaded by any permanent
obstacle between 9:00 a.m. and 3:00 p.m. on any day
of the year.
Figure 2 - Side Pitch Mounting
The solar collectors in a two collector staggered mount
installation must be spaced far enough apart to prevent
winter shading. Table 1 shows the correct spacing
between collectors to prevent shading on December
21, when the sun is at its lowest angle.
Figure 1 - Reverse Pitch Mounting
4.1 Collector Tilt
Optimal annual efciency is achieved by tilting the
solar collector at an angle that equals your latitude
plus an additional 10°. This tilt angle favors the lower
winter sun when collector performance is at it’s lowest
and minimizes overheating during the hottest summer
months.
The solar collector in your solar system can be
mounted in either a vertical or horizontal orientation
on the roof (See Figure 4). Although the collector is
protected from freeze conditions by the glycol HTF
and does not normally need to be drained, it is still
important to slope the collectors just slightly to allow
for complete drainage if necessary. The recommended
slope is 1/4" per foot of horizontal run.
Figure 4 - Collector Orientation
To ensure proper water drainage from the glazing,
the collectors must maintain a minimum angle from
horizontal of at least 10°. Never mount the collector
directly or parallel to a at roof surface. Use "Solar
Strut" tilt mount kits to rack the collectors to the
proper angle.
The collector should be mounted as close to the
storage tank as possible to minimize heat loss in the
piping runs. If the home has attic access, mounting the
collectors near the roof peak provides for additional
attic workspace.
The solar collector should be mounted on the roof in
accordance with these general principles:
4.2.1 The most important structural consideration is
to securely anchor the solar collector and the
mounting hardware to the structural members
of the roof with stainless steel hanger or lag
bolts. The solar collector must be attached to
the mounting hardware as detailed in Figures
5–10. (Note: The drawings in this manual detail
mounting hardware for the series collector.)
4.2.2 The collector must be raised from the roof
surface to allow for rainwater and debris to pass
under the collectors and for proper ventilation
of the roong material. There should be at least
3" of clearance between the roof surface and the
bottom of the solar collectors.
4.2.3 In selecting mounting hardware and fasteners
it is extremely important to avoid galvanic
corrosion resulting from the direct contact of
incompatible metals. Use of anodized aluminum
mounting hardware and stainless steel lag or
hanger bolts, lock washers and round washers
is recommended. In climates subject to severe
winters or high humidity use of galvanized
fasteners is prohibited.
4.2.4 Preserving the integrity of the roof membrane is
the most important roong consideration. Ensure
that all roof penetrations required to plumb and
mount the solar collector are properly ashed
and sealed in accordance with standard roong
practices.
4.2.5 If the region is subject to hurricane conditions,
additional steps may be required to secure the
collector and mounting hardware to the structural
members. In certain areas of the country, local
building codes may require collector wind
load testing or prescribe specic mounting
procedures. Consult your local building
department.
4.3 Collector Loop Pipe Insulation
The collector loop cold supply and hot return lines
must be well insulated with a high quality exible
closed cell insulation to minimize heat loss. The wall
thickness of the pipe insulation should not be less than
3/4". A 1" wall thickness is required in all areas prone
to annual hard freeze conditions. When it comes to
pipe insulation the rule is simple: thicker is better. Use
To the extent possible, slide the insulation material
over the pipe without cutting or taping. All butt
joints must be sealed with contact adhesive. The use
of rigid polyethylene pipe insulation is prohibited.
The temperatures generated by your collector in the
summer months or under stagnation conditions can
melt this type of material.
11
Page 12
FIGURES 5-10
Figure 5- Composition Shingle Mounting
ST STL SLIDING
NUT
ANODIZED ALUM
SOLAR STRUT
ST STL NUTS &
WASHERS
ST STL HANGER BOLT SET
IN SEALANT
* LE NGTH & DIA. VARY
WITH INSTALLATION
* DR ILL PILOT HOLE 3/4
OF BOLT DIA.
SOLAR COLLECTOR
MOUNTING
CLIP
SOLAR COLLECTOR
MOUNTING GROOVE
3/8" ST STL BOLT
W/ LOCKWASHER &
FLATWASHER
3" MIN.
CEDAR SHAKE OR SHINGLES ON
ROOF FELT OVER ROOF DECK
SHEATHING ON ROOF FRAMING
SYSTEM - BEAM OR RAFTER
SIDE VIEW
MOUNTING
CLIP
ROOFING SEALANT
12" X 12" LEAD
FLASHING
12
Figure 6- Shingle Roof Mounting
Page 13
MOUNTING
GROOVE
SIDE VIEW
3/8" ST STLBOLT W/ LOCK
-
WASHER & FLATWASHER
ROOFING SEALANT
12" X 12" LEAD FLASHING
HOLE 2X BOLT DIA. MIN.
CLAY OR CONCRETE TILE ON BATTEN OVER ROOF-ING FELT ON ROOF DECK SHEATHING ON ROOF FRAMING SYSTEM BEAM OR RAFTER
MOUNTING
CLIP
Figure 7 - Tile Roof Mounting
SOLAR COLLEC
TOR
MOUNTING CLIP
ST STL HANGER BOLT SET IN SEALANT * LE NGTH & DIA. VARY
WITH INSTALLA-TION
* DR ILL PILOT HOLE
3/4 OF BOLT DIA.
ST STL NUTS & WASH
-
ERS
ANODIZED ALUM
SOLAR STRUT
ST STL SLIDING
NUT
BLOCK BETWEEN RAFTERS FOR HANGAR BOLT ATTACHEMENT IF RAFTER SPACING DOES NOT MATCH BOTH SPACING.
SOLAR COLLECTOR
MOUNTING CLIP
MOUNTING
GROOVE
SIDE VIEW
ST STL SLIDING NUT
ANODIZED ALUM
SOLAR STRUT
ST STL NUTS & WASHERS
ST STL HANGER BOLT
SET IN SEALANT
* LE NGTH & DIA. VARY
WITH INSTALLATION
* DR ILL PILOT HOLE 3/4
OF BOLT DIA.
MOUNTING
CLIP
3/8" ST STL
ROOFING
SEALANT
BOLT W/ LOCKWASHER &
FLATWASHER
12" X 12" LEAD FLASHING
CLAY OR CONCRETE TILE
ON BATTEN OVER ROOFING FELT ON ROOF DECK
SHEATHING ON ROOF
FRAMING SYSTEM BEAM
OR RAFTER
HOLE 2X BOLT DIA. MIN.
BLOCK BETWEEN RAFTERS FOR
HANGAR BOLT ATTACHEMENT
IF RAFTER SPACING DOES NOT
MATCH BOTH SPACING.
Figure 8 - Tile Roof Mounting
13
Page 14
14
Figure 9 - Flush Mounting
Page 15
Detail "D"
Figure 10 - Universal Tilt Mount
15
Page 16
Section 4: Installation Requirements- Specific
collector in the summer months or under stagna-tion conditions can melt this type of material.
g.14
COLLECTOR PLUMBING - VERTICAL MOUNT
Figure 14
COLLECTOR PLUMBING - VERTICAL MOUNT
Figure 13
COLLECTOR
SENSOR
Any above ground exterior pipe insulation is subject
to UV degradation and must be wrapped with foil tape
or painted with two coats of high quality water-based
acrylic resin coating as supplied by the insulation
manufacturer. Use 3/4" Armaex (or similar) exible
elastomeric closed cell thermal insulation.
4.4 Collector Plumbing
This solar heating system requires the use of all
copper and brass ttings in the collector loop
plumbing. Couplings rather than unions should be
used to join the collectors to avoid leaks and uid loss.
Use only lead-free solder. Use of 50/50 lead solder is
expressly prohibited. Use of galvanized steel, CPVC,
PVC, or any other type of plastic pipe is prohibited.
Piping in new solar installations can be covered with
dirt, grease, solder ux or other impurities that over
time affect the quality of the glycol HTF. A thorough
cleaning is required before charging the system with
glycol. Carefully review the cleaning procedures in
"Charging The System" outlined below.
All vertical piping between the storage tank and
the collector shall be supported at each story or at
maximum intervals of ten feet (10'). Copper plumbers
tape or tube strap is required. The pipe insulation
may not be compressed or crimped by the strapping
material
The installation of all horizontal and vertical piping
may not reduce the performance or rating of any
structural member or re rated assembly. Adhere to all
applicable local codes and ordinances.
4.5 Collector Sensor Placement
The collector sensor must be located on the hot
water return line as close to the collector as possible.
Sensors are typically accurate to +/- 1/2°F if properly
installed and weatherized. To maximize sensor
accuracy, attach the anged portion of the sensor to
the collector header pipe with a stainless steel hose
clamp. Wire nuts used to connect the sensor and low
voltage wiring shall be all plastic, sealed with silicone
and thoroughly wrapped in electrician’s tape.
16
The sensor "bundle" must be placed under the
rubber pipe insulation covering the collector header.
Thoroughly wrap and weatherize the insulation with
electrician’s tape or insulation tape as provided by
the manufacturer (Rubatex Insul-Tape or equal). See
Figure 13 for collector sensor installation detail.
4.6 Low Voltage Wiring
The low voltage wiring used to connect the sensors
to the controller should be a minimum18 AWG. The
wiring should be bare or tinned copper, two conductor,
PVC insulated, with a PVC UV rated gray jacket
Page 17
suitable for exterior use. Use Eastman Wire & Cable
No. 5704, Belden Wire and Cable No. 8461 or equal.
4.7 Installing the Solar Storage Tank and Expansion
Tank
Refer to the installation manuals for the storage tank
and expansion tank.
Refer to Figure 16, Single Tank System Schematic
and Figure 17, 18 & 19 Double Tank System
Schematic on pages 28 - 31, for all items listed as
(No.##) through out this manual.
In plumbing the solar storage tank and expansion tank
make sure that all the components are accessible and
easy to reach. Provide for clear access to the storage
tank, pump, expansion tank, mixing valve, and other
key components. If a component in the potable water
side of the system may require future service or
maintenance make the connections with brass unions.
Use only brass nipples and unions and copper and
brass ttings in plumbing the solar storage tank and
expansion tank. The use of galvanized ttings or
nipples, di-electric unions, CPVC, PVC or other plastic
pipe is prohibited.
Hard copper connections to the city cold water
supply line and the home hot water feed lines
are recommended. The gaskets in standard water
heater ex hose connectors can become brittle and
compressed over time and begin leaking on the water
heater. If not detected in a timely manner even a small
drip or leak may cause serious damage to the tank’s
electrical components or, in extreme cases, may cause
the tank to leak from the outside in.
Tank plumbing is required to provide for the isolation
of the solar storage tank from the city cold water
supply line by means of an isolating ball valve (No.
19).
Line thermometers shall be installed in the collector
supply and return lines to allow for a simple diagnostic
check of proper system operation. On a sunny day the
hot water return line should be approximately 5 – 12°
warmer than the water in the collector supply line.
Compare the temperature readings in the two line
thermometers (No. 22).
In a single tank system install a third thermometer
(No. 22) directly after the mixing valve above the solar
storage tank. In a two tank system you may install the
third thermometer either directly above the hot outlet
on the solar storage tank or after the mixing valve on
the back-up water heater.
The circulation pump shall be the Grundfos model
UPS15-5BFC/LC, 115 volt or equivalent. The pump
shall be pre-wired with a 6’ line cord so that it can
be plugged directly into the 115 volt receptacle on
the side of the differential control. Isolation/Drain
valves (No. 6 & 7) must be installed on either side of
the circulating pump so that the pump can be isolated
from the collector loop. Repairs or routine system
maintenance can be completed without introducing air
into the system or draining the HTF.
The expansion tank shall have a minimum 60 PSIG
working pressure and have a total volume of not less
than 2.1 gallons. The expansion tank shall be Watts
Model ET-15 or equal (No. 11).
A high quality thermostatic mixing valve (No. 12) is
a required component in all OG-300 certied systems
and should be plumbed in line with brass union
connections for ease of future repair or replacement.
The specied mixing valve shall be the Heatguard
model HGBASE or equal and shall have an operating
range between 95°F and 140°F. The mixing valve shall
be set to 120°F.
The temperatures generated by your system will vary
throughout the year. In the Northern Hemisphere the
water temperature will be hottest in the spring and
summer months while cooler temperatures are to be
expect from November through March. On sunny
days system temperatures may range between 110ºF
to 180ºF depending upon the season and hot water
demand. The mixing valve described above blends the
hot and cold water supplies to deliver hot water to your
xtures at a safe, controlled temperature.
!
WARNING: SCALDING CAN OCCUR
WITHIN FIVE SECONDS WHEN WATER
TEMPERATURES APPROACH 140ºF. THE
MIXING VALVE SHOULD BE ADJUSTED BY
YOUR CONTRACTOR TO PROVIDE WATER
TO YOUR FIXTURES AT NO MORE THAN
120ºF.
17
Page 18
Section 4: Installation Requirements- Specific
Figure 18 TANK SENSOR
!
The 3/4" cold water supply line to the solar storage
tank must be insulated with minimum 7/8" X 1/2"
pipe insulation to a minimum distance of 5' behind the
storage tank, or to the wall if closer than 5'.
4.8 Tank Sensor Placement
Figure 18 details the proper placement of the solar
storage tank sensor. Make sure the sensor is secured to
the threaded stud on the storage tank with a 10-24
stainless steel nut.
Thoroughly weatherize the wire connections in
accordance with the roof sensor detail above. Replace
the berglass insulation batting and close the access
cover.
A properly licensed contractor must make the 230
volt electrical connection to the water heater or
solar storage tank and the electronic time switch
(Optional No. 33). If your solar contractor is not
allowed by law to make these connections consult
a licensed electrician
Never activate the circuit breaker controlling the
electrical heating element until the solar storage
tank is completely lled with water. This will
prevent “dry ring” of the heating element. The
electrical heating element will be destroyed
almost instantaneously if not completely
submerged in water when activated. Make sure
the water heater circuit breaker is off until the
solar storage tank is completely lled.
We recommend the use of a 115 volt differential
control with a factory installed six foot line cord. The
installation requires one 115 volt outlet to be installed
near the solar storage tank. Plug the control into the
outlet. The circulation pump line cord is plugged into
the receptacle on the side of the controller.
.
18
4.9 Charging the System
WARNING: Under no circumstances can any
fluid other than Dowfrost HD be used, alternate
fluids could be hazardous to your health.
Once the components are plumbed you are ready to
ll the solar storage tank with water and to charge
the collector loop with a mixture of heat transfer uid
(HTF) and distilled or deionized water. The use of
regular tap water as a mixing agent is prohibited.
Proceed as follows:
4.9.1 Begin by lling the solar tank with water. Do
this by opening the cold water isolation ball
valve to the solar tank (No. 19). When the tank
is lled, inspect all threaded ttings and solder
joints for leaks.
4.9.2 Fill and pressurize the solar collector loop
with water. Begin by connecting a washing
machine hose to the upper isolation/drain
valve (No. 7) and ll the collector loop with
water. The isolation ball valve (No. 7) remains
closed at this point. While the hose is still
connected to the upper isolation/drain valve
and the water is running, open the lower
isolation/drain valve (No. 6) and let the water
run out until it is free of impurities or debris
that might have entered the piping as the
components were plumbed. Run the water
long enough to eliminate any air bubbles that
may be trapped in the system.
Close the lower isolation/drain valve. The
collector loop now has been subjected to city
pressure and the pressure gauge (No. 10)
should read somewhere in the range of 50 - 75
PSI in most cases. Make a nal inspection
of the collector plumbing connections to
ensure that there are no leaks anywhere in the
collector loop piping.
4.9.3 After you have determined the integrity of the
entire piping system turn on the circulating
pump. Do this by setting the manual switch
within the controller to the “on” position. Run
the pump for a full ve minutes and carefully
check to ensure there is proper uid ow and
that all the air has been purged from the solar
collector glycol loop. An inexpensive
Page 19
ow meter is recommended as an optional
system component. A ow meter allows you
to monitor and adjust the ow rate through the
piping and also to visually inspect the HTF uid
quality.
Set the controller to the "off" position and
proceed to the next step.
4.9.4 Mix the Dowfrost HD propylene glycol and
distilled water mixture in accordance with
Table 4 and Table 5 in a large clean bucket.
You will need a second empty bucket as well.
The charging process also will require a low
ow diaphragm pump (Flojet or equal) to ll
and pressurize the collector loop.
Connect the discharge side of the pressure
pump to the upper isolation/drain valve (No.
7) Place the pump suction side hose in the
glycol solution. Close the isolation ball valve
(No. 7) and connect a second hose to the lower
isolation/drain valve (No. 6). Place the other
end of the hose in the empty bucket.
Table 4
Percent (volume) Glycol Concentration Required
Temperature FFor Freeze ProtectionFor Burst Protection
2018%12%
102920
03624
-104228
-204630
-305033
-405435
-505735
-606035
Table 5
Total Collector Loop Fluid Capacity In Gallons*
Open the upper drain valve and allow the
pressure from the expansion tank to push the
water in the glycol loop back to prime the
pressure pump. When the hose in the bucket
containing the glycol mixture stops bubbling
you may begin charging the collector loop with
glycol.
With both drain valves (No. 6 & 7) faucets
now open, run the Flojet pressure pump until
the pinkish glycol mixture begins owing into
the empty bucket. Quickly switch the hose
from the empty/return bucket to the bucket
containing the glycol mixture. Continue to
circulate the uid using the pressure pump until
the bubbling has stopped and the air has been
purged.
4.9.5 After charging the collector loop, shut the
lower drain valve (No. 6) and let the pressure
pump drive up the loop pressure to the
appropriate level (Generally in the range of
25 PSI). To more accurately calculate the
proper pressure measure the height of the solar
collector above the solar storage tank and
divide this number by 2.31. Then add 20 PSI to
this number. As a word of caution, the pressure
in the glycol loop should not exceed 45 PSI
when the system is operational on a good
sunny day. Contact your solar contractor if the
charged collector loop pressure exceeds this
threshold.
Your solar water heating system must be
charged and the uid quality maintained by an
experienced contractor. If the system is drained
during the winter, or you notice a signicant
drop in collector loop pressure, contact your
installation contractor immediately for service.
The glycol HTF provides the freeze protection
for your system and must be properly
maintained. An experienced contractor should
periodically check the HTF uid quality.
1 Collector System4 Gallons
2 Collector System5 Gallons
19
Page 20
Section 4: Installation Requirements- Specific
SOLAR COLLECTOR
(OPTIONAL)
4.9.6 Dowfrost HD HTF
To ensure maximum effectiveness for
corrosion protection, the glycol inhibitor
package is designed for a minimum 25-30
percent concentration of glycol in water.
Table 4 shows the concentrations of Dowfrost
HD required to provide freeze and burst
protection at various temperatures. Use the
mixture most appropriate for your climate. Do
not use a higher glycol to water concentration
than necessary, as this will adversely impact
the relative heat transfer efciency of the
solution.
Generally, for an extended margin of
protection, you should select a temperature
that is at least 5°F lower than the expected
lowest ambient temperature. These gures are
Water used to dilute the HTF must meet
Distilled or deionized water is required.
The HTF pH level must be maintained
examples only and should not be regarded as
specications. As conditions are not within
our control, we do not guarantee that freeze
damage may not occur at temperatures other
than shown.
certain minimum standards for purity.
Impurities in the dilution water can increase
metal corrosion, reduce the effectiveness
of corrosion inhibitors, increase inhibitor
depletion rate, and cause the formation
of scale and other deposits on the heat
exchanger's internal heat transfer surfaces.
between 8 and 10 to minimize corrosion and
glycol oxidation in the piping system.
Section 5: System Start - Up Procedures
Throughout the installation procedures outlined in
Section 4 ,emphasis has been placed on the correct
procedures for plumbing and wiring the components,
checking for plumbing leaks, pressurizing the
collector glycol loop, and eliminating any trapped air
that can impact uid quality and pump performance.
Having completed these tasks it is time to start up
your solar water heating system.
When the glycol loop has been fully charged and
the pressure is around 25 psi (check the pressure
gauge,(No. 10), set the differential controller to
the "Automatic" setting. This will activate your
circulating pump. The controller allows you to set the
"on" differential.
Adjust the valve settings in accordance with Section 6.
Solar Components
20
Page 21
Section 6: Three Modes of System Operation
6) THREE MODES OF SYSTEM OPERATION
Both single and double tank systems are designed to
accommodate three separate modes of operation. Your
solar water heating system can, (1) provide 100%
solar operation during good weather, or (2) serve as a
preheater to your electric or gas water heater adding
solar energy when and as available, or (3) completely
bypass the solar collector loop and solar storage tank
and run 100% on utility power during inclement
weather.
Single Tank Operating Instructions:
6.1 100% Solar Operation:
Turn off the heating element to your solar storage
tank. If a water heater time switch has been installed,
set the switch to the "off" position. If you have a
mechanical timer remove the trippers from the face of
the switch.
6.2 Solar Preheat
Leave the heating element to your solar storage tank
on and set the tank thermostat to the lowest acceptable
temperature setting. The heating element will come
on only when the tank temperature falls below the
thermostatic set point. If the solar heated water
entering the tank is warmer than the thermostat set
point, the heating element will not come on. If you
have a water heater timer, you may preset the timer to
turn the heating element on and off at specied times
throughout the day if desired.
Two Tank System Instructions:
6.4 100% Solar Operation
Follow the instructions for single tank systems above.
You also must change the position of the three way
ball valves above both the solar storage tank and the
back-up water heater (Nos. 24 and 25). Valve handle
No. 24 must be in the horizontal position. Valve
handle No. 25 must be in the vertical position. (See
Figure 19a, 100% Solar Operation)
6.5 Solar Preheat
Follow the instructions for the single tank system for
setting the heating element for automatic operation.
The three way valve above the solar storage tank (No.
24) must be in the vertical position. Each valve handle
(Nos. 24 and 25) must be placed in the horizontal
position. (See Figure 19b, Solar Preheat)
6.6 100% Utility Power
Follow the instructions for the single tank system
above. All three way ball valves above the heaters
(Nos. 24 and 25) must have the valve handles placed
in the horizontal position. (See Figures 19c, 100%
Utility Power and 19d, Valve Position Diagram)
6.3 100% Utility Power
Leave the heating element to your solar storage tank
on and close the isolation ball valves in the collector
loop (Nos. 6 and 8). In this mode of operation you
must turn off the circulation pump. To turn the pump
off open the controller and change the operational
setting from automatic to off. Failure to turn off the
pump can quickly damage the pump motor, shaft,
bearings or impeller.
21
Page 22
25
25
24
24
Figure 19a - 100% Solar Operation
25
Figure 19c - 100% Utility Power Operation
Hot Outlet
25
Figure 19b - Solar Preheat Operation
24
Cold Inlet
See Handle Above
24
22
Figure 19d - Valve Position Diagram - Two Tank System
Page 23
Section 7: Isolating the Major Components and System
Shut Down Procedures
7) ISOLATING THE MAJOR COMPONENTS
AND SYSTEM SHUT DOWN PROCEDURES
Your solar water heating system is designed so
that the key components can be easily isolated
for emergency repairs or routine maintenance. By
shutting a single valve you can isolate the entire
system from the pressurized cold water supply line
(No. 19). In the case of a storage tank or tting leak
immediately shut this valve and call your installation
contractor for service.
The collector loop can be isolated from the solar
storage tank by closing isolation ball valves (Nos.
6 and 8). If the pressure in this loop drops or you
nd a glycol leak shut these valves and contact your
installation contractor. Turn the circulating pump off
by setting the controller to the “off” position.
In two tank systems the solar storage tank can be
isolated from the back-up water heater.
Set all necessary isolation ball valves to the off
position to service the solar storage tank or the
back up water heater.
Section 8: Summer Vacation Recommendations and
Procedures
8) SUMMER VACATION
RECOMMENDATIONS AND PROCEDURES
Solar water heating systems can build up very
high temperatures when there is no daily draw on
the system. If a short summer vacation is planned
the best way to dissipate heat in the system is
to set the controller to the "on" position. The
circulating pump will run twenty-four hours a day
and cool off the water in the solar storage tank
at night. The collector radiates heat back to the
atmosphere at night, preventing the system from
stagnating at very high temperatures. This will
not harm the pump or add substantially to your
monthly utility bill. Remember to set the control
to the "Automatic" setting upon your return!
8.1 Turn the controller to the “off” position (No. 4).
8.2 Connect one end of a garden hose to the isolation/
drain valve (No. 6) and place the other end in a
ve gallon bucket. Open the valve and gravity will
drain the heat transfer uid into the bucket. Repeat
process using isolation / drain valve (No. 7) . A
licensed recycler, reclaimer or incinerator must
dispose of the Dowfrost HD.
DO NOT DUMP DOWFROST HD INTO A
STORM SEWER, ON THE GROUND OR INTO
ANY BODY OF WATER. BE CAREFUL. THE
HTF MAY BE EXTREMELY HOT!
During extended summer vacations (4 weeks
or more) it is advisable to either cover the solar
collectors with an opaque material or to manually
drain the collector loop HTF. The manufacturer
recommends that you cover the collectors if
practical.
If you choose to drain the HTF in the collector
loop follow these steps:
8.3 If the system is installed with an optional time
clock make sure the clock is not preset to go "ON"
during your absence. If you have a mechanical
time switch, remove the "on" tripper from the
clock face (No. 33).
When you return home contact your service
contractor to recharge the system with HTF. After
the system has been recharged, set the controller to
the “automatic” position.
23
Page 24
Section 9: Maintenance and Troubleshooting
9) MAINTENANCE AND TROUBLESHOOTING
The following simple procedures are intended to
optimize the performance of your solar water heating
system and also to extend the life of the primary
components.
9.1 Fluid Quality: It is extremely important to
monitor the quality of the Dowfrost HD HTF on
a periodic basis. The chemical composition of the
heat transfer uid may change over time. System
pH must be maintained between 8 and 10 to avoid
damage to the collector loop and absorber plate
piping.
9.2 The second most important component in your
system, at least from a longevity standpoint, is
often ignored and never seen. We are referring to
the sacricial "anode rod" installed in your solar
storage tank (No. 14). Typically constructed from
magnesium, anode rods are installed in "glass
lined" water heaters and storage tanks to inhibit
corrosion.
As the name implies, the "sacricial" anode rod
is consumed so that the tank lining is not. At a
certain point in the process, the anode rod is no
longer completely effective and the corrosive
processes begin to eat away at the tank's glass
lining. In time the solar storage tank, like any
other gas or electric water heater, will begin to
leak. The process is not reversible and the tank
must be replaced.
System temperatures and water quality affect
the rate at which the anode rod is consumed.
In general, the higher the average system
temperature the faster the rate of corrosion. By
changing the anode rod after the fth year of
system operation, and every three to ve years
thereafter, it is possible to extend the life of
the solar storage tank. Periodic replacement of
the anode rod in your solar storage tank can
signicantly extend the tank life.
9.3 The solar storage tank also should be ushed
annually to minimize sediment build-up on the
bottom of the tank. If you live in an area with
high mineral content in your water, ush the tank
on a semi-annual basis. Turn the heating element
to the solar tank off before ushing. Turn the
controller to the off position.
Open the ush valve on the bottom of the storage
tank (No. 18) and drain a sufcient volume
of water to eliminate the sediment. After the
procedure is complete make sure the tank is
completely full of water before turning on the
heating element. Turn the controller to the "on"
position.
9.4 If you live in a dusty climate it is a good idea to
wash off the dirt that settles on the collector glass
once a month. Clean glass allows the collector to
maintain a high level of thermal performance.
9.5 Check the exterior pipe insulation annually and
patch or repair any exposed surfaces or degraded
areas. Repaint as necessary.
9.6 In the unusual instance of collector glass
breakage, the glass should be replaced
immediately. This will reduce the likelihood
of water accumulating inside the collector
and deteriorating the insulation. Contact your
installation contractor.
9.7 If you detect a glycol or water leak, or the glycol
loop pressure drops unexpectedly, contact your
installation contractor immediately to diagnose
the problem and recharge the system.
9.8 If it’s been a sunny day and you don’t have
hot water, rst make sure that the controller is
set in the automatic position. If the controller
is properly set and the pump has not been
running, unplug the line cord from the controller
receptacle and plug the pump directly into a
nearby 115 volt outlet. If the pump does not run
it may need to be replaced. If the pump does run
24
Page 25
when plugged directly into the wall outlet, the
problem may be located in the controller or one
of the 10k ohm sensors. Contact your installation
contractor for service.
Never remove the protective access plate on the
exterior of the solar storaget tank or conventional
water heater without disconnecting the 230 volt
power supply at the circuit breaker.
9.9 If you have a full tank of hot water before bed and
the solar storage tank is cold in the morning, the
check valve (No. 20) may not be seating correctly
and should be cleaned or replaced. Also make
sure that the circulating pump is not running after
6:00 p.m. If the pump is running and the control
indictor light "Solar" #1 is on after 6:00 p.m.,
check both sensors to see that they calibrate to
10K ohm resistance at 77°F. If you nd a defective
sensor replace it immediately. Note that in a two
tank system nighttime heat loss will be harder to
detect, especially if you are operating in the solar
preheat mode. Check the line thermometers (No.
22) in the collector loop piping to detect night
thermosiphoning.
9.10 If the weather is poor and the auxillary heating
element will not re, the bright red reset button
on the thermostat may have to be depressed to
be reset. Single tank systems have one heating
element and thermostat. Double tank systems
with conventional electric water heaters have two
heating elements and thermostats.
After the circuit breaker has been turned off,
remove the access plate on the storage tank or
water heater and depress the red reset button
on the thermostat. If it clicks when depressed
the heating element should re immediately
when you reconnect the circuit breaker. If the
reset button does not click and you do not have
hot water after one hour, the heating element
of thermostat may be defective. Contact your
installation contractor for service.
In two tank systems the conventional electric
water heater will be wired for electrical back-up.
The solar tank will serve solely as a storage tank
and not be wired.
25
Page 26
Section 10: System Component Parts
10) SYSTEM COMPONENT PARTS
See Figures 16,17 18 and 19 for the location of
the specific components numbered below.
1) Solar Collector(s): Absorbs the sun’s heat
energy and transfers this heat to the HTF
circulating through the collector. (Provided)
2) Collector Sensor: Wired to the system controller.
Works in conjunction with the tank sensor to
automatically turn your circulating pump on and
off at preset temperature differentials. (Provided)
3) Tank Sensor: Wired to the system controller.
Works in conjunction with the collector sensor to
automatically turn your circulating pump on and
off at preset temperature differentials. (Provided)
4) Differential Thermostat: Known as the controller.
Automatically turns the circulating pump on and
off when there is sufficient heat to be gained
from the solar operation. The controller also
may be set to limit high temperature build
up in the solar storage tank. (Provided)
5) Circulating Pump: Circulates the HTF
through the collector loop. (Provided)
6) Isolation / Drain Valve: When closed in
conjunction with No. 7 will isolate the
circulation pump for repair or replacement.
Used to charge the collector loop with
glycol, purge air from the loop and drain
the heat exchange fluid. (Provided)
11) Expansion Tank: Pre-charged with air to
allow for the expansion and contraction of the
glycol HTF as it heats and cools. (Provided)
12) Mixing Valve: Automatically blends hot water
from the solar storage tank with incoming city
cold water to an acceptable set point. Note:
A mixing valve must be installed on every
solar water heating system. (Provided)
13) Temperature and Pressure Relief Valve:
Universally required by the plumbing code
on water heaters. Will automatically release
and dump water at either 150 PSI of pressure
or 210°F in temperature. (Provided)
14) Anode Rod: The “sacrificial” anode rod is
installed in your solar storage tank to prevent
corrosion to the tank lining by neutralizing
aggressive water action. Anode rods have a
finite life and require periodic replacement
depending on annual tank temperatures and
water quality. Determine a replacement schedule
with your installation contractor. (Provided)
15) Cold Water Dip Tube: Forces incoming
city cold water to the bottom of the solar
storage tank to prevent mixing with the warm
water at the top of the tank. (Provided)
16) Heat Exchanger: Transfers heat from the
solar collector loop to the potable water
in the solar storage tank. (Provided)
7) Isolation / Drain Valve: When closed in
conjunction with No. 6 it will isolate the
circulation pump for repair or replacement.
Used to charge the collector loop with
glycol, purge air from the loop and drain
the heat exchange fluid. (Provided)
8) Isolation Ball Valve: Used in conjunction with
component No. 7 to isolate the solar collector
loop from the solar storage tank. (Provided)
9) Pressure Relief Valve: Will release glycol
loop HTF at 75 PSI. If this valve opens
and the HTF fluid is expelled contact your
contractor immediately. This valve also can
be opened to drain the HTF from the charge
glycol loop for replacement. (Provided)
10) Pressure Gauge: Indicates pressure
in the collector loop. (Provided)
26
17) Heating Element & Tank Thermostat: The solar
storage tank is equipped with an auxiliary 4500
watt, 230 volt electrical heating element. The
thermostat controls the temperature setting of the
auxiliary heating element. (Provided)
18) Drain Valve: Used to drain the storage
tank and to flush sediment from the
tank on an annual basis. (Provided)
19) Isolation Ball Valve (Cold Water Supply Line):
When open allows potable water to fill the
solar storage tank or back-up water heater.
When closed isolates the solar storage tank
and back-up water heater from the pressurized
city cold water supply line. (Not Provided)
Page 27
20) Check Valve: This valve is installed to stop
or minimize convective evening heat loss in
the system. The heat in the solar storage tank
will rise through the collector loop piping in
the evening in the much cooler solar collector
and dissipate heat unless prevented from doing
so by a check valve. Check valves are also
referred to as one way valves. (Not Provided)
25) Three Way Ball Valve: Used in conjunction
with component No. 24 to establish the proper
mode of system operation. (Not Provided)
26) Isolation Ball Valve: Used in conjunction
with component No. 21 to completely
isolate the back-up water heater for repair or
replacement as necessary. (Not Provided)
21) Isolation Ball Valve (Hot Water): Used
in conjunction with component No. 19 to
completely isolate the solar storage tank for repair
or replacement as necessary. (Not Provided)
22) Tank / Line Thermometer(s): Will read the
temperature of the water and the collector supply
and return lines on sunny days. (Not Provided)
23) Optional Time Switch: Allows you
to automatically or manually turn the
auxiliary heating element in the solar
storage tank on and off. (Not Provided)
24) Three Way Ball Valve: Used in conjunction
with component No. 25 to establish the proper
mode of system operation. (Not Provided)
27) Temperature and Pressure Relief Valve:
See No. 13 above. (Provided)
28) Anode Rod: See No. 14 above. (Provided)
29) Cold Water Dip Tube: See No.
15 above. (Provided)
30) Drain Valve: See No. 18 above. (Provided)
31) Thermal Well: Not pictured. (Two
thermal wells provided)
27
Page 28
Section 10: System Component Parts
Note: When two collectors are
required, plumb in parallel.
1
2
Pipe Insulation
Collector Return
Hot Water Supply Outlet to
Fixtures
23 -
Optional
Time Switch
12
21
13
16
14
22
15
18
22
22
19
4
17
8
3
6
Feed
7
5
Cold Water Supply Inlet
20
10
11
9
Figure 16
28
SINGLE TANK SYSTEM SCHEMATIC
Page 29
Figure 17
DOUBLE TANK SYSTEM SCHEMATIC
with Gas or Electric Back up Tank
2
Pipe Insulation
Note: When two collectors are
required, plumb in parallel.
1
Collector Return
Roof Jacks
Hot Water Supply
Outlet to Fixtures
23 -
Optional
Time Switch
22
12
26
27
28
29
30
Gas or Electric Back up Tank
24
21
Cold
25
16
14
15
13
18
19
Cold Water Supply
Inlet
22
Feed
4
20
17
9
8
10
3
11
7
5
6
29
Page 30
Section 10: System Component Parts
Figure 18
DOUBLE TANK SYSTEM SCHEMATIC
with Heat Pump Back up Tank
Note: When two collectors are
required, plumb in parallel.
2
Pipe Insulation
1
Collector Return
Roof Jacks
Hot Water Supply
Outlet to Fixtures
23 -
Optional
Time Switch
22
26
27
30
Heat Pump Back-up Tank
12
24
25
21
16
14
15
18
13
19
3
Cold Water Supply
Inlet
Feed
4
17
7
5
6
22
20
9
10
11
30
Page 31
Note: When two collectors are
required, plumb in parallel.
2
Pipe Insulation
1
Collector Return
Roof Jacks
22
Hot Water Supply
Outlet to Fixtures
26
27
Tankless Back-up Tank
26
24
12
21
16
14
13
15
18
25
19
3
Cold Water Supply
Inlet
Feed
4
17
7
5
6
22
20
9
10
11
Figure 19
DOUBLE TANK SYSTEM SCHEMATIC
with Tankless Back up
31
Page 32
IF YOU NEED SERVICE
1. Should you have any questions about your new water heater, or if it requires
adjustment, repair, or routine maintenance, it is suggested that you first contact
your installer, plumbing contractor or previously agreed upon service agency. In
the event the firm has moved, or is unavailable, refer to the telephone directory,
commercial listings or local utility for qualified service assistance.
2. Should your problem not be solved to your complete satisfaction, you should
then contact the Manufacturer’s National Service Department at the following
address:
When contacting the manufacturer, the following information will be requested:
a. Model and serial number of the water heater as shown on the rating plate
attached to the jacket of the heater.
b. Address where the water heater is located and physical location.
c. Name and address of installer and any service agency who performed service
on the water heater.
d. Date of original installation and dates any service work was performed.
e. Details of the problems as you can best describe them.
f. List of people, with dates, who have been contacted regarding your problem.
32
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.